AG1-444 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:57
Chinquapin 230 kV
80.0 MW Capacity / 80.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-444 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing Storage generating facility located in the Dominion zone — Edgecombe County, North Carolina. This project is an increase to the Interconnection Customer's AG1-439 project, which will share the same point of interconnection. The AG1-444 queue position is a 80.0 MW uprate (80.0 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 330.0 MW with 230 MW of this output being recognized by PJM as Capacity. The proposed in-service date for this project is Sunday, December 31, 2023. This study does not imply a TO commitment to this in-service date.
Project Information | |
Queue Number | AG1-444 |
Project Name | Chinquapin 230 kV |
Developer Name | RWE Solar Development, LLC |
State | North Carolina |
County | Edgecombe |
Transmission Owner | Dominion |
MFO | 330.0 MW |
MWE | 80.0 MW |
MWC | 80.0 MW |
Fuel Type | Storage |
Basecase Study Year | 2024 |
Point of Interconnection
AG1-444 "Chinquapin 230 kV" will interconnect with the Dominion transmission system as an uprate to AG1- 439, sharing the POI and Attachment Facilities.
Summer Peak Analysis
The Queue Project was evaluated as a 80.0 MW (Capacity 80.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Summer Peak Analysis | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
DVP |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line
313725 to 314563 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 180.14 % | 183.71 % | 375.06 | B | 689.03 | 13.2 | |
DVP |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line
313725 to 314563 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 177.47 % | 181.04 % | 375.06 | B | 679.01 | 13.2 | |
DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
DVP_P1-2: LN 2092
CONTINGENCY 'DVP_P1-2: LN 2092' OPEN BRANCH FROM BUS 313714 TO BUS 314662 CKT 1 /*6PERQUIMANS 230.0 - 6S HERTFORD 230.0 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1 /*6WINFALL 230.0 - 6S HERTFORD 230.0 OPEN BUS 314662 /*6S HERTFORD 230.0 END |
Single | AC | 165.67 % | 168.62 % | 571.52 | B | 963.67 | 16.46 | |
DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
DVP_P1-2: LN 2131
CONTINGENCY 'DVP_P1-2: LN 2131' OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1 /*6PERQUIMANS 230.0 - 6WALBMRL 230.0 OPEN BRANCH FROM BUS 313885 TO BUS 314637 CKT 1 /*6WALBMRL 230.0 - 6EDENTON 230.0 OPEN BRANCH FROM BUS 314203 TO BUS 314637 CKT 1 /*6MACKEYS 230.0 - 6EDENTON 230.0 OPEN BUS 313885 /*6WALBMRL 230.0 OPEN BUS 314637 /*6EDENTON 230.0 END |
Single | AC | 163.71 % | 166.65 % | 571.52 | B | 952.43 | 16.47 | |
DVP |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line
314583 to 313725 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 162.88 % | 166.45 % | 375.06 | B | 624.29 | 13.23 | |
DVP |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line
314583 to 313725 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 160.22 % | 163.78 % | 375.06 | B | 614.26 | 13.23 | |
DVP |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
314575 to 314537 ckt 1 |
DVP_P1-2: LN 2092
CONTINGENCY 'DVP_P1-2: LN 2092' OPEN BRANCH FROM BUS 313714 TO BUS 314662 CKT 1 /*6PERQUIMANS 230.0 - 6S HERTFORD 230.0 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1 /*6WINFALL 230.0 - 6S HERTFORD 230.0 OPEN BUS 314662 /*6S HERTFORD 230.0 END |
Single | AC | 156.9 % | 159.83 % | 571.52 | B | 913.48 | 16.46 | |
DVP |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
314575 to 314537 ckt 1 |
DVP_P1-2: LN 2131
CONTINGENCY 'DVP_P1-2: LN 2131' OPEN BRANCH FROM BUS 313714 TO BUS 313885 CKT 1 /*6PERQUIMANS 230.0 - 6WALBMRL 230.0 OPEN BRANCH FROM BUS 313885 TO BUS 314637 CKT 1 /*6WALBMRL 230.0 - 6EDENTON 230.0 OPEN BRANCH FROM BUS 314203 TO BUS 314637 CKT 1 /*6MACKEYS 230.0 - 6EDENTON 230.0 OPEN BUS 313885 /*6WALBMRL 230.0 OPEN BUS 314637 /*6EDENTON 230.0 END |
Single | AC | 154.96 % | 157.89 % | 571.52 | B | 902.37 | 16.47 | |
DVP |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line
314583 to 314561 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 152.17 % | 153.66 % | 375.06 | B | 576.31 | 5.61 | |
DVP |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line
314583 to 314561 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 152.13 % | 153.63 % | 375.06 | B | 576.2 | 5.61 | |
DVP |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line
313725 to 314563 ckt 1 |
Base Case | Single | AC | 145.34 % | 148.16 % | 375.06 | A | 555.7 | 10.59 | |
DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 142.8 % | 144.79 % | 678.68 | B | 982.69 | 13.74 | |
DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 142.95 % | 144.7 % | 678.68 | B | 982.08 | 13.74 | |
DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 141.23 % | 143.22 % | 678.68 | B | 972.04 | 13.74 | |
DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 141.38 % | 143.13 % | 678.68 | B | 971.37 | 13.74 | |
DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 135.0 % | 137.11 % | 678.68 | B | 930.54 | 13.74 | |
DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 133.43 % | 135.53 % | 678.68 | B | 919.79 | 13.74 | |
DVP |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line
314583 to 313725 ckt 1 |
Base Case | Single | AC | 128.2 % | 131.03 % | 375.06 | A | 491.44 | 10.62 | |
DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
Base Case | Single | AC | 120.28 % | 121.9 % | 678.68 | A | 827.29 | 10.93 | |
DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
Base Case | Single | AC | 117.07 % | 118.2 % | 678.68 | A | 802.19 | 10.94 | |
DVP |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line
314569 to 314575 ckt 1 |
Base Case | Single | AC | 113.35 % | 115.64 % | 571.52 | A | 660.92 | 12.9 | |
DVP |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
314662 to 314651 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 112.64 % | 114.34 % | 733.2 | B | 838.36 | 11.9 | |
DVP |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line
313714 to 314662 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 111.92 % | 113.63 % | 733.2 | B | 833.14 | 11.9 | |
DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
Base Case | Single | AC | 110.64 % | 112.28 % | 678.68 | A | 762.04 | 10.94 | |
DVP |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
314662 to 314651 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 110.94 % | 112.64 % | 733.2 | B | 825.86 | 11.9 | |
DVP |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line
313714 to 314662 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 110.22 % | 111.92 % | 733.2 | B | 820.62 | 11.9 | |
DVP |
6EDENTON-6WALBMRL 230.0 kV Ckt 1 line
314637 to 313885 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 108.76 % | 110.47 % | 733.2 | B | 809.93 | 11.91 | |
DVP |
6WALBMRL-6PERQUIMANS 230.0 kV Ckt 1 line
313885 to 313714 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 108.75 % | 110.45 % | 733.2 | B | 809.86 | 11.91 | |
DVP |
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line
314203 to 314637 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 108.64 % | 110.33 % | 733.2 | B | 808.98 | 11.91 | |
DVP |
6EDENTON-6WALBMRL 230.0 kV Ckt 1 line
314637 to 313885 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 107.07 % | 108.76 % | 733.2 | B | 797.46 | 11.91 | |
DVP |
6WALBMRL-6PERQUIMANS 230.0 kV Ckt 1 line
313885 to 313714 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 107.06 % | 108.75 % | 733.2 | B | 797.39 | 11.91 | |
DVP |
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line
314203 to 314637 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 106.94 % | 108.63 % | 733.2 | B | 796.5 | 11.91 | |
DVP |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line
314575 to 314537 ckt 1 |
Base Case | Single | AC | 104.81 % | 107.09 % | 571.52 | A | 612.03 | 12.9 | |
CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
EXT_WILSON230TT-WILSON115TT-230-115-#1-&BUS
CONTINGENCY 'EXT_WILSON230TT-WILSON115TT-230-115-#1-&BUS' OPEN BRANCH FROM BUS 304222 TO BUS 304228 CKT 1 /*6ROCKYMT230T 230.0 - 6WILSON230 T 230.0 OPEN BRANCH FROM BUS 304228 TO BUS 304229 CKT 1 /*6WILSON230 T 230.0 - 6PA-FARMVILL 230.0 OPEN BRANCH FROM BUS 304228 TO BUS 304230 CKT 1 /*6WILSON230 T 230.0 - 3WILSON115 T 115.0 END |
Single | AC | 103.5 % | 106.56 % | 478.0 | B | 509.38 | 15.07 | |
DVP |
6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line
314638 to 314647 ckt 1 |
DVP_P1-2: LN 247
CONTINGENCY 'DVP_P1-2: LN 247' OPEN BRANCH FROM BUS 313713 TO BUS 314648 CKT 1 /*6SWAMP 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 OPEN BUS 314648 /*6SUNBURY 230.0 END |
Single | AC | 105.46 % | 106.69 % | 571.52 | B | 609.75 | 6.84 | |
DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P1-2: LN 249
CONTINGENCY 'DVP_P1-2: LN 249' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 END |
Single | AC | 103.76 % | 104.72 % | 441.8 | B | 462.64 | 4.52 | |
DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P1-2: LN 249
CONTINGENCY 'DVP_P1-2: LN 249' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 END |
Single | AC | 103.72 % | 104.67 % | 441.8 | B | 462.45 | 4.52 | |
CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P1-2: LN 2177
CONTINGENCY 'DVP_P1-2: LN 2177' OPEN BRANCH FROM BUS 313701 TO BUS 314609 CKT 1 /*6CHINQUAPIN 230.0 - 6TARBORO 230.0 OPEN BRANCH FROM BUS 314608 TO BUS 314609 CKT 2 /*3TARBORO 115.0 - 6TARBORO 230.0 END |
Single | AC | 96.9 % | 103.71 % | 478.0 | B | 495.74 | 33.53 | |
CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 100.16 % | 103.52 % | 478.0 | B | 494.82 | 16.28 | |
CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P1-2: LN 2167
CONTINGENCY 'DVP_P1-2: LN 2167' OPEN BRANCH FROM BUS 313845 TO BUS 314564 CKT 1 /*6HATHAWAY 230.0 - 6EDGECOM 230.0 END |
Single | AC | 96.19 % | 103.0 % | 478.0 | B | 492.34 | 33.53 | |
CPLE/DVP |
6NASH-6PA-RMOUNT#4 230.0 kV Ckt 1 line
314591 to 304226 ckt 1 |
DVP_P1-2: LN 2058
CONTINGENCY 'DVP_P1-2: LN 2058' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 END |
Single | AC | 97.63 % | 102.5 % | 478.0 | B | 489.97 | 23.76 | |
CPLE/DVP |
6HATHAWAY-6ROCKYMT230T 230.0 kV Ckt 1 line
313845 to 304222 ckt 1 |
DVP_P1-2: LN 2181
CONTINGENCY 'DVP_P1-2: LN 2181' OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1 /*6PA-RMOUNT#4 230.0 - 6NASH 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1 /*6HATHAWAY 230.0 - 6NASH 230.0 OPEN BUS 304226 /*6PA-RMOUNT#4 230.0 OPEN BUS 314591 /*6NASH 230.0 END |
Single | AC | 97.36 % | 102.01 % | 478.0 | B | 487.63 | 22.68 | |
CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P1-2: LN 2092
CONTINGENCY 'DVP_P1-2: LN 2092' OPEN BRANCH FROM BUS 313714 TO BUS 314662 CKT 1 /*6PERQUIMANS 230.0 - 6S HERTFORD 230.0 OPEN BRANCH FROM BUS 314651 TO BUS 314662 CKT 1 /*6WINFALL 230.0 - 6S HERTFORD 230.0 OPEN BUS 314662 /*6S HERTFORD 230.0 END |
Single | AC | 98.68 % | 101.87 % | 478.0 | B | 486.94 | 15.48 | |
DVP |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
314662 to 314651 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 99.1 % | 100.44 % | 733.2 | B | 736.4 | 9.33 | |
DVP |
6ELIZ CT-6SHAWBRO 230.0 kV Ckt 1 line
314638 to 314647 ckt 1 |
DVP_P4-2: 246T247
CONTINGENCY 'DVP_P4-2: 246T247' OPEN BRANCH FROM BUS 313713 TO BUS 314648 CKT 1 /*6SWAMP 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 OPEN BUS 314648 /*6SUNBURY 230.0 END |
Breaker | AC | 185.6 % | 187.34 % | 699.0 | C | 1309.48 | 10.11 | |
CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P4-2: 246T247
CONTINGENCY 'DVP_P4-2: 246T247' OPEN BRANCH FROM BUS 313713 TO BUS 314648 CKT 1 /*6SWAMP 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 OPEN BUS 314648 /*6SUNBURY 230.0 END |
Breaker | AC | 159.29 % | 162.67 % | 478.0 | B | 777.54 | 16.78 | |
CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P4-2: 2058T2167
CONTINGENCY 'DVP_P4-2: 2058T2167' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314564 CKT 1 /*6HATHAWAY 230.0 - 6EDGECOM 230.0 END |
Breaker | AC | 138.76 % | 145.53 % | 478.0 | B | 695.63 | 33.55 | |
DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 141.56 % | 142.44 % | 541.0 | C | 770.61 | 7.28 | |
DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 141.47 % | 142.35 % | 541.0 | C | 770.11 | 7.28 | |
DVP |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line
314662 to 314651 ckt 1 |
DVP_P4-2: 24642
CONTINGENCY 'DVP_P4-2: 24642' OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3 /*3SUFFOLK 115.0 - 6SUFFOLK 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2 /*6SUFFOLK 230.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Breaker | AC | 136.31 % | 137.76 % | 897.0 | C | 1235.74 | 11.85 | |
DVP |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line
313714 to 314662 ckt 1 |
DVP_P4-2: 24642
CONTINGENCY 'DVP_P4-2: 24642' OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3 /*3SUFFOLK 115.0 - 6SUFFOLK 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2 /*6SUFFOLK 230.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Breaker | AC | 135.7 % | 137.15 % | 897.0 | C | 1230.24 | 11.85 | |
DVP |
6EDENTON-6WALBMRL 230.0 kV Ckt 1 line
314637 to 313885 ckt 1 |
DVP_P4-2: 24642
CONTINGENCY 'DVP_P4-2: 24642' OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3 /*3SUFFOLK 115.0 - 6SUFFOLK 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2 /*6SUFFOLK 230.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Breaker | AC | 119.69 % | 121.07 % | 897.0 | C | 1085.97 | 11.86 | |
DVP |
6WALBMRL-6PERQUIMANS 230.0 kV Ckt 1 line
313885 to 313714 ckt 1 |
DVP_P4-2: 24642
CONTINGENCY 'DVP_P4-2: 24642' OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3 /*3SUFFOLK 115.0 - 6SUFFOLK 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2 /*6SUFFOLK 230.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Breaker | AC | 119.68 % | 121.06 % | 897.0 | C | 1085.92 | 11.86 | |
DVP |
6MACKEYS-6EDENTON 230.0 kV Ckt 1 line
314203 to 314637 ckt 1 |
DVP_P4-2: 24642
CONTINGENCY 'DVP_P4-2: 24642' OPEN BRANCH FROM BUS 314536 TO BUS 314537 CKT 3 /*3SUFFOLK 115.0 - 6SUFFOLK 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314537 TO BUS 314928 CKT 2 /*6SUFFOLK 230.0 - 8SUFFOLK 500.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 END |
Breaker | AC | 119.58 % | 120.96 % | 897.0 | C | 1085.04 | 11.86 | |
DVP |
6CARSON-6POE 230.0 kV Ckt 1 line
314282 to 314331 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 108.93 % | 109.76 % | 830.0 | C | 910.99 | 8.67 | |
DVP |
3POPLR C-3EVERETS 115.0 kV Ckt 1 line
314596 to 314573 ckt 1 |
DVP_P4-2: 203462
CONTINGENCY 'DVP_P4-2: 203462' OPEN BRANCH FROM BUS 314568 TO BUS 314569 CKT 2 /*3EARLEYS 115.0 - 6EARLEYS 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 965690 CKT 1 /*6EARLEYS 230.0 - AG1-437 TAP 230.0 END |
Breaker | AC | 99.97 % | 101.64 % | 349.0 | C | 354.72 | 5.47 | |
DVP |
3TRWBRDG2-3POPLR C 115.0 kV Ckt 1 line
314614 to 314596 ckt 1 |
DVP_P4-2: 203462
CONTINGENCY 'DVP_P4-2: 203462' OPEN BRANCH FROM BUS 314568 TO BUS 314569 CKT 2 /*3EARLEYS 115.0 - 6EARLEYS 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 965690 CKT 1 /*6EARLEYS 230.0 - AG1-437 TAP 230.0 END |
Breaker | AC | 99.33 % | 101.0 % | 350.0 | C | 353.49 | 5.47 | |
CPLE/DVP |
3BTLEBRO-3ROCKYMT115T 115.0 kV Ckt 1 line
314554 to 304223 ckt 1 |
DVP_P7-1: LN 2058-2181
CONTINGENCY 'DVP_P7-1: LN 2058-2181' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1 /*6PA-RMOUNT#4 230.0 - 6NASH 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1 /*6HATHAWAY 230.0 - 6NASH 230.0 OPEN BUS 304226 /*6PA-RMOUNT#4 230.0 OPEN BUS 314591 /*6NASH 230.0 END |
Tower | AC | 289.72 % | 296.58 % | 164.0 | B | 486.38 | 11.38 | |
CPLE/DVP |
6EVERETS-6GREENVILE T 230.0 kV Ckt 1 line
314574 to 304451 ckt 1 |
DVP_P7-1: LN 2058-2181
CONTINGENCY 'DVP_P7-1: LN 2058-2181' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1 /*6PA-RMOUNT#4 230.0 - 6NASH 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1 /*6HATHAWAY 230.0 - 6NASH 230.0 OPEN BUS 304226 /*6PA-RMOUNT#4 230.0 OPEN BUS 314591 /*6NASH 230.0 END |
Tower | AC | 159.61 % | 163.12 % | 478.0 | B | 779.72 | 20.76 | |
DVP |
3HATHAWAY-3BTLEBRO 115.0 kV Ckt 1 line
313844 to 314554 ckt 1 |
DVP_P7-1: LN 2058-2181
CONTINGENCY 'DVP_P7-1: LN 2058-2181' OPEN BRANCH FROM BUS 304222 TO BUS 313845 CKT 1 /*6ROCKYMT230T 230.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 304226 TO BUS 314591 CKT 1 /*6PA-RMOUNT#4 230.0 - 6NASH 230.0 OPEN BRANCH FROM BUS 313844 TO BUS 313845 CKT 2 /*3HATHAWAY 115.0 - 6HATHAWAY 230.0 OPEN BRANCH FROM BUS 313845 TO BUS 314591 CKT 1 /*6HATHAWAY 230.0 - 6NASH 230.0 OPEN BUS 304226 /*6PA-RMOUNT#4 230.0 OPEN BUS 314591 /*6NASH 230.0 END |
Tower | AC | 105.14 % | 109.55 % | 301.0 | C | 329.73 | 13.91 | |
AEP |
05EDAN 1-05DANVL2 138.0 kV Ckt 1 line
242631 to 242620 ckt 1 |
AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1
CONTINGENCY 'AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1' OPEN BRANCH FROM BUS 242520 TO BUS 242514 CKT 1 /*05J.FERR 500.0 - 05J.FERR 765.0 END |
Single | AC | 119.7 % | 120.99 % | 402.0 | B | 486.38 | 5.77 | |
AEP |
05EDAN 1-05DANVL2 138.0 kV Ckt 1 line
242631 to 242620 ckt 1 |
AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1
CONTINGENCY 'AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1' OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1 /*05J.FERR 500.0 - 8ANTIOCH 500.0 END |
Single | AC | 119.65 % | 120.94 % | 402.0 | B | 486.19 | 5.77 | |
AEP |
05EDAN 1-05DANVL2 138.0 kV Ckt 1 line
242631 to 242620 ckt 1 |
AEP_P4_#11112_05J.FERR 765_A1
CONTINGENCY 'AEP_P4_#11112_05J.FERR 765_A1' OPEN BRANCH FROM BUS 242511 TO BUS 242514 CKT 1 /*05BROADF 765.0 - 05J.FERR 765.0 OPEN BRANCH FROM BUS 242514 TO BUS 242520 CKT 1 /*05J.FERR 765.0 - 05J.FERR 500.0 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1 /*05J.FERR 500.0 - 8ANTIOCH 500.0 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB /*05BROADF 138.0 - 05BROADX 138.0 END |
Breaker | AC | 157.3 % | 158.46 % | 402.0 | B | 637.0 | 5.6 | |
AEP |
AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line
941430 to 242544 ckt 1 |
AEP_P4_#11112_05J.FERR 765_A1
CONTINGENCY 'AEP_P4_#11112_05J.FERR 765_A1' OPEN BRANCH FROM BUS 242511 TO BUS 242514 CKT 1 /*05BROADF 765.0 - 05J.FERR 765.0 OPEN BRANCH FROM BUS 242514 TO BUS 242520 CKT 1 /*05J.FERR 765.0 - 05J.FERR 500.0 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1 /*05J.FERR 500.0 - 8ANTIOCH 500.0 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB /*05BROADF 138.0 - 05BROADX 138.0 END |
Breaker | AC | 121.19 % | 122.24 % | 388.0 | B | 474.31 | 4.8 |
Details for 6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.0 MW | 1.0 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.51 MW | 0.51 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.06 MW | 2.06 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.06 MW | 2.06 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 4.21 MW | 4.21 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.12 MW | 2.12 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 2.08 MW | 2.08 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 1.4 MW | 1.4 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 9.58 MW | 9.58 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 9.58 MW | 9.58 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 24.76 MW | 24.76 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 3.28 MW | 3.28 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 3.28 MW | 3.28 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.59 MW | 5.59 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.59 MW | 5.59 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.2 MW | 13.2 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 1.9 MW | 1.9 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 1.9 MW | 1.9 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.26 MW | 1.26 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.41 MW | 0.41 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 1.41 MW | 1.41 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.7 MW | 8.7 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.7 MW | 8.7 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.47 MW | 4.47 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.77 MW | 2.77 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.1 MW | 2.1 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.86 MW | 6.86 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 45.28 MW | 45.28 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 6.42 MW | 6.42 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.15 MW | 2.15 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 8.66 MW | 8.66 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 9.27 MW | 9.27 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.66 MW | 15.66 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 40.99 MW | 40.99 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.44 MW | 1.44 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 2.98 MW | 2.98 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.47 MW | 5.47 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.71 MW | 6.71 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.49 MW | 1.49 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 1.57 MW | 1.57 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 1.86 MW | 1.86 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 4.62 MW | 4.62 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.6 MW | 0.6 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.58 MW | 1.58 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 30.75 MW | 30.75 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.94 MW | 0.94 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.09 MW | 7.09 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 9.15 MW | 9.15 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.2 MW | 4.2 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.64 MW | 4.64 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 14.34 MW | 14.34 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 9.98 MW | 9.98 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 7.86 MW | 7.86 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 0.71 MW | 0.71 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.86 MW | 6.86 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.14 MW | 1.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 1.27 MW | 1.27 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 0.72 MW | 0.72 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315611 | 6Z1-036WIND | 80/20 | 0.22 MW | 0.22 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.63 MW | 3.63 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.63 MW | 3.63 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.45 MW | 0.45 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.54 MW | 7.54 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.49 MW | 8.49 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 14.36 MW | 14.36 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.59 MW | 12.59 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.79 MW | 1.79 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.95 MW | 0.95 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.07 MW | 2.07 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.97 MW | 33.97 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.79 MW | 10.79 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.34 MW | 11.34 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.14 MW | 3.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.67 MW | 2.67 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.54 MW | 1.54 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.14 MW | 2.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
Details for 6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.0 MW | 1.0 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.51 MW | 0.51 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.06 MW | 2.06 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.06 MW | 2.06 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 4.21 MW | 4.21 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.12 MW | 2.12 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 2.08 MW | 2.08 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 1.4 MW | 1.4 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 9.58 MW | 9.58 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 9.58 MW | 9.58 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 24.76 MW | 24.76 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 3.28 MW | 3.28 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 3.28 MW | 3.28 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.59 MW | 5.59 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.59 MW | 5.59 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.2 MW | 13.2 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 1.9 MW | 1.9 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 1.9 MW | 1.9 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.26 MW | 1.26 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.41 MW | 0.41 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.41 MW | 1.41 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.7 MW | 8.7 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.7 MW | 8.7 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.47 MW | 4.47 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.77 MW | 2.77 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.1 MW | 2.1 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.86 MW | 6.86 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 45.28 MW | 45.28 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 6.42 MW | 6.42 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.15 MW | 2.15 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 8.66 MW | 8.66 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 9.27 MW | 9.27 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.66 MW | 15.66 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 40.99 MW | 40.99 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.44 MW | 1.44 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 2.98 MW | 2.98 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 0.39 MW | 0.39 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.47 MW | 5.47 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.71 MW | 6.71 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.49 MW | 1.49 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.57 MW | 1.57 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 1.86 MW | 1.86 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 4.62 MW | 4.62 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.6 MW | 0.6 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.58 MW | 1.58 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 30.75 MW | 30.75 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.94 MW | 0.94 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.09 MW | 7.09 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 9.15 MW | 9.15 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940491 | AE2-034 C | 80/20 | 4.2 MW | 4.2 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.64 MW | 4.64 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 14.34 MW | 14.34 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957531 | AF2-047 C | 80/20 | 9.98 MW | 9.98 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 7.86 MW | 7.86 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315115 | 1S HAMPT1 | 80/20 | 0.71 MW | 0.71 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.86 MW | 6.86 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.14 MW | 1.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.27 MW | 1.27 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.72 MW | 0.72 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315611 | 6Z1-036WIND | 80/20 | 0.22 MW | 0.22 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.63 MW | 3.63 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.63 MW | 3.63 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.45 MW | 0.45 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.54 MW | 7.54 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.49 MW | 8.49 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 14.36 MW | 14.36 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.59 MW | 12.59 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.79 MW | 1.79 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315614 | AA2-178 C | 80/20 | 0.95 MW | 0.95 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.07 MW | 2.07 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.97 MW | 33.97 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.79 MW | 10.79 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.34 MW | 11.34 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.14 MW | 3.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.67 MW | 2.67 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.54 MW | 1.54 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.14 MW | 2.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 961671 | AG1-007 C | 80/20 | 1.16 MW | 1.16 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 961941 | AG1-037 C | 80/20 | 0.86 MW | 0.86 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 962331 | AG1-082 C | 80/20 | 3.45 MW | 3.45 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 962341 | AG1-083 C | 80/20 | 3.45 MW | 3.45 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 963301 | AG1-179 C | 80/20 | 3.08 MW | 3.08 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 963311 | AG1-180 | 80/20 | 1.5 MW | 1.5 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 964241 | AG1-285 C O1 | 80/20 | 4.25 MW | 4.25 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 964801 | AG1-343 C | 80/20 | 4.72 MW | 4.72 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 966801 | AG1-551 C | 80/20 | 3.84 MW | 3.84 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 966811 | AG1-552 C | 80/20 | 2.05 MW | 2.05 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965291 | AG1-394 C | 80/20 | 1.49 MW | 1.49 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965591 | AG1-427 C | 80/20 | 4.01 MW | 4.01 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965601 | AG1-428 C O2 | 80/20 | 2.57 MW | 2.57 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965691 | AG1-437 C O1 | 80/20 | 22.13 MW | 22.13 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965701 | AG1-438 C O1 | 80/20 | 22.13 MW | 22.13 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965711 | AG1-439 C O1 | 80/20 | 30.86 MW | 30.86 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965721 | AG1-440 C | 80/20 | 4.3 MW | 4.3 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965731 | AG1-441 C | 80/20 | 4.3 MW | 4.3 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965741 | AG1-442 O1 | 80/20 | 12.91 MW | 12.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965751 | AG1-443 O1 | 80/20 | 12.91 MW | 12.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965761 | AG1-444 O1 | 80/20 | 16.46 MW | 16.46 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965771 | AG1-445 | 80/20 | 2.49 MW | 2.49 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965781 | AG1-446 | 80/20 | 2.49 MW | 2.49 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 966621 | AG1-532 C | 80/20 | 0.9 MW | 0.9 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 313506 | AB1-173 C OP | 80/20 | 5.39 MW | 5.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 313719 | 3CHESTNUT | 80/20 | 1.31 MW | 1.31 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314572 | 3EMPORIA | 80/20 | 0.29 MW | 0.29 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314582 | 3KELFORD | 80/20 | 0.65 MW | 0.65 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315126 | 1ROARAP2 | 80/20 | 1.39 MW | 1.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315128 | 1ROARAP4 | 80/20 | 1.33 MW | 1.33 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315131 | 1EDGECMA | 80/20 | 7.77 MW | 7.77 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315132 | 1EDGECMB | 80/20 | 7.77 MW | 7.77 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315136 | 1ROSEMG1 | 80/20 | 2.32 MW | 2.32 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315137 | 1ROSEMS1 | 80/20 | 1.44 MW | 1.44 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315138 | 1ROSEMG2 | 80/20 | 1.09 MW | 1.09 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315139 | 1GASTONA | 80/20 | 3.39 MW | 3.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315158 | 1KERR 1 | 80/20 | 0.21 MW | 0.21 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315159 | 1KERR 2 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315160 | 1KERR 3 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315161 | 1KERR 4 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315162 | 1KERR 5 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920591 | AA2-165 C | 80/20 | 0.18 MW | 0.18 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926070 | AC1-086 C | 80/20 | 22.38 MW | 22.38 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927024 | AC1-189 C | 80/20 | 11.88 MW | 11.88 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927145 | AC1-208 C | 80/20 | 10.16 MW | 10.16 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934331 | AD1-057 C O1 | 80/20 | 10.04 MW | 10.04 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934521 | AD1-076 C | 80/20 | 113.85 MW | 113.85 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315163 | 1KERR 6 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315164 | 1KERR 7 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315293 | 1DOMTR9 | 80/20 | 13.58 MW | 13.58 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315294 | 1DOMTR10 | 80/20 | 16.64 MW | 16.64 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315601 | 1CONETOE2SOL | 80/20 | 1.86 MW | 1.86 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315606 | 3AA2-053SOLA | 80/20 | 1.79 MW | 1.79 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316020 | AB2-059 C OP | 80/20 | 1.73 MW | 1.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316129 | AC1-054 C | 80/20 | 5.26 MW | 5.26 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316131 | AB2-060 C | 80/20 | 0.55 MW | 0.55 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316140 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 922922 | AB1-081 C OP | 80/20 | 1.47 MW | 1.47 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923262 | AB1-132 C OP | 80/20 | 15.2 MW | 15.2 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923991 | AB2-040 C O1 | 80/20 | 5.87 MW | 5.87 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924301 | AB2-077 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924311 | AB2-078 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924321 | AB2-079 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925121 | AB2-169 C | 80/20 | 2.04 MW | 2.04 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 932631 | AC2-084 C | 80/20 | 11.47 MW | 11.47 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 939181 | AE1-148 C | 80/20 | 4.23 MW | 4.23 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940491 | AE2-034 C | 80/20 | 14.91 MW | 14.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940661 | AE2-053 O1 | 80/20 | 1.56 MW | 1.56 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 946281 | AF1-292 C | 80/20 | 0.98 MW | 0.98 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957521 | AF2-046 C | 80/20 | 20.42 MW | 20.42 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957531 | AF2-047 C | 80/20 | 35.43 MW | 35.43 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957861 | AF2-080 C | 80/20 | 10.79 MW | 10.79 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940481 | AE2-033 C | 80/20 | 4.47 MW | 4.47 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 946011 | AF1-266 | 80/20 | 3.74 MW | 3.74 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315115 | 1S HAMPT1 | 80/20 | 0.54 MW | 0.54 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315141 | 1GASTONB | 80/20 | 3.39 MW | 3.