AG1-525 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:59
Sullivan-Rockport 765 kV
180.0 MW Capacity / 300.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-525 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing Solar generating facility located in the AEP zone — Sullivan County, Indiana. This project is an increase to the Interconnection Customer's AG1-522, AG1-523 and AG1-524 project, which will share the same point of interconnection. The AG1-525 queue position is a 300.0 MW uprate (180.0 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 1200.0 MW with 720.0 MW of this output being recognized by PJM as Capacity. The proposed in-service date for this project is Thursday, June 01, 2023. This study does not imply a TO commitment to this in-service date.
Project Information | |
Queue Number | AG1-525 |
Project Name | Sullivan-Rockport 765 kV |
Developer Name | PJM Solar Devco I, LLC |
State | Indiana |
County | Sullivan |
Transmission Owner | AEP |
MFO | 1200.0 MW |
MWE | 300.0 MW |
MWC | 180.0 MW |
Fuel Type | Solar |
Basecase Study Year | 2024 |
Point of Interconnection
AG1-525 will interconnect on the AEP transmission system tapping the Sullivan to Rockport 765 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 300.0 MW (Capacity 180.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Summer Peak Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
AEP/ARE_2 |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line
247712 to 956820 ckt 1 |
AEP_P1-2_#363_1682
CONTINGENCY 'AEP_P1-2_#363_1682' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Single | DC | 147.06 % | 151.56 % | 1466.0 | B | 2221.8 | 65.85 | |
AEP |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line
247712 to 243221 ckt 1 |
AEP_P1-2_#363_1682
CONTINGENCY 'AEP_P1-2_#363_1682' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Single | DC | 123.62 % | 126.56 % | 1335.0 | B | 1689.62 | 39.34 | |
AEP/ARE_2 |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line
247712 to 956820 ckt 1 |
AEP_P1-2_#10136
CONTINGENCY 'AEP_P1-2_#10136' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 OPEN BRANCH FROM BUS 243209 TO BUS 243443 CKT 2 /*05ROCKPT 765.0 - 05RKG2 26.0 REMOVE UNIT 2H FROM BUS 243443 /*05RKG2 26.0 REMOVE UNIT 2L FROM BUS 243443 /*05RKG2 26.0 END |
Single | AC | 118.45 % | 123.17 % | 1466.0 | B | 1805.66 | 66.29 | |
AEP/IPL |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line
247712 to 254529 ckt 1 |
AEP_P1-2_#363_1682
CONTINGENCY 'AEP_P1-2_#363_1682' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Single | DC | 119.42 % | 122.69 % | 1409.0 | B | 1728.7 | 46.03 | |
AEP |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line
243209 to 243208 ckt 1 |
AEP_P1-2_#8905_1697
CONTINGENCY 'AEP_P1-2_#8905_1697' OPEN BRANCH FROM BUS 243217 TO BUS 247712 CKT 1 /*05DEQUIN 345.0 - 05SULLIVAN 345.0 END |
Single | AC | 108.23 % | 110.61 % | 3970.0 | B | 4391.14 | 83.83 | |
AEP |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer
243210 to 247712 ckt 1 |
AEP_P1-2_#363_1682
CONTINGENCY 'AEP_P1-2_#363_1682' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Single | DC | 103.73 % | 108.84 % | 1737.0 | B | 1890.5 | 88.76 | |
AEP |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line
243209 to 243208 ckt 1 |
AEP_P1-2_#672_1713-B
CONTINGENCY 'AEP_P1-2_#672_1713-B' OPEN BRANCH FROM BUS 963840 TO BUS 963740 CKT 1 /*AG1-237 TAP 345.0 - AG1-226 TAP 345.0 END |
Single | AC | 106.3 % | 108.6 % | 3970.0 | B | 4311.26 | 80.43 | |
AEP/OVEC |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line
242865 to 248000 ckt Z1 |
AEP_P1-2_#709_546
CONTINGENCY 'AEP_P1-2_#709_546' OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 END |
Single | AC | 102.94 % | 105.0 % | 2255.0 | B | 2367.66 | 42.34 | |
AEP |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line
247712 to 243221 ckt 1 |
AEP_P1-2_#10136
CONTINGENCY 'AEP_P1-2_#10136' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 OPEN BRANCH FROM BUS 243209 TO BUS 243443 CKT 2 /*05ROCKPT 765.0 - 05RKG2 26.0 REMOVE UNIT 2H FROM BUS 243443 /*05RKG2 26.0 REMOVE UNIT 2L FROM BUS 243443 /*05RKG2 26.0 END |
Single | AC | 101.97 % | 105.0 % | 1335.0 | B | 1401.82 | 39.6 | |
AEP |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line
247712 to 243217 ckt 1 |
AEP_P1-2_#363_1682
CONTINGENCY 'AEP_P1-2_#363_1682' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Single | DC | 101.7 % | 103.7 % | 1318.0 | B | 1366.74 | 26.31 | |
AEP |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line
243209 to 243208 ckt 1 |
Base Case | Single | AC | 100.33 % | 102.54 % | 3970.0 | A | 4071.0 | 79.72 | |
AEP/IPL |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line
247712 to 254529 ckt 1 |
AEP_P1-2_#10136
CONTINGENCY 'AEP_P1-2_#10136' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 OPEN BRANCH FROM BUS 243209 TO BUS 243443 CKT 2 /*05ROCKPT 765.0 - 05RKG2 26.0 REMOVE UNIT 2H FROM BUS 243443 /*05RKG2 26.0 REMOVE UNIT 2L FROM BUS 243443 /*05RKG2 26.0 END |
Single | AC | 97.07 % | 100.42 % | 1409.0 | B | 1414.88 | 46.34 | |
AEP/OVEC |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line
242865 to 248000 ckt Z1 |
AEP_P4_#1760_05JEFRSO 765_A
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A' OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 OPEN BRANCH FROM BUS 243207 TO BUS 243208 CKT 1 /*05GRNTWN 765.0 - 05JEFRSO 765.0 END |
Breaker | AC | 168.84 % | 172.73 % | 2255.0 | B | 3894.99 | 102.33 | |
AEP/OVEC |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line
242865 to 248000 ckt Z1 |
AEP_P4_#6189_05HANG R 765_D1
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1' OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1 /*05CORNU 765.0 - 05HANG R 765.0 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1 /*05CORNU 765.0 - 05CORNU 345.0 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 REMOVE UNIT 1A FROM BUS 247245 /*05HRKG1A 18.0 REMOVE UNIT 1B FROM BUS 247246 /*05HRKG1B 18.0 REMOVE UNIT 1S FROM BUS 247247 /*05HRKG1S 18.0 REMOVE UNIT 2A FROM BUS 247248 /*05HRKG2A 18.0 REMOVE UNIT 2B FROM BUS 247249 /*05HRKG2B 18.0 REMOVE UNIT 2S FROM BUS 247250 /*05HRKG2S 18.0 END |
Breaker | AC | 139.42 % | 143.08 % | 2255.0 | B | 3226.48 | 70.48 | |
AEP |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line
243209 to 243208 ckt 1 |
AEP_P4_#8906_05SULLIVAN 345_C
CONTINGENCY 'AEP_P4_#8906_05SULLIVAN 345_C' OPEN BRANCH FROM BUS 243217 TO BUS 247712 CKT 1 /*05DEQUIN 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 247712 CKT 1 /*05EUGENE 345.0 - 05SULLIVAN 345.0 END |
Breaker | AC | 136.86 % | 141.75 % | 3970.0 | B | 5627.28 | 152.79 | |
AEP |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line
243209 to 243208 ckt 1 |
AEP_P4_#8910_05DEQUIN 345_C
CONTINGENCY 'AEP_P4_#8910_05DEQUIN 345_C' OPEN BRANCH FROM BUS 243217 TO BUS 243878 CKT 2 /*05DEQUIN 345.0 - 05MEADOW 345.0 OPEN BRANCH FROM BUS 243217 TO BUS 247712 CKT 1 /*05DEQUIN 345.0 - 05SULLIVAN 345.0 END |
Breaker | AC | 128.62 % | 132.92 % | 3970.0 | B | 5276.96 | 139.97 | |
AEP |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
243208 to 242865 ckt 2 |
AEP_P4_#1760_05JEFRSO 765_A
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A' OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 OPEN BRANCH FROM BUS 243207 TO BUS 243208 CKT 1 /*05GRNTWN 765.0 - 05JEFRSO 765.0 END |
Breaker | AC | 122.06 % | 124.38 % | 3039.0 | B | 3779.76 | 102.33 | |
AEP/DEI |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line
243221 to 249504 ckt 1 |
AEP_P4_#4697_05DEQUIN 345_B
CONTINGENCY 'AEP_P4_#4697_05DEQUIN 345_B' OPEN BRANCH FROM BUS 243217 TO BUS 243878 CKT 1 /*05DEQUIN 345.0 - 05MEADOW 345.0 OPEN BRANCH FROM BUS 243217 TO BUS 963840 CKT 1 /*05DEQUIN 345.0 - AG1-237 TAP 345.0 END |
Breaker | AC | 121.16 % | 122.26 % | 1374.0 | B | 1679.82 | 25.15 | |
AEP |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line
966530 to 243210 ckt 1 |
AEP_P4_#9336_05ROCKPT 765_C
CONTINGENCY 'AEP_P4_#9336_05ROCKPT 765_C' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 OPEN BRANCH FROM BUS 243209 TO BUS 247133 CKT Z7 /*05ROCKPT 765.0 - 05ROCKP WRK1 765.0 OPEN BRANCH FROM BUS 243239 TO BUS 243785 CKT 1 /*05ROCKP WRK1 138.0 - 05AKSTL 138.0 OPEN BRANCH FROM BUS 243239 TO BUS 247133 CKT 7 /*05ROCKP WRK1 138.0 - 05ROCKP WRK1 765.0 END |
Breaker | DC | 110.76 % | 118.43 % | 3859.0 | B | 4570.29 | 295.88 | |
AEP |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line
966530 to 243210 ckt 1 |
AEP_P4_#3002_05ROCKPT 765_C2
CONTINGENCY 'AEP_P4_#3002_05ROCKPT 765_C2' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 OPEN BRANCH FROM BUS 243209 TO BUS 247135 CKT Z8 /*05ROCKPT 765.0 - 05ROCKP WRK2 765.0 OPEN BRANCH FROM BUS 243240 TO BUS 243785 CKT 1 /*05ROCKP WRK2 138.0 - 05AKSTL 138.0 OPEN BRANCH FROM BUS 243240 TO BUS 247135 CKT 8 /*05ROCKP WRK2 138.0 - 05ROCKP WRK2 765.0 END |
Breaker | DC | 110.76 % | 118.43 % | 3859.0 | B | 4570.29 | 295.88 | |
AEP |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line
966530 to 243210 ckt 1 |
AEP_P4_#8648_05JEFRSO 765_B
CONTINGENCY 'AEP_P4_#8648_05JEFRSO 765_B' OPEN BRANCH FROM BUS 243208 TO BUS 243209 CKT 1 /*05JEFRSO 765.0 - 05ROCKPT 765.0 END |
Breaker | DC | 110.76 % | 118.43 % | 3859.0 | B | 4570.29 | 295.88 | |
OVEC |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line
248000 to 248001 ckt 1 |
AEP_P4_#1760_05JEFRSO 765_A
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A' OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 OPEN BRANCH FROM BUS 243207 TO BUS 243208 CKT 1 /*05GRNTWN 765.0 - 05JEFRSO 765.0 END |
Breaker | AC | 109.09 % | 111.1 % | 1099.0 | B | 1220.99 | 25.57 | |
AEP |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
243208 to 242865 ckt 2 |
AEP_P4_#6189_05HANG R 765_D1
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1' OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1 /*05CORNU 765.0 - 05HANG R 765.0 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1 /*05CORNU 765.0 - 05CORNU 345.0 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 REMOVE UNIT 1A FROM BUS 247245 /*05HRKG1A 18.0 REMOVE UNIT 1B FROM BUS 247246 /*05HRKG1B 18.0 REMOVE UNIT 1S FROM BUS 247247 /*05HRKG1S 18.0 REMOVE UNIT 2A FROM BUS 247248 /*05HRKG2A 18.0 REMOVE UNIT 2B FROM BUS 247249 /*05HRKG2B 18.0 REMOVE UNIT 2S FROM BUS 247250 /*05HRKG2S 18.0 END |
Breaker | AC | 99.66 % | 101.82 % | 3039.0 | B | 3094.25 | 70.48 | |
AEP |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line
243209 to 243208 ckt 1 |
AEP_P7-1_#11041
CONTINGENCY 'AEP_P7-1_#11041' OPEN BRANCH FROM BUS 243217 TO BUS 243878 CKT 1 /*05DEQUIN 345.0 - 05MEADOW 345.0 OPEN BRANCH FROM BUS 243217 TO BUS 243878 CKT 2 /*05DEQUIN 345.0 - 05MEADOW 345.0 END |
Tower | AC | 141.08 % | 145.8 % | 3970.0 | B | 5788.26 | 139.25 | |
AEP |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line
243209 to 243208 ckt 1 |
AEP_P7-1_#11014-A
CONTINGENCY 'AEP_P7-1_#11014-A' OPEN BRANCH FROM BUS 243217 TO BUS 247712 CKT 1 /*05DEQUIN 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243217 TO BUS 963840 CKT 1 /*05DEQUIN 345.0 - AG1-237 TAP 345.0 END |
Tower | AC | 141.0 % | 145.79 % | 3970.0 | B | 5788.06 | 143.03 | |
AEP/DEI |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line
243221 to 249504 ckt 1 |
AEP_P7-1_#11014-A
CONTINGENCY 'AEP_P7-1_#11014-A' OPEN BRANCH FROM BUS 243217 TO BUS 247712 CKT 1 /*05DEQUIN 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243217 TO BUS 963840 CKT 1 /*05DEQUIN 345.0 - AG1-237 TAP 345.0 END |
Tower | AC | 133.59 % | 134.86 % | 1374.0 | B | 1853.02 | 28.98 | |
AEP/DEI |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line
243221 to 249504 ckt 1 |
AEP_P7-1_#11014-B
CONTINGENCY 'AEP_P7-1_#11014-B' OPEN BRANCH FROM BUS 243217 TO BUS 247712 CKT 1 /*05DEQUIN 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 963840 TO BUS 963740 CKT 1 /*AG1-237 TAP 345.0 - AG1-226 TAP 345.0 END |
Tower | AC | 127.22 % | 128.45 % | 1374.0 | B | 1764.94 | 28.98 |
Details for 05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 963841 | AG1-237 C O1 | 80/20 | 1.3 MW | 1.3 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966841 | AG1-555 C | 80/20 | 4.57 MW | 4.57 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 965331 | AG1-398 | Adder | -0.6 MW | -0.51 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966531 | AG1-522 C | 80/20 | 65.85 MW | 65.85 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966541 | AG1-523 C | 80/20 | 65.85 MW | 65.85 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966551 | AG1-524 C | 80/20 | 65.85 MW | 65.85 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966561 | AG1-525 C | 80/20 | 65.85 MW | 65.85 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 935141 | AD1-148 | Adder | -3.25 MW | -2.77 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 942601 | AE2-276 | 80/20 | 18.29 MW | 18.29 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 960141 | AF2-305 | Adder | -0.76 MW | -0.65 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 960261 | AF2-317 | Adder | -1.41 MW | -1.2 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243442 | 05RKG1 | 80/20 | 84.5 MW | 84.5 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243443 | 05RKG2 | 80/20 | 81.01 MW | 81.01 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243859 | 05FR-11G C | 80/20 | 0.23 MW | 0.23 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243862 | 05FR-12G C | 80/20 | 0.11 MW | 0.11 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243864 | 05FR-21G C | 80/20 | 0.11 MW | 0.11 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243866 | 05FR-22G C | 80/20 | 0.11 MW | 0.11 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243870 | 05FR-3G C | 80/20 | 0.11 MW | 0.11 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243873 | 05FR-4G C | 80/20 | 0.26 MW | 0.26 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 924261 | AB2-070 C O1 | Adder | -2.14 MW | -1.82 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930461 | AB1-087 CT1 | 80/20 | 112.08 MW | 112.08 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930462 | AB1-087 ST1 | 80/20 | 89.1 MW | 89.1 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930471 | AB1-088 CT1 | 80/20 | 112.08 MW | 112.08 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930472 | AB1-088 ST1 | 80/20 | 89.1 MW | 89.1 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 933446 | AC2-157 1C | 80/20 | 13.9 MW | 13.9 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 933447 | AC2-157 2C | 80/20 | 13.9 MW | 13.9 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 941341 | AE2-130 C | 80/20 | 175.61 MW | 175.61 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 957141 | AF2-008 FTIR | 80/20 | 182.89 MW | 182.89 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 944201 | AF1-088 FTIR | 80/20 | 365.78 MW | 365.78 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 953161 | J837 C | External Queue | 2.09 MW | 2.09 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 953171 | J838 C | External Queue | 1.04 MW | 1.04 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 953351 | J805 | External Queue | 13.7 MW | 13.7 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 954351 | J903 | External Queue | 6.53 MW | 6.53 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 954421 | J913 C | External Queue | 10.69 MW | 10.69 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 954941 | J968 C | External Queue | 2.09 MW | 2.09 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 955151 | J993 | External Queue | 13.68 MW | 13.68 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 955841 | J1069 C | External Queue | 2.09 MW | 2.09 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 990426 | J1308 | External Queue | 18.91 MW | 18.91 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 991186 | J1593 | External Queue | 13.67 MW | 13.67 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 991206 | J1637 | External Queue | 11.24 MW | 11.24 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 991311 | J1772 | External Queue | 13.37 MW | 13.37 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 12.26 MW | 12.26 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.16 MW | 1.16 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.51 MW | 0.51 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.16 MW | 1.16 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 10.84 MW | 10.84 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.75 MW | 0.75 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.72 MW | 0.72 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 29.66 MW | 29.66 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.3 MW | 0.3 MW |
Details for 05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966531 | AG1-522 C | 80/20 | 39.34 MW | 39.34 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966541 | AG1-523 C | 80/20 | 39.34 MW | 39.34 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966551 | AG1-524 C | 80/20 | 39.34 MW | 39.34 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966561 | AG1-525 C | 80/20 | 39.34 MW | 39.34 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 942601 | AE2-276 | 80/20 | 10.93 MW | 10.93 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243442 | 05RKG1 | 80/20 | 50.48 MW | 50.48 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243443 | 05RKG2 | 80/20 | 48.39 MW | 48.39 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930461 | AB1-087 CT1 | 80/20 | 66.97 MW | 66.97 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930462 | AB1-087 ST1 | 80/20 | 53.24 MW | 53.24 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930471 | AB1-088 CT1 | 80/20 | 66.97 MW | 66.97 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930472 | AB1-088 ST1 | 80/20 | 53.24 MW | 53.24 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 933446 | AC2-157 1C | 80/20 | 8.3 MW | 8.3 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 933447 | AC2-157 2C | 80/20 | 8.3 MW | 8.3 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 941341 | AE2-130 C | 80/20 | 104.91 MW | 104.91 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 957141 | AF2-008 FTIR | 80/20 | 109.28 MW | 109.28 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 944201 | AF1-088 FTIR | 80/20 | 218.56 MW | 218.56 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 990071 | J1204 | External Queue | 16.31 MW | 16.31 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.4 MW | 0.4 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.11 MW | 3.11 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.48 MW | 11.48 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.19 MW | 2.19 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.28 MW | 0.28 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.04 MW | 1.04 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.22 MW | 0.22 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.65 MW | 1.65 MW |
Details for 05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 963841 | AG1-237 C O1 | 80/20 | 1.37 MW | 1.37 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966841 | AG1-555 C | 80/20 | 4.79 MW | 4.79 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 965331 | AG1-398 | Adder | -0.59 MW | -0.5 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966531 | AG1-522 C | 80/20 | 66.29 MW | 66.29 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966541 | AG1-523 C | 80/20 | 66.29 MW | 66.29 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966551 | AG1-524 C | 80/20 | 66.29 MW | 66.29 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966561 | AG1-525 C | 80/20 | 66.29 MW | 66.29 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 935141 | AD1-148 | Adder | -3.17 MW | -2.69 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942601 | AE2-276 | 80/20 | 18.41 MW | 18.41 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 960141 | AF2-305 | Adder | -0.74 MW | -0.62 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 960261 | AF2-317 | Adder | -1.37 MW | -1.16 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243442 | 05RKG1 | 80/20 | 85.07 MW | 85.07 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243859 | 05FR-11G C | 80/20 | 0.24 MW | 0.24 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243862 | 05FR-12G C | 80/20 | 0.12 MW | 0.12 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243864 | 05FR-21G C | 80/20 | 0.12 MW | 0.12 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243866 | 05FR-22G C | 80/20 | 0.12 MW | 0.12 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243870 | 05FR-3G C | 80/20 | 0.12 MW | 0.12 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243873 | 05FR-4G C | 80/20 | 0.27 MW | 0.27 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 924261 | AB2-070 C O1 | Adder | -2.08 MW | -1.77 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930461 | AB1-087 CT1 | 80/20 | 112.83 MW | 112.83 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930462 | AB1-087 ST1 | 80/20 | 89.7 MW | 89.7 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930471 | AB1-088 CT1 | 80/20 | 112.83 MW | 112.83 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930472 | AB1-088 ST1 | 80/20 | 89.7 MW | 89.7 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 933446 | AC2-157 1C | 80/20 | 13.99 MW | 13.99 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 933447 | AC2-157 2C | 80/20 | 13.99 MW | 13.99 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 941341 | AE2-130 C | 80/20 | 176.79 MW | 176.79 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 957141 | AF2-008 FTIR | 80/20 | 184.12 MW | 184.12 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 944201 | AF1-088 FTIR | 80/20 | 368.24 MW | 368.24 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 953161 | J837 C | External Queue | 2.09 MW | 2.09 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 953171 | J838 C | External Queue | 1.04 MW | 1.04 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 953351 | J805 | External Queue | 13.7 MW | 13.7 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 954351 | J903 | External Queue | 6.53 MW | 6.53 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 954421 | J913 C | External Queue | 10.69 MW | 10.69 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 954941 | J968 C | External Queue | 2.09 MW | 2.09 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 955151 | J993 | External Queue | 13.68 MW | 13.68 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 955841 | J1069 C | External Queue | 2.09 MW | 2.09 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 990426 | J1308 | External Queue | 18.91 MW | 18.91 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 991186 | J1593 | External Queue | 13.67 MW | 13.67 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 991206 | J1637 | External Queue | 11.24 MW | 11.24 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 991311 | J1772 | External Queue | 13.37 MW | 13.37 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 12.02 MW | 12.02 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.67 MW | 0.67 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.04 MW | 1.04 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.42 MW | 0.42 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.23 MW | 0.23 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.03 MW | 1.03 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 10.32 MW | 10.32 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.38 MW | 0.38 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.61 MW | 0.61 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.88 MW | 0.88 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 29.02 MW | 29.02 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.32 MW | 0.32 MW |
