AG1-552 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:47
Carolina 13.2 kV
12.2 MW Capacity / 18.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-552 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Northhampton County, North Carolina. The installed facilities will have a total capability of 18.0 MW with 12.2 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-552 |
| Project Name | Carolina 13.2 kV |
| Developer Name | Ray Solar, LLC |
| State | North Carolina |
| County | Northhampton |
| Transmission Owner | Dominion |
| MFO | 18.0 MW |
| MWE | 18.0 MW |
| MWC | 12.2 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-552 will interconnect with the Dominion transmission system at the Carolina 115 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 18.0 MW (Capacity 12.2 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 2201
CONTINGENCY 'DVP_P1-2: LN 2201' OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1 /*6DRY BREAD 230.0 - 6CLUBHSE 230.0 END |
Single | AC | 203.4 % | 204.44 % | 182.64 | B | 373.38 | 1.9 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 254
CONTINGENCY 'DVP_P1-2: LN 254' OPEN BRANCH FROM BUS 313725 TO BUS 314583 CKT 1 /*6DRY BREAD 230.0 - 6LAKEVEW 230.0 END |
Single | AC | 191.6 % | 192.62 % | 182.64 | B | 351.8 | 1.9 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P1-2: LN 140
CONTINGENCY 'DVP_P1-2: LN 140' OPEN BRANCH FROM BUS 313720 TO BUS 314526 CKT 1 /*3NEWSOMS 115.0 - 3HANDSOM 115.0 OPEN BRANCH FROM BUS 314526 TO BUS 314534 CKT 1 /*3HANDSOM 115.0 - 3S HAMPT 115.0 OPEN BUS 314526 /*3HANDSOM 115.0 END |
Single | AC | 124.81 % | 126.87 % | 239.89 | B | 304.35 | 5.13 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P1-2: LN 93
CONTINGENCY 'DVP_P1-2: LN 93' OPEN BRANCH FROM BUS 314524 TO BUS 314539 CKT 1 /*3FRNKLN 115.0 - 3UNCAMP 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314541 CKT 1 /*3FRNKLN 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 314541 CKT 1 /*3S HAMPT 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 315115 CKT 1 /*3S HAMPT 115.0 - 1S HAMPT1 13.8 OPEN BRANCH FROM BUS 314541 TO BUS 314826 CKT 1 /*3WATKINS 115.0 - 3WATKI_1 115.0 OPEN BRANCH FROM BUS 314541 TO BUS 314827 CKT 1 /*3WATKINS 115.0 - 3WATKI_2 115.0 OPEN BUS 314524 /*3FRNKLN 115.0 OPEN BUS 314541 /*3WATKINS 115.0 OPEN BUS 314826 /*3WATKI_1 115.0 OPEN BUS 314827 /*3WATKI_2 115.0 OPEN BUS 315115 /*1S HAMPT1 13.8 END |
Single | AC | 124.5 % | 126.56 % | 239.89 | B | 303.6 | 5.13 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
Base Case | Single | AC | 102.25 % | 104.31 % | 226.54 | A | 236.3 | 4.8 | |
| DVP |
3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer
314568 to 314569 ckt 2 |
DVP_P4-2: 201262
CONTINGENCY 'DVP_P4-2: 201262' OPEN BRANCH FROM BUS 314266 TO BUS 314569 CKT 1 /*6NORTHAMPTON 230.0 - 6EARLEYS 230.0 OPEN BRANCH FROM BUS 314266 TO BUS 314599 CKT 1 /*6NORTHAMPTON 230.0 - 6ROA VAL 230.0 OPEN BRANCH FROM BUS 314568 TO BUS 314569 CKT 1 /*3EARLEYS 115.0 - 6EARLEYS 230.0 OPEN BUS 314266 /*6NORTHAMPTON 230.0 END |
Breaker | AC | 179.91 % | 180.88 % | 208.0 | C | 376.24 | 2.38 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 176.55 % | 177.7 % | 199.0 | B | 353.62 | 2.7 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 176.55 % | 177.69 % | 199.0 | B | 353.61 | 2.7 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 102952
CONTINGENCY 'DVP_P4-2: 102952' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314572 CKT 1 /*3METCATP 115.0 - 3EMPORIA 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314588 CKT 1 /*3METCATP 115.0 - 3METCALF 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 314863 CKT 1 /*3EMPORIA 115.0 - 3EMPOR_1 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 316085 CKT 1 /*3EMPORIA 115.0 - 3IVORY LANE 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314570 /*3METCATP 115.0 OPEN BUS 314572 /*3EMPORIA 115.0 OPEN BUS 314588 /*3METCALF 115.0 OPEN BUS 314863 /*3EMPOR_1 115.0 END |
Breaker | AC | 159.44 % | 162.24 % | 288.6 | C | 468.22 | 8.12 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 14852
CONTINGENCY 'DVP_P4-2: 14852' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 END |
Breaker | AC | 148.22 % | 151.02 % | 288.6 | C | 435.85 | 8.12 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 7152
CONTINGENCY 'DVP_P4-2: 7152' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314516 TO BUS 314676 CKT 1 /*3BRUNWICK_1 115.0 - 3BRUNWICK 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314565 TO BUS 314693 CKT 1 /*3CLUBHSE71 115.0 - 3FRMAN D 115.0 OPEN BRANCH FROM BUS 314565 TO BUS 314850 CKT 1 /*3CLUBHSE71 115.0 - 3CLUBHSE71_1 115.0 OPEN BRANCH FROM BUS 314675 TO BUS 314676 CKT 1 /*3BRODNAX 115.0 - 3BRUNWICK 115.0 OPEN BRANCH FROM BUS 314676 TO BUS 314704 CKT 1 /*3BRUNWICK 115.0 - 3LAWRENC 115.0 OPEN BRANCH FROM BUS 314693 TO BUS 314704 CKT 1 /*3FRMAN D 115.0 - 3LAWRENC 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314516 /*3BRUNWICK_1 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314565 /*3CLUBHSE71 115.0 OPEN BUS 314676 /*3BRUNWICK 115.0 OPEN BUS 314693 /*3FRMAN D 115.0 OPEN BUS 314704 /*3LAWRENC 115.0 OPEN BUS 314782 /*2BRUNWICK 69.0 OPEN BUS 314785 /*2DANLTWN 69.0 OPEN BUS 314786 /*2GASBURG 69.0 OPEN BUS 314787 /*2BRUNWICK2 69.0 OPEN BUS 314850 /*3CLUBHSE71_1 115.0 OPEN BUS 314872 /*2BRUNSWICKDP 69.0 END |
Breaker | AC | 146.07 % | 148.86 % | 288.6 | C | 429.61 | 8.12 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 93T140
CONTINGENCY 'DVP_P4-2: 93T140' OPEN BRANCH FROM BUS 313720 TO BUS 314526 CKT 1 /*3NEWSOMS 115.0 - 3HANDSOM 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314539 CKT 1 /*3FRNKLN 115.0 - 3UNCAMP 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314541 CKT 1 /*3FRNKLN 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314526 TO BUS 314534 CKT 1 /*3HANDSOM 115.0 - 3S HAMPT 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 314541 CKT 1 /*3S HAMPT 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 315115 CKT 1 /*3S HAMPT 115.0 - 1S HAMPT1 13.8 OPEN BRANCH FROM BUS 314541 TO BUS 314826 CKT 1 /*3WATKINS 115.0 - 3WATKI_1 115.0 OPEN BRANCH FROM BUS 314541 TO BUS 314827 CKT 1 /*3WATKINS 115.0 - 3WATKI_2 115.0 OPEN BUS 314524 /*3FRNKLN 115.0 OPEN BUS 314526 /*3HANDSOM 115.0 OPEN BUS 314541 /*3WATKINS 115.0 OPEN BUS 314826 /*3WATKI_1 115.0 OPEN BUS 314827 /*3WATKI_2 115.0 OPEN BUS 315115 /*1S HAMPT1 13.8 END |
Breaker | AC | 146.14 % | 148.47 % | 288.6 | C | 428.48 | 7.32 | |
| DVP |
3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line
314623 to 313854 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 125.39 % | 128.81 % | 202.0 | C | 260.19 | 7.12 | |
| DVP |
3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line
314623 to 313854 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 125.39 % | 128.81 % | 202.0 | C | 260.19 | 7.12 | |
| DVP |
3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line
313854 to 314554 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 125.38 % | 128.8 % | 202.0 | C | 260.18 | 7.12 | |
| DVP |
3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line
313854 to 314554 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 125.38 % | 128.8 % | 202.0 | C | 260.18 | 7.12 | |
| DVP |
3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line
314623 to 313854 ckt 1 |
DVP_P4-2: 2202
CONTINGENCY 'DVP_P4-2: 2202' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Breaker | AC | 124.21 % | 127.63 % | 202.0 | C | 257.81 | 7.12 | |
| DVP |
3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line
313854 to 314554 ckt 1 |
DVP_P4-2: 2202
CONTINGENCY 'DVP_P4-2: 2202' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Breaker | AC | 124.21 % | 127.63 % | 202.0 | C | 257.8 | 7.12 | |
| DVP |
3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line
314673 to 314702 ckt 1 |
DVP_P4-2: 2202
CONTINGENCY 'DVP_P4-2: 2202' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Breaker | AC | 112.41 % | 116.94 % | 170.0 | C | 198.8 | 7.82 | |
| DVP |
3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line
314673 to 314702 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 111.65 % | 116.19 % | 170.0 | C | 197.52 | 7.82 | |
| DVP |
3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line
314673 to 314702 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 111.65 % | 116.19 % | 170.0 | C | 197.52 | 7.82 | |
| CPLE/DVP |
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
314554 to 304223 ckt 1 |
DVP_P7-1: LN 2058-2181
CONTINGENCY 'DVP_P7-1: LN 2058-2181' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1 /*6PA-RMOUNT#4 230.0 - 6NASH 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1 /*6HATHAWAY 230.0 - 6NASH 230.0 OPEN BUS 304226 /*6PA-RMOUNT#4 230.0 OPEN BUS 314591 /*6NASH 230.0 END |
Tower | AC | 297.76 % | 298.95 % | 164.0 | B | 490.28 | 1.98 | |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961791 | AG1-021 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961891 | AG1-030 C | 80/20 | 7.72 MW | 7.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963171 | AG1-166 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963181 | AG1-167 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963191 | AG1-168 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963201 | AG1-169 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963211 | AG1-170 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963301 | AG1-179 C | 80/20 | 12.96 MW | 12.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963311 | AG1-180 | 80/20 | 6.32 MW | 6.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963321 | AG1-181 C O1 | 80/20 | 10.66 MW | 10.66 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963361 | AG1-185 O1 | 80/20 | 5.16 MW | 5.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964111 | AG1-272 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964121 | AG1-273 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964131 | AG1-274 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964241 | AG1-285 C O1 | 80/20 | 9.13 MW | 9.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964791 | AG1-342 C | 80/20 | 1.94 MW | 1.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964801 | AG1-343 C | 80/20 | 2.87 MW | 2.87 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 966811 | AG1-552 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965191 | AG1-384 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965291 | AG1-394 C | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965591 | AG1-427 C | 80/20 | 8.62 MW | 8.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965601 | AG1-428 C O2 | 80/20 | 10.82 MW | 10.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965721 | AG1-440 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965731 | AG1-441 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965771 | AG1-445 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965781 | AG1-446 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 966621 | AG1-532 C | 80/20 | 4.38 MW | 4.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313506 | AB1-173 C OP | 80/20 | 14.92 MW | 14.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313719 | 3CHESTNUT | 80/20 | 0.56 MW | 0.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314572 | 3EMPORIA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314704 | 3LAWRENC | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315126 | 1ROARAP2 | 80/20 | 1.29 MW | 1.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315128 | 1ROARAP4 | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315136 | 1ROSEMG1 | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315139 | 1GASTONA | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315159 | 1KERR 2 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315160 | 1KERR 3 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315161 | 1KERR 4 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315162 | 1KERR 5 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926070 | AC1-086 C | 80/20 | 10.02 MW | 10.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926201 | AC1-098 C | 80/20 | 3.11 MW | 3.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926211 | AC1-099 C | 80/20 | 1.04 MW | 1.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 927145 | AC1-208 C | 80/20 | 5.26 MW | 5.