AG1-494 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:42
Boxwood-Riverville 138 kV
20.0 MW Capacity / 50.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-494 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the AEP zone — Amherst County, Virginia. The installed facilities will have a total capability of 50.0 MW with 20.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-494 |
| Project Name | Boxwood-Riverville 138 kV |
| Developer Name | Mainspring Grid, LLC |
| State | Virginia |
| County | Amherst |
| Transmission Owner | AEP |
| MFO | 50.0 MW |
| MWE | 50.0 MW |
| MWC | 20.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-494 will interconnect on the AEP transmission system Boxwood – Riverville 138 kV circuit.
Summer Peak Analysis
The Queue Project was evaluated as a 50.0 MW (Capacity 20.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
DVP_P1-2: LN 566
CONTINGENCY 'DVP_P1-2: LN 566' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 END |
Single | AC | 118.79 % | 120.91 % | 156.98 | B | 189.8 | 3.38 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
PJM_PLANT BEAR GARDEN
CONTINGENCY 'PJM_PLANT BEAR GARDEN' REMOVE MACHINE G1 FROM BUS 315191 /*1BEARGRDN G1 18.0 REMOVE MACHINE G2 FROM BUS 315192 /*1BEARGRDN G2 18.0 REMOVE MACHINE S1 FROM BUS 315193 /*1BEARGRDN S1 22.0 END |
Single | AC | 115.62 % | 117.6 % | 156.98 | B | 184.61 | 3.18 | |
| DVP |
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
314759 to 314734 ckt 1 |
DVP_P1-2: LN 550
CONTINGENCY 'DVP_P1-2: LN 550' OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1 /*8MT STM 500.0 - 8VALLEY 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 END |
Single | AC | 99.79 % | 100.02 % | 550.84 | B | 550.96 | 1.21 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
Base Case | Single | AC | 98.33 % | 100.33 % | 156.98 | A | 157.49 | 3.18 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
DVP_P4-2: 547T566
CONTINGENCY 'DVP_P4-2: 547T566' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 OPEN BRANCH FROM BUS 314901 TO BUS 314912 CKT 1 /*8BATH CO 500.0 - 8LEXNGTN 500.0 END |
Breaker | AC | 157.0 % | 161.44 % | 173.0 | C | 279.3 | 8.45 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
DVP_P4-2: 56602
CONTINGENCY 'DVP_P4-2: 56602' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1 /*6LEXNGT2 230.0 - 8LEXNGTN 500.0 END |
Breaker | AC | 155.74 % | 160.18 % | 173.0 | C | 277.12 | 8.45 | |
| AEP/DVP |
05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line
242701 to 314667 ckt 1 |
AEP_P4_#13922_05OPOSSUMCK 138_D
CONTINGENCY 'AEP_P4_#13922_05OPOSSUMCK 138_D' OPEN BRANCH FROM BUS 242575 TO BUS 242737 CKT 1 /*05CAMDLM 138.0 - 05OPOSSUMCK 138.0 OPEN BRANCH FROM BUS 242575 TO BUS 242781 CKT 1 /*05CAMDLM 138.0 - 05RUSTBR 138.0 OPEN BRANCH FROM BUS 242575 TO BUS 926520 CKT 1 /*05CAMDLM 138.0 - AC1-123 TAP 138.0 OPEN BRANCH FROM BUS 242737 TO BUS 242785 CKT 1 /*05OPOSSUMCK 138.0 - 05S.LYNC 138.0 END |
Breaker | AC | 115.18 % | 116.54 % | 284.0 | B | 330.96 | 3.84 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 210622
CONTINGENCY 'DVP_P4-2: 210622' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 105.11 % | 109.28 % | 167.0 | B | 182.51 | 7.13 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 105.08 % | 109.26 % | 167.0 | B | 182.47 | 7.13 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 202722
CONTINGENCY 'DVP_P4-2: 202722' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Breaker | AC | 105.08 % | 109.25 % | 167.0 | B | 182.45 | 7.13 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 547T566
CONTINGENCY 'DVP_P4-2: 547T566' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 OPEN BRANCH FROM BUS 314901 TO BUS 314912 CKT 1 /*8BATH CO 500.0 - 8LEXNGTN 500.0 END |
Breaker | AC | 104.6 % | 108.57 % | 167.0 | B | 181.31 | 8.45 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 219322
CONTINGENCY 'DVP_P4-2: 219322' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 104.37 % | 108.57 % | 167.0 | B | 181.31 | 7.13 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P2-2: BREMO B1
CONTINGENCY 'DVP_P2-2: BREMO B1' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Bus | AC | 105.12 % | 109.3 % | 167.0 | B | 182.53 | 7.13 | |
| AEP |
05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line
242802 to 242701 ckt 1 |
AEP_P4_#13922_05OPOSSUMCK 138_D
CONTINGENCY 'AEP_P4_#13922_05OPOSSUMCK 138_D' OPEN BRANCH FROM BUS 242575 TO BUS 242737 CKT 1 /*05CAMDLM 138.0 - 05OPOSSUMCK 138.0 OPEN BRANCH FROM BUS 242575 TO BUS 242781 CKT 1 /*05CAMDLM 138.0 - 05RUSTBR 138.0 OPEN BRANCH FROM BUS 242575 TO BUS 926520 CKT 1 /*05CAMDLM 138.0 - AC1-123 TAP 138.0 OPEN BRANCH FROM BUS 242737 TO BUS 242785 CKT 1 /*05OPOSSUMCK 138.0 - 05S.LYNC 138.0 END |
Breaker | AC | 111.0 % | 112.48 % | 255.0 | B | 286.83 | 3.83 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 210622
CONTINGENCY 'DVP_P4-2: 210622' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 110.93 % | 115.13 % | 167.0 | B | 192.27 | 7.13 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 110.91 % | 115.11 % | 167.0 | B | 192.23 | 7.13 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 202722
CONTINGENCY 'DVP_P4-2: 202722' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Breaker | AC | 110.9 % | 115.1 % | 167.0 | B | 192.21 | 7.13 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 547T566
CONTINGENCY 'DVP_P4-2: 547T566' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 OPEN BRANCH FROM BUS 314901 TO BUS 314912 CKT 1 /*8BATH CO 500.0 - 8LEXNGTN 500.0 END |
Breaker | AC | 110.38 % | 114.38 % | 167.0 | B | 191.01 | 8.45 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 219322
CONTINGENCY 'DVP_P4-2: 219322' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 110.15 % | 114.35 % | 167.0 | B | 190.96 | 7.13 | |
| AEP |
05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line
242775 to 242720 ckt 1 |
AEP_P4_#10164_05EDAN 2 138_M