05SULLIVAN-J1180 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.02 MW | 1.02 MW |
Details for 05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 963741 | AG1-226 C O1 | 80/20 | 18.65 MW | 18.65 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 963831 | AG1-236 C | 80/20 | 1.31 MW | 1.31 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 963841 | AG1-237 C O1 | 80/20 | 1.38 MW | 1.38 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966841 | AG1-555 C | 80/20 | 4.58 MW | 4.58 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 965911 | AG1-460 C | 80/20 | 0.66 MW | 0.66 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966531 | AG1-522 C | 80/20 | 46.03 MW | 46.03 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966541 | AG1-523 C | 80/20 | 46.03 MW | 46.03 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966551 | AG1-524 C | 80/20 | 46.03 MW | 46.03 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966561 | AG1-525 C | 80/20 | 46.03 MW | 46.03 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 925771 | AC1-053 C | 80/20 | 1.31 MW | 1.31 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 935141 | AD1-148 | 80/20 | 1.87 MW | 1.87 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 936771 | AD2-100 C | 80/20 | 7.12 MW | 7.12 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 936971 | AD2-131 C | 80/20 | 0.47 MW | 0.47 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 942481 | AE2-261 C | 80/20 | 9.91 MW | 9.91 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 942601 | AE2-276 | 80/20 | 12.79 MW | 12.79 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 945391 | AF1-204 C O1 | 80/20 | 4.02 MW | 4.02 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 945871 | AF1-252 O1 | 80/20 | 3.76 MW | 3.76 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 945881 | AF1-253 | 80/20 | 2.61 MW | 2.61 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 960261 | AF2-317 | 80/20 | 0.81 MW | 0.81 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243442 | 05RKG1 | 80/20 | 59.05 MW | 59.05 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243443 | 05RKG2 | 80/20 | 56.61 MW | 56.61 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243859 | 05FR-11G C | 80/20 | 0.23 MW | 0.23 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243862 | 05FR-12G C | 80/20 | 0.11 MW | 0.11 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243864 | 05FR-21G C | 80/20 | 0.12 MW | 0.12 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243866 | 05FR-22G C | 80/20 | 0.12 MW | 0.12 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243870 | 05FR-3G C | 80/20 | 0.11 MW | 0.11 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243873 | 05FR-4G C | 80/20 | 0.26 MW | 0.26 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 274650 | KINCAID ;1U | 80/20 | 5.19 MW | 5.19 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 274651 | KINCAID ;2U | 80/20 | 5.18 MW | 5.18 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930461 | AB1-087 CT1 | 80/20 | 78.36 MW | 78.36 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930462 | AB1-087 ST1 | 80/20 | 62.3 MW | 62.3 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930471 | AB1-088 CT1 | 80/20 | 78.36 MW | 78.36 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930472 | AB1-088 ST1 | 80/20 | 62.3 MW | 62.3 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 933446 | AC2-157 1C | 80/20 | 9.72 MW | 9.72 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 933447 | AC2-157 2C | 80/20 | 9.72 MW | 9.72 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 941341 | AE2-130 C | 80/20 | 122.72 MW | 122.72 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 944221 | AF1-090 C O1 | 80/20 | 2.12 MW | 2.12 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 957381 | AF2-032 C | 80/20 | 0.74 MW | 0.74 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 957141 | AF2-008 FTIR | 80/20 | 127.87 MW | 127.87 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 944201 | AF1-088 FTIR | 80/20 | 255.74 MW | 255.74 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 953401 | J811 | External Queue | 6.61 MW | 6.61 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 953651 | J815 | External Queue | 12.97 MW | 12.97 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 953881 | J848 C | External Queue | 2.08 MW | 2.08 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 954411 | J912 | External Queue | 5.57 MW | 5.57 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 954681 | J949 C | External Queue | 12.19 MW | 12.19 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 956451 | J1139 | External Queue | 7.87 MW | 7.87 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 990056 | J1201 | External Queue | 2.6 MW | 2.6 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 990071 | J1204 | External Queue | 23.9 MW | 23.9 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 990271 | J1263 | External Queue | 39.42 MW | 39.42 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 991196 | J1626 | External Queue | 10.01 MW | 10.01 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 991266 | J1714 | External Queue | 6.68 MW | 6.68 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 991261 | J1713 C | External Queue | 1.23 MW | 1.23 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.58 MW | 0.58 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 7.31 MW | 7.31 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.26 MW | 0.26 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 26.39 MW | 26.39 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.37 MW | 0.37 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 6.38 MW | 6.38 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.43 MW | 0.43 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.4 MW | 1.4 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.93 MW | 0.93 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.64 MW | 4.64 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.46 MW | 0.46 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 2.21 MW | 2.21 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.84 MW | 0.84 MW |
Details for 05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 965911 | AG1-460 C | 80/20 | 1.23 MW | 1.23 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 966531 | AG1-522 C | 80/20 | 83.83 MW | 83.83 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 966541 | AG1-523 C | 80/20 | 83.83 MW | 83.83 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 966551 | AG1-524 C | 80/20 | 83.83 MW | 83.83 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 966561 | AG1-525 C | 80/20 | 83.83 MW | 83.83 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 936771 | AD2-100 C | 80/20 | 13.19 MW | 13.19 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 936971 | AD2-131 C | 80/20 | 0.87 MW | 0.87 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 942481 | AE2-261 C | 80/20 | 18.34 MW | 18.34 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 942601 | AE2-276 | 80/20 | 16.77 MW | 16.77 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 945391 | AF1-204 C O1 | 80/20 | 8.0 MW | 8.0 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 945871 | AF1-252 O1 | 80/20 | 6.99 MW | 6.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 945881 | AF1-253 | 80/20 | 4.84 MW | 4.84 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 243442 | 05RKG1 | 80/20 | 146.59 MW | 146.59 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 243443 | 05RKG2 | 80/20 | 140.53 MW | 140.53 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 274650 | KINCAID ;1U | 80/20 | 9.59 MW | 9.59 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 274651 | KINCAID ;2U | 80/20 | 9.59 MW | 9.59 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 930461 | AB1-087 CT1 | 80/20 | 102.78 MW | 102.78 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 930462 | AB1-087 ST1 | 80/20 | 81.72 MW | 81.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 930471 | AB1-088 CT1 | 80/20 | 102.78 MW | 102.78 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 930472 | AB1-088 ST1 | 80/20 | 81.72 MW | 81.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 933446 | AC2-157 1C | 80/20 | 12.75 MW | 12.75 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 933447 | AC2-157 2C | 80/20 | 12.75 MW | 12.75 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 941341 | AE2-130 C | 80/20 | 304.64 MW | 304.64 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 944221 | AF1-090 C O1 | 80/20 | 3.94 MW | 3.94 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 957381 | AF2-032 C | 80/20 | 1.38 MW | 1.38 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 957141 | AF2-008 FTIR | 80/20 | 167.72 MW | 167.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 944201 | AF1-088 FTIR | 80/20 | 335.45 MW | 335.45 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 954681 | J949 C | External Queue | 17.21 MW | 17.21 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 990071 | J1204 | External Queue | 29.69 MW | 29.69 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | 990271 | J1263 | External Queue | 51.39 MW | 51.39 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.51 MW | 0.51 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.14 MW | 1.14 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.13 MW | 1.13 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 46.4 MW | 46.4 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 60.74 MW | 60.74 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.26 MW | 0.26 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.93 MW | 7.93 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.0 MW | 1.0 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.0 MW | 0.0 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.65 MW | 9.65 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.01 MW | 1.01 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.81 MW | 0.81 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.7 MW | 0.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.08 MW | 5.08 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#8905_1697 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.4 MW | 1.4 MW |
Details for 05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | 966531 | AG1-522 C | 80/20 | 88.76 MW | 88.76 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | 966541 | AG1-523 C | 80/20 | 88.76 MW | 88.76 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | 966551 | AG1-524 C | 80/20 | 88.76 MW | 88.76 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | 966561 | AG1-525 C | 80/20 | 88.76 MW | 88.76 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | 243442 | 05RKG1 | 80/20 | 113.9 MW | 113.9 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | 243443 | 05RKG2 | 80/20 | 109.19 MW | 109.19 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | 941341 | AE2-130 C | 80/20 | 236.7 MW | 236.7 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.69 MW | 0.69 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.19 MW | 1.19 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.34 MW | 0.34 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.34 MW | 0.34 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.44 MW | 1.44 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.38 MW | 0.38 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.38 MW | 0.38 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.77 MW | 1.77 MW |
05SULLIVAN-05SULLIVAN 765.0/345.0 kV Ckt 1 transformer l/o AEP_P1-2_#363_1682 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.38 MW | 0.38 MW |
Details for 05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 963741 | AG1-226 C O1 | 80/20 | 49.07 MW | 49.07 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 965911 | AG1-460 C | 80/20 | 1.24 MW | 1.24 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 966531 | AG1-522 C | 80/20 | 80.43 MW | 80.43 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 966541 | AG1-523 C | 80/20 | 80.43 MW | 80.43 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 966551 | AG1-524 C | 80/20 | 80.43 MW | 80.43 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 966561 | AG1-525 C | 80/20 | 80.43 MW | 80.43 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 936771 | AD2-100 C | 80/20 | 13.35 MW | 13.35 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 936971 | AD2-131 C | 80/20 | 0.88 MW | 0.88 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 942481 | AE2-261 C | 80/20 | 18.6 MW | 18.6 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 942601 | AE2-276 | 80/20 | 15.58 MW | 15.58 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 945391 | AF1-204 C O1 | 80/20 | 9.44 MW | 9.44 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 945871 | AF1-252 O1 | 80/20 | 7.03 MW | 7.03 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 945881 | AF1-253 | 80/20 | 4.87 MW | 4.87 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 243442 | 05RKG1 | 80/20 | 143.69 MW | 143.69 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 243443 | 05RKG2 | 80/20 | 137.74 MW | 137.74 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 274650 | KINCAID ;1U | 80/20 | 9.74 MW | 9.74 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 274651 | KINCAID ;2U | 80/20 | 9.73 MW | 9.73 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 930461 | AB1-087 CT1 | 80/20 | 95.5 MW | 95.5 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 930462 | AB1-087 ST1 | 80/20 | 75.92 MW | 75.92 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 930471 | AB1-088 CT1 | 80/20 | 95.5 MW | 95.5 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 930472 | AB1-088 ST1 | 80/20 | 75.92 MW | 75.92 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 933446 | AC2-157 1C | 80/20 | 11.84 MW | 11.84 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 933447 | AC2-157 2C | 80/20 | 11.84 MW | 11.84 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 941341 | AE2-130 C | 80/20 | 298.61 MW | 298.61 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 944221 | AF1-090 C O1 | 80/20 | 3.97 MW | 3.97 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 957381 | AF2-032 C | 80/20 | 1.4 MW | 1.4 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 957141 | AF2-008 FTIR | 80/20 | 155.84 MW | 155.84 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 944201 | AF1-088 FTIR | 80/20 | 311.68 MW | 311.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 954681 | J949 C | External Queue | 17.18 MW | 17.18 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 990071 | J1204 | External Queue | 27.98 MW | 27.98 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | 990271 | J1263 | External Queue | 49.6 MW | 49.6 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.56 MW | 0.56 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.36 MW | 1.36 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.11 MW | 0.11 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.09 MW | 1.09 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 48.5 MW | 48.5 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 60.56 MW | 60.56 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.3 MW | 0.3 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.8 MW | 7.8 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.02 MW | 1.02 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.79 MW | 9.79 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.03 MW | 1.03 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.8 MW | 0.8 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.77 MW | 0.77 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.95 MW | 4.95 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P1-2_#672_1713-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.46 MW | 1.46 MW |
Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 963741 | AG1-226 C O1 | 80/20 | 41.18 MW | 41.18 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 963841 | AG1-237 C O1 | 80/20 | 3.43 MW | 3.43 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 964401 | AG1-302 C O1 | 80/20 | 23.16 MW | 23.16 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 964861 | AG1-349 C O1 | 80/20 | 20.16 MW | 20.16 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 966841 | AG1-555 C | 80/20 | 11.96 MW | 11.96 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 965681 | AG1-436 C | 80/20 | 8.06 MW | 8.06 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 965791 | AG1-447 | 80/20 | 5.91 MW | 5.91 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 966531 | AG1-522 C | 80/20 | 42.34 MW | 42.34 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 966541 | AG1-523 C | 80/20 | 42.34 MW | 42.34 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 966551 | AG1-524 C | 80/20 | 42.34 MW | 42.34 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 966561 | AG1-525 C | 80/20 | 42.34 MW | 42.34 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 246909 | 05MDL-1G C | 80/20 | 0.61 MW | 0.61 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 246910 | 05MDL-2G C | 80/20 | 0.36 MW | 0.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 246976 | 05MDL-3G C | 80/20 | 0.36 MW | 0.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 246979 | 05MDL-4G C | 80/20 | 0.28 MW | 0.28 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 247556 | 05MDL-5G | 80/20 | 0.48 MW | 0.48 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 942601 | AE2-276 | 80/20 | 8.63 MW | 8.63 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 945391 | AF1-204 C O1 | 80/20 | 6.83 MW | 6.83 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 945421 | AF1-207 C O1 | 80/20 | 4.75 MW | 4.75 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 945501 | AF1-215 C O1 | 80/20 | 22.39 MW | 22.39 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 959141 | AF2-205 C | 80/20 | 15.89 MW | 15.89 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 960681 | AF2-359 C | 80/20 | 8.06 MW | 8.06 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243441 | 05CKG2 | 80/20 | 21.46 MW | 21.46 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243442 | 05RKG1 | 80/20 | 73.05 MW | 73.05 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243443 | 05RKG2 | 80/20 | 70.03 MW | 70.03 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243859 | 05FR-11G C | 80/20 | 0.59 MW | 0.59 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243862 | 05FR-12G C | 80/20 | 0.29 MW | 0.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243864 | 05FR-21G C | 80/20 | 0.3 MW | 0.3 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243866 | 05FR-22G C | 80/20 | 0.3 MW | 0.3 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243870 | 05FR-3G C | 80/20 | 0.29 MW | 0.