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315292 | 1DOMTR78 | 80/20 | 2.83 MW | 2.83 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315607 | 3AA1-063SOLA | 80/20 | 1.28 MW | 1.28 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315608 | 3AA2-088SOLA | 80/20 | 0.74 MW | 0.74 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315611 | 6Z1-036WIND | 80/20 | 1.48 MW | 1.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316087 | AB2-174 C | 80/20 | 0.91 MW | 0.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316096 | AB2-100 C1 | 80/20 | 0.62 MW | 0.62 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316098 | AB2-100 C2 | 80/20 | 0.62 MW | 0.62 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 938221 | AE1-035 C | 80/20 | 0.88 MW | 0.88 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957491 | AF2-043 C | Adder | -1.26 MW | -1.07 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 933981 | AD1-022 C | 80/20 | 18.79 MW | 18.79 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960331 | AF2-324 C | 80/20 | 7.58 MW | 7.58 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 961681 | AG1-008 C | 80/20 | 20.46 MW | 20.46 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 962571 | AG1-106 C | 80/20 | 6.22 MW | 6.22 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315602 | 1HOLLOMANSOL | 80/20 | 3.51 MW | 3.51 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315614 | AA2-178 C | 80/20 | 3.39 MW | 3.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 313527 | AB2-043 C | 80/20 | 0.2 MW | 0.2 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.58 MW | 40.58 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.94 MW | 13.94 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.07 MW | 14.07 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.28 MW | 3.28 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.67 MW | 0.67 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.95 MW | 1.95 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.62 MW | 2.62 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 961671 | AG1-007 C | 80/20 | 1.16 MW | 1.16 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 961941 | AG1-037 C | 80/20 | 0.86 MW | 0.86 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 962331 | AG1-082 C | 80/20 | 3.45 MW | 3.45 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 962341 | AG1-083 C | 80/20 | 3.45 MW | 3.45 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 963301 | AG1-179 C | 80/20 | 3.08 MW | 3.08 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 963311 | AG1-180 | 80/20 | 1.5 MW | 1.5 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 964241 | AG1-285 C O1 | 80/20 | 4.26 MW | 4.26 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 964801 | AG1-343 C | 80/20 | 4.72 MW | 4.72 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 966801 | AG1-551 C | 80/20 | 3.84 MW | 3.84 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 966811 | AG1-552 C | 80/20 | 2.05 MW | 2.05 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965291 | AG1-394 C | 80/20 | 1.49 MW | 1.49 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965591 | AG1-427 C | 80/20 | 4.02 MW | 4.02 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965601 | AG1-428 C O2 | 80/20 | 2.58 MW | 2.58 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965691 | AG1-437 C O1 | 80/20 | 22.13 MW | 22.13 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965701 | AG1-438 C O1 | 80/20 | 22.13 MW | 22.13 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965711 | AG1-439 C O1 | 80/20 | 30.87 MW | 30.87 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965721 | AG1-440 C | 80/20 | 4.31 MW | 4.31 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965731 | AG1-441 C | 80/20 | 4.31 MW | 4.31 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965741 | AG1-442 O1 | 80/20 | 12.91 MW | 12.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965751 | AG1-443 O1 | 80/20 | 12.91 MW | 12.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965761 | AG1-444 O1 | 80/20 | 16.47 MW | 16.47 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965771 | AG1-445 | 80/20 | 2.49 MW | 2.49 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965781 | AG1-446 | 80/20 | 2.49 MW | 2.49 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 966621 | AG1-532 C | 80/20 | 0.9 MW | 0.9 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 313506 | AB1-173 C OP | 80/20 | 5.39 MW | 5.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 313719 | 3CHESTNUT | 80/20 | 1.31 MW | 1.31 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314572 | 3EMPORIA | 80/20 | 0.29 MW | 0.29 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314582 | 3KELFORD | 80/20 | 0.65 MW | 0.65 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315126 | 1ROARAP2 | 80/20 | 1.4 MW | 1.4 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315128 | 1ROARAP4 | 80/20 | 1.33 MW | 1.33 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315131 | 1EDGECMA | 80/20 | 7.77 MW | 7.77 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315132 | 1EDGECMB | 80/20 | 7.77 MW | 7.77 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315136 | 1ROSEMG1 | 80/20 | 2.32 MW | 2.32 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315137 | 1ROSEMS1 | 80/20 | 1.44 MW | 1.44 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315138 | 1ROSEMG2 | 80/20 | 1.09 MW | 1.09 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315139 | 1GASTONA | 80/20 | 3.39 MW | 3.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315158 | 1KERR 1 | 80/20 | 0.21 MW | 0.21 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315159 | 1KERR 2 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315160 | 1KERR 3 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315161 | 1KERR 4 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315162 | 1KERR 5 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920591 | AA2-165 C | 80/20 | 0.18 MW | 0.18 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926070 | AC1-086 C | 80/20 | 22.39 MW | 22.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926201 | AC1-098 C | 80/20 | 8.05 MW | 8.05 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926211 | AC1-099 C | 80/20 | 2.7 MW | 2.7 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927024 | AC1-189 C | 80/20 | 11.88 MW | 11.88 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927145 | AC1-208 C | 80/20 | 10.16 MW | 10.16 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934331 | AD1-057 C O1 | 80/20 | 10.05 MW | 10.05 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934521 | AD1-076 C | 80/20 | 113.87 MW | 113.87 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315163 | 1KERR 6 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315164 | 1KERR 7 | 80/20 | 0.59 MW | 0.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315293 | 1DOMTR9 | 80/20 | 13.58 MW | 13.58 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315294 | 1DOMTR10 | 80/20 | 16.64 MW | 16.64 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315601 | 1CONETOE2SOL | 80/20 | 1.86 MW | 1.86 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315606 | 3AA2-053SOLA | 80/20 | 1.79 MW | 1.79 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316020 | AB2-059 C OP | 80/20 | 1.73 MW | 1.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316129 | AC1-054 C | 80/20 | 5.26 MW | 5.26 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316131 | AB2-060 C | 80/20 | 0.55 MW | 0.55 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316140 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 922922 | AB1-081 C OP | 80/20 | 1.47 MW | 1.47 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923262 | AB1-132 C OP | 80/20 | 15.21 MW | 15.21 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924301 | AB2-077 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924311 | AB2-078 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924321 | AB2-079 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925121 | AB2-169 C | 80/20 | 2.04 MW | 2.04 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 932631 | AC2-084 C | 80/20 | 11.47 MW | 11.47 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 939181 | AE1-148 C | 80/20 | 4.23 MW | 4.23 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940491 | AE2-034 C | 80/20 | 14.91 MW | 14.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940661 | AE2-053 O1 | 80/20 | 1.57 MW | 1.57 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 946281 | AF1-292 C | 80/20 | 0.98 MW | 0.98 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957521 | AF2-046 C | 80/20 | 20.43 MW | 20.43 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957531 | AF2-047 C | 80/20 | 35.43 MW | 35.43 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957861 | AF2-080 C | 80/20 | 10.79 MW | 10.79 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940481 | AE2-033 C | 80/20 | 4.47 MW | 4.47 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 946011 | AF1-266 | 80/20 | 3.75 MW | 3.75 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315115 | 1S HAMPT1 | 80/20 | 0.54 MW | 0.54 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315141 | 1GASTONB | 80/20 | 3.39 MW | 3.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315292 | 1DOMTR78 | 80/20 | 2.83 MW | 2.83 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315607 | 3AA1-063SOLA | 80/20 | 1.28 MW | 1.28 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315608 | 3AA2-088SOLA | 80/20 | 0.74 MW | 0.74 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316087 | AB2-174 C | 80/20 | 0.91 MW | 0.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316096 | AB2-100 C1 | 80/20 | 0.62 MW | 0.62 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316098 | AB2-100 C2 | 80/20 | 0.62 MW | 0.62 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 938221 | AE1-035 C | 80/20 | 0.88 MW | 0.88 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957491 | AF2-043 C | Adder | -1.26 MW | -1.07 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 933981 | AD1-022 C | 80/20 | 18.79 MW | 18.79 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960331 | AF2-324 C | 80/20 | 7.59 MW | 7.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 961681 | AG1-008 C | 80/20 | 20.47 MW | 20.47 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 962571 | AG1-106 C | 80/20 | 6.23 MW | 6.23 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315602 | 1HOLLOMANSOL | 80/20 | 3.51 MW | 3.51 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315614 | AA2-178 C | 80/20 | 3.39 MW | 3.39 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 313527 | AB2-043 C | 80/20 | 0.2 MW | 0.2 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.64 MW | 40.64 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 14.02 MW | 14.02 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.12 MW | 14.12 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.68 MW | 0.68 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.96 MW | 1.96 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.63 MW | 2.63 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
Details for 6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.01 MW | 1.01 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.52 MW | 0.52 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.06 MW | 2.06 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.06 MW | 2.06 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 4.22 MW | 4.22 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.12 MW | 2.12 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 2.08 MW | 2.08 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 1.4 MW | 1.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 9.6 MW | 9.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 9.6 MW | 9.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 24.81 MW | 24.81 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 3.29 MW | 3.29 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 3.29 MW | 3.29 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.6 MW | 5.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.6 MW | 5.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.23 MW | 13.23 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 1.9 MW | 1.9 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 1.9 MW | 1.9 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.27 MW | 1.27 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.41 MW | 0.41 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.71 MW | 8.71 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.71 MW | 8.71 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.47 MW | 4.47 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.77 MW | 2.77 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.1 MW | 2.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.87 MW | 6.87 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 45.32 MW | 45.32 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 6.43 MW | 6.43 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.16 MW | 2.16 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 8.68 MW | 8.68 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 9.29 MW | 9.29 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.68 MW | 15.68 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 41.1 MW | 41.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.44 MW | 1.44 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 2.99 MW | 2.99 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.49 MW | 5.49 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.73 MW | 6.73 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.49 MW | 1.49 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 1.57 MW | 1.57 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 1.87 MW | 1.87 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 4.63 MW | 4.63 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.6 MW | 0.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.58 MW | 1.58 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 30.77 MW | 30.77 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.94 MW | 0.94 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.1 MW | 7.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 9.17 MW | 9.17 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.21 MW | 4.21 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.65 MW | 4.65 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 14.37 MW | 14.37 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 10.02 MW | 10.02 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 7.88 MW | 7.88 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 0.71 MW | 0.71 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.87 MW | 6.87 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.15 MW | 1.15 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 1.27 MW | 1.27 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 0.72 MW | 0.72 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315611 | 6Z1-036WIND | 80/20 | 0.22 MW | 0.22 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.45 MW | 0.45 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.56 MW | 7.56 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.5 MW | 8.5 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 14.4 MW | 14.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.6 MW | 12.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.79 MW | 1.79 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.96 MW | 0.96 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.09 MW | 2.09 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.55 MW | 0.55 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 34.33 MW | 34.33 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.27 MW | 11.27 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.65 MW | 11.65 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.16 MW | 3.16 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.73 MW | 2.73 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.55 MW | 0.55 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.6 MW | 1.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.19 MW | 2.19 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