CONTINGENCY 'AEP_P4_#10164_05EDAN 2 138_M' OPEN BRANCH FROM BUS 242531 TO BUS 242632 CKT 4 /*05EDANV2 230.0 - 05EDAN 2 138.0 OPEN BRANCH FROM BUS 242531 TO BUS 304094 CKT 1 /*05EDANV2 230.0 - 6YANCY TAP 230.0 OPEN BRANCH FROM BUS 242549 TO BUS 242632 CKT 1 /*05BANSTR 138.0 - 05EDAN 2 138.0 OPEN BRANCH FROM BUS 242549 TO BUS 314668 CKT Z1 /*05BANSTR 138.0 - 4BANISTR 138.0 OPEN BRANCH FROM BUS 242549 TO BUS 940080 CKT 1 /*05BANSTR 138.0 - AE1-250 TAP 138.0 OPEN BRANCH FROM BUS 242629 TO BUS 242632 CKT 1 /*05E.MONU 138.0 - 05EDAN 2 138.0 OPEN BRANCH FROM BUS 242631 TO BUS 242632 CKT Z1 /*05EDAN 1 138.0 - 05EDAN 2 138.0 END |
Breaker | AC | 99.51 % | 100.06 % | 409.0 | B | 409.26 | 2.76 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P2-2: BREMO B1
CONTINGENCY 'DVP_P2-2: BREMO B1' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Bus | AC | 110.97 % | 115.18 % | 167.0 | B | 192.35 | 7.13 | |
| AEP |
AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line
926520 to 242575 ckt 1 |
AEP_P2-2_#10292_05NEWLDN 138_1
CONTINGENCY 'AEP_P2-2_#10292_05NEWLDN 138_1' OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1 /*05BRUSHT 138.0 - 05NEWLDN 138.0 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1 /*05FOREST 138.0 - 05NEWLDN 138.0 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1 /*05JOHNMT 138.0 - 05NEWLDN 138.0 END |
Bus | AC | 105.36 % | 106.95 % | 255.0 | B | 272.74 | 4.23 | |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 961801 | AG1-022 C | 80/20 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 962741 | AG1-123 C O1 | 80/20 | 5.64 MW | 5.64 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 962751 | AG1-124 C O1 | 80/20 | 7.19 MW | 7.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 966761 | AG1-547 C | 80/20 | 1.64 MW | 1.64 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 965581 | AG1-426 | 80/20 | 11.68 MW | 11.68 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 966251 | AG1-494 C | 80/20 | 3.38 MW | 3.38 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 926521 | AC1-123 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 926645 | AC1-145 C | 80/20 | 0.16 MW | 0.16 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 942671 | AE2-283 C | 80/20 | 1.99 MW | 1.99 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 960111 | AF2-302 C | 80/20 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 961121 | AF2-403 | 80/20 | 0.4 MW | 0.4 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 242889 | 05REUSENS | 80/20 | 0.06 MW | 0.06 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 925661 | AC1-042 C | 80/20 | 0.8 MW | 0.8 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 938821 | AE1-108 C O1 | 80/20 | 61.61 MW | 61.61 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 941801 | AE2-185 C | 80/20 | 1.81 MW | 1.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 941821 | AE2-187 C | 80/20 | 1.81 MW | 1.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 946591 | AF1-323 C | 80/20 | 20.19 MW | 20.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 958131 | AF2-107 C | 80/20 | 9.19 MW | 9.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.88 MW | 7.88 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.86 MW | 12.86 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.17 MW | 9.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.81 MW | 1.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.57 MW | 1.57 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.52 MW | 1.52 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 961801 | AG1-022 C | 80/20 | 7.33 MW | 7.33 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 962741 | AG1-123 C O1 | 80/20 | 5.23 MW | 5.23 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 962751 | AG1-124 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965581 | AG1-426 | 80/20 | 11.69 MW | 11.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 966251 | AG1-494 C | 80/20 | 3.18 MW | 3.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 960111 | AF2-302 C | 80/20 | 7.33 MW | 7.33 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 242889 | 05REUSENS | 80/20 | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 938821 | AE1-108 C O1 | 80/20 | 61.69 MW | 61.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 946591 | AF1-323 C | 80/20 | 20.17 MW | 20.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 958131 | AF2-107 C | 80/20 | 8.94 MW | 8.94 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.21 MW | 0.21 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.36 MW | 3.36 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.83 MW | 6.83 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.71 MW | 4.71 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.91 MW | 0.91 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.77 MW | 0.77 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961791 | AG1-021 C | 80/20 | 0.78 MW | 0.78 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961801 | AG1-022 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961891 | AG1-030 C | 80/20 | 5.49 MW | 5.49 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962491 | AG1-098 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962741 | AG1-123 C O1 | 80/20 | 2.24 MW | 2.24 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962751 | AG1-124 C O1 | 80/20 | 3.29 MW | 3.29 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963021 | AG1-151 O1 | 80/20 | 9.03 MW | 9.03 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963171 | AG1-166 C | 80/20 | 0.78 MW | 0.78 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963181 | AG1-167 C | 80/20 | 0.78 MW | 0.78 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963191 | AG1-168 C | 80/20 | 0.78 MW | 0.78 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963201 | AG1-169 C | 80/20 | 0.78 MW | 0.78 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963211 | AG1-170 C | 80/20 | 0.78 MW | 0.78 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963321 | AG1-181 C O1 | 80/20 | 5.27 MW | 5.27 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963361 | AG1-185 O1 | 80/20 | 2.55 MW | 2.55 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963471 | AG1-196 O1 | 80/20 | 17.34 MW | 17.34 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964111 | AG1-272 C | 80/20 | 0.83 MW | 0.83 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964121 | AG1-273 C | 80/20 | 0.83 MW | 0.83 