AG1-538 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:46
Remington-Gordonsville 230 kV
32.0 MW Capacity / 75.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-538 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the Dominion zone — Culpeper County, Virginia. The installed facilities will have a total capability of 75.0 MW with 32.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-538 |
| Project Name | Remington-Gordonsville 230 kV |
| Developer Name | Longleaf Storage, LLC |
| State | Virginia |
| County | Culpeper |
| Transmission Owner | Dominion |
| MFO | 75.0 MW |
| MWE | 75.0 MW |
| MWC | 32.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-538 "Remington-Gordonsville 230 kV" will interconnect with the Dominion transmission system. The primary POI is a direct connect to the new substation to be constructed for the AE1-153 project.
Summer Peak Analysis
The Queue Project was evaluated as a 75.0 MW (Capacity 32.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line
957430 to 314232 ckt 1 |
313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1
CONTINGENCY '313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1' /* Auto-generated /* 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 END |
Single | AC | 101.29 % | 103.17 % | 749.18 | B | 772.93 | 14.49 | |
| DVP |
AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line
957430 to 314232 ckt 1 |
DVP_P1-2: LN 9016
CONTINGENCY 'DVP_P1-2: LN 9016' OPEN BRANCH FROM BUS 313897 TO BUS 314080 CKT 1 /*6LUCKYHILL 230.0 - 6REMNGTN 230.0 END |
Single | AC | 99.67 % | 101.55 % | 749.18 | B | 760.8 | 14.49 | |
| DVP |
AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line
941850 to 314037 ckt 1 |
DVP_P1-2: LN 539
CONTINGENCY 'DVP_P1-2: LN 539' OPEN BRANCH FROM BUS 314900 TO BUS 314919 CKT 1 /*8BRISTER 500.0 - 8OX 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 END |
Single | AC | 99.68 % | 100.22 % | 984.18 | B | 986.31 | 5.32 | |
| DVP |
6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line
314085 to 314110 ckt 1 |
DVP_P1-2: LN 545
CONTINGENCY 'DVP_P1-2: LN 545' OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER 500.0 - 8MORRSVL 500.0 SET POSTCONTRATING 2598 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 SET PRECONTRATING 2552 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER 500.0 - 8CHANCE 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL 500.0 - 8SPOTSYL 500.0 END |
Single | AC | 99.65 % | 100.2 % | 984.18 | B | 986.15 | 5.52 | |
| DVP |
6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line
314099 to 314085 ckt 1 |
DVP_P4-2: 207762
CONTINGENCY 'DVP_P4-2: 207762' OPEN BRANCH FROM BUS 314078 TO BUS 314080 CKT 1 /*3REMNGTN 115.0 - 6REMNGTN 230.0 OPEN BRANCH FROM BUS 314080 TO BUS 314085 CKT 1 /*6REMNGTN 230.0 - 6REMNGCT 230.0 OPEN BRANCH FROM BUS 314085 TO BUS 315021 CKT 1 /*6REMNGCT 230.0 - 1REMNGT1 18.0 OPEN BRANCH FROM BUS 314085 TO BUS 315022 CKT 1 /*6REMNGCT 230.0 - 1REMNGT2 18.0 OPEN BUS 315021 /*1REMNGT1 18.0 OPEN BUS 315022 /*1REMNGT2 18.0 END |
Breaker | AC | 107.73 % | 109.33 % | 699.0 | C | 764.22 | 11.32 | |
| DVP |
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1 |
DVP_P4-2: H2T553
CONTINGENCY 'DVP_P4-2: H2T553' OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 2 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 END |
Breaker | AC | 100.84 % | 102.69 % | 674.0 | C | 692.16 | 13.08 | |
| DVP |
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1 |
DVP_P4-2: H1T553
CONTINGENCY 'DVP_P4-2: H1T553' OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1 /*6ELMONT 230.0 - 8ELMONT 500.0 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 END |
Breaker | AC | 100.84 % | 102.69 % | 674.0 | C | 692.16 | 13.08 | |
| DVP |
AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line
941850 to 314037 ckt 1 |
DVP_P4-2: H2T569
CONTINGENCY 'DVP_P4-2: H2T569' OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 2 /*6MORRSVL 230.0 - 8MORRSVL 500.0 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 END |
Breaker | AC | 100.17 % | 101.33 % | 1204.0 | C | 1219.98 | 16.31 | |
| DVP |
AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line
941850 to 314037 ckt 1 |
DVP_P4-2: H1T539
CONTINGENCY 'DVP_P4-2: H1T539' OPEN BRANCH FROM BUS 314130 TO BUS 314156 CKT 1 /*6BRISTER 230.0 - 3BRISTER 115.0 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 1 /*6BRISTER 230.0 - 8BRISTER 500.0 OPEN BRANCH FROM BUS 314900 TO BUS 314919 CKT 1 /*8BRISTER 500.0 - 8OX 500.0 END |
Breaker | AC | 100.24 % | 101.15 % | 1204.0 | C | 1217.89 | 12.63 | |
| DVP |
AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line
941850 to 314037 ckt 1 |
DVP_P7-1: LN 2039-2040
CONTINGENCY 'DVP_P7-1: LN 2039-2040' OPEN BRANCH FROM BUS 314063 TO BUS 314099 CKT 1 /*6MORRSVL 230.0 - 6GI1MRUN 230.0 OPEN BRANCH FROM BUS 314063 TO BUS 314099 CKT 2 /*6MORRSVL 230.0 - 6GI1MRUN 230.0 END |
Tower | AC | 112.82 % | 115.26 % | 1204.0 | C | 1387.77 | 34.36 | |
| DVP |
6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line
314085 to 314110 ckt 1 |
DVP_P7-1: LN 2039-2040
CONTINGENCY 'DVP_P7-1: LN 2039-2040' OPEN BRANCH FROM BUS 314063 TO BUS 314099 CKT 1 /*6MORRSVL 230.0 - 6GI1MRUN 230.0 OPEN BRANCH FROM BUS 314063 TO BUS 314099 CKT 2 /*6MORRSVL 230.0 - 6GI1MRUN 230.0 END |
Tower | AC | 108.26 % | 110.71 % | 1204.0 | C | 1332.92 | 34.36 | |
| DVP |
6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line
314110 to 941850 ckt 1 |
DVP_P7-1: LN 2039-2040
CONTINGENCY 'DVP_P7-1: LN 2039-2040' OPEN BRANCH FROM BUS 314063 TO BUS 314099 CKT 1 /*6MORRSVL 230.0 - 6GI1MRUN 230.0 OPEN BRANCH FROM BUS 314063 TO BUS 314099 CKT 2 /*6MORRSVL 230.0 - 6GI1MRUN 230.0 END |
Tower | AC | 107.92 % | 110.36 % | 1204.0 | C | 1328.76 | 34.36 | |
| DVP |
AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line
941850 to 314037 ckt 1 |
DVP_P7-1: LN 569-2101
CONTINGENCY 'DVP_P7-1: LN 569-2101' OPEN BRANCH FROM BUS 313716 TO BUS 314119 CKT 1 /*6VINTHIL_DP 230.0 - 6NOKESVL 230.0 OPEN BRANCH FROM BUS 313716 TO BUS 314125 CKT 1 /*6VINTHIL_DP 230.0 - 6VINTHIL 230.0 OPEN BRANCH FROM BUS 314119 TO BUS 314130 CKT 1 /*6NOKESVL 230.0 - 6BRISTER 230.0 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 OPEN BUS 313716 /*6VINTHIL_DP 230.0 OPEN BUS 314119 /*6NOKESVL 230.0 END |
Tower | AC | 103.2 % | 104.06 % | 1204.0 | C | 1252.82 | 13.14 | |
| DVP |
6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line
314085 to 314110 ckt 1 |
DVP_P7-1: LN 569-2101
CONTINGENCY 'DVP_P7-1: LN 569-2101' OPEN BRANCH FROM BUS 313716 TO BUS 314119 CKT 1 /*6VINTHIL_DP 230.0 - 6NOKESVL 230.0 OPEN BRANCH FROM BUS 313716 TO BUS 314125 CKT 1 /*6VINTHIL_DP 230.0 - 6VINTHIL 230.0 OPEN BRANCH FROM BUS 314119 TO BUS 314130 CKT 1 /*6NOKESVL 230.0 - 6BRISTER 230.0 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 OPEN BUS 313716 /*6VINTHIL_DP 230.0 OPEN BUS 314119 /*6NOKESVL 230.0 END |
Tower | AC | 100.99 % | 101.93 % | 1204.0 | C | 1227.21 | 13.14 | |
| DVP |
6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line
314110 to 941850 ckt 1 |
DVP_P7-1: LN 569-2101
CONTINGENCY 'DVP_P7-1: LN 569-2101' OPEN BRANCH FROM BUS 313716 TO BUS 314119 CKT 1 /*6VINTHIL_DP 230.0 - 6NOKESVL 230.0 OPEN BRANCH FROM BUS 313716 TO BUS 314125 CKT 1 /*6VINTHIL_DP 230.0 - 6VINTHIL 230.0 OPEN BRANCH FROM BUS 314119 TO BUS 314130 CKT 1 /*6NOKESVL 230.0 - 6BRISTER 230.0 OPEN BRANCH FROM BUS 314913 TO BUS 314916 CKT 1 /*8LOUDOUN 500.0 - 8MORRSVL 500.0 OPEN BUS 313716 /*6VINTHIL_DP 230.0 OPEN BUS 314119 /*6NOKESVL 230.0 END |
Tower | AC | 100.64 % | 101.58 % | 1204.0 | C | 1223.06 | 13.14 | |
| Details for AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 0.61 MW | 0.61 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 963471 | AG1-196 O1 | 80/20 | 7.71 MW | 7.71 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 965581 | AG1-426 | 80/20 | 0.95 MW | 0.95 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 0.61 MW | 0.61 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 4.99 MW | 4.99 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 5.6 MW | 5.6 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 7.38 MW | 7.38 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 1.69 MW | 1.69 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 7.0 MW | 7.0 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.12 MW | 0.12 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 926001 | AC1-076 C | 80/20 | 2.08 MW | 2.08 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 926481 | AC1-120 C O1 | 80/20 | 5.58 MW | 5.58 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 926501 | AC1-121 C O1 | 80/20 | 1.92 MW | 1.92 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 934861 | AD1-115 C | 80/20 | 1.96 MW | 1.96 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 966671 | AG1-537 C | 80/20 | 2.1 MW | 2.1 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 966681 | AG1-538 C | 80/20 | 14.49 MW | 14.49 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315172 | 1LOISA A | 80/20 | 6.08 MW | 6.08 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315173 | 1LOISA B | 80/20 | 6.11 MW | 6.11 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315174 | 1LOISA C | 80/20 | 6.11 MW | 6.11 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315175 | 1LOISA D | 80/20 | 6.11 MW | 6.11 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315176 | 1LOISA E | 80/20 | 12.46 MW | 12.46 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315177 | 1S ANNAG1 | 80/20 | 4.41 MW | 4.41 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315178 | 1S ANNAS1 | 80/20 | 2.27 MW | 2.27 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315179 | 1S ANNAG2 | 80/20 | 4.41 MW | 4.41 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315180 | 1S ANNAS2 | 80/20 | 2.27 MW | 2.27 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 2.25 MW | 2.25 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 2.25 MW | 2.25 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 2.91 MW | 2.91 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 925021 | AB2-158 C | 80/20 | 6.77 MW | 6.77 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 932854 | AC2-112 C | 80/20 | 6.77 MW | 6.77 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 938625 | AE1-084 C | 80/20 | 3.27 MW | 3.27 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 939225 | AE1-153 C | 80/20 | 40.5 MW | 40.5 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 941381 | AE2-134 | 80/20 | 1.43 MW | 1.43 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 946371 | AF1-301 C | 80/20 | 46.2 MW | 46.2 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 957431 | AF2-037 C | 80/20 | 41.9 MW | 41.9 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 957691 | AF2-063 C | 80/20 | 66.86 MW | 66.86 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 964421 | AG1-305 C O2 | 80/20 | 52.6 MW | 52.6 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 966001 | AG1-469 C | 80/20 | 3.88 MW | 3.88 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 925671 | AC1-043 C | 80/20 | 3.91 MW | 3.91 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 966331 | AG1-502 C | 80/20 | 9.23 MW | 9.23 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | 966341 | AG1-503 C | 80/20 | 2.31 MW | 2.31 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.08 MW | 0.08 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.97 MW | 3.97 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.14 MW | 7.14 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.99 MW | 4.99 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.12 MW | 0.12 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.97 MW | 0.97 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.86 MW | 0.86 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.82 MW | 0.82 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o 313897 6LUCKYHILL 230 939220 AE1-153 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