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 243873 | 05FR-4G C | 80/20 | 0.67 MW | 0.67 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 270100 | X2-052 CT1 | 80/20 | 4.26 MW | 4.26 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 270101 | X2-052 CT2 | 80/20 | 4.26 MW | 4.26 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 270102 | X2-052 ST | 80/20 | 4.61 MW | 4.61 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274751 | CRETE EC ;1U | 80/20 | 1.33 MW | 1.33 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274752 | CRETE EC ;2U | 80/20 | 1.33 MW | 1.33 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274753 | CRETE EC ;3U | 80/20 | 1.33 MW | 1.33 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274754 | CRETE EC ;4U | 80/20 | 1.33 MW | 1.33 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274770 | LINCOLN ;1U | 80/20 | 1.37 MW | 1.37 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274771 | LINCOLN ;2U | 80/20 | 1.37 MW | 1.37 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274772 | LINCOLN ;3U | 80/20 | 1.37 MW | 1.37 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274773 | LINCOLN ;4U | 80/20 | 1.37 MW | 1.37 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274774 | LINCOLN ;5U | 80/20 | 1.37 MW | 1.37 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274775 | LINCOLN ;6U | 80/20 | 1.37 MW | 1.37 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274776 | LINCOLN ;7U | 80/20 | 1.37 MW | 1.37 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274777 | LINCOLN ;8U | 80/20 | 1.37 MW | 1.37 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 274792 | SE CHICAG;9U | 80/20 | 3.98 MW | 3.98 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 930041 | AB1-006 C | 80/20 | 0.61 MW | 0.61 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 930461 | AB1-087 CT1 | 80/20 | 52.91 MW | 52.91 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 930462 | AB1-087 ST1 | 80/20 | 42.07 MW | 42.07 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 930471 | AB1-088 CT1 | 80/20 | 52.91 MW | 52.91 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 930472 | AB1-088 ST1 | 80/20 | 42.07 MW | 42.07 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 933281 | AC2-140 C | 80/20 | 0.71 MW | 0.71 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 933446 | AC2-157 1C | 80/20 | 6.56 MW | 6.56 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 933447 | AC2-157 2C | 80/20 | 6.56 MW | 6.56 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 940581 | AE2-045 C O1 | 80/20 | 11.33 MW | 11.33 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 941341 | AE2-130 C | 80/20 | 151.81 MW | 151.81 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 946581 | AF1-322 C | 80/20 | 11.65 MW | 11.65 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 957841 | AF2-078 C O1 | 80/20 | 16.78 MW | 16.78 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 958381 | AF2-132 C O1 | 80/20 | 23.16 MW | 23.16 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 958391 | AF2-133 C O1 | 80/20 | 23.55 MW | 23.55 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 958401 | AF2-134 C O1 | 80/20 | 7.46 MW | 7.46 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 957141 | AF2-008 FTIR | 80/20 | 86.34 MW | 86.34 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | 944201 | AF1-088 FTIR | 80/20 | 172.68 MW | 172.68 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.53 MW | 1.53 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 29.57 MW | 29.57 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.92 MW | 0.92 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.69 MW | 0.69 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 97.24 MW | 97.24 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 28.66 MW | 28.66 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.92 MW | 0.92 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.15 MW | 1.15 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.07 MW | 3.07 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 6.44 MW | 6.44 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.34 MW | 12.34 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.0 MW | 1.0 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 10.29 MW | 10.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.03 MW | 3.03 MW |
Details for 05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966531 | AG1-522 C | 80/20 | 39.6 MW | 39.6 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966541 | AG1-523 C | 80/20 | 39.6 MW | 39.6 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966551 | AG1-524 C | 80/20 | 39.6 MW | 39.6 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966561 | AG1-525 C | 80/20 | 39.6 MW | 39.6 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942601 | AE2-276 | 80/20 | 11.0 MW | 11.0 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243442 | 05RKG1 | 80/20 | 50.82 MW | 50.82 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930461 | AB1-087 CT1 | 80/20 | 67.42 MW | 67.42 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930462 | AB1-087 ST1 | 80/20 | 53.6 MW | 53.6 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930471 | AB1-088 CT1 | 80/20 | 67.42 MW | 67.42 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930472 | AB1-088 ST1 | 80/20 | 53.6 MW | 53.6 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 933446 | AC2-157 1C | 80/20 | 8.36 MW | 8.36 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 933447 | AC2-157 2C | 80/20 | 8.36 MW | 8.36 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 941341 | AE2-130 C | 80/20 | 105.61 MW | 105.61 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 957141 | AF2-008 FTIR | 80/20 | 110.01 MW | 110.01 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 944201 | AF1-088 FTIR | 80/20 | 220.03 MW | 220.03 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 990071 | J1204 | External Queue | 16.31 MW | 16.31 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.14 MW | 0.14 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.45 MW | 0.45 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.65 MW | 4.65 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 12.79 MW | 12.79 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.21 MW | 0.21 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.45 MW | 2.45 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.28 MW | 1.28 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.24 MW | 0.24 MW |
05SULLIVAN-05EUGENE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.86 MW | 1.86 MW |
Details for 05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966531 | AG1-522 C | 80/20 | 26.31 MW | 26.31 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966541 | AG1-523 C | 80/20 | 26.31 MW | 26.31 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966551 | AG1-524 C | 80/20 | 26.31 MW | 26.31 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 966561 | AG1-525 C | 80/20 | 26.31 MW | 26.31 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 942601 | AE2-276 | 80/20 | 7.31 MW | 7.31 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243442 | 05RKG1 | 80/20 | 33.76 MW | 33.76 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 243443 | 05RKG2 | 80/20 | 32.37 MW | 32.37 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930461 | AB1-087 CT1 | 80/20 | 44.79 MW | 44.79 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930462 | AB1-087 ST1 | 80/20 | 35.61 MW | 35.61 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930471 | AB1-088 CT1 | 80/20 | 44.79 MW | 44.79 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 930472 | AB1-088 ST1 | 80/20 | 35.61 MW | 35.61 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 933446 | AC2-157 1C | 80/20 | 5.55 MW | 5.55 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 933447 | AC2-157 2C | 80/20 | 5.55 MW | 5.55 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 941341 | AE2-130 C | 80/20 | 70.17 MW | 70.17 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 957141 | AF2-008 FTIR | 80/20 | 73.09 MW | 73.09 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 944201 | AF1-088 FTIR | 80/20 | 146.18 MW | 146.18 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 990071 | J1204 | External Queue | 13.66 MW | 13.66 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | 990271 | J1263 | External Queue | 22.47 MW | 22.47 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.59 MW | 0.59 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.76 MW | 5.76 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.16 MW | 21.16 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.04 MW | 3.04 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.71 MW | 0.71 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.86 MW | 1.86 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.34 MW | 0.34 MW |
05SULLIVAN-05DEQUIN 345.0 kV Ckt 1 line l/o AEP_P1-2_#363_1682 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.31 MW | 2.31 MW |
Details for 05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 966531 | AG1-522 C | 80/20 | 79.72 MW | 79.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 966541 | AG1-523 C | 80/20 | 79.72 MW | 79.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 966551 | AG1-524 C | 80/20 | 79.72 MW | 79.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 966561 | AG1-525 C | 80/20 | 79.72 MW | 79.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 936771 | AD2-100 C | 80/20 | 12.72 MW | 12.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 936971 | AD2-131 C | 80/20 | 0.84 MW | 0.84 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 942601 | AE2-276 | 80/20 | 15.32 MW | 15.32 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 945391 | AF1-204 C O1 | 80/20 | 8.04 MW | 8.04 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 6.7 MW | 6.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 4.64 MW | 4.64 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 243442 | 05RKG1 | 80/20 | 143.14 MW | 143.14 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 243443 | 05RKG2 | 80/20 | 137.22 MW | 137.22 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 930461 | AB1-087 CT1 | 80/20 | 93.9 MW | 93.9 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 930462 | AB1-087 ST1 | 80/20 | 74.65 MW | 74.65 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 930471 | AB1-088 CT1 | 80/20 | 93.9 MW | 93.9 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 930472 | AB1-088 ST1 | 80/20 | 74.65 MW | 74.65 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 933446 | AC2-157 1C | 80/20 | 11.64 MW | 11.64 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 933447 | AC2-157 2C | 80/20 | 11.64 MW | 11.64 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 941341 | AE2-130 C | 80/20 | 297.48 MW | 297.48 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 3.78 MW | 3.78 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 957141 | AF2-008 FTIR | 80/20 | 153.23 MW | 153.23 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 944201 | AF1-088 FTIR | 80/20 | 306.45 MW | 306.45 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 990071 | J1204 | External Queue | 26.9 MW | 26.9 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | 990271 | J1263 | External Queue | 46.92 MW | 46.92 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.62 MW | 0.62 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.76 MW | 1.76 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.0 MW | 1.0 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 48.77 MW | 48.77 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 57.12 MW | 57.12 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.35 MW | 0.35 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.37 MW | 7.37 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.04 MW | 1.04 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.53 MW | 9.53 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.03 MW | 1.03 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.74 MW | 0.74 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.9 MW | 0.9 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.61 MW | 4.61 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.46 MW | 1.46 MW |
Details for 05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 963741 | AG1-226 C O1 | 80/20 | 19.22 MW | 19.22 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 963831 | AG1-236 C | 80/20 | 1.35 MW | 1.35 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 963841 | AG1-237 C O1 | 80/20 | 1.43 MW | 1.43 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966841 | AG1-555 C | 80/20 | 4.73 MW | 4.73 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 965331 | AG1-398 | 80/20 | 0.38 MW | 0.38 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 965911 | AG1-460 C | 80/20 | 0.68 MW | 0.68 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966531 | AG1-522 C | 80/20 | 46.34 MW | 46.34 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966541 | AG1-523 C | 80/20 | 46.34 MW | 46.34 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966551 | AG1-524 C | 80/20 | 46.34 MW | 46.34 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 966561 | AG1-525 C | 80/20 | 46.34 MW | 46.34 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 925771 | AC1-053 C | 80/20 | 1.35 MW | 1.35 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 935141 | AD1-148 | 80/20 | 1.93 MW | 1.93 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 936771 | AD2-100 C | 80/20 | 7.34 MW | 7.34 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 936971 | AD2-131 C | 80/20 | 0.48 MW | 0.48 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942481 | AE2-261 C | 80/20 | 10.22 MW | 10.22 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 942601 | AE2-276 | 80/20 | 12.87 MW | 12.87 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 945391 | AF1-204 C O1 | 80/20 | 4.13 MW | 4.13 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 945871 | AF1-252 O1 | 80/20 | 3.87 MW | 3.87 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 945881 | AF1-253 | 80/20 | 2.68 MW | 2.68 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 960141 | AF2-305 | 80/20 | 0.47 MW | 0.47 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 960261 | AF2-317 | 80/20 | 0.83 MW | 0.83 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243442 | 05RKG1 | 80/20 | 59.45 MW | 59.45 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243859 | 05FR-11G C | 80/20 | 0.23 MW | 0.23 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243862 | 05FR-12G C | 80/20 | 0.11 MW | 0.11 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243864 | 05FR-21G C | 80/20 | 0.12 MW | 0.12 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243866 | 05FR-22G C | 80/20 | 0.12 MW | 0.12 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243870 | 05FR-3G C | 80/20 | 0.11 MW | 0.11 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 243873 | 05FR-4G C | 80/20 | 0.27 MW | 0.27 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 274650 | KINCAID ;1U | 80/20 | 5.35 MW | 5.35 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 274651 | KINCAID ;2U | 80/20 | 5.35 MW | 5.35 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 274880 | RADFORD R;1U | 80/20 | 0.4 MW | 0.4 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 924261 | AB2-070 C O1 | 80/20 | 1.34 MW | 1.34 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930461 | AB1-087 CT1 | 80/20 | 78.88 MW | 78.88 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930462 | AB1-087 ST1 | 80/20 | 62.72 MW | 62.72 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930471 | AB1-088 CT1 | 80/20 | 78.88 MW | 78.88 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 930472 | AB1-088 ST1 | 80/20 | 62.72 MW | 62.72 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 933446 | AC2-157 1C | 80/20 | 9.78 MW | 9.78 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 933447 | AC2-157 2C | 80/20 | 9.78 MW | 9.78 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 941341 | AE2-130 C | 80/20 | 123.54 MW | 123.54 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 944221 | AF1-090 C O1 | 80/20 | 2.18 MW | 2.18 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 957381 | AF2-032 C | 80/20 | 0.77 MW | 0.77 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 957141 | AF2-008 FTIR | 80/20 | 128.72 MW | 128.72 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 944201 | AF1-088 FTIR | 80/20 | 257.45 MW | 257.45 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 953401 | J811 | External Queue | 6.61 MW | 6.61 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 953651 | J815 | External Queue | 12.97 MW | 12.97 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 953881 | J848 C | External Queue | 2.08 MW | 2.08 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 954411 | J912 | External Queue | 5.57 MW | 5.57 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 954681 | J949 C | External Queue | 12.19 MW | 12.19 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 956451 | J1139 | External Queue | 7.87 MW | 7.87 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 990056 | J1201 | External Queue | 2.6 MW | 2.6 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 990071 | J1204 | External Queue | 23.9 MW | 23.9 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 990271 | J1263 | External Queue | 39.42 MW | 39.42 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 991196 | J1626 | External Queue | 10.01 MW | 10.01 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 991266 | J1714 | External Queue | 6.68 MW | 6.68 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | 991261 | J1713 C | External Queue | 1.23 MW | 1.23 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 7.02 MW | 7.02 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.29 MW | 0.29 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 28.78 MW | 28.78 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.29 MW | 0.29 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 6.29 MW | 6.29 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.33 MW | 0.33 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.7 MW | 1.7 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.93 MW | 0.93 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.91 MW | 4.91 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 2.12 MW | 2.12 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
05SULLIVAN-16PETE 345.0 kV Ckt 1 line l/o AEP_P1-2_#10136 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.9 MW | 0.9 MW |
Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 963741 | AG1-226 C O1 | Adder | 29.43 MW | 25.01 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 963742 | AG1-226 E O1 | Adder | 10.52 MW | 8.94 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 963831 | AG1-236 C | Adder | 2.05 MW | 1.74 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 963832 | AG1-236 E | Adder | 13.7 MW | 11.65 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 963841 | AG1-237 C O1 | Adder | 2.14 MW | 1.82 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 963842 | AG1-237 E O1 | Adder | 14.36 MW | 12.2 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966841 | AG1-555 C | Adder | 7.05 MW | 6.0 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966842 | AG1-555 E | Adder | 2.52 MW | 2.14 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965331 | AG1-398 | Adder | 0.57 MW | 0.49 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965341 | AG1-399 C | Adder | 3.94 MW | 3.35 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965342 | AG1-399 E | Adder | 18.47 MW | 15.7 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965351 | AG1-400 | Adder | 11.21 MW | 9.53 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965371 | AG1-402 | Adder | 11.21 MW | 9.53 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965391 | AG1-404 | Adder | 7.47 MW | 6.35 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965911 | AG1-460 C | Adder | 1.0 MW | 0.85 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965912 | AG1-460 E | Adder | 1.5 MW | 1.28 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966531 | AG1-522 C | 50/50 | 61.4 MW | 61.4 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966532 | AG1-522 E | 50/50 | 40.93 MW | 40.93 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966541 | AG1-523 C | 50/50 | 61.4 MW | 61.4 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966542 | AG1-523 E | 50/50 | 40.93 MW | 40.93 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966551 | AG1-524 C | 50/50 | 61.4 MW | 61.4 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966552 | AG1-524 E | 50/50 | 40.93 MW | 40.93 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966561 | AG1-525 C | 50/50 | 61.4 MW | 61.4 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966562 | AG1-525 E | 50/50 | 40.93 MW | 40.93 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247900 | 05FR-11G E | Adder | 6.25 MW | 5.31 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247901 | 05FR-12G E | Adder | 6.14 MW | 5.22 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247902 | 05FR-21G E | Adder | 6.57 MW | 5.58 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247903 | 05FR-22G E | Adder | 6.29 MW | 5.34 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247904 | 05FR-3G E | Adder | 12.73 MW | 10.82 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247905 | 05FR-4G E | Adder | 9.97 MW | 8.48 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 925771 | AC1-053 C | Adder | 2.05 MW | 1.74 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 925772 | AC1-053 E | Adder | 13.7 MW | 11.65 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 935141 | AD1-148 | Adder | 2.9 MW | 2.46 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936771 | AD2-100 C | Adder | 10.68 MW | 9.08 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936772 | AD2-100 E | Adder | 7.12 MW | 6.05 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936971 | AD2-131 C | Adder | 0.7 MW | 0.6 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936972 | AD2-131 E | Adder | 3.54 MW | 3.01 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942481 | AE2-261 C | Adder | 14.98 MW | 12.73 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942482 | AE2-261 E | Adder | 9.99 MW | 8.49 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942601 | AE2-276 | 50/50 | 11.79 MW | 11.79 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 945391 | AF1-204 C O1 | 50/50 | 6.54 MW | 6.54 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 945392 | AF1-204 E O1 | 50/50 | 19.61 MW | 19.61 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 945871 | AF1-252 O1 | Adder | 5.53 MW | 4.7 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 945881 | AF1-253 | Adder | 3.83 MW | 3.25 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960141 | AF2-305 | Adder | 0.72 MW | 0.61 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960261 | AF2-317 | Adder | 1.25 MW | 1.06 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 243442 | 05RKG1 | 50/50 | 110.29 MW | 110.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 243443 | 05RKG2 | 50/50 | 105.73 MW | 105.73 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 276615 | W2-048 GEN | Adder | 4.12 MW | 3.5 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 276621 | X2-022 GEN | Adder | 14.77 MW | 12.55 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 293798 | W4-005 E | Adder | 20.43 MW | 17.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 924261 | AB2-070 C O1 | Adder | 2.03 MW | 1.73 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 924262 | AB2-070 E O1 | Adder | 12.32 MW | 10.47 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930461 | AB1-087 CT1 | 50/50 | 72.27 MW | 72.27 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930462 | AB1-087 ST1 | 50/50 | 57.45 MW | 57.45 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930471 | AB1-088 CT1 | 50/50 | 72.27 MW | 72.27 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930472 | AB1-088 ST1 | 50/50 | 57.45 MW | 57.45 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933446 | AC2-157 1C | 50/50 | 8.96 MW | 8.96 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933447 | AC2-157 2C | 50/50 | 8.96 MW | 8.96 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933448 | AC2-157 1E | 50/50 | 14.62 MW | 14.62 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933449 | AC2-157 2E | 50/50 | 14.62 MW | 14.62 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941341 | AE2-130 C | 50/50 | 229.21 MW | 229.21 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941342 | AE2-130 E | 50/50 | 152.81 MW | 152.81 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 944221 | AF1-090 C O1 | Adder | 3.12 MW | 2.65 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 944222 | AF1-090 E O1 | Adder | 14.6 MW | 12.41 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957381 | AF2-032 C | Adder | 1.13 MW | 0.96 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957382 | AF2-032 E | Adder | 0.53 MW | 0.45 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957141 | AF2-008 FTIR | 50/50 | 117.93 MW | 117.93 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 944201 | AF1-088 FTIR | 50/50 | 235.86 MW | 235.86 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957142 | AF2-008 NFTI | 50/50 | 117.93 MW | 117.93 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 990071 | J1204 | External Queue | 19.59 MW | 19.59 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 990271 | J1263 | External Queue | 34.0 MW | 34.0 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.69 MW | 0.69 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 14.9 MW | 14.9 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 51.59 MW | 51.59 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.18 MW | 38.18 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.55 MW | 1.55 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.46 MW | 0.46 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.71 MW | 4.71 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 3.65 MW | 3.65 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.69 MW | 8.69 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.81 MW | 0.81 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.93 MW | 9.93 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.27 MW | 0.27 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 5.32 MW | 5.32 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.2 MW | 2.2 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.64 MW | 1.64 MW |
Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 963741 | AG1-226 C O1 | 50/50 | 41.08 MW | 41.08 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 963742 | AG1-226 E O1 | 50/50 | 14.69 MW | 14.69 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 963841 | AG1-237 C O1 | 50/50 | 3.42 MW | 3.42 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 963842 | AG1-237 E O1 | 50/50 | 22.91 MW | 22.91 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 964401 | AG1-302 C O1 | 50/50 | 23.11 MW | 23.11 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 964402 | AG1-302 E O1 | 50/50 | 15.4 MW | 15.4 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 964861 | AG1-349 C O1 | 50/50 | 20.12 MW | 20.12 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 964862 | AG1-349 E O1 | 50/50 | 13.41 MW | 13.41 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966841 | AG1-555 C | 50/50 | 11.94 MW | 11.94 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966842 | AG1-555 E | 50/50 | 4.27 MW | 4.27 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965681 | AG1-436 C | 50/50 | 8.04 MW | 8.04 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965682 | AG1-436 E | 50/50 | 5.36 MW | 5.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965791 | AG1-447 | 50/50 | 5.89 MW | 5.89 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966531 | AG1-522 C | 50/50 | 42.29 MW | 42.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966532 | AG1-522 E | 50/50 | 28.19 MW | 28.19 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966541 | AG1-523 C | 50/50 | 42.29 MW | 42.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966542 | AG1-523 E | 50/50 | 28.19 MW | 28.19 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966551 | AG1-524 C | 50/50 | 42.29 MW | 42.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966552 | AG1-524 E | 50/50 | 28.19 MW | 28.19 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966561 | AG1-525 C | 50/50 | 42.29 MW | 42.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966562 | AG1-525 E | 50/50 | 28.19 MW | 28.19 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 246909 | 05MDL-1G C | 50/50 | 0.61 MW | 0.61 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 246910 | 05MDL-2G C | 50/50 | 0.36 MW | 0.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 246976 | 05MDL-3G C | 50/50 | 0.36 MW | 0.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 246979 | 05MDL-4G C | 50/50 | 0.28 MW | 0.28 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247556 | 05MDL-5G | 50/50 | 0.48 MW | 0.48 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247900 | 05FR-11G E | 50/50 | 10.57 MW | 10.57 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247901 | 05FR-12G E | 50/50 | 10.4 MW | 10.4 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247902 | 05FR-21G E | 50/50 | 11.12 MW | 11.12 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247903 | 05FR-22G E | 50/50 | 10.64 MW | 10.64 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247904 | 05FR-3G E | 50/50 | 21.55 MW | 21.55 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247905 | 05FR-4G E | 50/50 | 16.88 MW | 16.88 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247906 | 05MDL-1G E | 50/50 | 22.1 MW | 22.1 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247907 | 05MDL-2G E | 50/50 | 11.07 MW | 11.07 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247912 | 05MDL-3G E | 50/50 | 11.07 MW | 11.07 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247913 | 05MDL-4G E | 50/50 | 11.07 MW | 11.07 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 247943 | T-127 E | 50/50 | 11.07 MW | 11.07 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 942601 | AE2-276 | 50/50 | 8.62 MW | 8.62 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 945391 | AF1-204 C O1 | 50/50 | 6.82 MW | 6.82 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 945392 | AF1-204 E O1 | 50/50 | 20.44 MW | 20.44 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 945421 | AF1-207 C O1 | 50/50 | 4.75 MW | 4.75 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 945422 | AF1-207 E O1 | 50/50 | 20.38 MW | 20.38 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 945501 | AF1-215 C O1 | 50/50 | 22.34 MW | 22.34 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 945502 | AF1-215 E O1 | 50/50 | 14.89 MW | 14.89 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 959141 | AF2-205 C | 50/50 | 15.86 MW | 15.86 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 959142 | AF2-205 E | 50/50 | 10.57 MW | 10.57 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960681 | AF2-359 C | 50/50 | 8.04 MW | 8.04 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960682 | AF2-359 E | 50/50 | 5.36 MW | 5.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243441 | 05CKG2 | 50/50 | 21.41 MW | 21.41 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243442 | 05RKG1 | 50/50 | 72.98 MW | 72.98 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243443 | 05RKG2 | 50/50 | 69.96 MW | 69.96 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243859 | 05FR-11G C | 50/50 | 0.59 MW | 0.59 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243862 | 05FR-12G C | 50/50 | 0.29 MW | 0.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243864 | 05FR-21G C | 50/50 | 0.3 MW | 0.3 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243866 | 05FR-22G C | 50/50 | 0.3 MW | 0.3 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243870 | 05FR-3G C | 50/50 | 0.29 MW | 0.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243873 | 05FR-4G C | 50/50 | 0.67 MW | 0.67 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 270100 | X2-052 CT1 | 50/50 | 4.25 MW | 4.25 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 270101 | X2-052 CT2 | 50/50 | 4.25 MW | 4.25 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 270102 | X2-052 ST | 50/50 | 4.59 MW | 4.59 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274772 | LINCOLN ;3U | 50/50 | 1.36 MW | 1.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274774 | LINCOLN ;5U | 50/50 | 1.36 MW | 1.36 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 913222 | Y1-054 E | Adder | -2.28 MW | -1.94 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 930041 | AB1-006 C | 50/50 | 0.61 MW | 0.61 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 930042 | AB1-006 E | 50/50 | 24.07 MW | 24.07 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 930461 | AB1-087 CT1 | 50/50 | 52.82 MW | 52.82 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 930462 | AB1-087 ST1 | 50/50 | 42.0 MW | 42.0 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 930471 | AB1-088 CT1 | 50/50 | 52.82 MW | 52.82 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 930472 | AB1-088 ST1 | 50/50 | 42.0 MW | 42.0 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933281 | AC2-140 C | 50/50 | 0.71 MW | 0.71 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933282 | AC2-140 E | 50/50 | 0.22 MW | 0.22 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933446 | AC2-157 1C | 50/50 | 6.55 MW | 6.55 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933447 | AC2-157 2C | 50/50 | 6.55 MW | 6.55 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933448 | AC2-157 1E | 50/50 | 10.69 MW | 10.69 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933449 | AC2-157 2E | 50/50 | 10.69 MW | 10.69 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 940581 | AE2-045 C O1 | 50/50 | 11.3 MW | 11.3 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 940582 | AE2-045 E O1 | 50/50 | 15.52 MW | 15.52 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 941341 | AE2-130 C | 50/50 | 151.67 MW | 151.67 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 941342 | AE2-130 E | 50/50 | 101.11 MW | 101.11 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 946581 | AF1-322 C | 50/50 | 11.62 MW | 11.62 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 946582 | AF1-322 E | 50/50 | 16.05 MW | 16.05 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957841 | AF2-078 C O1 | 50/50 | 16.75 MW | 16.75 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957842 | AF2-078 E O1 | 50/50 | 11.16 MW | 11.16 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958381 | AF2-132 C O1 | 50/50 | 23.11 MW | 23.11 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958382 | AF2-132 E O1 | 50/50 | 15.4 MW | 15.4 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958391 | AF2-133 C O1 | 50/50 | 23.5 MW | 23.5 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958392 | AF2-133 E O1 | 50/50 | 15.67 MW | 15.67 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958401 | AF2-134 C O1 | 50/50 | 7.45 MW | 7.45 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958402 | AF2-134 E O1 | 50/50 | 4.96 MW | 4.96 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 251823 | Z1-065 BAT | 50/50 | 0.65 MW | 0.65 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 250163 | Y3-099 BAT | 50/50 | 0.23 MW | 0.23 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957141 | AF2-008 FTIR | 50/50 | 86.2 MW | 86.2 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 944201 | AF1-088 FTIR | 50/50 | 172.4 MW | 172.4 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957142 | AF2-008 NFTI | 50/50 | 86.2 MW | 86.2 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.55 MW | 1.55 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 29.62 MW | 29.62 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.93 MW | 0.93 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 96.84 MW | 96.84 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 28.41 MW | 28.41 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.94 MW | 0.94 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.01 MW | 2.01 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.16 MW | 1.16 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.02 MW | 3.02 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 6.44 MW | 6.44 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.29 MW | 12.29 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.02 MW | 1.02 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.88 MW | 12.88 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 10.31 MW | 10.31 MW |
05JEFRSO-06CLIFTY 345.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.02 MW | 3.02 MW |
Details for 05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 966531 | AG1-522 C | 50/50 | 91.68 MW | 91.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 966532 | AG1-522 E | 50/50 | 61.12 MW | 61.12 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 966541 | AG1-523 C | 50/50 | 91.68 MW | 91.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 966542 | AG1-523 E | 50/50 | 61.12 MW | 61.12 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 966551 | AG1-524 C | 50/50 | 91.68 MW | 91.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 966552 | AG1-524 E | 50/50 | 61.12 MW | 61.12 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 966561 | AG1-525 C | 50/50 | 91.68 MW | 91.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 966562 | AG1-525 E | 50/50 | 61.12 MW | 61.12 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 936771 | AD2-100 C | 50/50 | 12.84 MW | 12.84 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 936772 | AD2-100 E | 50/50 | 8.56 MW | 8.56 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 936971 | AD2-131 C | 50/50 | 0.85 MW | 0.85 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 936972 | AD2-131 E | 50/50 | 4.25 MW | 4.25 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 942601 | AE2-276 | 50/50 | 19.51 MW | 19.51 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 945871 | AF1-252 O1 | 50/50 | 6.9 MW | 6.9 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 945881 | AF1-253 | 50/50 | 4.78 MW | 4.78 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 243442 | 05RKG1 | 50/50 | 153.28 MW | 153.28 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 243443 | 05RKG2 | 50/50 | 146.94 MW | 146.94 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 930461 | AB1-087 CT1 | 50/50 | 119.58 MW | 119.58 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 930462 | AB1-087 ST1 | 50/50 | 95.07 MW | 95.07 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 930471 | AB1-088 CT1 | 50/50 | 119.58 MW | 119.58 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 930472 | AB1-088 ST1 | 50/50 | 95.07 MW | 95.07 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 933446 | AC2-157 1C | 50/50 | 14.83 MW | 14.83 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 933447 | AC2-157 2C | 50/50 | 14.83 MW | 14.83 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 933448 | AC2-157 1E | 50/50 | 24.2 MW | 24.2 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 933449 | AC2-157 2E | 50/50 | 24.2 MW | 24.2 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 941341 | AE2-130 C | 50/50 | 318.55 MW | 318.55 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 941342 | AE2-130 E | 50/50 | 212.37 MW | 212.37 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 944221 | AF1-090 C O1 | 50/50 | 3.89 MW | 3.89 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 944222 | AF1-090 E O1 | 50/50 | 18.23 MW | 18.23 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 957141 | AF2-008 FTIR | 50/50 | 195.14 MW | 195.14 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 944201 | AF1-088 FTIR | 50/50 | 390.28 MW | 390.28 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 957142 | AF2-008 NFTI | 50/50 | 195.14 MW | 195.14 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 954681 | J949 C | External Queue | 17.31 MW | 17.31 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 990071 | J1204 | External Queue | 33.66 MW | 33.66 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | 990271 | J1263 | External Queue | 55.59 MW | 55.59 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.4 MW | 0.4 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.62 MW | 0.62 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.22 MW | 1.22 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.11 MW | 0.11 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 41.54 MW | 41.54 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 61.26 MW | 61.26 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.86 MW | 1.86 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.17 MW | 0.17 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.24 MW | 8.24 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.95 MW | 0.95 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.33 MW | 9.33 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.99 MW | 0.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 11.96 MW | 11.96 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.84 MW | 0.84 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.4 MW | 5.4 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8906_05SULLIVAN 345_C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.25 MW | 1.25 MW |
