AG1-462 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:57
Cordova B 345 kV
153.0 MW Capacity / 255.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-462 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the ComEd zone — Whiteside County, Illinois. The installed facilities will have a total capability of 255.0 MW with 153.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-462 |
| Project Name | Cordova B 345 kV |
| Developer Name | Gipper Solar Farm, LLC |
| State | Illinois |
| County | Whiteside |
| Transmission Owner | ComEd |
| MFO | 255.0 MW |
| MWE | 255.0 MW |
| MWC | 153.0 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-462 will interconnect on the ComEd transmission system tying into the Cordova B 345 kV substation..
Summer Peak Analysis
The Queue Project was evaluated as a 255.0 MW (Capacity 153.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 180.92 % | 182.06 % | 1409.0 | B | 2565.25 | 19.0 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 180.92 % | 182.06 % | 1409.0 | B | 2565.21 | 19.0 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 122.12 % | 123.31 % | 971.0 | STE | 1197.29 | 13.12 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 122.12 % | 123.31 % | 971.0 | STE | 1197.29 | 13.12 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 116.63 % | 117.81 % | 1399.0 | B | 1648.22 | 16.6 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 116.62 % | 117.81 % | 1399.0 | B | 1648.16 | 16.6 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
Base Case | Single | AC | 111.09 % | 112.2 % | 1201.0 | A | 1347.49 | 12.78 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
Base Case | Single | AC | 106.28 % | 107.9 % | 1334.0 | A | 1439.33 | 26.71 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 107.12 % | 108.17 % | 1091.0 | B | 1180.19 | 11.88 | |
| CE/NIPS |
17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line
255112 to 270886 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 107.12 % | 108.17 % | 1091.0 | B | 1180.18 | 11.88 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 107.12 % | 108.17 % | 1091.0 | B | 1180.17 | 11.88 | |
| CE/NIPS |
17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line
255112 to 270886 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 107.12 % | 108.17 % | 1091.0 | B | 1180.16 | 11.88 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1
CONTINGENCY '270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1' /* Auto-generated /* 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 END |
Single | AC | 99.44 % | 100.36 % | 1568.0 | STE | 1573.63 | 13.82 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P1-2_345-L0303__R-S
CONTINGENCY 'COMED_P1-2_345-L0303__R-S' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Single | AC | 99.44 % | 100.36 % | 1568.0 | STE | 1573.63 | 13.82 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3128_05EUGENE 345_A2
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2' OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1 /*05EUGENE 345.0 - 08CAYSUB 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 171.0 % | 171.37 % | 1466.0 | B | 2512.34 | 20.39 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3130_05EUGENE 345_B2
CONTINGENCY 'AEP_P4_#3130_05EUGENE 345_B2' OPEN BRANCH FROM BUS 243221 TO BUS 247712 CKT 1 /*05EUGENE 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 157.68 % | 157.96 % | 1466.0 | B | 2315.75 | 20.67 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 144.85 % | 146.28 % | 1568.0 | STE | 2293.65 | 25.6 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P4_144-45-BT6-7__
CONTINGENCY 'COMED_P4_144-45-BT6-7__' DISCONNECT BUS 275228 /*WAYNE ;1M 138.0 TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1 /*WAYNE ; B 345.0 - TOLLWAY ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 END |
Breaker | AC | 144.85 % | 146.28 % | 1568.0 | STE | 2293.6 | 25.6 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 135.36 % | 136.78 % | 1568.0 | STE | 2144.71 | 25.6 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P4_144-45-BT6-7__
CONTINGENCY 'COMED_P4_144-45-BT6-7__' DISCONNECT BUS 275228 /*WAYNE ;1M 138.0 TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1 /*WAYNE ; B 345.0 - TOLLWAY ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 END |
Breaker | AC | 135.36 % | 136.78 % | 1568.0 | STE | 2144.67 | 25.6 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 113.68 % | 117.07 % | 1837.0 | STE | 2150.6 | 60.5 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_112-45-BT4-5__
CONTINGENCY 'COMED_P4_112-45-BT4-5__' TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1 /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1 /*BLUE ISL ;BT 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1 /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0 TRIP BRANCH FROM BUS 270852 TO BUS 270704 CKT 1 /*PONTIAC ; B 345.0 - LORETTO ; B 345.0 END |
Breaker | AC | 110.71 % | 111.96 % | 2083.0 | STE | 2332.2 | 24.53 | |
| CE |
AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line
957470 to 270730 ckt 1 |
COMED_P4_006-45-BT3-8__
CONTINGENCY 'COMED_P4_006-45-BT3-8__' TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT 1 /*BYRON ; B 345.0 - BYRON ; R 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 END |
Breaker | AC | 112.38 % | 114.62 % | 1837.0 | STE | 2105.59 | 60.41 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_076-45-BT4-5__
CONTINGENCY 'COMED_P4_076-45-BT4-5__' TRIP BRANCH FROM BUS 270664 TO BUS 275162 CKT 1 /*BLUE ISL ; B 345.0 - BLUE ISL ;3M 138.0 TRIP BRANCH FROM BUS 270664 TO BUS 275181 CKT 1 /*BLUE ISL ; B 345.0 - BLUE ISL ;4M 138.0 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1 /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1 /*BLUE ISL ;BT 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 270674 TO BUS 270664 CKT 1 /*BURNHAM ; B 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1 /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0 TRIP BRANCH FROM BUS 275162 TO BUS 271100 CKT 1 /*BLUE ISL ;3M 138.0 - BLUE ISL ; B 138.0 TRIP BRANCH FROM BUS 275181 TO BUS 271100 CKT 1 /*BLUE ISL ;4M 138.0 - BLUE ISL ; B 138.0 TRIP BRANCH FROM BUS 275262 TO BUS 275162 CKT 1 /*BLUE ISLA;3C 34.5 - BLUE ISL ;3M 138.0 TRIP BRANCH FROM BUS 275281 TO BUS 275181 CKT 1 /*BLUE ISLA;4C 34.5 - BLUE ISL ;4M 138.0 END |
Breaker | AC | 107.62 % | 108.63 % | 2083.0 | STE | 2262.83 | 24.26 | |
| CE |
PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275207 to 270630 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 117.24 % | 117.59 % | 1469.0 | STE | 1727.36 | 18.73 | |
| CE |
PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line
270846 to 275207 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 117.13 % | 117.5 % | 1469.0 | STE | 1726.01 | 18.73 | |
| CE |
PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275208 to 270630 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 115.4 % | 115.63 % | 1469.0 | STE | 1698.61 | 15.83 | |
| CE |
PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line
270847 to 275208 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 114.99 % | 115.22 % | 1469.0 | STE | 1692.53 | 15.83 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 101.93 % | 105.27 % | 1837.0 | STE | 1933.83 | 60.5 | |
| CE |
ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line
270730 to 270812 ckt 1 |
COMED_P4_012-45-BT5-6__
CONTINGENCY 'COMED_P4_012-45-BT5-6__' TRIP BRANCH FROM BUS 270716 TO BUS 270736 CKT 1 /*DRESDEN ; B 345.0 - ELWOOD ; B 345.0 TRIP BRANCH FROM BUS 270736 TO BUS 270737 CKT 1 /*ELWOOD ; B 345.0 - ELWOOD ; R 345.0 TRIP BRANCH FROM BUS 274702 TO BUS 270716 CKT 1 /*KENDALL ;BU 345.0 - DRESDEN ; B 345.0 END |
Breaker | AC | 110.64 % | 111.54 % | 1568.0 | STE | 1748.87 | 16.57 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_937-45-BT1-4__
CONTINGENCY 'COMED_P4_937-45-BT1-4__' REMOVE UNIT W1 FROM BUS 274857 /*BIG SKY ;U1 0.7 REMOVE UNIT W2 FROM BUS 274858 /*BIG SKY ;U2 0.7 TRIP BRANCH FROM BUS 271421 TO BUS 274450 CKT 1 /*EASY ROAD; B 138.0 - EASY ROAD;1 34.5 TRIP BRANCH FROM BUS 271421 TO BUS 274451 CKT 1 /*EASY ROAD; B 138.0 - EASY ROAD;2 34.5 TRIP BRANCH FROM BUS 272528 TO BUS 271421 CKT 1 /*S DIXON ; B 138.0 - EASY ROAD; B 138.0 TRIP BRANCH FROM BUS 274420 TO BUS 274857 CKT 1 /*EASY ROAD;1H 34.5 - BIG SKY ;U1 0.7 TRIP BRANCH FROM BUS 274421 TO BUS 274858 CKT 1 /*EASY ROAD;2H 34.5 - BIG SKY ;U2 0.7 TRIP BRANCH FROM BUS 274450 TO BUS 274420 CKT 1 /*EASY ROAD;1 34.5 - EASY ROAD;1H 34.5 TRIP BRANCH FROM BUS 274451 TO BUS 274421 CKT 1 /*EASY ROAD;2 34.5 - EASY ROAD;2H 34.5 TRIP BRANCH FROM BUS 274768 TO BUS 272528 CKT 1 /*LEE CO EC;BP 345.0 - S DIXON ; B 138.0 TRIP BRANCH FROM BUS 946150 TO BUS 274768 CKT 1 /*AF1-280 TAP 345.0 - LEE CO EC;BP 345.0 END |
Breaker | AC | 98.06 % | 101.39 % | 1837.0 | STE | 1862.59 | 60.51 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_937-45-BT1-2__
CONTINGENCY 'COMED_P4_937-45-BT1-2__' TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 946150 TO BUS 274768 CKT 1 /*AF1-280 TAP 345.0 - LEE CO EC;BP 345.0 END |
Breaker | AC | 97.94 % | 101.27 % | 1837.0 | STE | 1860.38 | 60.51 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 99.96 % | 102.21 % | 1837.0 | STE | 1877.66 | 48.84 | |
| CE |
AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line
965660 to 957470 ckt 1 |
COMED_P4_144-45-BT6-7__
CONTINGENCY 'COMED_P4_144-45-BT6-7__' DISCONNECT BUS 275228 /*WAYNE ;1M 138.0 TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1 /*WAYNE ; B 345.0 - TOLLWAY ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 END |
Breaker | AC | 99.93 % | 102.19 % | 1837.0 | STE | 1877.14 | 48.84 | |
| CE |
NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer
270828 to 275204 ckt 1 |
COMED_P4_155-45-BT2-34_
CONTINGENCY 'COMED_P4_155-45-BT2-34_' TRIP BRANCH FROM BUS 270828 TO BUS 272094 TO BUS 275341 CKT 1 /*NELSON ; B 345.0 - NELSON ; B 138.0 - NELSON ;1C 34.5 TRIP BRANCH FROM BUS 270828 TO BUS 965660 CKT 1 /*NELSON ; B 345.0 - AG1-434 TAP 345.0 END |
Breaker | AC | 98.43 % | 100.65 % | 493.0 | STE | 496.18 | 12.86 | |
| CE |
NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line
270828 to 965660 ckt 1 |
COMED_P4_937-45-BT2-3__
CONTINGENCY 'COMED_P4_937-45-BT2-3__' REMOVE UNIT 1 FROM BUS 274760 /*LEE CO EC;1U 13.8 REMOVE UNIT 2 FROM BUS 274761 /*LEE CO EC;2U 13.8 REMOVE UNIT 3 FROM BUS 274762 /*LEE CO EC;3U 13.8 REMOVE UNIT 4 FROM BUS 274763 /*LEE CO EC;4U 13.8 REMOVE UNIT 5 FROM BUS 274764 /*LEE CO EC;5U 13.8 REMOVE UNIT 6 FROM BUS 274765 /*LEE CO EC;6U 13.8 REMOVE UNIT 7 FROM BUS 274766 /*LEE CO EC;7U 13.8 REMOVE UNIT 8 FROM BUS 274767 /*LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274760 TO BUS 274761 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;1U 13.8 - LEE CO EC;2U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274762 TO BUS 274763 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;3U 13.8 - LEE CO EC;4U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274764 TO BUS 274765 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;5U 13.8 - LEE CO EC;6U 13.8 TRIP BRANCH FROM BUS 274759 TO BUS 274766 TO BUS 274767 CKT 1 /*LEE CO EC; 345.0 - LEE CO EC;7U 13.8 - LEE CO EC;8U 13.8 TRIP BRANCH FROM BUS 274768 TO BUS 270678 CKT 1 /*LEE CO EC;BP 345.0 - BYRON ; B 345.0 TRIP BRANCH FROM BUS 274768 TO BUS 274759 CKT 1 /*LEE CO EC;BP 345.0 - LEE CO EC; 345.0 END |
Breaker | AC | 106.6 % | 110.33 % | 1656.0 | B | 1827.03 | 60.5 | |
| CE |
NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line
270828 to 965660 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 105.2 % | 107.72 % | 1656.0 | B | 1783.88 | 48.84 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P2-2_#286_05EUGENE 345_2
CONTINGENCY 'AEP_P2-2_#286_05EUGENE 345_2' OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Bus | AC | 157.98 % | 158.08 % | 1466.0 | B | 2317.41 | 20.65 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S' TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1 /*KATYDID ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 146.13 % | 147.47 % | 2033.0 | ALDR | 2998.0 | 25.53 | |
| AMIL/CE |
7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line
349662 to 930760 ckt 1 |
COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S
CONTINGENCY 'COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S' TRIP BRANCH FROM BUS 270790 TO BUS 270770 CKT 1 /*KATYDID ; B 345.0 - GOODINGS ;4B 345.0 TRIP BRANCH FROM BUS 270827 TO BUS 270769 CKT 1 /*NEVADA ; R 345.0 - GOODINGS ;2R 345.0 END |
Tower | AC | 162.51 % | 164.25 % | 1479.0 | B | 2429.27 | 25.53 | |
| CE |
AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line
930760 to 270717 ckt 1 |
COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B
CONTINGENCY 'COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 270854 TO BUS 270790 CKT 1 /*POWERTON ; B 345.0 - KATYDID ; B 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Tower | AC | 134.39 % | 135.64 % | 2033.0 | ALDR | 2757.53 | 25.58 | |
| AMIL/CE |
7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line
349662 to 930760 ckt 1 |
COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B
CONTINGENCY 'COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B' REMOVE SWSHUNT FROM BUS 270827 /*NEVADA ; R 345.0 TRIP BRANCH FROM BUS 270854 TO BUS 270790 CKT 1 /*POWERTON ; B 345.0 - KATYDID ; B 345.0 TRIP BRANCH FROM BUS 936290 TO BUS 270827 CKT 1 /*AD2-038 TAP 345.0 - NEVADA ; R 345.0 END |
Tower | AC | 148.62 % | 150.5 % | 1479.0 | B | 2225.95 | 25.58 | |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 19.53 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 25.97 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 25.57 MW | 21.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 10.11 MW | 8.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 8.2 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 95.03 MW | 95.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 15.96 MW | 13.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 29.36 MW | 24.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 4.18 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.39 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965091 | AG1-374 C | Adder | 19.52 MW | 16.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 19.89 MW | 16.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 17.05 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.84 MW | 4.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 4.55 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 19.0 MW | 16.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.47 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 2.1 MW | 1.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 16.63 MW | 16.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 3.09 MW | 2.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 20.75 MW | 17.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 3.42 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 22.92 MW | 19.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.86 MW | 3.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 5.54 MW | 4.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 3.26 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 9.91 MW | 8.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 2.21 MW | 1.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.62 MW | 3.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 1.02 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 14.94 MW | 12.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 9.93 MW | 8.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 4.47 MW | 3.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 13.4 MW | 11.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 13.16 MW | 11.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 24.1 MW | 20.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 4.28 MW | 3.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 8.36 MW | 7.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 16.73 MW | 14.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 7.05 MW | 5.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 7.15 MW | 6.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 6.27 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 25.46 MW | 21.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 9.78 MW | 8.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 1.3 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 8.18 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.98 MW | 6.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 5.32 MW | 4.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 15.09 MW | 15.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274723 | RIVER EC ;12 | 80/20 | 5.49 MW | 5.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274724 | RIVER EC ;11 | 80/20 | 5.46 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | 80/20 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | 80/20 | 7.57 MW | 7.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274792 | SE CHICAG;9U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274793 | SE CHICAG;0U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274794 | SE CHICAG;1U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274795 | SE CHICAG;2U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274798 | UNIV PARK;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274799 | UNIV PARK;2U | 80/20 | 1.52 MW | 1.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274826 | FISK ;BP | 80/20 | 2.86 MW | 2.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274827 | FISK ;RP | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276164 | X3-005 C | 80/20 | 0.11 MW | 0.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276592 | O-012 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.68 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 42.84 MW | 36.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 34.06 MW | 28.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 80.68 MW | 68.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 86.94 MW | 73.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 3.1 MW | 2.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 10.72 MW | 9.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 9.8 MW | 8.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.61 MW | 3.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 7.16 MW | 6.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 12.06 MW | 10.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 9.54 MW | 8.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 7.7 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 13.91 MW | 11.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 5.68 MW | 4.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 18.34 MW | 15.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 5.1 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 6.86 MW | 5.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.34 MW | 1.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.65 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 25.1 MW | 21.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.28 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 22.18 MW | 18.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | Adder | 39.58 MW | 33.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.82 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 6.52 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 361.52 MW | 307.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 953871 | J847 | External Queue | 13.43 MW | 13.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 954751 | J351 | External Queue | 441.39 MW | 441.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 955741 | J1058 | External Queue | 24.2 MW | 24.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990541 | J1332 | External Queue | 26.68 MW | 26.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990646 | J1355 | External Queue | 43.02 MW | 43.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990661 | J1358 | External Queue | 15.6 MW | 15.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990761 | J1386 | External Queue | 13.07 MW | 13.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990976 | J1447 | External Queue | 28.98 MW | 28.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 991271 | J1724 | External Queue | 41.93 MW | 41.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 991331 | J1785 | External Queue | 13.63 MW | 13.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.77 MW | 1.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 101.19 MW | 101.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.78 MW | 26.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.57 MW | 0.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.99 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.62 MW | 15.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.62 MW | 0.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.38 MW | 4.38 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 19.53 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 25.97 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 25.57 MW | 21.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 10.11 MW | 8.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 8.2 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 95.03 MW | 95.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 15.96 MW | 13.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 29.36 MW | 24.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 4.18 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.39 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965091 | AG1-374 C | Adder | 19.52 MW | 16.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 19.89 MW | 16.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 17.05 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.84 MW | 4.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 4.55 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 19.0 MW | 16.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.47 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 2.1 MW | 1.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 16.63 MW | 16.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 3.09 MW | 2.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 20.75 MW | 17.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 3.42 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 22.92 MW | 19.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.86 MW | 3.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 5.54 MW | 4.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 3.26 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 9.91 MW | 8.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 2.21 MW | 1.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.62 MW | 3.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 1.02 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 14.94 MW | 12.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 9.93 MW | 8.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 4.47 MW | 3.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 13.4 MW | 11.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 13.16 MW | 11.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 24.1 MW | 20.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 4.28 MW | 3.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 8.36 MW | 7.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 16.73 MW | 14.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 7.05 MW | 5.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 7.15 MW | 6.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 6.27 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 25.46 MW | 21.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 9.78 MW | 8.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 1.3 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 8.18 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.98 MW | 6.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 5.32 MW | 4.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 15.09 MW | 15.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274723 | RIVER EC ;12 | 80/20 | 5.49 MW | 5.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274724 | RIVER EC ;11 | 80/20 | 5.46 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | 80/20 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | 80/20 | 7.57 MW | 7.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274792 | SE CHICAG;9U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274793 | SE CHICAG;0U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274794 | SE CHICAG;1U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274795 | SE CHICAG;2U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274798 | UNIV PARK;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274799 | UNIV PARK;2U | 80/20 | 1.52 MW | 1.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274826 | FISK ;BP | 80/20 | 2.86 MW | 2.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274827 | FISK ;RP | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276164 | X3-005 C | 80/20 | 0.11 MW | 0.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276592 | O-012 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.68 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 42.84 MW | 36.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 34.06 MW | 28.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 80.68 MW | 68.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 86.94 MW | 73.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 3.1 MW | 2.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 10.72 MW | 9.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 9.8 MW | 8.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.61 MW | 3.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 7.16 MW | 6.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 12.06 MW | 10.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 9.54 MW | 8.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 7.7 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 13.91 MW | 11.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 5.68 MW | 4.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 18.34 MW | 15.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 5.1 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 6.86 MW | 5.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.34 MW | 1.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.65 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 25.1 MW | 21.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.28 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 22.18 MW | 18.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | Adder | 39.58 MW | 33.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.82 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 6.52 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 361.52 MW | 307.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 953871 | J847 | External Queue | 13.43 MW | 13.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 954751 | J351 | External Queue | 441.39 MW | 441.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 955741 | J1058 | External Queue | 24.2 MW | 24.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990541 | J1332 | External Queue | 26.68 MW | 26.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990646 | J1355 | External Queue | 43.02 MW | 43.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990661 | J1358 | External Queue | 15.6 MW | 15.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990761 | J1386 | External Queue | 13.07 MW | 13.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990976 | J1447 | External Queue | 28.98 MW | 28.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 991271 | J1724 | External Queue | 41.93 MW | 41.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 991331 | J1785 | External Queue | 13.63 MW | 13.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.77 MW | 1.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 101.19 MW | 101.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.78 MW | 26.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.57 MW | 0.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.99 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.62 MW | 15.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.62 MW | 0.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.38 MW | 4.38 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 13.52 MW | 11.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 4.66 MW | 3.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | Adder | 44.21 MW | 37.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 10.83 MW | 9.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 20.27 MW | 17.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 3.15 MW | 2.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 13.12 MW | 11.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | Adder | 6.98 MW | 5.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 14.38 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 0.95 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.36 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.48 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 2.97 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 4.78 MW | 4.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 3.25 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 5.53 MW | 4.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 3.69 MW | 3.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | Adder | 7.13 MW | 6.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 9.59 MW | 9.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274792 | SE CHICAG;9U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274793 | SE CHICAG;0U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274794 | SE CHICAG;1U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274795 | SE CHICAG;2U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.16 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 6.37 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 3.79 MW | 3.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 12.72 MW | 10.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.28 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | Adder | 0.65 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.28 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.26 MW | 1.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 13.52 MW | 11.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 4.66 MW | 3.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | Adder | 44.21 MW | 37.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 10.83 MW | 9.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 20.27 MW | 17.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 3.15 MW | 2.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 13.12 MW | 11.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | Adder | 6.98 MW | 5.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 14.38 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 0.95 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.36 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.48 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 2.97 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 4.78 MW | 4.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 3.25 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 5.53 MW | 4.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 3.69 MW | 3.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | Adder | 7.13 MW | 6.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 9.59 MW | 9.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274792 | SE CHICAG;9U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274793 | SE CHICAG;0U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274794 | SE CHICAG;1U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274795 | SE CHICAG;2U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.16 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 6.37 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 3.79 MW | 3.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 12.72 MW | 10.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.28 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | Adder | 0.65 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.28 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.26 MW | 1.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 17.02 MW | 14.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 22.84 MW | 19.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 22.56 MW | 19.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 8.9 MW | 7.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 5.89 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 13.52 MW | 11.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 25.65 MW | 21.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 3.69 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 16.6 MW | 14.