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 934331 | AD1-057 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 936265 | AD2-033 C | 80/20 | 8.32 MW | 8.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 944141 | AF1-082 | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 958801 | AF2-171 C | 80/20 | 7.02 MW | 7.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 959311 | AF2-222 C | 80/20 | 9.8 MW | 9.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 960081 | AF2-299 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315163 | 1KERR 6 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315164 | 1KERR 7 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315266 | 1PLYWOOD A | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315606 | 3AA2-053SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316020 | AB2-059 C OP | 80/20 | 0.59 MW | 0.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316118 | AC1-105 C | 80/20 | 2.02 MW | 2.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316129 | AC1-054 C | 80/20 | 5.72 MW | 5.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 922922 | AB1-081 C OP | 80/20 | 0.5 MW | 0.5 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 923262 | AB1-132 C OP | 80/20 | 6.8 MW | 6.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 923991 | AB2-040 C O1 | 80/20 | 16.25 MW | 16.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 925591 | AC1-034 C | 80/20 | 2.25 MW | 2.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 932631 | AC2-084 C | 80/20 | 4.43 MW | 4.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 938371 | AE1-056 C | 80/20 | 2.68 MW | 2.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 939181 | AE1-148 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 940571 | AE2-044 C | 80/20 | 1.47 MW | 1.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 940661 | AE2-053 O1 | 80/20 | 2.29 MW | 2.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 946281 | AF1-292 C | 80/20 | 4.81 MW | 4.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 946301 | AF1-294 C | 80/20 | 1.91 MW | 1.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 957521 | AF2-046 C | 80/20 | 7.43 MW | 7.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 958211 | AF2-115 C | 80/20 | 1.16 MW | 1.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315115 | 1S HAMPT1 | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315141 | 1GASTONB | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315608 | 3AA2-088SOLA | 80/20 | 0.51 MW | 0.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316087 | AB2-174 C | 80/20 | 2.96 MW | 2.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316096 | AB2-100 C1 | 80/20 | 0.46 MW | 0.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316098 | AB2-100 C2 | 80/20 | 0.46 MW | 0.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962561 | AG1-105 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961681 | AG1-008 C | 80/20 | 7.45 MW | 7.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962571 | AG1-106 C | 80/20 | 2.79 MW | 2.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.91 MW | 13.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.92 MW | 4.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.96 MW | 4.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.69 MW | 0.69 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961791 | AG1-021 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961891 | AG1-030 C | 80/20 | 7.73 MW | 7.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963171 | AG1-166 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963181 | AG1-167 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963191 | AG1-168 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963201 | AG1-169 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963211 | AG1-170 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963301 | AG1-179 C | 80/20 | 12.97 MW | 12.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963311 | AG1-180 | 80/20 | 6.32 MW | 6.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963321 | AG1-181 C O1 | 80/20 | 10.68 MW | 10.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963361 | AG1-185 O1 | 80/20 | 5.17 MW | 5.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964111 | AG1-272 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964121 | AG1-273 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964131 | AG1-274 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964241 | AG1-285 C O1 | 80/20 | 9.14 MW | 9.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964791 | AG1-342 C | 80/20 | 1.95 MW | 1.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964801 | AG1-343 C | 80/20 | 2.88 MW | 2.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 966811 | AG1-552 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965191 | AG1-384 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965291 | AG1-394 C | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965591 | AG1-427 C | 80/20 | 8.62 MW | 8.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965601 | AG1-428 C O2 | 80/20 | 10.83 MW | 10.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965721 | AG1-440 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965731 | AG1-441 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965771 | AG1-445 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965781 | AG1-446 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 966621 | AG1-532 C | 80/20 | 4.38 MW | 4.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313506 | AB1-173 C OP | 80/20 | 14.93 MW | 14.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313719 | 3CHESTNUT | 80/20 | 0.56 MW | 0.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314572 | 3EMPORIA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314704 | 3LAWRENC | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315126 | 1ROARAP2 | 80/20 | 1.29 MW | 1.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315128 | 1ROARAP4 | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315136 | 1ROSEMG1 | 80/20 | 1.01 MW | 1.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315139 | 1GASTONA | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315159 | 1KERR 2 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315160 | 1KERR 3 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315161 | 1KERR 4 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315162 | 1KERR 5 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926070 | AC1-086 C | 80/20 | 10.03 MW | 10.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926201 | AC1-098 C | 80/20 | 3.11 MW | 3.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926211 | AC1-099 C | 80/20 | 1.04 MW | 1.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 927145 | AC1-208 C | 80/20 | 5.27 MW | 5.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 934331 | AD1-057 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 936265 | AD2-033 C | 80/20 | 8.33 MW | 8.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 944141 | AF1-082 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 958801 | AF2-171 C | 80/20 | 7.03 MW | 7.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 959311 | AF2-222 C | 80/20 | 9.81 MW | 9.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 960081 | AF2-299 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315163 | 1KERR 6 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315164 | 1KERR 7 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315266 | 1PLYWOOD A | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315606 | 3AA2-053SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316020 | AB2-059 C OP | 80/20 | 0.59 MW | 0.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316118 | AC1-105 C | 80/20 | 2.02 MW | 2.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316129 | AC1-054 C | 80/20 | 5.72 MW | 5.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 922922 | AB1-081 C OP | 80/20 | 0.5 MW | 0.5 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 923262 | AB1-132 C OP | 80/20 | 6.81 MW | 6.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 923991 | AB2-040 C O1 | 80/20 | 16.26 MW | 16.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 925591 | AC1-034 C | 80/20 | 2.25 MW | 2.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 932631 | AC2-084 C | 80/20 | 4.43 MW | 4.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 938371 | AE1-056 C | 80/20 | 2.68 MW | 2.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 939181 | AE1-148 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 940571 | AE2-044 C | 80/20 | 1.47 MW | 1.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 940661 | AE2-053 O1 | 80/20 | 2.29 MW | 2.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 946281 | AF1-292 C | 80/20 | 4.81 MW | 4.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 946301 | AF1-294 C | 80/20 | 1.91 MW | 1.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 957521 | AF2-046 C | 80/20 | 7.44 MW | 7.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 958211 | AF2-115 C | 80/20 | 1.16 MW | 1.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315115 | 1S HAMPT1 | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315141 | 1GASTONB | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315608 | 3AA2-088SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316087 | AB2-174 C | 80/20 | 2.96 MW | 2.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962561 | AG1-105 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961681 | AG1-008 C | 80/20 | 7.46 MW | 7.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962571 | AG1-106 C | 80/20 | 2.79 MW | 2.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.01 MW | 14.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.06 MW | 5.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.05 MW | 5.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.17 MW | 1.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.71 MW | 0.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961791 | AG1-021 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961891 | AG1-030 C | 80/20 | 5.6 MW | 5.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962331 | AG1-082 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962341 | AG1-083 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963171 | AG1-166 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963181 | AG1-167 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963191 | AG1-168 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963201 | AG1-169 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963211 | AG1-170 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963301 | AG1-179 C | 80/20 | 2.95 MW | 2.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963311 | AG1-180 | 80/20 | 1.44 MW | 1.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963321 | AG1-181 C O1 | 80/20 | 7.68 MW | 7.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963361 | AG1-185 O1 | 80/20 | 3.72 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964111 | AG1-272 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964121 | AG1-273 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964131 | AG1-274 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964241 | AG1-285 C O1 | 80/20 | 6.55 MW | 6.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964791 | AG1-342 C | 80/20 | 1.42 MW | 1.42 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964801 | AG1-343 C | 80/20 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 966811 | AG1-552 C | 80/20 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965191 | AG1-384 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965291 | AG1-394 C | 80/20 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965591 | AG1-427 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965601 | AG1-428 C O2 | 80/20 | 2.46 MW | 2.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965721 | AG1-440 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965731 | AG1-441 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965771 | AG1-445 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965781 | AG1-446 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 966621 | AG1-532 C | 80/20 | 0.69 MW | 0.