AG1-432 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:56
Curdsville DP-Willis Mt. 115 kV
120.0 MW Capacity / 200.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-432 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Buckingham County, Virginia. The installed facilities will have a total capability of 200.0 MW with 120.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-432 |
| Project Name | Curdsville DP-Willis Mt. 115 kV |
| Developer Name | ACE Development Company II, LLC |
| State | Virginia |
| County | Buckingham |
| Transmission Owner | Dominion |
| MFO | 200.0 MW |
| MWE | 200.0 MW |
| MWC | 120.0 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-432 "Curdsville DP-Willis Mt. 115 kV" will interconnect with the Dominion transmission system. The primary POI will be a newly constructed 115 kV three breaker ring bus located on the line between the Curdsville DP substation and Willis Mt. substation. However, for modeling and analysis purpose, it is connected directly to Willis Mountain 115 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 120.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 293.15 % | 351.44 % | 205.86 | B | 723.47 | 120.0 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 256.72 % | 315.01 % | 205.86 | B | 648.48 | 120.0 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 235-A
CONTINGENCY 'DVP_P1-2: LN 235-A' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Single | AC | 218.99 % | 258.61 % | 182.64 | B | 472.33 | 73.68 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 192.37 % | 222.92 % | 182.64 | B | 407.13 | 55.78 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 180.95 % | 192.32 % | 559.3 | B | 1075.67 | 60.41 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 178.39 % | 189.55 % | 571.52 | B | 1083.33 | 60.4 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
Base Case | Single | AC | 136.56 % | 188.77 % | 186.12 | A | 351.34 | 100.11 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 180.47 % | 191.7 % | 559.3 | B | 1072.18 | 60.41 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 178.55 % | 189.73 % | 571.52 | B | 1084.35 | 60.4 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 298
CONTINGENCY 'DVP_P1-2: LN 298' OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Single | AC | 138.76 % | 172.08 % | 198.06 | B | 340.82 | 66.92 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 156.35 % | 160.82 % | 718.0 | B | 1154.69 | 29.38 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 154.14 % | 158.9 % | 674.92 | B | 1072.45 | 29.38 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
Base Case | Single | AC | 129.17 % | 156.5 % | 176.81 | A | 276.71 | 48.39 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 156.5 % | 160.99 % | 718.0 | B | 1155.91 | 29.38 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 138.31 % | 161.0 % | 198.06 | B | 318.87 | 44.93 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 154.15 % | 158.9 % | 674.92 | B | 1072.46 | 29.38 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 556-A
CONTINGENCY 'DVP_P1-2: LN 556-A' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 2 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 OPEN BUS 314906 /*8CLOVER 500.0 OPEN BUS 314915 /*8CLOVER_STC 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 142.4 % | 146.16 % | 182.64 | B | 266.95 | 6.9 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
314906 8CLOVER 500 945810 AF1-246 TAP 500 1
CONTINGENCY '314906 8CLOVER 500 945810 AF1-246 TAP 500 1' /* Auto-generated /* 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 END |
Single | AC | 142.31 % | 146.07 % | 182.64 | B | 266.79 | 6.9 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
Base Case | Single | AC | 148.27 % | 156.06 % | 247.22 | A | 385.81 | 19.89 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 146.79 % | 152.24 % | 661.76 | B | 1007.49 | 36.99 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 142.8 % | 148.25 % | 661.76 | B | 981.04 | 36.99 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 142.58 % | 148.03 % | 661.76 | B | 979.62 | 36.99 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 140.18 % | 147.51 % | 269.78 | B | 397.96 | 20.45 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
313868 6CARTERV 230 933500 AC2-165 TAP 230 1
CONTINGENCY '313868 6CARTERV 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 140.07 % | 147.41 % | 269.78 | B | 397.67 | 20.45 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 139.45 % | 144.89 % | 661.76 | B | 958.81 | 36.99 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 138.59 % | 144.04 % | 661.76 | B | 953.18 | 36.99 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 135.69 % | 141.48 % | 678.68 | B | 960.18 | 40.65 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 135.58 % | 141.04 % | 661.76 | B | 933.38 | 36.99 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 133.59 % | 139.38 % | 678.68 | B | 945.91 | 40.65 | |
| DVP |
AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line
935170 to 314697 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 123.93 % | 127.28 % | 814.98 | B | 1037.33 | 25.57 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 131.6 % | 137.43 % | 678.68 | B | 932.69 | 40.65 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 129.51 % | 135.33 % | 678.68 | B | 918.46 | 40.65 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P1-2: LN 298
CONTINGENCY 'DVP_P1-2: LN 298' OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Single | AC | 127.56 % | 138.05 % | 269.78 | B | 372.42 | 28.75 | |
| DVP |
6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line
314690 to 935170 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 118.3 % | 121.62 % | 814.98 | B | 991.18 | 25.57 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
Base Case | Single | AC | 123.97 % | 131.76 % | 247.22 | A | 325.74 | 19.89 | |
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193
CONTINGENCY 'DVP_P1-2: LN 2193' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 125.02 % | 131.29 % | 269.78 | B | 354.21 | 17.69 | |
| DVP |
AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line
935170 to 314697 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 124.09 % | 127.5 % | 814.98 | B | 1039.11 | 25.57 | |
| DVP |
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
314696 to 314697 ckt 1 |
DVP_P1-3: 6SEDGE HILL-TX#2
CONTINGENCY 'DVP_P1-3: 6SEDGE HILL-TX#2' OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2 /*3SEDGE HILL 115.0 - 6SEDGE HILL 230.0 END |
Single | AC | 110.72 % | 113.57 % | 242.52 | B | 275.43 | 6.93 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 117.96 % | 125.31 % | 269.78 | B | 338.05 | 20.45 | |
| DVP |
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1 |
DVP_P1-2: LN 553
CONTINGENCY 'DVP_P1-2: LN 553' OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 END |
Single | AC | 119.19 % | 120.56 % | 550.84 | B | 664.07 | 7.32 | |
| DVP |
6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line
314690 to 935170 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 118.44 % | 121.81 % | 814.98 | B | 992.76 | 25.57 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 103.89 % | 106.2 % | 285.76 | B | 303.48 | 6.38 | |
| DVP |
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
314696 to 314697 ckt 2 |
DVP_P1-3: 6SEDGE HILL-TX#1
CONTINGENCY 'DVP_P1-3: 6SEDGE HILL-TX#1' OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1 /*3SEDGE HILL 115.0 - 6SEDGE HILL 230.0 END |
Single | AC | 104.56 % | 107.26 % | 256.06 | B | 274.64 | 6.91 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
Base Case | Single | AC | 93.15 % | 113.23 % | 193.73 | A | 219.35 | 38.98 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 102.83 % | 105.14 % | 285.76 | B | 300.45 | 6.38 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 101.77 % | 104.22 % | 269.78 | B | 281.16 | 6.38 | |
| DVP |
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1 |
DVP_P1-2: LN 550
CONTINGENCY 'DVP_P1-2: LN 550' OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1 /*8MT STM 500.0 - 8VALLEY 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 END |
Single | AC | 113.04 % | 114.85 % | 550.84 | B | 632.62 | 9.5 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P1-2: LN 298
CONTINGENCY 'DVP_P1-2: LN 298' OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Single | AC | 105.77 % | 116.33 % | 269.78 | B | 313.84 | 28.75 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
Base Case | Single | AC | 101.15 % | 110.44 % | 559.3 | A | 617.67 | 52.09 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 110.7 % | 114.46 % | 800.88 | B | 916.66 | 30.1 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 110.69 % | 114.45 % | 800.88 | B | 916.59 | 30.1 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 110.66 % | 114.42 % | 800.88 | B | 916.33 | 30.1 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 110.65 % | 114.41 % | 800.88 | B | 916.25 | 30.1 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
Base Case | Single | AC | 100.16 % | 109.25 % | 571.52 | A | 624.41 | 52.08 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 110.05 % | 113.8 % | 800.88 | B | 911.43 | 30.11 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 110.04 % | 113.79 % | 800.88 | B | 911.35 | 30.11 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 103.72 % | 106.01 % | 285.76 | B | 302.94 | 6.38 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 102.66 % | 104.95 % | 285.76 | B | 299.9 | 6.38 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 101.59 % | 104.02 % | 269.78 | B | 280.64 | 6.38 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 106.08 % | 110.1 % | 169.2 | B | 186.29 | 6.79 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
Base Case | Single | AC | 101.31 % | 109.16 % | 247.22 | A | 269.85 | 19.89 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 105.74 % | 109.75 % | 169.2 | B | 185.7 | 6.79 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 104.71 % | 108.47 % | 800.88 | B | 868.68 | 30.11 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 104.7 % | 108.46 % | 800.88 | B | 868.61 | 30.11 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 103.44 % | 107.19 % | 800.88 | B | 858.49 | 30.11 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 103.43 % | 107.18 % | 800.88 | B | 858.41 | 30.11 | |
| DVP |
6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line
314759 to 314734 ckt 1 |
DVP_P1-2: LN 553
CONTINGENCY 'DVP_P1-2: LN 553' OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 END |
Single | AC | 103.8 % | 105.17 % | 550.84 | B | 579.3 | 7.32 | |
| DVP |
6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line
314734 to 314758 ckt 1 |
DVP_P1-2: LN 553
CONTINGENCY 'DVP_P1-2: LN 553' OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 END |
Single | AC | 103.77 % | 105.14 % | 550.84 | B | 579.13 | 7.32 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 97.15 % | 104.54 % | 269.78 | B | 282.04 | 20.45 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
313868 6CARTERV 230 933500 AC2-165 TAP 230 1
CONTINGENCY '313868 6CARTERV 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 97.03 % | 104.43 % | 269.78 | B | 281.73 | 20.45 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P1-2: LN 2028-C
CONTINGENCY 'DVP_P1-2: LN 2028-C' OPEN BRANCH FROM BUS 313707 TO BUS 961060 CKT 1 /*6FORK UNION 230.0 - AF2-397 TAP 230.0 END |
Single | AC | 98.87 % | 102.63 % | 800.88 | B | 821.97 | 30.11 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 371.02 % | 424.08 % | 208.7 | C | 885.06 | 110.73 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 265.48 % | 322.78 % | 349.0 | C | 1126.5 | 199.99 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 265.48 % | 322.78 % | 349.0 | C | 1126.5 | 199.99 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 281.69 % | 321.97 % | 221.4 | C | 712.84 | 89.19 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 229.66 % | 286.97 % | 349.0 | C | 1001.51 | 199.99 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 229.66 % | 286.97 % | 349.0 | C | 1001.51 | 199.99 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 206.07 % | 252.27 % | 221.4 | C | 558.52 | 111.53 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 195.68 % | 252.99 % | 349.0 | C | 882.92 | 199.99 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 195.68 % | 252.99 % | 349.0 | C | 882.92 | 199.99 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 204.1 % | 218.93 % | 684.0 | C | 1497.49 | 100.72 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 204.09 % | 218.93 % | 684.0 | C | 1497.47 | 100.72 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 204.04 % | 218.88 % | 684.0 | C | 1497.12 | 100.72 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 201.24 % | 215.76 % | 699.0 | C | 1508.14 | 100.71 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 201.24 % | 215.75 % | 699.0 | C | 1508.13 | 100.71 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 201.19 % | 215.7 % | 699.0 | C | 1507.77 | 100.71 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 153.8 % | 211.1 % | 349.0 | C | 736.75 | 199.99 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 153.8 % | 211.1 % | 349.0 | C | 736.75 | 199.99 | |
| DVP |
3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line
314679 to 963320 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 152.71 % | 210.01 % | 349.0 | C | 732.94 | 199.99 | |
| DVP |
3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line
314679 to 963320 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 152.71 % | 210.01 % | 349.0 | C | 732.94 | 199.99 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-6: CAROLIN T122
CONTINGENCY 'DVP_P4-6: CAROLIN T122' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314578 CKT 1 /*3CAROLNA 115.0 - 3HORNRTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 315126 CKT 1 /*3CAROLNA 115.0 - 1ROARAP2 14.4 OPEN BRANCH FROM BUS 314559 TO BUS 315128 CKT 1 /*3CAROLNA 115.0 - 1ROARAP4 14.4 OPEN BUS 314559 /*3CAROLNA 115.0 OPEN BUS 314835 /*3CAROL_1 115.0 OPEN BUS 315126 /*1ROARAP2 14.4 OPEN BUS 315128 /*1ROARAP4 14.4 END |
Breaker | AC | 164.31 % | 170.41 % | 199.0 | B | 339.11 | 14.77 | |
| DVP |
3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line
313898 to 314267 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 166.54 % | 196.23 % | 349.0 | C | 684.86 | 103.64 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 164.21 % | 191.8 % | 349.0 | C | 669.39 | 96.28 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 141.86 % | 147.33 % | 199.0 | B | 293.18 | 12.89 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 141.86 % | 147.32 % | 199.0 | B | 293.18 | 12.89 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 132.54 % | 160.12 % | 349.0 | C | 558.83 | 96.28 | |
| DVP |
3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line
314679 to 963320 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 131.45 % | 159.03 % | 349.0 | C | 555.03 | 96.28 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 134.8 % | 149.01 % | 406.0 | C | 604.97 | 59.28 | |
| DVP |
AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line
936260 to 313898 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 125.47 % | 151.4 % | 400.0 | C | 605.6 | 103.7 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 132.53 % | 146.57 % | 406.0 | C | 595.09 | 59.05 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 131.13 % | 145.18 % | 406.0 | C | 589.44 | 59.08 | |
| DVP |
AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line
961890 to 314725 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 116.26 % | 145.97 % | 349.0 | C | 509.45 | 103.7 | |
| DVP |
3VICT DP-3VICTRIA 115.0 kV Ckt 1 line
314725 to 314723 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 115.29 % | 145.0 % | 349.0 | C | 506.05 | 103.7 | |
| DVP |
AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line
959310 to 314722 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 98.84 % | 143.09 % | 452.0 | C | 646.76 | 200.0 | |
| DVP |
AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line
959310 to 314722 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 98.84 % | 143.09 % | 452.0 | C | 646.76 | 200.0 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 131.72 % | 138.0 % | 809.0 | C | 1116.42 | 51.96 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 131.72 % | 138.0 % | 809.0 | C | 1116.41 | 51.96 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 131.7 % | 137.98 % | 809.0 | C | 1116.26 | 51.96 | |
| DVP |
3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line
314684 to 316115 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 122.91 % | 137.01 % | 406.0 | C | 556.28 | 59.28 | |
| DVP |
3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line
314684 to 316115 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 121.19 % | 135.24 % | 406.0 | C | 549.09 | 59.05 | |
| DVP |
3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line
314684 to 316115 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 119.8 % | 133.85 % | 406.0 | C | 543.44 | 59.08 | |
| DVP |
AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line
962560 to 314684 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 117.97 % | 132.04 % | 406.0 | C | 536.07 | 59.28 | |
| DVP |
AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line
962560 to 314684 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 116.27 % | 130.29 % | 406.0 | C | 528.97 | 59.05 | |
| DVP |
3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line
313825 to 314696 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | AC | 110.11 % | 123.09 % | 172.0 | C | 211.72 | 26.2 | |
| DVP |
AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line
962560 to 314684 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 114.87 % | 128.9 % | 406.0 | C | 523.32 | 59.08 | |
| DVP |
3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line
313825 to 314696 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | AC | 107.56 % | 120.46 % | 172.0 | C | 207.19 | 26.04 | |
| DVP |
3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line
313825 to 314696 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | AC | 106.0 % | 118.9 % | 172.0 | C | 204.51 | 26.03 | |
| DVP |
3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line
314723 to 314427 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 99.38 % | 125.31 % | 400.0 | C | 501.22 | 103.7 | |
| DVP |
3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line
314267 to 314669 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 105.8 % | 119.78 % | 406.0 | C | 486.31 | 59.28 | |
| DVP |
3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line
314669 to 962560 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 104.9 % | 118.88 % | 406.0 | C | 482.64 | 59.28 | |
| DVP |
3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line
314267 to 314669 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 104.13 % | 118.06 % | 406.0 | C | 479.33 | 59.05 | |
| DVP |
3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line
314427 to 936260 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 96.49 % | 122.42 % | 400.0 | C | 489.66 | 103.7 | |
| DVP |
AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line
959310 to 314722 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | AC | 93.69 % | 122.07 % | 452.0 | C | 551.77 | 96.29 | |
| DVP |
3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line
314669 to 962560 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 103.23 % | 117.16 % | 406.0 | C | 475.65 | 59.05 | |
| DVP |
3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line
314267 to 314669 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 102.73 % | 116.67 % | 406.0 | C | 473.68 | 59.08 | |
| DVP |
3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line
314669 to 962560 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 101.83 % | 115.76 % | 406.0 | C | 470.0 | 59.08 | |
| DVP |
AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line
962490 to 314686 ckt 1 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 106.97 % | 118.91 % | 699.0 | C | 831.15 | 84.67 | |
| DVP |
AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line
962490 to 314686 ckt 1 |
DVP_P4-2: 219322
CONTINGENCY 'DVP_P4-2: 219322' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 100.24 % | 118.18 % | 699.0 | C | 826.05 | 124.5 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 111.02 % | 116.08 % | 980.0 | C | 1137.63 | 50.16 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 110.98 % | 116.05 % | 980.0 | C | 1137.26 | 50.16 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 110.65 % | 115.71 % | 980.0 | C | 1133.98 | 50.16 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 110.61 % | 115.67 % | 980.0 | C | 1133.62 | 50.16 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 109.84 % | 115.05 % | 980.0 | C | 1127.46 | 50.19 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 109.46 % | 114.66 % | 980.0 | C | 1123.65 | 50.19 | |
| DVP |
3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line
314706 to 961890 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 82.18 % | 111.89 % | 349.0 | C | 390.5 | 103.7 | |
| DVP |
3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line
314681 to 314708 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 97.12 % | 106.61 % | 400.0 | C | 426.44 | 38.67 | |
| DVP |
3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line
314704 to 314693 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 96.83 % | 106.34 % | 400.0 | C | 425.38 | 38.66 | |
| DVP |
3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line
314715 to 959310 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 61.89 % | 106.14 % | 452.0 | C | 479.76 | 200.0 | |
| DVP |
3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line
314715 to 959310 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 61.89 % | 106.14 % | 452.0 | C | 479.76 | 200.0 | |
| DVP |
3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line
314676 to 314704 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 96.56 % | 106.08 % | 400.0 | C | 424.33 | 38.67 | |
| DVP |
3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line
314681 to 314708 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 96.33 % | 105.96 % | 400.0 | C | 423.83 | 38.53 | |
| DVP |
3NORVIEW-3SO HILL 115.0 kV Ckt 1 line
314708 to 314721 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 96.35 % | 105.84 % | 400.0 | C | 423.36 | 38.67 | |
| DVP |
3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line
314704 to 314693 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 96.06 % | 105.69 % | 400.0 | C | 422.76 | 38.52 | |
| DVP |
3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line
314681 to 314708 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 96.17 % | 105.66 % | 400.0 | C | 422.63 | 38.65 | |
| DVP |
3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line
314693 to 314565 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 95.96 % | 105.47 % | 400.0 | C | 421.9 | 38.66 | |
| DVP |
3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line
314676 to 314704 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 95.8 % | 105.43 % | 400.0 | C | 421.71 | 38.53 | |
| DVP |
3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line
314704 to 314693 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 95.88 % | 105.39 % | 400.0 | C | 421.57 | 38.64 | |
| DVP |
3NORVIEW-3SO HILL 115.0 kV Ckt 1 line
314708 to 314721 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 95.56 % | 105.19 % | 400.0 | C | 420.76 | 38.53 | |
| DVP |
3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line
314676 to 314704 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 95.62 % | 105.13 % | 400.0 | C | 420.52 | 38.65 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 103.27 % | 108.51 % | 980.0 | C | 1063.42 | 50.19 | |
| DVP |
AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line
934620 to 962490 ckt 1 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 96.15 % | 108.06 % | 699.0 | C | 755.31 | 84.67 | |
| DVP |
3NORVIEW-3SO HILL 115.0 kV Ckt 1 line
314708 to 314721 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 95.41 % | 104.89 % | 400.0 | C | 419.55 | 38.65 | |
| DVP |
3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line
314693 to 314565 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 95.19 % | 104.82 % | 400.0 | C | 419.28 | 38.52 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 102.9 % | 108.14 % | 980.0 | C | 1059.74 | 50.19 | |
| DVP |
3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line
314693 to 314565 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 95.01 % | 104.52 % | 400.0 | C | 418.09 | 38.64 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 102.21 % | 107.44 % | 980.0 | C | 1052.87 | 50.19 | |
| DVP |
AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line
934620 to 962490 ckt 1 |
DVP_P4-2: 210622
CONTINGENCY 'DVP_P4-2: 210622' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 87.68 % | 106.19 % | 699.0 | C | 742.25 | 124.5 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 101.84 % | 107.06 % | 980.0 | C | 1049.2 | 50.19 | |
| DVP |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer
314686 to 314906 ckt 2 |
DVP_P4-5: L912
CONTINGENCY 'DVP_P4-5: L912' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BUS 313817 /*6CLOVER_1 230.0 END |
Breaker | AC | 101.25 % | 104.34 % | 1275.1 | C | 1330.48 | 40.35 | |
| DVP |
AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line
962490 to 314686 ckt 1 |
DVP_P2-2: BREMO B1
CONTINGENCY 'DVP_P2-2: BREMO B1' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Bus | AC | 100.23 % | 118.17 % | 699.0 | C | 825.99 | 124.5 | |
| DVP |
AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line
934620 to 962490 ckt 1 |
DVP_P2-2: BREMO B1
CONTINGENCY 'DVP_P2-2: BREMO B1' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Bus | AC | 87.68 % | 106.19 % | 699.0 | C | 742.26 | 124.5 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P7-1: LN 22-90
CONTINGENCY 'DVP_P7-1: LN 22-90' OPEN BRANCH FROM BUS 314265 TO BUS 314584 CKT 1 /*3FIVEFORKSDP 115.0 - 3LITTLTN 115.0 OPEN BRANCH FROM BUS 314265 TO BUS 314673 CKT 1 /*3FIVEFORKSDP 115.0 - 3PALMERSPRNG 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314584 TO BUS 314585 CKT 1 /*3LITTLTN 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314265 /*3FIVEFORKSDP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 314584 /*3LITTLTN 115.0 OPEN BUS 314585 /*3L GASTN 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Tower | AC | 161.58 % | 167.6 % | 199.0 | B | 333.52 | 14.6 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 111.39 % | 116.46 % | 980.0 | C | 1141.35 | 50.16 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 111.39 % | 116.46 % | 980.0 | C | 1141.27 | 50.16 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 111.36 % | 116.43 % | 980.0 | C | 1140.97 | 50.16 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 111.35 % | 116.42 % | 980.0 | C | 1140.91 | 50.16 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 110.2 % | 115.4 % | 980.0 | C | 1130.96 | 50.19 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 110.19 % | 115.4 % | 980.0 | C | 1130.89 | 50.19 | |
| DVP |
3KERRDP-3KERR 115.0 kV Ckt 1 line
313705 to 314702 ckt 1 |
DVP_P7-1: LN 171-1009
CONTINGENCY 'DVP_P7-1: LN 171-1009' OPEN BRANCH FROM BUS 313806 TO BUS 314681 CKT 1 /*3HERBERT 115.0 - 3CHASCTY 115.0 OPEN BRANCH FROM BUS 313849 TO BUS 314267 CKT 1 /*3RIDGERD 115.0 - 3CHASCTY2 115.0 END |
Tower | AC | 104.12 % | 108.95 % | 195.0 | C | 212.45 | 11.11 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 106.93 % | 111.52 % | 208.0 | C | 231.97 | 11.32 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 106.65 % | 111.25 % | 208.0 | C | 231.39 | 11.32 | |
| DVP |
3ISLND C-3KERRDP 115.0 kV Ckt 1 line
314699 to 313705 ckt 1 |
DVP_P7-1: LN 171-1009
CONTINGENCY 'DVP_P7-1: LN 171-1009' OPEN BRANCH FROM BUS 313806 TO BUS 314681 CKT 1 /*3HERBERT 115.0 - 3CHASCTY 115.0 OPEN BRANCH FROM BUS 313849 TO BUS 314267 CKT 1 /*3RIDGERD 115.0 - 3CHASCTY2 115.0 END |
Tower | AC | 101.33 % | 105.99 % | 202.0 | C | 214.1 | 11.11 | |
| DVP |
3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line
314682 to 314665 ckt 1 |
DVP_P7-1: LN 171-1009
CONTINGENCY 'DVP_P7-1: LN 171-1009' OPEN BRANCH FROM BUS 313806 TO BUS 314681 CKT 1 /*3HERBERT 115.0 - 3CHASCTY 115.0 OPEN BRANCH FROM BUS 313849 TO BUS 314267 CKT 1 /*3RIDGERD 115.0 - 3CHASCTY2 115.0 END |
Tower | AC | 99.69 % | 104.22 % | 208.0 | C | 216.77 | 11.11 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 103.74 % | 108.81 % | 980.0 | C | 1066.38 | 50.19 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 103.73 % | 108.81 % | 980.0 | C | 1066.3 | 50.19 | |
| DVP |
3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line
314665 to 314699 ckt 1 |
DVP_P7-1: LN 171-1009
CONTINGENCY 'DVP_P7-1: LN 171-1009' OPEN BRANCH FROM BUS 313806 TO BUS 314681 CKT 1 /*3HERBERT 115.0 - 3CHASCTY 115.0 OPEN BRANCH FROM BUS 313849 TO BUS 314267 CKT 1 /*3RIDGERD 115.0 - 3CHASCTY2 115.0 END |
Tower | AC | 98.46 % | 102.98 % | 208.0 | C | 214.2 | 11.11 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 102.68 % | 107.74 % | 980.0 | C | 1055.87 | 50.19 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 102.67 % | 107.73 % | 980.0 | C | 1055.8 | 50.19 | |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 120.0 MW | 120.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 20.0 MW | 20.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965641 | AG1-432 C O1 | 80/20 | 120.0 MW | 120.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965831 | AG1-451 | 80/20 | 20.0 MW | 20.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961791 | AG1-021 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961891 | AG1-030 C | 80/20 | 37.77 MW | 37.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963171 | AG1-166 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963181 | AG1-167 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963191 | AG1-168 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963201 | AG1-169 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963211 | AG1-170 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963301 | AG1-179 C | 80/20 | 3.87 MW | 3.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963311 | AG1-180 | 80/20 | 1.89 MW | 1.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963321 | AG1-181 C O1 | 80/20 | 32.77 MW | 32.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963361 | AG1-185 O1 | 80/20 | 15.86 MW | 15.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964111 | AG1-272 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964121 | AG1-273 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964131 | AG1-274 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964241 | AG1-285 C O1 | 80/20 | 18.39 MW | 18.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964791 | AG1-342 C | 80/20 | 3.1 MW | 3.1 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965191 | AG1-384 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965591 | AG1-427 C | 80/20 | 17.61 MW | 17.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965601 | AG1-428 C O2 | 80/20 | 3.23 MW | 3.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965641 | AG1-432 C O1 | 80/20 | 73.68 MW | 73.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965721 | AG1-440 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965731 | AG1-441 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965771 | AG1-445 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965781 | AG1-446 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965831 | AG1-451 | 80/20 | 12.28 MW | 12.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 966621 | AG1-532 C | 80/20 | 0.47 MW | 0.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313506 | AB1-173 C OP | 80/20 | 2.2 MW | 2.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314429 | 3JTRSVLE | 80/20 | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314704 | 3LAWRENC | 80/20 | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315158 | 1KERR 1 | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315159 | 1KERR 2 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315160 | 1KERR 3 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315161 | 1KERR 4 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315162 | 1KERR 5 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 927261 | AC1-222 C | 80/20 | 1.32 MW | 1.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 934311 | AD1-055 C | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 936265 | AD2-033 C | 80/20 | 24.79 MW | 24.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 942461 | AE2-259 C O1 | 80/20 | 36.84 MW | 36.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 943901 | AF1-058 C | 80/20 | 0.75 MW | 0.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958801 | AF2-171 C | 80/20 | 41.22 MW | 41.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 959311 | AF2-222 C | 80/20 | 36.05 MW | 36.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960061 | AF2-297 C | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960081 | AF2-299 C | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315163 | 1KERR 6 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315164 | 1KERR 7 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315266 | 1PLYWOOD A | 80/20 | 0.63 MW | 0.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316118 | AC1-105 C | 80/20 | 3.19 MW | 3.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316129 | AC1-054 C | 80/20 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316131 | AB2-060 C | 80/20 | 2.02 MW | 2.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924301 | AB2-077 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924311 | AB2-078 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924321 | AB2-079 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 925611 | AC1-036 C | 80/20 | 0.5 MW | 0.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 938371 | AE1-056 C | 80/20 | 19.46 MW | 19.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 939181 | AE1-148 C | 80/20 | 7.77 MW | 7.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 940661 | AE2-053 O1 | 80/20 | 2.88 MW | 2.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946281 | AF1-292 C | 80/20 | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946301 | AF1-294 C | 80/20 | 11.32 MW | 11.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958211 | AF2-115 C | 80/20 | 6.9 MW | 6.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316087 | AB2-174 C | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 962561 | AG1-105 C O1 | 80/20 | 7.36 MW | 7.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313527 | AB2-043 C | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.97 MW | 13.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.32 MW | 3.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.07 MW | 4.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.0 MW | 1.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.8 MW | 0.8 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 961791 | AG1-021 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 961891 | AG1-030 C | 80/20 | 24.36 MW | 24.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963171 | AG1-166 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963181 | AG1-167 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963191 | AG1-168 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963201 | AG1-169 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963211 | AG1-170 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963301 | AG1-179 C | 80/20 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963311 | AG1-180 | 80/20 | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 46.99 MW | 46.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 22.74 MW | 22.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 34.86 MW | 34.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964791 | AG1-342 C | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 33.05 MW | 33.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965601 | AG1-428 C O2 | 80/20 | 1.42 MW | 1.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 55.78 MW | 55.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965721 | AG1-440 C | 80/20 | 2.25 MW | 2.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965731 | AG1-441 C | 80/20 | 2.25 MW | 2.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965771 | AG1-445 | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965781 | AG1-446 | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 9.3 MW | 9.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 314429 | 3JTRSVLE | 80/20 | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315159 | 1KERR 2 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315160 | 1KERR 3 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 936265 | AD2-033 C | 80/20 | 14.45 MW | 14.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 27.89 MW | 27.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 41.84 MW | 41.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 46.48 MW | 46.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 316131 | AB2-060 C | 80/20 | 0.94 MW | 0.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924301 | AB2-077 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924311 | AB2-078 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924321 | AB2-079 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 0.68 MW | 0.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 18.04 MW | 18.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 939181 | AE1-148 C | 80/20 | 3.42 MW | 3.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 940661 | AE2-053 O1 | 80/20 | 1.27 MW | 1.27 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 946301 | AF1-294 C | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 958211 | AF2-115 C | 80/20 | 4.57 MW | 4.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 962561 | AG1-105 C O1 | 80/20 | 3.14 MW | 3.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.37 MW | 0.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 33.51 MW | 33.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 25.47 MW | 25.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 31.12 MW | 31.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 18.22 MW | 18.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 60.41 MW | 60.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 27.11 MW | 27.