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.71 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 18.22 MW | 15.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.2 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 13.07 MW | 13.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 13.1 MW | 13.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.41 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 8.25 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 8.27 MW | 8.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.84 MW | 1.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 8.45 MW | 7.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 13.09 MW | 11.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 11.16 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 11.17 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 21.18 MW | 18.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 3.76 MW | 3.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 7.38 MW | 6.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 6.2 MW | 5.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 5.49 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 22.47 MW | 19.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 7.19 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.11 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.0 MW | 5.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 4.67 MW | 3.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 26.96 MW | 26.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 27.07 MW | 27.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 12.28 MW | 12.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274733 | ELWOOD EC;3P | 80/20 | 3.51 MW | 3.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274751 | CRETE EC ;1U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274752 | CRETE EC ;2U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274753 | CRETE EC ;3U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274754 | CRETE EC ;4U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 37.77 MW | 32.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 30.03 MW | 25.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 70.93 MW | 60.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 78.7 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 10.51 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 5.21 MW | 4.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 7.93 MW | 6.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 4.72 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 16.12 MW | 13.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 5.98 MW | 5.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 22.13 MW | 18.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 16.36 MW | 13.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 40.19 MW | 40.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.59 MW | 1.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 317.97 MW | 270.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.01 MW | 62.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.89 MW | 18.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.41 MW | 13.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.87 MW | 3.87 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 17.02 MW | 14.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 22.84 MW | 19.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 22.56 MW | 19.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 8.9 MW | 7.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 5.89 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 13.52 MW | 11.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 25.65 MW | 21.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 3.69 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 16.6 MW | 14.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.71 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 18.22 MW | 15.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.2 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 13.07 MW | 13.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 13.1 MW | 13.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.41 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 8.25 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 8.27 MW | 8.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.84 MW | 1.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 8.45 MW | 7.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 13.09 MW | 11.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 11.16 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 11.17 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 21.18 MW | 18.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 3.76 MW | 3.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 7.38 MW | 6.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 6.2 MW | 5.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 5.49 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 22.47 MW | 19.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 7.19 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.11 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.0 MW | 5.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 4.67 MW | 3.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 26.96 MW | 26.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 27.07 MW | 27.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 12.28 MW | 12.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274733 | ELWOOD EC;3P | 80/20 | 3.51 MW | 3.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274751 | CRETE EC ;1U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274752 | CRETE EC ;2U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274753 | CRETE EC ;3U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274754 | CRETE EC ;4U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 37.77 MW | 32.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 30.03 MW | 25.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 70.93 MW | 60.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 78.7 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 10.51 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 5.21 MW | 4.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 7.93 MW | 6.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 4.72 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 16.12 MW | 13.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 5.98 MW | 5.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 22.13 MW | 18.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 16.36 MW | 13.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 40.19 MW | 40.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.59 MW | 1.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 317.97 MW | 270.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.01 MW | 62.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.89 MW | 18.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.41 MW | 13.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.87 MW | 3.87 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 961651 | AG1-005 C O1 | 80/20 | 18.46 MW | 18.46 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C O1 | 80/20 | 8.03 MW | 8.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 19.75 MW | 19.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965141 | AG1-379 C | 80/20 | 26.97 MW | 26.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 0.66 MW | 0.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 1.25 MW | 1.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | 80/20 | 4.5 MW | 4.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936291 | AD2-038 C O1 | 80/20 | 5.59 MW | 5.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936771 | AD2-100 C | 80/20 | 6.76 MW | 6.76 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 936971 | AD2-131 C | 80/20 | 0.45 MW | 0.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 4.91 MW | 4.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942481 | AE2-261 C | 80/20 | 9.79 MW | 9.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 1.48 MW | 1.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 3.18 MW | 3.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 2.2 MW | 2.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958481 | AF2-142 C | 80/20 | 13.06 MW | 13.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958491 | AF2-143 C | 80/20 | 19.05 MW | 19.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 959351 | AF2-226 C | 80/20 | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 960281 | AF2-319 C | 80/20 | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274650 | KINCAID ;1U | 80/20 | 5.2 MW | 5.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274651 | KINCAID ;2U | 80/20 | 5.21 MW | 5.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 12.92 MW | 12.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 12.88 MW | 12.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274677 | POWERTON ;5U | 80/20 | 48.16 MW | 48.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274678 | POWERTON ;6U | 80/20 | 48.42 MW | 48.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 2.29 MW | 2.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 2.29 MW | 2.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.57 MW | 2.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.84 MW | 0.84 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.26 MW | 0.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.27 MW | 0.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274861 | TOP CROP ;1U | 80/20 | 0.44 MW | 0.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274862 | TOP CROP ;2U | 80/20 | 0.83 MW | 0.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.57 MW | 0.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.57 MW | 0.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 1.34 MW | 1.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 274891 | OTTER CRK;1U | 80/20 | 0.48 MW | 0.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.15 MW | 0.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 2.19 MW | 2.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 930761 | AB1-122 CT1 | 80/20 | 367.02 MW | 367.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 12.97 MW | 12.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 10.37 MW | 10.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 6.75 MW | 6.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957381 | AF2-032 C | 80/20 | 0.75 MW | 0.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.47 MW | 0.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 1.72 MW | 1.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 934101 | AD2-000 1 | 80/20 | 29.68 MW | 29.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951511 | J530 C | External Queue | 3.3 MW | 3.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951631 | J456 C | External Queue | 3.6 MW | 3.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 951821 | J541 C | External Queue | 4.19 MW | 4.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 952651 | J756 C | External Queue | 3.25 MW | 3.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 952871 | J757 C | External Queue | 4.15 MW | 4.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 953201 | J715 C | External Queue | 1.4 MW | 1.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 953951 | J859 | External Queue | 21.59 MW | 21.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 954721 | J750 C | External Queue | 1.45 MW | 1.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 954981 | J974 C | External Queue | 12.78 MW | 12.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 955711 | J1055 C | External Queue | 4.11 MW | 4.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 956151 | J1102 | External Queue | 5.67 MW | 5.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 956411 | J1131 | External Queue | 7.32 MW | 7.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990051 | J1200 | External Queue | 2.79 MW | 2.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990351 | J1289 C | External Queue | 4.02 MW | 4.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 990751 | J1383 | External Queue | 30.22 MW | 30.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991091 | J1477 | External Queue | 3.66 MW | 3.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991216 | J1653 | External Queue | 28.71 MW | 28.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991276 | J1725 C | External Queue | 2.99 MW | 2.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | 991301 | J1755 C | External Queue | 2.92 MW | 2.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.8 MW | 0.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.23 MW | 10.23 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 32.25 MW | 32.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 31.99 MW | 31.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.51 MW | 0.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.05 MW | 6.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.29 MW | 12.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.44 MW | 3.44 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 41.26 MW | 41.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 | 80/20 | 16.27 MW | 16.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 | 80/20 | 5.42 MW | 5.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C O1 | 80/20 | 16.45 MW | 16.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 26.71 MW | 26.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | 80/20 | 1.75 MW | 1.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.1 MW | 0.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.1 MW | 0.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 6.46 MW | 6.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 37.96 MW | 37.96 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 926431 | AC1-114 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 927511 | AC1-113 1 | 80/20 | 0.13 MW | 0.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 927521 | AC1-113 2 | 80/20 | 0.13 MW | 0.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | 80/20 | 1.22 MW | 1.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | 80/20 | 2.11 MW | 2.11 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.01 MW | 0.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 1.74 MW | 1.74 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | 80/20 | 2.29 MW | 2.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 36.36 MW | 36.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 6.46 MW | 6.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 959081 | AF2-199 C | 80/20 | 32.54 MW | 32.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 959091 | AF2-200 C O1 | 80/20 | 65.08 MW | 65.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 7.07 MW | 7.07 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 12.04 MW | 12.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 8.03 MW | 8.03 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274656 | BYRON ;1U | 80/20 | 19.25 MW | 19.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274657 | BYRON ;2U | 80/20 | 18.75 MW | 18.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 26.95 MW | 26.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 27.03 MW | 27.03 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 4.75 MW | 4.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 4.75 MW | 4.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 5.34 MW | 5.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 6.93 MW | 6.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 5.06 MW | 5.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 6.99 MW | 6.99 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 5.1 MW | 5.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274763 | LEE CO EC;4U | 80/20 | 2.64 MW | 2.64 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 2.67 MW | 2.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274766 | LEE CO EC;7U | 80/20 | 2.63 MW | 2.63 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274767 | LEE CO EC;8U | 80/20 | 2.63 MW | 2.63 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274822 | ROCKFORD ;11 | 80/20 | 1.49 MW | 1.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274823 | ROCKFORD ;21 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274824 | ROCKFORD ;12 | 80/20 | 1.48 MW | 1.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.3 MW | 0.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.36 MW | 0.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.48 MW | 0.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.48 MW | 0.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.36 MW | 0.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.67 MW | 0.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276162 | X1-087 | 80/20 | 0.18 MW | 0.18 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 276590 | R-018 | 80/20 | 0.08 MW | 0.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.62 MW | 0.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.32 MW | 0.32 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.35 MW | 0.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 1.05 MW | 1.05 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 930482 | AB1-089 CT | Adder | 23.3 MW | 19.8 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 930483 | AB1-089 ST | Adder | 18.52 MW | 15.74 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 932881 | AC2-115 1 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 932891 | AC2-115 2 | 80/20 | 0.27 MW | 0.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 932921 | AC2-116 | 80/20 | 0.09 MW | 0.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 4.79 MW | 4.79 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 2.95 MW | 2.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 2.95 MW | 2.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | 80/20 | 2.29 MW | 2.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 27.67 MW | 27.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.61 MW | 0.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 4.06 MW | 4.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | 80/20 | 1.58 MW | 1.58 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 957471 | AF2-041 C | 80/20 | 97.62 MW | 97.62 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.18 MW | 0.18 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 951381 | J504 | External Queue | 3.81 MW | 3.81 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 951421 | J514 | External Queue | 2.28 MW | 2.28 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 955971 | J1084 | External Queue | 21.02 MW | 21.02 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 956411 | J1131 | External Queue | 11.0 MW | 11.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | 991091 | J1477 | External Queue | 5.5 MW | 5.5 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.08 MW | 0.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.22 MW | 0.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.39 MW | 0.39 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.46 MW | 3.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 50.61 MW | 50.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.83 MW | 15.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.12 MW | 0.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.85 MW | 3.85 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.23 MW | 0.23 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.35 MW | 13.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.19 MW | 0.19 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.09 MW | 0.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.79 MW | 1.79 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.67 MW | 0.67 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 12.18 MW | 10.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 16.33 MW | 13.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 16.12 MW | 13.7 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 4.21 MW | 3.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | Adder | 35.6 MW | 30.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 9.74 MW | 8.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 18.35 MW | 15.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965091 | AG1-374 C | Adder | 11.68 MW | 9.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 2.84 MW | 2.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 11.88 MW | 10.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.16 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 13.03 MW | 11.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 9.28 MW | 9.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 9.29 MW | 9.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.17 MW | 3.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 3.17 MW | 3.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.13 MW | 1.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 1.82 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 5.87 MW | 5.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.33 MW | 1.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 9.37 MW | 7.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.23 MW | 5.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 15.14 MW | 12.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 2.69 MW | 2.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.43 MW | 3.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 4.3 MW | 3.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | Adder | 1.3 MW | 1.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 16.05 MW | 13.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | Adder | 1.3 MW | 1.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.36 MW | 3.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 2.94 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 5.01 MW | 4.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 3.34 MW | 2.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 20.63 MW | 20.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 20.08 MW | 20.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 19.08 MW | 19.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 19.16 MW | 19.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 8.73 MW | 8.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 8.73 MW | 8.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 8.78 MW | 8.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 3.09 MW | 3.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.07 MW | 2.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 3.09 MW | 3.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.07 MW | 2.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274735 | ELWOOD EC;4P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274751 | CRETE EC ;1U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274752 | CRETE EC ;2U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274753 | CRETE EC ;3U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274754 | CRETE EC ;4U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | Adder | 2.5 MW | 2.12 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | Adder | 2.5 MW | 2.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | Adder | 2.54 MW | 2.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | Adder | 2.54 MW | 2.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.33 MW | 0.33 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.62 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.05 MW | 0.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 50.7 MW | 43.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 55.88 MW | 47.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 6.89 MW | 6.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 2.9 MW | 2.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.01 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.01 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 3.77 MW | 3.2 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 5.73 MW | 4.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 3.41 MW | 2.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 11.52 MW | 9.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 2.93 MW | 2.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.21 MW | 2.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 4.28 MW | 3.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.76 MW | 1.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | Adder | 0.54 MW | 0.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.07 MW | 1.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 15.81 MW | 13.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 27.74 MW | 27.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.14 MW | 0.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 227.54 MW | 193.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 955741 | J1058 | External Queue | 33.49 MW | 33.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.55 MW | 1.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.95 MW | 47.95 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 12.18 MW | 10.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 16.33 MW | 13.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 16.12 MW | 13.7 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 4.21 MW | 3.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | Adder | 35.6 MW | 30.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 9.74 MW | 8.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 18.35 MW | 15.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965091 | AG1-374 C | Adder | 11.68 MW | 9.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 2.84 MW | 2.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 11.88 MW | 10.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.16 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 13.03 MW | 11.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 9.28 MW | 9.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 9.29 MW | 9.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.17 MW | 3.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 3.17 MW | 3.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.13 MW | 1.81 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 1.82 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 5.87 MW | 5.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.33 MW | 1.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 9.37 MW | 7.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.23 MW | 5.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 15.14 MW | 12.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 2.69 MW | 2.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.43 MW | 3.77 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 4.3 MW | 3.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | Adder | 1.3 MW | 1.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 16.05 MW | 13.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | Adder | 1.3 MW | 1.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.36 MW | 3.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 2.94 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 5.01 MW | 4.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 3.34 MW | 2.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 20.63 MW | 20.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 20.08 MW | 20.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 19.08 MW | 19.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 19.16 MW | 19.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 8.73 MW | 8.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 8.73 MW | 8.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 8.78 MW | 8.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 3.09 MW | 3.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.07 MW | 2.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 3.09 MW | 3.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.07 MW | 2.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274735 | ELWOOD EC;4P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274751 | CRETE EC ;1U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274752 | CRETE EC ;2U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274753 | CRETE EC ;3U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274754 | CRETE EC ;4U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | Adder | 2.5 MW | 2.12 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | Adder | 2.5 MW | 2.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | Adder | 2.54 MW | 2.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | Adder | 2.54 MW | 2.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.33 MW | 0.33 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.62 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.05 MW | 0.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 50.7 MW | 43.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 55.88 MW | 47.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 6.89 MW | 6.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 2.9 MW | 2.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.01 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.01 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 3.77 MW | 3.2 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 5.73 MW | 4.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 3.41 MW | 2.9 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 11.52 MW | 9.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 2.93 MW | 2.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.21 MW | 2.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 4.28 MW | 3.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.76 MW | 1.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | Adder | 0.54 MW | 0.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.07 MW | 1.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 15.81 MW | 13.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 27.74 MW | 27.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.14 MW | 0.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 227.54 MW | 193.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 955741 | J1058 | External Queue | 33.49 MW | 33.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.55 MW | 1.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.95 MW | 47.95 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 12.18 MW | 10.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 16.33 MW | 13.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 16.12 MW | 13.7 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 4.21 MW | 3.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | Adder | 35.6 MW | 30.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 9.74 MW | 8.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 18.35 MW | 15.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965091 | AG1-374 C | Adder | 11.68 MW | 9.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 2.84 MW | 2.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 11.88 MW | 10.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.16 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 13.03 MW | 11.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 9.28 MW | 9.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 9.29 MW | 9.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.17 MW | 3.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 3.17 MW | 3.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.13 MW | 1.81 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 1.82 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 5.87 MW | 5.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.33 MW | 1.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 9.37 MW | 7.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.23 MW | 5.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 15.14 MW | 12.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 2.69 MW | 2.29 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.43 MW | 3.77 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 4.3 MW | 3.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | Adder | 1.3 MW | 1.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 16.05 MW | 13.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | Adder | 1.3 MW | 1.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.36 MW | 3.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 2.94 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 5.01 MW | 4.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 3.34 MW | 2.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 20.63 MW | 20.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 20.08 MW | 20.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 19.08 MW | 19.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 19.16 MW | 19.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 8.73 MW | 8.