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313506 | AB1-173 C OP | 80/20 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313719 | 3CHESTNUT | 80/20 | 0.72 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314429 | 3JTRSVLE | 80/20 | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314572 | 3EMPORIA | 80/20 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314582 | 3KELFORD | 80/20 | 0.22 MW | 0.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315126 | 1ROARAP2 | 80/20 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315128 | 1ROARAP4 | 80/20 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315158 | 1KERR 1 | 80/20 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315159 | 1KERR 2 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315160 | 1KERR 3 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315161 | 1KERR 4 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315162 | 1KERR 5 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 926201 | AC1-098 C | 80/20 | 5.16 MW | 5.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 926211 | AC1-099 C | 80/20 | 1.73 MW | 1.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 927145 | AC1-208 C | 80/20 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 936265 | AD2-033 C | 80/20 | 6.0 MW | 6.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 943171 | AE2-346 C | 80/20 | 0.9 MW | 0.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 958801 | AF2-171 C | 80/20 | 5.11 MW | 5.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 959311 | AF2-222 C | 80/20 | 7.08 MW | 7.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 960081 | AF2-299 C | 80/20 | 1.27 MW | 1.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315163 | 1KERR 6 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315164 | 1KERR 7 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315606 | 3AA2-053SOLA | 80/20 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316129 | AC1-054 C | 80/20 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316131 | AB2-060 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316140 | AB2-099 C | 80/20 | 0.38 MW | 0.38 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 923991 | AB2-040 C O1 | 80/20 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924301 | AB2-077 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924311 | AB2-078 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924321 | AB2-079 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 925611 | AC1-036 C | 80/20 | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 932631 | AC2-084 C | 80/20 | 7.36 MW | 7.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 938371 | AE1-056 C | 80/20 | 1.96 MW | 1.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 939181 | AE1-148 C | 80/20 | 7.6 MW | 7.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 940661 | AE2-053 O1 | 80/20 | 2.81 MW | 2.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 946281 | AF1-292 C | 80/20 | 0.75 MW | 0.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 946301 | AF1-294 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 957521 | AF2-046 C | 80/20 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 958211 | AF2-115 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314589 | 3MURPHYS | 80/20 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315607 | 3AA1-063SOLA | 80/20 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315608 | 3AA2-088SOLA | 80/20 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316087 | AB2-174 C | 80/20 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962561 | AG1-105 C O1 | 80/20 | 3.36 MW | 3.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961681 | AG1-008 C | 80/20 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 961791 | AG1-021 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 961891 | AG1-030 C | 80/20 | 5.6 MW | 5.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 962331 | AG1-082 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 962341 | AG1-083 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963171 | AG1-166 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963181 | AG1-167 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963191 | AG1-168 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963201 | AG1-169 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963211 | AG1-170 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963301 | AG1-179 C | 80/20 | 2.95 MW | 2.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963311 | AG1-180 | 80/20 | 1.44 MW | 1.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963321 | AG1-181 C O1 | 80/20 | 7.68 MW | 7.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963361 | AG1-185 O1 | 80/20 | 3.72 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964111 | AG1-272 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964121 | AG1-273 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964131 | AG1-274 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964241 | AG1-285 C O1 | 80/20 | 6.55 MW | 6.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964791 | AG1-342 C | 80/20 | 1.42 MW | 1.42 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964801 | AG1-343 C | 80/20 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 966811 | AG1-552 C | 80/20 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965191 | AG1-384 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965291 | AG1-394 C | 80/20 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965591 | AG1-427 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965601 | AG1-428 C O2 | 80/20 | 2.46 MW | 2.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965721 | AG1-440 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965731 | AG1-441 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965771 | AG1-445 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965781 | AG1-446 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 966621 | AG1-532 C | 80/20 | 0.69 MW | 0.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 313506 | AB1-173 C OP | 80/20 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 313719 | 3CHESTNUT | 80/20 | 0.72 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314429 | 3JTRSVLE | 80/20 | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314572 | 3EMPORIA | 80/20 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314582 | 3KELFORD | 80/20 | 0.22 MW | 0.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315126 | 1ROARAP2 | 80/20 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315128 | 1ROARAP4 | 80/20 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315158 | 1KERR 1 | 80/20 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315159 | 1KERR 2 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315160 | 1KERR 3 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315161 | 1KERR 4 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315162 | 1KERR 5 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 926201 | AC1-098 C | 80/20 | 5.16 MW | 5.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 926211 | AC1-099 C | 80/20 | 1.73 MW | 1.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 927145 | AC1-208 C | 80/20 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 936265 | AD2-033 C | 80/20 | 6.0 MW | 6.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 943171 | AE2-346 C | 80/20 | 0.9 MW | 0.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 958801 | AF2-171 C | 80/20 | 5.11 MW | 5.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 959311 | AF2-222 C | 80/20 | 7.08 MW | 7.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 960081 | AF2-299 C | 80/20 | 1.27 MW | 1.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315163 | 1KERR 6 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315164 | 1KERR 7 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315606 | 3AA2-053SOLA | 80/20 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 316129 | AC1-054 C | 80/20 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 316131 | AB2-060 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 316140 | AB2-099 C | 80/20 | 0.38 MW | 0.38 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 923991 | AB2-040 C O1 | 80/20 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 924301 | AB2-077 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 924311 | AB2-078 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 924321 | AB2-079 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 925611 | AC1-036 C | 80/20 | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 932631 | AC2-084 C | 80/20 | 7.36 MW | 7.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 938371 | AE1-056 C | 80/20 | 1.96 MW | 1.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 939181 | AE1-148 C | 80/20 | 7.6 MW | 7.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 940661 | AE2-053 O1 | 80/20 | 2.81 MW | 2.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 946281 | AF1-292 C | 80/20 | 0.75 MW | 0.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 946301 | AF1-294 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 957521 | AF2-046 C | 80/20 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 958211 | AF2-115 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314589 | 3MURPHYS | 80/20 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315607 | 3AA1-063SOLA | 80/20 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315608 | 3AA2-088SOLA | 80/20 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 316087 | AB2-174 C | 80/20 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 962561 | AG1-105 C O1 | 80/20 | 3.36 MW | 3.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 961681 | AG1-008 C | 80/20 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961791 | AG1-021 C | 80/20 | 0.62 MW | 0.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961891 | AG1-030 C | 80/20 | 5.15 MW | 5.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.22 MW | 0.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 962331 | AG1-082 C | 80/20 | 0.88 MW | 0.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 962341 | AG1-083 C | 80/20 | 0.88 MW | 0.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963171 | AG1-166 C | 80/20 | 0.62 MW | 0.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963181 | AG1-167 C | 80/20 | 0.62 MW | 0.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963191 | AG1-168 C | 80/20 | 0.62 MW | 0.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963201 | AG1-169 C | 80/20 | 0.62 MW | 0.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963211 | AG1-170 C | 80/20 | 0.62 MW | 0.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963301 | AG1-179 C | 80/20 | 2.6 MW | 2.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963311 | AG1-180 | 80/20 | 1.26 MW | 1.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 7.05 MW | 7.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 3.41 MW | 3.41 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.03 MW | 1.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.03 MW | 1.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.03 MW | 1.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 6.01 MW | 6.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.3 MW | 1.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964801 | AG1-343 C | 80/20 | 6.28 MW | 6.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 966811 | AG1-552 C | 80/20 | 4.8 MW | 4.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.03 MW | 1.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965291 | AG1-394 C | 80/20 | 2.24 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965591 | AG1-427 C | 80/20 | 5.67 MW | 5.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 2.17 MW | 2.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965721 | AG1-440 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965731 | AG1-441 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965771 | AG1-445 | 80/20 | 4.68 MW | 4.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965781 | AG1-446 | 80/20 | 4.68 MW | 4.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 966621 | AG1-532 C | 80/20 | 0.59 MW | 0.59 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 8.4 MW | 8.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 0.62 MW | 0.