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964131 | AG1-274 C | 80/20 | 0.83 MW | 0.83 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964231 | AG1-284 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964831 | AG1-346 C | 80/20 | 0.83 MW | 0.83 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965191 | AG1-384 C | 80/20 | 0.83 MW | 0.83 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965581 | AG1-426 | 80/20 | 1.92 MW | 1.92 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965641 | AG1-432 C O1 | 80/20 | 9.5 MW | 9.5 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965831 | AG1-451 | 80/20 | 1.58 MW | 1.58 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966251 | AG1-494 C | 80/20 | 1.21 MW | 1.21 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314429 | 3JTRSVLE | 80/20 | 0.18 MW | 0.18 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934625 | AD1-088 C | 80/20 | 3.65 MW | 3.65 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 936265 | AD2-033 C | 80/20 | 4.02 MW | 4.02 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942461 | AE2-259 C O1 | 80/20 | 4.75 MW | 4.75 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958801 | AF2-171 C | 80/20 | 5.81 MW | 5.81 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 959311 | AF2-222 C | 80/20 | 5.55 MW | 5.55 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 960111 | AF2-302 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 242889 | 05REUSENS | 80/20 | 0.04 MW | 0.04 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 925611 | AC1-036 C | 80/20 | 0.08 MW | 0.08 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938371 | AE1-056 C | 80/20 | 2.67 MW | 2.67 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938821 | AE1-108 C O1 | 80/20 | 10.13 MW | 10.13 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941011 | AE2-092 C | 80/20 | 11.2 MW | 11.2 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941791 | AE2-182 C | 80/20 | 0.59 MW | 0.59 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946291 | AF1-293 C O1 | 80/20 | 14.58 MW | 14.58 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946301 | AF1-294 C | 80/20 | 1.59 MW | 1.59 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946591 | AF1-323 C | 80/20 | 3.48 MW | 3.48 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958131 | AF2-107 C | 80/20 | 2.33 MW | 2.33 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958211 | AF2-115 C | 80/20 | 0.97 MW | 0.97 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 235034 | 01SHY_Z2-039 | 80/20 | 0.01 MW | 0.01 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 235035 | 01NHY_Z2-039 | 80/20 | 0.02 MW | 0.02 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 237092 | AD1-085_C | 80/20 | 0.16 MW | 0.16 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940451 | AE2-029 C | 80/20 | 3.28 MW | 3.28 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943571 | AF1-028 O1 | 80/20 | 18.07 MW | 18.07 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 933501 | AC2-165 C | 80/20 | 4.35 MW | 4.35 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944071 | AF1-075 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961061 | AF2-397 C | 80/20 | 12.98 MW | 12.98 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 313738 | 3CUSHAW | 80/20 | 0.1 MW | 0.1 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314333 | 6POWHATN | 80/20 | 0.15 MW | 0.15 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314677 | 6BUCKING | 80/20 | 0.26 MW | 0.26 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314859 | 4WSTVACO | 80/20 | 4.38 MW | 4.38 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 926001 | AC1-076 C | Adder | -2.55 MW | -2.17 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958501 | AF2-144 C | 80/20 | 0.65 MW | 0.65 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966671 | AG1-537 C | 80/20 | 4.45 MW | 4.45 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315186 | 1LOWMORA | 80/20 | 0.44 MW | 0.44 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315188 | 1LOWMORC | 80/20 | 0.44 MW | 0.44 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315191 | 1BEARGRDN G1 | 80/20 | 4.38 MW | 4.38 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315192 | 1BEARGRDN G2 | 80/20 | 4.38 MW | 4.38 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315193 | 1BEARGRDN S1 | 80/20 | 5.67 MW | 5.67 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315201 | 1BATH 1A | 80/20 | 7.89 MW | 7.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315202 | 1BATH 2B | 80/20 | 7.89 MW | 7.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315203 | 1BATH 3C | 80/20 | 7.89 MW | 7.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315204 | 1BATH 4D | 80/20 | 7.89 MW | 7.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315205 | 1BATH 5E | 80/20 | 7.9 MW | 7.9 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315206 | 1BATH 6F | 80/20 | 7.92 MW | 7.92 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315216 | 1CUNINGA | 80/20 | 1.89 MW | 1.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315217 | 1CUNINGB | 80/20 | 1.89 MW | 1.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315218 | 1CUNINGC | 80/20 | 1.89 MW | 1.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315219 | 1CUNINGD | 80/20 | 4.22 MW | 4.22 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315616 | AA1-038 C | 80/20 | 1.04 MW | 1.04 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 932854 | AC2-112 C | 80/20 | 14.33 MW | 14.33 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938561 | AE1-075 C | 80/20 | 0.13 MW | 0.13 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938625 | AE1-084 C | 80/20 | 6.92 MW | 6.92 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941381 | AE2-134 | Adder | -1.76 MW | -1.49 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963461 | AG1-195 | 80/20 | 16.21 MW | 16.21 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965531 | AG1-421 C | 80/20 | 13.88 MW | 13.88 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965541 | AG1-422 | 80/20 | 5.78 MW | 5.78 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966851 | AG1-556 