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 8.73 MW | 8.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 8.78 MW | 8.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 3.09 MW | 3.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.07 MW | 2.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 3.09 MW | 3.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.07 MW | 2.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274735 | ELWOOD EC;4P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 2.5 MW | 2.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274751 | CRETE EC ;1U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274752 | CRETE EC ;2U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274753 | CRETE EC ;3U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274754 | CRETE EC ;4U | 80/20 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | Adder | 2.5 MW | 2.12 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | Adder | 2.5 MW | 2.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | Adder | 2.54 MW | 2.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | Adder | 2.54 MW | 2.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.33 MW | 0.33 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.62 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.05 MW | 0.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 50.7 MW | 43.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 55.88 MW | 47.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 6.89 MW | 6.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 2.9 MW | 2.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.01 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.01 MW | 0.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 3.77 MW | 3.2 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 5.73 MW | 4.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 3.41 MW | 2.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 11.52 MW | 9.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 2.93 MW | 2.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.21 MW | 2.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 4.28 MW | 3.64 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.76 MW | 1.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | Adder | 0.54 MW | 0.46 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.07 MW | 1.07 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 15.81 MW | 13.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 27.74 MW | 27.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.14 MW | 0.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 227.54 MW | 193.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 955741 | J1058 | External Queue | 33.49 MW | 33.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.55 MW | 1.55 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.95 MW | 47.95 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 12.18 MW | 10.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 16.33 MW | 13.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 16.12 MW | 13.7 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 4.21 MW | 3.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | Adder | 35.6 MW | 30.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 9.74 MW | 8.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 18.35 MW | 15.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965091 | AG1-374 C | Adder | 11.68 MW | 9.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 2.84 MW | 2.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 11.88 MW | 10.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.16 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 13.03 MW | 11.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 0.85 MW | 0.72 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 9.28 MW | 9.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 9.29 MW | 9.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.17 MW | 3.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 3.17 MW | 3.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.13 MW | 1.81 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 1.82 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 5.87 MW | 5.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.33 MW | 1.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 9.37 MW | 7.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.23 MW | 5.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 15.14 MW | 12.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 2.69 MW | 2.29 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.43 MW | 3.77 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 4.3 MW | 3.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | Adder | 1.3 MW | 1.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 16.05 MW | 13.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | Adder | 1.3 MW | 1.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.36 MW | 3.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 2.94 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 5.01 MW | 4.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 3.34 MW | 2.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 20.63 MW | 20.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 20.08 MW | 20.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 19.08 MW | 19.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 19.16 MW | 19.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 8.73 MW | 8.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 8.73 MW | 8.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 8.78 MW | 8.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 3.09 MW | 3.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.07 MW | 2.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 3.09 MW | 3.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.07 MW | 2.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274735 | ELWOOD EC;4P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 2.5 MW | 2.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274751 | CRETE EC ;1U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274752 | CRETE EC ;2U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274753 | CRETE EC ;3U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274754 | CRETE EC ;4U | 80/20 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | Adder | 2.5 MW | 2.12 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | Adder | 2.5 MW | 2.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | Adder | 2.54 MW | 2.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | Adder | 2.54 MW | 2.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.33 MW | 0.33 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.62 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.05 MW | 0.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 50.7 MW | 43.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 55.88 MW | 47.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 6.89 MW | 6.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 2.9 MW | 2.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.01 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.01 MW | 0.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 3.77 MW | 3.2 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 5.73 MW | 4.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 3.41 MW | 2.9 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 11.52 MW | 9.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 2.93 MW | 2.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.21 MW | 2.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 4.28 MW | 3.64 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.76 MW | 1.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | Adder | 0.54 MW | 0.46 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.07 MW | 1.07 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 15.81 MW | 13.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.25 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 27.74 MW | 27.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.14 MW | 0.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 227.54 MW | 193.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 955741 | J1058 | External Queue | 33.49 MW | 33.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.55 MW | 1.55 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.95 MW | 47.95 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 961651 | AG1-005 C O1 | 80/20 | 19.99 MW | 19.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 962721 | AG1-121 C O1 | 80/20 | 8.66 MW | 8.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 966821 | AG1-553 C O1 | 80/20 | 21.36 MW | 21.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 965141 | AG1-379 C | 80/20 | 30.93 MW | 30.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 965671 | AG1-435 C O1 | 80/20 | 6.05 MW | 6.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 965911 | AG1-460 C | 80/20 | 0.73 MW | 0.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 965931 | AG1-462 C O1 | 80/20 | 13.82 MW | 13.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 295110 | SUBLETTE C | 80/20 | 0.03 MW | 0.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 919221 | AA1-146 | 80/20 | 1.42 MW | 1.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 919581 | AA2-030 C | 80/20 | 8.34 MW | 8.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 926821 | AC1-168 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 934051 | AD1-031 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 936291 | AD2-038 C O1 | 80/20 | 11.08 MW | 11.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 936771 | AD2-100 C | 80/20 | 7.53 MW | 7.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 936971 | AD2-131 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 942421 | AE2-255 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 942481 | AE2-261 C | 80/20 | 10.91 MW | 10.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 942651 | AE2-281 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 945871 | AF1-252 O1 | 80/20 | 3.53 MW | 3.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 945881 | AF1-253 | 80/20 | 2.44 MW | 2.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 958491 | AF2-143 C | 80/20 | 37.78 MW | 37.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 959351 | AF2-226 C | 80/20 | 3.16 MW | 3.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 960281 | AF2-319 C | 80/20 | 3.16 MW | 3.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 961011 | AF2-392 C O1 | 80/20 | 1.91 MW | 1.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 961021 | AF2-393 O1 | 80/20 | 3.25 MW | 3.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 961031 | AF2-394 O1 | 80/20 | 2.17 MW | 2.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274650 | KINCAID ;1U | 80/20 | 5.8 MW | 5.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274651 | KINCAID ;2U | 80/20 | 5.81 MW | 5.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274662 | QUAD CITI;1U | 80/20 | 13.98 MW | 13.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274663 | QUAD CITI;2U | 80/20 | 13.94 MW | 13.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274677 | POWERTON ;5U | 80/20 | 54.71 MW | 54.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274678 | POWERTON ;6U | 80/20 | 55.0 MW | 55.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274699 | CORDOVA ;1C | 80/20 | 2.47 MW | 2.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274700 | CORDOVA ;2C | 80/20 | 2.47 MW | 2.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274701 | CORDOVA ;1S | 80/20 | 2.78 MW | 2.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274715 | NELSON EC;1C | 80/20 | 1.52 MW | 1.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274716 | NELSON EC;1S | 80/20 | 1.11 MW | 1.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274717 | NELSON EC;2C | 80/20 | 1.53 MW | 1.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274718 | NELSON EC;2S | 80/20 | 1.12 MW | 1.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274848 | CAMPGROVE;RU | 80/20 | 0.9 MW | 0.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274861 | TOP CROP ;1U | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274862 | TOP CROP ;2U | 80/20 | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 276156 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 276157 | O-029 C | 80/20 | 0.18 MW | 0.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 276158 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 276173 | Z2-081 | 80/20 | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 293513 | O-009 C1 | 80/20 | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 293514 | O-009 C2 | 80/20 | 0.15 MW | 0.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 293515 | O-009 C3 | 80/20 | 0.17 MW | 0.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 925581 | AC1-033 C | 80/20 | 2.36 MW | 2.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 930761 | AB1-122 CT1 | 80/20 | 378.4 MW | 378.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 938851 | AE1-113 C O1 | 80/20 | 14.88 MW | 14.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 939051 | AE1-134 1 | 80/20 | 0.65 MW | 0.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 939061 | AE1-134 2 | 80/20 | 0.65 MW | 0.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 939321 | AE1-163 C O1 | 80/20 | 20.57 MW | 20.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 944221 | AF1-090 C O1 | 80/20 | 1.99 MW | 1.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 946321 | AF1-296 C O1 | 80/20 | 3.11 MW | 3.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 946541 | AF1-318 C O1 | 80/20 | 7.3 MW | 7.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 957381 | AF2-032 C | 80/20 | 0.83 MW | 0.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 957751 | AF2-069 C | 80/20 | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 957761 | AF2-070 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 958341 | AF2-128 C O1 | 80/20 | 1.86 MW | 1.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 934101 | AD2-000 1 | 80/20 | 30.6 MW | 30.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 951511 | J530 C | External Queue | 3.56 MW | 3.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 951631 | J456 C | External Queue | 3.87 MW | 3.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 951821 | J541 C | External Queue | 4.52 MW | 4.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 952651 | J756 C | External Queue | 3.53 MW | 3.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 952871 | J757 C | External Queue | 4.51 MW | 4.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 953201 | J715 C | External Queue | 1.52 MW | 1.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 953951 | J859 | External Queue | 23.25 MW | 23.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 954981 | J974 C | External Queue | 13.67 MW | 13.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 955711 | J1055 C | External Queue | 4.42 MW | 4.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 956151 | J1102 | External Queue | 6.2 MW | 6.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 956411 | J1131 | External Queue | 7.9 MW | 7.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 990051 | J1200 | External Queue | 3.01 MW | 3.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 990351 | J1289 C | External Queue | 4.34 MW | 4.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 990751 | J1383 | External Queue | 32.44 MW | 32.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 991091 | J1477 | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 991216 | J1653 | External Queue | 30.89 MW | 30.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 991276 | J1725 C | External Queue | 3.21 MW | 3.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | 991301 | J1755 C | External Queue | 3.15 MW | 3.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.35 MW | 0.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.86 MW | 0.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.82 MW | 10.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 34.57 MW | 34.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 34.67 MW | 34.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.53 MW | 0.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.54 MW | 6.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.28 MW | 13.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o 270827 NEVADA ; R 345 936290 AD2-038 TAP 345 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.71 MW | 3.71 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 961651 | AG1-005 C O1 | 80/20 | 19.99 MW | 19.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 962721 | AG1-121 C O1 | 80/20 | 8.66 MW | 8.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 966821 | AG1-553 C O1 | 80/20 | 21.36 MW | 21.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 965141 | AG1-379 C | 80/20 | 30.93 MW | 30.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 965671 | AG1-435 C O1 | 80/20 | 6.05 MW | 6.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 965911 | AG1-460 C | 80/20 | 0.73 MW | 0.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 965931 | AG1-462 C O1 | 80/20 | 13.82 MW | 13.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 295110 | SUBLETTE C | 80/20 | 0.03 MW | 0.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 919221 | AA1-146 | 80/20 | 1.42 MW | 1.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 919581 | AA2-030 C | 80/20 | 8.34 MW | 8.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 926821 | AC1-168 C O1 | 80/20 | 1.35 MW | 1.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 927201 | AC1-214 C O1 | 80/20 | 0.53 MW | 0.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 934051 | AD1-031 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 936291 | AD2-038 C O1 | 80/20 | 11.08 MW | 11.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 936771 | AD2-100 C | 80/20 | 7.53 MW | 7.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 936971 | AD2-131 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 942421 | AE2-255 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 942481 | AE2-261 C | 80/20 | 10.91 MW | 10.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 942651 | AE2-281 C O1 | 80/20 | 2.94 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 945871 | AF1-252 O1 | 80/20 | 3.53 MW | 3.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 945881 | AF1-253 | 80/20 | 2.44 MW | 2.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 958491 | AF2-143 C | 80/20 | 37.78 MW | 37.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 959351 | AF2-226 C | 80/20 | 3.16 MW | 3.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 960281 | AF2-319 C | 80/20 | 3.16 MW | 3.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 961011 | AF2-392 C O1 | 80/20 | 1.91 MW | 1.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 961021 | AF2-393 O1 | 80/20 | 3.25 MW | 3.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 961031 | AF2-394 O1 | 80/20 | 2.17 MW | 2.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274650 | KINCAID ;1U | 80/20 | 5.8 MW | 5.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274651 | KINCAID ;2U | 80/20 | 5.81 MW | 5.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274662 | QUAD CITI;1U | 80/20 | 13.98 MW | 13.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274663 | QUAD CITI;2U | 80/20 | 13.94 MW | 13.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274677 | POWERTON ;5U | 80/20 | 54.71 MW | 54.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274678 | POWERTON ;6U | 80/20 | 55.0 MW | 55.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274699 | CORDOVA ;1C | 80/20 | 2.47 MW | 2.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274700 | CORDOVA ;2C | 80/20 | 2.47 MW | 2.47 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274701 | CORDOVA ;1S | 80/20 | 2.78 MW | 2.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274715 | NELSON EC;1C | 80/20 | 1.52 MW | 1.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274716 | NELSON EC;1S | 80/20 | 1.11 MW | 1.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274717 | NELSON EC;2C | 80/20 | 1.53 MW | 1.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274718 | NELSON EC;2S | 80/20 | 1.12 MW | 1.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274848 | CAMPGROVE;RU | 80/20 | 0.9 MW | 0.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274861 | TOP CROP ;1U | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274862 | TOP CROP ;2U | 80/20 | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274877 | BISHOP HL;1U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274878 | BISHOP HL;2U | 80/20 | 0.61 MW | 0.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 274879 | MINONK ;1U | 80/20 | 1.54 MW | 1.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 276156 | O-029 C | 80/20 | 0.16 MW | 0.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 276157 | O-029 C | 80/20 | 0.18 MW | 0.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 276158 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 276173 | Z2-081 | 80/20 | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 293513 | O-009 C1 | 80/20 | 0.3 MW | 0.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 293514 | O-009 C2 | 80/20 | 0.15 MW | 0.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 293515 | O-009 C3 | 80/20 | 0.17 MW | 0.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 925581 | AC1-033 C | 80/20 | 2.36 MW | 2.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 930761 | AB1-122 CT1 | 80/20 | 378.4 MW | 378.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 938851 | AE1-113 C O1 | 80/20 | 14.88 MW | 14.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 939051 | AE1-134 1 | 80/20 | 0.65 MW | 0.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 939061 | AE1-134 2 | 80/20 | 0.65 MW | 0.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 939321 | AE1-163 C O1 | 80/20 | 20.57 MW | 20.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 944221 | AF1-090 C O1 | 80/20 | 1.99 MW | 1.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 946321 | AF1-296 C O1 | 80/20 | 3.11 MW | 3.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 946541 | AF1-318 C O1 | 80/20 | 7.3 MW | 7.3 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 957381 | AF2-032 C | 80/20 | 0.83 MW | 0.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 957751 | AF2-069 C | 80/20 | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 957761 | AF2-070 C | 80/20 | 0.5 MW | 0.5 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 958341 | AF2-128 C O1 | 80/20 | 1.86 MW | 1.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 934101 | AD2-000 1 | 80/20 | 30.6 MW | 30.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 951511 | J530 C | External Queue | 3.56 MW | 3.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 951631 | J456 C | External Queue | 3.87 MW | 3.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 951821 | J541 C | External Queue | 4.52 MW | 4.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 952651 | J756 C | External Queue | 3.53 MW | 3.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 952871 | J757 C | External Queue | 4.51 MW | 4.51 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 953201 | J715 C | External Queue | 1.52 MW | 1.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 953951 | J859 | External Queue | 23.25 MW | 23.25 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 954981 | J974 C | External Queue | 13.67 MW | 13.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 955711 | J1055 C | External Queue | 4.42 MW | 4.42 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 956151 | J1102 | External Queue | 6.2 MW | 6.2 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 956411 | J1131 | External Queue | 7.9 MW | 7.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 990051 | J1200 | External Queue | 3.01 MW | 3.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 990351 | J1289 C | External Queue | 4.34 MW | 4.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 990751 | J1383 | External Queue | 32.44 MW | 32.44 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 991091 | J1477 | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 991216 | J1653 | External Queue | 30.89 MW | 30.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 991276 | J1725 C | External Queue | 3.21 MW | 3.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | 991301 | J1755 C | External Queue | 3.15 MW | 3.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.35 MW | 0.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.86 MW | 0.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.82 MW | 10.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 34.57 MW | 34.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 34.67 MW | 34.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.53 MW | 0.53 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.54 MW | 6.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.33 MW | 0.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.28 MW | 13.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0303__R-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.71 MW | 3.71 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961651 | AG1-005 C O1 | Adder | 12.31 MW | 10.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961652 | AG1-005 E O1 | Adder | 8.21 MW | 6.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962721 | AG1-121 C O1 | Adder | 4.22 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962722 | AG1-121 E O1 | Adder | 19.72 MW | 16.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963831 | AG1-236 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963832 | AG1-236 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964581 | AG1-321 C O1 | Adder | 11.78 MW | 10.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964582 | AG1-321 E O1 | Adder | 6.86 MW | 5.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966821 | AG1-553 C O1 | Adder | 18.91 MW | 16.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966822 | AG1-553 E O1 | Adder | 3.81 MW | 3.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965091 | AG1-374 C | 50/50 | 21.96 MW | 21.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965092 | AG1-374 E | 50/50 | 14.64 MW | 14.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965331 | AG1-398 | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965341 | AG1-399 C | 50/50 | 7.26 MW | 7.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965342 | AG1-399 E | 50/50 | 33.99 MW | 33.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965351 | AG1-400 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965371 | AG1-402 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965391 | AG1-404 | 50/50 | 13.75 MW | 13.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965671 | AG1-435 C O1 | Adder | 2.87 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965672 | AG1-435 E O1 | Adder | 13.45 MW | 11.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965911 | AG1-460 C | 50/50 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965912 | AG1-460 E | 50/50 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965931 | AG1-462 C O1 | Adder | 12.24 MW | 10.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965932 | AG1-462 E O1 | Adder | 8.16 MW | 6.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290261 | S-027 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290265 | S-028 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 295111 | SUBLETTE E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919581 | AA2-030 C | Adder | 11.31 MW | 9.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925771 | AC1-053 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925772 | AC1-053 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926821 | AC1-168 C O1 | Adder | 0.79 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926822 | AC1-168 E O1 | Adder | 5.29 MW | 4.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927202 | AC1-214 E O1 | Adder | 4.96 MW | 4.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 935141 | AD1-148 | 50/50 | 5.71 MW | 5.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936771 | AD2-100 C | 50/50 | 22.42 MW | 22.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936772 | AD2-100 E | 50/50 | 14.95 MW | 14.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936971 | AD2-131 C | 50/50 | 1.48 MW | 1.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936972 | AD2-131 E | 50/50 | 7.42 MW | 7.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942111 | AE2-223 C | 50/50 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942112 | AE2-223 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942481 | AE2-261 C | 50/50 | 31.04 MW | 31.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942482 | AE2-261 E | 50/50 | 20.7 MW | 20.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945871 | AF1-252 O1 | 50/50 | 11.99 MW | 11.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945881 | AF1-253 | 50/50 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946542 | AF1-318 E O1 | Adder | 20.29 MW | 17.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958911 | AF2-182 C | Adder | 12.64 MW | 10.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958912 | AF2-182 E | Adder | 8.43 MW | 7.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958921 | AF2-183 C | Adder | 2.25 MW | 1.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958922 | AF2-183 E | Adder | 3.37 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959341 | AF2-225 C | 50/50 | 7.12 MW | 7.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959342 | AF2-225 E | 50/50 | 9.83 MW | 9.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959611 | AF2-252 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959612 | AF2-252 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960141 | AF2-305 | 50/50 | 1.38 MW | 1.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960261 | AF2-317 | 50/50 | 2.47 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960611 | AF2-352 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960612 | AF2-352 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961011 | AF2-392 C O1 | Adder | 2.52 MW | 2.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961012 | AF2-392 E O1 | Adder | 11.79 MW | 10.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961021 | AF2-393 O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961031 | AF2-394 O1 | Adder | 2.86 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274650 | KINCAID ;1U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274651 | KINCAID ;2U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274859 | EASYR;U1 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274860 | EASYR;U2 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274880 | RADFORD R;1U | 50/50 | 1.17 MW | 1.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276615 | W2-048 GEN | 50/50 | 8.12 MW | 8.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276621 | X2-022 GEN | 50/50 | 29.13 MW | 29.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293516 | O-009 E1 | Adder | 6.11 MW | 5.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293517 | O-009 E2 | Adder | 3.11 MW | 2.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293518 | O-009 E3 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293715 | O-029 E | Adder | 6.54 MW | 5.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293716 | O-029 E | Adder | 3.58 MW | 3.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293717 | O-029 E | Adder | 3.29 MW | 2.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293771 | O-035 E | Adder | 4.86 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293777 | CAYUG;1U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293778 | CAYUG;2U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293798 | W4-005 E | 50/50 | 39.32 MW | 39.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294401 | BSHIL;1U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294410 | BSHIL;2U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916211 | Z1-072 E | Adder | 3.68 MW | 3.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 917502 | Z2-087 E | 50/50 | 19.65 MW | 19.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924042 | AB2-047 E O1 | 50/50 | 24.56 MW | 24.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924261 | AB2-070 C O1 | 50/50 | 3.91 MW | 3.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924262 | AB2-070 E O1 | 50/50 | 23.69 MW | 23.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925581 | AC1-033 C | Adder | 1.08 MW | 0.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925582 | AC1-033 E | Adder | 7.21 MW | 6.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 930761 | AB1-122 CT1 | Adder | 39.4 MW | 33.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938861 | AE1-114 C O1 | Adder | 2.33 MW | 1.