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.28 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 3.26 MW | 3.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 3.11 MW | 3.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.01 MW | 1.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.01 MW | 1.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.01 MW | 1.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.01 MW | 1.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 926201 | AC1-098 C | 80/20 | 4.51 MW | 4.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 926211 | AC1-099 C | 80/20 | 1.51 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 927145 | AC1-208 C | 80/20 | 9.13 MW | 9.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 936265 | AD2-033 C | 80/20 | 5.5 MW | 5.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 943171 | AE2-346 C | 80/20 | 0.61 MW | 0.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 958801 | AF2-171 C | 80/20 | 4.69 MW | 4.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 959311 | AF2-222 C | 80/20 | 6.5 MW | 6.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 960081 | AF2-299 C | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.01 MW | 1.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.01 MW | 1.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.98 MW | 2.98 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316129 | AC1-054 C | 80/20 | 11.01 MW | 11.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316131 | AB2-060 C | 80/20 | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.26 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 923262 | AB1-132 C OP | Adder | -13.41 MW | -11.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 9.15 MW | 9.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.03 MW | 1.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.03 MW | 1.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.03 MW | 1.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 932631 | AC2-084 C | 80/20 | 6.42 MW | 6.42 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.03 MW | 7.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.6 MW | 2.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 946281 | AF1-292 C | 80/20 | 0.64 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 946301 | AF1-294 C | 80/20 | 1.27 MW | 1.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 957521 | AF2-046 C | 80/20 | 13.05 MW | 13.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 958211 | AF2-115 C | 80/20 | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 938771 | AE1-103 C | 80/20 | 1.48 MW | 1.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 1.19 MW | 1.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 2.64 MW | 2.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 1.16 MW | 1.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316087 | AB2-174 C | 80/20 | 1.23 MW | 1.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 3.07 MW | 3.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961681 | AG1-008 C | 80/20 | 13.08 MW | 13.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.27 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.0 MW | 0.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.08 MW | 0.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.02 MW | 0.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 961941 | AG1-037 C | 50/50 | 1.51 MW | 1.51 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 961942 | AG1-037 E | 50/50 | 1.0 MW | 1.0 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 962331 | AG1-082 C | 50/50 | 6.03 MW | 6.03 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 962332 | AG1-082 E | 50/50 | 4.02 MW | 4.02 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 962341 | AG1-083 C | 50/50 | 6.03 MW | 6.03 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 962342 | AG1-083 E | 50/50 | 4.02 MW | 4.02 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 964801 | AG1-343 C | 50/50 | 7.47 MW | 7.47 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 964802 | AG1-343 E | 50/50 | 5.87 MW | 5.87 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 966811 | AG1-552 C | 50/50 | 1.67 MW | 1.67 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 966812 | AG1-552 E | 50/50 | 0.72 MW | 0.72 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965291 | AG1-394 C | 50/50 | 2.32 MW | 2.32 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965292 | AG1-394 E | 50/50 | 1.55 MW | 1.55 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965721 | AG1-440 C | Adder | 3.02 MW | 2.57 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965722 | AG1-440 E | Adder | 2.01 MW | 1.71 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965731 | AG1-441 C | Adder | 3.02 MW | 2.57 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965732 | AG1-441 E | Adder | 2.01 MW | 1.71 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965771 | AG1-445 | Adder | 1.75 MW | 1.48 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965781 | AG1-446 | Adder | 1.75 MW | 1.48 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 313506 | AB1-173 C OP | Adder | 3.81 MW | 3.24 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 313719 | 3CHESTNUT | 50/50 | 0.89 MW | 0.89 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314541 | 3WATKINS | 50/50 | 0.51 MW | 0.51 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314572 | 3EMPORIA | Adder | 0.18 MW | 0.15 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314582 | 3KELFORD | 50/50 | 1.04 MW | 1.04 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315126 | 1ROARAP2 | 50/50 | 1.14 MW | 1.14 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315128 | 1ROARAP4 | 50/50 | 1.08 MW | 1.08 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 918492 | AA1-063AE OP | 50/50 | 3.76 MW | 3.76 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 919692 | AA2-053 E OP | 50/50 | 4.77 MW | 4.77 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 919702 | AA2-057 E OP | 50/50 | 2.47 MW | 2.47 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 920042 | AA2-088 E OP | 50/50 | 11.43 MW | 11.43 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 920591 | AA2-165 C | 50/50 | 0.12 MW | 0.12 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 920592 | AA2-165 E | 50/50 | 0.34 MW | 0.34 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 925785 | AC1-054 E | Adder | 1.83 MW | 1.55 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926201 | AC1-098 C | 50/50 | 9.36 MW | 9.36 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926202 | AC1-098 E | 50/50 | 5.58 MW | 5.58 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926211 | AC1-099 C | 50/50 | 3.14 MW | 3.14 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 926212 | AC1-099 E | 50/50 | 1.84 MW | 1.84 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 927145 | AC1-208 C | 50/50 | 9.01 MW | 9.01 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 927146 | AC1-208 E | 50/50 | 4.0 MW | 4.0 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 943171 | AE2-346 C | 50/50 | 4.22 MW | 4.22 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 943172 | AE2-346 E | 50/50 | 1.81 MW | 1.81 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315293 | 1DOMTR9 | Adder | -3.02 MW | -2.57 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315294 | 1DOMTR10 | Adder | -3.71 MW | -3.15 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315606 | 3AA2-053SOLA | 50/50 | 1.98 MW | 1.98 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 316088 | AB2-174 E | Adder | 3.28 MW | 2.79 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 316129 | AC1-054 C | Adder | 3.96 MW | 3.37 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 316140 | AB2-099 C | 50/50 | 1.76 MW | 1.76 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 316141 | AB2-099 E | 50/50 | 0.75 MW | 0.75 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 900672 | V4-068 E | 50/50 | 0.55 MW | 0.55 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 917332 | Z2-043 E | 50/50 | 2.88 MW | 2.88 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 917342 | Z2-044 E | Adder | 0.3 MW | 0.25 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923573 | AB1-173 E OP | Adder | 1.81 MW | 1.54 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923991 | AB2-040 C O1 | Adder | 4.15 MW | 3.52 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 923992 | AB2-040 E O1 | Adder | 3.39 MW | 2.88 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 932631 | AC2-084 C | 50/50 | 13.35 MW | 13.35 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 932632 | AC2-084 E | 50/50 | 6.57 MW | 6.57 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 940491 | AE2-034 C | Adder | -2.82 MW | -2.39 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 957521 | AF2-046 C | 50/50 | 34.47 MW | 34.47 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 957522 | AF2-046 E | 50/50 | 17.34 MW | 17.34 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314539 | 3UNCAMP | 50/50 | 3.54 MW | 3.54 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 938771 | AE1-103 C | Adder | 1.4 MW | 1.19 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 938772 | AE1-103 E | Adder | 1.94 MW | 1.65 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 314589 | 3MURPHYS | 50/50 | 0.17 MW | 0.17 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315115 | 1S HAMPT1 | 50/50 | 1.19 MW | 1.19 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315607 | 3AA1-063SOLA | 50/50 | 1.36 MW | 1.36 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 315608 | 3AA2-088SOLA | 50/50 | 1.19 MW | 1.19 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 961681 | AG1-008 C | 50/50 | 34.54 MW | 34.54 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 961682 | AG1-008 E | 50/50 | 17.27 MW | 17.27 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965752 | AG1-443 BAT | 50/50 | 3.52 MW | 3.52 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | 965742 | AG1-442 BAT | 50/50 | 3.52 MW | 3.52 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.1 MW | 0.1 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.08 MW | 2.08 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.73 MW | 0.73 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.77 MW | 0.77 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.15 MW | 0.15 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.1 MW | 0.1 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.18 MW | 0.18 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.61 MW | 0.61 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.15 MW | 0.15 MW |