| Details for AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 961801 | AG1-022 C | 80/20 | 0.61 MW | 0.61 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 963471 | AG1-196 O1 | 80/20 | 7.71 MW | 7.71 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 964231 | AG1-284 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 965581 | AG1-426 | 80/20 | 0.95 MW | 0.95 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 960111 | AF2-302 C | 80/20 | 0.61 MW | 0.61 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 938821 | AE1-108 C O1 | 80/20 | 4.99 MW | 4.99 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 941011 | AE2-092 C | 80/20 | 5.6 MW | 5.6 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 946291 | AF1-293 C O1 | 80/20 | 7.38 MW | 7.38 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 946591 | AF1-323 C | 80/20 | 1.69 MW | 1.69 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 961061 | AF2-397 C | 80/20 | 7.0 MW | 7.0 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 314677 | 6BUCKING | 80/20 | 0.12 MW | 0.12 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 926001 | AC1-076 C | 80/20 | 2.08 MW | 2.08 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 926481 | AC1-120 C O1 | 80/20 | 5.58 MW | 5.58 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 926501 | AC1-121 C O1 | 80/20 | 1.92 MW | 1.92 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 934861 | AD1-115 C | 80/20 | 1.96 MW | 1.96 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 966671 | AG1-537 C | 80/20 | 2.1 MW | 2.1 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 966681 | AG1-538 C | 80/20 | 14.49 MW | 14.49 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315172 | 1LOISA A | 80/20 | 6.08 MW | 6.08 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315173 | 1LOISA B | 80/20 | 6.11 MW | 6.11 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315174 | 1LOISA C | 80/20 | 6.11 MW | 6.11 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315175 | 1LOISA D | 80/20 | 6.11 MW | 6.11 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315176 | 1LOISA E | 80/20 | 12.46 MW | 12.46 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315177 | 1S ANNAG1 | 80/20 | 4.41 MW | 4.41 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315178 | 1S ANNAS1 | 80/20 | 2.27 MW | 2.27 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315179 | 1S ANNAG2 | 80/20 | 4.41 MW | 4.41 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315180 | 1S ANNAS2 | 80/20 | 2.27 MW | 2.27 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315191 | 1BEARGRDN G1 | 80/20 | 2.25 MW | 2.25 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315192 | 1BEARGRDN G2 | 80/20 | 2.25 MW | 2.25 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 315193 | 1BEARGRDN S1 | 80/20 | 2.91 MW | 2.91 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 925021 | AB2-158 C | 80/20 | 6.77 MW | 6.77 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 932854 | AC2-112 C | 80/20 | 6.77 MW | 6.77 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 938625 | AE1-084 C | 80/20 | 3.27 MW | 3.27 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 939225 | AE1-153 C | 80/20 | 40.5 MW | 40.5 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 941381 | AE2-134 | 80/20 | 1.43 MW | 1.43 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 946371 | AF1-301 C | 80/20 | 46.2 MW | 46.2 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 957431 | AF2-037 C | 80/20 | 41.9 MW | 41.9 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 957691 | AF2-063 C | 80/20 | 66.86 MW | 66.86 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 964421 | AG1-305 C O2 | 80/20 | 52.6 MW | 52.6 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 966001 | AG1-469 C | 80/20 | 3.88 MW | 3.88 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 925671 | AC1-043 C | 80/20 | 3.91 MW | 3.91 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 966331 | AG1-502 C | 80/20 | 9.23 MW | 9.23 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | 966341 | AG1-503 C | 80/20 | 2.31 MW | 2.31 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.08 MW | 0.08 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.97 MW | 3.97 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.14 MW | 7.14 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.99 MW | 4.99 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.12 MW | 0.12 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.97 MW | 0.97 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.86 MW | 0.86 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.82 MW | 0.82 MW |
| AF2-037 TAP-6NO ANNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 9016 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
| Details for AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 314078 | 3REMNGTN | 80/20 | 0.26 MW | 0.26 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315021 | 1REMNGT1 | 80/20 | 5.58 MW | 5.58 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315022 | 1REMNGT2 | 80/20 | 5.66 MW | 5.66 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315023 | 1REMNGT3 | 80/20 | 5.68 MW | 5.68 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315024 | 1REMNGT4 | 80/20 | 5.66 MW | 5.66 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315028 | 1M RUN A | 80/20 | 5.5 MW | 5.5 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315029 | 1M RUN B | 80/20 | 5.45 MW | 5.45 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315030 | 1M RUN C | 80/20 | 5.5 MW | 5.5 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 926001 | AC1-076 C | 80/20 | 1.87 MW | 1.87 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 926481 | AC1-120 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 926501 | AC1-121 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 926611 | AC1-143 C O1 | 80/20 | 7.58 MW | 7.58 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 934861 | AD1-115 C | 80/20 | 2.47 MW | 2.47 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 966681 | AG1-538 C | 80/20 | 5.32 MW | 5.32 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315172 | 1LOISA A | 80/20 | 1.2 MW | 1.2 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315173 | 1LOISA B | 80/20 | 1.2 MW | 1.2 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315174 | 1LOISA C | 80/20 | 1.2 MW | 1.2 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315175 | 1LOISA D | 80/20 | 1.2 MW | 1.2 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315176 | 1LOISA E | 80/20 | 2.45 MW | 2.45 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315177 | 1S ANNAG1 | 80/20 | 0.82 MW | 0.82 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315178 | 1S ANNAS1 | 80/20 | 0.42 MW | 0.42 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315179 | 1S ANNAG2 | 80/20 | 0.82 MW | 0.82 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 315180 | 1S ANNAS2 | 80/20 | 0.42 MW | 0.42 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 925021 | AB2-158 C | 80/20 | 0.7 MW | 0.7 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 938291 | AE1-044 C O1 | 80/20 | 17.4 MW | 17.4 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 938295 | AE1-044 C | 80/20 | 17.43 MW | 17.43 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 939225 | AE1-153 C | 80/20 | 14.87 MW | 14.87 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 941361 | AE2-132 | 80/20 | 0.66 MW | 0.66 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 941381 | AE2-134 | 80/20 | 1.29 MW | 1.29 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 946371 | AF1-301 C | 80/20 | 4.65 MW | 4.65 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 957431 | AF2-037 C | 80/20 | 3.16 MW | 3.16 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 957691 | AF2-063 C | 80/20 | 5.05 MW | 5.05 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 961901 | AG1-031 C | 80/20 | 2.73 MW | 2.73 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 963031 | AG1-152 C | 80/20 | 8.76 MW | 8.76 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 964271 | AG1-288 C | 80/20 | 5.54 MW | 5.54 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 964281 | AG1-289 | 80/20 | 3.06 MW | 3.06 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 964421 | AG1-305 C O2 | 80/20 | 3.97 MW | 3.97 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 966001 | AG1-469 C | 80/20 | 0.87 MW | 0.87 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 925671 | AC1-043 C | 80/20 | 4.94 MW | 4.94 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 941851 | AE2-190 C | 80/20 | 8.8 MW | 8.8 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 966331 | AG1-502 C | 80/20 | 6.42 MW | 6.42 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | 966341 | AG1-503 C | 80/20 | 1.6 MW | 1.6 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.68 MW | 0.68 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.31 MW | 0.31 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.65 MW | 13.65 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.47 MW | 7.47 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.66 MW | 6.66 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.03 MW | 1.03 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.46 MW | 1.46 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.38 MW | 0.38 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.0 MW | 1.0 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.2 MW | 1.2 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 539 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.18 MW | 0.18 MW |