Details for 05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 965911 | AG1-460 C | 50/50 | 1.23 MW | 1.23 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 965912 | AG1-460 E | 50/50 | 1.85 MW | 1.85 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 966531 | AG1-522 C | 50/50 | 83.98 MW | 83.98 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 966532 | AG1-522 E | 50/50 | 55.99 MW | 55.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 966541 | AG1-523 C | 50/50 | 83.98 MW | 83.98 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 966542 | AG1-523 E | 50/50 | 55.99 MW | 55.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 966551 | AG1-524 C | 50/50 | 83.98 MW | 83.98 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 966552 | AG1-524 E | 50/50 | 55.99 MW | 55.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 966561 | AG1-525 C | 50/50 | 83.98 MW | 83.98 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 966562 | AG1-525 E | 50/50 | 55.99 MW | 55.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 936771 | AD2-100 C | 50/50 | 13.28 MW | 13.28 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 936772 | AD2-100 E | 50/50 | 8.85 MW | 8.85 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 936971 | AD2-131 C | 50/50 | 0.88 MW | 0.88 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 936972 | AD2-131 E | 50/50 | 4.39 MW | 4.39 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 942481 | AE2-261 C | 50/50 | 18.45 MW | 18.45 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 942482 | AE2-261 E | 50/50 | 12.3 MW | 12.3 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 942601 | AE2-276 | 50/50 | 16.83 MW | 16.83 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 945391 | AF1-204 C O1 | 50/50 | 8.17 MW | 8.17 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 945392 | AF1-204 E O1 | 50/50 | 24.51 MW | 24.51 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 945871 | AF1-252 O1 | 50/50 | 7.04 MW | 7.04 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 945881 | AF1-253 | 50/50 | 4.87 MW | 4.87 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 243442 | 05RKG1 | 50/50 | 146.71 MW | 146.71 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 243443 | 05RKG2 | 50/50 | 140.64 MW | 140.64 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 274650 | KINCAID ;1U | 50/50 | 9.65 MW | 9.65 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 274651 | KINCAID ;2U | 50/50 | 9.65 MW | 9.65 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 930461 | AB1-087 CT1 | 50/50 | 103.11 MW | 103.11 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 930462 | AB1-087 ST1 | 50/50 | 81.97 MW | 81.97 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 930471 | AB1-088 CT1 | 50/50 | 103.11 MW | 103.11 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 930472 | AB1-088 ST1 | 50/50 | 81.97 MW | 81.97 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 933446 | AC2-157 1C | 50/50 | 12.79 MW | 12.79 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 933447 | AC2-157 2C | 50/50 | 12.79 MW | 12.79 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 933448 | AC2-157 1E | 50/50 | 20.86 MW | 20.86 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 933449 | AC2-157 2E | 50/50 | 20.86 MW | 20.86 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 941341 | AE2-130 C | 50/50 | 304.89 MW | 304.89 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 941342 | AE2-130 E | 50/50 | 203.26 MW | 203.26 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 944221 | AF1-090 C O1 | 50/50 | 3.97 MW | 3.97 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 944222 | AF1-090 E O1 | 50/50 | 18.58 MW | 18.58 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 957381 | AF2-032 C | 50/50 | 1.39 MW | 1.39 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 957382 | AF2-032 E | 50/50 | 0.65 MW | 0.65 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 957141 | AF2-008 FTIR | 50/50 | 168.26 MW | 168.26 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 944201 | AF1-088 FTIR | 50/50 | 336.51 MW | 336.51 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 957142 | AF2-008 NFTI | 50/50 | 168.26 MW | 168.26 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 954681 | J949 C | External Queue | 17.39 MW | 17.39 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 990071 | J1204 | External Queue | 29.87 MW | 29.87 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | 990271 | J1263 | External Queue | 51.8 MW | 51.8 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.5 MW | 0.5 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.07 MW | 1.07 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.14 MW | 1.14 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 46.29 MW | 46.29 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 61.24 MW | 61.24 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.92 MW | 1.92 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.25 MW | 0.25 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.99 MW | 7.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.99 MW | 0.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.03 MW | 0.03 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.68 MW | 9.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.01 MW | 1.01 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.34 MW | 12.34 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.82 MW | 0.82 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.13 MW | 5.13 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P4_#8910_05DEQUIN 345_C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.39 MW | 1.39 MW |
Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 963741 | AG1-226 C O1 | Adder | 29.43 MW | 25.01 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 963742 | AG1-226 E O1 | Adder | 10.52 MW | 8.94 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 963831 | AG1-236 C | Adder | 2.05 MW | 1.74 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 963832 | AG1-236 E | Adder | 13.7 MW | 11.65 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 963841 | AG1-237 C O1 | Adder | 2.14 MW | 1.82 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 963842 | AG1-237 E O1 | Adder | 14.36 MW | 12.2 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966841 | AG1-555 C | Adder | 7.05 MW | 6.0 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966842 | AG1-555 E | Adder | 2.52 MW | 2.14 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 965331 | AG1-398 | Adder | 0.57 MW | 0.49 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 965341 | AG1-399 C | Adder | 3.94 MW | 3.35 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 965342 | AG1-399 E | Adder | 18.47 MW | 15.7 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 965351 | AG1-400 | Adder | 11.21 MW | 9.53 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 965371 | AG1-402 | Adder | 11.21 MW | 9.53 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 965391 | AG1-404 | Adder | 7.47 MW | 6.35 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 965911 | AG1-460 C | Adder | 1.0 MW | 0.85 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 965912 | AG1-460 E | Adder | 1.5 MW | 1.28 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966531 | AG1-522 C | 50/50 | 61.4 MW | 61.4 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966532 | AG1-522 E | 50/50 | 40.93 MW | 40.93 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966541 | AG1-523 C | 50/50 | 61.4 MW | 61.4 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966542 | AG1-523 E | 50/50 | 40.93 MW | 40.93 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966551 | AG1-524 C | 50/50 | 61.4 MW | 61.4 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966552 | AG1-524 E | 50/50 | 40.93 MW | 40.93 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966561 | AG1-525 C | 50/50 | 61.4 MW | 61.4 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 966562 | AG1-525 E | 50/50 | 40.93 MW | 40.93 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 247900 | 05FR-11G E | Adder | 6.25 MW | 5.31 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 247901 | 05FR-12G E | Adder | 6.14 MW | 5.22 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 247902 | 05FR-21G E | Adder | 6.57 MW | 5.58 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 247903 | 05FR-22G E | Adder | 6.29 MW | 5.34 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 247904 | 05FR-3G E | Adder | 12.73 MW | 10.82 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 247905 | 05FR-4G E | Adder | 9.97 MW | 8.48 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 925771 | AC1-053 C | Adder | 2.05 MW | 1.74 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 925772 | AC1-053 E | Adder | 13.7 MW | 11.65 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 935141 | AD1-148 | Adder | 2.9 MW | 2.46 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 936771 | AD2-100 C | Adder | 10.68 MW | 9.08 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 936772 | AD2-100 E | Adder | 7.12 MW | 6.05 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 936971 | AD2-131 C | Adder | 0.7 MW | 0.6 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 936972 | AD2-131 E | Adder | 3.54 MW | 3.01 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 942481 | AE2-261 C | Adder | 14.98 MW | 12.73 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 942482 | AE2-261 E | Adder | 9.99 MW | 8.49 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 942601 | AE2-276 | 50/50 | 11.79 MW | 11.79 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 945391 | AF1-204 C O1 | 50/50 | 6.54 MW | 6.54 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 945392 | AF1-204 E O1 | 50/50 | 19.61 MW | 19.61 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 945871 | AF1-252 O1 | Adder | 5.53 MW | 4.7 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 945881 | AF1-253 | Adder | 3.83 MW | 3.25 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 960141 | AF2-305 | Adder | 0.72 MW | 0.61 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 960261 | AF2-317 | Adder | 1.25 MW | 1.06 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 243442 | 05RKG1 | 50/50 | 110.29 MW | 110.29 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 243443 | 05RKG2 | 50/50 | 105.73 MW | 105.73 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 276615 | W2-048 GEN | Adder | 4.12 MW | 3.5 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 276621 | X2-022 GEN | Adder | 14.77 MW | 12.55 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 293798 | W4-005 E | Adder | 20.43 MW | 17.36 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 924261 | AB2-070 C O1 | Adder | 2.03 MW | 1.73 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 924262 | AB2-070 E O1 | Adder | 12.32 MW | 10.47 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 930461 | AB1-087 CT1 | 50/50 | 72.27 MW | 72.27 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 930462 | AB1-087 ST1 | 50/50 | 57.45 MW | 57.45 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 930471 | AB1-088 CT1 | 50/50 | 72.27 MW | 72.27 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 930472 | AB1-088 ST1 | 50/50 | 57.45 MW | 57.45 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 933446 | AC2-157 1C | 50/50 | 8.96 MW | 8.96 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 933447 | AC2-157 2C | 50/50 | 8.96 MW | 8.96 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 933448 | AC2-157 1E | 50/50 | 14.62 MW | 14.62 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 933449 | AC2-157 2E | 50/50 | 14.62 MW | 14.62 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 941341 | AE2-130 C | 50/50 | 229.21 MW | 229.21 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 941342 | AE2-130 E | 50/50 | 152.81 MW | 152.81 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 944221 | AF1-090 C O1 | Adder | 3.12 MW | 2.65 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 944222 | AF1-090 E O1 | Adder | 14.6 MW | 12.41 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 957381 | AF2-032 C | Adder | 1.13 MW | 0.96 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 957382 | AF2-032 E | Adder | 0.53 MW | 0.45 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 957141 | AF2-008 FTIR | 50/50 | 117.93 MW | 117.93 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 944201 | AF1-088 FTIR | 50/50 | 235.86 MW | 235.86 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 957142 | AF2-008 NFTI | 50/50 | 117.93 MW | 117.93 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 990071 | J1204 | External Queue | 19.59 MW | 19.59 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | 990271 | J1263 | External Queue | 34.0 MW | 34.0 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.69 MW | 0.69 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 14.9 MW | 14.9 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.24 MW | 0.24 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 51.59 MW | 51.59 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.18 MW | 38.18 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.55 MW | 1.55 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.46 MW | 0.46 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.71 MW | 4.71 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 3.65 MW | 3.65 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.69 MW | 8.69 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.81 MW | 0.81 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.93 MW | 9.93 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.27 MW | 0.27 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 5.32 MW | 5.32 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.2 MW | 2.2 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.64 MW | 1.64 MW |
Details for 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963741 | AG1-226 C O1 | 50/50 | 175.72 MW | 175.72 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963742 | AG1-226 E O1 | 50/50 | 62.81 MW | 62.81 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963831 | AG1-236 C | Adder | 2.34 MW | 1.99 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963832 | AG1-236 E | Adder | 15.67 MW | 13.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963841 | AG1-237 C O1 | 50/50 | 13.78 MW | 13.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963842 | AG1-237 E O1 | 50/50 | 92.23 MW | 92.23 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 964581 | AG1-321 C O1 | Adder | 7.38 MW | 6.28 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 964582 | AG1-321 E O1 | Adder | 4.3 MW | 3.65 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965091 | AG1-374 C | Adder | 13.61 MW | 11.57 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965092 | AG1-374 E | Adder | 9.08 MW | 7.71 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965331 | AG1-398 | Adder | 0.67 MW | 0.57 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965341 | AG1-399 C | Adder | 4.45 MW | 3.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965342 | AG1-399 E | Adder | 20.83 MW | 17.7 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965351 | AG1-400 | Adder | 12.64 MW | 10.74 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965371 | AG1-402 | Adder | 12.64 MW | 10.74 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965391 | AG1-404 | Adder | 8.43 MW | 7.16 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965911 | AG1-460 C | Adder | 0.99 MW | 0.84 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965912 | AG1-460 E | Adder | 1.48 MW | 1.26 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966531 | AG1-522 C | Adder | 15.09 MW | 12.83 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966532 | AG1-522 E | Adder | 10.06 MW | 8.55 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966541 | AG1-523 C | Adder | 15.09 MW | 12.83 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966542 | AG1-523 E | Adder | 10.06 MW | 8.55 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966551 | AG1-524 C | Adder | 15.09 MW | 12.83 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966552 | AG1-524 E | Adder | 10.06 MW | 8.55 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966561 | AG1-525 C | Adder | 15.09 MW | 12.83 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966562 | AG1-525 E | Adder | 10.06 MW | 8.55 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 290261 | S-027 E | Adder | 11.98 MW | 10.18 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 290265 | S-028 E | Adder | 11.98 MW | 10.18 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 925771 | AC1-053 C | Adder | 2.34 MW | 1.99 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 925772 | AC1-053 E | Adder | 15.67 MW | 13.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 935141 | AD1-148 | Adder | 3.19 MW | 2.71 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 936771 | AD2-100 C | Adder | 10.29 MW | 8.75 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 936772 | AD2-100 E | Adder | 6.86 MW | 5.83 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 936971 | AD2-131 C | Adder | 0.68 MW | 0.58 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 936972 | AD2-131 E | Adder | 3.41 MW | 2.9 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942111 | AE2-223 C | Adder | 1.44 MW | 1.23 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942112 | AE2-223 E | Adder | 9.65 MW | 8.21 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942481 | AE2-261 C | Adder | 14.79 MW | 12.57 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942482 | AE2-261 E | Adder | 9.86 MW | 8.38 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942601 | AE2-276 | 50/50 | 5.41 MW | 5.41 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942791 | AE2-297 C O1 | Adder | -4.6 MW | -3.91 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 945391 | AF1-204 C O1 | 50/50 | 33.79 MW | 33.79 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 945392 | AF1-204 E O1 | 50/50 | 101.38 MW | 101.38 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 945871 | AF1-252 O1 | Adder | 4.96 MW | 4.21 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 945881 | AF1-253 | Adder | 3.43 MW | 2.92 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 959341 | AF2-225 C | Adder | 4.66 MW | 3.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 959342 | AF2-225 E | Adder | 6.44 MW | 5.47 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 959611 | AF2-252 C | Adder | 1.51 MW | 1.29 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 959612 | AF2-252 E | Adder | 2.27 MW | 1.93 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 960141 | AF2-305 | Adder | 0.84 MW | 0.71 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 960261 | AF2-317 | Adder | 1.38 MW | 1.17 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 960611 | AF2-352 C | Adder | 1.51 MW | 1.29 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 960612 | AF2-352 E | Adder | 2.27 MW | 1.93 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 276615 | W2-048 GEN | Adder | 4.53 MW | 3.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 276621 | X2-022 GEN | Adder | 16.25 MW | 13.81 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 293777 | CAYUG;1U E | Adder | 6.36 MW | 5.41 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 293778 | CAYUG;2U E | Adder | 6.36 MW | 5.41 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 293798 | W4-005 E | Adder | 23.9 MW | 20.31 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 917502 | Z2-087 E | Adder | 12.87 MW | 10.94 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 924042 | AB2-047 E O1 | Adder | 16.09 MW | 13.67 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 924261 | AB2-070 C O1 | Adder | 2.37 MW | 2.01 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 924262 | AB2-070 E O1 | Adder | 14.35 MW | 12.2 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 930461 | AB1-087 CT1 | 50/50 | 33.16 MW | 33.16 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 930462 | AB1-087 ST1 | 50/50 | 26.37 MW | 26.37 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 930471 | AB1-088 CT1 | 50/50 | 33.16 MW | 33.16 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 930472 | AB1-088 ST1 | 50/50 | 26.37 MW | 26.37 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 933446 | AC2-157 1C | 50/50 | 4.11 MW | 4.11 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 933447 | AC2-157 2C | 50/50 | 4.11 MW | 4.11 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 933448 | AC2-157 1E | 50/50 | 6.71 MW | 6.71 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 933449 | AC2-157 2E | 50/50 | 6.71 MW | 6.71 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 939741 | AE1-205 C O1 | Adder | 6.21 MW | 5.28 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 939742 | AE1-205 E O1 | Adder | 8.58 MW | 7.29 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 941341 | AE2-130 C | Adder | 25.05 MW | 21.29 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 941342 | AE2-130 E | Adder | 16.7 MW | 14.19 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 941731 | AE2-173 O1 | Adder | 3.7 MW | 3.14 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 944221 | AF1-090 C O1 | Adder | 2.8 MW | 2.38 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 944222 | AF1-090 E O1 | Adder | 13.09 MW | 11.13 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 957381 | AF2-032 C | Adder | 1.13 MW | 0.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 957382 | AF2-032 E | Adder | 0.53 MW | 0.45 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 961162 | AF2-407 BAT | Adder | 25.03 MW | 21.27 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 964353 | AG1-297 BAT | Adder | 37.19 MW | 31.61 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 957141 | AF2-008 FTIR | 50/50 | 54.12 MW | 54.12 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 944201 | AF1-088 FTIR | 50/50 | 108.24 MW | 108.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 957142 | AF2-008 NFTI | 50/50 | 54.12 MW | 54.12 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 961172 | AF2-408 BAT | Adder | 5.88 MW | 5.0 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 953741 | J826 C | External Queue | 2.37 MW | 2.37 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 953742 | J826 E | External Queue | 12.85 MW | 12.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 953851 | J845 C | External Queue | 2.98 MW | 2.98 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 953852 | J845 E | External Queue | 16.1 MW | 16.1 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 954681 | J949 C | External Queue | 12.72 MW | 12.72 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 954821 | J955 | External Queue | 73.5 MW | 73.5 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 955402 | J1022 E | External Queue | 22.84 MW | 22.84 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 956151 | J1102 | External Queue | 4.93 MW | 4.93 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 956281 | J1115 C | External Queue | 3.01 MW | 3.01 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 956282 | J1115 E | External Queue | 16.26 MW | 16.26 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 956451 | J1139 | External Queue | 29.98 MW | 29.98 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 990071 | J1204 | External Queue | 14.34 MW | 14.34 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 990271 | J1263 | External Queue | 9.29 MW | 9.29 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 990672 | J1360 E | External Queue | 47.19 MW | 47.19 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 991236 | J1676 C | External Queue | 4.53 MW | 4.53 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 991237 | J1676 E | External Queue | 24.5 MW | 24.5 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 991261 | J1713 C | External Queue | 1.8 MW | 1.8 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 991262 | J1713 E | External Queue | 9.76 MW | 9.76 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.38 MW | 3.38 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.38 MW | 0.38 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 26.14 MW | 26.14 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.81 MW | 4.81 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.59 MW | 0.59 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 2.47 MW | 2.47 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.03 MW | 0.03 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.18 MW | 3.18 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.64 MW | 0.64 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.97 MW | 5.97 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.81 MW | 3.81 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.03 MW | 1.03 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.44 MW | 1.44 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.0 MW | 1.0 MW |