| 3EARLEYS-6EARLEYS 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 201262 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961891 | AG1-030 C | Adder | 6.32 MW | 5.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961892 | AG1-030 E | Adder | 4.21 MW | 3.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963301 | AG1-179 C | Adder | 3.52 MW | 3.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963311 | AG1-180 | Adder | 1.72 MW | 1.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965601 | AG1-428 C O2 | Adder | 2.94 MW | 2.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965602 | AG1-428 E O2 | Adder | 1.96 MW | 1.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962561 | AG1-105 C O1 | Adder | 3.79 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962562 | AG1-105 E O1 | Adder | 2.53 MW | 2.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.31 MW | 2.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.91 MW | 0.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963301 | AG1-179 C | Adder | 3.52 MW | 3.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963311 | AG1-180 | Adder | 1.72 MW | 1.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965601 | AG1-428 C O2 | Adder | 2.94 MW | 2.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965602 | AG1-428 E O2 | Adder | 1.96 MW | 1.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314572 | 3EMPORIA | 50/50 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.31 MW | 2.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.91 MW | 0.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314572 | 3EMPORIA | 50/50 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.32 MW | 2.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.93 MW | 0.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961891 | AG1-030 C | Adder | 5.6 MW | 4.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961892 | AG1-030 E | Adder | 3.74 MW | 3.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961941 | AG1-037 C | Adder | 0.32 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961942 | AG1-037 E | Adder | 0.22 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962331 | AG1-082 C | Adder | 1.29 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962332 | AG1-082 E | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962341 | AG1-083 C | Adder | 1.29 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962342 | AG1-083 E | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963301 | AG1-179 C | Adder | 2.95 MW | 2.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963311 | AG1-180 | Adder | 1.44 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963321 | AG1-181 C O1 | Adder | 7.68 MW | 6.53 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963361 | AG1-185 O1 | Adder | 3.72 MW | 3.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964111 | AG1-272 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964112 | AG1-272 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964121 | AG1-273 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964122 | AG1-273 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964131 | AG1-274 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964132 | AG1-274 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964241 | AG1-285 C O1 | Adder | 6.55 MW | 5.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964242 | AG1-285 E O1 | Adder | 4.37 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964801 | AG1-343 C | 50/50 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964802 | AG1-343 E | 50/50 | 7.66 MW | 7.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966811 | AG1-552 C | 50/50 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966812 | AG1-552 E | 50/50 | 2.2 MW | 2.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965191 | AG1-384 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965192 | AG1-384 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965291 | AG1-394 C | 50/50 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965292 | AG1-394 E | 50/50 | 2.32 MW | 2.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965591 | AG1-427 C | Adder | 6.18 MW | 5.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965592 | AG1-427 E | Adder | 4.13 MW | 3.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965601 | AG1-428 C O2 | Adder | 2.46 MW | 2.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965602 | AG1-428 E O2 | Adder | 1.64 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965721 | AG1-440 C | 50/50 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965722 | AG1-440 E | 50/50 | 5.81 MW | 5.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965731 | AG1-441 C | 50/50 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965732 | AG1-441 E | 50/50 | 5.81 MW | 5.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965771 | AG1-445 | 50/50 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965781 | AG1-446 | 50/50 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966621 | AG1-532 C | Adder | 0.69 MW | 0.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966622 | AG1-532 E | Adder | 0.46 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 313506 | AB1-173 C OP | 50/50 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 314572 | 3EMPORIA | Adder | 0.31 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315126 | 1ROARAP2 | 50/50 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315128 | 1ROARAP4 | 50/50 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315159 | 1KERR 2 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315160 | 1KERR 3 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315161 | 1KERR 4 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315162 | 1KERR 5 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 918492 | AA1-063AE OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 919692 | AA2-053 E OP | 50/50 | 7.76 MW | 7.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 919702 | AA2-057 E OP | Adder | 2.0 MW | 1.7 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 920042 | AA2-088 E OP | 50/50 | 18.01 MW | 18.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 920592 | AA2-165 E | Adder | 0.28 MW | 0.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 925785 | AC1-054 E | 50/50 | 5.44 MW | 5.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926201 | AC1-098 C | Adder | 5.16 MW | 4.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926202 | AC1-098 E | Adder | 3.08 MW | 2.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926211 | AC1-099 C | Adder | 1.73 MW | 1.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926212 | AC1-099 E | Adder | 1.02 MW | 0.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 927145 | AC1-208 C | 50/50 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 927146 | AC1-208 E | 50/50 | 4.49 MW | 4.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 936265 | AD2-033 C | Adder | 6.0 MW | 5.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 936266 | AD2-033 E | Adder | 4.0 MW | 3.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 943171 | AE2-346 C | Adder | 0.9 MW | 0.77 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 943172 | AE2-346 E | Adder | 0.39 MW | 0.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 959311 | AF2-222 C | Adder | 7.08 MW | 6.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 959312 | AF2-222 E | Adder | 4.74 MW | 4.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 960081 | AF2-299 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 960082 | AF2-299 E | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315163 | 1KERR 6 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315164 | 1KERR 7 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315606 | 3AA2-053SOLA | 50/50 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316088 | AB2-174 E | 50/50 | 7.19 MW | 7.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316129 | AC1-054 C | 50/50 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316140 | AB2-099 C | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316141 | AB2-099 E | Adder | 0.16 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 900672 | V4-068 E | 50/50 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 917332 | Z2-043 E | Adder | 0.6 MW | 0.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923573 | AB1-173 E OP | 50/50 | 4.34 MW | 4.34 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923991 | AB2-040 C O1 | 50/50 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923992 | AB2-040 E O1 | 50/50 | 8.15 MW | 8.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924162 | AB2-060 E OP | Adder | 2.34 MW | 1.99 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924301 | AB2-077 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924302 | AB2-077 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924311 | AB2-078 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924312 | AB2-078 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924321 | AB2-079 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924322 | AB2-079 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 925612 | AC1-036 E | Adder | 0.68 MW | 0.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 932631 | AC2-084 C | Adder | 7.36 MW | 6.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 932632 | AC2-084 E | Adder | 3.62 MW | 3.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 939181 | AE1-148 C | Adder | 7.6 MW | 6.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 939182 | AE1-148 E | Adder | 5.06 MW | 4.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 940661 | AE2-053 O1 | Adder | 2.81 MW | 2.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 946281 | AF1-292 C | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 946282 | AF1-292 E | Adder | 0.51 MW | 0.43 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 957521 | AF2-046 C | 50/50 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 957522 | AF2-046 E | 50/50 | 10.06 MW | 10.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 314589 | 3MURPHYS | 50/50 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315608 | 3AA2-088SOLA | 50/50 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316087 | AB2-174 C | 50/50 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962561 | AG1-105 C O1 | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962562 | AG1-105 E O1 | Adder | 2.24 MW | 1.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961681 | AG1-008 C | 50/50 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961682 | AG1-008 E | 50/50 | 10.02 MW | 10.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924022 | AB2-043 E O1 | Adder | 1.57 MW | 1.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.76 MW | 0.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | 50/50 | 4.98 MW | 4.98 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | 50/50 | 2.13 MW | 2.13 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 6.04 MW | 6.04 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 4.03 MW | 4.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 6.04 MW | 6.04 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 4.03 MW | 4.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313719 | 3CHESTNUT | 50/50 | 5.34 MW | 5.34 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314582 | 3KELFORD | 50/50 | 0.5 MW | 0.5 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314623 | 3WITAKRS | 50/50 | 1.13 MW | 1.13 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 3.39 MW | 3.39 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315128 | 1ROARAP4 | 50/50 | 3.23 MW | 3.23 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 919702 | AA2-057 E OP | 50/50 | 14.8 MW | 14.8 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 920591 | AA2-165 C | 50/50 | 0.72 MW | 0.72 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 920592 | AA2-165 E | 50/50 | 2.03 MW | 2.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925785 | AC1-054 E | Adder | 1.72 MW | 1.46 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926201 | AC1-098 C | 50/50 | 17.72 MW | 17.72 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926202 | AC1-098 E | 50/50 | 10.56 MW | 10.56 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926211 | AC1-099 C | 50/50 | 5.94 MW | 5.94 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926212 | AC1-099 E | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | 50/50 | 30.77 MW | 30.77 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | 50/50 | 13.66 MW | 13.66 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | Adder | 3.73 MW | 3.17 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 917332 | Z2-043 E | 50/50 | 1.39 MW | 1.39 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 917342 | Z2-044 E | 50/50 | 2.85 MW | 2.85 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 932631 | AC2-084 C | 50/50 | 25.26 MW | 25.26 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 932632 | AC2-084 E | 50/50 | 12.44 MW | 12.44 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939182 | AE1-148 E | Adder | 2.74 MW | 2.33 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 944142 | AF1-082 BAT | 50/50 | 1.89 MW | 1.89 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.34 MW | 0.34 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.18 MW | 0.18 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.19 MW | 0.19 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.68 MW | 0.68 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.02 MW | 0.02 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.11 MW | 0.11 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.42 MW | 0.42 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.64 MW | 0.64 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.11 MW | 0.11 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.05 MW | 0.05 MW |