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 27.11 MW | 27.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313506 | AB1-173 C OP | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315128 | 1ROARAP4 | 80/20 | 0.53 MW | 0.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 22.65 MW | 22.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 23.68 MW | 23.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 6.74 MW | 6.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 8.39 MW | 8.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 33.24 MW | 33.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 9.36 MW | 9.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 90.36 MW | 90.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.95 MW | 41.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.23 MW | 12.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.5 MW | 13.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 33.5 MW | 33.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 25.46 MW | 25.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 1.69 MW | 1.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 18.21 MW | 18.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 60.4 MW | 60.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 27.1 MW | 27.1 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 27.1 MW | 27.1 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313506 | AB1-173 C OP | 80/20 | 2.68 MW | 2.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315128 | 1ROARAP4 | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 23.67 MW | 23.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 6.73 MW | 6.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 8.38 MW | 8.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 33.23 MW | 33.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 9.35 MW | 9.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 90.34 MW | 90.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 5.99 MW | 5.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.88 MW | 41.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.14 MW | 12.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.43 MW | 13.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.79 MW | 1.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 1.88 MW | 1.88 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 0.92 MW | 0.92 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 31.57 MW | 31.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 15.27 MW | 15.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 12.75 MW | 12.75 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.43 MW | 1.43 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 12.41 MW | 12.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 1.57 MW | 1.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 100.11 MW | 100.11 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 16.68 MW | 16.68 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 4.15 MW | 4.15 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 50.05 MW | 50.05 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 49.79 MW | 49.79 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 37.78 MW | 37.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.51 MW | 0.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 24.51 MW | 24.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 3.78 MW | 3.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.4 MW | 1.4 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.51 MW | 4.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.2 MW | 1.2 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.38 MW | 1.38 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.41 MW | 0.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 33.51 MW | 33.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 25.47 MW | 25.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 31.12 MW | 31.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 18.22 MW | 18.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 60.41 MW | 60.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.53 MW | 0.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.65 MW | 22.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 23.68 MW | 23.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 6.74 MW | 6.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.39 MW | 8.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.24 MW | 33.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 9.36 MW | 9.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 90.36 MW | 90.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | Adder | -6.03 MW | -5.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.95 MW | 41.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.23 MW | 12.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.5 MW | 13.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 33.5 MW | 33.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 25.46 MW | 25.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 1.69 MW | 1.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 18.21 MW | 18.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 60.4 MW | 60.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 2.68 MW | 2.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 23.67 MW | 23.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 6.73 MW | 6.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.38 MW | 8.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.23 MW | 33.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 9.35 MW | 9.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 90.34 MW | 90.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 5.99 MW | 5.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.88 MW | 41.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.14 MW | 12.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.43 MW | 13.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.79 MW | 1.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 961791 | AG1-021 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 961891 | AG1-030 C | 80/20 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963171 | AG1-166 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963181 | AG1-167 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963191 | AG1-168 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963201 | AG1-169 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963211 | AG1-170 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963301 | AG1-179 C | 80/20 | 3.09 MW | 3.09 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963311 | AG1-180 | 80/20 | 1.51 MW | 1.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963321 | AG1-181 C O1 | 80/20 | 28.69 MW | 28.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963361 | AG1-185 O1 | 80/20 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964111 | AG1-272 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964121 | AG1-273 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964131 | AG1-274 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964241 | AG1-285 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964791 | AG1-342 C | 80/20 | 2.21 MW | 2.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965191 | AG1-384 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965591 | AG1-427 C | 80/20 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965601 | AG1-428 C O2 | 80/20 | 2.58 MW | 2.58 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965641 | AG1-432 C O1 | 80/20 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965721 | AG1-440 C | 80/20 | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965731 | AG1-441 C | 80/20 | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965831 | AG1-451 | 80/20 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 314429 | 3JTRSVLE | 80/20 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315159 | 1KERR 2 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315160 | 1KERR 3 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315161 | 1KERR 4 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315162 | 1KERR 5 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 936265 | AD2-033 C | 80/20 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 942461 | AE2-259 C O1 | 80/20 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 958801 | AF2-171 C | 80/20 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 959311 | AF2-222 C | 80/20 | 31.82 MW | 31.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315163 | 1KERR 6 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315164 | 1KERR 7 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316118 | AC1-105 C | 80/20 | 1.97 MW | 1.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316129 | AC1-054 C | 80/20 | 3.16 MW | 3.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316131 | AB2-060 C | 80/20 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924301 | AB2-077 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924311 | AB2-078 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924321 | AB2-079 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 925611 | AC1-036 C | 80/20 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 938371 | AE1-056 C | 80/20 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 939181 | AE1-148 C | 80/20 | 6.24 MW | 6.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 940661 | AE2-053 O1 | 80/20 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 946301 | AF1-294 C | 80/20 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 958211 | AF2-115 C | 80/20 | 6.19 MW | 6.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 962561 | AG1-105 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 313527 | AB2-043 C | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.01 MW | 1.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 46.07 MW | 46.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 46.07 MW | 46.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 11.7 MW | 11.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 29.34 MW | 29.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 9.62 MW | 9.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 26.93 MW | 26.93 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 46.07 MW | 46.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 46.07 MW | 46.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | Adder | -2.9 MW | -2.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | Adder | -7.26 MW | -6.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | Adder | -2.38 MW | -2.02 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | Adder | -6.67 MW | -5.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 961791 | AG1-021 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 961891 | AG1-030 C | 80/20 | 24.59 MW | 24.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963171 | AG1-166 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963181 | AG1-167 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963191 | AG1-168 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963201 | AG1-169 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963211 | AG1-170 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963301 | AG1-179 C | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963311 | AG1-180 | 80/20 | 1.17 MW | 1.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 21.16 MW | 21.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 10.24 MW | 10.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964111 | AG1-272 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964121 | AG1-273 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964131 | AG1-274 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 11.73 MW | 11.73 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.83 MW | 1.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965191 | AG1-384 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965591 | AG1-427 C | 80/20 | 11.24 MW | 11.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 48.39 MW | 48.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965721 | AG1-440 C | 80/20 | 3.18 MW | 3.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965731 | AG1-441 C | 80/20 | 3.18 MW | 3.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965771 | AG1-445 | 80/20 | 1.84 MW | 1.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965781 | AG1-446 | 80/20 | 1.84 MW | 1.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965831 | AG1-451 | 80/20 | 8.06 MW | 8.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.82 MW | 0.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 936265 | AD2-033 C | 80/20 | 15.99 MW | 15.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 24.2 MW | 24.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 958801 | AF2-171 C | 80/20 | 26.89 MW | 26.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 959311 | AF2-222 C | 80/20 | 23.37 MW | 23.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316118 | AC1-105 C | 80/20 | 1.78 MW | 1.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316129 | AC1-054 C | 80/20 | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.28 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 938371 | AE1-056 C | 80/20 | 12.73 MW | 12.73 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 939181 | AE1-148 C | 80/20 | 4.82 MW | 4.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.79 MW | 1.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 946301 | AF1-294 C | 80/20 | 7.39 MW | 7.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 958211 | AF2-115 C | 80/20 | 4.5 MW | 4.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 4.42 MW | 4.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.74 MW | 5.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.5 MW | 1.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.75 MW | 1.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.23 MW | 0.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 11.7 MW | 11.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 29.34 MW | 29.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 9.62 MW | 9.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 26.93 MW | 26.93 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 961791 | AG1-021 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 961891 | AG1-030 C | 80/20 | 19.62 MW | 19.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963171 | AG1-166 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963181 | AG1-167 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963191 | AG1-168 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963201 | AG1-169 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963211 | AG1-170 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 37.85 MW | 37.85 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 18.31 MW | 18.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 28.08 MW | 28.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 26.62 MW | 26.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 44.93 MW | 44.93 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 314429 | 3JTRSVLE | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 936265 | AD2-033 C | 80/20 | 11.64 MW | 11.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 22.46 MW | 22.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 33.7 MW | 33.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 37.44 MW | 37.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 316131 | AB2-060 C | 80/20 | 0.76 MW | 0.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924301 | AB2-077 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924311 | AB2-078 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924321 | AB2-079 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 0.55 MW | 0.55 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 14.53 MW | 14.53 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 939181 | AE1-148 C | 80/20 | 2.75 MW | 2.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 940661 | AE2-053 O1 | 80/20 | 1.02 MW | 1.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 946301 | AF1-294 C | 80/20 | 6.04 MW | 6.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 958211 | AF2-115 C | 80/20 | 3.68 MW | 3.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 313527 | AB2-043 C | 80/20 | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.26 MW | 3.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.98 MW | 0.98 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | Adder | -2.9 MW | -2.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | Adder | -7.26 MW | -6.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | Adder | -2.38 MW | -2.02 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | Adder | -6.67 MW | -5.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 961791 | AG1-021 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 961891 | AG1-030 C | 80/20 | 8.6 MW | 8.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963171 | AG1-166 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963181 | AG1-167 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963191 | AG1-168 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963201 | AG1-169 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963211 | AG1-170 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963301 | AG1-179 C | 80/20 | 14.2 MW | 14.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963311 | AG1-180 | 80/20 | 6.92 MW | 6.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963321 | AG1-181 C O1 | 80/20 | 11.55 MW | 11.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 963361 | AG1-185 O1 | 80/20 | 5.59 MW | 5.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964111 | AG1-272 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964121 | AG1-273 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964131 | AG1-274 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964241 | AG1-285 C O1 | 80/20 | 9.73 MW | 9.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964791 | AG1-342 C | 80/20 | 2.17 MW | 2.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 966811 | AG1-552 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965191 | AG1-384 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965291 | AG1-394 C | 80/20 | 0.65 MW | 0.65 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965591 | AG1-427 C | 80/20 | 9.19 MW | 9.19 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965601 | AG1-428 C O2 | 80/20 | 11.86 MW | 11.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965641 | AG1-432 C O1 | 80/20 | 6.9 MW | 6.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965721 | AG1-440 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965731 | AG1-441 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965771 | AG1-445 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965781 | AG1-446 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 965831 | AG1-451 | 80/20 | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 966621 | AG1-532 C | 80/20 | 4.82 MW | 4.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 313506 | AB1-173 C OP | 80/20 | 15.44 MW | 15.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 314429 | 3JTRSVLE | 80/20 | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 314572 | 3EMPORIA | 80/20 | 1.34 MW | 1.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 314704 | 3LAWRENC | 80/20 | 0.86 MW | 0.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315126 | 1ROARAP2 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315128 | 1ROARAP4 | 80/20 | 0.9 MW | 0.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315158 | 1KERR 1 | 80/20 | 0.27 MW | 0.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 927145 | AC1-208 C | 80/20 | 3.04 MW | 3.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 936265 | AD2-033 C | 80/20 | 9.0 MW | 9.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 942461 | AE2-259 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 958801 | AF2-171 C | 80/20 | 7.93 MW | 7.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 959311 | AF2-222 C | 80/20 | 10.71 MW | 10.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 960081 | AF2-299 C | 80/20 | 8.93 MW | 8.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315266 | 1PLYWOOD A | 80/20 | 0.49 MW | 0.49 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315606 | 3AA2-053SOLA | 80/20 | 0.88 MW | 0.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 316118 | AC1-105 C | 80/20 | 2.34 MW | 2.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 316129 | AC1-054 C | 80/20 | 4.75 MW | 4.75 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 923991 | AB2-040 C O1 | 80/20 | 16.82 MW | 16.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 924301 | AB2-077 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 924311 | AB2-078 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 924321 | AB2-079 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 938371 | AE1-056 C | 80/20 | 3.09 MW | 3.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 939181 | AE1-148 C | 80/20 | 5.97 MW | 5.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 940661 | AE2-053 O1 | 80/20 | 2.21 MW | 2.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 946281 | AF1-292 C | 80/20 | 5.3 MW | 5.3 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 946301 | AF1-294 C | 80/20 | 2.15 MW | 2.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 958211 | AF2-115 C | 80/20 | 1.31 MW | 1.31 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315607 | 3AA1-063SOLA | 80/20 | 0.77 MW | 0.77 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 315608 | 3AA2-088SOLA | 80/20 | 0.33 MW | 0.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 316087 | AB2-174 C | 80/20 | 3.13 MW | 3.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 962561 | AG1-105 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | 313527 | AB2-043 C | 80/20 | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.41 MW | 0.41 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.14 MW | 0.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.36 MW | 7.36 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.23 MW | 3.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.99 MW | 2.99 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.67 MW | 0.67 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 556-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 961791 | AG1-021 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 961891 | AG1-030 C | 80/20 | 8.6 MW | 8.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963171 | AG1-166 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963181 | AG1-167 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963191 | AG1-168 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963201 | AG1-169 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963211 | AG1-170 C | 80/20 | 1.05 MW | 1.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963301 | AG1-179 C | 80/20 | 14.2 MW | 14.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963311 | AG1-180 | 80/20 | 6.92 MW | 6.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963321 | AG1-181 C O1 | 80/20 | 11.55 MW | 11.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 963361 | AG1-185 O1 | 80/20 | 5.59 MW | 5.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964111 | AG1-272 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964121 | AG1-273 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964131 | AG1-274 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964241 | AG1-285 C O1 | 80/20 | 9.73 MW | 9.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964791 | AG1-342 C | 80/20 | 2.17 MW | 2.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 966811 | AG1-552 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965191 | AG1-384 C | 80/20 | 1.7 MW | 1.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965291 | AG1-394 C | 80/20 | 0.65 MW | 0.65 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965591 | AG1-427 C | 80/20 | 9.19 MW | 9.19 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965601 | AG1-428 C O2 | 80/20 | 11.86 MW | 11.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965641 | AG1-432 C O1 | 80/20 | 6.9 MW | 6.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965721 | AG1-440 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965731 | AG1-441 C | 80/20 | 4.72 MW | 4.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965771 | AG1-445 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965781 | AG1-446 | 80/20 | 2.73 MW | 2.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 965831 | AG1-451 | 80/20 | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 966621 | AG1-532 C | 80/20 | 4.82 MW | 4.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 313506 | AB1-173 C OP | 80/20 | 15.44 MW | 15.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 314429 | 3JTRSVLE | 80/20 | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 314572 | 3EMPORIA | 80/20 | 1.34 MW | 1.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 314704 | 3LAWRENC | 80/20 | 0.86 MW | 0.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315126 | 1ROARAP2 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315128 | 1ROARAP4 | 80/20 | 0.9 MW | 0.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315158 | 1KERR 1 | 80/20 | 0.27 MW | 0.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315159 | 1KERR 2 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315160 | 1KERR 3 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315161 | 1KERR 4 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315162 | 1KERR 5 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 927145 | AC1-208 C | 80/20 | 3.04 MW | 3.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 936265 | AD2-033 C | 80/20 | 9.0 MW | 9.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 942461 | AE2-259 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 958801 | AF2-171 C | 80/20 | 7.93 MW | 7.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 959311 | AF2-222 C | 80/20 | 10.71 MW | 10.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 960081 | AF2-299 C | 80/20 | 8.93 MW | 8.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315163 | 1KERR 6 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315164 | 1KERR 7 | 80/20 | 0.74 MW | 0.74 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315266 | 1PLYWOOD A | 80/20 | 0.49 MW | 0.49 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315606 | 3AA2-053SOLA | 80/20 | 0.88 MW | 0.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316118 | AC1-105 C | 80/20 | 2.34 MW | 2.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316129 | AC1-054 C | 80/20 | 4.75 MW | 4.75 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 923991 | AB2-040 C O1 | 80/20 | 16.82 MW | 16.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 924301 | AB2-077 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 924311 | AB2-078 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 924321 | AB2-079 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 938371 | AE1-056 C | 80/20 | 3.09 MW | 3.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 939181 | AE1-148 C | 80/20 | 5.97 MW | 5.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 940661 | AE2-053 O1 | 80/20 | 2.21 MW | 2.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 946281 | AF1-292 C | 80/20 | 5.3 MW | 5.3 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 946301 | AF1-294 C | 80/20 | 2.15 MW | 2.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 958211 | AF2-115 C | 80/20 | 1.31 MW | 1.31 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315607 | 3AA1-063SOLA | 80/20 | 0.77 MW | 0.77 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.33 MW | 0.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 316087 | AB2-174 C | 80/20 | 3.13 MW | 3.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 962561 | AG1-105 C O1 | 80/20 | 5.08 MW | 5.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | 313527 | AB2-043 C | 80/20 | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.41 MW | 0.41 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.14 MW | 0.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.36 MW | 7.36 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.23 MW | 3.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.99 MW | 2.99 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.67 MW | 0.67 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.44 MW | 0.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.1 MW | 0.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o 314906 8CLOVER 500 945810 AF1-246 TAP 500 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 69.52 MW | 69.52 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 33.63 MW | 33.63 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 62.24 MW | 62.24 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 58.68 MW | 58.68 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 19.89 MW | 19.89 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 3.31 MW | 3.31 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 9.95 MW | 9.95 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 40.21 MW | 40.21 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 62.22 MW | 62.22 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.95 MW | 0.95 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 14.29 MW | 14.29 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.12 MW | 0.12 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.41 MW | 0.41 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.34 MW | 0.34 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.51 MW | 0.51 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 69.76 MW | 69.76 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 33.75 MW | 33.75 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 62.38 MW | 62.38 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 58.81 MW | 58.81 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 20.45 MW | 20.45 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 3.41 MW | 3.41 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 10.22 MW | 10.22 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 40.52 MW | 40.52 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 62.48 MW | 62.48 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.96 MW | 0.96 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 14.43 MW | 14.43 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.1 MW | 0.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.13 MW | 0.13 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.15 MW | 0.15 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.29 MW | 0.29 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.41 MW | 0.41 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 69.76 MW | 69.76 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 33.75 MW | 33.75 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 62.38 MW | 62.38 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 58.81 MW | 58.81 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 20.45 MW | 20.45 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 3.41 MW | 3.41 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 10.22 MW | 10.22 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 40.52 MW | 40.52 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 62.48 MW | 62.48 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.96 MW | 0.96 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 14.43 MW | 14.43 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.1 MW | 0.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.13 MW | 0.13 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.15 MW | 0.15 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.29 MW | 0.29 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.41 MW | 0.41 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.0 MW | 35.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.0 MW | 35.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.74 MW | 0.74 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 9.93 MW | 9.93 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 34.69 MW | 34.69 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 2.92 MW | 2.92 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.24 MW | 1.24 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 25.57 MW | 25.57 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.26 MW | 4.26 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 60.29 MW | 60.29 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 60.29 MW | 60.29 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.36 MW | 0.36 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 50.36 MW | 50.36 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 49.88 MW | 49.88 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | Adder | -1.57 MW | -1.34 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | Adder | -3.23 MW | -2.75 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | Adder | -2.24 MW | -1.91 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | Adder | -3.94 MW | -3.35 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 29.32 MW | 29.32 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 38.31 MW | 38.31 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | Adder | -1.29 MW | -1.1 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 35.11 MW | 35.11 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 4.4 MW | 4.4 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 8.59 MW | 8.59 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | Adder | -1.82 MW | -1.54 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 28.13 MW | 28.13 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 11.75 MW | 11.75 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 7.9 MW | 7.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.74 MW | 0.74 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | Adder | -4.16 MW | -3.53 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | Adder | -3.62 MW | -3.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 5.96 MW | 5.96 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.64 MW | 6.64 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 6.22 MW | 6.22 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.97 MW | 9.97 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 3.24 MW | 3.24 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.04 MW | 2.04 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 200.96 MW | 200.96 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 1.98 MW | 1.98 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 4.03 MW | 4.03 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.73 MW | 7.73 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.14 MW | 0.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.48 MW | 0.48 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.61 MW | 0.61 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.9 MW | 3.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.9 MW | 3.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 5.05 MW | 5.05 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.12 MW | 0.12 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 3.44 MW | 3.44 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.13 MW | 2.13 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.09 MW | 1.09 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.16 MW | 1.16 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.12 MW | 1.12 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.02 MW | 4.02 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.48 MW | 0.48 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 2.14 MW | 2.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.84 MW | 3.84 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.28 MW | 1.28 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 961791 | AG1-021 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963171 | AG1-166 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963181 | AG1-167 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963191 | AG1-168 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963201 | AG1-169 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963211 | AG1-170 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963321 | AG1-181 C O1 | 80/20 | 73.64 MW | 73.64 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963361 | AG1-185 O1 | 80/20 | 35.63 MW | 35.63 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964111 | AG1-272 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964121 | AG1-273 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964131 | AG1-274 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965191 | AG1-384 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965591 | AG1-427 C | 80/20 | 60.96 MW | 60.96 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965641 | AG1-432 C O1 | 80/20 | 28.75 MW | 28.75 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965831 | AG1-451 | 80/20 | 4.79 MW | 4.79 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 314429 | 3JTRSVLE | 80/20 | 0.18 MW | 0.18 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 942461 | AE2-259 C O1 | 80/20 | 14.38 MW | 14.38 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 958801 | AF2-171 C | 80/20 | 45.25 MW | 45.25 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 959311 | AF2-222 C | 80/20 | 66.71 MW | 66.71 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 925611 | AC1-036 C | 80/20 | 1.02 MW | 1.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 938371 | AE1-056 C | 80/20 | 16.65 MW | 16.65 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 946301 | AF1-294 C | 80/20 | 1.67 MW | 1.67 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 958211 | AF2-115 C | 80/20 | 1.02 MW | 1.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.02 MW | 0.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.13 MW | 0.13 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.15 MW | 0.15 MW |
