Project Status & Cost Allocation

The table below provides project status and cost allocation information for baseline, network and supplemental projects in PJM's Regional Transmission Expansion Plan (RTEP). Immediate-need reliability projects (exempted from proposal windows) are now consolidated with other project types and displayed on this page.

PJM’s Open Access Transmission Tariff, Schedule 12 contains the cost allocation factors and responsible parties, as filed with FERC:

Transmission Cost Planner (TC Planner)

Transmission Cost Planner (TC Planner) may be used to help PJM stakeholders better understand their current transmission costs and estimate their future transmission costs. TC Planner provides a wealth of pertinent information for PJM Regional Transmission Expansion Plan (RTEP) Baseline and Supplemental upgrades. TC Planner enables users to estimate annual revenue requirement and monthly transmission cost charges for the current month and a user selected future month within the 10-year horizon for a user selected responsible transmission zone.

An existing account in the PJM Account Manager will automatically grant users read-only access to the TC Planner. No additional access requests are required beyond having a valid Account Manager account. To request access or to set up a new PJM account, refer to the instructions (PDF).

Transmission Owner Non-binding indication of Intent to Fund Network Upgrades (PDF).

Production: Sign In | Register


Filters

Export: XLS XML
[Next]
Upgrade ID
Info
Voltage (kV)
Transmission Owner
State
Status
Info
Cost (millions)
Cost Allocation (%)
Info
Required Date
Info
Projected In-Service
Info
Actual In-Service
Info
PJM Board Approval
b0001
Seven 230 kV breakers at Shawville
230
PENELEC
PA
IS
1.3
5.9.2005
b0002
Increase emergency rating of Windy Edge - Lakespring - Texas 115 kV
115
BGE
MD
IS
3.77
BGE: 100.00
1.1.2006
5.9.2005
b0003
Install second East Windsor 500/230 kV transformer
500/230
JCPL
NJ
IS
9.5
5.9.2005
b0004
Increase rating of Collins - Cly Tap - Newberry - Round Top 115 kV
115
ME
PA
IS
0.33
ME: 100.00
4.1.2002
5.9.2005
b0005
Upgrade two 230 kV breakers at Whitpain #235 and #325
230
PECO
PA
IS
0.89
PECO: 100.00
1.1.2006
5.9.2005
b0006
Upgrade four 230 kV breakers at Whippany
230
JCPL
NJ
IS
0.1
5.9.2005
b0007
Addition of third Lewistown 230/115 kV transformer
230/115
PENELEC
PA
IS
2.75
5.9.2005
b0008
Install 2-12 MVAR capacitors at Mansfield 115 kV
115
PENELEC
PA
IS
0.9
PENELEC: 100.00
6.1.2003
5.30.2003
5.9.2005
b0009
Loop 230 kV into North Meshoppen install second 230/115 kV
230/115
PENELEC
PA
IS
2.07
PENELEC: 100.00
7.31.2003
10.27.2003
5.9.2005
b0010
Replace Northwest 230/115 kV transformers with 500 MVA transformers
230/115
BGE
MD
IS
9.06
BGE: 100.00
5.1.2003
5.1.2003
5.9.2005
b0011