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938862 | AE1-114 E O1 | Adder | 7.94 MW | 6.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939051 | AE1-134 1 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939061 | AE1-134 2 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939401 | AE1-172 C O1 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939402 | AE1-172 E O1 | Adder | 16.04 MW | 13.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939741 | AE1-205 C O1 | 50/50 | 9.49 MW | 9.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939742 | AE1-205 E O1 | 50/50 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941731 | AE2-173 O1 | 50/50 | 5.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944221 | AF1-090 C O1 | 50/50 | 6.77 MW | 6.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944222 | AF1-090 E O1 | 50/50 | 31.68 MW | 31.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946151 | AF1-280 C O1 | Adder | 9.62 MW | 8.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946152 | AF1-280 E O1 | Adder | 4.42 MW | 3.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946161 | AF1-281 C O1 | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946162 | AF1-281 E O1 | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946321 | AF1-296 C O1 | Adder | 2.94 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946322 | AF1-296 E O1 | Adder | 13.76 MW | 11.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946541 | AF1-318 C O1 | Adder | 4.33 MW | 3.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957381 | AF2-032 C | 50/50 | 2.33 MW | 2.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957382 | AF2-032 E | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957752 | AF2-069 E | Adder | 0.58 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957762 | AF2-070 E | Adder | 1.24 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958341 | AF2-128 C O1 | Adder | 1.15 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958342 | AF2-128 E O1 | Adder | 5.38 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990901 | L-005 E | Adder | 10.49 MW | 8.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934101 | AD2-000 1 | Adder | 3.19 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944202 | AF1-088 FTWR | 50/50 | 279.8 MW | 279.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942602 | AE2-276 BAT | 50/50 | 13.99 MW | 13.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941343 | AE2-130 BAT | 50/50 | 31.84 MW | 31.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953371 | J808 | External Queue | 2.59 MW | 2.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953401 | J811 | External Queue | 18.15 MW | 18.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953641 | J813 | External Queue | 40.39 MW | 40.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953651 | J815 | External Queue | 32.21 MW | 32.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953741 | J826 C | External Queue | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953742 | J826 E | External Queue | 9.11 MW | 9.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953881 | J848 C | External Queue | 5.26 MW | 5.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953882 | J848 E | External Queue | 28.46 MW | 28.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954411 | J912 | External Queue | 14.27 MW | 14.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954681 | J949 C | External Queue | 33.84 MW | 33.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954821 | J955 | External Queue | 112.27 MW | 112.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955402 | J1022 E | External Queue | 16.19 MW | 16.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956451 | J1139 | External Queue | 20.56 MW | 20.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990056 | J1201 | External Queue | 6.99 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990071 | J1204 | External Queue | 65.14 MW | 65.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990271 | J1263 | External Queue | 107.73 MW | 107.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990672 | J1360 E | External Queue | 35.45 MW | 35.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990856 | J1408 | External Queue | 10.19 MW | 10.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991196 | J1626 | External Queue | 27.49 MW | 27.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991266 | J1714 | External Queue | 18.33 MW | 18.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991261 | J1713 C | External Queue | 3.06 MW | 3.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991262 | J1713 E | External Queue | 16.55 MW | 16.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.68 MW | 2.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.77 MW | 1.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 16.49 MW | 16.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 68.32 MW | 68.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 74.8 MW | 74.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.26 MW | 13.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.26 MW | 15.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.79 MW | 4.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.99 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.32 MW | 8.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.01 MW | 2.01 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961651 | AG1-005 C O1 | Adder | 12.53 MW | 10.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961652 | AG1-005 E O1 | Adder | 8.35 MW | 7.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962721 | AG1-121 C O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962722 | AG1-121 E O1 | Adder | 20.08 MW | 17.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963831 | AG1-236 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963832 | AG1-236 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964581 | AG1-321 C O1 | Adder | 11.86 MW | 10.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964582 | AG1-321 E O1 | Adder | 6.91 MW | 5.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966821 | AG1-553 C O1 | Adder | 19.16 MW | 16.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965091 | AG1-374 C | 50/50 | 21.61 MW | 21.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965092 | AG1-374 E | 50/50 | 14.4 MW | 14.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965331 | AG1-398 | 50/50 | 1.07 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965341 | AG1-399 C | 50/50 | 7.08 MW | 7.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965342 | AG1-399 E | 50/50 | 33.15 MW | 33.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965351 | AG1-400 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965371 | AG1-402 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965391 | AG1-404 | 50/50 | 13.41 MW | 13.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965671 | AG1-435 C O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965672 | AG1-435 E O1 | Adder | 13.68 MW | 11.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965911 | AG1-460 C | 50/50 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965912 | AG1-460 E | 50/50 | 3.0 MW | 3.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965931 | AG1-462 C O1 | Adder | 12.4 MW | 10.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965932 | AG1-462 E O1 | Adder | 8.27 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290261 | S-027 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290265 | S-028 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 295111 | SUBLETTE E | Adder | 1.66 MW | 1.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 919581 | AA2-030 C | Adder | 11.63 MW | 9.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925771 | AC1-053 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925772 | AC1-053 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926821 | AC1-168 C O1 | Adder | 0.81 MW | 0.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926822 | AC1-168 E O1 | Adder | 5.42 MW | 4.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 927202 | AC1-214 E O1 | Adder | 5.04 MW | 4.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934051 | AD1-031 C O1 | Adder | 2.22 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934052 | AD1-031 E O1 | Adder | 3.62 MW | 3.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 935141 | AD1-148 | 50/50 | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936511 | AD2-066 C O1 | Adder | 4.85 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936512 | AD2-066 E O1 | Adder | 3.24 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936771 | AD2-100 C | 50/50 | 21.54 MW | 21.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936772 | AD2-100 E | 50/50 | 14.36 MW | 14.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936971 | AD2-131 C | 50/50 | 1.42 MW | 1.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936972 | AD2-131 E | 50/50 | 7.13 MW | 7.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937311 | AD2-172 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937312 | AD2-172 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942111 | AE2-223 C | 50/50 | 2.18 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942112 | AE2-223 E | 50/50 | 14.59 MW | 14.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942481 | AE2-261 C | 50/50 | 29.87 MW | 29.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942482 | AE2-261 E | 50/50 | 19.91 MW | 19.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945871 | AF1-252 O1 | 50/50 | 11.48 MW | 11.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945881 | AF1-253 | 50/50 | 7.95 MW | 7.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946542 | AF1-318 E O1 | Adder | 20.64 MW | 17.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958911 | AF2-182 C | Adder | 13.04 MW | 11.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958912 | AF2-182 E | Adder | 8.69 MW | 7.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958921 | AF2-183 C | Adder | 2.32 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958922 | AF2-183 E | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959101 | AF2-201 C O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959102 | AF2-201 E O1 | Adder | 10.24 MW | 8.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959341 | AF2-225 C | 50/50 | 7.04 MW | 7.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959342 | AF2-225 E | 50/50 | 9.73 MW | 9.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959611 | AF2-252 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959612 | AF2-252 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960141 | AF2-305 | 50/50 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960261 | AF2-317 | 50/50 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960611 | AF2-352 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960612 | AF2-352 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961011 | AF2-392 C O1 | Adder | 2.59 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961012 | AF2-392 E O1 | Adder | 12.14 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961021 | AF2-393 O1 | Adder | 4.42 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961031 | AF2-394 O1 | Adder | 2.95 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274650 | KINCAID ;1U | 50/50 | 15.61 MW | 15.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274651 | KINCAID ;2U | 50/50 | 15.6 MW | 15.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274853 | TWINGROVE;U1 | 50/50 | 0.71 MW | 0.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274854 | TWINGROVE;U2 | 50/50 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274859 | EASYR;U1 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274860 | EASYR;U2 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274880 | RADFORD R;1U | 50/50 | 1.14 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276615 | W2-048 GEN | 50/50 | 7.85 MW | 7.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276621 | X2-022 GEN | 50/50 | 28.17 MW | 28.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293516 | O-009 E1 | Adder | 6.27 MW | 5.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293517 | O-009 E2 | Adder | 3.18 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293518 | O-009 E3 | Adder | 3.51 MW | 2.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293715 | O-029 E | Adder | 6.7 MW | 5.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293716 | O-029 E | Adder | 3.67 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293717 | O-029 E | Adder | 3.38 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293771 | O-035 E | Adder | 4.94 MW | 4.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293777 | CAYUG;1U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293778 | CAYUG;2U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293798 | W4-005 E | 50/50 | 38.12 MW | 38.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294401 | BSHIL;1U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294410 | BSHIL;2U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294763 | P-046 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 916211 | Z1-072 E | Adder | 3.74 MW | 3.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 917502 | Z2-087 E | 50/50 | 19.45 MW | 19.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924042 | AB2-047 E O1 | 50/50 | 24.32 MW | 24.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924261 | AB2-070 C O1 | 50/50 | 3.79 MW | 3.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924262 | AB2-070 E O1 | 50/50 | 22.98 MW | 22.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925582 | AC1-033 E | Adder | 7.32 MW | 6.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 930761 | AB1-122 CT1 | Adder | 41.0 MW | 34.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938861 | AE1-114 C O1 | Adder | 2.41 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938862 | AE1-114 E O1 | Adder | 8.22 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939401 | AE1-172 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939402 | AE1-172 E O1 | Adder | 16.51 MW | 14.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939741 | AE1-205 C O1 | 50/50 | 9.39 MW | 9.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939742 | AE1-205 E O1 | 50/50 | 12.97 MW | 12.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940501 | AE2-035 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940502 | AE2-035 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941731 | AE2-173 O1 | 50/50 | 5.59 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944221 | AF1-090 C O1 | 50/50 | 6.48 MW | 6.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944222 | AF1-090 E O1 | 50/50 | 30.33 MW | 30.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946151 | AF1-280 C O1 | Adder | 9.92 MW | 8.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946152 | AF1-280 E O1 | Adder | 4.56 MW | 3.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946162 | AF1-281 E O1 | Adder | 1.23 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946322 | AF1-296 E O1 | Adder | 13.97 MW | 11.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946501 | AF1-314 C | Adder | 2.58 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946502 | AF1-314 E | Adder | 12.12 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946541 | AF1-318 C O1 | Adder | 4.41 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957381 | AF2-032 C | 50/50 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957382 | AF2-032 E | 50/50 | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957762 | AF2-070 E | Adder | 1.26 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958341 | AF2-128 C O1 | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958342 | AF2-128 E O1 | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990901 | L-005 E | Adder | 10.63 MW | 9.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934101 | AD2-000 1 | Adder | 3.32 MW | 2.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944202 | AF1-088 FTWR | 50/50 | 309.06 MW | 309.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942602 | AE2-276 BAT | 50/50 | 15.45 MW | 15.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941343 | AE2-130 BAT | 50/50 | 34.8 MW | 34.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953401 | J811 | External Queue | 17.16 MW | 17.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953641 | J813 | External Queue | 37.62 MW | 37.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953651 | J815 | External Queue | 30.66 MW | 30.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953881 | J848 C | External Queue | 4.99 MW | 4.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953882 | J848 E | External Queue | 27.02 MW | 27.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954411 | J912 | External Queue | 13.54 MW | 13.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954681 | J949 C | External Queue | 31.51 MW | 31.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954821 | J955 | External Queue | 84.37 MW | 84.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 956451 | J1139 | External Queue | 19.36 MW | 19.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990056 | J1201 | External Queue | 6.62 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990071 | J1204 | External Queue | 61.78 MW | 61.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990271 | J1263 | External Queue | 101.39 MW | 101.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990672 | J1360 E | External Queue | 33.75 MW | 33.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991196 | J1626 | External Queue | 26.01 MW | 26.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991266 | J1714 | External Queue | 17.34 MW | 17.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991261 | J1713 C | External Queue | 2.9 MW | 2.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991262 | J1713 E | External Queue | 15.68 MW | 15.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.8 MW | 3.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.57 MW | 13.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.43 MW | 71.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.74 MW | 67.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.36 MW | 12.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.6 MW | 1.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.01 MW | 15.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.1 MW | 5.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.33 MW | 1.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.55 MW | 7.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.1 MW | 2.1 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960581 | AF2-349 C | 50/50 | 87.91 MW | 87.91 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960582 | AF2-349 E | 50/50 | 58.6 MW | 58.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274761 | LEE CO EC;2U | 50/50 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960581 | AF2-349 C | 50/50 | 87.91 MW | 87.91 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960582 | AF2-349 E | 50/50 | 58.6 MW | 58.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274761 | LEE CO EC;2U | 50/50 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274762 | LEE CO EC;3U | 50/50 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274762 | LEE CO EC;3U | 50/50 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966821 | AG1-553 C O1 | 50/50 | 56.08 MW | 56.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965061 | AG1-371 | 50/50 | 17.78 MW | 17.78 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965081 | AG1-373 | 50/50 | 5.93 MW | 5.93 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965661 | AG1-434 C O1 | 50/50 | 18.61 MW | 18.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965662 | AG1-434 E O1 | 50/50 | 87.14 MW | 87.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965672 | AG1-435 E O1 | Adder | 15.63 MW | 13.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965931 | AG1-462 C O1 | 50/50 | 36.3 MW | 36.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.55 MW | 3.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 5.31 MW | 5.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 C | 50/50 | 52.74 MW | 52.74 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.43 MW | 1.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 8.22 MW | 6.99 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 60.46 MW | 60.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 40.3 MW | 40.3 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959081 | AF2-199 C | 50/50 | 35.57 MW | 35.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959082 | AF2-199 E | 50/50 | 17.78 MW | 17.78 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959091 | AF2-200 C O1 | 50/50 | 71.13 MW | 71.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959092 | AF2-200 E O1 | 50/50 | 47.42 MW | 47.42 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.47 MW | 9.47 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.36 MW | 44.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 36.71 MW | 36.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.7 MW | 9.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 0.87 MW | 0.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 0.87 MW | 0.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 32.24 MW | 32.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 32.24 MW | 32.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 11.12 MW | 11.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 21.26 MW | 21.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.71 MW | 10.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.37 MW | 4.56 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | 50/50 | 8.83 MW | 8.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | 50/50 | 8.83 MW | 8.83 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | 50/50 | 9.68 MW | 9.68 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 46.01 MW | 46.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | 50/50 | 40.52 MW | 40.52 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957471 | AF2-041 C | 50/50 | 106.7 MW | 106.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957472 | AF2-041 E | 50/50 | 53.35 MW | 53.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.01 MW | 10.21 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.7 MW | 6.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.36 MW | 52.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.73 MW | 21.73 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.17 MW | 0.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.12 MW | 5.12 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.7 MW | 16.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.08 MW | 1.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961651 | AG1-005 C O1 | Adder | 13.25 MW | 11.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961652 | AG1-005 E O1 | Adder | 8.83 MW | 7.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962012 | AG1-044 E | Adder | 0.06 MW | 0.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 17.0 MW | 14.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 11.33 MW | 9.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962701 | AG1-119 C | Adder | 18.64 MW | 15.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962702 | AG1-119 E | Adder | 12.42 MW | 10.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 6.95 MW | 5.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.63 MW | 3.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962721 | AG1-121 C O1 | Adder | 4.77 MW | 4.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962722 | AG1-121 E O1 | Adder | 22.31 MW | 18.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962781 | AG1-127 C | Adder | 5.4 MW | 4.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 962782 | AG1-127 E | Adder | 3.59 MW | 3.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 964581 | AG1-321 C O1 | Adder | 11.37 MW | 9.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 964582 | AG1-321 E O1 | Adder | 6.62 MW | 5.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966821 | AG1-553 C O1 | Adder | 22.74 MW | 19.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966822 | AG1-553 E O1 | Adder | 4.58 MW | 3.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965061 | AG1-371 | Adder | 3.07 MW | 2.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965081 | AG1-373 | Adder | 1.02 MW | 0.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965141 | AG1-379 C | Adder | 22.38 MW | 19.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965142 | AG1-379 E | Adder | 10.24 MW | 8.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 12.43 MW | 10.56 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 8.28 MW | 7.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.58 MW | 3.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 16.76 MW | 14.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965671 | AG1-435 C O1 | Adder | 3.3 MW | 2.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965672 | AG1-435 E O1 | Adder | 15.47 MW | 13.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965931 | AG1-462 C O1 | Adder | 14.72 MW | 12.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 965932 | AG1-462 E O1 | Adder | 9.81 MW | 8.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966441 | AG1-513 C | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 966442 | AG1-513 E | Adder | 0.58 MW | 0.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.1 MW | 1.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290021 | O50 E | Adder | 26.1 MW | 22.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290051 | GSG-6; E | Adder | 8.37 MW | 7.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.48 MW | 3.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 919581 | AA2-030 C | Adder | 15.6 MW | 13.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 920272 | AA2-123 E | Adder | 2.11 MW | 1.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.52 MW | 1.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.52 MW | 1.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927093 | AC1-204 GEN2 | 50/50 | 18.22 MW | 18.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 5.67 MW | 4.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927451 | AC1-142A 1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 927461 | AC1-142A 2 | Adder | 5.37 MW | 4.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933911 | AD1-013 C | Adder | 1.47 MW | 1.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933912 | AD1-013 E | Adder | 2.35 MW | 2.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933931 | AD1-016 C | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 933932 | AD1-016 E | Adder | 1.31 MW | 1.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934051 | AD1-031 C O1 | Adder | 2.59 MW | 2.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934052 | AD1-031 E O1 | Adder | 4.22 MW | 3.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934432 | AD1-067 E | Adder | 0.44 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934971 | AD1-129 C | Adder | 0.78 MW | 0.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934972 | AD1-129 E | Adder | 0.52 MW | 0.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.35 MW | 2.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.01 MW | 9.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 7.24 MW | 6.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.82 MW | 4.1 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937001 | AD2-134 C | Adder | 2.02 MW | 1.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937002 | AD2-134 E | Adder | 8.09 MW | 6.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937311 | AD2-172 C | Adder | 2.14 MW | 1.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937312 | AD2-172 E | Adder | 2.95 MW | 2.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937401 | AD2-194 1 | Adder | 11.36 MW | 9.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 937411 | AD2-194 2 | 50/50 | 11.5 MW | 11.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942111 | AE2-223 C | Adder | 1.51 MW | 1.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942112 | AE2-223 E | Adder | 10.12 MW | 8.6 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 12.24 MW | 10.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.62 MW | 0.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.83 MW | 3.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942991 | AE2-321 C | Adder | 7.07 MW | 6.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 942992 | AE2-321 E | Adder | 3.48 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943121 | AE2-341 C | Adder | 8.03 MW | 6.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943122 | AE2-341 E | Adder | 3.94 MW | 3.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 2.64 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943801 | AF1-048 C | Adder | 3.3 MW | 2.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 943802 | AF1-048 E | Adder | 2.2 MW | 1.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 22.06 MW | 18.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958491 | AF2-143 C | Adder | 8.02 MW | 6.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958492 | AF2-143 E | Adder | 5.34 MW | 4.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958911 | AF2-182 C | Adder | 18.05 MW | 15.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958912 | AF2-182 E | Adder | 12.03 MW | 10.23 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958921 | AF2-183 C | Adder | 3.21 MW | 2.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958922 | AF2-183 E | Adder | 4.81 MW | 4.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959081 | AF2-199 C | Adder | 6.15 MW | 5.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959082 | AF2-199 E | Adder | 3.07 MW | 2.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 12.29 MW | 10.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 8.2 MW | 6.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 5.23 MW | 4.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 15.02 MW | 12.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959341 | AF2-225 C | Adder | 4.88 MW | 4.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959342 | AF2-225 E | Adder | 6.74 MW | 5.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959351 | AF2-226 C | 50/50 | 7.16 MW | 7.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 959352 | AF2-226 E | 50/50 | 10.74 MW | 10.74 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960281 | AF2-319 C | 50/50 | 7.16 MW | 7.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960282 | AF2-319 E | 50/50 | 10.74 MW | 10.74 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960381 | AF2-329 | Adder | 3.37 MW | 2.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960581 | AF2-349 C | Adder | 18.9 MW | 16.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960582 | AF2-349 E | Adder | 12.6 MW | 10.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.77 MW | 4.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.18 MW | 2.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960751 | AF2-366 C | Adder | 5.38 MW | 4.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 960752 | AF2-366 E | Adder | 3.59 MW | 3.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 3.49 MW | 2.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 16.32 MW | 13.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961021 | AF2-393 O1 | Adder | 5.94 MW | 5.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.96 MW | 3.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 6.35 MW | 6.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 4.24 MW | 4.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 6.35 MW | 6.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 4.24 MW | 4.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274728 | ELWOOD EC;5P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274730 | ELWOOD EC;6P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274732 | ELWOOD EC;7P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274734 | ELWOOD EC;8P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274736 | ELWOOD EC;9P | 50/50 | 4.9 MW | 4.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274859 | EASYR;U1 E | Adder | 9.66 MW | 8.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274860 | EASYR;U2 E | Adder | 9.66 MW | 8.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 1.12 MW | 1.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 2.14 MW | 2.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 276170 | Z1-108 E | Adder | 2.16 MW | 1.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 276591 | L-013 2 | Adder | 2.95 MW | 2.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293516 | O-009 E1 | Adder | 8.09 MW | 6.87 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293517 | O-009 E2 | Adder | 4.11 MW | 3.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293518 | O-009 E3 | Adder | 4.52 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293644 | O22 E1 | 50/50 | 29.21 MW | 29.