| Details for 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 9.93 MW | 9.93 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 34.69 MW | 34.69 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.24 MW | 1.24 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 25.57 MW | 25.57 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.26 MW | 4.26 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 60.29 MW | 60.29 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 60.29 MW | 60.29 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.36 MW | 0.36 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 50.36 MW | 50.36 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 49.88 MW | 49.88 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | Adder | -1.57 MW | -1.34 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | Adder | -3.23 MW | -2.75 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | Adder | -2.24 MW | -1.91 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | Adder | -3.94 MW | -3.35 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 29.32 MW | 29.32 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 38.31 MW | 38.31 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | Adder | -1.29 MW | -1.1 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | Adder | -12.89 MW | -10.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 4.4 MW | 4.4 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 8.59 MW | 8.59 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | Adder | -1.82 MW | -1.54 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 28.13 MW | 28.13 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 11.75 MW | 11.75 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 7.9 MW | 7.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | Adder | -4.16 MW | -3.53 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | Adder | -3.62 MW | -3.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 5.96 MW | 5.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.64 MW | 6.64 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 6.22 MW | 6.22 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.97 MW | 9.97 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 3.24 MW | 3.24 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.04 MW | 2.04 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 200.96 MW | 200.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 1.98 MW | 1.98 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 4.03 MW | 4.03 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.73 MW | 7.73 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.14 MW | 0.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.48 MW | 0.48 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.9 MW | 3.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.9 MW | 3.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 5.05 MW | 5.05 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.12 MW | 0.12 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 3.44 MW | 3.44 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.13 MW | 2.13 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.09 MW | 1.09 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.16 MW | 1.16 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.12 MW | 1.12 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.02 MW | 4.02 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.48 MW | 0.48 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 2.14 MW | 2.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.84 MW | 3.84 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.28 MW | 1.28 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 69.52 MW | 69.52 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 33.63 MW | 33.63 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 58.68 MW | 58.68 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 19.89 MW | 19.89 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 3.31 MW | 3.31 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 9.95 MW | 9.95 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 40.21 MW | 40.21 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 62.22 MW | 62.22 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.95 MW | 0.95 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 14.29 MW | 14.29 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.41 MW | 0.41 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.34 MW | 0.34 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.51 MW | 0.51 MW |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961791 | AG1-021 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961891 | AG1-030 C | 80/20 | 9.77 MW | 9.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 962491 | AG1-098 C O1 | 80/20 | 6.05 MW | 6.05 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963171 | AG1-166 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963181 | AG1-167 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963191 | AG1-168 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963201 | AG1-169 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963211 | AG1-170 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963321 | AG1-181 C O1 | 80/20 | 9.04 MW | 9.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963361 | AG1-185 O1 | 80/20 | 4.37 MW | 4.37 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964111 | AG1-272 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964121 | AG1-273 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964131 | AG1-274 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964241 | AG1-285 C O1 | 80/20 | 5.52 MW | 5.52 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964791 | AG1-342 C | 80/20 | 1.28 MW | 1.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965191 | AG1-384 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965591 | AG1-427 C | 80/20 | 5.27 MW | 5.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965641 | AG1-432 C O1 | 80/20 | 17.69 MW | 17.69 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965831 | AG1-451 | 80/20 | 2.95 MW | 2.95 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314429 | 3JTRSVLE | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315153 | 1CLOVER1 | 80/20 | 4.15 MW | 4.15 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315154 | 1CLOVER2 | 80/20 | 4.11 MW | 4.11 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934615 | AD1-087 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934625 | AD1-088 C | 80/20 | 6.81 MW | 6.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 936265 | AD2-033 C | 80/20 | 6.87 MW | 6.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 937481 | AD2-202 C O1 | 80/20 | 0.7 MW | 0.7 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 942461 | AE2-259 C O1 | 80/20 | 8.85 MW | 8.85 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958801 | AF2-171 C | 80/20 | 10.46 MW | 10.46 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 959311 | AF2-222 C | 80/20 | 9.67 MW | 9.67 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 316131 | AB2-060 C | 80/20 | 0.63 MW | 0.63 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924301 | AB2-077 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924311 | AB2-078 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924321 | AB2-079 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 925611 | AC1-036 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938371 | AE1-056 C | 80/20 | 4.85 MW | 4.85 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 939181 | AE1-148 C | 80/20 | 2.81 MW | 2.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940661 | AE2-053 O1 | 80/20 | 1.04 MW | 1.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941791 | AE2-182 C | 80/20 | 1.11 MW | 1.11 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 946301 | AF1-294 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958211 | AF2-115 C | 80/20 | 1.75 MW | 1.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 933501 | AC2-165 C | 80/20 | 9.02 MW | 9.02 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314333 | 6POWHATN | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314677 | 6BUCKING | 80/20 | 0.49 MW | 0.49 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958501 | AF2-144 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315191 | 1BEARGRDN G1 | 80/20 | 8.45 MW | 8.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315192 | 1BEARGRDN G2 | 80/20 | 8.45 MW | 8.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315193 | 1BEARGRDN S1 | 80/20 | 10.93 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938561 | AE1-075 C | 80/20 | 0.28 MW | 0.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 957911 | AF2-085 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 962561 | AG1-105 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 313527 | AB2-043 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.79 MW | 0.79 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.27 MW | 0.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.2 MW | 1.2 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.19 MW | 0.19 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.56 MW | 0.56 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| Details for AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.74 MW | 0.74 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 9.93 MW | 9.93 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 34.69 MW | 34.69 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 1.58 MW | 1.58 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 2.92 MW | 2.92 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.24 MW | 1.24 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 25.57 MW | 25.57 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.26 MW | 4.26 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.36 MW | 0.36 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 50.36 MW | 50.36 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 49.88 MW | 49.88 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | Adder | -1.57 MW | -1.34 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | Adder | -3.23 MW | -2.75 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | Adder | -2.24 MW | -1.91 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | Adder | -3.94 MW | -3.35 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 29.32 MW | 29.32 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 38.31 MW | 38.31 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | Adder | -1.29 MW | -1.1 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 35.11 MW | 35.11 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 4.4 MW | 4.4 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 8.59 MW | 8.59 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | Adder | -1.82 MW | -1.54 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 28.13 MW | 28.13 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 11.75 MW | 11.75 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 7.9 MW | 7.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.74 MW | 0.74 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | Adder | -4.16 MW | -3.53 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | Adder | -3.62 MW | -3.08 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 5.96 MW | 5.96 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.64 MW | 6.64 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 6.22 MW | 6.22 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.97 MW | 9.97 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 3.24 MW | 3.24 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.04 MW | 2.04 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 200.96 MW | 200.96 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 1.98 MW | 1.98 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 4.03 MW | 4.03 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.73 MW | 7.73 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.14 MW | 0.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.48 MW | 0.48 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.61 MW | 0.61 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.9 MW | 3.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.9 MW | 3.9 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 5.05 MW | 5.05 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.12 MW | 0.12 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 3.44 MW | 3.44 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.13 MW | 2.13 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.09 MW | 1.09 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.16 MW | 1.16 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.12 MW | 1.12 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.02 MW | 4.02 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.48 MW | 0.48 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 2.14 MW | 2.14 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.84 MW | 3.84 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
| AD1-152 TAP-6SEDGE HILL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.28 MW | 1.28 MW |
| Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 961791 | AG1-021 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 961891 | AG1-030 C | 80/20 | 12.04 MW | 12.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963171 | AG1-166 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963181 | AG1-167 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963191 | AG1-168 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963201 | AG1-169 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963211 | AG1-170 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963301 | AG1-179 C | 80/20 | 3.76 MW | 3.76 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963311 | AG1-180 | 80/20 | 1.83 MW | 1.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963321 | AG1-181 C O1 | 80/20 | 17.29 MW | 17.29 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963361 | AG1-185 O1 | 80/20 | 8.37 MW | 8.37 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964111 | AG1-272 C | 80/20 | 2.52 MW | 2.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964121 | AG1-273 C | 80/20 | 2.52 MW | 2.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964131 | AG1-274 C | 80/20 | 2.52 MW | 2.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964241 | AG1-285 C O1 | 80/20 | 15.15 MW | 15.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964791 | AG1-342 C | 80/20 | 10.69 MW | 10.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 966691 | AG1-539 C | 80/20 | 10.08 MW | 10.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 966761 | AG1-547 C | 80/20 | 4.43 MW | 4.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965191 | AG1-384 C | 80/20 | 2.52 MW | 2.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965591 | AG1-427 C | 80/20 | 14.29 MW | 14.29 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965601 | AG1-428 C O2 | 80/20 | 3.14 MW | 3.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965641 | AG1-432 C O1 | 80/20 | 6.93 MW | 6.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965721 | AG1-440 C | 80/20 | 6.18 MW | 6.18 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965731 | AG1-441 C | 80/20 | 6.18 MW | 6.18 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965771 | AG1-445 | 80/20 | 3.57 MW | 3.57 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965781 | AG1-446 | 80/20 | 3.57 MW | 3.57 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965831 | AG1-451 | 80/20 | 1.16 MW | 1.16 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246843 | 05SMG1 | 80/20 | 0.62 MW | 0.62 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246844 | 05SMG2 | 80/20 | 1.7 MW | 1.7 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246845 | 05SMG3 | 80/20 | 1.06 MW | 1.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246846 | 05SMG4 | 80/20 | 1.67 MW | 1.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246847 | 05SMG5 | 80/20 | 0.65 MW | 0.65 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 247284 | 05LEESVG | 80/20 | 0.79 MW | 0.79 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 314429 | 3JTRSVLE | 80/20 | 0.32 MW | 0.32 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315156 | 1HALLBR1 | 80/20 | 1.46 MW | 1.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315159 | 1KERR 2 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315160 | 1KERR 3 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315161 | 1KERR 4 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315162 | 1KERR 5 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 926023 | AC1-080 C | 80/20 | 0.83 MW | 0.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 926645 | AC1-145 C | 80/20 | 0.44 MW | 0.44 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 927261 | AC1-222 C | 80/20 | 12.12 MW | 12.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 934311 | AD1-055 C | 80/20 | 8.42 MW | 8.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 935171 | AD1-152 C O1 | Adder | -4.33 MW | -3.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 936265 | AD2-033 C | 80/20 | 13.55 MW | 13.55 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 942461 | AE2-259 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 942671 | AE2-283 C | 80/20 | 5.39 MW | 5.39 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 942751 | AE2-291 C | 80/20 | 19.28 MW | 19.28 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 942761 | AE2-292 C O1 | 80/20 | 24.0 MW | 24.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 943901 | AF1-058 C | 80/20 | 6.86 MW | 6.86 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 958801 | AF2-171 C | 80/20 | 10.69 MW | 10.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 959311 | AF2-222 C | 80/20 | 15.68 MW | 15.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 960061 | AF2-297 C | 80/20 | 27.43 MW | 27.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 961121 | AF2-403 | 80/20 | 1.09 MW | 1.09 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315163 | 1KERR 6 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315164 | 1KERR 7 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315266 | 1PLYWOOD A | 80/20 | 3.89 MW | 3.89 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 316118 | AC1-105 C | 80/20 | 17.19 MW | 17.19 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 316129 | AC1-054 C | 80/20 | 4.67 MW | 4.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 316131 | AB2-060 C | 80/20 | 1.97 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 924301 | AB2-077 C O1 | 80/20 | 2.68 MW | 2.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 924311 | AB2-078 C O1 | 80/20 | 2.68 MW | 2.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 924321 | AB2-079 C O1 | 80/20 | 2.68 MW | 2.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 925611 | AC1-036 C | 80/20 | 0.24 MW | 0.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 925661 | AC1-042 C | 80/20 | 2.17 MW | 2.17 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 938371 | AE1-056 C | 80/20 | 3.95 MW | 3.95 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 939181 | AE1-148 C | 80/20 | 9.08 MW | 9.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 940661 | AE2-053 O1 | 80/20 | 3.36 MW | 3.36 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 941801 | AE2-185 C | 80/20 | 4.9 MW | 4.9 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 941821 | AE2-187 C | 80/20 | 4.9 MW | 4.9 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 946301 | AF1-294 C | 80/20 | 2.9 MW | 2.9 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 958211 | AF2-115 C | 80/20 | 1.77 MW | 1.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 962561 | AG1-105 C O1 | 80/20 | 21.13 MW | 21.13 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 313527 | AB2-043 C | 80/20 | 0.7 MW | 0.7 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 316123 | AC1-075 C | 80/20 | 2.48 MW | 2.48 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.16 MW | 1.16 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.43 MW | 0.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.08 MW | 0.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 69.76 MW | 69.76 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 33.75 MW | 33.75 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 58.81 MW | 58.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 20.45 MW | 20.45 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 3.41 MW | 3.41 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 10.22 MW | 10.22 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 40.52 MW | 40.52 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 62.48 MW | 62.48 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.96 MW | 0.96 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 14.43 MW | 14.43 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.1 MW | 0.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.13 MW | 0.13 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.15 MW | 0.15 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.29 MW | 0.29 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.41 MW | 0.41 MW |
| Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 961801 | AG1-022 C | 80/20 | 1.12 MW | 1.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 962741 | AG1-123 C O1 | 80/20 | 1.95 MW | 1.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963021 | AG1-151 O1 | 80/20 | 8.16 MW | 8.16 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963471 | AG1-196 O1 | 80/20 | 16.03 MW | 16.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 964231 | AG1-284 C O1 | 80/20 | 5.0 MW | 5.0 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 964831 | AG1-346 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965581 | AG1-426 | 80/20 | 1.7 MW | 1.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965641 | AG1-432 C O1 | 80/20 | 7.32 MW | 7.32 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965831 | AG1-451 | 80/20 | 1.22 MW | 1.22 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966251 | AG1-494 C | 80/20 | 1.05 MW | 1.05 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 942461 | AE2-259 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 960111 | AF2-302 C | 80/20 | 1.12 MW | 1.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938371 | AE1-056 C | 80/20 | 1.95 MW | 1.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938821 | AE1-108 C O1 | 80/20 | 8.96 MW | 8.96 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 941011 | AE2-092 C | 80/20 | 10.11 MW | 10.11 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 946291 | AF1-293 C O1 | 80/20 | 13.04 MW | 13.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 946591 | AF1-323 C | 80/20 | 3.07 MW | 3.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 958131 | AF2-107 C | 80/20 | 2.04 MW | 2.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 235034 | 01SHY_Z2-039 | 80/20 | 0.01 MW | 0.01 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 235035 | 01NHY_Z2-039 | 80/20 | 0.02 MW | 0.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 237092 | AD1-085_C | 80/20 | 0.15 MW | 0.15 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 940451 | AE2-029 C | 80/20 | 3.03 MW | 3.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 943571 | AF1-028 O1 | 80/20 | 16.32 MW | 16.32 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 933501 | AC2-165 C | 80/20 | 3.12 MW | 3.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 944071 | AF1-075 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 961061 | AF2-397 C | 80/20 | 11.82 MW | 11.82 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 313738 | 3CUSHAW | 80/20 | 0.09 MW | 0.09 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 314677 | 6BUCKING | 80/20 | 0.21 MW | 0.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 314859 | 4WSTVACO | 80/20 | 4.02 MW | 4.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 926001 | AC1-076 C | Adder | -2.89 MW | -2.45 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966671 | AG1-537 C | 80/20 | 4.18 MW | 4.18 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315186 | 1LOWMORA | 80/20 | 0.41 MW | 0.41 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315188 | 1LOWMORC | 80/20 | 0.41 MW | 0.41 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315191 | 1BEARGRDN G1 | 80/20 | 3.85 MW | 3.85 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315192 | 1BEARGRDN G2 | 80/20 | 3.85 MW | 3.85 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315193 | 1BEARGRDN S1 | 80/20 | 4.97 MW | 4.97 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315201 | 1BATH 1A | 80/20 | 6.84 MW | 6.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315202 | 1BATH 2B | 80/20 | 6.84 MW | 6.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315203 | 1BATH 3C | 80/20 | 6.84 MW | 6.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315204 | 1BATH 4D | 80/20 | 6.84 MW | 6.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315205 | 1BATH 5E | 80/20 | 6.85 MW | 6.85 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315206 | 1BATH 6F | 80/20 | 6.86 MW | 6.86 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315216 | 1CUNINGA | 80/20 | 2.89 MW | 2.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315217 | 1CUNINGB | 80/20 | 2.89 MW | 2.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315218 | 1CUNINGC | 80/20 | 2.89 MW | 2.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315219 | 1CUNINGD | 80/20 | 6.46 MW | 6.46 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315616 | AA1-038 C | 80/20 | 0.96 MW | 0.96 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 932854 | AC2-112 C | 80/20 | 13.48 MW | 13.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938625 | AE1-084 C | 80/20 | 6.51 MW | 6.51 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 941381 | AE2-134 | Adder | -1.99 MW | -1.69 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963461 | AG1-195 | 80/20 | 14.13 MW | 14.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965531 | AG1-421 C | 80/20 | 12.9 MW | 12.9 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965541 | AG1-422 | 80/20 | 5.38 MW | 5.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966851 | AG1-556 C | 80/20 | 9.46 MW | 9.46 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.47 MW | 0.47 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.72 MW | 0.72 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.48 MW | 15.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 23.83 MW | 23.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.39 MW | 16.39 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.7 MW | 0.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.17 MW | 1.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.84 MW | 2.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.64 MW | 0.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.55 MW | 0.55 MW |
| Details for 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 9.93 MW | 9.93 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 34.69 MW | 34.69 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 1.58 MW | 1.58 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 4.2 MW | 4.2 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.24 MW | 1.24 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 25.57 MW | 25.57 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.26 MW | 4.26 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.36 MW | 0.36 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 50.36 MW | 50.36 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 49.88 MW | 49.88 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | Adder | -1.57 MW | -1.34 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | Adder | -3.23 MW | -2.75 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | Adder | -2.24 MW | -1.91 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | Adder | -3.94 MW | -3.35 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 29.32 MW | 29.32 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 38.31 MW | 38.31 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | Adder | -1.29 MW | -1.1 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | Adder | -12.89 MW | -10.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 4.4 MW | 4.4 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 8.59 MW | 8.59 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 12.78 MW | 12.78 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | Adder | -1.82 MW | -1.54 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 28.13 MW | 28.13 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 11.75 MW | 11.75 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 7.9 MW | 7.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | Adder | -4.16 MW | -3.53 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | Adder | -3.62 MW | -3.08 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 5.96 MW | 5.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.64 MW | 6.64 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 6.22 MW | 6.22 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.97 MW | 9.97 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 3.24 MW | 3.24 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.04 MW | 2.04 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 200.96 MW | 200.96 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 1.98 MW | 1.98 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 4.03 MW | 4.03 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.73 MW | 7.73 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.14 MW | 0.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.48 MW | 0.48 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.9 MW | 3.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.9 MW | 3.9 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 5.05 MW | 5.05 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.12 MW | 0.12 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.37 MW | 1.37 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 3.44 MW | 3.44 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.13 MW | 2.13 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.09 MW | 1.09 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.16 MW | 1.16 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.12 MW | 1.12 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 4.02 MW | 4.02 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.48 MW | 0.48 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 2.14 MW | 2.14 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.84 MW | 3.84 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.68 MW | 0.68 MW |
| 6BLACK WALNU-AD1-152 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.28 MW | 1.28 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 7.33 MW | 7.33 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 7.33 MW | 7.33 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 961791 | AG1-021 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 961891 | AG1-030 C | 80/20 | 12.01 MW | 12.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963171 | AG1-166 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963181 | AG1-167 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963191 | AG1-168 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963201 | AG1-169 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963211 | AG1-170 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963301 | AG1-179 C | 80/20 | 3.75 MW | 3.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963311 | AG1-180 | 80/20 | 1.83 MW | 1.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963321 | AG1-181 C O1 | 80/20 | 17.24 MW | 17.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963361 | AG1-185 O1 | 80/20 | 8.34 MW | 8.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964111 | AG1-272 C | 80/20 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964121 | AG1-273 C | 80/20 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964131 | AG1-274 C | 80/20 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964241 | AG1-285 C O1 | 80/20 | 15.1 MW | 15.1 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964791 | AG1-342 C | 80/20 | 10.66 MW | 10.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 966691 | AG1-539 C | 80/20 | 10.05 MW | 10.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 966761 | AG1-547 C | 80/20 | 4.41 MW | 4.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965191 | AG1-384 C | 80/20 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965591 | AG1-427 C | 80/20 | 14.24 MW | 14.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965601 | AG1-428 C O2 | 80/20 | 3.13 MW | 3.13 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965641 | AG1-432 C O1 | 80/20 | 6.91 MW | 6.91 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965721 | AG1-440 C | 80/20 | 6.17 MW | 6.17 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965731 | AG1-441 C | 80/20 | 6.17 MW | 6.17 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965771 | AG1-445 | 80/20 | 3.56 MW | 3.56 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965781 | AG1-446 | 80/20 | 3.56 MW | 3.56 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965831 | AG1-451 | 80/20 | 1.15 MW | 1.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246843 | 05SMG1 | 80/20 | 0.62 MW | 0.62 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246844 | 05SMG2 | 80/20 | 1.69 MW | 1.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246845 | 05SMG3 | 80/20 | 1.06 MW | 1.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246846 | 05SMG4 | 80/20 | 1.67 MW | 1.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246847 | 05SMG5 | 80/20 | 0.65 MW | 0.65 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 247284 | 05LEESVG | 80/20 | 0.78 MW | 0.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 314429 | 3JTRSVLE | 80/20 | 0.32 MW | 0.32 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315156 | 1HALLBR1 | 80/20 | 1.46 MW | 1.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315159 | 1KERR 2 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315160 | 1KERR 3 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315161 | 1KERR 4 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315162 | 1KERR 5 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 926023 | AC1-080 C | 80/20 | 0.83 MW | 0.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 926645 | AC1-145 C | 80/20 | 0.44 MW | 0.44 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 927261 | AC1-222 C | 80/20 | 12.09 MW | 12.09 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 934311 | AD1-055 C | 80/20 | 8.39 MW | 8.39 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 935171 | AD1-152 C O1 | Adder | -4.31 MW | -3.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 936265 | AD2-033 C | 80/20 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 942461 | AE2-259 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 942671 | AE2-283 C | 80/20 | 5.37 MW | 5.37 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 942751 | AE2-291 C | 80/20 | 19.22 MW | 19.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 942761 | AE2-292 C O1 | 80/20 | 23.93 MW | 23.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 943901 | AF1-058 C | 80/20 | 6.84 MW | 6.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 958801 | AF2-171 C | 80/20 | 10.66 MW | 10.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 959311 | AF2-222 C | 80/20 | 15.64 MW | 15.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 960061 | AF2-297 C | 80/20 | 27.34 MW | 27.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 961121 | AF2-403 | 80/20 | 1.08 MW | 1.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315163 | 1KERR 6 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315164 | 1KERR 7 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315266 | 1PLYWOOD A | 80/20 | 3.88 MW | 3.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 316118 | AC1-105 C | 80/20 | 17.14 MW | 17.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 316129 | AC1-054 C | 80/20 | 4.66 MW | 4.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 316131 | AB2-060 C | 80/20 | 1.97 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 924301 | AB2-077 C O1 | 80/20 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 924311 | AB2-078 C O1 | 80/20 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 924321 | AB2-079 C O1 | 80/20 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 925611 | AC1-036 C | 80/20 | 0.24 MW | 0.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 925661 | AC1-042 C | 80/20 | 2.17 MW | 2.17 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 938371 | AE1-056 C | 80/20 | 3.93 MW | 3.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 939181 | AE1-148 C | 80/20 | 9.05 MW | 9.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 940661 | AE2-053 O1 | 80/20 | 3.35 MW | 3.35 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 941801 | AE2-185 C | 80/20 | 4.88 MW | 4.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 941821 | AE2-187 C | 80/20 | 4.88 MW | 4.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 946301 | AF1-294 C | 80/20 | 2.89 MW | 2.89 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 958211 | AF2-115 C | 80/20 | 1.76 MW | 1.76 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 962561 | AG1-105 C O1 | 80/20 | 21.07 MW | 21.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 313527 | AB2-043 C | 80/20 | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 316123 | AC1-075 C | 80/20 | 2.47 MW | 2.47 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.15 MW | 1.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.43 MW | 0.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.08 MW | 0.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961791 | AG1-021 C | 80/20 | 2.9 MW | 2.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961891 | AG1-030 C | 80/20 | 19.8 MW | 19.8 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963171 | AG1-166 C | 80/20 | 2.9 MW | 2.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963181 | AG1-167 C | 80/20 | 2.9 MW | 2.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963191 | AG1-168 C | 80/20 | 2.9 MW | 2.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963201 | AG1-169 C | 80/20 | 2.9 MW | 2.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963211 | AG1-170 C | 80/20 | 2.9 MW | 2.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963301 | AG1-179 C | 80/20 | 1.93 MW | 1.93 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963311 | AG1-180 | 80/20 | 0.94 MW | 0.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 17.04 MW | 17.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 8.24 MW | 8.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964111 | AG1-272 C | 80/20 | 2.76 MW | 2.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964121 | AG1-273 C | 80/20 | 2.76 MW | 2.