Install a single 24 MVAR capacitors bank at Round Top 115 kV
115
ME
PA
IS
0.5
ME: 100.00
8.22.2003
8.29.2003
5.9.2005
b0012
Install distribution capacitors in South Akron and South Manheim area
230
PPL
PA
IS
0.4
PPL: 100.00
6.1.2004
6.30.2004
6.30.2004
5.9.2005
b0013
Construct Yorkanna - Otter Creek 230 kV and Otter Creek substation
230
PPL
PA
IS
22.3
PPL: 100.00
6.1.2004
5.20.2004
5.9.2005
b0015
Replace one Athenia 230 kV breaker #B-2228-5
230
PSEG
NJ
IS
0.35
PSEG: 100.00
6.1.2002
5.31.2002
5.31.2002
5.9.2005
b0016
Replace one Hudson 230 kV breaker #BS1-6
230
PSEG
NJ
IS
0.35
PSEG: 100.00
6.1.2002
6.30.2002
6.30.2002
5.9.2005
b0017
Replace four Roseland 230 kV breakers #BS3-4 #BS4-5 #BS5-6 #BS1-7 with 50KA
230
PSEG
NJ
IS
1.4
PSEG: 100.00
6.1.2002
5.1.2005
5.1.2005
5.9.2005
b0018
Provide additional cooling for Hudson 230/138 kV #2 transformer
230/138
PSEG
NJ
IS
0.1
PSEG: 100.00
6.1.2003
5.1.2005
1.10.2005
5.9.2005
b0022
Upgrade Plymouth Meeting 230 kV breakers #215
230
PECO
PA
IS
0.1
PECO: 100.00
6.1.2003
5.31.2003
5.9.2005
b0023
Construct four breaker ring bus and install SVC at Cardiff
AEC
NJ
IS
13.9
AEC: 100.00
6.1.2003
6.1.2003
4.24.2003
5.9.2005
b0024
Construct new 230 kV circuit between Cardiff and Oyster Creek
230
AEC
NJ
IS
58
AEC: 100.00
6.1.2005
7.1.2005
6.29.2005
5.9.2005
b0025
Convert the Bergen-Leonia 138kV circuit to 230kV circuit.
230
PSEG
NJ
IS
25
PSEG: 100.00
6.1.2008
6.1.2008
5.23.2008
9.22.2005
b0026
Install a breaker at Brunner Island 230 kV on the Yorkanna circuit
230
PPL
PA
IS
0.8
PPL: 100.00
6.1.2004
6.1.2004
11.9.2003
5.9.2005
b0027
Replace two Manor 230 kV Breakers WH-N WH-S
230
PPL
PA
IS
1
PPL: 100.00
6.1.2004
6.1.2004
5.23.2003
5.9.2005
b0030
Construct a new 230kV tower line to separate the existing Brandon Shores-Riverside DCTL to...
230
BGE
MD
IS
4
BGE: 100.00
6.1.2005
1.1.2007
11.6.2006
5.9.2005
b0031.1
Replace one (1) Conastone 230 kV breaker #6 (GCB) (2322/2302 line)
230
BGE
MD
IS
0.5
BGE: 100.00
5.14.2004
5.14.2004
5.9.2005
b0031.2
Replace one (1) Conastone 230 kV breaker #5(ATB) (500-2/2322 line)
230
BGE
MD
IS
0.22
BGE: 100.00
3.7.2003
3.7.2003
5.9.2005
b0032
Upgrade two Waugh Chapel 230 kV breakers
230
BGE
MD
IS
0
BGE: 100.00
1.1.2006
5.9.2005
b0034
Replace one Sewaren 230 kV breaker
230
PSEG
NJ
IS
0.35
PSEG: 100.00
10.31.2002
10.31.2002
5.9.2005
b0035
Change Calvert Cliffs unit 1 & 2 GSU tap settings
BGE
MD
IS
0
BGE: 100.00
5.1.2004
5.1.2004
5.9.2005
b0036
Install a second 230/138 kV transformer at Indian River
230/138
DPL
DE
IS
5.04
DPL: 100.00
6.1.2004
6.1.2004
5.9.2005
b0039.1
BGE Reactive Upgrades
BGE
MD
IS
9.12
BGE: 100.00
6.1.2007
6.1.2004
6.1.2004
5.9.2005
b0039.2
PEPCO Reactive Upgrades
PEPCO
MD
IS
2.64
PEPCO: 100.00
6.1.2007
6.1.2005
5.31.2005
5.9.2005
b0039.5
Install Waugh Chapel 230kV 360MVAR capacitor bank
230
BGE
MD
IS
1.7
BGE: 100.00
6.1.2006