Details for 6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.01 MW | 1.01 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.52 MW | 0.52 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.06 MW | 2.06 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.06 MW | 2.06 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 4.22 MW | 4.22 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.12 MW | 2.12 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 2.08 MW | 2.08 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 1.4 MW | 1.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 9.6 MW | 9.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 9.6 MW | 9.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 24.81 MW | 24.81 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 3.29 MW | 3.29 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 3.29 MW | 3.29 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.6 MW | 5.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.6 MW | 5.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.23 MW | 13.23 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 1.9 MW | 1.9 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 1.9 MW | 1.9 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.27 MW | 1.27 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.41 MW | 0.41 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.24 MW | 0.24 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.42 MW | 1.42 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.35 MW | 1.35 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.71 MW | 8.71 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.71 MW | 8.71 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.47 MW | 4.47 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.77 MW | 2.77 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.1 MW | 2.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.87 MW | 6.87 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 45.32 MW | 45.32 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 6.43 MW | 6.43 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.16 MW | 2.16 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 8.68 MW | 8.68 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 9.29 MW | 9.29 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.68 MW | 15.68 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 41.1 MW | 41.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.44 MW | 1.44 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 2.99 MW | 2.99 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.49 MW | 5.49 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.73 MW | 6.73 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.49 MW | 1.49 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.57 MW | 1.57 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 1.87 MW | 1.87 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 4.63 MW | 4.63 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.6 MW | 0.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.58 MW | 1.58 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 30.77 MW | 30.77 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.94 MW | 0.94 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.1 MW | 7.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 9.17 MW | 9.17 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940491 | AE2-034 C | 80/20 | 4.21 MW | 4.21 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.65 MW | 4.65 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 14.37 MW | 14.37 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957531 | AF2-047 C | 80/20 | 10.02 MW | 10.02 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 7.88 MW | 7.88 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315115 | 1S HAMPT1 | 80/20 | 0.71 MW | 0.71 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.87 MW | 6.87 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.15 MW | 1.15 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.27 MW | 1.27 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.72 MW | 0.72 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315611 | 6Z1-036WIND | 80/20 | 0.22 MW | 0.22 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.45 MW | 0.45 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.56 MW | 7.56 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.5 MW | 8.5 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 14.4 MW | 14.4 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.6 MW | 12.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.79 MW | 1.79 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315614 | AA2-178 C | 80/20 | 0.96 MW | 0.96 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.09 MW | 2.09 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.55 MW | 0.55 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 34.33 MW | 34.33 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.27 MW | 11.27 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.65 MW | 11.65 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.16 MW | 3.16 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.73 MW | 2.73 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.55 MW | 0.55 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.6 MW | 1.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.29 MW | 0.29 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.19 MW | 2.19 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 961671 | AG1-007 C | 80/20 | 1.16 MW | 1.16 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 961941 | AG1-037 C | 80/20 | 0.86 MW | 0.86 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 962331 | AG1-082 C | 80/20 | 3.45 MW | 3.45 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 962341 | AG1-083 C | 80/20 | 3.45 MW | 3.45 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 963301 | AG1-179 C | 80/20 | 3.08 MW | 3.08 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 963311 | AG1-180 | 80/20 | 1.5 MW | 1.5 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 964241 | AG1-285 C O1 | 80/20 | 4.25 MW | 4.25 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 964801 | AG1-343 C | 80/20 | 4.72 MW | 4.72 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 966801 | AG1-551 C | 80/20 | 3.84 MW | 3.84 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 966811 | AG1-552 C | 80/20 | 2.05 MW | 2.05 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965291 | AG1-394 C | 80/20 | 1.49 MW | 1.49 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965591 | AG1-427 C | 80/20 | 4.01 MW | 4.01 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965601 | AG1-428 C O2 | 80/20 | 2.57 MW | 2.57 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965691 | AG1-437 C O1 | 80/20 | 22.13 MW | 22.13 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965701 | AG1-438 C O1 | 80/20 | 22.13 MW | 22.13 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965711 | AG1-439 C O1 | 80/20 | 30.86 MW | 30.86 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965721 | AG1-440 C | 80/20 | 4.3 MW | 4.3 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965731 | AG1-441 C | 80/20 | 4.3 MW | 4.3 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965741 | AG1-442 O1 | 80/20 | 12.91 MW | 12.91 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965751 | AG1-443 O1 | 80/20 | 12.91 MW | 12.91 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965761 | AG1-444 O1 | 80/20 | 16.46 MW | 16.46 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965771 | AG1-445 | 80/20 | 2.49 MW | 2.49 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 965781 | AG1-446 | 80/20 | 2.49 MW | 2.49 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 966621 | AG1-532 C | 80/20 | 0.9 MW | 0.9 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 313506 | AB1-173 C OP | 80/20 | 5.39 MW | 5.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 313719 | 3CHESTNUT | 80/20 | 1.31 MW | 1.31 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314572 | 3EMPORIA | 80/20 | 0.29 MW | 0.29 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314582 | 3KELFORD | 80/20 | 0.65 MW | 0.65 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315126 | 1ROARAP2 | 80/20 | 1.39 MW | 1.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315128 | 1ROARAP4 | 80/20 | 1.33 MW | 1.33 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315131 | 1EDGECMA | 80/20 | 7.77 MW | 7.77 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315132 | 1EDGECMB | 80/20 | 7.77 MW | 7.77 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315136 | 1ROSEMG1 | 80/20 | 2.32 MW | 2.32 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315137 | 1ROSEMS1 | 80/20 | 1.44 MW | 1.44 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315138 | 1ROSEMG2 | 80/20 | 1.09 MW | 1.09 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315139 | 1GASTONA | 80/20 | 3.39 MW | 3.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315158 | 1KERR 1 | 80/20 | 0.21 MW | 0.21 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315159 | 1KERR 2 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315160 | 1KERR 3 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315161 | 1KERR 4 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315162 | 1KERR 5 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 920591 | AA2-165 C | 80/20 | 0.18 MW | 0.18 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926070 | AC1-086 C | 80/20 | 22.38 MW | 22.38 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926201 | AC1-098 C | 80/20 | 8.04 MW | 8.04 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 926211 | AC1-099 C | 80/20 | 2.69 MW | 2.69 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927024 | AC1-189 C | 80/20 | 11.88 MW | 11.88 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 927145 | AC1-208 C | 80/20 | 10.16 MW | 10.16 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934331 | AD1-057 C O1 | 80/20 | 10.04 MW | 10.04 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 934521 | AD1-076 C | 80/20 | 113.85 MW | 113.85 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315163 | 1KERR 6 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315164 | 1KERR 7 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315293 | 1DOMTR9 | 80/20 | 13.58 MW | 13.58 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315294 | 1DOMTR10 | 80/20 | 16.64 MW | 16.64 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315601 | 1CONETOE2SOL | 80/20 | 1.86 MW | 1.86 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315606 | 3AA2-053SOLA | 80/20 | 1.79 MW | 1.79 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316020 | AB2-059 C OP | 80/20 | 1.73 MW | 1.73 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316129 | AC1-054 C | 80/20 | 5.26 MW | 5.26 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316131 | AB2-060 C | 80/20 | 0.55 MW | 0.55 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316140 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 922922 | AB1-081 C OP | 80/20 | 1.47 MW | 1.47 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923262 | AB1-132 C OP | 80/20 | 15.2 MW | 15.2 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 923991 | AB2-040 C O1 | 80/20 | 5.87 MW | 5.87 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924301 | AB2-077 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924311 | AB2-078 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 924321 | AB2-079 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925121 | AB2-169 C | 80/20 | 2.04 MW | 2.04 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 932631 | AC2-084 C | 80/20 | 11.47 MW | 11.47 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 939181 | AE1-148 C | 80/20 | 4.23 MW | 4.23 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940491 | AE2-034 C | 80/20 | 14.91 MW | 14.91 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940661 | AE2-053 O1 | 80/20 | 1.56 MW | 1.56 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 946281 | AF1-292 C | 80/20 | 0.98 MW | 0.98 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957521 | AF2-046 C | 80/20 | 20.42 MW | 20.42 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957531 | AF2-047 C | 80/20 | 35.43 MW | 35.43 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957861 | AF2-080 C | 80/20 | 10.79 MW | 10.79 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 940481 | AE2-033 C | 80/20 | 4.47 MW | 4.47 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 946011 | AF1-266 | 80/20 | 3.74 MW | 3.74 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315115 | 1S HAMPT1 | 80/20 | 0.54 MW | 0.54 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315141 | 1GASTONB | 80/20 | 3.39 MW | 3.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315292 | 1DOMTR78 | 80/20 | 2.83 MW | 2.83 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315607 | 3AA1-063SOLA | 80/20 | 1.28 MW | 1.28 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315608 | 3AA2-088SOLA | 80/20 | 0.74 MW | 0.74 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315611 | 6Z1-036WIND | 80/20 | 1.48 MW | 1.48 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316087 | AB2-174 C | 80/20 | 0.91 MW | 0.91 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316096 | AB2-100 C1 | 80/20 | 0.62 MW | 0.62 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 316098 | AB2-100 C2 | 80/20 | 0.62 MW | 0.62 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 938221 | AE1-035 C | 80/20 | 0.88 MW | 0.88 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 957491 | AF2-043 C | Adder | -1.26 MW | -1.07 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 933981 | AD1-022 C | 80/20 | 18.79 MW | 18.79 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 960331 | AF2-324 C | 80/20 | 7.58 MW | 7.58 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 961681 | AG1-008 C | 80/20 | 20.46 MW | 20.46 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 962571 | AG1-106 C | 80/20 | 6.22 MW | 6.22 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315602 | 1HOLLOMANSOL | 80/20 | 3.51 MW | 3.51 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 315614 | AA2-178 C | 80/20 | 3.39 MW | 3.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | 313527 | AB2-043 C | 80/20 | 0.2 MW | 0.2 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.58 MW | 40.58 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.94 MW | 13.94 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.07 MW | 14.07 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.28 MW | 3.28 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.67 MW | 0.67 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.95 MW | 1.95 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.62 MW | 2.62 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2092 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
Details for 6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 961671 | AG1-007 C | 80/20 | 1.16 MW | 1.16 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 961941 | AG1-037 C | 80/20 | 0.86 MW | 0.86 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 962331 | AG1-082 C | 80/20 | 3.45 MW | 3.45 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 962341 | AG1-083 C | 80/20 | 3.45 MW | 3.45 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 963301 | AG1-179 C | 80/20 | 3.08 MW | 3.08 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 963311 | AG1-180 | 80/20 | 1.5 MW | 1.5 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 964241 | AG1-285 C O1 | 80/20 | 4.26 MW | 4.26 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 964801 | AG1-343 C | 80/20 | 4.72 MW | 4.72 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 966801 | AG1-551 C | 80/20 | 3.84 MW | 3.84 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 966811 | AG1-552 C | 80/20 | 2.05 MW | 2.05 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965291 | AG1-394 C | 80/20 | 1.49 MW | 1.49 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965591 | AG1-427 C | 80/20 | 4.02 MW | 4.02 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965601 | AG1-428 C O2 | 80/20 | 2.58 MW | 2.58 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965691 | AG1-437 C O1 | 80/20 | 22.13 MW | 22.13 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965701 | AG1-438 C O1 | 80/20 | 22.13 MW | 22.13 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965711 | AG1-439 C O1 | 80/20 | 30.87 MW | 30.87 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965721 | AG1-440 C | 80/20 | 4.31 MW | 4.31 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965731 | AG1-441 C | 80/20 | 4.31 MW | 4.31 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965741 | AG1-442 O1 | 80/20 | 12.91 MW | 12.91 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965751 | AG1-443 O1 | 80/20 | 12.91 MW | 12.91 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965761 | AG1-444 O1 | 80/20 | 16.47 MW | 16.47 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965771 | AG1-445 | 80/20 | 2.49 MW | 2.49 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 965781 | AG1-446 | 80/20 | 2.49 MW | 2.49 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 966621 | AG1-532 C | 80/20 | 0.9 MW | 0.9 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 313506 | AB1-173 C OP | 80/20 | 5.39 MW | 5.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 313719 | 3CHESTNUT | 80/20 | 1.31 MW | 1.31 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314572 | 3EMPORIA | 80/20 | 0.29 MW | 0.29 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314582 | 3KELFORD | 80/20 | 0.65 MW | 0.65 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315126 | 1ROARAP2 | 80/20 | 1.4 MW | 1.4 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315128 | 1ROARAP4 | 80/20 | 1.33 MW | 1.33 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315131 | 1EDGECMA | 80/20 | 7.77 MW | 7.77 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315132 | 1EDGECMB | 80/20 | 7.77 MW | 7.77 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315136 | 1ROSEMG1 | 80/20 | 2.32 MW | 2.32 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315137 | 1ROSEMS1 | 80/20 | 1.44 MW | 1.44 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315138 | 1ROSEMG2 | 80/20 | 1.09 MW | 1.09 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315139 | 1GASTONA | 80/20 | 3.39 MW | 3.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315158 | 1KERR 1 | 80/20 | 0.21 MW | 0.21 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315159 | 1KERR 2 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315160 | 1KERR 3 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315161 | 1KERR 4 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315162 | 1KERR 5 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 920591 | AA2-165 C | 80/20 | 0.18 MW | 0.18 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926070 | AC1-086 C | 80/20 | 22.39 MW | 22.