| Details for 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 314078 | 3REMNGTN | 80/20 | 0.27 MW | 0.27 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315021 | 1REMNGT1 | 80/20 | 5.83 MW | 5.83 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315022 | 1REMNGT2 | 80/20 | 5.91 MW | 5.91 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315023 | 1REMNGT3 | 80/20 | 5.94 MW | 5.94 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315024 | 1REMNGT4 | 80/20 | 5.91 MW | 5.91 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315028 | 1M RUN A | 80/20 | 5.78 MW | 5.78 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315029 | 1M RUN B | 80/20 | 5.73 MW | 5.73 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315030 | 1M RUN C | 80/20 | 5.78 MW | 5.78 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 926001 | AC1-076 C | 80/20 | 1.78 MW | 1.78 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 926481 | AC1-120 C O1 | 80/20 | 4.04 MW | 4.04 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 926501 | AC1-121 C O1 | 80/20 | 1.39 MW | 1.39 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 926611 | AC1-143 C O1 | 80/20 | 7.87 MW | 7.87 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 934861 | AD1-115 C | 80/20 | 2.51 MW | 2.51 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 966681 | AG1-538 C | 80/20 | 5.52 MW | 5.52 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315172 | 1LOISA A | 80/20 | 1.2 MW | 1.2 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315173 | 1LOISA B | 80/20 | 1.21 MW | 1.21 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315174 | 1LOISA C | 80/20 | 1.21 MW | 1.21 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315175 | 1LOISA D | 80/20 | 1.21 MW | 1.21 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315176 | 1LOISA E | 80/20 | 2.46 MW | 2.46 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315177 | 1S ANNAG1 | 80/20 | 0.82 MW | 0.82 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315178 | 1S ANNAS1 | 80/20 | 0.42 MW | 0.42 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315179 | 1S ANNAG2 | 80/20 | 0.82 MW | 0.82 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 315180 | 1S ANNAS2 | 80/20 | 0.42 MW | 0.42 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 925021 | AB2-158 C | 80/20 | 0.68 MW | 0.68 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 938291 | AE1-044 C O1 | 80/20 | 18.75 MW | 18.75 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 938295 | AE1-044 C | 80/20 | 18.79 MW | 18.79 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 939225 | AE1-153 C | 80/20 | 15.43 MW | 15.43 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 941361 | AE2-132 | 80/20 | 0.69 MW | 0.69 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 941381 | AE2-134 | 80/20 | 1.23 MW | 1.23 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 946371 | AF1-301 C | 80/20 | 4.51 MW | 4.51 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 957431 | AF2-037 C | 80/20 | 2.99 MW | 2.99 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 957691 | AF2-063 C | 80/20 | 4.78 MW | 4.78 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 963031 | AG1-152 C | 80/20 | 9.15 MW | 9.15 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 964271 | AG1-288 C | 80/20 | 4.97 MW | 4.97 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 964281 | AG1-289 | 80/20 | 2.75 MW | 2.75 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 964421 | AG1-305 C O2 | 80/20 | 3.76 MW | 3.76 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 966001 | AG1-469 C | 80/20 | 0.88 MW | 0.88 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 925671 | AC1-043 C | 80/20 | 5.01 MW | 5.01 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 966331 | AG1-502 C | 80/20 | 6.37 MW | 6.37 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | 966341 | AG1-503 C | 80/20 | 1.59 MW | 1.59 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.5 MW | 0.5 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.26 MW | 0.26 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.42 MW | 10.42 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.01 MW | 7.01 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.77 MW | 5.77 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.76 MW | 0.76 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.23 MW | 1.23 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.9 MW | 0.9 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.6 MW | 0.6 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 545 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
| Details for 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 315028 | 1M RUN A | 50/50 | 5.83 MW | 5.83 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 315029 | 1M RUN B | 50/50 | 5.78 MW | 5.78 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 315030 | 1M RUN C | 50/50 | 5.83 MW | 5.83 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 926001 | AC1-076 C | Adder | -1.99 MW | -1.69 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 966681 | AG1-538 C | 50/50 | 4.83 MW | 4.83 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 966682 | AG1-538 E | 50/50 | 6.49 MW | 6.49 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 938291 | AE1-044 C O1 | 50/50 | 18.2 MW | 18.2 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 938292 | AE1-044 E O1 | 50/50 | 14.36 MW | 14.36 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 938295 | AE1-044 C | 50/50 | 18.23 MW | 18.23 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 938296 | AE1-044 E | 50/50 | 14.32 MW | 14.32 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 939225 | AE1-153 C | 50/50 | 13.5 MW | 13.5 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 939226 | AE1-153 E | 50/50 | 9.0 MW | 9.0 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 941381 | AE2-134 | Adder | -1.37 MW | -1.17 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 963033 | AG1-152 BAT | 50/50 | 74.07 MW | 74.07 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 966343 | AG1-503 BAT | 50/50 | 1.34 MW | 1.34 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | 966333 | AG1-502 BAT | 50/50 | 5.37 MW | 5.37 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.52 MW | 0.52 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.26 MW | 0.26 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.62 MW | 10.62 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.25 MW | 7.25 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.86 MW | 5.86 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.79 MW | 0.79 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.87 MW | 0.87 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.25 MW | 1.25 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.92 MW | 0.92 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.5 MW | 5.5 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.01 MW | 1.01 MW |
| 6GI1MRUN-6REMNGCT 230.0 kV Ckt 1 line l/o DVP_P4-2: 207762 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
| Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 961801 | AG1-022 C | Adder | 1.12 MW | 0.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 961802 | AG1-022 E | Adder | 0.75 MW | 0.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 963021 | AG1-151 O1 | Adder | 8.16 MW | 6.94 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 963471 | AG1-196 O1 | 50/50 | 16.03 MW | 16.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 964231 | AG1-284 C O1 | 50/50 | 5.01 MW | 5.01 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 964232 | AG1-284 E O1 | 50/50 | 3.34 MW | 3.34 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 964831 | AG1-346 C | Adder | 0.76 MW | 0.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 964832 | AG1-346 E | Adder | 0.51 MW | 0.43 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 965581 | AG1-426 | 50/50 | 1.7 MW | 1.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 946592 | AF1-323 E | Adder | 2.05 MW | 1.75 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 960111 | AF2-302 C | Adder | 1.12 MW | 0.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 960112 | AF2-302 E | Adder | 0.75 MW | 0.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 938821 | AE1-108 C O1 | 50/50 | 8.98 MW | 8.98 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 938822 | AE1-108 E O1 | 50/50 | 5.99 MW | 5.99 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 941011 | AE2-092 C | 50/50 | 10.13 MW | 10.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 941012 | AE2-092 E | 50/50 | 6.75 MW | 6.75 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 946291 | AF1-293 C O1 | 50/50 | 13.07 MW | 13.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 946292 | AF1-293 E O1 | 50/50 | 2.35 MW | 2.35 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 946591 | AF1-323 C | Adder | 3.08 MW | 2.62 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 958131 | AF2-107 C | Adder | 2.05 MW | 1.74 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 958132 | AF2-107 E | Adder | 1.12 MW | 0.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 237093 | AD1-085_E | Adder | 0.54 MW | 0.46 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 314807 | 3MT JACK | Adder | 0.62 MW | 0.52 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 940451 | AE2-029 C | 50/50 | 3.03 MW | 3.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 940452 | AE2-029 E | 50/50 | 2.02 MW | 2.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 943571 | AF1-028 O1 | Adder | 16.32 MW | 13.87 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 924032 | AB2-045 E | Adder | 0.59 MW | 0.5 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 944071 | AF1-075 C O1 | Adder | 4.39 MW | 3.73 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 944072 | AF1-075 E O1 | Adder | 2.65 MW | 2.25 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 961061 | AF2-397 C | 50/50 | 11.84 MW | 11.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 961062 | AF2-397 E | 50/50 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 314859 | 4WSTVACO | Adder | 4.02 MW | 3.42 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 314860 | 4E MILL | Adder | 4.73 MW | 4.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 918232 | AA1-038 E | Adder | 6.31 MW | 5.37 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 926001 | AC1-076 C | Adder | -2.89 MW | -2.46 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 966671 | AG1-537 C | 50/50 | 4.19 MW | 4.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 966672 | AG1-537 E | 50/50 | 5.63 MW | 5.63 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 315191 | 1BEARGRDN G1 | 50/50 | 3.86 MW | 3.86 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 315192 | 1BEARGRDN G2 | 50/50 | 3.86 MW | 3.86 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 315193 | 1BEARGRDN S1 | 50/50 | 4.99 MW | 4.99 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 315616 | AA1-038 C | Adder | 0.96 MW | 0.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 932854 | AC2-112 C | 50/50 | 13.49 MW | 13.49 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 938625 | AE1-084 C | 50/50 | 6.52 MW | 6.52 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 941381 | AE2-134 | Adder | -1.99 MW | -1.69 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 963461 | AG1-195 | Adder | 14.14 MW | 12.