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293645 | O22 E2 | 50/50 | 56.7 MW | 56.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293715 | O-029 E | Adder | 8.65 MW | 7.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293716 | O-029 E | Adder | 4.74 MW | 4.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293717 | O-029 E | Adder | 4.36 MW | 3.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 293771 | O-035 E | Adder | 5.56 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294401 | BSHIL;1U E | Adder | 7.77 MW | 6.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294410 | BSHIL;2U E | Adder | 7.77 MW | 6.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 294763 | P-046 E | Adder | 8.14 MW | 6.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 916211 | Z1-072 E | Adder | 4.2 MW | 3.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 916221 | Z1-073 E | Adder | 4.35 MW | 3.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 917502 | Z2-087 E | Adder | 13.49 MW | 11.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 924042 | AB2-047 E O1 | Adder | 16.86 MW | 14.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 925581 | AC1-033 C | Adder | 1.27 MW | 1.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 925582 | AC1-033 E | Adder | 8.52 MW | 7.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930482 | AB1-089 CT | Adder | 31.55 MW | 26.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930483 | AB1-089 ST | Adder | 25.08 MW | 21.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 73.53 MW | 62.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 101.92 MW | 86.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938511 | AE1-070 1 | 50/50 | 13.52 MW | 13.52 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938521 | AE1-070 2 | Adder | 12.21 MW | 10.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 10.77 MW | 9.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 38.17 MW | 32.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.42 MW | 2.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 11.67 MW | 9.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939051 | AE1-134 1 | Adder | 1.21 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939061 | AE1-134 2 | Adder | 1.21 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.36 MW | 3.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 26.81 MW | 22.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939741 | AE1-205 C O1 | Adder | 6.51 MW | 5.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 939742 | AE1-205 E O1 | Adder | 8.99 MW | 7.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 940501 | AE2-035 C | Adder | 2.14 MW | 1.82 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 940502 | AE2-035 E | Adder | 2.95 MW | 2.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941131 | AE2-107 C | Adder | 5.09 MW | 4.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941132 | AE2-107 E | Adder | 3.39 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 941731 | AE2-173 O1 | Adder | 3.88 MW | 3.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946151 | AF1-280 C O1 | Adder | 13.74 MW | 11.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946152 | AF1-280 E O1 | Adder | 6.32 MW | 5.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946161 | AF1-281 C O1 | Adder | 0.3 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946162 | AF1-281 E O1 | Adder | 1.7 MW | 1.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 3.6 MW | 3.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 16.83 MW | 14.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946501 | AF1-314 C | Adder | 3.79 MW | 3.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946502 | AF1-314 E | Adder | 17.79 MW | 15.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 4.71 MW | 4.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946661 | AF1-330 C | Adder | 1.73 MW | 1.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946662 | AF1-330 E | Adder | 0.38 MW | 0.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 946671 | AF1-331 | Adder | 1.91 MW | 1.62 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957331 | AF2-027 C | Adder | 2.3 MW | 1.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957332 | AF2-027 E | Adder | 3.45 MW | 2.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957401 | AF2-034 C | 50/50 | 2.21 MW | 2.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.88 MW | 1.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957471 | AF2-041 C | Adder | 18.44 MW | 15.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957472 | AF2-041 E | Adder | 9.22 MW | 7.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957751 | AF2-069 C | Adder | 0.21 MW | 0.18 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957752 | AF2-069 E | Adder | 0.67 MW | 0.57 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957761 | AF2-070 C | Adder | 0.29 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 957762 | AF2-070 E | Adder | 1.41 MW | 1.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.24 MW | 1.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 5.78 MW | 4.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 990901 | L-005 E | Adder | 12.26 MW | 10.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.95 MW | 5.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 934111 | AD2-000 2 | Adder | 8.24 MW | 7.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 290108 | LEEDK;1U E | Adder | 18.85 MW | 16.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 958023 | AF2-096 BAT | Adder | 8.6 MW | 7.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 954981 | J974 C | External Queue | 3.02 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | 954982 | J974 E | External Queue | 10.86 MW | 10.86 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.3 MW | 0.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.02 MW | 1.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.06 MW | 0.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.43 MW | 57.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.2 MW | 21.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.27 MW | 1.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.17 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.22 MW | 4.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 12.32 MW | 12.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.69 MW | 0.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.14 MW | 8.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.36 MW | 0.36 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.89 MW | 1.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_112-45-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.43 MW | 3.43 MW |
| Details for AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 962012 | AG1-044 E | Adder | 0.16 MW | 0.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 966821 | AG1-553 C O1 | Adder | 56.0 MW | 47.6 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 966822 | AG1-553 E O1 | Adder | 11.28 MW | 9.59 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965061 | AG1-371 | 50/50 | 17.75 MW | 17.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965081 | AG1-373 | 50/50 | 5.92 MW | 5.92 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965661 | AG1-434 C O1 | 50/50 | 18.58 MW | 18.58 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965662 | AG1-434 E O1 | 50/50 | 86.99 MW | 86.99 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965931 | AG1-462 C O1 | Adder | 36.25 MW | 30.81 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 965932 | AG1-462 E O1 | Adder | 24.16 MW | 20.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 295111 | SUBLETTE E | Adder | 5.31 MW | 4.51 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 919221 | AA1-146 | 50/50 | 8.97 MW | 8.97 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 919581 | AA2-030 C | 50/50 | 52.66 MW | 52.66 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 934051 | AD1-031 C O1 | Adder | 2.89 MW | 2.46 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 934052 | AD1-031 E O1 | Adder | 4.72 MW | 4.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958911 | AF2-182 C | 50/50 | 60.37 MW | 60.37 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958912 | AF2-182 E | 50/50 | 40.24 MW | 40.24 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958921 | AF2-183 C | 50/50 | 10.73 MW | 10.73 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 958922 | AF2-183 E | 50/50 | 16.1 MW | 16.1 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959081 | AF2-199 C | 50/50 | 35.51 MW | 35.51 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959082 | AF2-199 E | 50/50 | 17.75 MW | 17.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959091 | AF2-200 C O1 | 50/50 | 71.01 MW | 71.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 959092 | AF2-200 E O1 | 50/50 | 47.34 MW | 47.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961011 | AF2-392 C O1 | Adder | 9.47 MW | 8.05 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961012 | AF2-392 E O1 | Adder | 44.32 MW | 37.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961021 | AF2-393 O1 | Adder | 16.13 MW | 13.71 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 961031 | AF2-394 O1 | Adder | 10.76 MW | 9.14 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274715 | NELSON EC;1C | 50/50 | 9.61 MW | 9.61 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274716 | NELSON EC;1S | 50/50 | 7.01 MW | 7.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274717 | NELSON EC;2C | 50/50 | 9.69 MW | 9.69 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274718 | NELSON EC;2S | 50/50 | 7.08 MW | 7.08 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274760 | LEE CO EC;1U | 50/50 | 4.85 MW | 4.85 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274764 | LEE CO EC;5U | 50/50 | 4.86 MW | 4.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274765 | LEE CO EC;6U | 50/50 | 4.86 MW | 4.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274859 | EASYR;U1 E | Adder | 32.19 MW | 27.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 274860 | EASYR;U2 E | Adder | 32.19 MW | 27.36 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293516 | O-009 E1 | Adder | 19.85 MW | 16.87 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293517 | O-009 E2 | Adder | 10.08 MW | 8.57 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293518 | O-009 E3 | Adder | 11.1 MW | 9.44 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293715 | O-029 E | Adder | 21.22 MW | 18.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293716 | O-029 E | Adder | 11.64 MW | 9.89 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 293717 | O-029 E | Adder | 10.69 MW | 9.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 294401 | BSHIL;1U E | Adder | 8.76 MW | 7.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 294410 | BSHIL;2U E | Adder | 8.76 MW | 7.45 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 925581 | AC1-033 C | Adder | 1.44 MW | 1.22 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 925582 | AC1-033 E | Adder | 9.61 MW | 8.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 938861 | AE1-114 C O1 | Adder | 5.1 MW | 4.34 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 938862 | AE1-114 E O1 | Adder | 17.41 MW | 14.8 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 939051 | AE1-134 1 | 50/50 | 4.09 MW | 4.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 939061 | AE1-134 2 | 50/50 | 4.09 MW | 4.09 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946151 | AF1-280 C O1 | 50/50 | 45.95 MW | 45.95 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946152 | AF1-280 E O1 | 50/50 | 21.13 MW | 21.13 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946162 | AF1-281 E O1 | 50/50 | 5.7 MW | 5.7 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946321 | AF1-296 C O1 | Adder | 8.65 MW | 7.35 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 946322 | AF1-296 E O1 | Adder | 40.48 MW | 34.41 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 957471 | AF2-041 C | 50/50 | 106.52 MW | 106.52 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 957472 | AF2-041 E | 50/50 | 53.26 MW | 53.26 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951381 | J504 | External Queue | 5.06 MW | 5.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951421 | J514 | External Queue | 3.07 MW | 3.07 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951511 | J530 C | External Queue | 4.96 MW | 4.96 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 951512 | J530 E | External Queue | 19.86 MW | 19.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 955971 | J1084 | External Queue | 29.58 MW | 29.58 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 956411 | J1131 | External Queue | 15.49 MW | 15.49 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 990947 | J1432 E | External Queue | 41.67 MW | 41.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | 991091 | J1477 | External Queue | 7.75 MW | 7.75 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.15 MW | 0.15 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.54 MW | 5.54 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.0 MW | 52.0 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 20.86 MW | 20.86 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.23 MW | 0.23 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.29 MW | 0.29 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.96 MW | 4.96 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.67 MW | 16.67 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.88 MW | 1.88 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.4 MW | 2.4 MW |
| AF2-041 TAP-ELECT JCT; B 345.0 kV Ckt 1 line l/o COMED_P4_006-45-BT3-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961651 | AG1-005 C O1 | Adder | 12.71 MW | 10.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961652 | AG1-005 E O1 | Adder | 8.47 MW | 7.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962012 | AG1-044 E | Adder | 0.06 MW | 0.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 17.56 MW | 14.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 11.71 MW | 9.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962701 | AG1-119 C | Adder | 19.08 MW | 16.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962702 | AG1-119 E | Adder | 12.72 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 7.14 MW | 6.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.76 MW | 4.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962721 | AG1-121 C O1 | Adder | 4.61 MW | 3.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962722 | AG1-121 E O1 | Adder | 21.58 MW | 18.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962781 | AG1-127 C | Adder | 5.57 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962782 | AG1-127 E | Adder | 3.71 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966821 | AG1-553 C O1 | Adder | 22.49 MW | 19.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966822 | AG1-553 E O1 | Adder | 4.53 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965061 | AG1-371 | Adder | 3.13 MW | 2.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965081 | AG1-373 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965141 | AG1-379 C | Adder | 22.42 MW | 19.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965142 | AG1-379 E | Adder | 10.26 MW | 8.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 12.72 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 8.48 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.64 MW | 3.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 17.03 MW | 14.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965671 | AG1-435 C O1 | Adder | 3.19 MW | 2.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965672 | AG1-435 E O1 | Adder | 14.96 MW | 12.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965931 | AG1-462 C O1 | Adder | 14.56 MW | 12.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965932 | AG1-462 E O1 | Adder | 9.7 MW | 8.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966441 | AG1-513 C | Adder | 0.4 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966442 | AG1-513 E | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290021 | O50 E | Adder | 26.14 MW | 22.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290051 | GSG-6; E | Adder | 8.56 MW | 7.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 919581 | AA2-030 C | Adder | 15.68 MW | 13.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 920272 | AA2-123 E | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927093 | AC1-204 GEN2 | 50/50 | 18.42 MW | 18.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 5.46 MW | 4.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927451 | AC1-142A 1 | Adder | 5.49 MW | 4.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927461 | AC1-142A 2 | Adder | 5.52 MW | 4.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933931 | AD1-016 C | Adder | 0.82 MW | 0.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933932 | AD1-016 E | Adder | 1.34 MW | 1.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934051 | AD1-031 C O1 | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934052 | AD1-031 E O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934971 | AD1-129 C | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934972 | AD1-129 E | Adder | 0.53 MW | 0.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.39 MW | 2.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.17 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 7.28 MW | 6.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.86 MW | 4.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937002 | AD2-134 E | Adder | 8.28 MW | 7.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937311 | AD2-172 C | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937312 | AD2-172 E | Adder | 3.0 MW | 2.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937401 | AD2-194 1 | Adder | 11.49 MW | 9.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937411 | AD2-194 2 | 50/50 | 11.63 MW | 11.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 12.26 MW | 10.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.89 MW | 3.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942991 | AE2-321 C | Adder | 7.24 MW | 6.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942992 | AE2-321 E | Adder | 3.57 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943121 | AE2-341 C | Adder | 8.48 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943122 | AE2-341 E | Adder | 4.16 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 5.64 MW | 4.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 2.79 MW | 2.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943801 | AF1-048 C | Adder | 3.39 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943802 | AF1-048 E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 21.19 MW | 18.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958491 | AF2-143 C | Adder | 8.13 MW | 6.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958492 | AF2-143 E | Adder | 5.42 MW | 4.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958911 | AF2-182 C | Adder | 18.2 MW | 15.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958912 | AF2-182 E | Adder | 12.13 MW | 10.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958921 | AF2-183 C | Adder | 3.24 MW | 2.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958922 | AF2-183 E | Adder | 4.85 MW | 4.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959081 | AF2-199 C | Adder | 6.27 MW | 5.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959082 | AF2-199 E | Adder | 3.13 MW | 2.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 12.54 MW | 10.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 8.36 MW | 7.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 5.31 MW | 4.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 15.24 MW | 12.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959351 | AF2-226 C | 50/50 | 7.21 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959352 | AF2-226 E | 50/50 | 10.81 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960281 | AF2-319 C | 50/50 | 7.21 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960282 | AF2-319 E | 50/50 | 10.81 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960381 | AF2-329 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960581 | AF2-349 C | Adder | 19.33 MW | 16.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960582 | AF2-349 E | Adder | 12.89 MW | 10.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.9 MW | 4.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.27 MW | 2.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960751 | AF2-366 C | Adder | 5.55 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960752 | AF2-366 E | Adder | 3.7 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 3.5 MW | 2.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 16.4 MW | 13.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961021 | AF2-393 O1 | Adder | 5.97 MW | 5.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.98 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 6.46 MW | 6.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 4.32 MW | 4.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 6.46 MW | 6.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 4.32 MW | 4.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274728 | ELWOOD EC;5P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274730 | ELWOOD EC;6P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274732 | ELWOOD EC;7P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274734 | ELWOOD EC;8P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274736 | ELWOOD EC;9P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274859 | EASYR;U1 E | Adder | 9.76 MW | 8.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274860 | EASYR;U2 E | Adder | 9.76 MW | 8.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 1.13 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 2.15 MW | 2.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 276170 | Z1-108 E | Adder | 2.22 MW | 1.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 276591 | L-013 2 | Adder | 3.05 MW | 2.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293516 | O-009 E1 | Adder | 8.05 MW | 6.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293517 | O-009 E2 | Adder | 4.09 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293518 | O-009 E3 | Adder | 4.5 MW | 3.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293644 | O22 E1 | 50/50 | 29.41 MW | 29.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293645 | O22 E2 | 50/50 | 57.09 MW | 57.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293715 | O-029 E | Adder | 8.6 MW | 7.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293716 | O-029 E | Adder | 4.72 MW | 4.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293717 | O-029 E | Adder | 4.33 MW | 3.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293771 | O-035 E | Adder | 5.36 MW | 4.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294401 | BSHIL;1U E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294410 | BSHIL;2U E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294763 | P-046 E | Adder | 8.26 MW | 7.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 916211 | Z1-072 E | Adder | 4.05 MW | 3.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 916221 | Z1-073 E | Adder | 4.45 MW | 3.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 925581 | AC1-033 C | Adder | 1.23 MW | 1.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 925582 | AC1-033 E | Adder | 8.23 MW | 7.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930482 | AB1-089 CT | Adder | 32.18 MW | 27.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930483 | AB1-089 ST | Adder | 25.58 MW | 21.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 71.38 MW | 60.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 103.64 MW | 88.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938511 | AE1-070 1 | 50/50 | 13.67 MW | 13.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938521 | AE1-070 2 | Adder | 12.35 MW | 10.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 10.78 MW | 9.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 38.24 MW | 32.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.46 MW | 2.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 11.81 MW | 10.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939051 | AE1-134 1 | Adder | 1.22 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939061 | AE1-134 2 | Adder | 1.22 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.43 MW | 3.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 27.2 MW | 23.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 940501 | AE2-035 C | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 940502 | AE2-035 E | Adder | 3.0 MW | 2.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 941131 | AE2-107 C | Adder | 5.24 MW | 4.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 941132 | AE2-107 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946151 | AF1-280 C O1 | Adder | 13.85 MW | 11.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946152 | AF1-280 E O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946161 | AF1-281 C O1 | Adder | 0.3 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946162 | AF1-281 E O1 | Adder | 1.72 MW | 1.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 3.56 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 16.69 MW | 14.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946501 | AF1-314 C | Adder | 3.84 MW | 3.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946502 | AF1-314 E | Adder | 18.05 MW | 15.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 4.53 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946661 | AF1-330 C | Adder | 1.78 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946662 | AF1-330 E | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957331 | AF2-027 C | Adder | 2.37 MW | 2.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957332 | AF2-027 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957401 | AF2-034 C | 50/50 | 2.25 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.91 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957471 | AF2-041 C | Adder | 18.81 MW | 15.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957472 | AF2-041 E | Adder | 9.4 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 5.55 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 990901 | L-005 E | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.77 MW | 4.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934111 | AD2-000 2 | Adder | 8.38 MW | 7.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.41 MW | 16.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958023 | AF2-096 BAT | Adder | 7.3 MW | 6.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 953151 | J831 | External Queue | 3.03 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 953491 | J947 | External Queue | 15.9 MW | 15.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954141 | J878 | External Queue | 15.94 MW | 15.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954981 | J974 C | External Queue | 2.94 MW | 2.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954982 | J974 E | External Queue | 15.91 MW | 15.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 991321 | J1778 | External Queue | 7.97 MW | 7.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.42 MW | 0.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.4 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.54 MW | 57.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.5 MW | 16.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.51 MW | 3.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.27 MW | 0.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 11.83 MW | 11.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.53 MW | 8.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.5 MW | 3.5 MW |