Details for AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 966531 | AG1-522 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 966532 | AG1-522 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 966541 | AG1-523 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 966542 | AG1-523 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 966551 | AG1-524 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 966552 | AG1-524 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 966561 | AG1-525 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 966562 | AG1-525 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 243442 | 05RKG1 | 50/50 | 227.8 MW | 227.8 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 243443 | 05RKG2 | 50/50 | 218.37 MW | 218.37 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 941341 | AE2-130 C | 50/50 | 473.41 MW | 473.41 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | 941342 | AE2-130 E | 50/50 | 315.61 MW | 315.61 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.03 MW | 1.03 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.38 MW | 2.38 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.68 MW | 0.68 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.48 MW | 0.48 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.69 MW | 0.69 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.88 MW | 2.88 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.44 MW | 1.44 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.75 MW | 0.75 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.79 MW | 0.79 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.76 MW | 0.76 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.24 MW | 9.24 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.55 MW | 3.55 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#9336_05ROCKPT 765_C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.76 MW | 0.76 MW |
Details for AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 966531 | AG1-522 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 966532 | AG1-522 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 966541 | AG1-523 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 966542 | AG1-523 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 966551 | AG1-524 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 966552 | AG1-524 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 966561 | AG1-525 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 966562 | AG1-525 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 243442 | 05RKG1 | 50/50 | 227.8 MW | 227.8 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 243443 | 05RKG2 | 50/50 | 218.37 MW | 218.37 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 941341 | AE2-130 C | 50/50 | 473.41 MW | 473.41 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | 941342 | AE2-130 E | 50/50 | 315.61 MW | 315.61 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.03 MW | 1.03 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.38 MW | 2.38 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.68 MW | 0.68 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.48 MW | 0.48 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.69 MW | 0.69 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.88 MW | 2.88 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.44 MW | 1.44 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.75 MW | 0.75 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.79 MW | 0.79 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.76 MW | 0.76 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.24 MW | 9.24 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.55 MW | 3.55 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#3002_05ROCKPT 765_C2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.76 MW | 0.76 MW |
Details for AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966531 | AG1-522 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966532 | AG1-522 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966541 | AG1-523 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966542 | AG1-523 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966551 | AG1-524 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966552 | AG1-524 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966561 | AG1-525 C | 50/50 | 177.53 MW | 177.53 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 966562 | AG1-525 E | 50/50 | 118.35 MW | 118.35 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 243442 | 05RKG1 | 50/50 | 227.8 MW | 227.8 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 243443 | 05RKG2 | 50/50 | 218.37 MW | 218.37 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 941341 | AE2-130 C | 50/50 | 473.41 MW | 473.41 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | 941342 | AE2-130 E | 50/50 | 315.61 MW | 315.61 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.03 MW | 1.03 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.38 MW | 2.38 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.68 MW | 0.68 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.48 MW | 0.48 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.69 MW | 0.69 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.88 MW | 2.88 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.44 MW | 1.44 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.75 MW | 0.75 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.79 MW | 0.79 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.76 MW | 0.76 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.24 MW | 9.24 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.55 MW | 3.55 MW |
AG1-522 TAP-05SULLIVAN 765.0 kV Ckt 1 line l/o AEP_P4_#8648_05JEFRSO 765_B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.76 MW | 0.76 MW |
Details for 06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 964571 | AG1-320 C O1 | Adder | 2.91 MW | 2.47 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 964572 | AG1-320 E O1 | Adder | 1.44 MW | 1.23 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966531 | AG1-522 C | Adder | 15.34 MW | 13.04 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966532 | AG1-522 E | Adder | 10.23 MW | 8.7 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966541 | AG1-523 C | Adder | 15.34 MW | 13.04 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966542 | AG1-523 E | Adder | 10.23 MW | 8.7 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966551 | AG1-524 C | Adder | 15.34 MW | 13.04 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966552 | AG1-524 E | Adder | 10.23 MW | 8.7 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966561 | AG1-525 C | Adder | 15.34 MW | 13.04 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966562 | AG1-525 E | Adder | 10.23 MW | 8.7 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942601 | AE2-276 | Adder | 3.03 MW | 2.58 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 959691 | AF2-260 C | Adder | 2.88 MW | 2.45 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 959692 | AF2-260 E | Adder | 1.74 MW | 1.48 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960171 | AF2-308 | Adder | 1.54 MW | 1.31 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960181 | AF2-309 C | Adder | 2.3 MW | 1.96 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960182 | AF2-309 E | Adder | 1.54 MW | 1.31 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 961001 | AF2-391 C O1 | Adder | 4.14 MW | 3.52 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 961002 | AF2-391 E O1 | Adder | 2.76 MW | 2.35 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930461 | AB1-087 CT1 | Adder | 18.57 MW | 15.78 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930462 | AB1-087 ST1 | Adder | 14.76 MW | 12.55 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930471 | AB1-088 CT1 | Adder | 18.57 MW | 15.78 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930472 | AB1-088 ST1 | Adder | 14.76 MW | 12.55 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933446 | AC2-157 1C | Adder | 2.3 MW | 1.96 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933447 | AC2-157 2C | Adder | 2.3 MW | 1.96 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933448 | AC2-157 1E | Adder | 3.76 MW | 3.19 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933449 | AC2-157 2E | Adder | 3.76 MW | 3.19 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941341 | AE2-130 C | Adder | 56.25 MW | 47.81 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941342 | AE2-130 E | Adder | 37.5 MW | 31.87 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957961 | AF2-090 C | Adder | 4.35 MW | 3.7 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957962 | AF2-090 E | Adder | 2.15 MW | 1.83 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248014 | 06CLIFTY 1HP | 50/50 | 4.07 MW | 4.07 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248015 | 06CLIFTY 1LP | 50/50 | 2.39 MW | 2.39 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248016 | 06CLIFTY 2HP | 50/50 | 4.07 MW | 4.07 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248017 | 06CLIFTY 2LP | 50/50 | 2.39 MW | 2.39 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248018 | 06CLIFTY 3HP | 50/50 | 4.07 MW | 4.07 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248019 | 06CLIFTY 3LP | 50/50 | 2.39 MW | 2.39 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248020 | 06CLIFTY 4HP | 50/50 | 4.07 MW | 4.07 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248021 | 06CLIFTY 4LP | 50/50 | 2.39 MW | 2.39 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248022 | 06CLIFTY 5HP | 50/50 | 4.07 MW | 4.07 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248023 | 06CLIFTY 5LP | 50/50 | 2.39 MW | 2.39 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248024 | 06CLIFTY 6HP | 50/50 | 4.07 MW | 4.07 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 248025 | 06CLIFTY 6LP | 50/50 | 2.39 MW | 2.39 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957141 | AF2-008 FTIR | Adder | 35.65 MW | 30.3 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 944201 | AF1-088 FTIR | Adder | 71.3 MW | 60.6 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957142 | AF2-008 NFTI | Adder | 35.65 MW | 30.3 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.24 MW | 1.24 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.53 MW | 8.53 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 14.49 MW | 14.49 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 20.76 MW | 20.76 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.39 MW | 0.39 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.25 MW | 0.25 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.58 MW | 3.58 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 5.18 MW | 5.18 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.62 MW | 2.62 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.59 MW | 1.59 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.44 MW | 0.44 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.02 MW | 3.02 MW |
06CLIFTY-06DEARB1 345.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 963741 | AG1-226 C O1 | 50/50 | 41.08 MW | 41.08 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 963742 | AG1-226 E O1 | 50/50 | 14.69 MW | 14.69 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 963841 | AG1-237 C O1 | 50/50 | 3.42 MW | 3.42 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 963842 | AG1-237 E O1 | 50/50 | 22.91 MW | 22.91 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 964401 | AG1-302 C O1 | 50/50 | 23.11 MW | 23.11 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 964402 | AG1-302 E O1 | 50/50 | 15.4 MW | 15.4 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 964861 | AG1-349 C O1 | 50/50 | 20.12 MW | 20.12 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 964862 | AG1-349 E O1 | 50/50 | 13.41 MW | 13.41 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966841 | AG1-555 C | 50/50 | 11.94 MW | 11.94 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966842 | AG1-555 E | 50/50 | 4.27 MW | 4.27 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 965681 | AG1-436 C | 50/50 | 8.04 MW | 8.04 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 965682 | AG1-436 E | 50/50 | 5.36 MW | 5.36 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 965791 | AG1-447 | 50/50 | 5.89 MW | 5.89 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966531 | AG1-522 C | 50/50 | 42.29 MW | 42.29 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966532 | AG1-522 E | 50/50 | 28.19 MW | 28.19 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966541 | AG1-523 C | 50/50 | 42.29 MW | 42.29 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966542 | AG1-523 E | 50/50 | 28.19 MW | 28.19 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966551 | AG1-524 C | 50/50 | 42.29 MW | 42.29 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966552 | AG1-524 E | 50/50 | 28.19 MW | 28.19 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966561 | AG1-525 C | 50/50 | 42.29 MW | 42.29 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 966562 | AG1-525 E | 50/50 | 28.19 MW | 28.19 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 246909 | 05MDL-1G C | 50/50 | 0.61 MW | 0.61 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 246910 | 05MDL-2G C | 50/50 | 0.36 MW | 0.36 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 246976 | 05MDL-3G C | 50/50 | 0.36 MW | 0.36 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 246979 | 05MDL-4G C | 50/50 | 0.28 MW | 0.28 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247556 | 05MDL-5G | 50/50 | 0.48 MW | 0.48 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247900 | 05FR-11G E | 50/50 | 10.57 MW | 10.57 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247901 | 05FR-12G E | 50/50 | 10.4 MW | 10.4 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247902 | 05FR-21G E | 50/50 | 11.12 MW | 11.12 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247903 | 05FR-22G E | 50/50 | 10.64 MW | 10.64 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247904 | 05FR-3G E | 50/50 | 21.55 MW | 21.55 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247905 | 05FR-4G E | 50/50 | 16.88 MW | 16.88 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247906 | 05MDL-1G E | 50/50 | 22.1 MW | 22.1 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247907 | 05MDL-2G E | 50/50 | 11.07 MW | 11.07 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247912 | 05MDL-3G E | 50/50 | 11.07 MW | 11.07 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247913 | 05MDL-4G E | 50/50 | 11.07 MW | 11.07 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 247943 | T-127 E | 50/50 | 11.07 MW | 11.07 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 942601 | AE2-276 | 50/50 | 8.62 MW | 8.62 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 945391 | AF1-204 C O1 | 50/50 | 6.82 MW | 6.82 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 945392 | AF1-204 E O1 | 50/50 | 20.44 MW | 20.44 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 945421 | AF1-207 C O1 | 50/50 | 4.75 MW | 4.75 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 945422 | AF1-207 E O1 | 50/50 | 20.38 MW | 20.38 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 945501 | AF1-215 C O1 | 50/50 | 22.34 MW | 22.34 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 945502 | AF1-215 E O1 | 50/50 | 14.89 MW | 14.89 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 959141 | AF2-205 C | 50/50 | 15.86 MW | 15.86 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 959142 | AF2-205 E | 50/50 | 10.57 MW | 10.57 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 960681 | AF2-359 C | 50/50 | 8.04 MW | 8.04 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 960682 | AF2-359 E | 50/50 | 5.36 MW | 5.36 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243441 | 05CKG2 | 50/50 | 21.41 MW | 21.41 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243442 | 05RKG1 | 50/50 | 72.98 MW | 72.98 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243443 | 05RKG2 | 50/50 | 69.96 MW | 69.96 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243859 | 05FR-11G C | 50/50 | 0.59 MW | 0.59 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243862 | 05FR-12G C | 50/50 | 0.29 MW | 0.29 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243864 | 05FR-21G C | 50/50 | 0.3 MW | 0.3 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243866 | 05FR-22G C | 50/50 | 0.3 MW | 0.3 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243870 | 05FR-3G C | 50/50 | 0.29 MW | 0.29 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 243873 | 05FR-4G C | 50/50 | 0.67 MW | 0.67 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 270100 | X2-052 CT1 | 50/50 | 4.25 MW | 4.25 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 270101 | X2-052 CT2 | 50/50 | 4.25 MW | 4.25 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 270102 | X2-052 ST | 50/50 | 4.59 MW | 4.59 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 274772 | LINCOLN ;3U | 50/50 | 1.36 MW | 1.36 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 274774 | LINCOLN ;5U | 50/50 | 1.36 MW | 1.36 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 913222 | Y1-054 E | Adder | -2.28 MW | -1.94 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 930041 | AB1-006 C | 50/50 | 0.61 MW | 0.61 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 930042 | AB1-006 E | 50/50 | 24.07 MW | 24.07 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 930461 | AB1-087 CT1 | 50/50 | 52.82 MW | 52.82 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 930462 | AB1-087 ST1 | 50/50 | 42.0 MW | 42.0 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 930471 | AB1-088 CT1 | 50/50 | 52.82 MW | 52.82 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 930472 | AB1-088 ST1 | 50/50 | 42.0 MW | 42.0 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 933281 | AC2-140 C | 50/50 | 0.71 MW | 0.71 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 933282 | AC2-140 E | 50/50 | 0.22 MW | 0.22 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 933446 | AC2-157 1C | 50/50 | 6.55 MW | 6.55 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 933447 | AC2-157 2C | 50/50 | 6.55 MW | 6.55 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 933448 | AC2-157 1E | 50/50 | 10.69 MW | 10.69 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 933449 | AC2-157 2E | 50/50 | 10.69 MW | 10.69 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 940581 | AE2-045 C O1 | 50/50 | 11.3 MW | 11.3 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 940582 | AE2-045 E O1 | 50/50 | 15.52 MW | 15.52 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 941341 | AE2-130 C | 50/50 | 151.67 MW | 151.67 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 941342 | AE2-130 E | 50/50 | 101.11 MW | 101.11 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 946581 | AF1-322 C | 50/50 | 11.62 MW | 11.62 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 946582 | AF1-322 E | 50/50 | 16.05 MW | 16.05 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 957841 | AF2-078 C O1 | 50/50 | 16.75 MW | 16.75 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 957842 | AF2-078 E O1 | 50/50 | 11.16 MW | 11.16 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 958381 | AF2-132 C O1 | 50/50 | 23.11 MW | 23.11 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 958382 | AF2-132 E O1 | 50/50 | 15.4 MW | 15.4 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 958391 | AF2-133 C O1 | 50/50 | 23.5 MW | 23.5 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 958392 | AF2-133 E O1 | 50/50 | 15.67 MW | 15.67 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 958401 | AF2-134 C O1 | 50/50 | 7.45 MW | 7.45 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 958402 | AF2-134 E O1 | 50/50 | 4.96 MW | 4.96 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 251823 | Z1-065 BAT | 50/50 | 0.65 MW | 0.65 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 250163 | Y3-099 BAT | 50/50 | 0.23 MW | 0.23 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 957141 | AF2-008 FTIR | 50/50 | 86.2 MW | 86.2 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 944201 | AF1-088 FTIR | 50/50 | 172.4 MW | 172.4 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | 957142 | AF2-008 NFTI | 50/50 | 86.2 MW | 86.2 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.55 MW | 1.55 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 29.62 MW | 29.62 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.93 MW | 0.93 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 96.84 MW | 96.84 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 28.41 MW | 28.41 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.94 MW | 0.94 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.01 MW | 2.01 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.16 MW | 1.16 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.02 MW | 3.02 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 6.44 MW | 6.44 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.29 MW | 12.29 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.02 MW | 1.02 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.88 MW | 12.88 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 10.31 MW | 10.31 MW |