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964131 | AG1-274 C | 80/20 | 2.76 MW | 2.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.47 MW | 1.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965191 | AG1-384 C | 80/20 | 2.76 MW | 2.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965591 | AG1-427 C | 80/20 | 9.06 MW | 9.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 1.61 MW | 1.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 38.98 MW | 38.98 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965721 | AG1-440 C | 80/20 | 2.56 MW | 2.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965731 | AG1-441 C | 80/20 | 2.56 MW | 2.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965771 | AG1-445 | 80/20 | 1.48 MW | 1.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965781 | AG1-446 | 80/20 | 1.48 MW | 1.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965831 | AG1-451 | 80/20 | 6.5 MW | 6.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.1 MW | 0.1 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 936265 | AD2-033 C | 80/20 | 12.88 MW | 12.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 19.49 MW | 19.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 958801 | AF2-171 C | 80/20 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 959311 | AF2-222 C | 80/20 | 18.82 MW | 18.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.26 MW | 0.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 938371 | AE1-056 C | 80/20 | 10.25 MW | 10.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 939181 | AE1-148 C | 80/20 | 3.89 MW | 3.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.44 MW | 1.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 946301 | AF1-294 C | 80/20 | 5.95 MW | 5.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 958211 | AF2-115 C | 80/20 | 3.63 MW | 3.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 3.56 MW | 3.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.28 MW | 0.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.62 MW | 4.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.21 MW | 1.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.41 MW | 1.41 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.27 MW | 0.27 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 7.33 MW | 7.33 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 7.33 MW | 7.33 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 7.33 MW | 7.33 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 7.33 MW | 7.33 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961791 | AG1-021 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961801 | AG1-022 C | 80/20 | 1.26 MW | 1.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961891 | AG1-030 C | 80/20 | 5.49 MW | 5.49 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962491 | AG1-098 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962741 | AG1-123 C O1 | 80/20 | 2.24 MW | 2.24 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962751 | AG1-124 C O1 | 80/20 | 3.29 MW | 3.29 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963021 | AG1-151 O1 | 80/20 | 9.03 MW | 9.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963171 | AG1-166 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963181 | AG1-167 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963191 | AG1-168 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963201 | AG1-169 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963211 | AG1-170 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963321 | AG1-181 C O1 | 80/20 | 5.27 MW | 5.27 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963361 | AG1-185 O1 | 80/20 | 2.55 MW | 2.55 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963471 | AG1-196 O1 | 80/20 | 17.34 MW | 17.34 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964111 | AG1-272 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964121 | AG1-273 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964131 | AG1-274 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964231 | AG1-284 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964831 | AG1-346 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965191 | AG1-384 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965581 | AG1-426 | 80/20 | 1.92 MW | 1.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965641 | AG1-432 C O1 | 80/20 | 9.5 MW | 9.5 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965831 | AG1-451 | 80/20 | 1.58 MW | 1.58 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966251 | AG1-494 C | 80/20 | 1.21 MW | 1.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314429 | 3JTRSVLE | 80/20 | 0.18 MW | 0.18 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934625 | AD1-088 C | 80/20 | 3.65 MW | 3.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 936265 | AD2-033 C | 80/20 | 4.02 MW | 4.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942461 | AE2-259 C O1 | 80/20 | 4.75 MW | 4.75 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958801 | AF2-171 C | 80/20 | 5.81 MW | 5.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 959311 | AF2-222 C | 80/20 | 5.55 MW | 5.55 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 960111 | AF2-302 C | 80/20 | 1.26 MW | 1.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 242889 | 05REUSENS | 80/20 | 0.04 MW | 0.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 925611 | AC1-036 C | 80/20 | 0.08 MW | 0.08 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938371 | AE1-056 C | 80/20 | 2.67 MW | 2.67 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938821 | AE1-108 C O1 | 80/20 | 10.13 MW | 10.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941011 | AE2-092 C | 80/20 | 11.2 MW | 11.2 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941791 | AE2-182 C | 80/20 | 0.59 MW | 0.59 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946291 | AF1-293 C O1 | 80/20 | 14.58 MW | 14.58 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946301 | AF1-294 C | 80/20 | 1.59 MW | 1.59 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946591 | AF1-323 C | 80/20 | 3.48 MW | 3.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958131 | AF2-107 C | 80/20 | 2.33 MW | 2.33 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958211 | AF2-115 C | 80/20 | 0.97 MW | 0.97 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 235034 | 01SHY_Z2-039 | 80/20 | 0.01 MW | 0.01 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 235035 | 01NHY_Z2-039 | 80/20 | 0.02 MW | 0.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 237092 | AD1-085_C | 80/20 | 0.16 MW | 0.16 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940451 | AE2-029 C | 80/20 | 3.28 MW | 3.28 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943571 | AF1-028 O1 | 80/20 | 18.07 MW | 18.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 933501 | AC2-165 C | 80/20 | 4.35 MW | 4.35 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944071 | AF1-075 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961061 | AF2-397 C | 80/20 | 12.98 MW | 12.98 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 313738 | 3CUSHAW | 80/20 | 0.1 MW | 0.1 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314333 | 6POWHATN | 80/20 | 0.15 MW | 0.15 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314677 | 6BUCKING | 80/20 | 0.26 MW | 0.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314859 | 4WSTVACO | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 926001 | AC1-076 C | Adder | -2.55 MW | -2.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958501 | AF2-144 C | 80/20 | 0.65 MW | 0.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966671 | AG1-537 C | 80/20 | 4.45 MW | 4.45 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315186 | 1LOWMORA | 80/20 | 0.44 MW | 0.44 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315188 | 1LOWMORC | 80/20 | 0.44 MW | 0.44 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315191 | 1BEARGRDN G1 | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315192 | 1BEARGRDN G2 | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315193 | 1BEARGRDN S1 | 80/20 | 5.67 MW | 5.67 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315201 | 1BATH 1A | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315202 | 1BATH 2B | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315203 | 1BATH 3C | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315204 | 1BATH 4D | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315205 | 1BATH 5E | 80/20 | 7.9 MW | 7.9 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315206 | 1BATH 6F | 80/20 | 7.92 MW | 7.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315216 | 1CUNINGA | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315217 | 1CUNINGB | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315218 | 1CUNINGC | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315219 | 1CUNINGD | 80/20 | 4.22 MW | 4.22 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315616 | AA1-038 C | 80/20 | 1.04 MW | 1.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 932854 | AC2-112 C | 80/20 | 14.33 MW | 14.33 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938561 | AE1-075 C | 80/20 | 0.13 MW | 0.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938625 | AE1-084 C | 80/20 | 6.92 MW | 6.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941381 | AE2-134 | Adder | -1.76 MW | -1.49 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963461 | AG1-195 | 80/20 | 16.21 MW | 16.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965531 | AG1-421 C | 80/20 | 13.88 MW | 13.88 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965541 | AG1-422 | 80/20 | 5.78 MW | 5.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966851 | AG1-556 C | 80/20 | 10.31 MW | 10.31 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.09 MW | 1.09 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.81 MW | 0.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.07 MW | 26.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 21.87 MW | 21.87 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.65 MW | 17.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.7 MW | 3.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.12 MW | 1.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.81 MW | 2.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.07 MW | 3.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.52 MW | 0.52 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 961791 | AG1-021 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963171 | AG1-166 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963181 | AG1-167 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963191 | AG1-168 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963201 | AG1-169 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963211 | AG1-170 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963321 | AG1-181 C O1 | 80/20 | 73.64 MW | 73.64 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963361 | AG1-185 O1 | 80/20 | 35.63 MW | 35.63 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964111 | AG1-272 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964121 | AG1-273 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964131 | AG1-274 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965191 | AG1-384 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965641 | AG1-432 C O1 | 80/20 | 28.75 MW | 28.75 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965831 | AG1-451 | 80/20 | 4.79 MW | 4.79 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 314429 | 3JTRSVLE | 80/20 | 0.18 MW | 0.18 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 942461 | AE2-259 C O1 | 80/20 | 14.38 MW | 14.38 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 958801 | AF2-171 C | 80/20 | 45.25 MW | 45.25 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 959311 | AF2-222 C | 80/20 | 66.71 MW | 66.71 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 925611 | AC1-036 C | 80/20 | 1.02 MW | 1.02 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 938371 | AE1-056 C | 80/20 | 16.65 MW | 16.65 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 946301 | AF1-294 C | 80/20 | 1.67 MW | 1.67 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 958211 | AF2-115 C | 80/20 | 1.02 MW | 1.02 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.12 MW | 0.12 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.02 MW | 0.02 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.13 MW | 0.13 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.12 MW | 0.12 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.15 MW | 0.15 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 961791 | AG1-021 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 961891 | AG1-030 C | 80/20 | 28.04 MW | 28.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 962491 | AG1-098 C O1 | 80/20 | 16.65 MW | 16.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963171 | AG1-166 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963181 | AG1-167 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963191 | AG1-168 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963201 | AG1-169 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963211 | AG1-170 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 1.76 MW | 1.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 25.4 MW | 25.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 12.29 MW | 12.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 15.11 MW | 15.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 3.44 MW | 3.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966691 | AG1-539 C | 80/20 | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 0.75 MW | 0.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 14.44 MW | 14.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 3.02 MW | 3.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 52.09 MW | 52.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 5.04 MW | 5.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 5.04 MW | 5.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 2.91 MW | 2.91 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 2.91 MW | 2.91 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 8.68 MW | 8.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966361 | AG1-505 C | 80/20 | 5.44 MW | 5.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966371 | AG1-506 C | 80/20 | 5.44 MW | 5.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 2.51 MW | 2.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.92 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.16 MW | 0.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 0.51 MW | 0.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315153 | 1CLOVER1 | 80/20 | 9.98 MW | 9.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315154 | 1CLOVER2 | 80/20 | 9.89 MW | 9.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.31 MW | 0.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 926023 | AC1-080 C | 80/20 | 0.15 MW | 0.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 2.79 MW | 2.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 927251 | AC1-221 C | 80/20 | 0.96 MW | 0.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 927261 | AC1-222 C | 80/20 | 2.26 MW | 2.26 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934311 | AD1-055 C | 80/20 | 1.57 MW | 1.57 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934341 | AD1-058 C | 80/20 | 2.4 MW | 2.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934615 | AD1-087 C | 80/20 | 5.79 MW | 5.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934625 | AD1-088 C | 80/20 | 18.78 MW | 18.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934991 | AD1-131 C | 80/20 | 0.79 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 935171 | AD1-152 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 19.29 MW | 19.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 937481 | AD2-202 C O1 | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 26.05 MW | 26.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 942751 | AE2-291 C | 80/20 | 3.53 MW | 3.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 942761 | AE2-292 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 943901 | AF1-058 C | 80/20 | 1.28 MW | 1.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 945811 | AF1-246 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 27.43 MW | 27.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 960061 | AF2-297 C | 80/20 | 5.12 MW | 5.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 0.97 MW | 0.97 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315266 | 1PLYWOOD A | 80/20 | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316118 | AC1-105 C | 80/20 | 4.19 MW | 4.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 4.2 MW | 4.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.71 MW | 1.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 932761 | AC2-100 C | 80/20 | 2.2 MW | 2.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 14.09 MW | 14.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.2 MW | 7.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.67 MW | 2.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 941791 | AE2-182 C | 80/20 | 3.05 MW | 3.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 0.57 MW | 0.57 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 946301 | AF1-294 C | 80/20 | 8.29 MW | 8.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 957481 | AF2-042 C | 80/20 | 31.67 MW | 31.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 958211 | AF2-115 C | 80/20 | 5.06 MW | 5.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 933501 | AC2-165 C | Adder | -6.54 MW | -5.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 958501 | AF2-144 C | Adder | -0.97 MW | -0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 0.46 MW | 0.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 7.72 MW | 7.72 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.57 MW | 0.57 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316123 | AC1-075 C | 80/20 | 0.46 MW | 0.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.82 MW | 1.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 30.99 MW | 30.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.51 MW | 6.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.56 MW | 8.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.76 MW | 2.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.13 MW | 2.13 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.32 MW | 0.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.05 MW | 1.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.26 MW | 0.26 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 961791 | AG1-021 C | 80/20 | 4.04 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 961891 | AG1-030 C | 80/20 | 28.03 MW | 28.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 962491 | AG1-098 C O1 | 80/20 | 16.64 MW | 16.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963171 | AG1-166 C | 80/20 | 4.04 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963181 | AG1-167 C | 80/20 | 4.04 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963191 | AG1-168 C | 80/20 | 4.04 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963201 | AG1-169 C | 80/20 | 4.04 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963211 | AG1-170 C | 80/20 | 4.04 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 3.61 MW | 3.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 1.76 MW | 1.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 25.4 MW | 25.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 12.29 MW | 12.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 4.07 MW | 4.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 4.07 MW | 4.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 4.07 MW | 4.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 15.11 MW | 15.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 966691 | AG1-539 C | 80/20 | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 0.75 MW | 0.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 4.07 MW | 4.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 14.44 MW | 14.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 3.02 MW | 3.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 52.08 MW | 52.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 5.03 MW | 5.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 5.03 MW | 5.03 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 2.91 MW | 2.91 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 2.91 MW | 2.91 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 8.68 MW | 8.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 966361 | AG1-505 C | 80/20 | 5.44 MW | 5.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 966371 | AG1-506 C | 80/20 | 5.44 MW | 5.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 2.51 MW | 2.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.92 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.16 MW | 0.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 0.51 MW | 0.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315153 | 1CLOVER1 | 80/20 | 9.98 MW | 9.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315154 | 1CLOVER2 | 80/20 | 9.88 MW | 9.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.31 MW | 0.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.87 MW | 0.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.87 MW | 0.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.87 MW | 0.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.87 MW | 0.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 926023 | AC1-080 C | 80/20 | 0.15 MW | 0.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 2.78 MW | 2.78 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 927251 | AC1-221 C | 80/20 | 0.96 MW | 0.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 927261 | AC1-222 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 934311 | AD1-055 C | 80/20 | 1.57 MW | 1.57 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 934341 | AD1-058 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 934615 | AD1-087 C | 80/20 | 5.79 MW | 5.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 934625 | AD1-088 C | 80/20 | 18.77 MW | 18.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 934991 | AD1-131 C | 80/20 | 0.79 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 935171 | AD1-152 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 19.28 MW | 19.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 937481 | AD2-202 C O1 | 80/20 | 1.7 MW | 1.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 26.04 MW | 26.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 942751 | AE2-291 C | 80/20 | 3.53 MW | 3.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 942761 | AE2-292 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 943901 | AF1-058 C | 80/20 | 1.28 MW | 1.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 945811 | AF1-246 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 27.42 MW | 27.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 960061 | AF2-297 C | 80/20 | 5.12 MW | 5.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 0.96 MW | 0.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.87 MW | 0.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.87 MW | 0.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315266 | 1PLYWOOD A | 80/20 | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 316118 | AC1-105 C | 80/20 | 4.19 MW | 4.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 4.19 MW | 4.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.71 MW | 1.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 932761 | AC2-100 C | 80/20 | 2.2 MW | 2.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 14.09 MW | 14.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.19 MW | 7.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.66 MW | 2.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 941791 | AE2-182 C | 80/20 | 3.05 MW | 3.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 0.57 MW | 0.57 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 946301 | AF1-294 C | 80/20 | 8.29 MW | 8.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 957481 | AF2-042 C | 80/20 | 31.64 MW | 31.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 958211 | AF2-115 C | 80/20 | 5.06 MW | 5.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 933501 | AC2-165 C | Adder | -6.54 MW | -5.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 314677 | 6BUCKING | 80/20 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 958501 | AF2-144 C | Adder | -0.97 MW | -0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 0.46 MW | 0.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 7.71 MW | 7.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.57 MW | 0.57 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | 316123 | AC1-075 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.82 MW | 1.82 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 30.91 MW | 30.91 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.41 MW | 6.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.5 MW | 8.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.75 MW | 2.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.32 MW | 0.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.04 MW | 1.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.26 MW | 0.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.7 MW | 1.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 6.79 MW | 6.79 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314333 | 6POWHATN | 80/20 | 0.12 MW | 0.12 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.18 MW | 0.18 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | 80/20 | 0.52 MW | 0.52 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 4.14 MW | 4.14 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938561 | AE1-075 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 69.52 MW | 69.52 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 33.63 MW | 33.63 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 19.89 MW | 19.89 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 3.31 MW | 3.31 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 9.95 MW | 9.95 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 40.21 MW | 40.21 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 62.22 MW | 62.22 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.95 MW | 0.95 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 14.29 MW | 14.29 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.12 MW | 0.12 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.41 MW | 0.41 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.34 MW | 0.34 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.51 MW | 0.51 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 6.79 MW | 6.79 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314333 | 6POWHATN | 80/20 | 0.12 MW | 0.12 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.18 MW | 0.18 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | 80/20 | 0.52 MW | 0.52 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 4.14 MW | 4.14 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938561 | AE1-075 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 961801 | AG1-022 C | 80/20 | 1.12 MW | 1.12 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 962741 | AG1-123 C O1 | 80/20 | 1.95 MW | 1.95 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963021 | AG1-151 O1 | 80/20 | 8.16 MW | 8.16 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963471 | AG1-196 O1 | 80/20 | 16.03 MW | 16.03 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 964231 | AG1-284 C O1 | 80/20 | 5.0 MW | 5.0 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 964831 | AG1-346 C | 80/20 | 0.76 MW | 0.76 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965581 | AG1-426 | 80/20 | 1.7 MW | 1.7 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965641 | AG1-432 C O1 | 80/20 | 7.32 MW | 7.32 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965831 | AG1-451 | 80/20 | 1.22 MW | 1.22 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966251 | AG1-494 C | 80/20 | 1.05 MW | 1.05 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 942461 | AE2-259 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 960111 | AF2-302 C | 80/20 | 1.12 MW | 1.12 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938371 | AE1-056 C | 80/20 | 1.95 MW | 1.95 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938821 | AE1-108 C O1 | 80/20 | 8.96 MW | 8.96 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 941011 | AE2-092 C | 80/20 | 10.11 MW | 10.11 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 946291 | AF1-293 C O1 | 80/20 | 13.04 MW | 13.04 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 946591 | AF1-323 C | 80/20 | 3.07 MW | 3.07 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 958131 | AF2-107 C | 80/20 | 2.04 MW | 2.04 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 235034 | 01SHY_Z2-039 | 80/20 | 0.01 MW | 0.01 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 235035 | 01NHY_Z2-039 | 80/20 | 0.02 MW | 0.02 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 237092 | AD1-085_C | 80/20 | 0.15 MW | 0.15 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 940451 | AE2-029 C | 80/20 | 3.03 MW | 3.03 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 943571 | AF1-028 O1 | 80/20 | 16.32 MW | 16.32 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 933501 | AC2-165 C | 80/20 | 3.12 MW | 3.12 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 944071 | AF1-075 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 961061 | AF2-397 C | 80/20 | 11.82 MW | 11.82 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 313738 | 3CUSHAW | 80/20 | 0.09 MW | 0.09 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 314677 | 6BUCKING | 80/20 | 0.21 MW | 0.21 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 314859 | 4WSTVACO | 80/20 | 4.02 MW | 4.02 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 926001 | AC1-076 C | Adder | -2.89 MW | -2.45 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966671 | AG1-537 C | 80/20 | 4.18 MW | 4.18 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315186 | 1LOWMORA | 80/20 | 0.41 MW | 0.41 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315188 | 1LOWMORC | 80/20 | 0.41 MW | 0.41 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315191 | 1BEARGRDN G1 | 80/20 | 3.85 MW | 3.85 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315192 | 1BEARGRDN G2 | 80/20 | 3.85 MW | 3.85 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315193 | 1BEARGRDN S1 | 80/20 | 4.97 MW | 4.97 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315201 | 1BATH 1A | 80/20 | 6.84 MW | 6.84 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315202 | 1BATH 2B | 80/20 | 6.84 MW | 6.84 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315203 | 1BATH 3C | 80/20 | 6.84 MW | 6.84 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315204 | 1BATH 4D | 80/20 | 6.84 MW | 6.84 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315205 | 1BATH 5E | 80/20 | 6.85 MW | 6.85 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315206 | 1BATH 6F | 80/20 | 6.86 MW | 6.86 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315216 | 1CUNINGA | 80/20 | 2.89 MW | 2.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315217 | 1CUNINGB | 80/20 | 2.89 MW | 2.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315218 | 1CUNINGC | 80/20 | 2.89 MW | 2.89 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315219 | 1CUNINGD | 80/20 | 6.46 MW | 6.46 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315616 | AA1-038 C | 80/20 | 0.96 MW | 0.96 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 932854 | AC2-112 C | 80/20 | 13.48 MW | 13.48 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938625 | AE1-084 C | 80/20 | 6.51 MW | 6.51 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 941381 | AE2-134 | Adder | -1.99 MW | -1.69 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963461 | AG1-195 | 80/20 | 14.13 MW | 14.13 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965531 | AG1-421 C | 80/20 | 12.9 MW | 12.9 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965541 | AG1-422 | 80/20 | 5.38 MW | 5.38 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966851 | AG1-556 C | 80/20 | 9.46 MW | 9.46 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.47 MW | 0.47 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.72 MW | 0.72 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.48 MW | 15.48 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 23.83 MW | 23.83 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.39 MW | 16.39 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.7 MW | 0.7 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.17 MW | 1.17 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.84 MW | 2.84 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.64 MW | 0.64 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6HOLLYMD-6CASHSCORNER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.55 MW | 0.55 MW |