| Details for 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | 50/50 | 4.98 MW | 4.98 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | 50/50 | 2.13 MW | 2.13 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 6.04 MW | 6.04 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 4.03 MW | 4.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 6.04 MW | 6.04 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 4.03 MW | 4.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313719 | 3CHESTNUT | 50/50 | 5.34 MW | 5.34 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314582 | 3KELFORD | 50/50 | 0.5 MW | 0.5 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314623 | 3WITAKRS | 50/50 | 1.13 MW | 1.13 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 3.39 MW | 3.39 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315128 | 1ROARAP4 | 50/50 | 3.23 MW | 3.23 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 919702 | AA2-057 E OP | 50/50 | 14.8 MW | 14.8 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 920591 | AA2-165 C | 50/50 | 0.72 MW | 0.72 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 920592 | AA2-165 E | 50/50 | 2.03 MW | 2.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925785 | AC1-054 E | Adder | 1.72 MW | 1.46 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926201 | AC1-098 C | 50/50 | 17.72 MW | 17.72 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926202 | AC1-098 E | 50/50 | 10.56 MW | 10.56 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926211 | AC1-099 C | 50/50 | 5.94 MW | 5.94 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926212 | AC1-099 E | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | 50/50 | 30.77 MW | 30.77 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | 50/50 | 13.66 MW | 13.66 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | Adder | 3.73 MW | 3.17 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 917332 | Z2-043 E | 50/50 | 1.39 MW | 1.39 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 917342 | Z2-044 E | 50/50 | 2.85 MW | 2.85 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 932631 | AC2-084 C | 50/50 | 25.26 MW | 25.26 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 932632 | AC2-084 E | 50/50 | 12.44 MW | 12.44 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939182 | AE1-148 E | Adder | 2.74 MW | 2.33 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 944142 | AF1-082 BAT | 50/50 | 1.89 MW | 1.89 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.34 MW | 0.34 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.18 MW | 0.18 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.19 MW | 0.19 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.68 MW | 0.68 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.02 MW | 0.02 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.11 MW | 0.11 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.42 MW | 0.42 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.64 MW | 0.64 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.11 MW | 0.11 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.05 MW | 0.05 MW |
| Details for 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | 50/50 | 4.98 MW | 4.98 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | 50/50 | 2.13 MW | 2.13 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 6.04 MW | 6.04 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 4.03 MW | 4.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 6.04 MW | 6.04 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 4.03 MW | 4.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313719 | 3CHESTNUT | 50/50 | 5.34 MW | 5.34 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314582 | 3KELFORD | 50/50 | 0.5 MW | 0.5 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314623 | 3WITAKRS | 50/50 | 1.13 MW | 1.13 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 3.39 MW | 3.39 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315128 | 1ROARAP4 | 50/50 | 3.23 MW | 3.23 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 919702 | AA2-057 E OP | 50/50 | 14.8 MW | 14.8 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 920591 | AA2-165 C | 50/50 | 0.72 MW | 0.72 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 920592 | AA2-165 E | 50/50 | 2.03 MW | 2.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925785 | AC1-054 E | Adder | 1.72 MW | 1.46 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926201 | AC1-098 C | 50/50 | 17.72 MW | 17.72 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926202 | AC1-098 E | 50/50 | 10.56 MW | 10.56 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926211 | AC1-099 C | 50/50 | 5.94 MW | 5.94 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926212 | AC1-099 E | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | 50/50 | 30.77 MW | 30.77 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | 50/50 | 13.66 MW | 13.66 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | Adder | 3.73 MW | 3.17 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 917332 | Z2-043 E | 50/50 | 1.39 MW | 1.39 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 917342 | Z2-044 E | 50/50 | 2.85 MW | 2.85 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 932631 | AC2-084 C | 50/50 | 25.26 MW | 25.26 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 932632 | AC2-084 E | 50/50 | 12.44 MW | 12.44 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939182 | AE1-148 E | Adder | 2.74 MW | 2.33 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 944142 | AF1-082 BAT | 50/50 | 1.89 MW | 1.89 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.34 MW | 0.34 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.18 MW | 0.18 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.19 MW | 0.19 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.68 MW | 0.68 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.02 MW | 0.02 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.11 MW | 0.11 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.42 MW | 0.42 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.64 MW | 0.64 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.11 MW | 0.11 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.05 MW | 0.05 MW |
| Details for 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | 50/50 | 4.98 MW | 4.98 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | 50/50 | 2.13 MW | 2.13 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 6.04 MW | 6.04 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 4.03 MW | 4.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 6.04 MW | 6.04 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 4.03 MW | 4.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313719 | 3CHESTNUT | 50/50 | 5.34 MW | 5.34 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314582 | 3KELFORD | 50/50 | 0.5 MW | 0.5 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314623 | 3WITAKRS | 50/50 | 1.13 MW | 1.13 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 3.39 MW | 3.39 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315128 | 1ROARAP4 | 50/50 | 3.23 MW | 3.23 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 919702 | AA2-057 E OP | 50/50 | 14.8 MW | 14.8 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 920591 | AA2-165 C | 50/50 | 0.72 MW | 0.72 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 920592 | AA2-165 E | 50/50 | 2.03 MW | 2.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925785 | AC1-054 E | Adder | 1.72 MW | 1.46 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926201 | AC1-098 C | 50/50 | 17.72 MW | 17.72 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926202 | AC1-098 E | 50/50 | 10.56 MW | 10.56 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926211 | AC1-099 C | 50/50 | 5.94 MW | 5.94 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926212 | AC1-099 E | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | 50/50 | 30.77 MW | 30.77 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | 50/50 | 13.66 MW | 13.66 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | Adder | 3.73 MW | 3.17 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 917332 | Z2-043 E | 50/50 | 1.39 MW | 1.39 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 917342 | Z2-044 E | 50/50 | 2.85 MW | 2.85 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 932631 | AC2-084 C | 50/50 | 25.26 MW | 25.26 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 932632 | AC2-084 E | 50/50 | 12.44 MW | 12.44 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939182 | AE1-148 E | Adder | 2.74 MW | 2.33 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 944142 | AF1-082 BAT | 50/50 | 1.89 MW | 1.89 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.34 MW | 0.34 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.18 MW | 0.18 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.19 MW | 0.19 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.68 MW | 0.68 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.02 MW | 0.02 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.11 MW | 0.11 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.42 MW | 0.42 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.64 MW | 0.64 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.11 MW | 0.11 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.05 MW | 0.05 MW |
| Details for 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 966811 | AG1-552 C | 50/50 | 4.98 MW | 4.98 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 966812 | AG1-552 E | 50/50 | 2.13 MW | 2.13 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965721 | AG1-440 C | 50/50 | 6.04 MW | 6.04 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965722 | AG1-440 E | 50/50 | 4.03 MW | 4.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965731 | AG1-441 C | 50/50 | 6.04 MW | 6.04 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965732 | AG1-441 E | 50/50 | 4.03 MW | 4.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965771 | AG1-445 | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965781 | AG1-446 | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 313719 | 3CHESTNUT | 50/50 | 5.34 MW | 5.34 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 314582 | 3KELFORD | 50/50 | 0.5 MW | 0.5 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 314623 | 3WITAKRS | 50/50 | 1.13 MW | 1.13 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 315126 | 1ROARAP2 | 50/50 | 3.39 MW | 3.39 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 315128 | 1ROARAP4 | 50/50 | 3.23 MW | 3.23 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 919702 | AA2-057 E OP | 50/50 | 14.8 MW | 14.8 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 920591 | AA2-165 C | 50/50 | 0.72 MW | 0.72 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 920592 | AA2-165 E | 50/50 | 2.03 MW | 2.03 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926201 | AC1-098 C | 50/50 | 17.72 MW | 17.72 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926202 | AC1-098 E | 50/50 | 10.56 MW | 10.56 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926211 | AC1-099 C | 50/50 | 5.94 MW | 5.94 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926212 | AC1-099 E | 50/50 | 3.49 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 927145 | AC1-208 C | 50/50 | 30.77 MW | 30.77 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 927146 | AC1-208 E | 50/50 | 13.66 MW | 13.66 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 917332 | Z2-043 E | 50/50 | 1.39 MW | 1.39 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 917342 | Z2-044 E | 50/50 | 2.85 MW | 2.85 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 932631 | AC2-084 C | 50/50 | 25.26 MW | 25.26 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 932632 | AC2-084 E | 50/50 | 12.44 MW | 12.44 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 939182 | AE1-148 E | Adder | 2.74 MW | 2.33 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 944142 | AF1-082 BAT | 50/50 | 1.89 MW | 1.89 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.34 MW | 0.34 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.18 MW | 0.18 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.19 MW | 0.19 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.68 MW | 0.68 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.02 MW | 0.02 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.11 MW | 0.11 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.42 MW | 0.42 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.64 MW | 0.64 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.11 MW | 0.11 MW |