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926201 | AC1-098 C | 80/20 | 8.05 MW | 8.05 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 926211 | AC1-099 C | 80/20 | 2.7 MW | 2.7 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927024 | AC1-189 C | 80/20 | 11.88 MW | 11.88 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 927145 | AC1-208 C | 80/20 | 10.16 MW | 10.16 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934331 | AD1-057 C O1 | 80/20 | 10.05 MW | 10.05 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 934521 | AD1-076 C | 80/20 | 113.87 MW | 113.87 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943171 | AE2-346 C | 80/20 | 2.42 MW | 2.42 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 944141 | AF1-082 | 80/20 | 2.77 MW | 2.77 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960081 | AF2-299 C | 80/20 | 1.66 MW | 1.66 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315163 | 1KERR 6 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315164 | 1KERR 7 | 80/20 | 0.59 MW | 0.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315293 | 1DOMTR9 | 80/20 | 13.58 MW | 13.58 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315294 | 1DOMTR10 | 80/20 | 16.64 MW | 16.64 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315601 | 1CONETOE2SOL | 80/20 | 1.86 MW | 1.86 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315606 | 3AA2-053SOLA | 80/20 | 1.79 MW | 1.79 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316020 | AB2-059 C OP | 80/20 | 1.73 MW | 1.73 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316129 | AC1-054 C | 80/20 | 5.26 MW | 5.26 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316131 | AB2-060 C | 80/20 | 0.55 MW | 0.55 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316140 | AB2-099 C | 80/20 | 1.01 MW | 1.01 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 922922 | AB1-081 C OP | 80/20 | 1.47 MW | 1.47 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923262 | AB1-132 C OP | 80/20 | 15.21 MW | 15.21 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 923991 | AB2-040 C O1 | 80/20 | 5.88 MW | 5.88 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924301 | AB2-077 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924311 | AB2-078 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 924321 | AB2-079 C O1 | 80/20 | 0.73 MW | 0.73 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925121 | AB2-169 C | 80/20 | 2.04 MW | 2.04 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 925591 | AC1-034 C | 80/20 | 6.57 MW | 6.57 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 932631 | AC2-084 C | 80/20 | 11.47 MW | 11.47 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 939181 | AE1-148 C | 80/20 | 4.23 MW | 4.23 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940491 | AE2-034 C | 80/20 | 14.91 MW | 14.91 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940571 | AE2-044 C | 80/20 | 4.3 MW | 4.3 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940661 | AE2-053 O1 | 80/20 | 1.57 MW | 1.57 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 946281 | AF1-292 C | 80/20 | 0.98 MW | 0.98 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957521 | AF2-046 C | 80/20 | 20.43 MW | 20.43 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957531 | AF2-047 C | 80/20 | 35.43 MW | 35.43 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957861 | AF2-080 C | 80/20 | 10.79 MW | 10.79 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 940481 | AE2-033 C | 80/20 | 4.47 MW | 4.47 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 946011 | AF1-266 | 80/20 | 3.75 MW | 3.75 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 943611 | AF1-032 C | Adder | -1.03 MW | -0.88 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315115 | 1S HAMPT1 | 80/20 | 0.54 MW | 0.54 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315141 | 1GASTONB | 80/20 | 3.39 MW | 3.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315292 | 1DOMTR78 | 80/20 | 2.83 MW | 2.83 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315607 | 3AA1-063SOLA | 80/20 | 1.28 MW | 1.28 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315608 | 3AA2-088SOLA | 80/20 | 0.74 MW | 0.74 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316087 | AB2-174 C | 80/20 | 0.91 MW | 0.91 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316096 | AB2-100 C1 | 80/20 | 0.62 MW | 0.62 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 316098 | AB2-100 C2 | 80/20 | 0.62 MW | 0.62 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 938221 | AE1-035 C | 80/20 | 0.88 MW | 0.88 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 957491 | AF2-043 C | Adder | -1.26 MW | -1.07 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 933981 | AD1-022 C | 80/20 | 18.79 MW | 18.79 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 960331 | AF2-324 C | 80/20 | 7.59 MW | 7.59 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 961681 | AG1-008 C | 80/20 | 20.47 MW | 20.47 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 962571 | AG1-106 C | 80/20 | 6.23 MW | 6.23 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315602 | 1HOLLOMANSOL | 80/20 | 3.51 MW | 3.51 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 315614 | AA2-178 C | 80/20 | 3.39 MW | 3.39 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | 313527 | AB2-043 C | 80/20 | 0.2 MW | 0.2 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.64 MW | 40.64 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 14.02 MW | 14.02 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.12 MW | 14.12 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.68 MW | 0.68 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.96 MW | 1.96 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.63 MW | 2.63 MW |
6NUCO TP-6SUFFOLK 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2131 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.33 MW | 0.33 MW |
Details for 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961671 | AG1-007 C | 80/20 | 0.55 MW | 0.55 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 5.1 MW | 5.1 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 2.49 MW | 2.49 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 4.26 MW | 4.26 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965711 | AG1-439 C O1 | 80/20 | 10.52 MW | 10.52 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965761 | AG1-444 O1 | 80/20 | 5.61 MW | 5.61 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 1.88 MW | 1.88 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 2.54 MW | 2.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.46 MW | 0.46 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314623 | 3WITAKRS | 80/20 | 0.1 MW | 0.1 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.32 MW | 0.32 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315131 | 1EDGECMA | 80/20 | 7.54 MW | 7.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315132 | 1EDGECMB | 80/20 | 7.54 MW | 7.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 6.49 MW | 6.49 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 4.03 MW | 4.03 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 3.04 MW | 3.04 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 10.22 MW | 10.22 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 67.5 MW | 67.5 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934331 | AD1-057 C O1 | 80/20 | 19.73 MW | 19.73 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 943171 | AE2-346 C | Adder | -0.97 MW | -0.83 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 944141 | AF1-082 | 80/20 | 2.16 MW | 2.16 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.49 MW | 3.49 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315601 | 1CONETOE2SOL | 80/20 | 0.63 MW | 0.63 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316020 | AB2-059 C OP | 80/20 | 1.35 MW | 1.35 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | Adder | -3.61 MW | -3.07 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316140 | AB2-099 C | Adder | -0.4 MW | -0.34 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 922922 | AB1-081 C OP | 80/20 | 1.15 MW | 1.15 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 45.84 MW | 45.84 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 2.77 MW | 2.77 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925591 | AC1-034 C | 80/20 | 5.13 MW | 5.13 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940571 | AE2-044 C | 80/20 | 3.36 MW | 3.36 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.07 MW | 2.07 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 38.46 MW | 38.46 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 32.19 MW | 32.19 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 10.22 MW | 10.22 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 0.77 MW | 0.77 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 2.54 MW | 2.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 2.54 MW | 2.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960331 | AF2-324 C | 80/20 | 7.36 MW | 7.36 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 18.77 MW | 18.77 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.08 MW | 1.08 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.43 MW | 18.43 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.11 MW | 6.11 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.33 MW | 6.33 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.48 MW | 1.48 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.19 MW | 1.19 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
Details for 6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961671 | AG1-007 C | 80/20 | 0.55 MW | 0.55 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 5.1 MW | 5.1 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 2.49 MW | 2.49 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 4.26 MW | 4.26 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965711 | AG1-439 C O1 | 80/20 | 10.52 MW | 10.52 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965761 | AG1-444 O1 | 80/20 | 5.61 MW | 5.61 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 1.88 MW | 1.88 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.54 MW | 2.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.46 MW | 0.46 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314623 | 3WITAKRS | 80/20 | 0.1 MW | 0.1 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.32 MW | 0.32 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315131 | 1EDGECMA | 80/20 | 7.54 MW | 7.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315132 | 1EDGECMB | 80/20 | 7.54 MW | 7.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 6.49 MW | 6.49 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 4.03 MW | 4.03 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 3.04 MW | 3.04 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 10.22 MW | 10.22 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 67.5 MW | 67.5 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 19.73 MW | 19.73 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 943171 | AE2-346 C | Adder | -0.97 MW | -0.83 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 944141 | AF1-082 | 80/20 | 2.16 MW | 2.16 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.49 MW | 3.49 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.63 MW | 0.63 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316020 | AB2-059 C OP | 80/20 | 1.35 MW | 1.35 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | Adder | -3.61 MW | -3.07 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316140 | AB2-099 C | Adder | -0.4 MW | -0.34 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.15 MW | 1.15 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 45.84 MW | 45.84 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.77 MW | 2.77 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925591 | AC1-034 C | 80/20 | 5.13 MW | 5.13 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940571 | AE2-044 C | 80/20 | 3.36 MW | 3.36 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.07 MW | 2.07 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 38.46 MW | 38.46 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 32.19 MW | 32.19 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 10.22 MW | 10.22 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.77 MW | 0.77 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 2.54 MW | 2.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 2.54 MW | 2.54 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960331 | AF2-324 C | 80/20 | 7.36 MW | 7.36 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 18.77 MW | 18.77 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.08 MW | 1.08 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 18.43 MW | 18.43 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.11 MW | 6.11 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.33 MW | 6.33 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.48 MW | 1.48 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.08 MW | 0.08 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.87 MW | 0.87 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.19 MW | 1.19 MW |
6LAKEVEW-6CAROLNA 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
Details for 6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.82 MW | 0.82 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.37 MW | 0.37 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.48 MW | 1.48 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.48 MW | 1.48 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 3.42 MW | 3.42 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.56 MW | 1.56 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 1.74 MW | 1.74 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.15 MW | 1.15 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.57 MW | 6.57 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.57 MW | 6.57 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 19.85 MW | 19.85 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 2.56 MW | 2.56 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 2.56 MW | 2.56 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.83 MW | 3.83 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.83 MW | 3.83 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.59 MW | 10.59 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 1.48 MW | 1.48 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 1.48 MW | 1.48 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.05 MW | 1.05 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.3 MW | 0.3 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.2 MW | 0.2 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 1.18 MW | 1.18 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 1.13 MW | 1.13 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.44 MW | 7.44 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.44 MW | 7.44 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 4.08 MW | 4.08 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.53 MW | 2.53 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.91 MW | 1.91 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 6.29 MW | 6.29 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.14 MW | 0.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 41.53 MW | 41.53 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 5.08 MW | 5.08 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 1.7 MW | 1.7 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 6.78 MW | 6.78 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 7.58 MW | 7.58 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 14.01 MW | 14.01 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | 80/20 | 29.09 MW | 29.09 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.03 MW | 1.03 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.54 MW | 2.54 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315293 | 1DOMTR9 | 80/20 | 3.93 MW | 3.93 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315294 | 1DOMTR10 | 80/20 | 4.82 MW | 4.82 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.2 MW | 1.2 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 1.27 MW | 1.27 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.58 MW | 1.58 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 3.74 MW | 3.74 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.43 MW | 0.43 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.34 MW | 1.34 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 28.2 MW | 28.2 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.68 MW | 0.68 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.02 MW | 6.02 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 7.24 MW | 7.24 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 940491 | AE2-034 C | 80/20 | 3.08 MW | 3.08 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 3.94 MW | 3.94 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 10.9 MW | 10.9 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957531 | AF2-047 C | 80/20 | 7.33 MW | 7.33 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.16 MW | 6.16 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.06 MW | 0.06 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.62 MW | 0.62 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 6.29 MW | 6.29 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315292 | 1DOMTR78 | 80/20 | 0.82 MW | 0.82 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.05 MW | 1.05 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.59 MW | 0.59 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 3.52 MW | 3.52 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 3.52 MW | 3.52 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.3 MW | 0.3 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.24 MW | 5.24 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.26 MW | 7.26 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 10.93 MW | 10.93 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 11.55 MW | 11.55 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.19 MW | 1.19 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | 315614 | AA2-178 C | 80/20 | 0.7 MW | 0.7 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.67 MW | 1.67 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.43 MW | 0.43 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 27.44 MW | 27.44 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.53 MW | 8.53 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.07 MW | 9.07 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.54 MW | 2.54 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.14 MW | 2.14 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.23 MW | 1.23 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.26 MW | 0.26 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.72 MW | 1.72 MW |