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 965531 | AG1-421 C | 50/50 | 12.9 MW | 12.9 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 965532 | AG1-421 E | 50/50 | 8.6 MW | 8.6 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 965541 | AG1-422 | 50/50 | 5.38 MW | 5.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 966851 | AG1-556 C | Adder | 9.47 MW | 8.05 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 938626 | AE1-084 E | 50/50 | 4.34 MW | 4.34 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 932855 | AC2-112 E | 50/50 | 6.14 MW | 6.14 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 966683 | AG1-538 BAT | 50/50 | 13.08 MW | 13.08 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 963033 | AG1-152 BAT | Adder | 10.23 MW | 8.69 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 966343 | AG1-503 BAT | 50/50 | 1.54 MW | 1.54 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 966333 | AG1-502 BAT | 50/50 | 6.17 MW | 6.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | 964282 | AG1-289 BAT | Adder | 9.51 MW | 8.08 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.48 MW | 0.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.72 MW | 0.72 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.66 MW | 15.66 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 23.87 MW | 23.87 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.44 MW | 16.44 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.72 MW | 0.72 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.6 MW | 1.6 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.23 MW | 3.23 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.17 MW | 1.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.85 MW | 2.85 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.65 MW | 0.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.11 MW | 10.11 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.67 MW | 2.67 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T553 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.56 MW | 0.56 MW |
| Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 961801 | AG1-022 C | Adder | 1.12 MW | 0.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 961802 | AG1-022 E | Adder | 0.75 MW | 0.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 963021 | AG1-151 O1 | Adder | 8.16 MW | 6.94 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 963471 | AG1-196 O1 | 50/50 | 16.03 MW | 16.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 964231 | AG1-284 C O1 | 50/50 | 5.01 MW | 5.01 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 964232 | AG1-284 E O1 | 50/50 | 3.34 MW | 3.34 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 964831 | AG1-346 C | Adder | 0.76 MW | 0.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 964832 | AG1-346 E | Adder | 0.51 MW | 0.43 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 965581 | AG1-426 | 50/50 | 1.7 MW | 1.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 946592 | AF1-323 E | Adder | 2.05 MW | 1.75 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 960111 | AF2-302 C | Adder | 1.12 MW | 0.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 960112 | AF2-302 E | Adder | 0.75 MW | 0.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 938821 | AE1-108 C O1 | 50/50 | 8.98 MW | 8.98 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 938822 | AE1-108 E O1 | 50/50 | 5.99 MW | 5.99 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 941011 | AE2-092 C | 50/50 | 10.13 MW | 10.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 941012 | AE2-092 E | 50/50 | 6.75 MW | 6.75 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 946291 | AF1-293 C O1 | 50/50 | 13.07 MW | 13.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 946292 | AF1-293 E O1 | 50/50 | 2.35 MW | 2.35 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 946591 | AF1-323 C | Adder | 3.08 MW | 2.62 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 958131 | AF2-107 C | Adder | 2.05 MW | 1.74 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 958132 | AF2-107 E | Adder | 1.12 MW | 0.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 237093 | AD1-085_E | Adder | 0.54 MW | 0.46 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 314807 | 3MT JACK | Adder | 0.62 MW | 0.52 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 940451 | AE2-029 C | 50/50 | 3.03 MW | 3.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 940452 | AE2-029 E | 50/50 | 2.02 MW | 2.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 943571 | AF1-028 O1 | Adder | 16.32 MW | 13.87 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 924032 | AB2-045 E | Adder | 0.59 MW | 0.5 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 944071 | AF1-075 C O1 | Adder | 4.39 MW | 3.73 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 944072 | AF1-075 E O1 | Adder | 2.65 MW | 2.25 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 961061 | AF2-397 C | 50/50 | 11.84 MW | 11.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 961062 | AF2-397 E | 50/50 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 314859 | 4WSTVACO | Adder | 4.02 MW | 3.42 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 314860 | 4E MILL | Adder | 4.73 MW | 4.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 918232 | AA1-038 E | Adder | 6.31 MW | 5.37 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 926001 | AC1-076 C | Adder | -2.89 MW | -2.46 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 966671 | AG1-537 C | 50/50 | 4.19 MW | 4.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 966672 | AG1-537 E | 50/50 | 5.63 MW | 5.63 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 315191 | 1BEARGRDN G1 | 50/50 | 3.86 MW | 3.86 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 315192 | 1BEARGRDN G2 | 50/50 | 3.86 MW | 3.86 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 315193 | 1BEARGRDN S1 | 50/50 | 4.99 MW | 4.99 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 315616 | AA1-038 C | Adder | 0.96 MW | 0.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 932854 | AC2-112 C | 50/50 | 13.49 MW | 13.49 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 938625 | AE1-084 C | 50/50 | 6.52 MW | 6.52 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 941381 | AE2-134 | Adder | -1.99 MW | -1.69 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 963461 | AG1-195 | Adder | 14.14 MW | 12.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 965531 | AG1-421 C | 50/50 | 12.9 MW | 12.9 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 965532 | AG1-421 E | 50/50 | 8.6 MW | 8.6 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 965541 | AG1-422 | 50/50 | 5.38 MW | 5.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 966851 | AG1-556 C | Adder | 9.47 MW | 8.05 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 938626 | AE1-084 E | 50/50 | 4.34 MW | 4.34 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 932855 | AC2-112 E | 50/50 | 6.14 MW | 6.14 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 966683 | AG1-538 BAT | 50/50 | 13.08 MW | 13.08 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 963033 | AG1-152 BAT | Adder | 10.23 MW | 8.69 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 966343 | AG1-503 BAT | 50/50 | 1.54 MW | 1.54 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 966333 | AG1-502 BAT | 50/50 | 6.17 MW | 6.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | 964282 | AG1-289 BAT | Adder | 9.51 MW | 8.08 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.48 MW | 0.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.72 MW | 0.72 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.66 MW | 15.66 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 23.87 MW | 23.87 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.44 MW | 16.44 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.72 MW | 0.72 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.6 MW | 1.6 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.23 MW | 3.23 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.17 MW | 1.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.85 MW | 2.85 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.65 MW | 0.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.11 MW | 10.11 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.67 MW | 2.67 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T553 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.56 MW | 0.56 MW |
| Details for AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 315021 | 1REMNGT1 | 50/50 | 7.28 MW | 7.28 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 315022 | 1REMNGT2 | 50/50 | 7.37 MW | 7.37 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 315023 | 1REMNGT3 | 50/50 | 7.4 MW | 7.4 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 315024 | 1REMNGT4 | 50/50 | 7.37 MW | 7.37 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 315028 | 1M RUN A | 50/50 | 7.4 MW | 7.4 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 315030 | 1M RUN C | 50/50 | 7.4 MW | 7.4 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 926001 | AC1-076 C | Adder | 2.31 MW | 1.97 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 926002 | AC1-076 E | Adder | 2.16 MW | 1.83 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 926481 | AC1-120 C O1 | Adder | 5.16 MW | 4.39 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 926482 | AC1-120 E O1 | Adder | 2.66 MW | 2.26 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 926501 | AC1-121 C O1 | Adder | 1.77 MW | 1.51 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 926502 | AC1-121 E O1 | Adder | 0.83 MW | 0.71 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 926611 | AC1-143 C O1 | Adder | 9.88 MW | 8.4 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 926612 | AC1-143 E O1 | Adder | 4.51 MW | 3.83 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 934861 | AD1-115 C | Adder | 3.18 MW | 2.7 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 934862 | AD1-115 E | Adder | 5.18 MW | 4.41 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 966681 | AG1-538 C | Adder | 6.96 MW | 5.92 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 966682 | AG1-538 E | Adder | 9.35 MW | 7.95 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 923892 | AB2-029 E | Adder | 3.16 MW | 2.68 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 925022 | AB2-158 E | Adder | 2.3 MW | 1.96 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 938291 | AE1-044 C O1 | Adder | 25.99 MW | 22.09 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 938292 | AE1-044 E O1 | Adder | 20.5 MW | 17.43 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 938295 | AE1-044 C | Adder | 26.03 MW | 22.13 