6.1.2006
6.29.2006
11.1.2006
b0040
Replace Doubs 500/230 kv transformer #1
500/230
APS
MD
IS
4.1
APS: 100.00
6.1.2007
12.31.2005
12.31.2005
5.9.2005
b0042
Upgrade Midd Jct - Zions View 115 kV
115
ME
PA
IS
0.95
ME: 100.00
6.1.2007
6.1.2005
6.1.2005
5.9.2005
b0043.1
Add capacitors in north Philadelphia - Buckingham
PECO
PA
IS
1.38
PECO: 100.00
12.1.2007
6.1.2003
5.9.2005
b0043.2
Add capacitors in north Philadelphia - Woodburne
PECO
PA
IS
1.38
PECO: 100.00
12.1.2007
5.14.2004
5.9.2005
b0043.3
Add capacitors in north Philadelphia - North Wales
PECO
PA
IS
1.38
PECO: 100.00
12.1.2007
6.1.2005
5.31.2005
5.9.2005
b0044
Replace Richmond 69KV breaker #20 with 40,000 A
69
PECO
PA
IS
0.1
PECO: 100.00
2.1.2004
2.1.2004
5.9.2005
b0045
Jumper out Richmond 69KV breaker #40
69
PECO
PA
IS
0
PECO: 100.00
12.12.2003
12.12.2003
5.9.2005
b0047
Replace Richmond 69KV breaker #120 with 40,000 A
69
PECO
PA
IS
0.1
PECO: 100.00
11.18.2003
11.18.2003
5.9.2005
b0049
Modify 21 structures for Canaan Valley-Williams 138KV circuit
138
APS
WV
IS
0.4
APS: 100.00
10.1.2003
12.31.2003
11.3.2003
5.9.2005
b0050.1
Add 5.1 MVAR cap at W. Waynesboro 34.5KV
34
APS
PA
IS
0.05
APS: 100.00
10.1.2003
5.1.2003
8.1.2003
5.9.2005
b0050.2
5.1 MVAR cap at Lime Kiln 34.5 KV
34
APS
MD
IS
0.05
APS: 100.00
10.1.2003
5.1.2003
8.1.2003
5.9.2005
b0050.3
2.1 MVAR cap at Chamber's No. 5
APS
PA
IS
0.05
APS: 100.00
10.1.2003
6.30.2003
5.23.2003
5.9.2005
b0051
Add 10.2 MVAR cap at Aqueduct 34.5KV
34
APS
MD
IS
0.15
APS: 100.00
10.1.2003
5.1.2003
8.26.2003
5.9.2005
b0052.1
Add a second 10.2 MVAR at Montgomery 34.5 KV for a total of 20.4 MVAR (eff.)
34
APS
MD
IS
0.34
APS: 100.00
6.1.2005
6.15.2006
6.15.2006
5.9.2005
b0052.2
5.1 MVAR cap at Boonsboro 34.5 KV
34
APS
MD
IS
0.34
APS: 100.00
6.1.2004
9.30.2004
9.16.2004
5.9.2005
b0052.3
Add a second 10.2 MVAR cap at Mt. Airy 34.5 KV for a total of 20.4 MVAR (eff.)
34
APS
MD
IS
0.34
APS: 100.00
6.1.2004
9.30.2004
10.27.2004
5.9.2005
b0052.4
Increase the 8.2 MVAR capacitor to 10.2 MVAR (eff.) at Antietam 34.5 KV
34
APS
MD
IS
0.34
APS: 100.00
6.1.2004
10.15.2004
11.1.2004
5.9.2005
b0052.5
Install 10.2 MVAR (effective) 34.5 kV Capacitor at McCain Substation
34
APS
MD
IS
0.19
APS: 100.00
6.1.2006
1.15.2005
2.2.2005
5.9.2005
b0053
Add a second 10.2 MVAR capacitor for a total of 20.4 MVAR (eff.) at Davis Mill 34.5 KV
34
APS
MD
IS
0.3
APS: 100.00
6.1.2006
9.1.2005
8.3.2005
5.9.2005
b0054
Add 22 MVAR of capacitance at Ringgold 138 KV for a total of 66 MVAR (eff.)
138
APS
MD
IS
0.17
APS: 100.00
6.1.2005
6.30.2005
6.30.2005
5.9.2005
b0055
Add 44 MVAR cap at Carroll 138 KV
138
APS
MD
IS
0.4
APS: 100.00
6.1.2005
6.30.2006
5.23.2006
5.9.2005
b0057
Install two breakers at Lake Nelson 230kV
230
PSEG
NJ
IS
5.2
PSEG: 100.00
6.1.2005
5.26.2006
6.9.2006
5.9.2005
b0058
Replace two Athenia 230/138KV transformers