6DRY BREAD-6CLUBHSE 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.44 MW | 2.44 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.44 MW | 2.44 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.29 MW | 9.29 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.76 MW | 25.76 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.72 MW | 14.72 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.2 MW | 0.2 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.2 MW | 43.2 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.39 MW | 12.39 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.51 MW | 42.51 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.69 MW | 5.69 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.28 MW | 9.28 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.56 MW | 11.56 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.18 MW | 8.18 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.76 MW | 18.76 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.2 MW | 8.2 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940481 | AE2-033 C | 80/20 | 63.95 MW | 63.95 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946011 | AF1-266 | 80/20 | 53.53 MW | 53.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314435 | 6SAPONY | 80/20 | 1.75 MW | 1.75 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.73 MW | 2.73 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940541 | AE2-040 | 80/20 | 11.72 MW | 11.72 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.85 MW | 7.85 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.8 MW | 18.8 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965281 | AG1-393 C | 80/20 | 8.96 MW | 8.96 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.87 MW | 1.87 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.11 MW | 40.11 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.23 MW | 13.23 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.7 MW | 13.7 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.88 MW | 1.88 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963361 | AG1-185 O1 | Adder | 5.53 MW | 4.7 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940481 | AE2-033 C | 80/20 | 63.96 MW | 63.96 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946011 | AF1-266 | 80/20 | 53.54 MW | 53.54 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.44 MW | 2.44 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.44 MW | 2.44 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.29 MW | 9.29 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.76 MW | 25.76 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.72 MW | 14.72 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.2 MW | 0.2 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.2 MW | 43.2 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.39 MW | 12.39 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.51 MW | 42.51 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.69 MW | 5.69 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.28 MW | 9.28 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.56 MW | 11.56 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.18 MW | 8.18 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.76 MW | 18.76 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.2 MW | 8.2 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940481 | AE2-033 C | 80/20 | 63.95 MW | 63.95 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946011 | AF1-266 | 80/20 | 53.53 MW | 53.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314435 | 6SAPONY | 80/20 | 1.75 MW | 1.75 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.73 MW | 2.73 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940541 | AE2-040 | 80/20 | 11.72 MW | 11.72 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.85 MW | 7.85 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.8 MW | 18.8 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965281 | AG1-393 C | 80/20 | 8.96 MW | 8.96 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.87 MW | 1.87 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.11 MW | 40.11 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.23 MW | 13.23 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.7 MW | 13.7 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.88 MW | 1.88 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963361 | AG1-185 O1 | Adder | 5.53 MW | 4.7 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940481 | AE2-033 C | 80/20 | 63.96 MW | 63.96 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946011 | AF1-266 | 80/20 | 53.54 MW | 53.54 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961891 | AG1-030 C | 80/20 | 8.19 MW | 8.19 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963361 | AG1-185 O1 | 80/20 | 5.53 MW | 5.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964111 | AG1-272 C | 80/20 | 1.67 MW | 1.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964121 | AG1-273 C | 80/20 | 1.67 MW | 1.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964131 | AG1-274 C | 80/20 | 1.67 MW | 1.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964791 | AG1-342 C | 80/20 | 2.24 MW | 2.24 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965191 | AG1-384 C | 80/20 | 1.67 MW | 1.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 958801 | AF2-171 C | 80/20 | 7.4 MW | 7.4 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 959311 | AF2-222 C | 80/20 | 10.47 MW | 10.47 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.32 MW | 4.32 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 10.25 MW | 10.25 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962561 | AG1-105 C O1 | 80/20 | 5.23 MW | 5.23 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961891 | AG1-030 C | 80/20 | 8.19 MW | 8.19 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963361 | AG1-185 O1 | 80/20 | 5.53 MW | 5.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964111 | AG1-272 C | 80/20 | 1.67 MW | 1.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964121 | AG1-273 C | 80/20 | 1.67 MW | 1.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964131 | AG1-274 C | 80/20 | 1.67 MW | 1.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964791 | AG1-342 C | 80/20 | 2.24 MW | 2.24 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965191 | AG1-384 C | 80/20 | 1.67 MW | 1.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 958801 | AF2-171 C | 80/20 | 7.4 MW | 7.4 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 959311 | AF2-222 C | 80/20 | 10.47 MW | 10.47 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940491 | AE2-034 C | 80/20 | 4.32 MW | 4.32 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957531 | AF2-047 C | 80/20 | 10.25 MW | 10.25 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.23 MW | 5.23 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
Details for 6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.82 MW | 0.82 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.37 MW | 0.37 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.48 MW | 1.48 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.48 MW | 1.48 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 3.43 MW | 3.43 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.56 MW | 1.56 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 1.74 MW | 1.74 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.16 MW | 1.16 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.59 MW | 6.59 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.59 MW | 6.59 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 19.9 MW | 19.9 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.84 MW | 3.84 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.84 MW | 3.84 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.62 MW | 10.62 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.05 MW | 1.05 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.3 MW | 0.3 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.2 MW | 0.2 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 1.18 MW | 1.18 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 1.13 MW | 1.13 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.45 MW | 7.45 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.45 MW | 7.45 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 4.09 MW | 4.09 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.54 MW | 2.54 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.92 MW | 1.92 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 6.3 MW | 6.3 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.14 MW | 0.14 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 41.58 MW | 41.58 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 5.09 MW | 5.09 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 1.71 MW | 1.71 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 6.8 MW | 6.8 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 7.6 MW | 7.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 14.03 MW | 14.03 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | 80/20 | 29.2 MW | 29.2 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.04 MW | 1.04 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.54 MW | 2.54 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315293 | 1DOMTR9 | 80/20 | 3.95 MW | 3.95 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315294 | 1DOMTR10 | 80/20 | 4.83 MW | 4.83 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.2 MW | 1.2 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 1.27 MW | 1.27 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.59 MW | 1.59 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 3.76 MW | 3.76 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.43 MW | 0.43 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.35 MW | 1.35 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 28.23 MW | 28.23 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.69 MW | 0.69 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.04 MW | 6.04 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 7.26 MW | 7.26 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 940491 | AE2-034 C | 80/20 | 3.1 MW | 3.1 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 3.95 MW | 3.95 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 10.94 MW | 10.94 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 957531 | AF2-047 C | 80/20 | 7.37 MW | 7.37 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.17 MW | 6.17 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.06 MW | 0.06 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.63 MW | 0.63 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 6.3 MW | 6.3 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315292 | 1DOMTR78 | 80/20 | 0.82 MW | 0.82 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.05 MW | 1.05 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.6 MW | 0.6 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.3 MW | 0.3 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.26 MW | 5.26 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.28 MW | 7.28 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 10.96 MW | 10.96 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 11.56 MW | 11.56 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.2 MW | 1.2 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | 315614 | AA2-178 C | 80/20 | 0.7 MW | 0.7 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.69 MW | 1.69 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.44 MW | 0.44 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 27.8 MW | 27.8 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.02 MW | 9.02 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.38 MW | 9.38 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.56 MW | 2.56 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.2 MW | 2.2 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.28 MW | 1.28 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.76 MW | 1.76 MW |
6LAKEVEW-6DRY BREAD 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.84 MW | 0.84 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.46 MW | 0.46 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.82 MW | 1.82 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.82 MW | 1.82 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 10.29 MW | 10.29 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 5.02 MW | 5.02 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.55 MW | 10.55 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.11 MW | 5.11 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.54 MW | 1.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.54 MW | 1.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.54 MW | 1.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.09 MW | 9.09 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 5.27 MW | 5.27 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.62 MW | 1.62 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 3.12 MW | 3.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.54 MW | 1.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.81 MW | 1.81 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.58 MW | 8.58 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 8.6 MW | 8.6 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.77 MW | 6.77 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.77 MW | 6.77 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 20.5 MW | 20.5 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 7.07 MW | 7.07 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 7.07 MW | 7.07 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.95 MW | 3.95 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.95 MW | 3.95 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.93 MW | 10.93 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 4.09 MW | 4.09 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 4.09 MW | 4.09 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 3.35 MW | 3.35 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 13.76 MW | 13.76 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.3 MW | 1.3 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.98 MW | 0.98 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.62 MW | 0.62 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 2.12 MW | 2.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 2.02 MW | 2.02 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.64 MW | 7.64 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.64 MW | 7.64 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 3.87 MW | 3.87 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.4 MW | 2.4 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.81 MW | 1.81 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 5.94 MW | 5.94 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 39.19 MW | 39.19 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.67 MW | 6.67 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.24 MW | 2.24 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 7.01 MW | 7.01 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 10.58 MW | 10.58 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 13.64 MW | 13.64 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.24 MW | 8.24 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.27 MW | 1.27 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.73 MW | 2.73 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 6.2 MW | 6.2 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.23 MW | 1.23 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.15 MW | 2.15 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.7 MW | 1.7 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 8.34 MW | 8.34 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.53 MW | 0.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.44 MW | 1.44 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 26.61 MW | 26.61 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 14.98 MW | 14.98 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.71 MW | 0.71 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.47 MW | 6.47 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.51 MW | 9.51 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.43 MW | 7.43 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 4.24 MW | 4.24 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.75 MW | 2.75 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 3.68 MW | 3.68 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 15.09 MW | 15.09 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.37 MW | 6.37 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 80/20 | 63.14 MW | 63.14 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 | 80/20 | 52.85 MW | 52.85 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314435 | 6SAPONY | 80/20 | 1.74 MW | 1.74 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.96 MW | 0.96 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 5.94 MW | 5.94 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.81 MW | 1.81 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.93 MW | 0.93 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 2.57 MW | 2.57 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 2.94 MW | 2.94 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 2.94 MW | 2.94 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.31 MW | 0.31 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 | 80/20 | 11.6 MW | 11.6 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.39 MW | 5.39 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.46 MW | 7.46 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 15.12 MW | 15.