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 938296 | AE1-044 E | Adder | 20.45 MW | 17.39 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 939225 | AE1-153 C | Adder | 19.44 MW | 16.53 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 939226 | AE1-153 E | Adder | 12.96 MW | 11.02 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 941361 | AE2-132 | 50/50 | 0.86 MW | 0.86 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 941381 | AE2-134 | Adder | 1.59 MW | 1.35 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 946371 | AF1-301 C | Adder | 5.82 MW | 4.94 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 946372 | AF1-301 E | Adder | 3.91 MW | 3.32 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 957431 | AF2-037 C | Adder | 3.9 MW | 3.31 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 957432 | AF2-037 E | Adder | 2.6 MW | 2.21 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 957691 | AF2-063 C | Adder | 6.22 MW | 5.28 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 957692 | AF2-063 E | Adder | 4.14 MW | 3.52 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 961901 | AG1-031 C | 50/50 | 3.21 MW | 3.21 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 961902 | AG1-031 E | 50/50 | 4.43 MW | 4.43 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 963031 | AG1-152 C | 50/50 | 11.41 MW | 11.41 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 963032 | AG1-152 E | 50/50 | 17.12 MW | 17.12 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 964271 | AG1-288 C | Adder | 6.61 MW | 5.62 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 964281 | AG1-289 | Adder | 3.65 MW | 3.1 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 964421 | AG1-305 C O2 | Adder | 4.89 MW | 4.16 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 964422 | AG1-305 E O2 | Adder | 3.26 MW | 2.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 966001 | AG1-469 C | Adder | 1.12 MW | 0.95 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 966002 | AG1-469 E | Adder | 0.56 MW | 0.47 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 925671 | AC1-043 C | Adder | 6.35 MW | 5.4 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 925672 | AC1-043 E | Adder | 10.36 MW | 8.81 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 941851 | AE2-190 C | 50/50 | 10.32 MW | 10.32 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 941852 | AE2-190 E | 50/50 | 16.42 MW | 16.42 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 966331 | AG1-502 C | Adder | 8.14 MW | 6.92 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 966332 | AG1-502 E | Adder | 2.04 MW | 1.73 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 966341 | AG1-503 C | Adder | 2.04 MW | 1.73 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 966342 | AG1-503 E | Adder | 0.51 MW | 0.43 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | 940352 | AE2-019 BAT | Adder | 10.19 MW | 8.66 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.77 MW | 0.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.32 MW | 0.32 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.11 MW | 15.11 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.29 MW | 7.29 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.92 MW | 6.92 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.16 MW | 1.16 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.71 MW | 1.71 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.54 MW | 1.54 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.38 MW | 0.38 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.01 MW | 1.01 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.77 MW | 0.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.86 MW | 10.86 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T569 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.18 MW | 0.18 MW |
| Details for AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 315021 | 1REMNGT1 | 50/50 | 5.6 MW | 5.6 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 315022 | 1REMNGT2 | 50/50 | 5.68 MW | 5.68 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 315023 | 1REMNGT3 | 50/50 | 5.7 MW | 5.7 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 315024 | 1REMNGT4 | 50/50 | 5.68 MW | 5.68 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 315028 | 1M RUN A | 50/50 | 5.54 MW | 5.54 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 315030 | 1M RUN C | 50/50 | 5.54 MW | 5.54 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 926001 | AC1-076 C | Adder | 2.02 MW | 1.71 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 926002 | AC1-076 E | Adder | 1.88 MW | 1.6 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 926481 | AC1-120 C O1 | Adder | 4.26 MW | 3.62 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 926482 | AC1-120 E O1 | Adder | 2.2 MW | 1.87 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 926501 | AC1-121 C O1 | Adder | 1.46 MW | 1.24 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 926502 | AC1-121 E O1 | Adder | 0.69 MW | 0.58 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 926611 | AC1-143 C O1 | Adder | 7.66 MW | 6.51 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 926612 | AC1-143 E O1 | Adder | 3.5 MW | 2.97 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 934861 | AD1-115 C | Adder | 2.54 MW | 2.16 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 934862 | AD1-115 E | Adder | 4.15 MW | 3.53 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 966681 | AG1-538 C | Adder | 5.39 MW | 4.58 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 966682 | AG1-538 E | Adder | 7.24 MW | 6.16 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 923892 | AB2-029 E | Adder | 2.44 MW | 2.07 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 925022 | AB2-158 E | Adder | 1.97 MW | 1.68 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 938291 | AE1-044 C O1 | Adder | 17.82 MW | 15.15 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 938292 | AE1-044 E O1 | Adder | 14.06 MW | 11.95 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 938295 | AE1-044 C | Adder | 17.85 MW | 15.17 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 938296 | AE1-044 E | Adder | 14.03 MW | 11.92 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 939225 | AE1-153 C | Adder | 15.06 MW | 12.8 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 939226 | AE1-153 E | Adder | 10.04 MW | 8.53 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 941361 | AE2-132 | 50/50 | 0.66 MW | 0.66 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 941381 | AE2-134 | Adder | 1.39 MW | 1.18 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 946371 | AF1-301 C | Adder | 5.01 MW | 4.26 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 946372 | AF1-301 E | Adder | 3.36 MW | 2.86 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 957431 | AF2-037 C | Adder | 3.48 MW | 2.96 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 957432 | AF2-037 E | Adder | 2.32 MW | 1.97 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 957691 | AF2-063 C | Adder | 5.56 MW | 4.72 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 957692 | AF2-063 E | Adder | 3.7 MW | 3.15 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 961901 | AG1-031 C | 50/50 | 2.7 MW | 2.7 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 961902 | AG1-031 E | 50/50 | 3.73 MW | 3.73 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 963031 | AG1-152 C | 50/50 | 8.79 MW | 8.79 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 963032 | AG1-152 E | 50/50 | 13.19 MW | 13.19 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 964271 | AG1-288 C | Adder | 6.26 MW | 5.32 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 964281 | AG1-289 | Adder | 3.46 MW | 2.94 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 964421 | AG1-305 C O2 | Adder | 4.37 MW | 3.71 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 964422 | AG1-305 E O2 | Adder | 2.91 MW | 2.48 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 966001 | AG1-469 C | Adder | 0.91 MW | 0.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 966002 | AG1-469 E | Adder | 0.46 MW | 0.39 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 925671 | AC1-043 C | Adder | 5.09 MW | 4.33 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 925672 | AC1-043 E | Adder | 8.31 MW | 7.06 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 941851 | AE2-190 C | 50/50 | 8.69 MW | 8.69 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 941852 | AE2-190 E | 50/50 | 13.82 MW | 13.82 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 966331 | AG1-502 C | Adder | 6.74 MW | 5.73 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 966332 | AG1-502 E | Adder | 1.69 MW | 1.43 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 966341 | AG1-503 C | Adder | 1.69 MW | 1.43 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 966342 | AG1-503 E | Adder | 0.42 MW | 0.36 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 963693 | AG1-221 BAT | Adder | 3.56 MW | 3.03 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | 940352 | AE2-019 BAT | Adder | 11.73 MW | 9.97 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 16.58 MW | 16.58 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.09 MW | 9.09 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.08 MW | 8.08 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.77 MW | 1.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.77 MW | 1.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.46 MW | 0.46 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.22 MW | 1.22 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.78 MW | 0.78 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 11.22 MW | 11.22 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.45 MW | 1.45 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T539 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