230/138
PSEG
NJ
IS
6
PSEG: 100.00
6.1.2007
6.1.2005
6.1.2005
5.9.2005
b0059
Add a new Roxborough 69kV breaker (#215)
69
PECO
PA
IS
0.25
PECO: 100.00
1.1.2003
1.1.2003
5.9.2005
b0060
Replace Deans 230KV circuit breaker #2-10
230
PSEG
NJ
IS
0.48
PSEG: 100.00
4.30.2006
4.7.2006
4.7.2006
5.9.2005
b0061
Replace Deans 230KV circuit breaker #2-8
230
PSEG
NJ
IS
0.48
PSEG: 100.00
6.1.2006
3.24.2006
3.24.2006
5.9.2005
b0062
Replace Deans 230KV circuit breaker #5-6
230
PSEG
NJ
IS
0.48
PSEG: 100.00
6.1.2006
4.21.2006
4.21.2006
5.9.2005
b0063
Replace Deans 230KV circuit breaker #2-6
230
PSEG
NJ
IS
0.48
PSEG: 100.00
4.30.2006
3.10.2006
3.10.2006
5.9.2005
b0064
Replace Linden 230 KV breaker#1-5
230
PSEG
NJ
IS
0.48
PSEG: 100.00
4.30.2006
5.15.2006
5.11.2006
5.9.2005
b0065
Replace Linden 230 kV circuit breaker #1-3
230
PSEG
NJ
IS
0.48
PSEG: 100.00
4.30.2006
4.30.2006
4.26.2006
5.9.2005
b0066
Replace Linden 230KV circuit breaker #2-3
230
PSEG
NJ
IS
0.48
PSEG: 100.00
4.30.2006
6.1.2007
2.2.2007
5.9.2005
b0067
Replace a section of Jackson-Baker Tap bus
115
ME
PA
IS
0.02
ME: 100.00
6.1.2008
12.31.2004
12.31.2004
5.9.2005
b0069
Replace disconnect switch at Glory/Dixonville
230
PENELEC
PA
IS
0.1
PENELEC: 100.00
6.1.2008
5.31.2007
4.27.2007
5.9.2005
b0071
Loop the W-1323 line into the Bayway 138 kV bus
138
PSEG
NJ
IS
4.5
PSEG: 100.00
6.1.2008
6.1.2008
7.14.2008
5.9.2005
b0073
Reconductor 605 ft of the Kearny-Turnpike "D" 138 kV circuit
138
PSEG
NJ
IS
0.2
PSEG: 100.00
6.1.2008
6.1.2008
3.5.2013
5.9.2005
b0074
S. Akron-Berks, Double Circuit, Rebuild 12 miles of S Akron-Berks to double circuit, looping Met...
PPL
PA
IS
48.27
PPL: 100.00
6.1.2008
6.1.2008
5.2.2008
5.9.2005
b0076
Add Werner 230/115 KV transformer
230/115
JCPL
NJ
IS
0
JCPL: 100.00
6.1.2004
5.19.2004
5.19.2004
5.9.2005
b0077
Replace wavetrap on Morris Park - Gilbert 230kV
230
JCPL
NJ
IS
0
JCPL: 100.00
6.1.2008
6.1.2004
5.27.2004
5.9.2005
b0078
Replace disconnect switch on Morris Park - Gilbert 230kV
230
JCPL
NJ
IS
0
JCPL: 100.00
6.1.2008
6.1.2004
5.27.2004
5.9.2005
b0079
Install SPS at Branchburg
PSEG
NJ
IS
0
PSEG: 100.00
6.1.2008
6.1.2004
6.1.2004
5.9.2005
b0080
Relay upgrade on Dresden 345/138 kV “Blue”
345/138
ComEd
IL
IS
0.1
ComEd: 100.00
6.1.2004
4.30.2004
4.16.2004
5.9.2005
b0081
Reconductor Des Plaines - Howard 138 kV
138
ComEd
IL
IS
1.4
ComEd: 100.00
6.1.2005
6.1.2005
5.14.2005
5.9.2005
b0085
Install third Branchburg 500/230 kV transformer
500/230
PSEG
NJ
IS
15
PSEG: 100.00
6.30.2005
6.30.2005
4.24.2005
5.9.2005
b0086
Capacitor Additions at Cedar
AEC
NJ
IS
0.07
AEC: 100.00
6.30.2004
6.30.2004
5.9.2005
b0087
Capacitor Additions at Motts Farm
AEC
NJ
IS
0.76
AEC: 100.00
6.30.2004
6.29.2004
5.9.2005
b0088
Landis - Minotola 138kV upgrade
138
AEC
NJ
IS
0.08
AEC: 100.00
6.30.2004
4.21.2004
5.9.2005
b0089