| Details for 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 961801 | AG1-022 C | 80/20 | 1.12 MW | 1.12 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 962741 | AG1-123 C O1 | 80/20 | 1.95 MW | 1.95 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963021 | AG1-151 O1 | 80/20 | 8.16 MW | 8.16 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963471 | AG1-196 O1 | 80/20 | 16.03 MW | 16.03 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 964231 | AG1-284 C O1 | 80/20 | 5.0 MW | 5.0 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 964831 | AG1-346 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965581 | AG1-426 | 80/20 | 1.7 MW | 1.7 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965641 | AG1-432 C O1 | 80/20 | 7.32 MW | 7.32 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965831 | AG1-451 | 80/20 | 1.22 MW | 1.22 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966251 | AG1-494 C | 80/20 | 1.05 MW | 1.05 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 942461 | AE2-259 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 960111 | AF2-302 C | 80/20 | 1.12 MW | 1.12 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938371 | AE1-056 C | 80/20 | 1.95 MW | 1.95 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938821 | AE1-108 C O1 | 80/20 | 8.96 MW | 8.96 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 941011 | AE2-092 C | 80/20 | 10.11 MW | 10.11 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 946291 | AF1-293 C O1 | 80/20 | 13.04 MW | 13.04 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 946591 | AF1-323 C | 80/20 | 3.07 MW | 3.07 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 958131 | AF2-107 C | 80/20 | 2.04 MW | 2.04 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 235034 | 01SHY_Z2-039 | 80/20 | 0.01 MW | 0.01 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 235035 | 01NHY_Z2-039 | 80/20 | 0.02 MW | 0.02 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 237092 | AD1-085_C | 80/20 | 0.15 MW | 0.15 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 940451 | AE2-029 C | 80/20 | 3.03 MW | 3.03 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 943571 | AF1-028 O1 | 80/20 | 16.32 MW | 16.32 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 933501 | AC2-165 C | 80/20 | 3.12 MW | 3.12 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 944071 | AF1-075 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 961061 | AF2-397 C | 80/20 | 11.82 MW | 11.82 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 313738 | 3CUSHAW | 80/20 | 0.09 MW | 0.09 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 314677 | 6BUCKING | 80/20 | 0.21 MW | 0.21 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 314859 | 4WSTVACO | 80/20 | 4.02 MW | 4.02 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 926001 | AC1-076 C | Adder | -2.89 MW | -2.45 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966671 | AG1-537 C | 80/20 | 4.18 MW | 4.18 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315186 | 1LOWMORA | 80/20 | 0.41 MW | 0.41 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315188 | 1LOWMORC | 80/20 | 0.41 MW | 0.41 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315191 | 1BEARGRDN G1 | 80/20 | 3.85 MW | 3.85 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315192 | 1BEARGRDN G2 | 80/20 | 3.85 MW | 3.85 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315193 | 1BEARGRDN S1 | 80/20 | 4.97 MW | 4.97 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315201 | 1BATH 1A | 80/20 | 6.84 MW | 6.84 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315202 | 1BATH 2B | 80/20 | 6.84 MW | 6.84 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315203 | 1BATH 3C | 80/20 | 6.84 MW | 6.84 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315204 | 1BATH 4D | 80/20 | 6.84 MW | 6.84 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315205 | 1BATH 5E | 80/20 | 6.85 MW | 6.85 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315206 | 1BATH 6F | 80/20 | 6.86 MW | 6.86 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315216 | 1CUNINGA | 80/20 | 2.89 MW | 2.89 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315217 | 1CUNINGB | 80/20 | 2.89 MW | 2.89 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315218 | 1CUNINGC | 80/20 | 2.89 MW | 2.89 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315219 | 1CUNINGD | 80/20 | 6.46 MW | 6.46 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315616 | AA1-038 C | 80/20 | 0.96 MW | 0.96 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 932854 | AC2-112 C | 80/20 | 13.48 MW | 13.48 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938625 | AE1-084 C | 80/20 | 6.51 MW | 6.51 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 941381 | AE2-134 | Adder | -1.99 MW | -1.69 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963461 | AG1-195 | 80/20 | 14.13 MW | 14.13 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965531 | AG1-421 C | 80/20 | 12.9 MW | 12.9 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965541 | AG1-422 | 80/20 | 5.38 MW | 5.38 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966851 | AG1-556 C | 80/20 | 9.46 MW | 9.46 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.47 MW | 0.47 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.72 MW | 0.72 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.48 MW | 15.48 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 23.83 MW | 23.83 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.39 MW | 16.39 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.7 MW | 0.7 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.17 MW | 1.17 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.84 MW | 2.84 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.64 MW | 0.64 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6CASHSCORNER-6GORDNVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.55 MW | 0.55 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 69.76 MW | 69.76 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 33.75 MW | 33.75 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 20.45 MW | 20.45 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 3.41 MW | 3.41 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 10.22 MW | 10.22 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 40.52 MW | 40.52 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 62.48 MW | 62.48 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.96 MW | 0.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 14.43 MW | 14.43 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.1 MW | 0.1 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.13 MW | 0.13 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.15 MW | 0.15 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.29 MW | 0.29 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.41 MW | 0.41 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 69.76 MW | 69.76 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 33.75 MW | 33.75 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 20.45 MW | 20.45 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 3.41 MW | 3.41 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 10.22 MW | 10.22 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 40.52 MW | 40.52 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 62.48 MW | 62.48 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.96 MW | 0.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 14.43 MW | 14.43 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.1 MW | 0.1 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.13 MW | 0.13 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.15 MW | 0.15 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.29 MW | 0.29 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.41 MW | 0.41 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 55.97 MW | 55.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 27.08 MW | 27.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 41.52 MW | 41.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 27.68 MW | 27.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 39.37 MW | 39.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 26.3 MW | 26.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 66.44 MW | 66.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 44.29 MW | 44.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 11.07 MW | 11.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 2.21 MW | 2.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.51 MW | 1.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 5.39 MW | 5.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 43.19 MW | 43.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 28.79 MW | 28.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 22.15 MW | 22.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 55.37 MW | 55.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 37.09 MW | 37.09 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 5.13 MW | 5.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 14.17 MW | 14.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.81 MW | 0.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 5.15 MW | 5.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 21.48 MW | 21.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 11.74 MW | 11.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 13.62 MW | 13.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 9.08 MW | 9.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 8.3 MW | 8.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 5.54 MW | 5.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 45.08 MW | 45.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 21.81 MW | 21.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 33.45 MW | 33.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 22.3 MW | 22.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 31.71 MW | 31.71 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 21.18 MW | 21.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 53.51 MW | 53.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 35.67 MW | 35.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 8.92 MW | 8.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 1.78 MW | 1.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 4.34 MW | 4.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 34.78 MW | 34.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 23.19 MW | 23.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 17.84 MW | 17.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 44.59 MW | 44.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 29.88 MW | 29.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 4.13 MW | 4.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 11.42 MW | 11.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.65 MW | 0.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 17.3 MW | 17.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 9.45 MW | 9.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 10.97 MW | 10.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 7.31 MW | 7.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 6.69 MW | 6.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 4.46 MW | 4.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961791 | AG1-021 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961792 | AG1-021 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961891 | AG1-030 C | 50/50 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961892 | AG1-030 E | 50/50 | 22.44 MW | 22.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963171 | AG1-166 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963172 | AG1-166 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963181 | AG1-167 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963182 | AG1-167 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963191 | AG1-168 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963192 | AG1-168 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963201 | AG1-169 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963202 | AG1-169 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963211 | AG1-170 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963212 | AG1-170 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963301 | AG1-179 C | Adder | 3.09 MW | 2.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963311 | AG1-180 | Adder | 1.5 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963321 | AG1-181 C O1 | 50/50 | 28.68 MW | 28.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963361 | AG1-185 O1 | 50/50 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964111 | AG1-272 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964112 | AG1-272 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964121 | AG1-273 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964122 | AG1-273 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964131 | AG1-274 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964132 | AG1-274 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964241 | AG1-285 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964242 | AG1-285 E O1 | 50/50 | 10.46 MW | 10.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964791 | AG1-342 C | Adder | 2.21 MW | 1.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964792 | AG1-342 E | Adder | 1.74 MW | 1.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965191 | AG1-384 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965192 | AG1-384 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965591 | AG1-427 C | 50/50 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965592 | AG1-427 E | 50/50 | 10.05 MW | 10.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965601 | AG1-428 C O2 | Adder | 2.58 MW | 2.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965602 | AG1-428 E O2 | Adder | 1.72 MW | 1.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965641 | AG1-432 C O1 | 50/50 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965642 | AG1-432 E O1 | 50/50 | 44.61 MW | 44.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965721 | AG1-440 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965722 | AG1-440 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965731 | AG1-441 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965732 | AG1-441 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965771 | AG1-445 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965781 | AG1-446 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965831 | AG1-451 | 50/50 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313853 | 3PONTONDP | 50/50 | 1.65 MW | 1.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314429 | 3JTRSVLE | 50/50 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314713 | 3PAMPLIN | 50/50 | 4.39 MW | 4.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315159 | 1KERR 2 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315160 | 1KERR 3 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315161 | 1KERR 4 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315162 | 1KERR 5 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936265 | AD2-033 C | 50/50 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936266 | AD2-033 E | 50/50 | 14.44 MW | 14.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942461 | AE2-259 C O1 | 50/50 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942462 | AE2-259 E O1 | 50/50 | 22.31 MW | 22.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958801 | AF2-171 C | 50/50 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958802 | AF2-171 E | 50/50 | 24.61 MW | 24.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959311 | AF2-222 C | 50/50 | 31.81 MW | 31.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959312 | AF2-222 E | 50/50 | 21.32 MW | 21.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315163 | 1KERR 6 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 316131 | AB2-060 C | 50/50 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924162 | AB2-060 E OP | 50/50 | 4.68 MW | 4.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925611 | AC1-036 C | 50/50 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925612 | AC1-036 E | 50/50 | 2.81 MW | 2.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938371 | AE1-056 C | 50/50 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938372 | AE1-056 E | 50/50 | 9.57 MW | 9.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939181 | AE1-148 C | 50/50 | 6.23 MW | 6.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939182 | AE1-148 E | 50/50 | 4.16 MW | 4.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 940661 | AE2-053 O1 | 50/50 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946301 | AF1-294 C | 50/50 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946302 | AF1-294 E | 50/50 | 6.76 MW | 6.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958211 | AF2-115 C | 50/50 | 6.18 MW | 6.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958212 | AF2-115 E | 50/50 | 4.12 MW | 4.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962561 | AG1-105 C O1 | 50/50 | 5.47 MW | 5.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962562 | AG1-105 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313527 | AB2-043 C | 50/50 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924022 | AB2-043 E O1 | 50/50 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961791 | AG1-021 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961792 | AG1-021 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961891 | AG1-030 C | 50/50 | 11.84 MW | 11.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961892 | AG1-030 E | 50/50 | 7.89 MW | 7.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963171 | AG1-166 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963172 | AG1-166 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963181 | AG1-167 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963182 | AG1-167 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963191 | AG1-168 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963192 | AG1-168 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963201 | AG1-169 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963202 | AG1-169 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963211 | AG1-170 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963212 | AG1-170 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963301 | AG1-179 C | Adder | 3.43 MW | 2.92 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963311 | AG1-180 | Adder | 1.67 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963321 | AG1-181 C O1 | 50/50 | 16.16 MW | 16.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963361 | AG1-185 O1 | 50/50 | 7.82 MW | 7.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964111 | AG1-272 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964121 | AG1-273 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964131 | AG1-274 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964241 | AG1-285 C O1 | 50/50 | 13.75 MW | 13.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964242 | AG1-285 E O1 | 50/50 | 9.16 MW | 9.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964791 | AG1-342 C | Adder | 2.86 MW | 2.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964792 | AG1-342 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965191 | AG1-384 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965591 | AG1-427 C | 50/50 | 12.98 MW | 12.98 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965592 | AG1-427 E | 50/50 | 8.67 MW | 8.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965601 | AG1-428 C O2 | Adder | 2.87 MW | 2.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965602 | AG1-428 E O2 | Adder | 1.91 MW | 1.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965641 | AG1-432 C O1 | Adder | 8.86 MW | 7.53 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965642 | AG1-432 E O1 | Adder | 5.91 MW | 5.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965721 | AG1-440 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965722 | AG1-440 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965731 | AG1-441 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965732 | AG1-441 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965771 | AG1-445 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965781 | AG1-446 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965831 | AG1-451 | Adder | 1.48 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313853 | 3PONTONDP | Adder | 0.48 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 314713 | 3PAMPLIN | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315159 | 1KERR 2 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315160 | 1KERR 3 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315161 | 1KERR 4 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315162 | 1KERR 5 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925785 | AC1-054 E | 50/50 | 7.3 MW | 7.3 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 926274 | AC1-105 E | Adder | 1.4 MW | 1.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936265 | AD2-033 C | 50/50 | 12.62 MW | 12.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936266 | AD2-033 E | 50/50 | 8.41 MW | 8.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942461 | AE2-259 C O1 | Adder | 4.43 MW | 3.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942462 | AE2-259 E O1 | Adder | 2.95 MW | 2.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958801 | AF2-171 C | 50/50 | 10.81 MW | 10.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958802 | AF2-171 E | 50/50 | 7.21 MW | 7.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959311 | AF2-222 C | 50/50 | 14.91 MW | 14.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959312 | AF2-222 E | 50/50 | 9.99 MW | 9.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315163 | 1KERR 6 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315164 | 1KERR 7 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316118 | AC1-105 C | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316129 | AC1-054 C | 50/50 | 15.84 MW | 15.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316131 | AB2-060 C | 50/50 | 1.77 MW | 1.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924162 | AB2-060 E OP | 50/50 | 4.9 MW | 4.9 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924301 | AB2-077 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924302 | AB2-077 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924311 | AB2-078 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924312 | AB2-078 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924321 | AB2-079 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924322 | AB2-079 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925611 | AC1-036 C | 50/50 | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925612 | AC1-036 E | 50/50 | 1.43 MW | 1.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938371 | AE1-056 C | Adder | 4.16 MW | 3.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938372 | AE1-056 E | Adder | 2.27 MW | 1.93 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939181 | AE1-148 C | 50/50 | 17.48 MW | 17.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939182 | AE1-148 E | 50/50 | 11.65 MW | 11.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 940661 | AE2-053 O1 | 50/50 | 6.47 MW | 6.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946301 | AF1-294 C | Adder | 2.94 MW | 2.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946302 | AF1-294 E | Adder | 1.96 MW | 1.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958211 | AF2-115 C | Adder | 1.79 MW | 1.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958212 | AF2-115 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962561 | AG1-105 C O1 | 50/50 | 6.82 MW | 6.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962562 | AG1-105 E O1 | 50/50 | 4.55 MW | 4.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313527 | AB2-043 C | 50/50 | 0.63 MW | 0.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.44 MW | 0.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.66 MW | 0.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.42 MW | 0.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.06 MW | 0.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.18 MW | 0.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.81 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.24 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.47 MW | 0.47 MW |
| Details for 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.34 MW | 71.34 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.56 MW | 47.56 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 14.97 MW | 14.97 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.24 MW | 7.24 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.18 MW | 62.18 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.46 MW | 41.46 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.36 MW | 10.36 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 69.6 MW | 69.6 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 46.4 MW | 46.4 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.09 MW | 31.09 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.73 MW | 20.73 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.7 MW | 28.7 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.14 MW | 19.14 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.45 MW | 19.45 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.03 MW | 13.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 9.18 MW | 9.18 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 25.35 MW | 25.35 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.54 MW | 14.54 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.94 MW | 7.94 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.35 MW | 12.35 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.04 MW | 0.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.03 MW | 0.03 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.07 MW | 0.07 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.23 MW | 0.23 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.09 MW | 0.09 MW |
| 3BUTCHER CRK-3CHASCTY2 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 86.08 MW | 86.08 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 41.65 MW | 41.65 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963362 | AG1-185 BAT | 50/50 | 13.36 MW | 13.36 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963362 | AG1-185 BAT | 50/50 | 13.36 MW | 13.36 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 16.45 MW | 16.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 12.93 MW | 12.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | 50/50 | 12.87 MW | 12.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | 50/50 | 26.91 MW | 26.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.37 MW | 71.37 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.58 MW | 47.58 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 69.62 MW | 69.62 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 46.41 MW | 46.41 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| AD2-033 TAP-3BUTCHER CRK 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | 50/50 | 12.85 MW | 12.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | 50/50 | 26.86 MW | 26.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 926274 | AC1-105 E | 50/50 | 12.85 MW | 12.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | 50/50 | 26.86 MW | 26.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.37 MW | 71.37 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.58 MW | 47.58 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| AG1-030 TAP-3VICT DP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.37 MW | 71.37 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.58 MW | 47.58 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 3VICT DP-3VICTRIA 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| Details for AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 16.45 MW | 16.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 12.93 MW | 12.93 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964793 | AG1-342 BAT | 50/50 | 3.12 MW | 3.12 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | Adder | 11.78 MW | 10.01 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | Adder | 7.85 MW | 6.67 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 2.51 MW | 2.13 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 1.22 MW | 1.04 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | Adder | 13.24 MW | 11.26 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | Adder | 6.41 MW | 5.45 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | Adder | 2.02 MW | 1.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | Adder | 2.02 MW | 1.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | Adder | 2.02 MW | 1.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | Adder | 9.83 MW | 8.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | Adder | 6.55 MW | 5.57 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | Adder | 2.02 MW | 1.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | Adder | 9.32 MW | 7.92 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | Adder | 6.22 MW | 5.29 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 2.09 MW | 1.78 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 1.39 MW | 1.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | Adder | 15.72 MW | 13.36 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | Adder | 10.48 MW | 8.91 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 5.57 MW | 4.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 3.72 MW | 3.16 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 5.57 MW | 4.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 3.72 MW | 3.16 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.22 MW | 2.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.22 MW | 2.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | Adder | 2.62 MW | 2.23 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | Adder | 0.52 MW | 0.45 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | Adder | 1.28 MW | 1.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315158 | 1KERR 1 | 50/50 | 0.36 MW | 0.36 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 1.98 MW | 1.68 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -1.45 MW | -1.23 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.01 MW | -0.85 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | Adder | 10.21 MW | 8.68 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | Adder | 6.81 MW | 5.79 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | Adder | 7.86 MW | 6.68 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | Adder | 5.24 MW | 4.45 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -0.82 MW | -0.69 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | Adder | 11.79 MW | 10.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | Adder | 7.86 MW | 6.68 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | Adder | 13.1 MW | 11.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | Adder | 8.78 MW | 7.46 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315266 | 1PLYWOOD A | 50/50 | 6.11 MW | 6.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 4.29 MW | 3.65 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | Adder | 3.35 MW | 2.85 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 1.83 MW | 1.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 1.83 MW | 1.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 1.83 MW | 1.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | Adder | 1.22 MW | 1.04 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | Adder | 5.08 MW | 4.32 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | Adder | 2.78 MW | 2.36 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 7.45 MW | 7.45 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 4.96 MW | 4.96 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | Adder | 2.76 MW | 2.34 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | Adder | 3.22 MW | 2.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | Adder | 2.15 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | Adder | 1.96 MW | 1.67 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | Adder | 1.31 MW | 1.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | Adder | 2.21 MW | 1.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.08 MW | 0.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.08 MW | 0.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.16 MW | 0.16 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.57 MW | 0.57 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.11 MW | 0.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.12 MW | 0.12 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.05 MW | 0.05 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.19 MW | 0.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.19 MW | 0.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| Details for AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | Adder | 11.71 MW | 9.95 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | Adder | 7.8 MW | 6.63 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 2.49 MW | 2.12 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 1.21 MW | 1.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | Adder | 13.16 MW | 11.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | Adder | 6.37 MW | 5.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | Adder | 9.76 MW | 8.3 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | Adder | 6.51 MW | 5.53 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | Adder | 9.26 MW | 7.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | Adder | 6.18 MW | 5.26 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 2.08 MW | 1.77 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 1.38 MW | 1.18 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | Adder | 15.62 MW | 13.28 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | Adder | 10.42 MW | 8.85 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 5.54 MW | 4.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 3.7 MW | 3.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 5.54 MW | 4.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 3.7 MW | 3.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | Adder | 2.6 MW | 2.21 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | Adder | 0.52 MW | 0.44 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | Adder | 1.27 MW | 1.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315158 | 1KERR 1 | 50/50 | 0.35 MW | 0.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 1.97 MW | 1.67 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -1.47 MW | -1.25 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.02 MW | -0.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | Adder | 10.14 MW | 8.62 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | Adder | 6.76 MW | 5.75 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | Adder | 7.81 MW | 6.64 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | Adder | 5.21 MW | 4.43 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -0.83 MW | -0.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | Adder | 11.72 MW | 9.96 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | Adder | 7.81 MW | 6.64 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | Adder | 13.02 MW | 11.07 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.42 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315266 | 1PLYWOOD A | 50/50 | 6.1 MW | 6.1 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 4.27 MW | 3.63 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | Adder | 3.33 MW | 2.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | Adder | 1.21 MW | 1.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | Adder | 5.05 MW | 4.29 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | Adder | 2.76 MW | 2.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 7.41 MW | 7.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 4.94 MW | 4.94 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | Adder | 2.74 MW | 2.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | Adder | 2.13 MW | 1.81 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | Adder | 1.95 MW | 1.66 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | Adder | 1.3 MW | 1.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | Adder | 2.2 MW | 1.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.09 MW | 0.09 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.18 MW | 0.18 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.08 MW | 0.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.05 MW | 0.05 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.22 MW | 0.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| Details for 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | Adder | 11.71 MW | 9.95 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | Adder | 7.81 MW | 6.63 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 2.49 MW | 2.12 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 1.21 MW | 1.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | Adder | 13.16 MW | 11.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | Adder | 6.37 MW | 5.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | Adder | 9.76 MW | 8.3 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | Adder | 6.51 MW | 5.53 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | Adder | 9.26 MW | 7.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | Adder | 6.18 MW | 5.26 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 2.08 MW | 1.77 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 1.38 MW | 1.18 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | Adder | 15.62 MW | 13.27 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | Adder | 10.41 MW | 8.85 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 5.54 MW | 4.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 3.7 MW | 3.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 5.54 MW | 4.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 3.7 MW | 3.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | Adder | 2.6 MW | 2.21 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | Adder | 0.52 MW | 0.44 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | Adder | 1.27 MW | 1.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315158 | 1KERR 1 | 50/50 | 0.35 MW | 0.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 1.97 MW | 1.67 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -1.47 MW | -1.25 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.02 MW | -0.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | Adder | 10.15 MW | 8.62 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | Adder | 6.76 MW | 5.75 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | Adder | 7.81 MW | 6.64 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | Adder | 5.21 MW | 4.42 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -0.83 MW | -0.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | Adder | 11.71 MW | 9.96 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | Adder | 7.81 MW | 6.64 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | Adder | 13.02 MW | 11.06 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315266 | 1PLYWOOD A | 50/50 | 6.1 MW | 6.1 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 4.27 MW | 3.63 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | Adder | 3.33 MW | 2.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | Adder | 1.21 MW | 1.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | Adder | 5.05 MW | 4.29 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | Adder | 2.76 MW | 2.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 7.41 MW | 7.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 4.94 MW | 4.94 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | Adder | 2.74 MW | 2.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | Adder | 2.13 MW | 1.81 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | Adder | 1.95 MW | 1.66 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | Adder | 1.3 MW | 1.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | Adder | 2.2 MW | 1.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.09 MW | 0.09 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.18 MW | 0.18 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.08 MW | 0.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.05 MW | 0.05 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.22 MW | 0.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| Details for 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.37 MW | 71.37 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.58 MW | 47.58 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 3VICTRIA-3LUNENBURG 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964793 | AG1-342 BAT | 50/50 | 3.12 MW | 3.12 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964793 | AG1-342 BAT | 50/50 | 3.12 MW | 3.12 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 71.37 MW | 71.37 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 47.58 MW | 47.58 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 3LUNENBURG-AD2-033 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.52 MW | 38.52 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.89 MW | 28.89 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.27 MW | 61.27 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.07 MW | 6.07 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.47 MW | 2.47 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963362 | AG1-185 BAT | 50/50 | 13.36 MW | 13.36 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964133 | AG1-274 BAT | 50/50 | 3.47 MW | 3.47 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964113 | AG1-272 BAT | 50/50 | 3.47 MW | 3.47 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965193 | AG1-384 BAT | 50/50 | 1.49 MW | 1.49 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964123 | AG1-273 BAT | 50/50 | 3.47 MW | 3.47 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.01 MW | 0.01 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961801 | AG1-022 C | 50/50 | 1.23 MW | 1.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961802 | AG1-022 E | 50/50 | 0.82 MW | 0.82 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 38.1 MW | 38.1 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 25.4 MW | 25.4 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 962491 | AG1-098 C O1 | 50/50 | 46.0 MW | 46.0 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 962492 | AG1-098 E O1 | 50/50 | 30.66 MW | 30.66 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 42.79 MW | 42.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 20.7 MW | 20.7 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 6.53 MW | 6.53 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 1.94 MW | 1.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 6.53 MW | 6.53 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 1.94 MW | 1.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 6.53 MW | 6.53 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 1.94 MW | 1.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964231 | AG1-284 C O1 | 50/50 | 6.34 MW | 6.34 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964232 | AG1-284 E O1 | 50/50 | 4.23 MW | 4.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 31.75 MW | 31.75 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 21.17 MW | 21.17 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 6.53 MW | 6.53 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 1.94 MW | 1.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965581 | AG1-426 | 50/50 | 1.98 MW | 1.98 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 30.1 MW | 30.1 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 20.11 MW | 20.11 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 50.8 MW | 50.8 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 33.87 MW | 33.87 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 8.47 MW | 8.47 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 1.69 MW | 1.69 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.15 MW | 1.15 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 4.12 MW | 4.12 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934615 | AD1-087 C | Adder | -6.0 MW | -5.1 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934625 | AD1-088 C | 50/50 | 50.85 MW | 50.85 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934626 | AD1-088 E | 50/50 | 23.93 MW | 23.93 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 935171 | AD1-152 C O1 | Adder | -5.61 MW | -4.77 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 33.02 MW | 33.02 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 22.01 MW | 22.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 937481 | AD2-202 C O1 | Adder | -1.76 MW | -1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 25.4 MW | 25.4 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 16.93 MW | 16.93 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946592 | AF1-323 E | 50/50 | 2.25 MW | 2.25 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 38.1 MW | 38.1 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 25.4 MW | 25.4 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 42.33 MW | 42.33 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 28.36 MW | 28.36 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 960111 | AF2-302 C | 50/50 | 1.23 MW | 1.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 960112 | AF2-302 E | 50/50 | 0.82 MW | 0.82 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 3.92 MW | 3.92 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 10.84 MW | 10.84 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.62 MW | 0.62 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 3.94 MW | 3.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 16.43 MW | 16.43 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 8.97 MW | 8.97 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938821 | AE1-108 C O1 | 50/50 | 10.45 MW | 10.45 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938822 | AE1-108 E O1 | 50/50 | 6.96 MW | 6.96 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941011 | AE2-092 C | 50/50 | 10.07 MW | 10.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941012 | AE2-092 E | 50/50 | 6.71 MW | 6.71 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941791 | AE2-182 C | 50/50 | 8.26 MW | 8.26 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941792 | AE2-182 E | 50/50 | 3.85 MW | 3.85 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946291 | AF1-293 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946292 | AF1-293 E O1 | 50/50 | 2.71 MW | 2.71 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 10.41 MW | 10.41 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 6.94 MW | 6.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946591 | AF1-323 C | 50/50 | 3.38 MW | 3.38 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 6.35 MW | 6.35 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 4.23 MW | 4.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 924032 | AB2-045 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961061 | AF2-397 C | 50/50 | 11.54 MW | 11.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961062 | AF2-397 E | 50/50 | 7.7 MW | 7.7 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314677 | 6BUCKING | 50/50 | 0.72 MW | 0.72 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315191 | 1BEARGRDN G1 | 50/50 | 5.83 MW | 5.83 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315192 | 1BEARGRDN G2 | 50/50 | 5.83 MW | 5.83 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315193 | 1BEARGRDN S1 | 50/50 | 7.54 MW | 7.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.54 MW | 0.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.51 MW | 2.51 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.71 MW | 0.71 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.61 MW | 0.61 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.79 MW | 0.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.42 MW | 0.42 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.64 MW | 0.64 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.14 MW | 2.14 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.92 MW | 0.92 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.24 MW | 0.24 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.63 MW | 1.63 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.66 MW | 1.66 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.22 MW | 0.22 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 2.46 MW | 2.46 MW |