| Details for AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315021 | 1REMNGT1 | 50/50 | 15.45 MW | 15.45 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315022 | 1REMNGT2 | 50/50 | 15.66 MW | 15.66 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315023 | 1REMNGT3 | 50/50 | 15.72 MW | 15.72 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315024 | 1REMNGT4 | 50/50 | 15.66 MW | 15.66 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315028 | 1M RUN A | 50/50 | 16.62 MW | 16.62 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315030 | 1M RUN C | 50/50 | 16.62 MW | 16.62 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926001 | AC1-076 C | Adder | 3.82 MW | 3.25 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926002 | AC1-076 E | Adder | 3.56 MW | 3.03 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926481 | AC1-120 C O1 | Adder | 9.63 MW | 8.18 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926482 | AC1-120 E O1 | Adder | 4.96 MW | 4.22 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926501 | AC1-121 C O1 | Adder | 3.31 MW | 2.81 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926502 | AC1-121 E O1 | Adder | 1.56 MW | 1.32 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926611 | AC1-143 C O1 | Adder | 20.76 MW | 17.65 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926612 | AC1-143 E O1 | Adder | 9.47 MW | 8.05 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 934861 | AD1-115 C | Adder | 6.28 MW | 5.34 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 934862 | AD1-115 E | Adder | 10.25 MW | 8.71 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966681 | AG1-538 C | Adder | 14.66 MW | 12.46 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966682 | AG1-538 E | Adder | 19.7 MW | 16.75 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 923892 | AB2-029 E | Adder | 6.7 MW | 5.7 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925022 | AB2-158 E | Adder | 3.84 MW | 3.27 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 939225 | AE1-153 C | Adder | 40.96 MW | 34.81 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 939226 | AE1-153 E | Adder | 27.3 MW | 23.21 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 941361 | AE2-132 | 50/50 | 1.83 MW | 1.83 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 941381 | AE2-134 | Adder | 2.63 MW | 2.24 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 946371 | AF1-301 C | Adder | 9.62 MW | 8.18 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 946372 | AF1-301 E | Adder | 6.46 MW | 5.49 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957431 | AF2-037 C | Adder | 5.76 MW | 4.9 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957432 | AF2-037 E | Adder | 3.84 MW | 3.26 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957691 | AF2-063 C | Adder | 9.19 MW | 7.81 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957692 | AF2-063 E | Adder | 6.13 MW | 5.21 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 961901 | AG1-031 C | 50/50 | 5.53 MW | 5.53 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 961902 | AG1-031 E | 50/50 | 7.63 MW | 7.63 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 963031 | AG1-152 C | 50/50 | 24.24 MW | 24.24 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 963032 | AG1-152 E | 50/50 | 36.36 MW | 36.36 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 964421 | AG1-305 C O2 | Adder | 7.23 MW | 6.15 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 964422 | AG1-305 E O2 | Adder | 4.82 MW | 4.1 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966001 | AG1-469 C | Adder | 2.12 MW | 1.8 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966002 | AG1-469 E | Adder | 1.06 MW | 0.9 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925671 | AC1-043 C | Adder | 12.57 MW | 10.68 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925672 | AC1-043 E | Adder | 20.5 MW | 17.43 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 941851 | AE2-190 C | 50/50 | 17.77 MW | 17.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 941852 | AE2-190 E | 50/50 | 28.27 MW | 28.27 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966331 | AG1-502 C | Adder | 15.08 MW | 12.81 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966332 | AG1-502 E | Adder | 3.77 MW | 3.2 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966341 | AG1-503 C | Adder | 3.77 MW | 3.2 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966342 | AG1-503 E | Adder | 0.94 MW | 0.8 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.48 MW | 0.48 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 9.61 MW | 9.61 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.9 MW | 2.9 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.76 MW | 3.76 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.73 MW | 0.73 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.6 MW | 1.6 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.89 MW | 0.89 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.18 MW | 0.18 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.49 MW | 0.49 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.75 MW | 0.75 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.21 MW | 10.21 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.74 MW | 0.74 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315021 | 1REMNGT1 | 50/50 | 15.45 MW | 15.45 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315022 | 1REMNGT2 | 50/50 | 15.66 MW | 15.66 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315023 | 1REMNGT3 | 50/50 | 15.72 MW | 15.72 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315024 | 1REMNGT4 | 50/50 | 15.66 MW | 15.66 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315028 | 1M RUN A | 50/50 | 16.62 MW | 16.62 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315030 | 1M RUN C | 50/50 | 16.62 MW | 16.62 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926001 | AC1-076 C | Adder | 3.82 MW | 3.25 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926002 | AC1-076 E | Adder | 3.56 MW | 3.03 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926481 | AC1-120 C O1 | Adder | 9.63 MW | 8.18 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926482 | AC1-120 E O1 | Adder | 4.96 MW | 4.22 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926501 | AC1-121 C O1 | Adder | 3.31 MW | 2.81 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926502 | AC1-121 E O1 | Adder | 1.56 MW | 1.32 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926611 | AC1-143 C O1 | Adder | 20.76 MW | 17.65 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926612 | AC1-143 E O1 | Adder | 9.47 MW | 8.05 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 934861 | AD1-115 C | Adder | 6.28 MW | 5.34 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 934862 | AD1-115 E | Adder | 10.25 MW | 8.71 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966681 | AG1-538 C | Adder | 14.66 MW | 12.46 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966682 | AG1-538 E | Adder | 19.7 MW | 16.75 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 923892 | AB2-029 E | Adder | 6.7 MW | 5.7 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925022 | AB2-158 E | Adder | 3.84 MW | 3.27 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 939225 | AE1-153 C | Adder | 40.96 MW | 34.81 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 939226 | AE1-153 E | Adder | 27.3 MW | 23.21 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 941361 | AE2-132 | 50/50 | 1.83 MW | 1.83 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 941381 | AE2-134 | Adder | 2.63 MW | 2.24 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 946371 | AF1-301 C | Adder | 9.62 MW | 8.18 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 946372 | AF1-301 E | Adder | 6.46 MW | 5.49 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957431 | AF2-037 C | Adder | 5.76 MW | 4.9 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957432 | AF2-037 E | Adder | 3.84 MW | 3.26 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957691 | AF2-063 C | Adder | 9.19 MW | 7.81 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957692 | AF2-063 E | Adder | 6.13 MW | 5.21 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 963031 | AG1-152 C | 50/50 | 24.24 MW | 24.24 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 963032 | AG1-152 E | 50/50 | 36.36 MW | 36.36 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 964421 | AG1-305 C O2 | Adder | 7.23 MW | 6.15 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 964422 | AG1-305 E O2 | Adder | 4.82 MW | 4.1 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966001 | AG1-469 C | Adder | 2.12 MW | 1.8 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966002 | AG1-469 E | Adder | 1.06 MW | 0.9 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925671 | AC1-043 C | Adder | 12.57 MW | 10.68 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925672 | AC1-043 E | Adder | 20.5 MW | 17.43 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966331 | AG1-502 C | Adder | 15.08 MW | 12.81 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966332 | AG1-502 E | Adder | 3.77 MW | 3.2 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966341 | AG1-503 C | Adder | 3.77 MW | 3.2 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966342 | AG1-503 E | Adder | 0.94 MW | 0.8 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.48 MW | 0.48 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 9.61 MW | 9.61 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.9 MW | 2.9 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.76 MW | 3.76 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.73 MW | 0.73 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.6 MW | 1.6 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.89 MW | 0.89 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.18 MW | 0.18 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.49 MW | 0.49 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.75 MW | 0.75 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.21 MW | 10.21 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.74 MW | 0.74 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315021 | 1REMNGT1 | 50/50 | 15.45 MW | 15.45 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315022 | 1REMNGT2 | 50/50 | 15.66 MW | 15.66 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315023 | 1REMNGT3 | 50/50 | 15.72 MW | 15.72 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315024 | 1REMNGT4 | 50/50 | 15.66 MW | 15.66 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315028 | 1M RUN A | 50/50 | 16.62 MW | 16.62 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 315030 | 1M RUN C | 50/50 | 16.62 MW | 16.62 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926001 | AC1-076 C | Adder | 3.82 MW | 3.25 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926002 | AC1-076 E | Adder | 3.56 MW | 3.03 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926481 | AC1-120 C O1 | Adder | 9.63 MW | 8.18 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926482 | AC1-120 E O1 | Adder | 4.96 MW | 4.22 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926501 | AC1-121 C O1 | Adder | 3.31 MW | 2.81 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926502 | AC1-121 E O1 | Adder | 1.56 MW | 1.32 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926611 | AC1-143 C O1 | Adder | 20.76 MW | 17.65 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 926612 | AC1-143 E O1 | Adder | 9.47 MW | 8.05 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 934861 | AD1-115 C | Adder | 6.28 MW | 5.34 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 934862 | AD1-115 E | Adder | 10.25 MW | 8.71 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966681 | AG1-538 C | Adder | 14.66 MW | 12.46 