C | 80/20 | 10.31 MW | 10.31 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.09 MW | 1.09 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.81 MW | 0.81 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.07 MW | 26.07 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 21.87 MW | 21.87 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.65 MW | 17.65 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.7 MW | 3.7 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.12 MW | 1.12 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.81 MW | 2.81 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.78 MW | 0.78 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.07 MW | 3.07 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.52 MW | 0.52 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 961801 | AG1-022 C | 80/20 | 7.33 MW | 7.33 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 962741 | AG1-123 C O1 | 80/20 | 5.23 MW | 5.23 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 962751 | AG1-124 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 965581 | AG1-426 | 80/20 | 11.69 MW | 11.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 966251 | AG1-494 C | 80/20 | 3.18 MW | 3.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 960111 | AF2-302 C | 80/20 | 7.33 MW | 7.33 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 242889 | 05REUSENS | 80/20 | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 938821 | AE1-108 C O1 | 80/20 | 61.69 MW | 61.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 946591 | AF1-323 C | 80/20 | 20.17 MW | 20.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | 958131 | AF2-107 C | 80/20 | 8.94 MW | 8.94 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.21 MW | 0.21 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.36 MW | 3.36 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.83 MW | 6.83 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.71 MW | 4.71 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.91 MW | 0.91 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.77 MW | 0.77 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961801 | AG1-022 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961802 | AG1-022 E | 50/50 | 4.89 MW | 4.89 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962741 | AG1-123 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962742 | AG1-123 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962751 | AG1-124 C O1 | 50/50 | 7.19 MW | 7.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962752 | AG1-124 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 965581 | AG1-426 | 50/50 | 11.68 MW | 11.68 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966251 | AG1-494 C | 50/50 | 3.38 MW | 3.38 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966252 | AG1-494 E | 50/50 | 5.07 MW | 5.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946592 | AF1-323 E | 50/50 | 13.46 MW | 13.46 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960111 | AF2-302 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960112 | AF2-302 E | 50/50 | 4.89 MW | 4.89 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 938821 | AE1-108 C O1 | 50/50 | 61.6 MW | 61.6 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 938822 | AE1-108 E O1 | 50/50 | 41.07 MW | 41.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946591 | AF1-323 C | 50/50 | 20.19 MW | 20.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958131 | AF2-107 C | 50/50 | 9.19 MW | 9.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958132 | AF2-107 E | 50/50 | 5.04 MW | 5.04 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946293 | AF1-293 BAT | 50/50 | 8.39 MW | 8.39 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.85 MW | 7.85 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.85 MW | 12.85 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.8 MW | 1.8 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.56 MW | 1.56 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.65 MW | 3.65 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.51 MW | 1.51 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 961801 | AG1-022 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 961802 | AG1-022 E | 50/50 | 4.89 MW | 4.89 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 962741 | AG1-123 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 962742 | AG1-123 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 962751 | AG1-124 C O1 | 50/50 | 7.19 MW | 7.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 962752 | AG1-124 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 965581 | AG1-426 | 50/50 | 11.68 MW | 11.68 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 966251 | AG1-494 C | 50/50 | 3.38 MW | 3.38 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 966252 | AG1-494 E | 50/50 | 5.07 MW | 5.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 946592 | AF1-323 E | 50/50 | 13.46 MW | 13.46 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 960111 | AF2-302 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 960112 | AF2-302 E | 50/50 | 4.89 MW | 4.89 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 938821 | AE1-108 C O1 | 50/50 | 61.61 MW | 61.61 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 938822 | AE1-108 E O1 | 50/50 | 41.07 MW | 41.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 946591 | AF1-323 C | 50/50 | 20.19 MW | 20.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 958131 | AF2-107 C | 50/50 | 9.19 MW | 9.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 958132 | AF2-107 E | 50/50 | 5.04 MW | 5.04 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 946293 | AF1-293 BAT | 50/50 | 8.38 MW | 8.38 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.88 MW | 7.88 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.86 MW | 12.86 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.17 MW | 9.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.57 MW | 0.57 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.81 MW | 1.