| Details for PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962722 | AG1-121 E O1 | Adder | 20.72 MW | 17.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966821 | AG1-553 C O1 | 50/50 | 56.08 MW | 56.08 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965661 | AG1-434 C O1 | 50/50 | 18.61 MW | 18.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965662 | AG1-434 E O1 | 50/50 | 87.14 MW | 87.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965672 | AG1-435 E O1 | Adder | 15.63 MW | 13.29 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965931 | AG1-462 C O1 | 50/50 | 36.3 MW | 36.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.55 MW | 3.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 5.31 MW | 5.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 C | 50/50 | 52.74 MW | 52.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.43 MW | 1.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 8.22 MW | 6.99 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 60.46 MW | 60.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 40.3 MW | 40.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.19 MW | 3.56 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 12.04 MW | 10.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.47 MW | 9.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.36 MW | 44.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 36.71 MW | 36.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.7 MW | 9.7 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 0.87 MW | 0.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 0.87 MW | 0.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 32.24 MW | 32.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 32.24 MW | 32.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 11.12 MW | 11.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 21.26 MW | 21.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.71 MW | 10.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.37 MW | 4.56 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | 50/50 | 8.83 MW | 8.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | 50/50 | 8.83 MW | 8.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | 50/50 | 9.68 MW | 9.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 46.01 MW | 46.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | 50/50 | 40.52 MW | 40.52 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946501 | AF1-314 C | Adder | 3.03 MW | 2.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946502 | AF1-314 E | Adder | 14.26 MW | 12.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.01 MW | 10.21 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.7 MW | 6.7 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.36 MW | 52.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.73 MW | 21.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.17 MW | 0.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.12 MW | 5.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.7 MW | 16.7 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.08 MW | 1.08 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 20.68 MW | 20.68 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 13.79 MW | 13.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962701 | AG1-119 C | Adder | 13.59 MW | 11.55 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962702 | AG1-119 E | Adder | 9.06 MW | 7.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962711 | AG1-120 C O1 | Adder | 6.32 MW | 5.37 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962712 | AG1-120 E O1 | Adder | 4.21 MW | 3.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.08 MW | 6.08 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.05 MW | 4.05 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 15.36 MW | 13.05 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.09 MW | 2.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 4.75 MW | 4.75 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.58 MW | 1.58 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965141 | AG1-379 C | Adder | 9.32 MW | 7.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965142 | AG1-379 E | Adder | 4.27 MW | 3.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 9.08 MW | 7.71 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 6.05 MW | 5.14 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965661 | AG1-434 C O1 | 50/50 | 4.96 MW | 4.96 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965662 | AG1-434 E O1 | 50/50 | 23.23 MW | 23.23 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 9.94 MW | 8.45 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 6.63 MW | 5.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966091 | AG1-478 C | Adder | 0.89 MW | 0.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.22 MW | 0.19 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.29 MW | 0.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.43 MW | 0.37 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 272364 | ESS H440N ;R | Adder | 2.19 MW | 1.86 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 290021 | O50 E | Adder | 10.87 MW | 9.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 290051 | GSG-6; E | Adder | 8.69 MW | 7.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 295109 | WESTBROOK E | Adder | 4.65 MW | 3.96 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 1.87 MW | 1.59 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.9 MW | 11.81 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 2.63 MW | 2.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 2.63 MW | 2.63 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 933911 | AD1-013 C | Adder | 1.54 MW | 1.31 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 933912 | AD1-013 E | Adder | 2.45 MW | 2.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.4 MW | 0.34 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.27 MW | 0.23 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.45 MW | 3.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 2.97 MW | 2.52 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 937001 | AD2-134 C | Adder | 2.1 MW | 1.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 937002 | AD2-134 E | Adder | 8.41 MW | 7.14 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.33 MW | 1.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 937312 | AD2-172 E | Adder | 1.83 MW | 1.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 942421 | AE2-255 C O1 | Adder | 1.7 MW | 1.44 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 942422 | AE2-255 E O1 | Adder | 5.1 MW | 4.33 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 10.68 MW | 10.68 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 5.25 MW | 5.25 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 7.1 MW | 7.1 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 3.51 MW | 3.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 958911 | AF2-182 C | Adder | 14.78 MW | 12.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 958912 | AF2-182 E | Adder | 9.85 MW | 8.37 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.63 MW | 2.23 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 958922 | AF2-183 E | Adder | 3.94 MW | 3.35 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 9.51 MW | 9.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 4.75 MW | 4.75 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 19.01 MW | 19.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 12.67 MW | 12.67 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 3.25 MW | 2.76 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 9.33 MW | 7.93 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 4.48 MW | 4.48 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960721 | AF2-363 C O1 | Adder | 4.31 MW | 3.66 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960722 | AF2-363 E O1 | Adder | 2.87 MW | 2.44 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.06 MW | 6.06 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.04 MW | 4.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 2.93 MW | 2.49 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 13.72 MW | 11.66 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.0 MW | 4.25 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.33 MW | 2.83 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274658 | DRESDEN ;2U | 50/50 | 25.41 MW | 25.41 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 4.54 MW | 4.54 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 4.54 MW | 4.54 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 7.61 MW | 6.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 7.61 MW | 6.47 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 3.04 MW | 3.04 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.06 MW | 5.16 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.08 MW | 2.62 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.39 MW | 2.88 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293715 | O-029 E | Adder | 6.48 MW | 5.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293716 | O-029 E | Adder | 3.55 MW | 3.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 293717 | O-029 E | Adder | 3.27 MW | 2.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 294763 | P-046 E | Adder | 5.06 MW | 4.3 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 916221 | Z1-073 E | Adder | 4.52 MW | 3.84 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 21.19 MW | 18.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 16.85 MW | 14.32 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 930771 | AB1-122 CT2 | 50/50 | 77.18 MW | 77.18 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 938851 | AE1-113 C O1 | Adder | 4.48 MW | 3.81 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 938852 | AE1-113 E O1 | Adder | 15.9 MW | 13.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.42 MW | 2.05 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 8.24 MW | 7.01 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.08 MW | 0.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.08 MW | 0.92 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.33 MW | 1.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 940502 | AE2-035 E | Adder | 1.83 MW | 1.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 5.7 MW | 5.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 3.8 MW | 3.8 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.25 MW | 9.56 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.17 MW | 4.4 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.25 MW | 0.21 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.4 MW | 1.19 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.46 MW | 2.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 11.51 MW | 9.78 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946501 | AF1-314 C | Adder | 2.35 MW | 2.0 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946502 | AF1-314 E | Adder | 11.05 MW | 9.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 946671 | AF1-331 | Adder | 2.0 MW | 1.7 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 28.51 MW | 28.51 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 14.26 MW | 14.26 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 934111 | AD2-000 2 | 50/50 | 6.24 MW | 6.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.72 MW | 0.72 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 21.09 MW | 21.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 957403 | AF2-034 BAT | 50/50 | 1.02 MW | 1.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 945351 | AF1-200 FTIR | Adder | 182.13 MW | 154.81 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | 955971 | J1084 | External Queue | 8.52 MW | 8.52 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.02 MW | 0.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.24 MW | 0.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.12 MW | 0.12 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.36 MW | 9.36 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.71 MW | 5.71 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.24 MW | 0.24 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.34 MW | 1.34 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.09 MW | 0.09 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.79 MW | 4.79 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.13 MW | 0.13 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.55 MW | 1.55 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.08 MW | 0.08 MW |
| ELECT JCT; B-LOMBARD ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.59 MW | 0.59 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 962722 | AG1-121 E O1 | Adder | 20.73 MW | 17.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 966821 | AG1-553 C O1 | 50/50 | 56.1 MW | 56.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965661 | AG1-434 C O1 | 50/50 | 18.61 MW | 18.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965662 | AG1-434 E O1 | 50/50 | 87.14 MW | 87.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965672 | AG1-435 E O1 | Adder | 15.64 MW | 13.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965931 | AG1-462 C O1 | 50/50 | 36.31 MW | 36.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 295109 | WESTBROOK E | Adder | 4.56 MW | 3.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 295111 | SUBLETTE E | 50/50 | 5.32 MW | 5.32 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 919581 | AA2-030 C | 50/50 | 52.75 MW | 52.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 933911 | AD1-013 C | Adder | 1.44 MW | 1.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 937002 | AD2-134 E | Adder | 8.23 MW | 7.0 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 958911 | AF2-182 C | 50/50 | 60.47 MW | 60.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 958912 | AF2-182 E | 50/50 | 40.31 MW | 40.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 959101 | AF2-201 C O1 | Adder | 4.2 MW | 3.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 959102 | AF2-201 E O1 | Adder | 12.05 MW | 10.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 961011 | AF2-392 C O1 | 50/50 | 9.48 MW | 9.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 961012 | AF2-392 E O1 | 50/50 | 44.37 MW | 44.37 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274663 | QUAD CITI;2U | 50/50 | 36.72 MW | 36.72 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274717 | NELSON EC;2C | 50/50 | 9.71 MW | 9.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 276157 | O-029 C | 50/50 | 0.5 MW | 0.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293518 | O-009 E3 | 50/50 | 11.13 MW | 11.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293715 | O-029 E | 50/50 | 21.27 MW | 21.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293717 | O-029 E | 50/50 | 10.72 MW | 10.72 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 293771 | O-035 E | Adder | 5.37 MW | 4.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 294401 | BSHIL;1U E | 50/50 | 8.84 MW | 8.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 294410 | BSHIL;2U E | 50/50 | 8.84 MW | 8.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 925582 | AC1-033 E | 50/50 | 9.69 MW | 9.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946151 | AF1-280 C O1 | 50/50 | 46.02 MW | 46.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946322 | AF1-296 E O1 | 50/50 | 40.53 MW | 40.53 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946501 | AF1-314 C | Adder | 3.04 MW | 2.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946502 | AF1-314 E | Adder | 14.27 MW | 12.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 957762 | AF2-070 E | Adder | 1.37 MW | 1.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 990901 | L-005 E | Adder | 12.02 MW | 10.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.58 MW | 0.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.76 MW | 6.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.44 MW | 52.44 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.78 MW | 21.78 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.13 MW | 5.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.71 MW | 16.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.05 MW | 1.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.55 MW | 2.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 962722 | AG1-121 E O1 | Adder | 20.73 MW | 17.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 966821 | AG1-553 C O1 | 50/50 | 56.1 MW | 56.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965661 | AG1-434 C O1 | 50/50 | 18.61 MW | 18.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965662 | AG1-434 E O1 | 50/50 | 87.14 MW | 87.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965672 | AG1-435 E O1 | Adder | 15.64 MW | 13.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965931 | AG1-462 C O1 | 50/50 | 36.31 MW | 36.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 295109 | WESTBROOK E | Adder | 4.56 MW | 3.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 295111 | SUBLETTE E | 50/50 | 5.32 MW | 5.32 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 919581 | AA2-030 C | 50/50 | 52.75 MW | 52.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 933911 | AD1-013 C | Adder | 1.44 MW | 1.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 937002 | AD2-134 E | Adder | 8.23 MW | 7.0 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 958911 | AF2-182 C | 50/50 | 60.47 MW | 60.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 958912 | AF2-182 E | 50/50 | 40.31 MW | 40.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 959101 | AF2-201 C O1 | Adder | 4.2 MW | 3.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 959102 | AF2-201 E O1 | Adder | 12.05 MW | 10.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 961011 | AF2-392 C O1 | 50/50 | 9.48 MW | 9.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 961012 | AF2-392 E O1 | 50/50 | 44.37 MW | 44.37 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274663 | QUAD CITI;2U | 50/50 | 36.72 MW | 36.72 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274717 | NELSON EC;2C | 50/50 | 9.71 MW | 9.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 276157 | O-029 C | 50/50 | 0.5 MW | 0.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293518 | O-009 E3 | 50/50 | 11.13 MW | 11.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293715 | O-029 E | 50/50 | 21.27 MW | 21.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293717 | O-029 E | 50/50 | 10.72 MW | 10.72 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 293771 | O-035 E | Adder | 5.37 MW | 4.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 294401 | BSHIL;1U E | 50/50 | 8.84 MW | 8.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 294410 | BSHIL;2U E | 50/50 | 8.84 MW | 8.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 925582 | AC1-033 E | 50/50 | 9.69 MW | 9.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946151 | AF1-280 C O1 | 50/50 | 46.02 MW | 46.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946322 | AF1-296 E O1 | 50/50 | 40.53 MW | 40.53 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946501 | AF1-314 C | Adder | 3.04 MW | 2.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946502 | AF1-314 E | Adder | 14.27 MW | 12.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 957762 | AF2-070 E | Adder | 1.37 MW | 1.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 990901 | L-005 E | Adder | 12.02 MW | 10.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.76 MW | 6.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.43 MW | 52.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.78 MW | 21.78 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.16 MW | 0.16 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.13 MW | 5.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.71 MW | 16.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.05 MW | 1.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.55 MW | 2.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT1-2__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | Adder | 26.65 MW | 22.65 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | Adder | 17.77 MW | 15.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 45.28 MW | 38.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 9.12 MW | 7.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | Adder | 17.77 MW | 15.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | Adder | 11.84 MW | 10.07 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965661 | AG1-434 C O1 | 50/50 | 16.66 MW | 16.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965662 | AG1-434 E O1 | 50/50 | 78.01 MW | 78.01 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 29.3 MW | 24.91 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 19.54 MW | 16.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.01 MW | 1.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.22 MW | 6.99 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.4 MW | 3.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 4.56 MW | 3.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919221 | AA1-146 | 50/50 | 7.02 MW | 7.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | 50/50 | 41.23 MW | 41.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.4 MW | 1.19 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.23 MW | 1.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934051 | AD1-031 C O1 | Adder | 2.31 MW | 1.96 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934052 | AD1-031 E O1 | Adder | 3.76 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.43 MW | 0.37 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 1.99 MW | 1.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 7.95 MW | 6.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | Adder | 2.99 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | Adder | 4.13 MW | 3.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | 50/50 | 41.62 MW | 41.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | 50/50 | 27.75 MW | 27.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | 50/50 | 7.4 MW | 7.4 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | 50/50 | 11.1 MW | 11.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | Adder | 7.32 MW | 6.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | Adder | 21.01 MW | 17.86 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960581 | AF2-349 C | Adder | 15.01 MW | 12.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960582 | AF2-349 E | Adder | 10.01 MW | 8.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | 50/50 | 7.79 MW | 7.79 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | 50/50 | 36.47 MW | 36.47 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | 50/50 | 13.28 MW | 13.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | 50/50 | 8.85 MW | 8.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274715 | NELSON EC;1C | 50/50 | 7.53 MW | 7.53 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274716 | NELSON EC;1S | 50/50 | 5.49 MW | 5.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274717 | NELSON EC;2C | 50/50 | 7.59 MW | 7.59 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274718 | NELSON EC;2S | 50/50 | 5.54 MW | 5.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274760 | LEE CO EC;1U | 50/50 | 3.14 MW | 3.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 3.15 MW | 3.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 3.15 MW | 3.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 20.86 MW | 17.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 20.86 MW | 17.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 16.04 MW | 13.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 8.15 MW | 6.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 8.97 MW | 7.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 17.15 MW | 14.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 9.4 MW | 7.99 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 8.64 MW | 7.34 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294401 | BSHIL;1U E | Adder | 6.98 MW | 5.94 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294410 | BSHIL;2U E | Adder | 6.98 MW | 5.94 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | Adder | 11.39 MW | 9.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.27 MW | 3.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925581 | AC1-033 C | Adder | 1.14 MW | 0.97 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925582 | AC1-033 E | Adder | 7.66 MW | 6.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | Adder | 45.39 MW | 38.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | Adder | 36.09 MW | 30.67 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | Adder | 5.75 MW | 4.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | Adder | 19.61 MW | 16.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | 50/50 | 3.2 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | 50/50 | 3.2 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | Adder | 2.99 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | Adder | 4.13 MW | 3.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | 50/50 | 31.68 MW | 31.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | 50/50 | 14.57 MW | 14.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | 50/50 | 3.93 MW | 3.93 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 7.08 MW | 6.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 33.16 MW | 28.19 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | Adder | 5.3 MW | 4.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | Adder | 24.88 MW | 21.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.82 MW | 1.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990901 | L-005 E | Adder | 9.46 MW | 8.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965082 | AG1-373 BAT | 50/50 | 11.42 MW | 11.42 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965062 | AG1-371 BAT | 50/50 | 34.25 MW | 34.25 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951381 | J504 | External Queue | 4.22 MW | 4.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951421 | J514 | External Queue | 2.51 MW | 2.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951511 | J530 C | External Queue | 3.88 MW | 3.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951512 | J530 E | External Queue | 15.5 MW | 15.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.83 MW | 6.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 22.66 MW | 22.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 956411 | J1131 | External Queue | 11.85 MW | 11.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 7.58 MW | 7.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 33.18 MW | 33.18 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 991091 | J1477 | External Queue | 5.93 MW | 5.93 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.36 MW | 0.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.42 MW | 0.42 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.35 MW | 3.35 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 61.98 MW | 61.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.54 MW | 17.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.44 MW | 0.44 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.3 MW | 4.3 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.2 MW | 15.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.96 MW | 1.96 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.09 MW | 1.09 MW |
| Details for AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962012 | AG1-044 E | 50/50 | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962701 | AG1-119 C | Adder | 26.65 MW | 22.65 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962702 | AG1-119 E | Adder | 17.77 MW | 15.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966821 | AG1-553 C O1 | Adder | 45.28 MW | 38.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966822 | AG1-553 E O1 | Adder | 9.12 MW | 7.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965551 | AG1-423 C O1 | Adder | 17.77 MW | 15.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965552 | AG1-423 E O1 | Adder | 11.84 MW | 10.07 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965661 | AG1-434 C O1 | 50/50 | 16.66 MW | 16.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965662 | AG1-434 E O1 | 50/50 | 78.0 MW | 78.0 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965931 | AG1-462 C O1 | Adder | 29.31 MW | 24.91 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965932 | AG1-462 E O1 | Adder | 19.54 MW | 16.61 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 272364 | ESS H440N ;R | Adder | 2.01 MW | 1.71 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290051 | GSG-6; E | Adder | 8.21 MW | 6.98 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.4 MW | 3.74 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 4.56 MW | 3.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919221 | AA1-146 | 50/50 | 7.02 MW | 7.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919581 | AA2-030 C | 50/50 | 41.23 MW | 41.23 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.4 MW | 1.19 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.23 MW | 1.9 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934051 | AD1-031 C O1 | Adder | 2.31 MW | 1.96 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934052 | AD1-031 E O1 | Adder | 3.76 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.43 MW | 0.37 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937001 | AD2-134 C | Adder | 1.99 MW | 1.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937002 | AD2-134 E | Adder | 7.94 MW | 6.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937311 | AD2-172 C | Adder | 2.99 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937312 | AD2-172 E | Adder | 4.13 MW | 3.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958911 | AF2-182 C | 50/50 | 41.62 MW | 41.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958912 | AF2-182 E | 50/50 | 27.75 MW | 27.75 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958921 | AF2-183 C | 50/50 | 7.4 MW | 7.4 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958922 | AF2-183 E | 50/50 | 11.1 MW | 11.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959101 | AF2-201 C O1 | Adder | 7.32 MW | 6.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959102 | AF2-201 E O1 | Adder | 21.01 MW | 17.86 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960581 | AF2-349 C | Adder | 15.01 MW | 12.76 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960582 | AF2-349 E | Adder | 10.01 MW | 8.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961011 | AF2-392 C O1 | 50/50 | 7.79 MW | 7.79 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961012 | AF2-392 E O1 | 50/50 | 36.46 MW | 36.46 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961021 | AF2-393 O1 | 50/50 | 13.28 MW | 13.28 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961031 | AF2-394 O1 | 50/50 | 8.85 MW | 8.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274715 | NELSON EC;1C | 50/50 | 7.53 MW | 7.53 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274716 | NELSON EC;1S | 50/50 | 5.49 MW | 5.49 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274717 | NELSON EC;2C | 50/50 | 7.59 MW | 7.59 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274718 | NELSON EC;2S | 50/50 | 5.54 MW | 5.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274760 | LEE CO EC;1U | 50/50 | 3.14 MW | 3.14 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274764 | LEE CO EC;5U | 50/50 | 3.15 MW | 3.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274765 | LEE CO EC;6U | 50/50 | 3.15 MW | 3.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274859 | EASYR;U1 E | Adder | 20.86 MW | 17.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274860 | EASYR;U2 E | Adder | 20.86 MW | 17.73 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293516 | O-009 E1 | Adder | 16.04 MW | 13.63 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293517 | O-009 E2 | Adder | 8.15 MW | 6.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293518 | O-009 E3 | Adder | 8.97 MW | 7.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293715 | O-029 E | Adder | 17.15 MW | 14.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293716 | O-029 E | Adder | 9.4 MW | 7.99 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293717 | O-029 E | Adder | 8.64 MW | 7.34 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294401 | BSHIL;1U E | Adder | 6.98 MW | 5.94 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294410 | BSHIL;2U E | Adder | 6.98 MW | 5.94 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294763 | P-046 E | Adder | 11.39 MW | 9.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 916221 | Z1-073 E | Adder | 4.26 MW | 3.62 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 925581 | AC1-033 C | Adder | 1.14 MW | 0.97 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 925582 | AC1-033 E | Adder | 7.66 MW | 6.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930482 | AB1-089 CT | Adder | 45.4 MW | 38.59 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930483 | AB1-089 ST | Adder | 36.09 MW | 30.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938861 | AE1-114 C O1 | Adder | 5.75 MW | 4.88 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938862 | AE1-114 E O1 | Adder | 19.6 MW | 16.66 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939051 | AE1-134 1 | 50/50 | 3.2 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939061 | AE1-134 2 | 50/50 | 3.2 MW | 3.2 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940501 | AE2-035 C | Adder | 2.99 MW | 2.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940502 | AE2-035 E | Adder | 4.13 MW | 3.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946151 | AF1-280 C O1 | 50/50 | 31.68 MW | 31.68 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946152 | AF1-280 E O1 | 50/50 | 14.57 MW | 14.57 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946161 | AF1-281 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946162 | AF1-281 E O1 | 50/50 | 3.93 MW | 3.93 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946321 | AF1-296 C O1 | Adder | 7.08 MW | 6.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946322 | AF1-296 E O1 | Adder | 33.16 MW | 28.19 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946501 | AF1-314 C | Adder | 5.3 MW | 4.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946502 | AF1-314 E | Adder | 24.89 MW | 21.15 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.81 MW | 1.54 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990901 | L-005 E | Adder | 9.46 MW | 8.04 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965082 | AG1-373 BAT | 50/50 | 11.42 MW | 11.42 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965062 | AG1-371 BAT | 50/50 | 34.26 MW | 34.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 951381 | J504 | External Queue | 4.22 MW | 4.22 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 951421 | J514 | External Queue | 2.51 MW | 2.51 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 951511 | J530 C | External Queue | 3.87 MW | 3.87 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 951512 | J530 E | External Queue | 15.5 MW | 15.5 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953922 | J855 E | External Queue | 6.84 MW | 6.84 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 955971 | J1084 | External Queue | 22.65 MW | 22.65 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 956411 | J1131 | External Queue | 11.85 MW | 11.85 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990726 | J1377 | External Queue | 7.58 MW | 7.58 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990947 | J1432 E | External Queue | 33.17 MW | 33.17 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 991091 | J1477 | External Queue | 5.92 MW | 5.92 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.36 MW | 0.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.43 MW | 0.43 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.36 MW | 3.36 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.1 MW | 62.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.55 MW | 17.55 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.44 MW | 0.44 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.31 MW | 4.31 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.21 MW | 15.21 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.96 MW | 1.96 MW |
| AG1-434 TAP-AF2-041 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.1 MW | 1.1 MW |