Load reconfiguration at Motts Farm
AEC
NJ
IS
0
AEC: 100.00
6.30.2004
6.30.2004
5.9.2005
b0090
Add 150 MVAR capacitor at Camden 230 kV
230
PSEG
NJ
IS
1.25
PSEG: 100.00
6.1.2005
7.14.2005
7.14.2005
5.9.2005
b0091
Replace Wavetrap on Doubs - Montgomery Tap 230 kV
230
APS
WV
IS
0.05
APS: 100.00
6.1.2008
11.1.2005
5.6.2005
5.9.2005
b0098
Install Silver Lake - Pleasant Valley 345 kV and Pleasant Valley 345/138 kV
345/138
ComEd
IL
IS
13.5
ComEd: 100.00
6.1.2005
5.27.2005
5.25.2005
5.9.2005
b0099
Install third Nelson 345/138 kV
345/138
ComEd
IL
IS
5
ComEd: 100.00
6.1.2008
6.1.2008
3.29.2008
5.9.2005
b0101
Install auto-close scheme at Waukegan
ComEd
IL
IS
0.05
ComEd: 100.00
6.1.2005
6.1.2005
5.25.2005
5.9.2005
b0104
Install a 345/138 kV transformer at East Frankfort and reconductor East Frankfort - Mokena Tap 138...
345/138
ComEd
IL
IS
15
ComEd: 100.00
6.1.2008
6.1.2006
5.26.2006
5.9.2005
b0105
Install new 138 kV line 11107 from Electric Junction to Warrenville
138
ComEd
IL
IS
1.04
ComEd: 100.00
6.1.2008
6.1.2006
5.27.2006
5.9.2005
b0108
Replace Deans 230 kV breaker #7-8
230
PSEG
NJ
IS
0.48
PSEG: 100.00
4.30.2006
5.5.2006
5.5.2006
5.9.2005
b0109
Install SPS at Wylie Ridge
APS
WV
IS
0
APS: 100.00
9.1.2004
3.31.2005
3.31.2005
5.9.2005
b0110
Purchase spare 500/230 kV transformer for Doubs
500/230
APS
MD
IS
0
APS: 100.00
6.1.2005
10.30.2006
10.22.2005
5.9.2005
b0113
Roberts Station / Bixby, LSII 138kV/Bixby, Install new 345/138 kV transformer at Roberts Station;...
345/138
AEP
OH
IS
14.2
AEP: 100.00
6.1.2009
12.1.2007
11.8.2007
5.9.2005
b0114
Install new 345/138 kV transformer at existing Don Marquis Station and reconfigure 138 kV system in...
345/138
AEP
OH
IS
35.23
AEP: 100.00
6.1.2009
12.31.2010
11.14.2010
5.9.2005
b0115
Install 5% series reactor at Hyatt Station and install 29 MVAR capacitor at Trent 138 kV Station
138
AEP
OH
IS
0.9
AEP: 100.00
6.1.2009
6.30.2005
7.12.2005
5.9.2005
b0116
Replace breakers K, K2, and M at Cook 345 kV Station
345
AEP
MI
IS
4.1
AEP: 100.00
6.1.2005
6.30.2005
6.24.2005
5.9.2005
b0117
Replace breakers E, E1, E2, F, F1 and F2 at Dumont 345 kV Station
345
AEP
IN
IS
3.3
AEP: 100.00
6.1.2005
6.10.2005
5.20.2005
5.9.2005
b0118
Replacement of AA and AA1 breakers at Tidd 345 KV substation
345
AEP
OH
IS
1.3
AEP: 100.00
6.1.2005
11.11.2004
5.9.2005
b0119
Replace breakers FF1 and FF2 at Tidd 345 kV Station
345
Buckeye Power
OH
IS
1.3
6.1.2005
6.2.2006
6.18.2006
5.9.2005
b0121
Add 150 MVAR capacitor at Aldene 230 kV
230
PSEG
NJ
IS
1.25
PSEG: 100.00
6.1.2005
6.8.2005
7.7.2005
5.9.2005
b0122
Bypass the Essex 138 kV series reactors
138
PSEG
NJ
IS
0.5
PSEG: 100.00
6.1.2005
6.1.2005
5.14.2005
5.9.2005
b0123
Add 180 MVAR of distributed capacitors in JCP&L. 65 MVAR are being added in northern JCP&L and 115...
JCPL
NJ
IS
2.7
JCPL: 100.00
6.1.2005
12.31.2005
8.1.2005
5.9.2005
[Next]