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.57 MW | 1.57 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.65 MW | 3.65 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.52 MW | 1.52 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246843 | 05SMG1 | 50/50 | 2.99 MW | 2.99 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246844 | 05SMG2 | 50/50 | 8.13 MW | 8.13 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246845 | 05SMG3 | 50/50 | 5.1 MW | 5.1 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246846 | 05SMG4 | 50/50 | 8.01 MW | 8.01 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246847 | 05SMG5 | 50/50 | 3.12 MW | 3.12 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 247284 | 05LEESVG | 50/50 | 3.66 MW | 3.66 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 926051 | AC1-083 C O1 | 50/50 | 6.86 MW | 6.86 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 926052 | AC1-083 E O1 | 50/50 | 11.19 MW | 11.19 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 926521 | AC1-123 C O1 | 50/50 | 2.29 MW | 2.29 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 926522 | AC1-123 E O1 | 50/50 | 6.33 MW | 6.33 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 927261 | AC1-222 C | Adder | -1.97 MW | -1.67 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 933941 | AD1-017 C | 50/50 | 1.37 MW | 1.37 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 933942 | AD1-017 E | 50/50 | 2.24 MW | 2.24 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 934311 | AD1-055 C | Adder | -1.36 MW | -1.16 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 943901 | AF1-058 C | Adder | -0.68 MW | -0.57 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 925661 | AC1-042 C | Adder | -5.97 MW | -5.07 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 938451 | AE1-064 C | 50/50 | 13.77 MW | 13.77 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 938452 | AE1-064 E | 50/50 | 7.12 MW | 7.12 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 940081 | AE1-250 C | 50/50 | 11.77 MW | 11.77 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 940082 | AE1-250 E | 50/50 | 7.84 MW | 7.84 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 966693 | AG1-539 BAT | 50/50 | 17.75 MW | 17.75 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 961131 | AF2-404 BAT | 50/50 | 7.48 MW | 7.48 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 966763 | AG1-547 BAT | 50/50 | 4.49 MW | 4.49 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 961122 | AF2-403 BAT | 50/50 | 7.48 MW | 7.48 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 966253 | AG1-494 BAT | Adder | 4.52 MW | 3.84 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.14 MW | 0.14 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.86 MW | 2.86 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.65 MW | 1.65 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.44 MW | 1.44 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.2 MW | 0.2 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.18 MW | 0.18 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.31 MW | 0.31 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.22 MW | 0.22 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.12 MW | 1.12 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.26 MW | 0.26 MW |
| 05LEESVI-4ALTVSTA 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961801 | AG1-022 C | 50/50 | 7.34 MW | 7.34 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961802 | AG1-022 E | 50/50 | 4.89 MW | 4.89 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962741 | AG1-123 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962742 | AG1-123 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962751 | AG1-124 C O1 | 50/50 | 7.19 MW | 7.19 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962752 | AG1-124 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966251 | AG1-494 C | 50/50 | 3.38 MW | 3.38 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966252 | AG1-494 E | 50/50 | 5.07 MW | 5.07 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 926522 | AC1-123 E O1 | Adder | 1.34 MW | 1.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946592 | AF1-323 E | 50/50 | 13.46 MW | 13.46 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960111 | AF2-302 C | 50/50 | 7.34 MW | 7.34 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960112 | AF2-302 E | 50/50 | 4.89 MW | 4.89 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946591 | AF1-323 C | 50/50 | 20.19 MW | 20.19 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958131 | AF2-107 C | 50/50 | 9.19 MW | 9.19 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958132 | AF2-107 E | 50/50 | 5.04 MW | 5.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 965582 | AG1-426 BAT | 50/50 | 13.31 MW | 13.31 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946293 | AF1-293 BAT | 50/50 | 8.39 MW | 8.39 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961063 | AF2-397 BAT | Adder | 3.4 MW | 2.89 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.85 MW | 7.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.85 MW | 12.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.8 MW | 1.8 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.56 MW | 1.56 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.65 MW | 3.65 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.51 MW | 1.51 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246843 | 05SMG1 | 50/50 | 3.0 MW | 3.0 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246844 | 05SMG2 | 50/50 | 8.14 MW | 8.14 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246845 | 05SMG3 | 50/50 | 5.1 MW | 5.1 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246846 | 05SMG4 | 50/50 | 8.01 MW | 8.01 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 246847 | 05SMG5 | 50/50 | 3.12 MW | 3.12 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 926051 | AC1-083 C O1 | 50/50 | 6.87 MW | 6.87 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 926052 | AC1-083 E O1 | 50/50 | 11.21 MW | 11.21 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 926521 | AC1-123 C O1 | 50/50 | 2.29 MW | 2.29 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 926522 | AC1-123 E O1 | 