| Details for AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961791 | AG1-021 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961792 | AG1-021 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961891 | AG1-030 C | 50/50 | 37.57 MW | 37.57 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961892 | AG1-030 E | 50/50 | 25.05 MW | 25.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962491 | AG1-098 C O1 | 50/50 | 57.29 MW | 57.29 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962492 | AG1-098 E O1 | 50/50 | 38.19 MW | 38.19 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963171 | AG1-166 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963172 | AG1-166 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963181 | AG1-167 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963182 | AG1-167 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963191 | AG1-168 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963192 | AG1-168 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963201 | AG1-169 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963202 | AG1-169 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963211 | AG1-170 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963212 | AG1-170 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963321 | AG1-181 C O1 | 50/50 | 32.02 MW | 32.02 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963361 | AG1-185 O1 | 50/50 | 15.49 MW | 15.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964111 | AG1-272 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964112 | AG1-272 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964121 | AG1-273 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964122 | AG1-273 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964131 | AG1-274 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964132 | AG1-274 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964241 | AG1-285 C O1 | 50/50 | 17.5 MW | 17.5 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964242 | AG1-285 E O1 | 50/50 | 11.67 MW | 11.67 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965191 | AG1-384 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965192 | AG1-384 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965591 | AG1-427 C | 50/50 | 16.79 MW | 16.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965592 | AG1-427 E | 50/50 | 11.21 MW | 11.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965641 | AG1-432 C O1 | 50/50 | 74.7 MW | 74.7 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965642 | AG1-432 E O1 | 50/50 | 49.8 MW | 49.8 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965831 | AG1-451 | 50/50 | 12.45 MW | 12.45 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 313853 | 3PONTONDP | 50/50 | 1.84 MW | 1.84 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 314429 | 3JTRSVLE | 50/50 | 1.25 MW | 1.25 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 314713 | 3PAMPLIN | 50/50 | 4.9 MW | 4.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315160 | 1KERR 3 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315161 | 1KERR 4 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315162 | 1KERR 5 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 934625 | AD1-088 C | 50/50 | 63.57 MW | 63.57 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 934626 | AD1-088 E | 50/50 | 29.92 MW | 29.92 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 936265 | AD2-033 C | 50/50 | 24.18 MW | 24.18 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 936266 | AD2-033 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 942461 | AE2-259 C O1 | 50/50 | 37.35 MW | 37.35 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 942462 | AE2-259 E O1 | 50/50 | 24.9 MW | 24.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958801 | AF2-171 C | 50/50 | 41.21 MW | 41.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958802 | AF2-171 E | 50/50 | 27.47 MW | 27.47 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 959311 | AF2-222 C | 50/50 | 35.51 MW | 35.51 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 959312 | AF2-222 E | 50/50 | 23.79 MW | 23.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315163 | 1KERR 6 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315164 | 1KERR 7 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 316131 | AB2-060 C | 50/50 | 1.89 MW | 1.89 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924162 | AB2-060 E OP | 50/50 | 5.23 MW | 5.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924301 | AB2-077 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924302 | AB2-077 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924311 | AB2-078 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924312 | AB2-078 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924321 | AB2-079 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924322 | AB2-079 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 925611 | AC1-036 C | 50/50 | 0.49 MW | 0.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 925612 | AC1-036 E | 50/50 | 3.14 MW | 3.14 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 938371 | AE1-056 C | 50/50 | 19.55 MW | 19.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 938372 | AE1-056 E | 50/50 | 10.68 MW | 10.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 939181 | AE1-148 C | 50/50 | 6.96 MW | 6.96 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 939182 | AE1-148 E | 50/50 | 4.64 MW | 4.64 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 940661 | AE2-053 O1 | 50/50 | 2.58 MW | 2.58 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 941791 | AE2-182 C | 50/50 | 10.33 MW | 10.33 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 941792 | AE2-182 E | 50/50 | 4.81 MW | 4.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946301 | AF1-294 C | 50/50 | 11.32 MW | 11.32 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946302 | AF1-294 E | 50/50 | 7.55 MW | 7.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958211 | AF2-115 C | 50/50 | 6.9 MW | 6.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958212 | AF2-115 E | 50/50 | 4.6 MW | 4.6 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924032 | AB2-045 E | 50/50 | 4.76 MW | 4.76 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 314677 | 6BUCKING | 50/50 | 1.74 MW | 1.74 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962561 | AG1-105 C O1 | 50/50 | 6.11 MW | 6.11 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962562 | AG1-105 E O1 | 50/50 | 4.07 MW | 4.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.76 MW | 2.76 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.07 MW | 1.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.03 MW | 1.03 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.54 MW | 0.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.04 MW | 9.04 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.22 MW | 10.22 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.74 MW | 28.74 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.16 MW | 19.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.39 MW | 25.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.92 MW | 16.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.62 MW | 39.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.44 MW | 9.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.23 MW | 39.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.52 MW | 29.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.71 MW | 14.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.69 MW | 8.69 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.56 MW | 7.56 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.83 MW | 0.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.15 MW | 1.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.3 MW | 5.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.35 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.04 MW | 9.04 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.22 MW | 10.22 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.74 MW | 28.74 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.16 MW | 19.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.39 MW | 25.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.92 MW | 16.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.62 MW | 39.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.44 MW | 9.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.23 MW | 39.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.52 MW | 29.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.71 MW | 14.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.69 MW | 8.69 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.56 MW | 7.56 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.83 MW | 0.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.15 MW | 1.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.3 MW | 5.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.35 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.45 MW | 14.45 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.21 MW | 8.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.24 MW | 7.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.09 MW | 1.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.12 MW | 5.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.45 MW | 14.45 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.21 MW | 8.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.24 MW | 7.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.09 MW | 1.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.12 MW | 5.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.44 MW | 3.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.06 MW | 14.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.08 MW | 20.08 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966251 | AG1-494 C | Adder | 1.67 MW | 1.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966252 | AG1-494 E | Adder | 2.5 MW | 2.12 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.3 MW | 6.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.44 MW | 3.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.76 MW | 28.76 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.17 MW | 19.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.4 MW | 25.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.93 MW | 16.93 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.64 MW | 39.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.45 MW | 9.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.67 MW | 36.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.45 MW | 24.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | Adder | -2.72 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.92 MW | 19.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.73 MW | 0.73 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.85 MW | 14.85 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.88 MW | 8.88 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.68 MW | 7.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.82 MW | 0.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.67 MW | 1.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.45 MW | 0.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.17 MW | 1.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.01 MW | 17.01 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966252 | AG1-494 E | Adder | 2.48 MW | 2.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.3 MW | 25.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.87 MW | 16.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.56 MW | 39.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.12 MW | 7.12 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.59 MW | 14.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.39 MW | 8.39 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.36 MW | 7.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.6 MW | 1.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.11 MW | 1.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.03 MW | 5.03 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.32 MW | 1.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 9.04 MW | 9.04 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 6.03 MW | 6.03 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 9.04 MW | 9.04 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 6.03 MW | 6.03 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 9.04 MW | 9.04 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 6.03 MW | 6.03 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 9.04 MW | 9.04 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 6.03 MW | 6.03 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 9.04 MW | 9.04 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 6.03 MW | 6.03 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 9.04 MW | 9.04 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 6.03 MW | 6.03 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 15.0 MW | 15.0 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 7.25 MW | 7.25 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.68 MW | 2.68 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.8 MW | 0.8 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.68 MW | 2.68 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.8 MW | 0.8 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.68 MW | 2.68 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.8 MW | 0.8 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.68 MW | 2.68 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.8 MW | 0.8 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 62.22 MW | 62.22 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 41.48 MW | 41.48 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 10.37 MW | 10.37 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 3.01 MW | 3.01 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 2.05 MW | 2.05 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 3.65 MW | 3.65 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 31.11 MW | 31.11 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 20.74 MW | 20.74 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 28.73 MW | 28.73 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 19.15 MW | 19.15 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.48 MW | 19.48 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 13.05 MW | 13.05 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 14.55 MW | 14.55 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 7.95 MW | 7.95 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 18.53 MW | 18.53 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 12.36 MW | 12.36 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 11.3 MW | 11.3 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 7.53 MW | 7.53 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.02 MW | 0.02 MW |
| 3MARTIN TAP-AG1-030 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 17.39 MW | 17.39 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 19.55 MW | 19.55 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 9.46 MW | 9.46 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 9.67 MW | 9.67 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 13.75 MW | 13.75 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 23.2 MW | 23.2 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 15.47 MW | 15.47 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 3.87 MW | 3.87 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | Adder | 1.32 MW | 1.12 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 15.07 MW | 15.07 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 10.04 MW | 10.04 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 11.6 MW | 11.6 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 17.4 MW | 17.4 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 11.6 MW | 11.6 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 19.33 MW | 19.33 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923991 | AB2-040 C O1 | Adder | -3.86 MW | -3.29 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 4.95 MW | 4.95 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963312 | AG1-180 BAT | 50/50 | 11.79 MW | 11.79 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.34 MW | 4.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.13 MW | 2.13 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.9 MW | 1.9 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.28 MW | 0.28 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.72 MW | 0.72 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 17.38 MW | 17.38 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | 50/50 | 20.43 MW | 20.43 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | 50/50 | 9.96 MW | 9.96 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 19.54 MW | 19.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 9.45 MW | 9.45 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 9.66 MW | 9.66 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 13.74 MW | 13.74 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | 50/50 | 17.06 MW | 17.06 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | 50/50 | 11.35 MW | 11.35 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 23.19 MW | 23.19 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 3.87 MW | 3.87 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314704 | 3LAWRENC | 50/50 | 1.24 MW | 1.24 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | Adder | 1.31 MW | 1.12 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 15.06 MW | 15.06 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 10.04 MW | 10.04 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 11.6 MW | 11.6 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 17.39 MW | 17.39 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 11.6 MW | 11.6 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 19.33 MW | 19.33 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923991 | AB2-040 C O1 | Adder | -3.87 MW | -3.29 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 4.94 MW | 4.94 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.29 MW | 4.29 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.06 MW | 2.06 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.85 MW | 1.85 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.41 MW | 0.41 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.27 MW | 0.27 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.76 MW | 0.76 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| Details for 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3MADSONV-AF2-222 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| Details for 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 17.39 MW | 17.39 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | 50/50 | 20.43 MW | 20.43 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | 50/50 | 9.96 MW | 9.96 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 19.55 MW | 19.55 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 9.46 MW | 9.46 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 9.67 MW | 9.67 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 13.75 MW | 13.75 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | 50/50 | 17.06 MW | 17.06 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | 50/50 | 11.35 MW | 11.35 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 23.2 MW | 23.2 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 15.47 MW | 15.47 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 3.87 MW | 3.87 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | Adder | 1.32 MW | 1.12 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 15.07 MW | 15.07 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 10.04 MW | 10.04 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 11.6 MW | 11.6 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 17.4 MW | 17.4 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 11.6 MW | 11.6 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 19.33 MW | 19.33 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923991 | AB2-040 C O1 | Adder | -3.86 MW | -3.29 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 4.95 MW | 4.95 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.34 MW | 4.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.13 MW | 2.13 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.9 MW | 1.9 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.28 MW | 0.28 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.72 MW | 0.72 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 2.31 MW | 2.31 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 17.32 MW | 17.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 11.55 MW | 11.55 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 2.31 MW | 2.31 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 2.31 MW | 2.31 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 2.31 MW | 2.31 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 2.31 MW | 2.31 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 2.31 MW | 2.31 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 19.48 MW | 19.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 9.42 MW | 9.42 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 2.97 MW | 2.97 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 0.88 MW | 0.88 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 2.97 MW | 2.97 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 0.88 MW | 0.88 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 2.97 MW | 2.97 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 0.88 MW | 0.88 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 14.45 MW | 14.45 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 9.63 MW | 9.63 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 2.74 MW | 2.74 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 2.15 MW | 2.15 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 2.97 MW | 2.97 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 0.88 MW | 0.88 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 13.7 MW | 13.7 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 9.15 MW | 9.15 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 23.12 MW | 23.12 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 15.41 MW | 15.41 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 3.85 MW | 3.85 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313506 | AB1-173 C OP | Adder | -3.56 MW | -3.03 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | Adder | 1.3 MW | 1.1 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 15.01 MW | 15.01 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 10.01 MW | 10.01 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 11.56 MW | 11.56 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 7.71 MW | 7.71 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 17.34 MW | 17.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 11.56 MW | 11.56 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 19.27 MW | 19.27 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 12.91 MW | 12.91 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | 2.72 MW | 2.31 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 1.78 MW | 1.78 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923991 | AB2-040 C O1 | Adder | -3.88 MW | -3.3 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 4.93 MW | 4.93 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 7.47 MW | 7.47 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 4.08 MW | 4.08 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 6.36 MW | 6.36 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 4.24 MW | 4.24 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 4.74 MW | 4.74 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 3.16 MW | 3.16 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 2.89 MW | 2.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 6.58 MW | 6.58 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 4.39 MW | 4.39 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 3.26 MW | 3.26 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963312 | AG1-180 BAT | 50/50 | 11.8 MW | 11.8 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.02 MW | 4.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.07 MW | 2.07 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.81 MW | 1.81 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.4 MW | 0.4 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.27 MW | 0.27 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.69 MW | 0.69 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.33 MW | 0.33 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 17.39 MW | 17.39 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 19.55 MW | 19.55 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 9.46 MW | 9.46 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 9.67 MW | 9.67 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 13.75 MW | 13.75 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 23.2 MW | 23.2 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 15.47 MW | 15.47 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 3.87 MW | 3.87 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | Adder | 1.32 MW | 1.12 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 15.07 MW | 15.07 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 10.04 MW | 10.04 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 11.6 MW | 11.6 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 17.4 MW | 17.4 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 11.6 MW | 11.6 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 19.33 MW | 19.33 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923991 | AB2-040 C O1 | Adder | -3.86 MW | -3.29 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 4.95 MW | 4.95 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963312 | AG1-180 BAT | 50/50 | 11.79 MW | 11.79 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.34 MW | 4.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.13 MW | 2.13 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.9 MW | 1.9 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.28 MW | 0.28 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.72 MW | 0.72 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 2.31 MW | 2.31 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 17.32 MW | 17.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 11.54 MW | 11.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 2.31 MW | 2.31 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 2.31 MW | 2.31 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 2.31 MW | 2.31 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 2.31 MW | 2.31 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 2.31 MW | 2.31 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | 50/50 | 20.41 MW | 20.41 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | 50/50 | 9.95 MW | 9.95 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 19.47 MW | 19.47 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 9.42 MW | 9.42 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 2.97 MW | 2.97 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 0.88 MW | 0.88 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 2.97 MW | 2.97 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 0.88 MW | 0.88 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 2.97 MW | 2.97 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 0.88 MW | 0.88 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 14.45 MW | 14.45 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 9.63 MW | 9.63 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 2.74 MW | 2.74 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 2.15 MW | 2.15 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 2.97 MW | 2.97 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 0.88 MW | 0.88 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 13.69 MW | 13.69 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 9.15 MW | 9.15 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | 50/50 | 17.04 MW | 17.04 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | 50/50 | 11.34 MW | 11.34 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 23.11 MW | 23.11 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 15.41 MW | 15.41 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 3.85 MW | 3.85 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313506 | AB1-173 C OP | Adder | -3.57 MW | -3.03 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314704 | 3LAWRENC | 50/50 | 1.24 MW | 1.24 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 1.87 MW | 1.87 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | Adder | 1.3 MW | 1.1 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 15.01 MW | 15.01 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 10.01 MW | 10.01 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 11.55 MW | 11.55 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 7.7 MW | 7.7 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 17.33 MW | 17.33 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 11.56 MW | 11.56 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 19.26 MW | 19.26 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 12.9 MW | 12.9 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | 2.72 MW | 2.31 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 1.78 MW | 1.78 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923991 | AB2-040 C O1 | Adder | -3.88 MW | -3.3 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 4.93 MW | 4.93 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 1.79 MW | 1.79 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 7.47 MW | 7.47 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 4.08 MW | 4.08 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 6.35 MW | 6.35 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 4.24 MW | 4.24 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 4.73 MW | 4.73 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 3.16 MW | 3.16 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 2.89 MW | 2.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 6.58 MW | 6.58 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 4.39 MW | 4.39 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 3.25 MW | 3.25 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.96 MW | 3.96 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.99 MW | 1.99 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.76 MW | 1.76 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.39 MW | 0.39 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.26 MW | 0.26 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.72 MW | 0.72 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.32 MW | 0.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.55 MW | 1.55 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 17.39 MW | 17.39 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.55 MW | 1.55 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.55 MW | 1.55 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.55 MW | 1.55 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.55 MW | 1.55 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.55 MW | 1.55 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 19.54 MW | 19.54 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 9.46 MW | 9.46 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 9.67 MW | 9.67 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 13.75 MW | 13.75 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 23.19 MW | 23.19 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 3.87 MW | 3.87 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 926274 | AC1-105 E | Adder | 1.32 MW | 1.12 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 15.07 MW | 15.07 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 10.05 MW | 10.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 11.6 MW | 11.6 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 17.39 MW | 17.39 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 11.6 MW | 11.6 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.33 MW | 19.33 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 923991 | AB2-040 C O1 | Adder | -3.86 MW | -3.29 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 4.95 MW | 4.95 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963312 | AG1-180 BAT | 50/50 | 11.79 MW | 11.79 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.34 MW | 4.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.13 MW | 2.13 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.9 MW | 1.9 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.28 MW | 0.28 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.72 MW | 0.72 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3CHASCTY-3NORVIEW 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 17.38 MW | 17.38 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | 50/50 | 20.43 MW | 20.43 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | 50/50 | 9.96 MW | 9.96 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 19.54 MW | 19.