| 3WITAKRS-3CONSLDL 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.05 MW | 0.05 MW |
| Details for 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 966811 | AG1-552 C | 50/50 | 4.98 MW | 4.98 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 966812 | AG1-552 E | 50/50 | 2.13 MW | 2.13 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965721 | AG1-440 C | 50/50 | 6.04 MW | 6.04 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965722 | AG1-440 E | 50/50 | 4.03 MW | 4.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965731 | AG1-441 C | 50/50 | 6.04 MW | 6.04 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965732 | AG1-441 E | 50/50 | 4.03 MW | 4.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965771 | AG1-445 | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965781 | AG1-446 | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 313719 | 3CHESTNUT | 50/50 | 5.34 MW | 5.34 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 314582 | 3KELFORD | 50/50 | 0.5 MW | 0.5 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 314623 | 3WITAKRS | 50/50 | 1.13 MW | 1.13 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 315126 | 1ROARAP2 | 50/50 | 3.39 MW | 3.39 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 315128 | 1ROARAP4 | 50/50 | 3.23 MW | 3.23 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 919702 | AA2-057 E OP | 50/50 | 14.8 MW | 14.8 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 920591 | AA2-165 C | 50/50 | 0.72 MW | 0.72 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 920592 | AA2-165 E | 50/50 | 2.03 MW | 2.03 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926201 | AC1-098 C | 50/50 | 17.72 MW | 17.72 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926202 | AC1-098 E | 50/50 | 10.56 MW | 10.56 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926211 | AC1-099 C | 50/50 | 5.94 MW | 5.94 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926212 | AC1-099 E | 50/50 | 3.49 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 927145 | AC1-208 C | 50/50 | 30.77 MW | 30.77 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 927146 | AC1-208 E | 50/50 | 13.66 MW | 13.66 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 917332 | Z2-043 E | 50/50 | 1.39 MW | 1.39 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 917342 | Z2-044 E | 50/50 | 2.85 MW | 2.85 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 932631 | AC2-084 C | 50/50 | 25.26 MW | 25.26 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 932632 | AC2-084 E | 50/50 | 12.44 MW | 12.44 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 939182 | AE1-148 E | Adder | 2.74 MW | 2.33 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 944142 | AF1-082 BAT | 50/50 | 1.89 MW | 1.89 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.34 MW | 0.34 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.18 MW | 0.18 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.19 MW | 0.19 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.68 MW | 0.68 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.02 MW | 0.02 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.11 MW | 0.11 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.42 MW | 0.42 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.64 MW | 0.64 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.11 MW | 0.11 MW |
| 3CONSLDL-3BTLEBRO 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.05 MW | 0.05 MW |
| Details for 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 966811 | AG1-552 C | 50/50 | 5.48 MW | 5.48 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 966812 | AG1-552 E | 50/50 | 2.35 MW | 2.35 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965721 | AG1-440 C | 50/50 | 36.18 MW | 36.18 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965722 | AG1-440 E | 50/50 | 24.12 MW | 24.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965731 | AG1-441 C | 50/50 | 36.18 MW | 36.18 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965732 | AG1-441 E | 50/50 | 24.12 MW | 24.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965771 | AG1-445 | 50/50 | 20.9 MW | 20.9 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 965781 | AG1-446 | 50/50 | 20.9 MW | 20.9 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 313719 | 3CHESTNUT | 50/50 | 0.98 MW | 0.98 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 315126 | 1ROARAP2 | 50/50 | 3.72 MW | 3.72 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 315128 | 1ROARAP4 | 50/50 | 3.55 MW | 3.55 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 919702 | AA2-057 E OP | 50/50 | 2.7 MW | 2.7 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 920591 | AA2-165 C | 50/50 | 0.13 MW | 0.13 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 920592 | AA2-165 E | 50/50 | 0.37 MW | 0.37 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926201 | AC1-098 C | 50/50 | 5.64 MW | 5.64 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926202 | AC1-098 E | 50/50 | 3.36 MW | 3.36 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926211 | AC1-099 C | 50/50 | 1.89 MW | 1.89 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 926212 | AC1-099 E | 50/50 | 1.11 MW | 1.11 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 927145 | AC1-208 C | 50/50 | 11.53 MW | 11.53 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 927146 | AC1-208 E | 50/50 | 5.12 MW | 5.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 917332 | Z2-043 E | Adder | 0.49 MW | 0.42 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 917342 | Z2-044 E | Adder | 0.33 MW | 0.28 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 932631 | AC2-084 C | 50/50 | 8.04 MW | 8.04 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 932632 | AC2-084 E | 50/50 | 3.96 MW | 3.96 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | 940662 | AE2-053 BAT | 50/50 | 2.27 MW | 2.27 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.03 MW | 0.03 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.62 MW | 0.62 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.09 MW | 0.09 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 2202 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| Details for 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | 50/50 | 5.48 MW | 5.48 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | 50/50 | 2.35 MW | 2.35 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 36.18 MW | 36.18 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 24.12 MW | 24.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 36.18 MW | 36.18 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 24.12 MW | 24.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 20.9 MW | 20.9 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 20.9 MW | 20.9 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313719 | 3CHESTNUT | 50/50 | 0.98 MW | 0.98 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 3.72 MW | 3.72 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315128 | 1ROARAP4 | 50/50 | 3.55 MW | 3.55 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 919702 | AA2-057 E OP | 50/50 | 2.7 MW | 2.7 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 920591 | AA2-165 C | 50/50 | 0.13 MW | 0.13 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 920592 | AA2-165 E | 50/50 | 0.37 MW | 0.37 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926201 | AC1-098 C | 50/50 | 5.64 MW | 5.64 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926202 | AC1-098 E | 50/50 | 3.36 MW | 3.36 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926211 | AC1-099 C | 50/50 | 1.89 MW | 1.89 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926212 | AC1-099 E | 50/50 | 1.11 MW | 1.11 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | 50/50 | 11.53 MW | 11.53 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | 50/50 | 5.12 MW | 5.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | Adder | -5.55 MW | -4.71 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 917332 | Z2-043 E | Adder | 0.49 MW | 0.42 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 917342 | Z2-044 E | Adder | 0.33 MW | 0.28 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 932631 | AC2-084 C | 50/50 | 8.04 MW | 8.04 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 932632 | AC2-084 E | 50/50 | 3.96 MW | 3.96 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940662 | AE2-053 BAT | 50/50 | 2.27 MW | 2.27 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.03 MW | 0.03 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.62 MW | 0.62 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.09 MW | 0.09 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| Details for 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | 50/50 | 5.48 MW | 5.48 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | 50/50 | 2.35 MW | 2.35 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 36.18 MW | 36.18 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 24.12 MW | 24.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 36.18 MW | 36.18 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 24.12 MW | 24.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 20.9 MW | 20.9 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 20.9 MW | 20.9 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313719 | 3CHESTNUT | 50/50 | 0.98 MW | 0.98 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 3.72 MW | 3.72 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315128 | 1ROARAP4 | 50/50 | 3.55 MW | 3.55 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 919702 | AA2-057 E OP | 50/50 | 2.7 MW | 2.7 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 920591 | AA2-165 C | 50/50 | 0.13 MW | 0.13 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 920592 | AA2-165 E | 50/50 | 0.37 MW | 0.37 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926201 | AC1-098 C | 50/50 | 5.64 MW | 5.64 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926202 | AC1-098 E | 50/50 | 3.36 MW | 3.36 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926211 | AC1-099 C | 50/50 | 1.89 MW | 1.89 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926212 | AC1-099 E | 50/50 | 1.11 MW | 1.11 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | 50/50 | 11.53 MW | 11.53 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | 50/50 | 5.12 MW | 5.12 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | Adder | -5.55 MW | -4.71 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 917332 | Z2-043 E | Adder | 0.49 MW | 0.42 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 917342 | Z2-044 E | Adder | 0.33 MW | 0.28 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 932631 | AC2-084 C | 50/50 | 8.04 MW | 8.04 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 932632 | AC2-084 E | 50/50 | 3.96 MW | 3.96 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940662 | AE2-053 BAT | 50/50 | 2.27 MW | 2.27 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.03 MW | 0.03 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.62 MW | 0.62 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.09 MW | 0.09 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 3PALMERSPRNG-3KERR 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| Details for 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 961671 | AG1-007 C | 50/50 | 0.97 MW | 0.97 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 961672 | AG1-007 E | 50/50 | 0.55 MW | 0.55 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 961941 | AG1-037 C | Adder | 0.28 MW | 0.23 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 961942 | AG1-037 E | Adder | 0.18 MW | 0.16 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 962331 | AG1-082 C | Adder | 1.1 MW | 0.94 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 962332 | AG1-082 E | Adder | 0.73 MW | 0.62 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 962341 | AG1-083 