50/50 | 6.34 MW | 6.34 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 927261 | AC1-222 C | Adder | -1.96 MW | -1.67 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 933941 | AD1-017 C | 50/50 | 1.37 MW | 1.37 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 933942 | AD1-017 E | 50/50 | 2.24 MW | 2.24 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 934311 | AD1-055 C | Adder | -1.36 MW | -1.16 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 943901 | AF1-058 C | Adder | -0.67 MW | -0.57 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 925661 | AC1-042 C | Adder | -5.97 MW | -5.07 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 938451 | AE1-064 C | 50/50 | 13.79 MW | 13.79 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 938452 | AE1-064 E | 50/50 | 7.13 MW | 7.13 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 940081 | AE1-250 C | 50/50 | 11.79 MW | 11.79 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 940082 | AE1-250 E | 50/50 | 7.86 MW | 7.86 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 966763 | AG1-547 BAT | 50/50 | 4.49 MW | 4.49 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 961131 | AF2-404 BAT | 50/50 | 7.48 MW | 7.48 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 961122 | AF2-403 BAT | 50/50 | 7.48 MW | 7.48 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 966693 | AG1-539 BAT | 50/50 | 17.73 MW | 17.73 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | 966253 | AG1-494 BAT | Adder | 4.5 MW | 3.83 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.15 MW | 0.15 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.13 MW | 3.13 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.01 MW | 2.01 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.67 MW | 1.67 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.22 MW | 0.22 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.35 MW | 0.35 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.26 MW | 0.26 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.29 MW | 0.29 MW |
| 05SMITHMTN-05LEESVI 138.0 kV Ckt 1 line l/o AEP_P4_#13922_05OPOSSUMCK 138_D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961801 | AG1-022 C | 50/50 | 7.34 MW | 7.34 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961802 | AG1-022 E | 50/50 | 4.89 MW | 4.89 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962741 | AG1-123 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962742 | AG1-123 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962751 | AG1-124 C O1 | 50/50 | 7.19 MW | 7.19 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962752 | AG1-124 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966251 | AG1-494 C | 50/50 | 3.38 MW | 3.38 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966252 | AG1-494 E | 50/50 | 5.07 MW | 5.07 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 926522 | AC1-123 E O1 | Adder | 1.34 MW | 1.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946592 | AF1-323 E | 50/50 | 13.46 MW | 13.46 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960111 | AF2-302 C | 50/50 | 7.34 MW | 7.34 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960112 | AF2-302 E | 50/50 | 4.89 MW | 4.89 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946591 | AF1-323 C | 50/50 | 20.19 MW | 20.19 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958131 | AF2-107 C | 50/50 | 9.19 MW | 9.19 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958132 | AF2-107 E | 50/50 | 5.04 MW | 5.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 965582 | AG1-426 BAT | 50/50 | 13.31 MW | 13.31 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946293 | AF1-293 BAT | 50/50 | 8.39 MW | 8.39 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961063 | AF2-397 BAT | Adder | 3.4 MW | 2.89 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.85 MW | 7.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.85 MW | 12.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.8 MW | 1.8 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.56 MW | 1.56 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.65 MW | 3.65 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.51 MW | 1.51 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 962741 | AG1-123 C O1 | Adder | 2.16 MW | 1.84 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 962742 | AG1-123 E O1 | Adder | 1.49 MW | 1.26 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 962751 | AG1-124 C O1 | Adder | 3.3 MW | 2.81 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 962752 | AG1-124 E O1 | Adder | 1.74 MW | 1.48 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 966691 | AG1-539 C | 50/50 | 3.62 MW | 3.62 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 966692 | AG1-539 E | 50/50 | 4.86 MW | 4.86 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 966761 | AG1-547 C | 50/50 | 5.68 MW | 5.68 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 966762 | AG1-547 E | 50/50 | 3.05 MW | 3.05 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 966251 | AG1-494 C | Adder | 1.1 MW | 0.94 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 966252 | AG1-494 E | Adder | 1.65 MW | 1.41 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 246843 | 05SMG1 | 50/50 | 4.02 MW | 4.02 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 246844 | 05SMG2 | 50/50 | 10.92 MW | 10.92 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 246845 | 05SMG3 | 50/50 | 6.85 MW | 6.85 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 246846 | 05SMG4 | 50/50 | 10.75 MW | 10.75 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 246847 | 05SMG5 | 50/50 | 4.19 MW | 4.19 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 247284 | 05LEESVG | 50/50 | 2.17 MW | 2.17 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 315156 | 1HALLBR1 | 50/50 | 1.44 MW | 1.44 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 926051 | AC1-083 C O1 | 50/50 | 12.62 MW | 12.62 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 926052 | AC1-083 E O1 | 50/50 | 20.6 MW | 20.6 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 926521 | AC1-123 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 