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 10.9 MW | 10.9 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965281 | AG1-393 C | 80/20 | 8.87 MW | 8.87 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.24 MW | 1.24 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.99 MW | 1.99 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.12 MW | 33.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.81 MW | 10.81 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.27 MW | 11.27 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.02 MW | 3.02 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.64 MW | 2.64 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.54 MW | 1.54 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.34 MW | 0.34 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.84 MW | 0.84 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.46 MW | 0.46 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.82 MW | 1.82 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.82 MW | 1.82 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 10.3 MW | 10.3 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 5.02 MW | 5.02 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.56 MW | 10.56 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.11 MW | 5.11 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.55 MW | 1.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.55 MW | 1.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.55 MW | 1.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.09 MW | 9.09 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 5.28 MW | 5.28 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.62 MW | 1.62 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 3.12 MW | 3.12 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.55 MW | 1.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.81 MW | 1.81 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.58 MW | 8.58 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 8.6 MW | 8.6 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.78 MW | 6.78 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.78 MW | 6.78 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 20.51 MW | 20.51 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 7.08 MW | 7.08 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 7.08 MW | 7.08 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.95 MW | 3.95 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.95 MW | 3.95 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.94 MW | 10.94 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 4.09 MW | 4.09 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 4.09 MW | 4.09 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 3.35 MW | 3.35 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 13.76 MW | 13.76 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.3 MW | 1.3 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.98 MW | 0.98 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.62 MW | 0.62 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 2.12 MW | 2.12 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 2.02 MW | 2.02 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.64 MW | 7.64 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.64 MW | 7.64 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 3.87 MW | 3.87 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.4 MW | 2.4 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.81 MW | 1.81 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 5.94 MW | 5.94 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 39.2 MW | 39.2 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.67 MW | 6.67 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.24 MW | 2.24 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 7.02 MW | 7.02 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 10.59 MW | 10.59 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 13.64 MW | 13.64 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.25 MW | 8.25 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.28 MW | 1.28 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.73 MW | 2.73 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 6.2 MW | 6.2 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.23 MW | 1.23 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.15 MW | 2.15 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.7 MW | 1.7 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 8.35 MW | 8.35 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.53 MW | 0.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.45 MW | 1.45 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 26.62 MW | 26.62 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 14.98 MW | 14.98 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.71 MW | 0.71 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.48 MW | 6.48 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.52 MW | 9.52 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.43 MW | 7.43 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 4.24 MW | 4.24 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.75 MW | 2.75 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 3.68 MW | 3.68 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 15.09 MW | 15.09 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.37 MW | 6.37 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 80/20 | 63.15 MW | 63.15 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 | 80/20 | 52.86 MW | 52.86 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.96 MW | 0.96 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 5.94 MW | 5.94 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.81 MW | 1.81 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.93 MW | 0.93 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 2.57 MW | 2.57 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 2.94 MW | 2.94 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 2.94 MW | 2.94 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.31 MW | 0.31 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.39 MW | 5.39 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.46 MW | 7.46 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 15.12 MW | 15.12 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 10.9 MW | 10.9 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.24 MW | 1.24 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.0 MW | 2.0 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.19 MW | 33.19 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.91 MW | 10.91 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.33 MW | 11.33 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.02 MW | 3.02 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.65 MW | 2.65 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.55 MW | 1.55 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.13 MW | 2.13 MW |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
Details for 6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.91 MW | 0.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.72 MW | 0.72 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 2.87 MW | 2.87 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 2.87 MW | 2.87 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 2.54 MW | 2.54 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 1.24 MW | 1.24 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 3.88 MW | 3.88 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 2.75 MW | 2.75 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 1.69 MW | 1.69 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.22 MW | 1.22 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 2.12 MW | 2.12 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 14.85 MW | 14.85 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 14.85 MW | 14.85 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 24.19 MW | 24.19 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 3.53 MW | 3.53 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 3.53 MW | 3.53 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 8.66 MW | 8.66 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 8.66 MW | 8.66 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 12.9 MW | 12.9 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 2.04 MW | 2.04 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 2.04 MW | 2.04 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 0.74 MW | 0.74 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 4.45 MW | 4.45 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.07 MW | 1.07 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.24 MW | 0.24 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.54 MW | 0.54 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.19 MW | 0.19 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 1.15 MW | 1.15 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 1.1 MW | 1.1 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 6.2 MW | 6.2 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 6.2 MW | 6.2 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 1.9 MW | 1.9 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 1.18 MW | 1.18 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 0.89 MW | 0.89 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 2.79 MW | 2.79 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.17 MW | 0.17 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.48 MW | 0.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.48 MW | 0.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.48 MW | 0.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.48 MW | 0.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.14 MW | 0.14 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 18.45 MW | 18.45 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.61 MW | 6.61 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.22 MW | 2.22 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 9.27 MW | 9.27 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 8.32 MW | 8.32 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 8.14 MW | 8.14 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | 80/20 | 58.63 MW | 58.63 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 2.01 MW | 2.01 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.22 MW | 2.22 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 1.37 MW | 1.37 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.48 MW | 0.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.48 MW | 0.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315293 | 1DOMTR9 | 80/20 | 7.61 MW | 7.61 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315294 | 1DOMTR10 | 80/20 | 9.32 MW | 9.32 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.46 MW | 1.46 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 1.48 MW | 1.48 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.38 MW | 1.38 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 4.32 MW | 4.32 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.84 MW | 0.84 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.18 MW | 1.18 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 12.53 MW | 12.53 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 4.84 MW | 4.84 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 1.27 MW | 1.27 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 5.26 MW | 5.26 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.43 MW | 9.43 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 3.46 MW | 3.46 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 940491 | AE2-034 C | 80/20 | 5.5 MW | 5.5 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 3.45 MW | 3.45 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.28 MW | 1.28 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 0.81 MW | 0.81 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 16.91 MW | 16.91 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 957531 | AF2-047 C | 80/20 | 13.06 MW | 13.06 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 8.42 MW | 8.42 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 943611 | AF1-032 C | Adder | -0.89 MW | -0.76 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 2.79 MW | 2.79 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315292 | 1DOMTR78 | 80/20 | 1.59 MW | 1.59 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.05 MW | 1.05 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.61 MW | 0.61 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 0.75 MW | 0.75 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 0.51 MW | 0.51 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 0.51 MW | 0.51 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.73 MW | 0.73 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 957491 | AF2-043 C | Adder | -1.09 MW | -0.93 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 11.34 MW | 11.34 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 6.05 MW | 6.05 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 16.94 MW | 16.94 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 5.13 MW | 5.13 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 2.93 MW | 2.93 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | 315614 | AA2-178 C | 80/20 | 1.25 MW | 1.25 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.96 MW | 1.96 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.52 MW | 0.52 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 32.15 MW | 32.15 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.1 MW | 11.1 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.18 MW | 11.18 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.97 MW | 2.97 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.6 MW | 2.6 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.54 MW | 0.54 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.55 MW | 1.55 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.08 MW | 2.08 MW |
6EARLEYS-6NUCO TP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
Details for 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 0.83 MW | 0.83 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.54 MW | 0.54 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.17 MW | 2.17 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.17 MW | 2.17 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 1.99 MW | 1.99 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 0.97 MW | 0.97 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 3.06 MW | 3.06 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 3.29 MW | 3.29 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 1.32 MW | 1.32 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 0.97 MW | 0.97 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 1.66 MW | 1.66 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 20.88 MW | 20.88 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 20.88 MW | 20.88 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 22.31 MW | 22.31 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 2.8 MW | 2.8 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 2.8 MW | 2.8 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 12.18 MW | 12.18 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 12.18 MW | 12.18 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 11.9 MW | 11.9 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 1.62 MW | 1.62 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 1.62 MW | 1.62 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 0.57 MW | 0.57 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 3.47 MW | 3.47 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 0.88 MW | 0.88 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 0.19 MW | 0.19 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.41 MW | 0.41 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.16 MW | 0.16 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.12 MW | 0.12 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 0.9 MW | 0.9 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 0.86 MW | 0.86 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 5.4 MW | 5.4 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 5.4 MW | 5.4 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 1.5 MW | 1.5 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 0.93 MW | 0.93 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 0.7 MW | 0.7 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 2.18 MW | 2.18 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 0.39 MW | 0.39 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 0.39 MW | 0.39 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 0.39 MW | 0.39 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 0.39 MW | 0.39 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.12 MW | 0.12 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 14.41 MW | 14.41 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 5.21 MW | 5.21 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 1.75 MW | 1.75 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 8.66 MW | 8.66 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 6.66 MW | 6.66 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 6.73 MW | 6.73 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 