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966682 | AG1-538 E | Adder | 19.7 MW | 16.75 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 923892 | AB2-029 E | Adder | 6.7 MW | 5.7 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925022 | AB2-158 E | Adder | 3.84 MW | 3.27 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 939225 | AE1-153 C | Adder | 40.96 MW | 34.81 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 939226 | AE1-153 E | Adder | 27.3 MW | 23.21 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 941361 | AE2-132 | 50/50 | 1.83 MW | 1.83 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 941381 | AE2-134 | Adder | 2.63 MW | 2.24 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 946371 | AF1-301 C | Adder | 9.62 MW | 8.18 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 946372 | AF1-301 E | Adder | 6.46 MW | 5.49 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957431 | AF2-037 C | Adder | 5.76 MW | 4.9 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957432 | AF2-037 E | Adder | 3.84 MW | 3.26 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957691 | AF2-063 C | Adder | 9.19 MW | 7.81 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 957692 | AF2-063 E | Adder | 6.13 MW | 5.21 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 963031 | AG1-152 C | 50/50 | 24.24 MW | 24.24 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 963032 | AG1-152 E | 50/50 | 36.36 MW | 36.36 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 964421 | AG1-305 C O2 | Adder | 7.23 MW | 6.15 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 964422 | AG1-305 E O2 | Adder | 4.82 MW | 4.1 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966001 | AG1-469 C | Adder | 2.12 MW | 1.8 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966002 | AG1-469 E | Adder | 1.06 MW | 0.9 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925671 | AC1-043 C | Adder | 12.57 MW | 10.68 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 925672 | AC1-043 E | Adder | 20.5 MW | 17.43 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966331 | AG1-502 C | Adder | 15.08 MW | 12.81 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966332 | AG1-502 E | Adder | 3.77 MW | 3.2 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966341 | AG1-503 C | Adder | 3.77 MW | 3.2 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | 966342 | AG1-503 E | Adder | 0.94 MW | 0.8 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.48 MW | 0.48 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 9.61 MW | 9.61 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.9 MW | 2.9 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 3.76 MW | 3.76 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.73 MW | 0.73 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.6 MW | 1.6 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.89 MW | 0.89 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.18 MW | 0.18 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.49 MW | 0.49 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.75 MW | 0.75 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.21 MW | 10.21 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.74 MW | 0.74 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2039-2040 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315021 | 1REMNGT1 | 50/50 | 5.8 MW | 5.8 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315022 | 1REMNGT2 | 50/50 | 5.88 MW | 5.88 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315023 | 1REMNGT3 | 50/50 | 5.9 MW | 5.9 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315024 | 1REMNGT4 | 50/50 | 5.88 MW | 5.88 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315028 | 1M RUN A | 50/50 | 5.76 MW | 5.76 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315030 | 1M RUN C | 50/50 | 5.76 MW | 5.76 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926001 | AC1-076 C | Adder | 2.15 MW | 1.83 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926002 | AC1-076 E | Adder | 2.0 MW | 1.7 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926481 | AC1-120 C O1 | Adder | 4.5 MW | 3.82 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926482 | AC1-120 E O1 | Adder | 2.32 MW | 1.97 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926501 | AC1-121 C O1 | Adder | 1.54 MW | 1.31 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926502 | AC1-121 E O1 | Adder | 0.73 MW | 0.62 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926611 | AC1-143 C O1 | Adder | 7.96 MW | 6.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926612 | AC1-143 E O1 | Adder | 3.63 MW | 3.09 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 934861 | AD1-115 C | Adder | 2.67 MW | 2.27 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 934862 | AD1-115 E | Adder | 4.35 MW | 3.7 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966681 | AG1-538 C | Adder | 5.61 MW | 4.77 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966682 | AG1-538 E | Adder | 7.53 MW | 6.4 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 923892 | AB2-029 E | Adder | 2.53 MW | 2.15 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925022 | AB2-158 E | Adder | 2.13 MW | 1.81 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938291 | AE1-044 C O1 | Adder | 18.82 MW | 15.99 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938292 | AE1-044 E O1 | Adder | 14.84 MW | 12.62 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938295 | AE1-044 C | Adder | 18.85 MW | 16.02 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938296 | AE1-044 E | Adder | 14.81 MW | 12.59 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 939225 | AE1-153 C | Adder | 15.66 MW | 13.31 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 939226 | AE1-153 E | Adder | 10.44 MW | 8.88 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 941361 | AE2-132 | 50/50 | 0.69 MW | 0.69 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 941381 | AE2-134 | Adder | 1.48 MW | 1.26 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 946371 | AF1-301 C | Adder | 5.4 MW | 4.59 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 946372 | AF1-301 E | Adder | 3.62 MW | 3.08 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957431 | AF2-037 C | Adder | 3.8 MW | 3.23 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957432 | AF2-037 E | Adder | 2.53 MW | 2.15 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957691 | AF2-063 C | Adder | 6.07 MW | 5.16 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957692 | AF2-063 E | Adder | 4.04 MW | 3.44 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 961901 | AG1-031 C | 50/50 | 2.75 MW | 2.75 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 961902 | AG1-031 E | 50/50 | 3.8 MW | 3.8 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963031 | AG1-152 C | 50/50 | 9.1 MW | 9.1 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963032 | AG1-152 E | 50/50 | 13.64 MW | 13.64 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964271 | AG1-288 C | Adder | 6.78 MW | 5.76 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964281 | AG1-289 | Adder | 3.75 MW | 3.19 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964421 | AG1-305 C O2 | Adder | 4.77 MW | 4.06 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964422 | AG1-305 E O2 | Adder | 3.18 MW | 2.7 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966001 | AG1-469 C | Adder | 0.96 MW | 0.82 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966002 | AG1-469 E | Adder | 0.48 MW | 0.41 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925671 | AC1-043 C | Adder | 5.33 MW | 4.53 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925672 | AC1-043 E | Adder | 8.7 MW | 7.39 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 941851 | AE2-190 C | 50/50 | 8.85 MW | 8.85 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 941852 | AE2-190 E | 50/50 | 14.08 MW | 14.08 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966331 | AG1-502 C | Adder | 7.12 MW | 6.05 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966332 | AG1-502 E | Adder | 1.78 MW | 1.51 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966341 | AG1-503 C | Adder | 1.78 MW | 1.51 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966342 | AG1-503 E | Adder | 0.44 MW | 0.38 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963693 | AG1-221 BAT | Adder | 3.91 MW | 3.32 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 940352 | AE2-019 BAT | Adder | 12.5 MW | 10.62 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.93 MW | 0.93 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.39 MW | 0.39 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.32 MW | 18.32 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.15 MW | 9.15 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.48 MW | 8.48 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.41 MW | 1.41 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.92 MW | 1.92 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.09 MW | 0.09 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.47 MW | 0.47 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.25 MW | 1.25 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.86 MW | 0.86 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.17 MW | 12.17 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.54 MW | 1.54 MW |
| AE2-190 TAP-6GAINSVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