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.02 MW | 3.02 MW |
Details for 05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 963741 | AG1-226 C O1 | 50/50 | 58.76 MW | 58.76 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 963742 | AG1-226 E O1 | 50/50 | 21.0 MW | 21.0 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 963831 | AG1-236 C | 50/50 | 2.6 MW | 2.6 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 963832 | AG1-236 E | 50/50 | 17.43 MW | 17.43 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 963841 | AG1-237 C O1 | 50/50 | 4.72 MW | 4.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 963842 | AG1-237 E O1 | 50/50 | 31.58 MW | 31.58 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966841 | AG1-555 C | 50/50 | 16.2 MW | 16.2 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966842 | AG1-555 E | 50/50 | 5.79 MW | 5.79 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 965911 | AG1-460 C | 50/50 | 1.33 MW | 1.33 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 965912 | AG1-460 E | 50/50 | 1.99 MW | 1.99 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966531 | AG1-522 C | 50/50 | 83.55 MW | 83.55 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966532 | AG1-522 E | 50/50 | 55.7 MW | 55.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966541 | AG1-523 C | 50/50 | 83.55 MW | 83.55 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966542 | AG1-523 E | 50/50 | 55.7 MW | 55.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966551 | AG1-524 C | 50/50 | 83.55 MW | 83.55 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966552 | AG1-524 E | 50/50 | 55.7 MW | 55.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966561 | AG1-525 C | 50/50 | 83.55 MW | 83.55 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 966562 | AG1-525 E | 50/50 | 55.7 MW | 55.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 247900 | 05FR-11G E | 50/50 | 14.35 MW | 14.35 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 247901 | 05FR-12G E | 50/50 | 14.12 MW | 14.12 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 247902 | 05FR-21G E | 50/50 | 15.09 MW | 15.09 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 247903 | 05FR-22G E | 50/50 | 14.45 MW | 14.45 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 247904 | 05FR-3G E | 50/50 | 29.26 MW | 29.26 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 247905 | 05FR-4G E | 50/50 | 22.91 MW | 22.91 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 925771 | AC1-053 C | 50/50 | 2.6 MW | 2.6 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 925772 | AC1-053 E | 50/50 | 17.43 MW | 17.43 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 935141 | AD1-148 | 50/50 | 3.72 MW | 3.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 936771 | AD2-100 C | 50/50 | 14.25 MW | 14.25 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 936772 | AD2-100 E | 50/50 | 9.5 MW | 9.5 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 936971 | AD2-131 C | 50/50 | 0.94 MW | 0.94 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 936972 | AD2-131 E | 50/50 | 4.72 MW | 4.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 942481 | AE2-261 C | 50/50 | 19.82 MW | 19.82 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 942482 | AE2-261 E | 50/50 | 13.22 MW | 13.22 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 942601 | AE2-276 | 50/50 | 16.69 MW | 16.69 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 945391 | AF1-204 C O1 | 50/50 | 10.71 MW | 10.71 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 945392 | AF1-204 E O1 | 50/50 | 32.12 MW | 32.12 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 945871 | AF1-252 O1 | 50/50 | 7.53 MW | 7.53 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 945881 | AF1-253 | 50/50 | 5.21 MW | 5.21 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 960261 | AF2-317 | 50/50 | 1.61 MW | 1.61 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 243442 | 05RKG1 | 50/50 | 146.24 MW | 146.24 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 243443 | 05RKG2 | 50/50 | 140.19 MW | 140.19 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 243859 | 05FR-11G C | 50/50 | 0.8 MW | 0.8 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 243862 | 05FR-12G C | 50/50 | 0.39 MW | 0.39 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 243864 | 05FR-21G C | 50/50 | 0.41 MW | 0.41 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 243866 | 05FR-22G C | 50/50 | 0.41 MW | 0.41 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 243870 | 05FR-3G C | 50/50 | 0.39 MW | 0.39 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 243873 | 05FR-4G C | 50/50 | 0.91 MW | 0.91 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 274650 | KINCAID ;1U | 50/50 | 10.37 MW | 10.37 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 274651 | KINCAID ;2U | 50/50 | 10.37 MW | 10.37 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 276615 | W2-048 GEN | 50/50 | 5.29 MW | 5.29 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 276621 | X2-022 GEN | 50/50 | 18.97 MW | 18.97 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 930461 | AB1-087 CT1 | 50/50 | 102.28 MW | 102.28 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 930462 | AB1-087 ST1 | 50/50 | 81.32 MW | 81.32 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 930471 | AB1-088 CT1 | 50/50 | 102.28 MW | 102.28 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 930472 | AB1-088 ST1 | 50/50 | 81.32 MW | 81.32 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 933446 | AC2-157 1C | 50/50 | 12.69 MW | 12.69 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 933447 | AC2-157 2C | 50/50 | 12.69 MW | 12.69 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 933448 | AC2-157 1E | 50/50 | 20.7 MW | 20.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 933449 | AC2-157 2E | 50/50 | 20.7 MW | 20.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 941341 | AE2-130 C | 50/50 | 303.91 MW | 303.91 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 941342 | AE2-130 E | 50/50 | 202.61 MW | 202.61 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 944221 | AF1-090 C O1 | 50/50 | 4.25 MW | 4.25 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 944222 | AF1-090 E O1 | 50/50 | 19.89 MW | 19.89 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 957381 | AF2-032 C | 50/50 | 1.49 MW | 1.49 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 957382 | AF2-032 E | 50/50 | 0.7 MW | 0.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 957141 | AF2-008 FTIR | 50/50 | 166.91 MW | 166.91 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 944201 | AF1-088 FTIR | 50/50 | 333.83 MW | 333.83 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 957142 | AF2-008 NFTI | 50/50 | 166.91 MW | 166.91 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 954681 | J949 C | External Queue | 19.33 MW | 19.33 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 990071 | J1204 | External Queue | 30.75 MW | 30.75 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | 990271 | J1263 | External Queue | 55.06 MW | 55.06 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.42 MW | 0.42 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.49 MW | 0.49 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.27 MW | 1.27 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 46.28 MW | 46.28 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 66.43 MW | 66.43 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.93 MW | 1.93 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.18 MW | 0.18 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.57 MW | 8.57 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.96 MW | 0.96 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.07 MW | 10.07 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.02 MW | 1.02 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.36 MW | 12.36 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.9 MW | 0.9 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.51 MW | 0.51 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.58 MW | 5.58 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11041 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.4 MW | 1.4 MW |
Details for 05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963741 | AG1-226 C O1 | 50/50 | 53.69 MW | 53.69 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963742 | AG1-226 E O1 | 50/50 | 19.19 MW | 19.19 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963841 | AG1-237 C O1 | 50/50 | 4.21 MW | 4.21 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963842 | AG1-237 E O1 | 50/50 | 28.18 MW | 28.18 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965911 | AG1-460 C | 50/50 | 1.33 MW | 1.33 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965912 | AG1-460 E | 50/50 | 2.0 MW | 2.0 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966531 | AG1-522 C | 50/50 | 85.81 MW | 85.81 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966532 | AG1-522 E | 50/50 | 57.21 MW | 57.21 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966541 | AG1-523 C | 50/50 | 85.81 MW | 85.81 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966542 | AG1-523 E | 50/50 | 57.21 MW | 57.21 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966551 | AG1-524 C | 50/50 | 85.81 MW | 85.81 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966552 | AG1-524 E | 50/50 | 57.21 MW | 57.21 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966561 | AG1-525 C | 50/50 | 85.81 MW | 85.81 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966562 | AG1-525 E | 50/50 | 57.21 MW | 57.21 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 935141 | AD1-148 | 50/50 | 3.72 MW | 3.72 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936771 | AD2-100 C | 50/50 | 14.33 MW | 14.33 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936772 | AD2-100 E | 50/50 | 9.56 MW | 9.56 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936971 | AD2-131 C | 50/50 | 0.94 MW | 0.94 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936972 | AD2-131 E | 50/50 | 4.74 MW | 4.74 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942481 | AE2-261 C | 50/50 | 19.92 MW | 19.92 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942482 | AE2-261 E | 50/50 | 13.28 MW | 13.28 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942601 | AE2-276 | 50/50 | 17.48 MW | 17.48 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945391 | AF1-204 C O1 | 50/50 | 10.33 MW | 10.33 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945392 | AF1-204 E O1 | 50/50 | 30.98 MW | 30.98 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945871 | AF1-252 O1 | 50/50 | 7.6 MW | 7.6 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945881 | AF1-253 | 50/50 | 5.26 MW | 5.26 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960261 | AF2-317 | 50/50 | 1.61 MW | 1.61 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 243442 | 05RKG1 | 50/50 | 148.16 MW | 148.16 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 243443 | 05RKG2 | 50/50 | 142.03 MW | 142.03 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 274650 | KINCAID ;1U | 50/50 | 10.42 MW | 10.42 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 274651 | KINCAID ;2U | 50/50 | 10.41 MW | 10.41 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 276615 | W2-048 GEN | 50/50 | 5.29 MW | 5.29 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 276621 | X2-022 GEN | 50/50 | 18.97 MW | 18.97 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930461 | AB1-087 CT1 | 50/50 | 107.15 MW | 107.15 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930462 | AB1-087 ST1 | 50/50 | 85.19 MW | 85.19 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930471 | AB1-088 CT1 | 50/50 | 107.15 MW | 107.15 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930472 | AB1-088 ST1 | 50/50 | 85.19 MW | 85.19 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933446 | AC2-157 1C | 50/50 | 13.29 MW | 13.29 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933447 | AC2-157 2C | 50/50 | 13.29 MW | 13.29 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933448 | AC2-157 1E | 50/50 | 21.68 MW | 21.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933449 | AC2-157 2E | 50/50 | 21.68 MW | 21.68 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 941341 | AE2-130 C | 50/50 | 307.91 MW | 307.91 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 941342 | AE2-130 E | 50/50 | 205.27 MW | 205.27 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944221 | AF1-090 C O1 | 50/50 | 4.29 MW | 4.29 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944222 | AF1-090 E O1 | 50/50 | 20.07 MW | 20.07 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957381 | AF2-032 C | 50/50 | 1.5 MW | 1.5 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957382 | AF2-032 E | 50/50 | 0.7 MW | 0.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957141 | AF2-008 FTIR | 50/50 | 174.85 MW | 174.85 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944201 | AF1-088 FTIR | 50/50 | 349.7 MW | 349.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957142 | AF2-008 NFTI | 50/50 | 174.85 MW | 174.85 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 954681 | J949 C | External Queue | 19.61 MW | 19.61 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 990071 | J1204 | External Queue | 32.02 MW | 32.02 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 990271 | J1263 | External Queue | 56.7 MW | 56.7 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.38 MW | 0.38 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.34 MW | 0.34 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.3 MW | 1.3 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.62 MW | 0.62 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.49 MW | 45.49 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.17 MW | 67.17 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.91 MW | 1.91 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.15 MW | 0.15 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 8.75 MW | 8.75 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.96 MW | 0.96 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.09 MW | 10.09 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.01 MW | 1.01 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.25 MW | 12.25 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.91 MW | 0.91 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.46 MW | 0.46 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.73 MW | 5.73 MW |
05ROCKPT-05JEFRSO 765.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.38 MW | 1.38 MW |
Details for 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963741 | AG1-226 C O1 | 50/50 | 177.68 MW | 177.68 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963742 | AG1-226 E O1 | 50/50 | 63.52 MW | 63.52 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963831 | AG1-236 C | Adder | 2.4 MW | 2.04 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963832 | AG1-236 E | Adder | 16.08 MW | 13.66 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963841 | AG1-237 C O1 | 50/50 | 13.94 MW | 13.94 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963842 | AG1-237 E O1 | 50/50 | 93.26 MW | 93.26 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 964581 | AG1-321 C O1 | Adder | 7.37 MW | 6.26 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 964582 | AG1-321 E O1 | Adder | 4.29 MW | 3.65 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965091 | AG1-374 C | Adder | 13.81 MW | 11.74 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965092 | AG1-374 E | Adder | 9.2 MW | 7.82 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965331 | AG1-398 | Adder | 0.68 MW | 0.58 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965341 | AG1-399 C | Adder | 4.54 MW | 3.86 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965342 | AG1-399 E | Adder | 21.25 MW | 18.06 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965351 | AG1-400 | Adder | 12.9 MW | 10.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965371 | AG1-402 | Adder | 12.9 MW | 10.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965391 | AG1-404 | Adder | 8.6 MW | 7.31 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965911 | AG1-460 C | Adder | 1.03 MW | 0.87 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965912 | AG1-460 E | Adder | 1.54 MW | 1.31 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966531 | AG1-522 C | Adder | 17.39 MW | 14.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966532 | AG1-522 E | Adder | 11.59 MW | 9.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966541 | AG1-523 C | Adder | 17.39 MW | 14.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966542 | AG1-523 E | Adder | 11.59 MW | 9.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966551 | AG1-524 C | Adder | 17.39 MW | 14.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966552 | AG1-524 E | Adder | 11.59 MW | 9.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966561 | AG1-525 C | Adder | 17.39 MW | 14.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966562 | AG1-525 E | Adder | 11.59 MW | 9.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 290261 | S-027 E | Adder | 12.15 MW | 10.33 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 290265 | S-028 E | Adder | 12.15 MW | 10.33 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 925771 | AC1-053 C | Adder | 2.4 MW | 2.04 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 925772 | AC1-053 E | Adder | 16.08 MW | 13.66 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 935141 | AD1-148 | Adder | 3.28 MW | 2.79 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936771 | AD2-100 C | Adder | 10.71 MW | 9.11 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936772 | AD2-100 E | Adder | 7.14 MW | 6.07 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936971 | AD2-131 C | Adder | 0.71 MW | 0.6 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936972 | AD2-131 E | Adder | 3.54 MW | 3.01 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942111 | AE2-223 C | Adder | 1.46 MW | 1.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942112 | AE2-223 E | Adder | 9.74 MW | 8.28 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942481 | AE2-261 C | Adder | 15.36 MW | 13.05 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942482 | AE2-261 E | Adder | 10.24 MW | 8.7 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942601 | AE2-276 | 50/50 | 6.22 MW | 6.22 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945391 | AF1-204 C O1 | 50/50 | 34.17 MW | 34.17 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945392 | AF1-204 E O1 | 50/50 | 102.52 MW | 102.52 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945871 | AF1-252 O1 | Adder | 5.2 MW | 4.42 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945881 | AF1-253 | Adder | 3.6 MW | 3.06 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 959341 | AF2-225 C | Adder | 4.7 MW | 4.0 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 959342 | AF2-225 E | Adder | 6.5 MW | 5.52 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 959611 | AF2-252 C | Adder | 1.53 MW | 1.3 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 959612 | AF2-252 E | Adder | 2.3 MW | 1.