C | Adder | 1.1 MW | 0.94 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 962342 | AG1-083 E | Adder | 0.73 MW | 0.62 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 964801 | AG1-343 C | Adder | 2.86 MW | 2.43 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 964802 | AG1-343 E | Adder | 2.25 MW | 1.91 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 966801 | AG1-551 C | Adder | 0.91 MW | 0.77 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 966802 | AG1-551 E | Adder | 0.39 MW | 0.33 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 966811 | AG1-552 C | 50/50 | 1.38 MW | 1.38 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 966812 | AG1-552 E | 50/50 | 0.59 MW | 0.59 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965291 | AG1-394 C | Adder | 0.97 MW | 0.83 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965292 | AG1-394 E | Adder | 0.65 MW | 0.55 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965691 | AG1-437 C O1 | Adder | 3.86 MW | 3.28 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965692 | AG1-437 E O1 | Adder | 2.57 MW | 2.19 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965701 | AG1-438 C O1 | Adder | 3.86 MW | 3.28 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965702 | AG1-438 E O1 | Adder | 2.57 MW | 2.19 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965711 | AG1-439 C O1 | 50/50 | 21.33 MW | 21.33 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965712 | AG1-439 E O1 | 50/50 | 14.22 MW | 14.22 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965741 | AG1-442 O1 | Adder | 2.25 MW | 1.91 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965751 | AG1-443 O1 | Adder | 2.25 MW | 1.91 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 965761 | AG1-444 O1 | 50/50 | 11.38 MW | 11.38 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 966621 | AG1-532 C | Adder | 0.61 MW | 0.52 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 966622 | AG1-532 E | Adder | 0.41 MW | 0.35 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 313506 | AB1-173 C OP | Adder | 3.67 MW | 3.12 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 313719 | 3CHESTNUT | 50/50 | 2.62 MW | 2.62 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314541 | 3WATKINS | Adder | 0.26 MW | 0.22 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314572 | 3EMPORIA | Adder | 0.2 MW | 0.17 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314582 | 3KELFORD | 50/50 | 0.34 MW | 0.34 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 314623 | 3WITAKRS | 50/50 | 0.57 MW | 0.57 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315126 | 1ROARAP2 | 50/50 | 0.94 MW | 0.94 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315128 | 1ROARAP4 | 50/50 | 0.9 MW | 0.9 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315131 | 1EDGECMA | 50/50 | 10.84 MW | 10.84 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315132 | 1EDGECMB | 50/50 | 10.84 MW | 10.84 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315136 | 1ROSEMG1 | 50/50 | 1.63 MW | 1.63 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315137 | 1ROSEMS1 | 50/50 | 1.01 MW | 1.01 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315138 | 1ROSEMG2 | 50/50 | 0.76 MW | 0.76 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315139 | 1GASTONA | 50/50 | 2.09 MW | 2.09 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917512 | Z2-088 E OP1 | 50/50 | 7.05 MW | 7.05 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918492 | AA1-063AE OP | Adder | 2.36 MW | 2.01 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918532 | AA1-067 E | Adder | 0.3 MW | 0.25 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919692 | AA2-053 E OP | 50/50 | 2.4 MW | 2.4 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 919702 | AA2-057 E OP | 50/50 | 7.26 MW | 7.26 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920042 | AA2-088 E OP | Adder | 4.88 MW | 4.15 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920591 | AA2-165 C | 50/50 | 0.35 MW | 0.35 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 920592 | AA2-165 E | 50/50 | 1.0 MW | 1.0 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925785 | AC1-054 E | Adder | 1.38 MW | 1.18 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926070 | AC1-086 C | 50/50 | 13.81 MW | 13.81 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926071 | AC1-086 E | 50/50 | 6.29 MW | 6.29 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926201 | AC1-098 C | 50/50 | 8.82 MW | 8.82 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926202 | AC1-098 E | 50/50 | 5.25 MW | 5.25 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926211 | AC1-099 C | 50/50 | 2.96 MW | 2.96 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 926212 | AC1-099 E | 50/50 | 1.74 MW | 1.74 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927024 | AC1-189 C | 50/50 | 6.28 MW | 6.28 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927025 | AC1-189 E | 50/50 | 3.13 MW | 3.13 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927145 | AC1-208 C | 50/50 | 14.04 MW | 14.04 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 927146 | AC1-208 E | 50/50 | 6.23 MW | 6.23 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934331 | AD1-057 C O1 | 50/50 | 10.42 MW | 10.42 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 934332 | AD1-057 E O1 | 50/50 | 5.57 MW | 5.57 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943171 | AE2-346 C | Adder | 0.77 MW | 0.66 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 943172 | AE2-346 E | Adder | 0.33 MW | 0.28 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 944141 | AF1-082 | 50/50 | 7.65 MW | 7.65 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960081 | AF2-299 C | Adder | 1.14 MW | 0.97 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960082 | AF2-299 E | Adder | 0.76 MW | 0.65 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315601 | 1CONETOE2SOL | 50/50 | 1.28 MW | 1.28 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315606 | 3AA2-053SOLA | 50/50 | 1.0 MW | 1.0 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 316020 | AB2-059 C OP | 50/50 | 4.78 MW | 4.78 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 316088 | AB2-174 E | Adder | 3.3 MW | 2.81 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 316097 | AB2-100 E1 | Adder | 1.27 MW | 1.08 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 316099 | AB2-100 E2 | Adder | 1.27 MW | 1.08 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 316129 | AC1-054 C | Adder | 3.0 MW | 2.55 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 316140 | AB2-099 C | Adder | 0.32 MW | 0.27 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 900672 | V4-068 E | Adder | 0.15 MW | 0.13 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917332 | Z2-043 E | 50/50 | 0.93 MW | 0.93 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 917342 | Z2-044 E | 50/50 | 1.42 MW | 1.42 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 922922 | AB1-081 C OP | 50/50 | 4.05 MW | 4.05 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 922923 | AB1-081 E OP | 50/50 | 10.2 MW | 10.2 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923262 | AB1-132 C OP | 50/50 | 9.38 MW | 9.38 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923263 | AB1-132 E OP | 50/50 | 4.02 MW | 4.02 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923573 | AB1-173 E OP | Adder | 1.74 MW | 1.48 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923991 | AB2-040 C O1 | Adder | 3.99 MW | 3.39 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 923992 | AB2-040 E O1 | Adder | 3.27 MW | 2.78 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 924152 | AB2-059 E OP | 50/50 | 14.45 MW | 14.45 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925591 | AC1-034 C | 50/50 | 18.17 MW | 18.17 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 925592 | AC1-034 E | 50/50 | 13.71 MW | 13.71 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 932631 | AC2-084 C | 50/50 | 12.57 MW | 12.57 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 932632 | AC2-084 E | 50/50 | 6.19 MW | 6.19 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 938222 | AE1-035 E | Adder | 0.48 MW | 0.41 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940571 | AE2-044 C | 50/50 | 11.9 MW | 11.9 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 940572 | AE2-044 E | 50/50 | 5.1 MW | 5.1 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946281 | AF1-292 C | Adder | 0.68 MW | 0.57 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 946282 | AF1-292 E | Adder | 0.46 MW | 0.39 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957521 | AF2-046 C | Adder | 8.62 MW | 7.32 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957522 | AF2-046 E | Adder | 4.33 MW | 3.68 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957861 | AF2-080 C | 50/50 | 5.7 MW | 5.7 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 957862 | AF2-080 E | 50/50 | 2.53 MW | 2.53 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 315141 | 1GASTONB | 50/50 | 2.09 MW | 2.09 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960331 | AF2-324 C | 50/50 | 10.58 MW | 10.58 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 960332 | AF2-324 E | 50/50 | 5.68 MW | 5.68 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 962572 | AG1-106 E | 50/50 | 1.74 MW | 1.74 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 961681 | AG1-008 C | Adder | 8.63 MW | 7.34 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 961682 | AG1-008 E | Adder | 4.32 MW | 3.67 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 962571 | AG1-106 C | 50/50 | 3.84 MW | 3.84 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | 918512 | AA1-065 E OP | Adder | 1.74 MW | 1.48 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.87 MW | 0.87 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.35 MW | 2.35 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.7 MW | 0.7 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.76 MW | 0.76 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.17 MW | 0.17 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.72 MW | 0.72 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.61 MW | 2.61 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.51 MW | 0.51 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.43 MW | 0.43 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.53 MW | 1.53 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.45 MW | 2.45 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.42 MW | 0.42 MW |
| 3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 2058-2181 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.35 MW | 1.35 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n6113 | Add additional 230/115 kV transformer at Carolina substation. | $6,000,000 | |
| n6114 | Add additional 230/115 kV transformer at Clubhouse substation. Cost changed during facility study phase. | $13,653,448 | |
| n8299 | Rebuild 4.24 miles of 115 kV Line 1001 from Consolidated Diesel to Battleboro with 636 ACSR. | $5,512,000 | |
| n7203 | Rebuild 0.41 miles of 115 kV Line 1001 from Whitakers to Consolidated Diesel with 636 ACSR. | $533,000 | |
| n7541 | 230/115 kV Transformer Addition | $6,000,000 | |
| (TBD) | Reconductor 20 miles with single 795 ACSS-TW per phase, replace breaker, disconnect switches, wave trap, line switch | $60,000,000 | |
| s2614 | For DEV portion, rebuild 4.7 miles of 115 kV Line 45 from Kerr Dam to GW King Tap with 768 ACSS. | $6,123,000 | |
| n8257 | Reconductor 115 kV line #1019 from Kerr Dam to Palmer Springs. | $204,000 | |
| (TBD) | Reconductor 8.5 miles RockyMt-Battleborro with single 795 ACSS-TW per phase, upgrade disconnect switches and CT ratios. | $31,000,000 | |
| n6618.1 | Hathaway 115 kV Bus Split. | $20,749 | |
| s2825.1 | Rebuild entire line#2167 Edgecombe NUG to Hathaway. | $39,500,000 | |
| s2825.2 | Rebuild line #55 Tarboro to Hart Mills. | $3,500,000 | |
| n6118 | Upgrade the breaker leads at DVPs Battleboro terminal will bring the rating to 239/239/239 MVA (Limited by terminal equipment at Rocky Mount) | $100,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-552 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.