| Details for NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 966821 | AG1-553 C O1 | Adder | 11.93 MW | 10.14 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 966822 | AG1-553 E O1 | Adder | 2.4 MW | 2.04 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 965931 | AG1-462 C O1 | Adder | 7.72 MW | 6.56 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 965932 | AG1-462 E O1 | Adder | 5.15 MW | 4.37 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 272364 | ESS H440N ;R | Adder | -3.12 MW | -2.65 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 919581 | AA2-030 C | Adder | 15.44 MW | 13.13 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 937311 | AD2-172 C | Adder | -2.08 MW | -1.77 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 958911 | AF2-182 C | Adder | 14.0 MW | 11.9 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 958912 | AF2-182 E | Adder | 9.34 MW | 7.93 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 958921 | AF2-183 C | Adder | 2.49 MW | 2.12 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 958922 | AF2-183 E | Adder | 3.73 MW | 3.17 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 274859 | EASYR;U1 E | Adder | 6.59 MW | 5.6 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 274860 | EASYR;U2 E | Adder | 6.59 MW | 5.6 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 925581 | AC1-033 C | Adder | -0.97 MW | -0.83 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 939051 | AE1-134 1 | Adder | 1.2 MW | 1.02 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 939061 | AE1-134 2 | Adder | 1.2 MW | 1.02 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 940501 | AE2-035 C | Adder | -2.08 MW | -1.77 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 946151 | AF1-280 C O1 | Adder | 10.66 MW | 9.06 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 946152 | AF1-280 E O1 | Adder | 4.9 MW | 4.17 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 946161 | AF1-281 C O1 | Adder | 0.23 MW | 0.2 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 946162 | AF1-281 E O1 | Adder | 1.32 MW | 1.12 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 962013 | AG1-044 BAT | 50/50 | 0.16 MW | 0.16 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 961022 | AF2-393 BAT | 50/50 | 25.7 MW | 25.7 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | 961032 | AF2-394 BAT | 50/50 | 17.13 MW | 17.13 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.15 MW | 0.15 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.06 MW | 0.06 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.14 MW | 9.14 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.89 MW | 1.89 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.1 MW | 0.1 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.58 MW | 0.58 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.54 MW | 2.54 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.66 MW | 0.66 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.22 MW | 0.22 MW |
| NELSON ; B-NELSON ;4M 345.0/138.0 kV Ckt 1 transformer l/o COMED_P4_155-45-BT2-34_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962012 | AG1-044 E | 50/50 | 0.16 MW | 0.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962721 | AG1-121 C O1 | Adder | 4.43 MW | 3.77 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 962722 | AG1-121 E O1 | Adder | 20.72 MW | 17.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966821 | AG1-553 C O1 | 50/50 | 56.08 MW | 56.08 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 966822 | AG1-553 E O1 | 50/50 | 11.29 MW | 11.29 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965671 | AG1-435 C O1 | Adder | 3.34 MW | 2.84 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965672 | AG1-435 E O1 | Adder | 15.63 MW | 13.29 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965931 | AG1-462 C O1 | 50/50 | 36.3 MW | 36.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965932 | AG1-462 E O1 | 50/50 | 24.2 MW | 24.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 272364 | ESS H440N ;R | Adder | 2.07 MW | 1.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 290051 | GSG-6; E | Adder | 8.51 MW | 7.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295109 | WESTBROOK E | Adder | 4.55 MW | 3.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295110 | SUBLETTE C | 50/50 | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 295111 | SUBLETTE E | 50/50 | 5.31 MW | 5.31 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919221 | AA1-146 | 50/50 | 8.98 MW | 8.98 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 919581 | AA2-030 C | 50/50 | 52.74 MW | 52.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 927202 | AC1-214 E O1 | Adder | 5.48 MW | 4.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933911 | AD1-013 C | Adder | 1.43 MW | 1.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 933912 | AD1-013 E | Adder | 2.29 MW | 1.95 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934051 | AD1-031 C O1 | 50/50 | 2.92 MW | 2.92 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934052 | AD1-031 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937001 | AD2-134 C | Adder | 2.06 MW | 1.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937002 | AD2-134 E | Adder | 8.22 MW | 6.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937311 | AD2-172 C | Adder | 1.71 MW | 1.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 937312 | AD2-172 E | Adder | 2.37 MW | 2.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958911 | AF2-182 C | 50/50 | 60.46 MW | 60.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958912 | AF2-182 E | 50/50 | 40.3 MW | 40.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958921 | AF2-183 C | 50/50 | 10.75 MW | 10.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 958922 | AF2-183 E | 50/50 | 16.12 MW | 16.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959101 | AF2-201 C O1 | Adder | 4.19 MW | 3.56 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 959102 | AF2-201 E O1 | Adder | 12.04 MW | 10.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961011 | AF2-392 C O1 | 50/50 | 9.47 MW | 9.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961012 | AF2-392 E O1 | 50/50 | 44.36 MW | 44.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961021 | AF2-393 O1 | 50/50 | 16.15 MW | 16.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 961031 | AF2-394 O1 | 50/50 | 10.77 MW | 10.77 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274662 | QUAD CITI;1U | 50/50 | 36.61 MW | 36.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274663 | QUAD CITI;2U | 50/50 | 36.71 MW | 36.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274699 | CORDOVA ;1C | 50/50 | 6.45 MW | 6.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274700 | CORDOVA ;2C | 50/50 | 6.45 MW | 6.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274701 | CORDOVA ;1S | 50/50 | 7.25 MW | 7.25 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274715 | NELSON EC;1C | 50/50 | 9.63 MW | 9.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274716 | NELSON EC;1S | 50/50 | 7.03 MW | 7.03 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274717 | NELSON EC;2C | 50/50 | 9.7 MW | 9.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274718 | NELSON EC;2S | 50/50 | 7.09 MW | 7.09 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274857 | BIG SKY ;U1 | 50/50 | 0.87 MW | 0.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274858 | BIG SKY ;U2 | 50/50 | 0.87 MW | 0.87 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274859 | EASYR;U1 E | 50/50 | 32.24 MW | 32.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274860 | EASYR;U2 E | 50/50 | 32.24 MW | 32.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274877 | BISHOP HL;1U | 50/50 | 0.38 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 274878 | BISHOP HL;2U | 50/50 | 0.38 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276156 | O-029 C | 50/50 | 0.46 MW | 0.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276157 | O-029 C | 50/50 | 0.49 MW | 0.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 276158 | O-029 C | 50/50 | 0.9 MW | 0.9 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293513 | O-009 C1 | 50/50 | 0.85 MW | 0.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293514 | O-009 C2 | 50/50 | 0.43 MW | 0.43 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293515 | O-009 C3 | 50/50 | 0.47 MW | 0.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293516 | O-009 E1 | 50/50 | 19.89 MW | 19.89 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293517 | O-009 E2 | 50/50 | 10.1 MW | 10.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293518 | O-009 E3 | 50/50 | 11.12 MW | 11.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293715 | O-029 E | 50/50 | 21.26 MW | 21.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293716 | O-029 E | 50/50 | 11.66 MW | 11.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293717 | O-029 E | 50/50 | 10.71 MW | 10.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 293771 | O-035 E | Adder | 5.37 MW | 4.56 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294401 | BSHIL;1U E | 50/50 | 8.83 MW | 8.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294410 | BSHIL;2U E | 50/50 | 8.83 MW | 8.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 294763 | P-046 E | Adder | 6.53 MW | 5.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916211 | Z1-072 E | Adder | 4.06 MW | 3.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 916221 | Z1-073 E | Adder | 4.42 MW | 3.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925581 | AC1-033 C | 50/50 | 1.45 MW | 1.45 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 925582 | AC1-033 E | 50/50 | 9.68 MW | 9.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938861 | AE1-114 C O1 | 50/50 | 5.06 MW | 5.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 938862 | AE1-114 E O1 | 50/50 | 17.27 MW | 17.27 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939051 | AE1-134 1 | 50/50 | 4.1 MW | 4.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 939061 | AE1-134 2 | 50/50 | 4.1 MW | 4.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940501 | AE2-035 C | Adder | 1.71 MW | 1.46 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 940502 | AE2-035 E | Adder | 2.37 MW | 2.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946151 | AF1-280 C O1 | 50/50 | 46.01 MW | 46.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946152 | AF1-280 E O1 | 50/50 | 21.16 MW | 21.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946161 | AF1-281 C O1 | 50/50 | 1.01 MW | 1.01 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946162 | AF1-281 E O1 | 50/50 | 5.71 MW | 5.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946321 | AF1-296 C O1 | 50/50 | 8.66 MW | 8.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946322 | AF1-296 E O1 | 50/50 | 40.52 MW | 40.52 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946501 | AF1-314 C | Adder | 3.03 MW | 2.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946502 | AF1-314 E | Adder | 14.26 MW | 12.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 946671 | AF1-331 | Adder | 1.86 MW | 1.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990901 | L-005 E | Adder | 12.01 MW | 10.21 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965082 | AG1-373 BAT | 50/50 | 10.18 MW | 10.18 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 965062 | AG1-371 BAT | 50/50 | 30.54 MW | 30.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951031 | J344 C | External Queue | 2.71 MW | 2.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951032 | J344 E | External Queue | 8.14 MW | 8.14 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951381 | J504 | External Queue | 5.04 MW | 5.04 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951421 | J514 | External Queue | 3.06 MW | 3.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951511 | J530 C | External Queue | 4.95 MW | 4.95 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951512 | J530 E | External Queue | 19.82 MW | 19.82 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951841 | J555 C | External Queue | 1.82 MW | 1.82 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 951842 | J555 E | External Queue | 9.84 MW | 9.84 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 954702 | J844 E | External Queue | 12.62 MW | 12.62 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 955971 | J1084 | External Queue | 29.54 MW | 29.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 956411 | J1131 | External Queue | 15.48 MW | 15.48 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 990947 | J1432 E | External Queue | 41.55 MW | 41.55 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | 991091 | J1477 | External Queue | 7.74 MW | 7.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.7 MW | 6.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 52.36 MW | 52.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.73 MW | 21.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.17 MW | 0.17 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.12 MW | 5.12 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.28 MW | 0.28 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.7 MW | 16.7 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 1.08 MW | 1.08 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.54 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_937-45-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | 50/50 | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | Adder | 26.65 MW | 22.65 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | Adder | 17.77 MW | 15.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 45.28 MW | 38.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 9.12 MW | 7.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | Adder | 17.77 MW | 15.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | Adder | 11.84 MW | 10.07 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 29.3 MW | 24.91 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 19.54 MW | 16.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.01 MW | 1.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.22 MW | 6.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.4 MW | 3.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 4.56 MW | 3.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919221 | AA1-146 | 50/50 | 7.02 MW | 7.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | 50/50 | 41.23 MW | 41.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.4 MW | 1.19 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.23 MW | 1.9 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934051 | AD1-031 C O1 | Adder | 2.31 MW | 1.96 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934052 | AD1-031 E O1 | Adder | 3.76 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.43 MW | 0.37 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 1.99 MW | 1.69 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 7.95 MW | 6.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | Adder | 2.99 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | Adder | 4.13 MW | 3.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | 50/50 | 41.62 MW | 41.62 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | 50/50 | 27.75 MW | 27.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | 50/50 | 7.4 MW | 7.4 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | 50/50 | 11.1 MW | 11.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | Adder | 7.32 MW | 6.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | Adder | 21.01 MW | 17.86 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960581 | AF2-349 C | Adder | 15.01 MW | 12.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960582 | AF2-349 E | Adder | 10.01 MW | 8.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | 50/50 | 7.79 MW | 7.79 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | 50/50 | 36.47 MW | 36.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | 50/50 | 13.28 MW | 13.28 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | 50/50 | 8.85 MW | 8.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274715 | NELSON EC;1C | 50/50 | 7.53 MW | 7.53 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274716 | NELSON EC;1S | 50/50 | 5.49 MW | 5.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274717 | NELSON EC;2C | 50/50 | 7.59 MW | 7.59 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274718 | NELSON EC;2S | 50/50 | 5.54 MW | 5.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274761 | LEE CO EC;2U | 50/50 | 3.14 MW | 3.14 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 3.15 MW | 3.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 3.15 MW | 3.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 20.86 MW | 17.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 20.86 MW | 17.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 16.04 MW | 13.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 8.15 MW | 6.92 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 8.97 MW | 7.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 17.15 MW | 14.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 9.4 MW | 7.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 8.64 MW | 7.34 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294401 | BSHIL;1U E | Adder | 6.98 MW | 5.94 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294410 | BSHIL;2U E | Adder | 6.98 MW | 5.94 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | Adder | 11.39 MW | 9.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.27 MW | 3.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925581 | AC1-033 C | Adder | 1.14 MW | 0.97 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925582 | AC1-033 E | Adder | 7.66 MW | 6.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | Adder | 45.39 MW | 38.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | Adder | 36.09 MW | 30.67 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | Adder | 5.75 MW | 4.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | Adder | 19.61 MW | 16.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | 50/50 | 3.2 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | 50/50 | 3.2 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | Adder | 2.99 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | Adder | 4.13 MW | 3.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | 50/50 | 31.68 MW | 31.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | 50/50 | 14.57 MW | 14.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | 50/50 | 3.93 MW | 3.93 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 7.08 MW | 6.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 33.16 MW | 28.19 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | Adder | 5.3 MW | 4.5 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | Adder | 24.88 MW | 21.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.82 MW | 1.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990901 | L-005 E | Adder | 9.46 MW | 8.04 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965082 | AG1-373 BAT | 50/50 | 11.42 MW | 11.42 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965062 | AG1-371 BAT | 50/50 | 34.25 MW | 34.25 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951381 | J504 | External Queue | 4.22 MW | 4.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951421 | J514 | External Queue | 2.51 MW | 2.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951511 | J530 C | External Queue | 3.88 MW | 3.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951512 | J530 E | External Queue | 15.5 MW | 15.5 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.83 MW | 6.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 22.66 MW | 22.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 956411 | J1131 | External Queue | 11.85 MW | 11.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 7.58 MW | 7.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 33.18 MW | 33.18 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 991091 | J1477 | External Queue | 5.93 MW | 5.93 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.36 MW | 0.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.42 MW | 0.42 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.35 MW | 3.35 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 61.98 MW | 61.98 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.54 MW | 17.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.44 MW | 0.44 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.3 MW | 4.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.2 MW | 15.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.96 MW | 1.96 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.09 MW | 1.09 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961651 | AG1-005 C O1 | Adder | 12.46 MW | 10.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961652 | AG1-005 E O1 | Adder | 8.31 MW | 7.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962721 | AG1-121 C O1 | Adder | 4.27 MW | 3.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962722 | AG1-121 E O1 | Adder | 19.98 MW | 16.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963831 | AG1-236 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963832 | AG1-236 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964581 | AG1-321 C O1 | Adder | 11.85 MW | 10.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964582 | AG1-321 E O1 | Adder | 6.9 MW | 5.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966821 | AG1-553 C O1 | Adder | 19.15 MW | 16.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965061 | AG1-371 | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965081 | AG1-373 | Adder | 0.66 MW | 0.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965091 | AG1-374 C | 50/50 | 21.84 MW | 21.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965092 | AG1-374 E | 50/50 | 14.56 MW | 14.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965331 | AG1-398 | 50/50 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965341 | AG1-399 C | 50/50 | 7.19 MW | 7.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965342 | AG1-399 E | 50/50 | 33.66 MW | 33.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965351 | AG1-400 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965371 | AG1-402 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965391 | AG1-404 | 50/50 | 13.62 MW | 13.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965661 | AG1-434 C O1 | Adder | 2.4 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965662 | AG1-434 E O1 | Adder | 11.22 MW | 9.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965671 | AG1-435 C O1 | Adder | 2.91 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965672 | AG1-435 E O1 | Adder | 13.62 MW | 11.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965911 | AG1-460 C | 50/50 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965912 | AG1-460 E | 50/50 | 3.07 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965931 | AG1-462 C O1 | Adder | 12.39 MW | 10.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965932 | AG1-462 E O1 | Adder | 8.26 MW | 7.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 272364 | ESS H440N ;R | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290051 | GSG-6; E | Adder | 5.74 MW | 4.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290261 | S-027 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290265 | S-028 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295109 | WESTBROOK E | Adder | 3.07 MW | 2.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295111 | SUBLETTE E | Adder | 1.64 MW | 1.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 919581 | AA2-030 C | Adder | 11.53 MW | 9.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925771 | AC1-053 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925772 | AC1-053 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 927202 | AC1-214 E O1 | Adder | 5.02 MW | 4.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933911 | AD1-013 C | Adder | 1.01 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933912 | AD1-013 E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934051 | AD1-031 C O1 | Adder | 2.21 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934052 | AD1-031 E O1 | Adder | 3.61 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934432 | AD1-067 E | Adder | 0.3 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 935141 | AD1-148 | 50/50 | 5.64 MW | 5.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936771 | AD2-100 C | 50/50 | 22.11 MW | 22.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936772 | AD2-100 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936971 | AD2-131 C | 50/50 | 1.46 MW | 1.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936972 | AD2-131 E | 50/50 | 7.32 MW | 7.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937001 | AD2-134 C | Adder | 1.39 MW | 1.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937002 | AD2-134 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937311 | AD2-172 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937312 | AD2-172 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942111 | AE2-223 C | 50/50 | 2.19 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942112 | AE2-223 E | 50/50 | 14.69 MW | 14.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942481 | AE2-261 C | 50/50 | 30.63 MW | 30.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942482 | AE2-261 E | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945871 | AF1-252 O1 | 50/50 | 11.82 MW | 11.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945881 | AF1-253 | 50/50 | 8.19 MW | 8.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946542 | AF1-318 E O1 | Adder | 20.54 MW | 17.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958911 | AF2-182 C | Adder | 12.9 MW | 10.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958912 | AF2-182 E | Adder | 8.6 MW | 7.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958921 | AF2-183 C | Adder | 2.29 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958922 | AF2-183 E | Adder | 3.44 MW | 2.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959081 | AF2-199 C | Adder | 3.98 MW | 3.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959082 | AF2-199 E | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959091 | AF2-200 C O1 | Adder | 7.96 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959092 | AF2-200 E O1 | Adder | 5.31 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959101 | AF2-201 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959102 | AF2-201 E O1 | Adder | 10.09 MW | 8.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959341 | AF2-225 C | 50/50 | 7.09 MW | 7.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959342 | AF2-225 E | 50/50 | 9.79 MW | 9.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959611 | AF2-252 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959612 | AF2-252 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960141 | AF2-305 | 50/50 | 1.37 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960261 | AF2-317 | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960611 | AF2-352 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960612 | AF2-352 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961011 | AF2-392 C O1 | Adder | 2.57 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961012 | AF2-392 E O1 | Adder | 12.02 MW | 10.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961021 | AF2-393 O1 | Adder | 4.38 MW | 3.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961031 | AF2-394 O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274650 | KINCAID ;1U | 50/50 | 16.0 MW | 16.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274651 | KINCAID ;2U | 50/50 | 15.99 MW | 15.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274859 | EASYR;U1 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274860 | EASYR;U2 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274880 | RADFORD R;1U | 50/50 | 1.16 MW | 1.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276615 | W2-048 GEN | 50/50 | 8.02 MW | 8.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276621 | X2-022 GEN | 50/50 | 28.76 MW | 28.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293516 | O-009 E1 | Adder | 6.22 MW | 5.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293517 | O-009 E2 | Adder | 3.16 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293518 | O-009 E3 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293715 | O-029 E | Adder | 6.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293716 | O-029 E | Adder | 3.65 MW | 3.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293717 | O-029 E | Adder | 3.35 MW | 2.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293771 | O-035 E | Adder | 4.92 MW | 4.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293777 | CAYUG;1U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293778 | CAYUG;2U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293798 | W4-005 E | 50/50 | 38.82 MW | 38.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294401 | BSHIL;1U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294410 | BSHIL;2U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294763 | P-046 E | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916211 | Z1-072 E | Adder | 3.73 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916221 | Z1-073 E | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 917502 | Z2-087 E | 50/50 | 19.59 MW | 19.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924042 | AB2-047 E O1 | 50/50 | 24.48 MW | 24.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924261 | AB2-070 C O1 | 50/50 | 3.86 MW | 3.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924262 | AB2-070 E O1 | 50/50 | 23.4 MW | 23.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925582 | AC1-033 E | Adder | 7.3 MW | 6.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930482 | AB1-089 CT | Adder | 20.14 MW | 17.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930483 | AB1-089 ST | Adder | 16.01 MW | 13.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930761 | AB1-122 CT1 | Adder | 40.35 MW | 34.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938861 | AE1-114 C O1 | Adder | 2.38 MW | 2.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938862 | AE1-114 E O1 | Adder | 8.12 MW | 6.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939401 | AE1-172 C O1 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939402 | AE1-172 E O1 | Adder | 16.31 MW | 13.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939741 | AE1-205 C O1 | 50/50 | 9.46 MW | 9.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939742 | AE1-205 E O1 | 50/50 | 13.06 MW | 13.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940501 | AE2-035 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940502 | AE2-035 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941731 | AE2-173 O1 | 50/50 | 5.63 MW | 5.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944221 | AF1-090 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944222 | AF1-090 E O1 | 50/50 | 31.22 MW | 31.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946151 | AF1-280 C O1 | Adder | 9.82 MW | 8.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946152 | AF1-280 E O1 | Adder | 4.52 MW | 3.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946322 | AF1-296 E O1 | Adder | 13.95 MW | 11.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946501 | AF1-314 C | Adder | 2.54 MW | 2.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946502 | AF1-314 E | Adder | 11.95 MW | 10.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946541 | AF1-318 C O1 | Adder | 4.39 MW | 3.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946671 | AF1-331 | Adder | 1.31 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957381 | AF2-032 C | 50/50 | 2.3 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957382 | AF2-032 E | 50/50 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957471 | AF2-041 C | Adder | 11.94 MW | 10.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957472 | AF2-041 E | Adder | 5.97 MW | 5.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957762 | AF2-070 E | Adder | 1.25 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958341 | AF2-128 C O1 | Adder | 1.16 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958342 | AF2-128 E O1 | Adder | 5.44 MW | 4.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990901 | L-005 E | Adder | 10.6 MW | 9.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934101 | AD2-000 1 | Adder | 3.26 MW | 2.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944202 | AF1-088 FTWR | 50/50 | 260.6 MW | 260.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942602 | AE2-276 BAT | 50/50 | 13.03 MW | 13.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941343 | AE2-130 BAT | 50/50 | 29.76 MW | 29.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953401 | J811 | External Queue | 18.24 MW | 18.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953641 | J813 | External Queue | 40.35 MW | 40.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953881 | J848 C | External Queue | 5.27 MW | 5.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953882 | J848 E | External Queue | 28.49 MW | 28.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954411 | J912 | External Queue | 14.3 MW | 14.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954681 | J949 C | External Queue | 32.68 MW | 32.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 956451 | J1139 | External Queue | 20.06 MW | 20.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990056 | J1201 | External Queue | 7.03 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990071 | J1204 | External Queue | 65.85 MW | 65.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990271 | J1263 | External Queue | 106.84 MW | 106.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991196 | J1626 | External Queue | 27.64 MW | 27.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991266 | J1714 | External Queue | 18.43 MW | 18.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991261 | J1713 C | External Queue | 3.03 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991262 | J1713 E | External Queue | 3.46 MW | 3.