926522 | AC1-123 E O1 | 50/50 | 6.12 MW | 6.12 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 926645 | AC1-145 C | 50/50 | 0.56 MW | 0.56 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 926646 | AC1-145 E | 50/50 | 2.98 MW | 2.98 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 933941 | AD1-017 C | 50/50 | 2.52 MW | 2.52 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 933942 | AD1-017 E | 50/50 | 4.12 MW | 4.12 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 942671 | AE2-283 C | 50/50 | 6.91 MW | 6.91 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 942672 | AE2-283 E | 50/50 | 3.63 MW | 3.63 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 942751 | AE2-291 C | 50/50 | 6.92 MW | 6.92 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 942752 | AE2-291 E | 50/50 | 4.61 MW | 4.61 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 942761 | AE2-292 C O1 | 50/50 | 8.61 MW | 8.61 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 942762 | AE2-292 E O1 | 50/50 | 5.74 MW | 5.74 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 961121 | AF2-403 | 50/50 | 1.4 MW | 1.4 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 925661 | AC1-042 C | 50/50 | 2.79 MW | 2.79 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 925662 | AC1-042 E | 50/50 | 4.54 MW | 4.54 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 938451 | AE1-064 C | 50/50 | 30.15 MW | 30.15 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 938452 | AE1-064 E | 50/50 | 15.59 MW | 15.59 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 940081 | AE1-250 C | 50/50 | 29.9 MW | 29.9 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 940082 | AE1-250 E | 50/50 | 19.93 MW | 19.93 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 941801 | AE2-185 C | 50/50 | 6.28 MW | 6.28 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 941802 | AE2-185 E | 50/50 | 4.19 MW | 4.19 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 941821 | AE2-187 C | 50/50 | 6.28 MW | 6.28 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 941822 | AE2-187 E | 50/50 | 2.79 MW | 2.79 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 925997 | AC1-075 E | Adder | 2.0 MW | 1.7 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | 926024 | AC1-080 E | Adder | 0.66 MW | 0.56 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.22 MW | 0.22 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.2 MW | 0.2 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.42 MW | 0.42 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.79 MW | 2.79 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.21 MW | 0.21 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.12 MW | 0.12 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.71 MW | 0.71 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.47 MW | 0.47 MW |
| 05ROCKCAS SS-05MONETA 138.0 kV Ckt 1 line l/o AEP_P4_#10164_05EDAN 2 138_M | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 966691 | AG1-539 C | Adder | 2.11 MW | 1.8 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 966692 | AG1-539 E | Adder | 2.84 MW | 2.42 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 966761 | AG1-547 C | 50/50 | 3.38 MW | 3.38 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 966762 | AG1-547 E | 50/50 | 1.81 MW | 1.81 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 246843 | 05SMG1 | 50/50 | 2.1 MW | 2.1 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 246844 | 05SMG2 | 50/50 | 5.7 MW | 5.7 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 246845 | 05SMG3 | 50/50 | 3.58 MW | 3.58 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 246846 | 05SMG4 | 50/50 | 5.61 MW | 5.61 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 246847 | 05SMG5 | 50/50 | 2.19 MW | 2.19 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 247284 | 05LEESVG | 50/50 | 1.19 MW | 1.19 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 926051 | AC1-083 C O1 | 50/50 | 4.89 MW | 4.89 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 926052 | AC1-083 E O1 | 50/50 | 7.98 MW | 7.98 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 926521 | AC1-123 C O1 | 50/50 | 3.94 MW | 3.94 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 926522 | AC1-123 E O1 | 50/50 | 10.88 MW | 10.88 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 926645 | AC1-145 C | 50/50 | 0.34 MW | 0.34 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 926646 | AC1-145 E | 50/50 | 1.77 MW | 1.77 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 933941 | AD1-017 C | 50/50 | 0.98 MW | 0.98 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 933942 | AD1-017 E | 50/50 | 1.6 MW | 1.6 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 942671 | AE2-283 C | 50/50 | 4.11 MW | 4.11 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 942672 | AE2-283 E | 50/50 | 2.16 MW | 2.16 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 942751 | AE2-291 C | Adder | 4.04 MW | 3.44 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 942752 | AE2-291 E | Adder | 2.7 MW | 2.29 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 942761 | AE2-292 C O1 | Adder | 5.04 MW | 4.28 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 942762 | AE2-292 E O1 | Adder | 3.36 MW | 2.85 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 961121 | AF2-403 | 50/50 | 0.83 MW | 0.83 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 925661 | AC1-042 C | 50/50 | 1.66 MW | 1.66 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 925662 | AC1-042 E | 50/50 | 2.71 MW | 2.71 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 938451 | AE1-064 C | 50/50 | 9.55 MW | 9.55 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 938452 | AE1-064 E | 50/50 | 4.94 MW | 4.94 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 940081 | AE1-250 C | Adder | 8.58 MW | 7.3 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 940082 | AE1-250 E | Adder | 5.72 MW | 4.86 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 941801 | AE2-185 C | 50/50 | 3.74 MW | 3.74 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 941802 | AE2-185 E | 50/50 | 2.49 MW | 2.49 