| Details for 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315021 | 1REMNGT1 | 50/50 | 5.8 MW | 5.8 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315022 | 1REMNGT2 | 50/50 | 5.88 MW | 5.88 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315023 | 1REMNGT3 | 50/50 | 5.9 MW | 5.9 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315024 | 1REMNGT4 | 50/50 | 5.88 MW | 5.88 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315028 | 1M RUN A | 50/50 | 5.76 MW | 5.76 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315030 | 1M RUN C | 50/50 | 5.76 MW | 5.76 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926001 | AC1-076 C | Adder | 2.15 MW | 1.83 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926002 | AC1-076 E | Adder | 2.0 MW | 1.7 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926481 | AC1-120 C O1 | Adder | 4.5 MW | 3.82 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926482 | AC1-120 E O1 | Adder | 2.32 MW | 1.97 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926501 | AC1-121 C O1 | Adder | 1.54 MW | 1.31 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926502 | AC1-121 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926611 | AC1-143 C O1 | Adder | 7.96 MW | 6.77 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926612 | AC1-143 E O1 | Adder | 3.63 MW | 3.09 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 934861 | AD1-115 C | Adder | 2.67 MW | 2.27 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 934862 | AD1-115 E | Adder | 4.35 MW | 3.7 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966681 | AG1-538 C | Adder | 5.61 MW | 4.77 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966682 | AG1-538 E | Adder | 7.53 MW | 6.4 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 923892 | AB2-029 E | Adder | 2.53 MW | 2.15 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925022 | AB2-158 E | Adder | 2.13 MW | 1.81 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938291 | AE1-044 C O1 | Adder | 18.82 MW | 15.99 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938292 | AE1-044 E O1 | Adder | 14.84 MW | 12.62 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938295 | AE1-044 C | Adder | 18.85 MW | 16.02 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938296 | AE1-044 E | Adder | 14.81 MW | 12.59 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 939225 | AE1-153 C | Adder | 15.66 MW | 13.31 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 939226 | AE1-153 E | Adder | 10.44 MW | 8.88 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 941361 | AE2-132 | 50/50 | 0.69 MW | 0.69 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 941381 | AE2-134 | Adder | 1.48 MW | 1.26 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 946371 | AF1-301 C | Adder | 5.4 MW | 4.59 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 946372 | AF1-301 E | Adder | 3.62 MW | 3.08 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957431 | AF2-037 C | Adder | 3.8 MW | 3.23 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957432 | AF2-037 E | Adder | 2.53 MW | 2.15 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957691 | AF2-063 C | Adder | 6.07 MW | 5.16 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957692 | AF2-063 E | Adder | 4.04 MW | 3.44 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963031 | AG1-152 C | 50/50 | 9.1 MW | 9.1 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963032 | AG1-152 E | 50/50 | 13.64 MW | 13.64 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964271 | AG1-288 C | Adder | 6.78 MW | 5.76 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964281 | AG1-289 | Adder | 3.75 MW | 3.19 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964421 | AG1-305 C O2 | Adder | 4.77 MW | 4.06 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964422 | AG1-305 E O2 | Adder | 3.18 MW | 2.7 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966001 | AG1-469 C | Adder | 0.96 MW | 0.82 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966002 | AG1-469 E | Adder | 0.48 MW | 0.41 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925671 | AC1-043 C | Adder | 5.33 MW | 4.53 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925672 | AC1-043 E | Adder | 8.7 MW | 7.39 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966331 | AG1-502 C | Adder | 7.12 MW | 6.05 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966332 | AG1-502 E | Adder | 1.78 MW | 1.51 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966341 | AG1-503 C | Adder | 1.78 MW | 1.51 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966342 | AG1-503 E | Adder | 0.44 MW | 0.38 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963693 | AG1-221 BAT | Adder | 3.91 MW | 3.32 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 940352 | AE2-019 BAT | Adder | 12.5 MW | 10.62 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.93 MW | 0.93 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.39 MW | 0.39 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.32 MW | 18.32 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.15 MW | 9.15 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.48 MW | 8.48 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.41 MW | 1.41 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.92 MW | 1.92 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.09 MW | 0.09 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.47 MW | 0.47 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.25 MW | 1.25 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.86 MW | 0.86 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.17 MW | 12.17 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.54 MW | 1.54 MW |
| 6REMNGCT-6ELK RUN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
| Details for 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315021 | 1REMNGT1 | 50/50 | 5.8 MW | 5.8 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315022 | 1REMNGT2 | 50/50 | 5.88 MW | 5.88 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315023 | 1REMNGT3 | 50/50 | 5.9 MW | 5.9 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315024 | 1REMNGT4 | 50/50 | 5.88 MW | 5.88 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315028 | 1M RUN A | 50/50 | 5.76 MW | 5.76 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 315030 | 1M RUN C | 50/50 | 5.76 MW | 5.76 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926001 | AC1-076 C | Adder | 2.15 MW | 1.83 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926002 | AC1-076 E | Adder | 2.0 MW | 1.7 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926481 | AC1-120 C O1 | Adder | 4.5 MW | 3.82 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926482 | AC1-120 E O1 | Adder | 2.32 MW | 1.97 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926501 | AC1-121 C O1 | Adder | 1.54 MW | 1.31 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926502 | AC1-121 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926611 | AC1-143 C O1 | Adder | 7.96 MW | 6.77 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 926612 | AC1-143 E O1 | Adder | 3.63 MW | 3.09 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 934861 | AD1-115 C | Adder | 2.67 MW | 2.27 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 934862 | AD1-115 E | Adder | 4.35 MW | 3.7 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966681 | AG1-538 C | Adder | 5.61 MW | 4.77 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966682 | AG1-538 E | Adder | 7.53 MW | 6.4 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 923892 | AB2-029 E | Adder | 2.53 MW | 2.15 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925022 | AB2-158 E | Adder | 2.13 MW | 1.81 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938291 | AE1-044 C O1 | Adder | 18.82 MW | 15.99 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938292 | AE1-044 E O1 | Adder | 14.84 MW | 12.62 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938295 | AE1-044 C | Adder | 18.85 MW | 16.02 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 938296 | AE1-044 E | Adder | 14.81 MW | 12.59 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 939225 | AE1-153 C | Adder | 15.66 MW | 13.31 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 939226 | AE1-153 E | Adder | 10.44 MW | 8.88 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 941361 | AE2-132 | 50/50 | 0.69 MW | 0.69 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 941381 | AE2-134 | Adder | 1.48 MW | 1.26 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 946371 | AF1-301 C | Adder | 5.4 MW | 4.59 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 946372 | AF1-301 E | Adder | 3.62 MW | 3.08 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957431 | AF2-037 C | Adder | 3.8 MW | 3.23 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957432 | AF2-037 E | Adder | 2.53 MW | 2.15 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957691 | AF2-063 C | Adder | 6.07 MW | 5.16 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 957692 | AF2-063 E | Adder | 4.04 MW | 3.44 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963031 | AG1-152 C | 50/50 | 9.1 MW | 9.1 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963032 | AG1-152 E | 50/50 | 13.64 MW | 13.64 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964271 | AG1-288 C | Adder | 6.78 MW | 5.76 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964281 | AG1-289 | Adder | 3.75 MW | 3.19 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964421 | AG1-305 C O2 | Adder | 4.77 MW | 4.06 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 964422 | AG1-305 E O2 | Adder | 3.18 MW | 2.7 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966001 | AG1-469 C | Adder | 0.96 MW | 0.82 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966002 | AG1-469 E | Adder | 0.48 MW | 0.41 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925671 | AC1-043 C | Adder | 5.33 MW | 4.53 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 925672 | AC1-043 E | Adder | 8.7 MW | 7.39 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966331 | AG1-502 C | Adder | 7.12 MW | 6.05 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966332 | AG1-502 E | Adder | 1.78 MW | 1.51 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966341 | AG1-503 C | Adder | 1.78 MW | 1.51 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 966342 | AG1-503 E | Adder | 0.44 MW | 0.38 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 963693 | AG1-221 BAT | Adder | 3.91 MW | 3.32 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | 940352 | AE2-019 BAT | Adder | 12.5 MW | 10.62 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.93 MW | 0.93 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.39 MW | 0.39 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.32 MW | 18.32 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.15 MW | 9.15 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.48 MW | 8.48 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.41 MW | 1.41 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.92 MW | 1.92 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.09 MW | 0.09 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.47 MW | 0.47 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.25 MW | 1.25 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.86 MW | 0.86 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.17 MW | 12.17 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.54 MW | 1.54 MW |
| 6ELK RUN-AE2-190 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 569-2101 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.22 MW | 0.22 MW |
Light Load Analysis
The Queue Project was evaluated as a 75.0 MW (Capacity 32.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7580 | Rebuild 8.72 miles of 230 kV Line 2054 from Charlottesville to Profit D.P. with 2-636 ACSR 150 C | $21,800,000 | |
| b3689.1 | PJM Baseline: Reconductor 230 kV Line #2114 Remington CT-Elk Run-Gainsville. | $0 | |
| n6773 | Replace Wave traps at the Louisa and North Anna 230 kV substations. | $300,000 | |
| n7513 | Rebuild 1.07 miles of 230 kV Line 299 from Marsh Run to Remington CT with 2-636 ACSR 150 C | $2,900,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-538 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.