142.12 MW | 142.12 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.52 MW | 1.52 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 1.9 MW | 1.9 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 1.06 MW | 1.06 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 0.39 MW | 0.39 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 0.39 MW | 0.39 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 15.75 MW | 15.75 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 19.3 MW | 19.3 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.34 MW | 1.34 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 1.14 MW | 1.14 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 1.19 MW | 1.19 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 3.4 MW | 3.4 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.63 MW | 0.63 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.01 MW | 1.01 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 9.79 MW | 9.79 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 3.77 MW | 3.77 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 2.12 MW | 2.12 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 4.52 MW | 4.52 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 7.42 MW | 7.42 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 2.76 MW | 2.76 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 22.88 MW | 22.88 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 2.96 MW | 2.96 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 1.02 MW | 1.02 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 0.63 MW | 0.63 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 12.99 MW | 12.99 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 54.36 MW | 54.36 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 7.87 MW | 7.87 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 937221 | AD2-160 C O1 | Adder | -2.93 MW | -2.49 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 942401 | AE2-253 C | Adder | -3.09 MW | -2.62 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 2.18 MW | 2.18 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 3.29 MW | 3.29 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 0.83 MW | 0.83 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 0.49 MW | 0.49 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315611 | 6Z1-036WIND | 80/20 | 2.99 MW | 2.99 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 0.59 MW | 0.59 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 0.4 MW | 0.4 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 0.4 MW | 0.4 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.55 MW | 0.55 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 20.21 MW | 20.21 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 5.27 MW | 5.27 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 13.02 MW | 13.02 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 4.01 MW | 4.01 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 2.19 MW | 2.19 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 5.2 MW | 5.2 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.75 MW | 1.75 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.46 MW | 0.46 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 28.65 MW | 28.65 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.73 MW | 9.73 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.88 MW | 9.88 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.66 MW | 2.66 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.3 MW | 2.3 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.47 MW | 0.47 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.37 MW | 1.37 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.22 MW | 0.22 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.84 MW | 1.84 MW |
6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
Details for 6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 0.83 MW | 0.83 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.54 MW | 0.54 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.17 MW | 2.17 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.17 MW | 2.17 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 1.99 MW | 1.99 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 0.97 MW | 0.97 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 3.06 MW | 3.06 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 3.29 MW | 3.29 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 1.32 MW | 1.32 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 0.97 MW | 0.97 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 1.66 MW | 1.66 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 20.88 MW | 20.88 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 20.88 MW | 20.88 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 22.31 MW | 22.31 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 2.8 MW | 2.8 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 2.8 MW | 2.8 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 12.18 MW | 12.18 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 12.18 MW | 12.18 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 11.9 MW | 11.9 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 1.62 MW | 1.62 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 1.62 MW | 1.62 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 0.57 MW | 0.57 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 3.47 MW | 3.47 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 0.88 MW | 0.88 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 0.19 MW | 0.19 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.41 MW | 0.41 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.16 MW | 0.16 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.12 MW | 0.12 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 0.9 MW | 0.9 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 0.86 MW | 0.86 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 5.4 MW | 5.4 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 5.4 MW | 5.4 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 1.5 MW | 1.5 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 0.93 MW | 0.93 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 0.7 MW | 0.7 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 2.18 MW | 2.18 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 0.39 MW | 0.39 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 0.39 MW | 0.39 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 0.39 MW | 0.39 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 0.39 MW | 0.39 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.12 MW | 0.12 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 14.41 MW | 14.41 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 5.21 MW | 5.21 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 1.75 MW | 1.75 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 8.66 MW | 8.66 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 6.66 MW | 6.66 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 6.73 MW | 6.73 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 142.12 MW | 142.12 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.52 MW | 1.52 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 1.9 MW | 1.9 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 1.06 MW | 1.06 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 0.39 MW | 0.39 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 0.39 MW | 0.39 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 15.75 MW | 15.75 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 19.3 MW | 19.3 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.34 MW | 1.34 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 1.14 MW | 1.14 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 1.19 MW | 1.19 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 3.4 MW | 3.4 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.63 MW | 0.63 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.01 MW | 1.01 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 9.79 MW | 9.79 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 3.77 MW | 3.77 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 2.12 MW | 2.12 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 4.52 MW | 4.52 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 7.42 MW | 7.42 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 2.76 MW | 2.76 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 22.88 MW | 22.88 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 2.96 MW | 2.96 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 1.02 MW | 1.02 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 0.63 MW | 0.63 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 12.99 MW | 12.99 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 54.36 MW | 54.36 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 7.87 MW | 7.87 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 937221 | AD2-160 C O1 | Adder | -2.93 MW | -2.49 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 942401 | AE2-253 C | Adder | -3.09 MW | -2.62 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 2.18 MW | 2.18 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 3.29 MW | 3.29 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 0.83 MW | 0.83 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 0.49 MW | 0.49 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315611 | 6Z1-036WIND | 80/20 | 2.99 MW | 2.99 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 0.59 MW | 0.59 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 0.4 MW | 0.4 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 0.4 MW | 0.4 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.55 MW | 0.55 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 20.21 MW | 20.21 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 5.27 MW | 5.27 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 13.02 MW | 13.02 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 4.01 MW | 4.01 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 2.19 MW | 2.19 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 5.2 MW | 5.2 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.75 MW | 1.75 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.46 MW | 0.46 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 28.65 MW | 28.65 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 9.73 MW | 9.73 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.88 MW | 9.88 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.66 MW | 2.66 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.3 MW | 2.3 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.47 MW | 0.47 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.37 MW | 1.37 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.22 MW | 0.22 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.84 MW | 1.84 MW |
6PERQUIMANS-6S HERTFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.84 MW | 0.84 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 961891 | AG1-030 C | 80/20 | 7.57 MW | 7.57 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.46 MW | 0.46 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.82 MW | 1.82 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.82 MW | 1.82 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 10.3 MW | 10.3 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 5.02 MW | 5.02 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.56 MW | 10.56 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.11 MW | 5.11 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.55 MW | 1.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.55 MW | 1.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.55 MW | 1.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.09 MW | 9.09 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 2.04 MW | 2.04 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 5.28 MW | 5.28 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.62 MW | 1.62 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 3.12 MW | 3.12 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.55 MW | 1.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.81 MW | 1.81 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.58 MW | 8.58 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 8.6 MW | 8.6 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.78 MW | 6.78 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.78 MW | 6.78 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 20.51 MW | 20.51 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 7.08 MW | 7.08 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 7.08 MW | 7.08 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.95 MW | 3.95 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.95 MW | 3.95 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.94 MW | 10.94 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 4.09 MW | 4.09 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 4.09 MW | 4.09 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 3.35 MW | 3.35 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 13.76 MW | 13.76 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.3 MW | 1.3 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.98 MW | 0.98 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.62 MW | 0.62 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 2.12 MW | 2.12 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 2.02 MW | 2.02 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.64 MW | 7.64 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.64 MW | 7.64 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 3.87 MW | 3.87 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.4 MW | 2.4 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.81 MW | 1.81 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 5.94 MW | 5.94 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 39.2 MW | 39.2 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.67 MW | 6.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.24 MW | 2.24 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 7.02 MW | 7.02 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 10.59 MW | 10.59 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 13.64 MW | 13.64 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | 80/20 | 29.78 MW | 29.78 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.25 MW | 8.25 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.28 MW | 1.28 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.73 MW | 2.73 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 6.84 MW | 6.84 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 9.67 MW | 9.67 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 6.2 MW | 6.2 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315293 | 1DOMTR9 | 80/20 | 4.04 MW | 4.04 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315294 | 1DOMTR10 | 80/20 | 4.95 MW | 4.95 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.23 MW | 1.23 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.15 MW | 2.15 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.7 MW | 1.7 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 8.35 MW | 8.35 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.53 MW | 0.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.45 MW | 1.45 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 26.62 MW | 26.62 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 14.98 MW | 14.98 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.71 MW | 0.71 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.48 MW | 6.48 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.52 MW | 9.52 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.43 MW | 7.43 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 4.24 MW | 4.24 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.75 MW | 2.75 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 3.68 MW | 3.68 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 15.09 MW | 15.09 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.37 MW | 6.37 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.96 MW | 0.96 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 5.94 MW | 5.94 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315292 | 1DOMTR78 | 80/20 | 0.84 MW | 0.84 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.81 MW | 1.81 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.93 MW | 0.93 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 2.57 MW | 2.57 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 2.94 MW | 2.94 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 2.94 MW | 2.94 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.31 MW | 0.31 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.39 MW | 5.39 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.46 MW | 7.46 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 4.79 MW | 4.79 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 15.12 MW | 15.12 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 10.9 MW | 10.9 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.24 MW | 1.24 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.0 MW | 2.0 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.19 MW | 33.19 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.91 MW | 10.91 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.33 MW | 11.33 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.02 MW | 3.02 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.65 MW | 2.65 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.55 MW | 1.55 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.13 MW | 2.13 MW |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
Details for 6S HERTFORD-6WINFALL 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
---|---|---|---|---|---|
Monitored Fac/Ctg | Bu |