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 941821 | AE2-187 C | 50/50 | 3.74 MW | 3.74 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 941822 | AE2-187 E | 50/50 | 1.66 MW | 1.66 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 925997 | AC1-075 E | Adder | 1.2 MW | 1.02 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 926024 | AC1-080 E | Adder | 0.4 MW | 0.34 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | 966253 | AG1-494 BAT | Adder | 4.98 MW | 4.23 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.47 MW | 0.47 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.09 MW | 0.09 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.25 MW | 0.25 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.67 MW | 6.67 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.71 MW | 0.71 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.07 MW | 0.07 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.1 MW | 0.1 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.48 MW | 0.48 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.16 MW | 0.16 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.08 MW | 0.08 MW |
| AC1-123 TAP-05CAMDLM 138.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.06 MW | 0.06 MW |
Light Load Analysis
The Queue Project was evaluated as a 50.0 MW (Capacity 20.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193
CONTINGENCY 'DVP_P1-2: LN 2193' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 135.97 % | 137.45 % | 269.78 | B | 370.81 | 3.94 | |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940661 | AE2-053 O1 | 80/20 | 1.03 MW | 1.03 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941281 | AE2-122 C O1 | Adder | 3.34 MW | 2.84 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941282 | AE2-122 E O1 | Adder | 13.48 MW | 11.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941291 | AE2-123 C O1 | Adder | 3.43 MW | 2.92 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941292 | AE2-123 E O1 | Adder | 13.38 MW | 11.38 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941301 | AE2-124 C O1 | Adder | 3.12 MW | 2.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941302 | AE2-124 E O1 | Adder | 13.69 MW | 11.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 957911 | AF2-085 | 80/20 | 1.09 MW | 1.09 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958502 | AF2-144 E | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964111 | AG1-272 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964112 | AG1-272 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964121 | AG1-273 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964122 | AG1-273 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964131 | AG1-274 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964132 | AG1-274 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964791 | AG1-342 C | 80/20 | 0.18 MW | 0.18 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964792 | AG1-342 E | 80/20 | 0.27 MW | 0.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965191 | AG1-384 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965192 | AG1-384 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965831 | AG1-451 | 80/20 | 2.94 MW | 2.94 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944581 | AF1-123 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944582 | AF1-123 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944591 | AF1-124 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944592 | AF1-124 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944601 | AF1-125 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944602 | AF1-125 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963361 | AG1-185 C | 80/20 | 4.34 MW | 4.34 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963362 | AG1-185 E | 80/20 | 3.64 MW | 3.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 946293 | AF1-293 BAT | 80/20 | 27.71 MW | 27.71 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961063 | AF2-397 BAT | 80/20 | 8.65 MW | 8.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965583 | AG1-426 BAT | 80/20 | 14.15 MW | 14.15 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 966253 | AG1-494 BAT | 80/20 | 3.94 MW | 3.94 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 966673 | AG1-537 BAT | 80/20 | 4.39 MW | 4.39 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n8360 | Reconductor/ Rebuild 17.2 miles between Candiers Mountain - Redeye 138kV which currently has ACSR ~ 556 ACSR ~ 26/7 overhead conductor | $34,400,000 | |
| n6972.3 | Increase CT thermal limit at Leesville above 327 MVA | $25,000 | |
| n6972.2 | Rebuild the 8.1 mile section ACSR ~556.5 ~26/7~DOVE on the Smith Mountain - Leesville 138 kV line. | $12,150,000 | |
| n6972.1 | Replace Leesville & Smithmtn Riser Sub Cond 795 AAC 37 Str | $100,000 | |
| n6594.3 | An engineering study will need to be conducted. | $25,000 | |
| n6594.4 | Replace Leesville Wavetrap (1200A) | $100,000 | |
| n6594.1 | Rebuild 8.4 miles section of the Leesville - Alta Vista 138 kV line | $23,571,948 | |
| n6594.2 | An engineering study will need to be conducted to determine | $50,000 | |
| n8381 | A sag study will be required on the 5.08 miles of 2-bundle ACSR ~ 556.5 ~ 26/7 ~ DOVE~ Conductor to determine what mitigation | $60,000 | |
| n8347.2 | Replace 7.21 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK, Conductor Section 1 | $9,750,000 | |
| n8347.1 | A sag study will be required on the 6.5 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK ~ Conductor | $39,000 | |
| n7811 | A sag study will be required on the 0.85 miles of ACSR ~ 397.5 ~ 30/7 | $3,400 | |
| n6852 | Add an additional 2 miles single circuit 230 kV line from Fork Union to Bremo parallel to existing line. Add a breaker at Fork Union 230 kV and Bremo 230 kV | $3,500,000 | |
| n7812 | Reconductor 8.502 miles of 138 kV line 8 from AE1-108 Tap to Bremo with 636 ACSR 150 C | $5,101,200 | |
| n7581 | Rebuild 4.27 miles of 230 kV Line 2135 from Hollymead to Cashs Corner D.P. with 2-636 ACSR 150 C | $10,675,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-494 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.