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960141 | AF2-305 | Adder | 0.86 MW | 0.73 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960261 | AF2-317 | Adder | 1.42 MW | 1.2 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960611 | AF2-352 C | Adder | 1.53 MW | 1.3 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960612 | AF2-352 E | Adder | 2.3 MW | 1.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 276615 | W2-048 GEN | Adder | 4.66 MW | 3.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 276621 | X2-022 GEN | Adder | 16.71 MW | 14.21 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 293777 | CAYUG;1U E | Adder | 6.31 MW | 5.36 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 293778 | CAYUG;2U E | Adder | 6.31 MW | 5.36 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 293798 | W4-005 E | Adder | 24.49 MW | 20.81 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 917502 | Z2-087 E | Adder | 12.99 MW | 11.04 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 924042 | AB2-047 E O1 | Adder | 16.24 MW | 13.8 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 924261 | AB2-070 C O1 | Adder | 2.43 MW | 2.06 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 924262 | AB2-070 E O1 | Adder | 14.7 MW | 12.49 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930461 | AB1-087 CT1 | 50/50 | 38.14 MW | 38.14 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930462 | AB1-087 ST1 | 50/50 | 30.32 MW | 30.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930471 | AB1-088 CT1 | 50/50 | 38.14 MW | 38.14 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930472 | AB1-088 ST1 | 50/50 | 30.32 MW | 30.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933446 | AC2-157 1C | 50/50 | 4.73 MW | 4.73 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933447 | AC2-157 2C | 50/50 | 4.73 MW | 4.73 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933448 | AC2-157 1E | 50/50 | 7.72 MW | 7.72 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933449 | AC2-157 2E | 50/50 | 7.72 MW | 7.72 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 939741 | AE1-205 C O1 | Adder | 6.27 MW | 5.33 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 939742 | AE1-205 E O1 | Adder | 8.66 MW | 7.36 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 941341 | AE2-130 C | Adder | 29.02 MW | 24.67 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 941342 | AE2-130 E | Adder | 19.35 MW | 16.44 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 941731 | AE2-173 O1 | Adder | 3.73 MW | 3.17 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944221 | AF1-090 C O1 | Adder | 2.93 MW | 2.49 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944222 | AF1-090 E O1 | Adder | 13.73 MW | 11.67 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957381 | AF2-032 C | Adder | 1.17 MW | 0.99 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957382 | AF2-032 E | Adder | 0.55 MW | 0.47 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 961162 | AF2-407 BAT | Adder | 24.49 MW | 20.82 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 964353 | AG1-297 BAT | Adder | 35.59 MW | 30.25 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957141 | AF2-008 FTIR | 50/50 | 62.24 MW | 62.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944201 | AF1-088 FTIR | 50/50 | 124.48 MW | 124.48 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957142 | AF2-008 NFTI | 50/50 | 62.24 MW | 62.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 961172 | AF2-408 BAT | Adder | 5.77 MW | 4.9 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 953741 | J826 C | External Queue | 2.41 MW | 2.41 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 953742 | J826 E | External Queue | 13.06 MW | 13.06 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 953851 | J845 C | External Queue | 3.0 MW | 3.0 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 953852 | J845 E | External Queue | 16.24 MW | 16.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 954681 | J949 C | External Queue | 13.76 MW | 13.76 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 954821 | J955 | External Queue | 66.87 MW | 66.87 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 955402 | J1022 E | External Queue | 23.21 MW | 23.21 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 956281 | J1115 C | External Queue | 3.07 MW | 3.07 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 956282 | J1115 E | External Queue | 16.59 MW | 16.59 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 956451 | J1139 | External Queue | 30.58 MW | 30.58 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 990071 | J1204 | External Queue | 16.07 MW | 16.07 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 990271 | J1263 | External Queue | 31.12 MW | 31.12 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 990672 | J1360 E | External Queue | 48.09 MW | 48.09 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 991236 | J1676 C | External Queue | 4.6 MW | 4.6 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 991237 | J1676 E | External Queue | 24.9 MW | 24.9 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 991261 | J1713 C | External Queue | 1.88 MW | 1.88 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 991262 | J1713 E | External Queue | 10.19 MW | 10.19 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.95 MW | 2.95 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.27 MW | 0.27 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.63 MW | 1.63 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 24.86 MW | 24.86 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.64 MW | 7.64 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 2.19 MW | 2.19 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.59 MW | 3.59 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.61 MW | 0.61 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.1 MW | 6.1 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.7 MW | 3.7 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.89 MW | 0.89 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.77 MW | 1.77 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.96 MW | 0.96 MW |
Details for 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 963741 | AG1-226 C O1 | 50/50 | 177.68 MW | 177.68 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 963742 | AG1-226 E O1 | 50/50 | 63.52 MW | 63.52 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 963831 | AG1-236 C | Adder | 2.4 MW | 2.04 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 963832 | AG1-236 E | Adder | 16.08 MW | 13.66 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 964581 | AG1-321 C O1 | Adder | 7.37 MW | 6.26 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 964582 | AG1-321 E O1 | Adder | 4.29 MW | 3.65 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965091 | AG1-374 C | Adder | 13.81 MW | 11.74 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965092 | AG1-374 E | Adder | 9.2 MW | 7.82 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965331 | AG1-398 | Adder | 0.68 MW | 0.58 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965341 | AG1-399 C | Adder | 4.54 MW | 3.86 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965342 | AG1-399 E | Adder | 21.25 MW | 18.06 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965351 | AG1-400 | Adder | 12.9 MW | 10.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965371 | AG1-402 | Adder | 12.9 MW | 10.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965391 | AG1-404 | Adder | 8.6 MW | 7.31 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965911 | AG1-460 C | Adder | 1.03 MW | 0.87 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965912 | AG1-460 E | Adder | 1.54 MW | 1.31 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966531 | AG1-522 C | Adder | 17.39 MW | 14.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966532 | AG1-522 E | Adder | 11.59 MW | 9.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966541 | AG1-523 C | Adder | 17.39 MW | 14.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966542 | AG1-523 E | Adder | 11.59 MW | 9.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966551 | AG1-524 C | Adder | 17.39 MW | 14.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966552 | AG1-524 E | Adder | 11.59 MW | 9.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966561 | AG1-525 C | Adder | 17.39 MW | 14.78 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966562 | AG1-525 E | Adder | 11.59 MW | 9.85 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 290261 | S-027 E | Adder | 12.15 MW | 10.33 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 290265 | S-028 E | Adder | 12.15 MW | 10.33 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 925771 | AC1-053 C | Adder | 2.4 MW | 2.04 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 925772 | AC1-053 E | Adder | 16.08 MW | 13.66 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 935141 | AD1-148 | Adder | 3.28 MW | 2.79 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 936771 | AD2-100 C | Adder | 10.71 MW | 9.11 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 936772 | AD2-100 E | Adder | 7.14 MW | 6.07 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 936971 | AD2-131 C | Adder | 0.71 MW | 0.6 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 936972 | AD2-131 E | Adder | 3.54 MW | 3.01 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942111 | AE2-223 C | Adder | 1.46 MW | 1.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942112 | AE2-223 E | Adder | 9.74 MW | 8.28 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942481 | AE2-261 C | Adder | 15.36 MW | 13.05 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942482 | AE2-261 E | Adder | 10.24 MW | 8.7 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942601 | AE2-276 | 50/50 | 6.22 MW | 6.22 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 945391 | AF1-204 C O1 | 50/50 | 34.17 MW | 34.17 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 945392 | AF1-204 E O1 | 50/50 | 102.52 MW | 102.52 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 945871 | AF1-252 O1 | Adder | 5.2 MW | 4.42 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 945881 | AF1-253 | Adder | 3.6 MW | 3.06 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 959341 | AF2-225 C | Adder | 4.7 MW | 4.0 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 959342 | AF2-225 E | Adder | 6.5 MW | 5.52 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 959611 | AF2-252 C | Adder | 1.53 MW | 1.3 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 959612 | AF2-252 E | Adder | 2.3 MW | 1.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 960141 | AF2-305 | Adder | 0.86 MW | 0.73 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 960261 | AF2-317 | Adder | 1.42 MW | 1.2 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 960611 | AF2-352 C | Adder | 1.53 MW | 1.3 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 960612 | AF2-352 E | Adder | 2.3 MW | 1.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 276615 | W2-048 GEN | Adder | 4.66 MW | 3.96 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 276621 | X2-022 GEN | Adder | 16.71 MW | 14.21 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 293777 | CAYUG;1U E | Adder | 6.31 MW | 5.36 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 293778 | CAYUG;2U E | Adder | 6.31 MW | 5.36 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 293798 | W4-005 E | Adder | 24.49 MW | 20.81 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 917502 | Z2-087 E | Adder | 12.99 MW | 11.04 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 924042 | AB2-047 E O1 | Adder | 16.24 MW | 13.8 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 924261 | AB2-070 C O1 | Adder | 2.43 MW | 2.06 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 924262 | AB2-070 E O1 | Adder | 14.7 MW | 12.49 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 930461 | AB1-087 CT1 | 50/50 | 38.14 MW | 38.14 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 930462 | AB1-087 ST1 | 50/50 | 30.32 MW | 30.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 930471 | AB1-088 CT1 | 50/50 | 38.14 MW | 38.14 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 930472 | AB1-088 ST1 | 50/50 | 30.32 MW | 30.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 933446 | AC2-157 1C | 50/50 | 4.73 MW | 4.73 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 933447 | AC2-157 2C | 50/50 | 4.73 MW | 4.73 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 933448 | AC2-157 1E | 50/50 | 7.72 MW | 7.72 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 933449 | AC2-157 2E | 50/50 | 7.72 MW | 7.72 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 939741 | AE1-205 C O1 | Adder | 6.27 MW | 5.33 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 939742 | AE1-205 E O1 | Adder | 8.66 MW | 7.36 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 941341 | AE2-130 C | Adder | 29.02 MW | 24.67 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 941342 | AE2-130 E | Adder | 19.35 MW | 16.44 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 941731 | AE2-173 O1 | Adder | 3.73 MW | 3.17 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 944221 | AF1-090 C O1 | Adder | 2.93 MW | 2.49 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 944222 | AF1-090 E O1 | Adder | 13.73 MW | 11.67 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 957381 | AF2-032 C | Adder | 1.17 MW | 0.99 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 957382 | AF2-032 E | Adder | 0.55 MW | 0.47 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 961162 | AF2-407 BAT | Adder | 24.49 MW | 20.82 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 964353 | AG1-297 BAT | Adder | 35.59 MW | 30.25 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 957141 | AF2-008 FTIR | 50/50 | 62.24 MW | 62.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 944201 | AF1-088 FTIR | 50/50 | 124.48 MW | 124.48 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 957142 | AF2-008 NFTI | 50/50 | 62.24 MW | 62.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 961172 | AF2-408 BAT | Adder | 5.77 MW | 4.9 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 953741 | J826 C | External Queue | 2.41 MW | 2.41 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 953742 | J826 E | External Queue | 13.06 MW | 13.06 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 953851 | J845 C | External Queue | 3.0 MW | 3.0 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 953852 | J845 E | External Queue | 16.24 MW | 16.24 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 954411 | J912 | External Queue | 5.35 MW | 5.35 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 954681 | J949 C | External Queue | 13.76 MW | 13.76 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 954821 | J955 | External Queue | 76.05 MW | 76.05 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 955402 | J1022 E | External Queue | 23.21 MW | 23.21 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 956281 | J1115 C | External Queue | 3.07 MW | 3.07 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 956282 | J1115 E | External Queue | 16.59 MW | 16.59 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 956451 | J1139 | External Queue | 30.58 MW | 30.58 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 990071 | J1204 | External Queue | 16.07 MW | 16.07 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 990271 | J1263 | External Queue | 31.12 MW | 31.12 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 990672 | J1360 E | External Queue | 48.09 MW | 48.09 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 991236 | J1676 C | External Queue | 4.6 MW | 4.6 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 991237 | J1676 E | External Queue | 24.9 MW | 24.9 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 991261 | J1713 C | External Queue | 1.88 MW | 1.88 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 991262 | J1713 E | External Queue | 10.19 MW | 10.19 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.95 MW | 2.95 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.27 MW | 0.27 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.63 MW | 1.63 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 24.86 MW | 24.86 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.64 MW | 7.64 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 2.19 MW | 2.19 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.59 MW | 3.59 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.61 MW | 0.61 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.1 MW | 6.1 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.7 MW | 3.7 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.89 MW | 0.89 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.77 MW | 1.77 MW |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.96 MW | 0.96 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
System Reinforcements | |||
---|---|---|---|
RTEP ID | Title | Total Cost | |
n7924 | Replace 5 Sub cond 2156 ACSR 84/19 STD | $5,000,000 | |
n7980.1 | Rebuild 3.83 miles of 2303.5 ACAR , conductor section 1 | $7,660,000 | |
n7980.2 | Rebuild 47.02 miles of 1414 ACSR/PE, conductor section 2 | $94,000,000 | |
(TBD) | An engineering study will need to be conducted for the Relay Settings. | $25,000 | |
n7943.4 | Replace 9 Jefferson 5000 A switches | $4,500,000 | |
n7943.3 | An engineering study will need to be conducted to determine if the Jefferso [...] l be required if the settings cannot be adjusted. Estimated Cost: $600,000. | $25,000 | |
n7943.2 | Replace Jefferson 345kV Circuit Breaker (5000A) | $1,200,000 | |
n7964 | Replace 765/345 Transformer | $6,000,000 | |
n6497.1 | An engineering study will need to be conducted to determine if the Rockport [...] ll be required if the settings cannot be adjusted, Estimated Cost: $600,000 | $50,144 | |
n6497.2 | Replace 6 Rockport Current Transformers 3000Amps | $4,800,000 | |
n6497.3 | Replace 2 Rockport 3000A non-oil Breakers at Rockport | $6,000,000 | |
s2280 | Replace Rockport CB’s B, B2, C and C2 with 765kV SFMT 4000A Cb’s | $0 | |
n6497.4 | AEPI0002e: Replace 3 3000A Wavetraps at Rockport $150k; AEPI0002f Replace 3 3000A Wavetraps at Jefferson $150k | $426,497 | |
n6497.6 | Replace 2 Jefferson 4000A non-oil Breakers | $7,000,000 | |
n6497.5 | Replace 12 3000A switches at Rockport | $6,000,000 | |
(TBD) | Replace 1 Jefferson (Sub cond 3-2500 kcm AAC 91 Str) | $10,000 | |
(TBD) | Replace 3 Jefferson 5000 A switches | $150,000 | |
(TBD) | Replace 2 clifty Breaker (3000A) | $2,400,000 | |
(TBD) | An engineering study will need to be conducted to determine if the Clifty R [...] l be required if the settings cannot be adjusted. Estimated Cost: $600,000. | $25,000 | |
n4106.7 | An engineering study will need to be conducted to determine if the Jefferso [...] l be required if the settings cannot be adjusted. Estimated Cost: $600,000. | $25,000 | |
n4106.6 | Replace Jefferson Breaker (5000A) | $1,200,000 | |
n4106.4 | Rebuild 0.75 miles of ACSR ~ 2156 ~ 64/19 ~ BLUEBIRD conductor to mitigate the overload. | $2,500,000 | |
n4106.5 | Replace Clifty Bus 5"0 AL Tubular Sch 40 | $100,000 | |
n4106.3 | Extend One (1) Tower on the Jefferson - Clifty Creek (IKEC) 345 kV Circuit | $409,714 | |
b3748 | Replace four Clifty Creek 345 kV 3000A switches with 5000 A 345 kV switches | $850,000 | |
n4106 | Replace Two (2) Switches at the Clifty Creek 345 kV Station | $412,916 | |
b2878 | Upgrade the Clifty Creek 345 kV risers | $3,675,000 | |
n8346 | An engineering study will need to be conducted to determine if the Sullivan [...] l be required if the settings cannot be adjusted. Estimated Cost: $600,000. | $25,000 | |
n6781 | A Sag Study will be required on the ~0.5 miles section of 954 2x Rail Condu [...] t sag study) and $0.75 million (complete line reconductor/rebuild required) | $25,000 | |
s2280 | Sullivan 765/345kV Station: Replace Sullivan CB A2 765kV CB and associated equipment. Replace Rockport CB’s B, B2, C and C2 with 765kV SFMT 4000A Cb’s | $0 | |
n7925.2 | Reconductor/rebuild 1 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 6 | $2,000,000 | |
n7925.1 | Reconductor/rebuild 0.82 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 5 | $1,640,000 | |
n7925.3 | Replace two sullivan 3000A Wavetrap | $400,000 | |
b2943 | PJM Baseline Upgrade b2943. Perform a LIDAR study on the Clifty Creek - Dea [...] rating. The baseline project had a projected in-service date of 12/01/2020. | $127,896 | |
n7979 | Replace one 1600 A Wavetrap at Clifty Creek, $200k, 12-18 months. The new SE rating is 1281 MVA SE. | $200,000 |
Attachments
Download all tables in report
Uprate Chain | |||||
---|---|---|---|---|---|
Project | Project Status | MFO | MWE | MWC | Disposition |
AG1-522 | Active | 300.0 | 300.0 | 180.0 | Transition Cycle 1 |
AG1-523 | Active | 600.0 | 300.0 | 180.0 | Transition Cycle 1 |
AG1-524 | Active | 900.0 | 300.0 | 180.0 | Transition Cycle 1 |
AG1-525 | Active | 1200.0 | 300.0 | 180.0 | Transition Cycle 1 |
Conclusion
The Transition Sort load flow retool results indicate that AG1-525 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.