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 9.45 MW | 9.45 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 9.66 MW | 9.66 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 13.74 MW | 13.74 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | 50/50 | 17.06 MW | 17.06 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | 50/50 | 11.35 MW | 11.35 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 23.19 MW | 23.19 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 3.87 MW | 3.87 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314704 | 3LAWRENC | 50/50 | 1.24 MW | 1.24 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | Adder | 1.31 MW | 1.12 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 15.06 MW | 15.06 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 10.04 MW | 10.04 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 11.6 MW | 11.6 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 17.39 MW | 17.39 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 11.6 MW | 11.6 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 19.33 MW | 19.33 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 923991 | AB2-040 C O1 | Adder | -3.87 MW | -3.29 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 4.94 MW | 4.94 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.29 MW | 4.29 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.06 MW | 2.06 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.85 MW | 1.85 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.41 MW | 0.41 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.27 MW | 0.27 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.76 MW | 0.76 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 2.31 MW | 2.31 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 17.32 MW | 17.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 11.55 MW | 11.55 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 2.31 MW | 2.31 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 2.31 MW | 2.31 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 2.31 MW | 2.31 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 2.31 MW | 2.31 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 2.31 MW | 2.31 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | 50/50 | 20.42 MW | 20.42 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | 50/50 | 9.95 MW | 9.95 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 19.48 MW | 19.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 9.42 MW | 9.42 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 2.97 MW | 2.97 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 0.88 MW | 0.88 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 2.97 MW | 2.97 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 0.88 MW | 0.88 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 2.97 MW | 2.97 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 0.88 MW | 0.88 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 14.45 MW | 14.45 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 9.63 MW | 9.63 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 2.74 MW | 2.74 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 2.15 MW | 2.15 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 2.97 MW | 2.97 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 0.88 MW | 0.88 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 13.7 MW | 13.7 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 9.15 MW | 9.15 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | 50/50 | 17.05 MW | 17.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | 50/50 | 11.34 MW | 11.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 23.12 MW | 23.12 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 15.41 MW | 15.41 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 3.85 MW | 3.85 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313506 | AB1-173 C OP | Adder | -3.56 MW | -3.03 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | Adder | 1.3 MW | 1.1 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 15.01 MW | 15.01 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 10.01 MW | 10.01 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 11.56 MW | 11.56 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 7.71 MW | 7.71 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 17.34 MW | 17.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 11.56 MW | 11.56 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 19.27 MW | 19.27 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 12.91 MW | 12.91 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | 2.72 MW | 2.31 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 1.78 MW | 1.78 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923991 | AB2-040 C O1 | Adder | -3.88 MW | -3.3 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 4.93 MW | 4.93 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 1.79 MW | 1.79 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 7.47 MW | 7.47 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 4.08 MW | 4.08 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 6.36 MW | 6.36 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 4.24 MW | 4.24 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 4.74 MW | 4.74 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 3.16 MW | 3.16 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 2.89 MW | 2.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 6.58 MW | 6.58 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 4.39 MW | 4.39 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 3.26 MW | 3.26 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.02 MW | 4.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.07 MW | 2.07 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.81 MW | 1.81 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.4 MW | 0.4 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.27 MW | 0.27 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.69 MW | 0.69 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.33 MW | 0.33 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 17.38 MW | 17.38 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | 50/50 | 20.43 MW | 20.43 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | 50/50 | 9.96 MW | 9.96 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 19.54 MW | 19.54 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 9.45 MW | 9.45 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 9.66 MW | 9.66 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 13.74 MW | 13.74 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | 50/50 | 17.06 MW | 17.06 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | 50/50 | 11.35 MW | 11.35 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 23.18 MW | 23.18 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 3.86 MW | 3.86 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314704 | 3LAWRENC | 50/50 | 1.24 MW | 1.24 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 926274 | AC1-105 E | Adder | 1.31 MW | 1.12 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 15.06 MW | 15.06 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 10.04 MW | 10.04 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 11.59 MW | 11.59 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 17.39 MW | 17.39 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 11.59 MW | 11.59 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.32 MW | 19.32 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 923991 | AB2-040 C O1 | Adder | -3.87 MW | -3.29 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 4.94 MW | 4.94 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.29 MW | 4.29 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.05 MW | 2.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.85 MW | 1.85 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.41 MW | 0.41 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.27 MW | 0.27 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.76 MW | 0.76 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3LAWRENC-3FRMAN D 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 2.31 MW | 2.31 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 17.32 MW | 17.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 11.55 MW | 11.55 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 2.31 MW | 2.31 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 2.31 MW | 2.31 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 2.31 MW | 2.31 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 2.31 MW | 2.31 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 2.31 MW | 2.31 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 19.48 MW | 19.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 9.42 MW | 9.42 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 2.97 MW | 2.97 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 0.88 MW | 0.88 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 2.97 MW | 2.97 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 0.88 MW | 0.88 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 2.97 MW | 2.97 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 0.88 MW | 0.88 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 14.45 MW | 14.45 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 9.63 MW | 9.63 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 2.74 MW | 2.74 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 2.15 MW | 2.15 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 2.97 MW | 2.97 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 0.88 MW | 0.88 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 13.7 MW | 13.7 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 9.15 MW | 9.15 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 23.12 MW | 23.12 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 15.41 MW | 15.41 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 3.85 MW | 3.85 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313506 | AB1-173 C OP | Adder | -3.56 MW | -3.03 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | Adder | 1.3 MW | 1.1 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 15.01 MW | 15.01 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 10.01 MW | 10.01 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 11.56 MW | 11.56 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 7.71 MW | 7.71 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 17.34 MW | 17.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 11.56 MW | 11.56 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 19.27 MW | 19.27 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 12.91 MW | 12.91 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | 2.72 MW | 2.31 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 1.78 MW | 1.78 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923991 | AB2-040 C O1 | Adder | -3.88 MW | -3.3 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 4.93 MW | 4.93 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 1.79 MW | 1.79 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 7.47 MW | 7.47 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 4.08 MW | 4.08 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 6.36 MW | 6.36 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 4.24 MW | 4.24 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 4.74 MW | 4.74 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 3.16 MW | 3.16 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 2.89 MW | 2.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 6.58 MW | 6.58 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 4.39 MW | 4.39 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 3.26 MW | 3.26 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963312 | AG1-180 BAT | 50/50 | 11.8 MW | 11.8 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.02 MW | 4.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.07 MW | 2.07 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.81 MW | 1.81 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.4 MW | 0.4 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.27 MW | 0.27 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.69 MW | 0.69 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.33 MW | 0.33 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.55 MW | 1.55 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 17.39 MW | 17.39 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.55 MW | 1.55 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.55 MW | 1.55 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.55 MW | 1.55 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.55 MW | 1.55 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.55 MW | 1.55 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | 50/50 | 20.43 MW | 20.43 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | 50/50 | 9.96 MW | 9.96 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 19.54 MW | 19.54 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 9.46 MW | 9.46 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 9.67 MW | 9.67 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 13.75 MW | 13.75 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | 50/50 | 17.06 MW | 17.06 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | 50/50 | 11.35 MW | 11.35 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 23.19 MW | 23.19 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 3.87 MW | 3.87 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 926274 | AC1-105 E | Adder | 1.32 MW | 1.12 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 15.07 MW | 15.07 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 10.05 MW | 10.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 11.6 MW | 11.6 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 17.39 MW | 17.39 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 11.6 MW | 11.6 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.33 MW | 19.33 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 923991 | AB2-040 C O1 | Adder | -3.86 MW | -3.29 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 4.95 MW | 4.95 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.34 MW | 4.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.13 MW | 2.13 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.9 MW | 1.9 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.28 MW | 0.28 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.72 MW | 0.72 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3BRUNWICK-3LAWRENC 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.44 MW | 3.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.06 MW | 14.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.08 MW | 20.08 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966251 | AG1-494 C | Adder | 1.67 MW | 1.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966252 | AG1-494 E | Adder | 2.5 MW | 2.12 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.3 MW | 6.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.44 MW | 3.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.76 MW | 28.76 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.17 MW | 19.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.4 MW | 25.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.93 MW | 16.93 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.64 MW | 39.64 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.45 MW | 9.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | Adder | -17.76 MW | -15.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.67 MW | 36.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.45 MW | 24.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | Adder | -2.72 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.92 MW | 19.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.73 MW | 0.73 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.85 MW | 14.85 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.88 MW | 8.88 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.68 MW | 7.68 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.82 MW | 0.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.67 MW | 1.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.45 MW | 0.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.17 MW | 1.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 5.08 MW | 5.08 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 3.39 MW | 3.39 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961801 | AG1-022 C | 50/50 | 1.23 MW | 1.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961802 | AG1-022 E | 50/50 | 0.82 MW | 0.82 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 38.1 MW | 38.1 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 25.4 MW | 25.4 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 5.08 MW | 5.08 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 3.39 MW | 3.39 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 5.08 MW | 5.08 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 3.39 MW | 3.39 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 5.08 MW | 5.08 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 3.39 MW | 3.39 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 5.08 MW | 5.08 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 3.39 MW | 3.39 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 5.08 MW | 5.08 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 3.39 MW | 3.39 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 42.79 MW | 42.79 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 20.7 MW | 20.7 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 6.53 MW | 6.53 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 1.94 MW | 1.94 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 6.53 MW | 6.53 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 1.94 MW | 1.94 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 6.53 MW | 6.53 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 1.94 MW | 1.94 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964231 | AG1-284 C O1 | 50/50 | 6.34 MW | 6.34 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964232 | AG1-284 E O1 | 50/50 | 4.23 MW | 4.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 31.75 MW | 31.75 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 21.17 MW | 21.17 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 6.53 MW | 6.53 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 1.94 MW | 1.94 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965581 | AG1-426 | 50/50 | 1.98 MW | 1.98 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 30.1 MW | 30.1 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 20.11 MW | 20.11 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 50.8 MW | 50.8 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 33.87 MW | 33.87 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 8.47 MW | 8.47 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 1.69 MW | 1.69 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.15 MW | 1.15 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 4.12 MW | 4.12 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934615 | AD1-087 C | Adder | -6.0 MW | -5.1 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934625 | AD1-088 C | 50/50 | 50.85 MW | 50.85 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934626 | AD1-088 E | 50/50 | 23.93 MW | 23.93 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 935171 | AD1-152 C O1 | Adder | -5.61 MW | -4.77 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 33.02 MW | 33.02 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 22.01 MW | 22.01 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 937481 | AD2-202 C O1 | Adder | -1.76 MW | -1.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 25.4 MW | 25.4 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 16.93 MW | 16.93 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946592 | AF1-323 E | 50/50 | 2.25 MW | 2.25 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 38.1 MW | 38.1 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 25.4 MW | 25.4 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 42.33 MW | 42.33 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 28.36 MW | 28.36 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 960111 | AF2-302 C | 50/50 | 1.23 MW | 1.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 960112 | AF2-302 E | 50/50 | 0.82 MW | 0.82 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 3.92 MW | 3.92 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 10.84 MW | 10.84 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.62 MW | 0.62 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 3.94 MW | 3.94 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 16.43 MW | 16.43 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 8.97 MW | 8.97 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938821 | AE1-108 C O1 | 50/50 | 10.45 MW | 10.45 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938822 | AE1-108 E O1 | 50/50 | 6.96 MW | 6.96 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941011 | AE2-092 C | 50/50 | 10.07 MW | 10.07 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941012 | AE2-092 E | 50/50 | 6.71 MW | 6.71 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941791 | AE2-182 C | 50/50 | 8.26 MW | 8.26 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941792 | AE2-182 E | 50/50 | 3.85 MW | 3.85 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946291 | AF1-293 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946292 | AF1-293 E O1 | 50/50 | 2.71 MW | 2.71 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 10.41 MW | 10.41 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 6.94 MW | 6.94 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946591 | AF1-323 C | 50/50 | 3.38 MW | 3.38 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 6.35 MW | 6.35 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 4.23 MW | 4.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 924032 | AB2-045 E | 50/50 | 1.97 MW | 1.97 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961061 | AF2-397 C | 50/50 | 11.54 MW | 11.54 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961062 | AF2-397 E | 50/50 | 7.7 MW | 7.7 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314677 | 6BUCKING | 50/50 | 0.72 MW | 0.72 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315191 | 1BEARGRDN G1 | 50/50 | 5.83 MW | 5.83 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315192 | 1BEARGRDN G2 | 50/50 | 5.83 MW | 5.83 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315193 | 1BEARGRDN S1 | 50/50 | 7.54 MW | 7.54 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.54 MW | 0.54 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.51 MW | 2.51 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.71 MW | 0.71 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.61 MW | 0.61 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.79 MW | 0.79 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.42 MW | 0.42 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.64 MW | 0.64 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.14 MW | 2.14 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.92 MW | 0.92 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.24 MW | 0.24 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.63 MW | 1.63 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.66 MW | 1.66 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.22 MW | 0.22 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 2.46 MW | 2.46 MW |
| Details for 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.55 MW | 1.55 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 17.39 MW | 17.39 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.55 MW | 1.55 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.55 MW | 1.55 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.55 MW | 1.55 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.55 MW | 1.55 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.55 MW | 1.55 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 19.54 MW | 19.54 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 9.46 MW | 9.46 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 9.67 MW | 9.67 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 13.75 MW | 13.75 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 23.19 MW | 23.19 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 3.87 MW | 3.87 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 926274 | AC1-105 E | Adder | 1.32 MW | 1.12 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 15.07 MW | 15.07 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 10.05 MW | 10.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 11.6 MW | 11.6 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 17.39 MW | 17.39 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 11.6 MW | 11.6 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.33 MW | 19.33 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 923991 | AB2-040 C O1 | Adder | -3.86 MW | -3.29 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 4.95 MW | 4.95 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963312 | AG1-180 BAT | 50/50 | 11.79 MW | 11.79 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.34 MW | 4.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.13 MW | 2.13 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.9 MW | 1.9 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.28 MW | 0.28 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.72 MW | 0.72 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3NORVIEW-3SO HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 2.31 MW | 2.31 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 17.32 MW | 17.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 11.54 MW | 11.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 2.31 MW | 2.31 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 2.31 MW | 2.31 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 2.31 MW | 2.31 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 2.31 MW | 2.31 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 2.31 MW | 2.31 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | 50/50 | 20.41 MW | 20.41 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | 50/50 | 9.95 MW | 9.95 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 19.47 MW | 19.47 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 9.42 MW | 9.42 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 2.97 MW | 2.97 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 0.88 MW | 0.88 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 2.97 MW | 2.97 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 0.88 MW | 0.88 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 2.97 MW | 2.97 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 0.88 MW | 0.88 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 14.45 MW | 14.45 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 9.63 MW | 9.63 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 2.74 MW | 2.74 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 2.15 MW | 2.15 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 2.97 MW | 2.97 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 0.88 MW | 0.88 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 13.69 MW | 13.69 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 9.15 MW | 9.15 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | 50/50 | 17.04 MW | 17.04 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | 50/50 | 11.34 MW | 11.34 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 23.11 MW | 23.11 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 15.41 MW | 15.41 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 3.85 MW | 3.85 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313506 | AB1-173 C OP | Adder | -3.57 MW | -3.03 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314704 | 3LAWRENC | 50/50 | 1.24 MW | 1.24 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 1.87 MW | 1.87 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | Adder | 1.3 MW | 1.1 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 15.01 MW | 15.01 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 10.01 MW | 10.01 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 11.55 MW | 11.55 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 7.7 MW | 7.7 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 17.33 MW | 17.33 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 11.56 MW | 11.56 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 19.26 MW | 19.26 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 12.9 MW | 12.9 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | 2.72 MW | 2.31 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 1.78 MW | 1.78 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 923991 | AB2-040 C O1 | Adder | -3.88 MW | -3.3 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 4.93 MW | 4.93 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 2.21 MW | 2.21 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 1.79 MW | 1.79 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 7.47 MW | 7.47 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 4.08 MW | 4.08 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 6.35 MW | 6.35 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 4.24 MW | 4.24 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 4.73 MW | 4.73 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 3.16 MW | 3.16 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 2.89 MW | 2.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 6.58 MW | 6.58 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 4.39 MW | 4.39 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 3.25 MW | 3.25 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.96 MW | 3.96 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.99 MW | 1.99 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.76 MW | 1.76 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.31 MW | 0.31 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.11 MW | 0.11 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.39 MW | 0.39 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.26 MW | 0.26 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.72 MW | 0.72 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.32 MW | 0.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.01 MW | 17.01 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966252 | AG1-494 E | Adder | 2.48 MW | 2.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.3 MW | 25.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.87 MW | 16.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.56 MW | 39.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.12 MW | 7.12 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.59 MW | 14.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.39 MW | 8.39 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.36 MW | 7.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.6 MW | 1.6 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.11 MW | 1.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.03 MW | 5.03 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.32 MW | 1.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 17.38 MW | 17.38 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 11.59 MW | 11.59 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.32 MW | 2.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.54 MW | 1.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | 50/50 | 20.43 MW | 20.43 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | 50/50 | 9.96 MW | 9.96 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 19.54 MW | 19.54 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 9.45 MW | 9.45 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 2.98 MW | 2.98 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 0.89 MW | 0.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 2.98 MW | 2.98 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 0.89 MW | 0.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 2.98 MW | 2.98 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 0.89 MW | 0.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 9.66 MW | 9.66 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 2.76 MW | 2.76 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 2.17 MW | 2.17 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 2.98 MW | 2.98 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 0.89 MW | 0.89 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 13.74 MW | 13.74 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 9.18 MW | 9.18 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | 50/50 | 17.06 MW | 17.06 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | 50/50 | 11.35 MW | 11.35 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 23.18 MW | 23.18 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 15.46 MW | 15.46 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 3.61 MW | 3.07 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 2.41 MW | 2.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 3.61 MW | 3.07 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 2.41 MW | 2.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 2.09 MW | 1.77 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 2.09 MW | 1.77 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 3.86 MW | 3.86 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313506 | AB1-173 C OP | Adder | -3.55 MW | -3.02 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.53 MW | 0.53 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314704 | 3LAWRENC | 50/50 | 1.24 MW | 1.24 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 1.88 MW | 1.88 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 926274 | AC1-105 E | Adder | 1.31 MW | 1.12 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 15.06 MW | 15.06 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 10.04 MW | 10.04 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 11.59 MW | 11.59 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 17.39 MW | 17.39 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 11.59 MW | 11.59 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 19.32 MW | 19.32 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 12.95 MW | 12.95 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | 2.75 MW | 2.34 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 1.79 MW | 1.79 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 923991 | AB2-040 C O1 | Adder | -3.87 MW | -3.29 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 4.94 MW | 4.94 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 2.22 MW | 2.22 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 1.48 MW | 1.48 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.28 MW | 0.28 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 1.8 MW | 1.8 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 7.5 MW | 7.5 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 4.1 MW | 4.1 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 6.39 MW | 6.39 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 4.26 MW | 4.26 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 2.37 MW | 2.37 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 4.75 MW | 4.75 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 3.17 MW | 3.17 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 2.9 MW | 2.9 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 1.93 MW | 1.93 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 6.63 MW | 6.63 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 3.27 MW | 3.27 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.23 MW | 0.23 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.09 MW | 0.09 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.29 MW | 4.29 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.05 MW | 2.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.85 MW | 1.85 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.34 MW | 0.34 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.41 MW | 0.41 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.27 MW | 0.27 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.76 MW | 0.76 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3FRMAN D-3CLUBHSE71 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.44 MW | 3.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.06 MW | 14.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.08 MW | 20.08 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966251 | AG1-494 C | Adder | 1.67 MW | 1.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966252 | AG1-494 E | Adder | 2.5 MW | 2.12 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.3 MW | 6.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.44 MW | 3.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.76 MW | 28.76 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.17 MW | 19.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.4 MW | 25.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.93 MW | 16.93 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.64 MW | 39.64 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.45 MW | 9.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | Adder | -17.76 MW | -15.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.67 MW | 36.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.45 MW | 24.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | Adder | -2.72 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.92 MW | 19.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.73 MW | 0.73 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.85 MW | 14.85 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.88 MW | 8.88 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.68 MW | 7.68 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.82 MW | 0.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.67 MW | 1.