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.61 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.0 MW | 15.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 69.74 MW | 69.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.94 MW | 68.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.87 MW | 12.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.61 MW | 1.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.25 MW | 15.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.26 MW | 1.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.93 MW | 7.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.06 MW | 2.06 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961651 | AG1-005 C O1 | 50/50 | 22.19 MW | 22.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961652 | AG1-005 E O1 | 50/50 | 14.79 MW | 14.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962721 | AG1-121 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962722 | AG1-121 E O1 | 50/50 | 44.72 MW | 44.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966821 | AG1-553 C O1 | 50/50 | 23.66 MW | 23.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966822 | AG1-553 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965141 | AG1-379 C | 50/50 | 36.67 MW | 36.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965142 | AG1-379 E | 50/50 | 16.79 MW | 16.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965672 | AG1-435 E O1 | 50/50 | 31.26 MW | 31.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965931 | AG1-462 C O1 | 50/50 | 15.32 MW | 15.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965932 | AG1-462 E O1 | 50/50 | 10.21 MW | 10.21 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 290021 | O50 E | 50/50 | 42.77 MW | 42.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 918052 | AA1-018 E OP | 50/50 | 64.27 MW | 64.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926822 | AC1-168 E O1 | 50/50 | 10.02 MW | 10.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927202 | AC1-214 E O1 | 50/50 | 10.86 MW | 10.86 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934051 | AD1-031 C O1 | 50/50 | 5.34 MW | 5.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936292 | AD2-038 E O1 | 50/50 | 60.89 MW | 60.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942421 | AE2-255 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942422 | AE2-255 E O1 | 50/50 | 20.05 MW | 20.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942652 | AE2-281 E O1 | 50/50 | 21.18 MW | 21.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946542 | AF1-318 E O1 | 50/50 | 37.91 MW | 37.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958481 | AF2-142 C | 50/50 | 44.33 MW | 44.33 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958482 | AF2-142 E | 50/50 | 29.55 MW | 29.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958491 | AF2-143 C | 50/50 | 44.34 MW | 44.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958492 | AF2-143 E | 50/50 | 29.56 MW | 29.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959351 | AF2-226 C | 50/50 | 9.82 MW | 9.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959352 | AF2-226 E | 50/50 | 14.73 MW | 14.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960281 | AF2-319 C | 50/50 | 9.82 MW | 9.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960282 | AF2-319 E | 50/50 | 14.73 MW | 14.73 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274677 | POWERTON ;5U | 50/50 | 64.38 MW | 64.38 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274678 | POWERTON ;6U | 50/50 | 64.56 MW | 64.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274701 | CORDOVA ;1S | 50/50 | 3.08 MW | 3.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274861 | TOP CROP ;1U | 50/50 | 1.54 MW | 1.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274862 | TOP CROP ;2U | 50/50 | 2.94 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274891 | OTTER CRK;1U | 50/50 | 1.64 MW | 1.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293516 | O-009 E1 | Adder | 7.88 MW | 6.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293517 | O-009 E2 | Adder | 4.0 MW | 3.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293518 | O-009 E3 | Adder | 4.4 MW | 3.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293644 | O22 E1 | 50/50 | 40.08 MW | 40.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293645 | O22 E2 | 50/50 | 77.79 MW | 77.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293715 | O-029 E | Adder | 8.42 MW | 7.16 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293716 | O-029 E | Adder | 4.62 MW | 3.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293717 | O-029 E | Adder | 4.24 MW | 3.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293771 | O-035 E | 50/50 | 10.64 MW | 10.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294401 | BSHIL;1U E | 50/50 | 15.9 MW | 15.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294410 | BSHIL;2U E | 50/50 | 15.9 MW | 15.9 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 916211 | Z1-072 E | 50/50 | 8.05 MW | 8.05 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925581 | AC1-033 C | 50/50 | 2.6 MW | 2.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925582 | AC1-033 E | 50/50 | 17.43 MW | 17.43 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 930761 | AB1-122 CT1 | 50/50 | 395.01 MW | 395.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938851 | AE1-113 C O1 | 50/50 | 17.64 MW | 17.64 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938852 | AE1-113 E O1 | 50/50 | 62.55 MW | 62.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939321 | AE1-163 C O1 | 50/50 | 24.14 MW | 24.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939322 | AE1-163 E O1 | 50/50 | 148.28 MW | 148.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946321 | AF1-296 C O1 | Adder | 3.45 MW | 2.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946322 | AF1-296 E O1 | Adder | 16.16 MW | 13.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958342 | AF2-128 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990901 | L-005 E | 50/50 | 27.78 MW | 27.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934101 | AD2-000 1 | 50/50 | 31.94 MW | 31.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.49 MW | 11.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.6 MW | 37.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.43 MW | 38.43 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.55 MW | 0.55 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.22 MW | 7.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.7 MW | 14.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.92 MW | 0.92 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.08 MW | 4.08 MW |
| Details for 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961651 | AG1-005 C O1 | 50/50 | 22.19 MW | 22.19 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 961652 | AG1-005 E O1 | 50/50 | 14.79 MW | 14.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962721 | AG1-121 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 962722 | AG1-121 E O1 | 50/50 | 44.72 MW | 44.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966821 | AG1-553 C O1 | 50/50 | 23.66 MW | 23.66 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 966822 | AG1-553 E O1 | 50/50 | 4.76 MW | 4.76 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965141 | AG1-379 C | 50/50 | 36.67 MW | 36.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965142 | AG1-379 E | 50/50 | 16.79 MW | 16.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965672 | AG1-435 E O1 | 50/50 | 31.26 MW | 31.26 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965931 | AG1-462 C O1 | 50/50 | 15.32 MW | 15.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 965932 | AG1-462 E O1 | 50/50 | 10.21 MW | 10.21 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 290021 | O50 E | 50/50 | 42.77 MW | 42.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 918052 | AA1-018 E OP | 50/50 | 64.27 MW | 64.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 926822 | AC1-168 E O1 | 50/50 | 10.02 MW | 10.02 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 927202 | AC1-214 E O1 | 50/50 | 10.86 MW | 10.86 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934051 | AD1-031 C O1 | 50/50 | 5.34 MW | 5.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 936292 | AD2-038 E O1 | 50/50 | 60.89 MW | 60.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942421 | AE2-255 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942422 | AE2-255 E O1 | 50/50 | 20.05 MW | 20.05 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 942652 | AE2-281 E O1 | 50/50 | 21.18 MW | 21.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946542 | AF1-318 E O1 | 50/50 | 37.91 MW | 37.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958481 | AF2-142 C | 50/50 | 44.33 MW | 44.33 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958482 | AF2-142 E | 50/50 | 29.55 MW | 29.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958491 | AF2-143 C | 50/50 | 44.34 MW | 44.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958492 | AF2-143 E | 50/50 | 29.56 MW | 29.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959351 | AF2-226 C | 50/50 | 9.82 MW | 9.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 959352 | AF2-226 E | 50/50 | 14.73 MW | 14.73 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960281 | AF2-319 C | 50/50 | 9.82 MW | 9.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 960282 | AF2-319 E | 50/50 | 14.73 MW | 14.73 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274677 | POWERTON ;5U | 50/50 | 64.38 MW | 64.38 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274678 | POWERTON ;6U | 50/50 | 64.56 MW | 64.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274701 | CORDOVA ;1S | 50/50 | 3.08 MW | 3.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274861 | TOP CROP ;1U | 50/50 | 1.54 MW | 1.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274862 | TOP CROP ;2U | 50/50 | 2.94 MW | 2.94 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 274891 | OTTER CRK;1U | 50/50 | 1.64 MW | 1.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293516 | O-009 E1 | Adder | 7.88 MW | 6.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293517 | O-009 E2 | Adder | 4.0 MW | 3.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293518 | O-009 E3 | Adder | 4.4 MW | 3.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293644 | O22 E1 | 50/50 | 40.08 MW | 40.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293645 | O22 E2 | 50/50 | 77.79 MW | 77.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293715 | O-029 E | Adder | 8.42 MW | 7.16 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293716 | O-029 E | Adder | 4.62 MW | 3.92 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293717 | O-029 E | Adder | 4.24 MW | 3.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 293771 | O-035 E | 50/50 | 10.64 MW | 10.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294401 | BSHIL;1U E | 50/50 | 15.9 MW | 15.9 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 294410 | BSHIL;2U E | 50/50 | 15.9 MW | 15.9 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 916211 | Z1-072 E | 50/50 | 8.05 MW | 8.05 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925581 | AC1-033 C | 50/50 | 2.6 MW | 2.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 925582 | AC1-033 E | 50/50 | 17.43 MW | 17.43 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 930761 | AB1-122 CT1 | Adder | -179.99 MW | -152.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938851 | AE1-113 C O1 | 50/50 | 17.64 MW | 17.64 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 938852 | AE1-113 E O1 | 50/50 | 62.55 MW | 62.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939321 | AE1-163 C O1 | 50/50 | 24.14 MW | 24.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 939322 | AE1-163 E O1 | 50/50 | 148.28 MW | 148.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946321 | AF1-296 C O1 | Adder | 3.45 MW | 2.93 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946322 | AF1-296 E O1 | Adder | 16.16 MW | 13.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 946541 | AF1-318 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 958342 | AF2-128 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990901 | L-005 E | 50/50 | 27.78 MW | 27.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.49 MW | 11.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.6 MW | 37.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.43 MW | 38.43 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.55 MW | 0.55 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.22 MW | 7.22 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.7 MW | 14.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.92 MW | 0.92 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L9806__R-S_+_345-L19601_B-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.08 MW | 4.08 MW |
| Details for AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 22.22 MW | 22.22 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 14.81 MW | 14.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 9.57 MW | 9.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 44.77 MW | 44.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966821 | AG1-553 C O1 | 50/50 | 23.71 MW | 23.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966822 | AG1-553 E O1 | 50/50 | 4.78 MW | 4.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965141 | AG1-379 C | 50/50 | 36.7 MW | 36.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965142 | AG1-379 E | 50/50 | 16.8 MW | 16.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 31.29 MW | 31.29 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965931 | AG1-462 C O1 | 50/50 | 15.35 MW | 15.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965932 | AG1-462 E O1 | 50/50 | 10.23 MW | 10.23 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 290021 | O50 E | 50/50 | 42.8 MW | 42.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 10.87 MW | 10.87 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.35 MW | 5.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936292 | AD2-038 E O1 | 50/50 | 60.91 MW | 60.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942421 | AE2-255 C O1 | 50/50 | 6.69 MW | 6.69 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942422 | AE2-255 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942652 | AE2-281 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.96 MW | 37.96 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958491 | AF2-143 C | 50/50 | 44.35 MW | 44.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958492 | AF2-143 E | 50/50 | 29.57 MW | 29.57 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274662 | QUAD CITI;1U | 50/50 | 15.52 MW | 15.52 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274677 | POWERTON ;5U | 50/50 | 64.4 MW | 64.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274678 | POWERTON ;6U | 50/50 | 64.59 MW | 64.59 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274701 | CORDOVA ;1S | 50/50 | 3.09 MW | 3.09 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293516 | O-009 E1 | Adder | 7.89 MW | 6.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293517 | O-009 E2 | Adder | 4.01 MW | 3.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293518 | O-009 E3 | Adder | 4.41 MW | 3.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293715 | O-029 E | Adder | 8.44 MW | 7.17 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293716 | O-029 E | Adder | 4.63 MW | 3.93 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293717 | O-029 E | Adder | 4.25 MW | 3.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293771 | O-035 E | 50/50 | 10.65 MW | 10.65 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.91 MW | 15.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.91 MW | 15.91 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 916211 | Z1-072 E | 50/50 | 8.06 MW | 8.06 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925581 | AC1-033 C | 50/50 | 2.61 MW | 2.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925582 | AC1-033 E | 50/50 | 17.45 MW | 17.45 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 930761 | AB1-122 CT1 | 50/50 | 395.13 MW | 395.13 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938851 | AE1-113 C O1 | 50/50 | 17.66 MW | 17.66 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938852 | AE1-113 E O1 | 50/50 | 62.6 MW | 62.6 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939321 | AE1-163 C O1 | 50/50 | 24.15 MW | 24.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939322 | AE1-163 E O1 | 50/50 | 148.34 MW | 148.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946321 | AF1-296 C O1 | Adder | 3.46 MW | 2.94 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946322 | AF1-296 E O1 | Adder | 16.2 MW | 13.77 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.11 MW | 8.11 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990901 | L-005 E | 50/50 | 27.81 MW | 27.81 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934101 | AD2-000 1 | 50/50 | 31.95 MW | 31.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951511 | J530 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951512 | J530 E | External Queue | 15.79 MW | 15.79 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951821 | J541 C | External Queue | 5.02 MW | 5.02 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951822 | J541 E | External Queue | 27.15 MW | 27.15 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.7 MW | 11.7 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.89 MW | 37.89 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.61 MW | 38.61 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.26 MW | 7.26 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.74 MW | 14.74 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.78 MW | 0.78 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| AB1-122 TAP1-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.11 MW | 4.11 MW |
| Details for 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961651 | AG1-005 C O1 | 50/50 | 22.22 MW | 22.22 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 961652 | AG1-005 E O1 | 50/50 | 14.81 MW | 14.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962721 | AG1-121 C O1 | 50/50 | 9.57 MW | 9.57 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 962722 | AG1-121 E O1 | 50/50 | 44.77 MW | 44.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966821 | AG1-553 C O1 | 50/50 | 23.71 MW | 23.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 966822 | AG1-553 E O1 | 50/50 | 4.78 MW | 4.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965141 | AG1-379 C | 50/50 | 36.7 MW | 36.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965142 | AG1-379 E | 50/50 | 16.8 MW | 16.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965671 | AG1-435 C O1 | 50/50 | 6.68 MW | 6.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965672 | AG1-435 E O1 | 50/50 | 31.29 MW | 31.29 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965911 | AG1-460 C | Adder | 0.84 MW | 0.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965912 | AG1-460 E | Adder | 1.26 MW | 1.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965931 | AG1-462 C O1 | 50/50 | 15.35 MW | 15.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 965932 | AG1-462 E O1 | 50/50 | 10.23 MW | 10.23 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 290021 | O50 E | 50/50 | 42.8 MW | 42.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926821 | AC1-168 C O1 | 50/50 | 1.49 MW | 1.49 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 926822 | AC1-168 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927201 | AC1-214 C O1 | 50/50 | 0.58 MW | 0.58 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 927202 | AC1-214 E O1 | 50/50 | 10.87 MW | 10.87 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934051 | AD1-031 C O1 | 50/50 | 5.35 MW | 5.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 934052 | AD1-031 E O1 | 50/50 | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936291 | AD2-038 C O1 | 50/50 | 13.01 MW | 13.01 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 936292 | AD2-038 E O1 | 50/50 | 60.91 MW | 60.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942421 | AE2-255 C O1 | 50/50 | 6.69 MW | 6.69 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942422 | AE2-255 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942481 | AE2-261 C | Adder | 12.56 MW | 10.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942482 | AE2-261 E | Adder | 8.38 MW | 7.12 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942651 | AE2-281 C O1 | 50/50 | 3.45 MW | 3.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 942652 | AE2-281 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946542 | AF1-318 E O1 | 50/50 | 37.96 MW | 37.96 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958491 | AF2-143 C | 50/50 | 44.35 MW | 44.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958492 | AF2-143 E | 50/50 | 29.57 MW | 29.57 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274662 | QUAD CITI;1U | 50/50 | 15.52 MW | 15.52 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274677 | POWERTON ;5U | 50/50 | 64.4 MW | 64.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274678 | POWERTON ;6U | 50/50 | 64.59 MW | 64.59 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274699 | CORDOVA ;1C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274700 | CORDOVA ;2C | 50/50 | 2.74 MW | 2.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274701 | CORDOVA ;1S | 50/50 | 3.09 MW | 3.09 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274848 | CAMPGROVE;RU | 50/50 | 0.99 MW | 0.99 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274849 | CRESCENT ;1U | 50/50 | 0.31 MW | 0.31 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274851 | PROVIDENC;RU | 50/50 | 0.32 MW | 0.32 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274877 | BISHOP HL;1U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274878 | BISHOP HL;2U | 50/50 | 0.68 MW | 0.68 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 274879 | MINONK ;1U | 50/50 | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293516 | O-009 E1 | Adder | 7.89 MW | 6.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293517 | O-009 E2 | Adder | 4.01 MW | 3.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293518 | O-009 E3 | Adder | 4.41 MW | 3.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293715 | O-029 E | Adder | 8.44 MW | 7.17 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293716 | O-029 E | Adder | 4.63 MW | 3.93 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293717 | O-029 E | Adder | 4.25 MW | 3.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 293771 | O-035 E | 50/50 | 10.65 MW | 10.65 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294401 | BSHIL;1U E | 50/50 | 15.91 MW | 15.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 294410 | BSHIL;2U E | 50/50 | 15.91 MW | 15.91 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 916211 | Z1-072 E | 50/50 | 8.06 MW | 8.06 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925581 | AC1-033 C | 50/50 | 2.61 MW | 2.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 925582 | AC1-033 E | 50/50 | 17.45 MW | 17.45 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 930761 | AB1-122 CT1 | Adder | -179.87 MW | -152.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938851 | AE1-113 C O1 | 50/50 | 17.66 MW | 17.66 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 938852 | AE1-113 E O1 | 50/50 | 62.6 MW | 62.6 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939321 | AE1-163 C O1 | 50/50 | 24.15 MW | 24.15 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 939322 | AE1-163 E O1 | 50/50 | 148.34 MW | 148.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946321 | AF1-296 C O1 | Adder | 3.46 MW | 2.94 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946322 | AF1-296 E O1 | Adder | 16.2 MW | 13.77 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 946541 | AF1-318 C O1 | 50/50 | 8.11 MW | 8.11 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957381 | AF2-032 C | Adder | 0.96 MW | 0.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957382 | AF2-032 E | Adder | 0.45 MW | 0.38 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957751 | AF2-069 C | 50/50 | 0.4 MW | 0.4 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957752 | AF2-069 E | 50/50 | 1.28 MW | 1.28 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957761 | AF2-070 C | 50/50 | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 957762 | AF2-070 E | 50/50 | 2.71 MW | 2.71 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958341 | AF2-128 C O1 | 50/50 | 2.07 MW | 2.07 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 958342 | AF2-128 E O1 | 50/50 | 9.7 MW | 9.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990901 | L-005 E | 50/50 | 27.81 MW | 27.81 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951031 | J344 C | External Queue | 2.36 MW | 2.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951032 | J344 E | External Queue | 7.09 MW | 7.09 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951511 | J530 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951512 | J530 E | External Queue | 15.79 MW | 15.79 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951631 | J456 C | External Queue | 4.27 MW | 4.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951632 | J456 E | External Queue | 23.08 MW | 23.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951821 | J541 C | External Queue | 5.02 MW | 5.02 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951822 | J541 E | External Queue | 27.15 MW | 27.15 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951841 | J555 C | External Queue | 1.61 MW | 1.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 951842 | J555 E | External Queue | 8.72 MW | 8.72 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952651 | J756 C | External Queue | 3.95 MW | 3.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952652 | J756 E | External Queue | 21.35 MW | 21.35 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952871 | J757 C | External Queue | 5.04 MW | 5.04 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 952872 | J757 E | External Queue | 27.24 MW | 27.24 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953201 | J715 C | External Queue | 1.7 MW | 1.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953202 | J715 E | External Queue | 9.18 MW | 9.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 953951 | J859 | External Queue | 25.67 MW | 25.67 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954702 | J844 E | External Queue | 29.27 MW | 29.27 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954721 | J750 C | External Queue | 1.82 MW | 1.82 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954722 | J750 E | External Queue | 9.84 MW | 9.84 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954981 | J974 C | External Queue | 14.97 MW | 14.97 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 954982 | J974 E | External Queue | 80.98 MW | 80.98 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955711 | J1055 C | External Queue | 4.88 MW | 4.88 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 955712 | J1055 E | External Queue | 26.41 MW | 26.41 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956151 | J1102 | External Queue | 7.0 MW | 7.0 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 956411 | J1131 | External Queue | 8.75 MW | 8.75 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990051 | J1200 | External Queue | 3.34 MW | 3.34 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990351 | J1289 C | External Queue | 4.8 MW | 4.8 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990352 | J1289 E | External Queue | 25.95 MW | 25.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 990751 | J1383 | External Queue | 35.7 MW | 35.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991091 | J1477 | External Queue | 4.37 MW | 4.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991191 | J1610 | External Queue | 7.16 MW | 7.16 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991216 | J1653 | External Queue | 34.08 MW | 34.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991276 | J1725 C | External Queue | 3.54 MW | 3.54 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991277 | J1725 E | External Queue | 19.18 MW | 19.18 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991301 | J1755 C | External Queue | 3.48 MW | 3.48 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | 991302 | J1755 E | External Queue | 18.83 MW | 18.83 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.95 MW | 0.95 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.7 MW | 11.7 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.89 MW | 37.89 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 38.61 MW | 38.61 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.56 MW | 0.56 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.26 MW | 7.26 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.37 MW | 0.37 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 14.74 MW | 14.74 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.78 MW | 0.78 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 7TAZEWELL-AB1-122 TAP1 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L0301__B-S_+_345-L0303__R-S-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.11 MW | 4.11 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| b3775.11 | Upgrade the limiting element at Stillwell substation to increase the rating of the Stillwell-Dumont. | $0 | |
| b3775.7 | Upgrade limiting element at Dumont substation on the Stillwell-Dumont 345 kV line. | $0 | |
| b3775.6 | Perform sag study mitigation work on the Dumont-Stillwell 345 kV line | $0 | |
| n5769.2 | Replace two Dumont 3000A Non-Oil breakers. | $2,000,000 | |
| (TBD) | Rebuild NIPS portion of line and upgrade substation conductor (MISO - Upgrade #2) | $8,000,000 | |
| n5769.4 | Rebuild/Recondutor 8.6 miles of ACSR ~ 954 ~ 45/7 ~ RAIL conductor to mitigate the overload | $17,200,000 | |
| n5769.3 | Replace 11 jumpers/risers at Dumont substation | $275,000 | |
| n5769.5 | Replace 4 Dumont switches (3000 A). | $2,400,000 | |
| (TBD) | Upgrade transmission conductor and conductor drop.. (MISO - Upgrade #3) | $6,500,000 | |
| (TBD) | Upgrade circuit breakers and MODs at Stillwell. (MISO Upgrade #4) | $1,500,000 | |
| n5769.6 | An engineering study will need to be conducted to determine if the Dumont Relay Compliance Trip limit settings can be adjusted | $600,000 | |
| b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
| b3775.10 | Sag study on the Olive – University Park | $0 | |
| s2509 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| n7925.1 | Reconductor/rebuild 0.82 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 5 | $1,640,000 | |
| n7925.2 | Reconductor/rebuild 1 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 6 | $2,000,000 | |
| n7925.3 | Replace two sullivan 3000A Wavetrap | $400,000 | |
| n7925.4 | Replace three 2-2000 AAC 91 Str | $300,000 | |
| b3775.9 | Upgrade existing terminal equipment (substation conductor) at Green Acres on the St. John to Green Acres 345 kV lin | $0 | |
| b3775.8 | Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line | $0 | |
| b3775.3 | Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete | $0 | |
| b3775.2 | Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles). | $0 | |
| n8375 | AB1-122 - Tazewell 345 kV Line Sag Mitigation | $39,900,000 | |
| (TBD) | MISO review required. | $0 | |
| n5324 | Re-conductor the line segment - Dresden - AB1-122 345 kV line | $4,000,000 | |
| n5324.1 | Dresden - AB1-122 345 kV line - Re-conductor the line segment and upgrade relay package. | $5,000,000 | |
| n6639.1 | Replace station conductor at TSS111 EJ, replace MOD. Relay upgrades, re-conductor part of the line. | $22,300,000 | |
| n6279 | TSS 116 Replace 345 kV Circuit Breaker | $3,200,000 | |
| n8389 | TSS 116 Replace Station Conductor | $1,000,000 | |
| n8427 | Replace Nelson Transformer 94 Station Conductor Leads. | $100,000 | |
| n8373 | Plano - Install 3rd Auto Transformer at TSS 167 Plano. | $20,000,000 | |
| n5808 | AEP: eliminate the Eugene stuck breaker contingency. (AMIL upgrade will not be required) | $3,424,014 | |
| s2929 | Move 345 kV line 11126 (Electric Junction-Wayne) to Bus 6 and install 345 kV Bus Tie 5-6 CB. | $0 | |
| n8392 | install a new 345kV bus tie circuit breaker at TSS 167 Plano (BT CB 8-14) | $6,000,000 | |
| b3711 | Install 345 kV bus tie 5-20 circuit breaker in the ring at Dresden station in series with existing bus tie 5-6. | $4,260,000 | |
| n8264 | Add 345 kV circuit breaker at Wayne (BT5-6). | $10,000,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-462 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.