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.45 MW | 0.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.17 MW | 1.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961791 | AG1-021 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961792 | AG1-021 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961891 | AG1-030 C | 50/50 | 37.57 MW | 37.57 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961892 | AG1-030 E | 50/50 | 25.05 MW | 25.05 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963171 | AG1-166 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963172 | AG1-166 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963181 | AG1-167 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963182 | AG1-167 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963191 | AG1-168 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963192 | AG1-168 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963201 | AG1-169 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963202 | AG1-169 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963211 | AG1-170 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963212 | AG1-170 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963321 | AG1-181 C O1 | 50/50 | 32.02 MW | 32.02 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 963361 | AG1-185 O1 | 50/50 | 15.49 MW | 15.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 964111 | AG1-272 C | 50/50 | 5.21 MW | 5.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 964112 | AG1-272 E | 50/50 | 1.55 MW | 1.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 964121 | AG1-273 C | 50/50 | 5.21 MW | 5.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 964122 | AG1-273 E | 50/50 | 1.55 MW | 1.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 964131 | AG1-274 C | 50/50 | 5.21 MW | 5.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 964132 | AG1-274 E | 50/50 | 1.55 MW | 1.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 964241 | AG1-285 C O1 | 50/50 | 17.5 MW | 17.5 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 964242 | AG1-285 E O1 | 50/50 | 11.67 MW | 11.67 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965191 | AG1-384 C | 50/50 | 5.21 MW | 5.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965192 | AG1-384 E | 50/50 | 1.55 MW | 1.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965591 | AG1-427 C | 50/50 | 16.79 MW | 16.79 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965592 | AG1-427 E | 50/50 | 11.21 MW | 11.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965641 | AG1-432 C O1 | 50/50 | 74.7 MW | 74.7 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965642 | AG1-432 E O1 | 50/50 | 49.8 MW | 49.8 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965831 | AG1-451 | 50/50 | 12.45 MW | 12.45 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 313853 | 3PONTONDP | 50/50 | 1.84 MW | 1.84 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 314429 | 3JTRSVLE | 50/50 | 1.25 MW | 1.25 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 314713 | 3PAMPLIN | 50/50 | 4.9 MW | 4.9 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 315159 | 1KERR 2 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 315160 | 1KERR 3 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 315161 | 1KERR 4 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 934625 | AD1-088 C | 50/50 | 63.57 MW | 63.57 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 934626 | AD1-088 E | 50/50 | 29.92 MW | 29.92 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 936265 | AD2-033 C | 50/50 | 24.18 MW | 24.18 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 936266 | AD2-033 E | 50/50 | 16.12 MW | 16.12 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 942461 | AE2-259 C O1 | 50/50 | 37.35 MW | 37.35 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 942462 | AE2-259 E O1 | 50/50 | 24.9 MW | 24.9 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958801 | AF2-171 C | 50/50 | 41.21 MW | 41.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958802 | AF2-171 E | 50/50 | 27.47 MW | 27.47 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 959311 | AF2-222 C | 50/50 | 35.51 MW | 35.51 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 959312 | AF2-222 E | 50/50 | 23.79 MW | 23.79 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 315163 | 1KERR 6 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 315164 | 1KERR 7 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 316131 | AB2-060 C | 50/50 | 1.89 MW | 1.89 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924162 | AB2-060 E OP | 50/50 | 5.23 MW | 5.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924301 | AB2-077 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924302 | AB2-077 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924311 | AB2-078 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924312 | AB2-078 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924321 | AB2-079 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924322 | AB2-079 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 925611 | AC1-036 C | 50/50 | 0.49 MW | 0.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 925612 | AC1-036 E | 50/50 | 3.14 MW | 3.14 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 938371 | AE1-056 C | 50/50 | 19.55 MW | 19.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 938372 | AE1-056 E | 50/50 | 10.68 MW | 10.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 939181 | AE1-148 C | 50/50 | 6.96 MW | 6.96 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 939182 | AE1-148 E | 50/50 | 4.64 MW | 4.64 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 940661 | AE2-053 O1 | 50/50 | 2.58 MW | 2.58 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 941791 | AE2-182 C | 50/50 | 10.33 MW | 10.33 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 941792 | AE2-182 E | 50/50 | 4.81 MW | 4.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946301 | AF1-294 C | 50/50 | 11.32 MW | 11.32 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946302 | AF1-294 E | 50/50 | 7.55 MW | 7.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958211 | AF2-115 C | 50/50 | 6.9 MW | 6.9 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958212 | AF2-115 E | 50/50 | 4.6 MW | 4.6 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924032 | AB2-045 E | 50/50 | 4.76 MW | 4.76 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 314677 | 6BUCKING | 50/50 | 1.74 MW | 1.74 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962561 | AG1-105 C O1 | 50/50 | 6.11 MW | 6.11 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962562 | AG1-105 E O1 | 50/50 | 4.07 MW | 4.07 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.76 MW | 2.76 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.07 MW | 1.07 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.03 MW | 1.03 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.54 MW | 0.54 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.01 MW | 17.01 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966252 | AG1-494 E | Adder | 2.48 MW | 2.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.3 MW | 25.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.87 MW | 16.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.56 MW | 39.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.12 MW | 7.12 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.59 MW | 14.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.39 MW | 8.39 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.36 MW | 7.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.6 MW | 1.6 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.11 MW | 1.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.03 MW | 5.03 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.32 MW | 1.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961791 | AG1-021 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961792 | AG1-021 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961891 | AG1-030 C | 50/50 | 15.91 MW | 15.91 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961892 | AG1-030 E | 50/50 | 10.61 MW | 10.61 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962491 | AG1-098 C O1 | 50/50 | 25.66 MW | 25.66 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962492 | AG1-098 E O1 | 50/50 | 17.11 MW | 17.11 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963171 | AG1-166 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963172 | AG1-166 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963181 | AG1-167 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963182 | AG1-167 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963191 | AG1-168 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963192 | AG1-168 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963201 | AG1-169 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963202 | AG1-169 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963211 | AG1-170 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963212 | AG1-170 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963321 | AG1-181 C O1 | 50/50 | 16.63 MW | 16.63 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963361 | AG1-185 O1 | 50/50 | 8.04 MW | 8.04 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964111 | AG1-272 C | 50/50 | 2.58 MW | 2.58 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964112 | AG1-272 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964121 | AG1-273 C | 50/50 | 2.58 MW | 2.58 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964122 | AG1-273 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964131 | AG1-274 C | 50/50 | 2.58 MW | 2.58 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964132 | AG1-274 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964241 | AG1-285 C O1 | 50/50 | 11.57 MW | 11.57 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964242 | AG1-285 E O1 | 50/50 | 7.72 MW | 7.72 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964791 | AG1-342 C | 50/50 | 5.29 MW | 5.29 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964792 | AG1-342 E | 50/50 | 4.16 MW | 4.16 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 966691 | AG1-539 C | 50/50 | 4.88 MW | 4.88 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 966692 | AG1-539 E | 50/50 | 6.56 MW | 6.56 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965191 | AG1-384 C | 50/50 | 2.58 MW | 2.58 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965192 | AG1-384 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965591 | AG1-427 C | 50/50 | 10.99 MW | 10.99 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965592 | AG1-427 E | 50/50 | 7.35 MW | 7.35 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965641 | AG1-432 C O1 | 50/50 | 24.21 MW | 24.21 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965642 | AG1-432 E O1 | 50/50 | 16.14 MW | 16.14 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965721 | AG1-440 C | Adder | 4.18 MW | 3.55 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965722 | AG1-440 E | Adder | 2.79 MW | 2.37 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965731 | AG1-441 C | Adder | 4.18 MW | 3.55 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965732 | AG1-441 E | Adder | 2.79 MW | 2.37 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965771 | AG1-445 | Adder | 2.42 MW | 2.05 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965781 | AG1-446 | Adder | 2.42 MW | 2.05 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965831 | AG1-451 | 50/50 | 4.04 MW | 4.04 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 313853 | 3PONTONDP | 50/50 | 0.73 MW | 0.73 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314429 | 3JTRSVLE | 50/50 | 0.5 MW | 0.5 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314713 | 3PAMPLIN | 50/50 | 1.82 MW | 1.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315153 | 1CLOVER1 | 50/50 | 36.85 MW | 36.85 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315154 | 1CLOVER2 | 50/50 | 36.49 MW | 36.49 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926023 | AC1-080 C | 50/50 | 0.39 MW | 0.39 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926274 | AC1-105 E | 50/50 | 3.82 MW | 3.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927251 | AC1-221 C | 50/50 | 2.11 MW | 2.11 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927252 | AC1-221 E | 50/50 | 2.11 MW | 2.11 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927261 | AC1-222 C | 50/50 | 5.42 MW | 5.42 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927262 | AC1-222 E | 50/50 | 5.16 MW | 5.16 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934311 | AD1-055 C | 50/50 | 3.76 MW | 3.76 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934312 | AD1-055 E | 50/50 | 0.97 MW | 0.97 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934341 | AD1-058 C | 50/50 | 5.3 MW | 5.3 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934342 | AD1-058 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934615 | AD1-087 C | 50/50 | 21.34 MW | 21.34 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934616 | AD1-087 E | 50/50 | 10.01 MW | 10.01 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934625 | AD1-088 C | 50/50 | 28.35 MW | 28.35 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934626 | AD1-088 E | 50/50 | 13.34 MW | 13.34 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934991 | AD1-131 C | 50/50 | 1.74 MW | 1.74 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934992 | AD1-131 E | 50/50 | 1.16 MW | 1.16 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 935171 | AD1-152 C O1 | 50/50 | 19.21 MW | 19.21 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 935172 | AD1-152 E O1 | 50/50 | 12.81 MW | 12.81 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 936265 | AD2-033 C | 50/50 | 12.77 MW | 12.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 936266 | AD2-033 E | 50/50 | 8.51 MW | 8.51 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 937481 | AD2-202 C O1 | 50/50 | 6.25 MW | 6.25 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 937482 | AD2-202 E O1 | 50/50 | 2.93 MW | 2.93 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942461 | AE2-259 C O1 | 50/50 | 12.11 MW | 12.11 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942462 | AE2-259 E O1 | 50/50 | 8.07 MW | 8.07 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942751 | AE2-291 C | 50/50 | 9.33 MW | 9.33 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942752 | AE2-291 E | 50/50 | 6.22 MW | 6.22 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942761 | AE2-292 C O1 | 50/50 | 11.62 MW | 11.62 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942762 | AE2-292 E O1 | 50/50 | 7.75 MW | 7.75 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 943901 | AF1-058 C | 50/50 | 3.04 MW | 3.04 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 943902 | AF1-058 E | 50/50 | 2.02 MW | 2.02 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958801 | AF2-171 C | 50/50 | 16.35 MW | 16.35 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958802 | AF2-171 E | 50/50 | 10.9 MW | 10.9 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 959311 | AF2-222 C | 50/50 | 16.92 MW | 16.92 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 959312 | AF2-222 E | 50/50 | 11.33 MW | 11.33 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 960061 | AF2-297 C | 50/50 | 12.14 MW | 12.14 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 960062 | AF2-297 E | 50/50 | 8.09 MW | 8.09 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315266 | 1PLYWOOD A | 50/50 | 1.79 MW | 1.79 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316118 | AC1-105 C | 50/50 | 7.99 MW | 7.99 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316131 | AB2-060 C | 50/50 | 1.4 MW | 1.4 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924162 | AB2-060 E OP | 50/50 | 3.86 MW | 3.86 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924301 | AB2-077 C O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924302 | AB2-077 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924311 | AB2-078 C O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924312 | AB2-078 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924321 | AB2-079 C O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924322 | AB2-079 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925611 | AC1-036 C | 50/50 | 0.24 MW | 0.24 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925612 | AC1-036 E | 50/50 | 1.55 MW | 1.55 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 932761 | AC2-100 C | 50/50 | 4.86 MW | 4.86 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 932762 | AC2-100 E | 50/50 | 2.37 MW | 2.37 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 938371 | AE1-056 C | 50/50 | 7.27 MW | 7.27 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 938372 | AE1-056 E | 50/50 | 3.97 MW | 3.97 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 939181 | AE1-148 C | 50/50 | 6.28 MW | 6.28 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 939182 | AE1-148 E | 50/50 | 4.19 MW | 4.19 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 940661 | AE2-053 O1 | 50/50 | 2.33 MW | 2.33 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 941791 | AE2-182 C | 50/50 | 4.61 MW | 4.61 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 941792 | AE2-182 E | 50/50 | 2.14 MW | 2.14 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 946301 | AF1-294 C | 50/50 | 4.48 MW | 4.48 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 946302 | AF1-294 E | 50/50 | 2.98 MW | 2.98 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958211 | AF2-115 C | 50/50 | 2.73 MW | 2.73 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958212 | AF2-115 E | 50/50 | 1.82 MW | 1.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924032 | AB2-045 E | 50/50 | 0.98 MW | 0.98 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314677 | 6BUCKING | 50/50 | 0.36 MW | 0.36 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962561 | AG1-105 C O1 | 50/50 | 10.82 MW | 10.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962562 | AG1-105 E O1 | 50/50 | 7.22 MW | 7.22 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 313527 | AB2-043 C | 50/50 | 0.48 MW | 0.48 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924022 | AB2-043 E O1 | 50/50 | 2.53 MW | 2.53 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316123 | AC1-075 C | 50/50 | 1.16 MW | 1.16 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925997 | AC1-075 E | 50/50 | 3.86 MW | 3.86 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926024 | AC1-080 E | 50/50 | 1.28 MW | 1.28 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963043 | AG1-153 BAT | Adder | 8.71 MW | 7.4 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963113 | AG1-160 BAT | Adder | 8.5 MW | 7.22 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965812 | AG1-449 BAT | 50/50 | 13.37 MW | 13.37 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.75 MW | 1.75 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 31.9 MW | 31.9 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 16.65 MW | 16.65 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.36 MW | 14.36 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.65 MW | 2.65 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.97 MW | 0.97 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.13 MW | 3.13 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.82 MW | 0.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.42 MW | 0.42 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.15 MW | 6.15 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.56 MW | 2.56 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.39 MW | 0.39 MW |
| Details for AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961791 | AG1-021 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961792 | AG1-021 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961891 | AG1-030 C | 50/50 | 37.57 MW | 37.57 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961892 | AG1-030 E | 50/50 | 25.05 MW | 25.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962491 | AG1-098 C O1 | 50/50 | 57.29 MW | 57.29 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962492 | AG1-098 E O1 | 50/50 | 38.19 MW | 38.19 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963171 | AG1-166 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963172 | AG1-166 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963181 | AG1-167 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963182 | AG1-167 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963191 | AG1-168 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963192 | AG1-168 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963201 | AG1-169 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963202 | AG1-169 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963211 | AG1-170 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963212 | AG1-170 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963321 | AG1-181 C O1 | 50/50 | 32.02 MW | 32.02 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963361 | AG1-185 O1 | 50/50 | 15.49 MW | 15.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964111 | AG1-272 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964112 | AG1-272 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964121 | AG1-273 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964122 | AG1-273 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964131 | AG1-274 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964132 | AG1-274 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964241 | AG1-285 C O1 | 50/50 | 17.5 MW | 17.5 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964242 | AG1-285 E O1 | 50/50 | 11.67 MW | 11.67 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965191 | AG1-384 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965192 | AG1-384 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965591 | AG1-427 C | 50/50 | 16.79 MW | 16.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965592 | AG1-427 E | 50/50 | 11.21 MW | 11.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965641 | AG1-432 C O1 | 50/50 | 74.7 MW | 74.7 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965642 | AG1-432 E O1 | 50/50 | 49.8 MW | 49.8 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965831 | AG1-451 | 50/50 | 12.45 MW | 12.45 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 313853 | 3PONTONDP | 50/50 | 1.84 MW | 1.84 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314429 | 3JTRSVLE | 50/50 | 1.25 MW | 1.25 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314713 | 3PAMPLIN | 50/50 | 4.9 MW | 4.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315160 | 1KERR 3 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315161 | 1KERR 4 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315162 | 1KERR 5 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 934625 | AD1-088 C | 50/50 | 63.57 MW | 63.57 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 934626 | AD1-088 E | 50/50 | 29.92 MW | 29.92 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 936265 | AD2-033 C | 50/50 | 24.18 MW | 24.18 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 936266 | AD2-033 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 942461 | AE2-259 C O1 | 50/50 | 37.35 MW | 37.35 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 942462 | AE2-259 E O1 | 50/50 | 24.9 MW | 24.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958801 | AF2-171 C | 50/50 | 41.21 MW | 41.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958802 | AF2-171 E | 50/50 | 27.47 MW | 27.47 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 959311 | AF2-222 C | 50/50 | 35.51 MW | 35.51 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 959312 | AF2-222 E | 50/50 | 23.79 MW | 23.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315163 | 1KERR 6 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315164 | 1KERR 7 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 316131 | AB2-060 C | 50/50 | 1.89 MW | 1.89 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924162 | AB2-060 E OP | 50/50 | 5.23 MW | 5.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924301 | AB2-077 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924302 | AB2-077 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924311 | AB2-078 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924312 | AB2-078 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924321 | AB2-079 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924322 | AB2-079 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 925611 | AC1-036 C | 50/50 | 0.49 MW | 0.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 925612 | AC1-036 E | 50/50 | 3.14 MW | 3.14 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 938371 | AE1-056 C | 50/50 | 19.55 MW | 19.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 938372 | AE1-056 E | 50/50 | 10.68 MW | 10.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 939181 | AE1-148 C | 50/50 | 6.96 MW | 6.96 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 939182 | AE1-148 E | 50/50 | 4.64 MW | 4.64 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 940661 | AE2-053 O1 | 50/50 | 2.58 MW | 2.58 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 941791 | AE2-182 C | 50/50 | 10.33 MW | 10.33 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 941792 | AE2-182 E | 50/50 | 4.81 MW | 4.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946301 | AF1-294 C | 50/50 | 11.32 MW | 11.32 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946302 | AF1-294 E | 50/50 | 7.55 MW | 7.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958211 | AF2-115 C | 50/50 | 6.9 MW | 6.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958212 | AF2-115 E | 50/50 | 4.6 MW | 4.6 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924032 | AB2-045 E | 50/50 | 4.76 MW | 4.76 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314677 | 6BUCKING | 50/50 | 1.74 MW | 1.74 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962561 | AG1-105 C O1 | 50/50 | 6.11 MW | 6.11 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962562 | AG1-105 E O1 | 50/50 | 4.07 MW | 4.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.76 MW | 2.76 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.07 MW | 1.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.03 MW | 1.03 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.54 MW | 0.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961791 | AG1-021 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961792 | AG1-021 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961891 | AG1-030 C | 50/50 | 37.57 MW | 37.57 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961892 | AG1-030 E | 50/50 | 25.05 MW | 25.05 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963171 | AG1-166 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963172 | AG1-166 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963181 | AG1-167 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963182 | AG1-167 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963191 | AG1-168 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963192 | AG1-168 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963201 | AG1-169 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963202 | AG1-169 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963211 | AG1-170 C | 50/50 | 5.52 MW | 5.52 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963212 | AG1-170 E | 50/50 | 3.68 MW | 3.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963321 | AG1-181 C O1 | 50/50 | 32.02 MW | 32.02 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963361 | AG1-185 O1 | 50/50 | 15.49 MW | 15.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964111 | AG1-272 C | 50/50 | 5.21 MW | 5.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964112 | AG1-272 E | 50/50 | 1.55 MW | 1.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964121 | AG1-273 C | 50/50 | 5.21 MW | 5.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964122 | AG1-273 E | 50/50 | 1.55 MW | 1.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964131 | AG1-274 C | 50/50 | 5.21 MW | 5.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964132 | AG1-274 E | 50/50 | 1.55 MW | 1.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964241 | AG1-285 C O1 | 50/50 | 17.5 MW | 17.5 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964242 | AG1-285 E O1 | 50/50 | 11.67 MW | 11.67 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965191 | AG1-384 C | 50/50 | 5.21 MW | 5.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965192 | AG1-384 E | 50/50 | 1.55 MW | 1.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965591 | AG1-427 C | 50/50 | 16.79 MW | 16.79 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965592 | AG1-427 E | 50/50 | 11.21 MW | 11.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965641 | AG1-432 C O1 | 50/50 | 74.7 MW | 74.7 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965642 | AG1-432 E O1 | 50/50 | 49.8 MW | 49.8 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965831 | AG1-451 | 50/50 | 12.45 MW | 12.45 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 313853 | 3PONTONDP | 50/50 | 1.84 MW | 1.84 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314429 | 3JTRSVLE | 50/50 | 1.25 MW | 1.25 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314713 | 3PAMPLIN | 50/50 | 4.9 MW | 4.9 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315159 | 1KERR 2 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315160 | 1KERR 3 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315161 | 1KERR 4 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 934625 | AD1-088 C | 50/50 | 63.57 MW | 63.57 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 934626 | AD1-088 E | 50/50 | 29.92 MW | 29.92 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 936265 | AD2-033 C | 50/50 | 24.18 MW | 24.18 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 936266 | AD2-033 E | 50/50 | 16.12 MW | 16.12 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 942461 | AE2-259 C O1 | 50/50 | 37.35 MW | 37.35 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 942462 | AE2-259 E O1 | 50/50 | 24.9 MW | 24.9 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958801 | AF2-171 C | 50/50 | 41.21 MW | 41.21 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958802 | AF2-171 E | 50/50 | 27.47 MW | 27.47 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 959311 | AF2-222 C | 50/50 | 35.51 MW | 35.51 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 959312 | AF2-222 E | 50/50 | 23.79 MW | 23.79 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315163 | 1KERR 6 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315164 | 1KERR 7 | 50/50 | 0.81 MW | 0.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 316131 | AB2-060 C | 50/50 | 1.89 MW | 1.89 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924162 | AB2-060 E OP | 50/50 | 5.23 MW | 5.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924301 | AB2-077 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924302 | AB2-077 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924311 | AB2-078 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924312 | AB2-078 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924321 | AB2-079 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924322 | AB2-079 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 925611 | AC1-036 C | 50/50 | 0.49 MW | 0.49 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 925612 | AC1-036 E | 50/50 | 3.14 MW | 3.14 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 938371 | AE1-056 C | 50/50 | 19.55 MW | 19.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 938372 | AE1-056 E | 50/50 | 10.68 MW | 10.68 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 939181 | AE1-148 C | 50/50 | 6.96 MW | 6.96 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 939182 | AE1-148 E | 50/50 | 4.64 MW | 4.64 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 940661 | AE2-053 O1 | 50/50 | 2.58 MW | 2.58 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 941791 | AE2-182 C | 50/50 | 10.33 MW | 10.33 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 941792 | AE2-182 E | 50/50 | 4.81 MW | 4.81 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946301 | AF1-294 C | 50/50 | 11.32 MW | 11.32 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946302 | AF1-294 E | 50/50 | 7.55 MW | 7.55 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958211 | AF2-115 C | 50/50 | 6.9 MW | 6.9 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958212 | AF2-115 E | 50/50 | 4.6 MW | 4.6 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924032 | AB2-045 E | 50/50 | 4.76 MW | 4.76 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314677 | 6BUCKING | 50/50 | 1.74 MW | 1.74 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962561 | AG1-105 C O1 | 50/50 | 6.11 MW | 6.11 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962562 | AG1-105 E O1 | 50/50 | 4.07 MW | 4.07 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.76 MW | 2.76 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.07 MW | 1.07 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.03 MW | 1.03 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.54 MW | 0.54 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| AD1-088 TAP-AG1-098 TAP 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961791 | AG1-021 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961891 | AG1-030 C | 50/50 | 11.7 MW | 11.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961892 | AG1-030 E | 50/50 | 7.8 MW | 7.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963171 | AG1-166 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963181 | AG1-167 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963191 | AG1-168 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963201 | AG1-169 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963211 | AG1-170 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963301 | AG1-179 C | Adder | 3.17 MW | 2.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963311 | AG1-180 | Adder | 1.55 MW | 1.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963321 | AG1-181 C O1 | 50/50 | 15.97 MW | 15.97 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963361 | AG1-185 O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964111 | AG1-272 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964121 | AG1-273 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964131 | AG1-274 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964241 | AG1-285 C O1 | 50/50 | 13.59 MW | 13.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964242 | AG1-285 E O1 | 50/50 | 9.06 MW | 9.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964791 | AG1-342 C | Adder | 2.83 MW | 2.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964792 | AG1-342 E | Adder | 2.22 MW | 1.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965191 | AG1-384 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965591 | AG1-427 C | 50/50 | 12.83 MW | 12.83 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965592 | AG1-427 E | 50/50 | 8.57 MW | 8.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965601 | AG1-428 C O2 | Adder | 2.65 MW | 2.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965602 | AG1-428 E O2 | Adder | 1.76 MW | 1.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965641 | AG1-432 C O1 | Adder | 8.76 MW | 7.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965642 | AG1-432 E O1 | Adder | 5.84 MW | 4.96 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965721 | AG1-440 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965722 | AG1-440 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965731 | AG1-441 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965732 | AG1-441 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965771 | AG1-445 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965781 | AG1-446 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965831 | AG1-451 | Adder | 1.46 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 314713 | 3PAMPLIN | Adder | 1.03 MW | 0.88 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315159 | 1KERR 2 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315160 | 1KERR 3 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315161 | 1KERR 4 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315162 | 1KERR 5 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 926274 | AC1-105 E | Adder | 1.38 MW | 1.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936265 | AD2-033 C | 50/50 | 12.47 MW | 12.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936266 | AD2-033 E | 50/50 | 8.31 MW | 8.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942461 | AE2-259 C O1 | Adder | 4.38 MW | 3.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942462 | AE2-259 E O1 | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958801 | AF2-171 C | 50/50 | 10.69 MW | 10.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958802 | AF2-171 E | 50/50 | 7.13 MW | 7.13 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959311 | AF2-222 C | 50/50 | 14.73 MW | 14.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959312 | AF2-222 E | 50/50 | 9.87 MW | 9.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315163 | 1KERR 6 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315164 | 1KERR 7 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316118 | AC1-105 C | Adder | 2.89 MW | 2.46 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316131 | AB2-060 C | 50/50 | 1.75 MW | 1.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924162 | AB2-060 E OP | 50/50 | 4.84 MW | 4.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924301 | AB2-077 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924302 | AB2-077 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924311 | AB2-078 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924312 | AB2-078 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924321 | AB2-079 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924322 | AB2-079 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925611 | AC1-036 C | 50/50 | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925612 | AC1-036 E | 50/50 | 1.42 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938371 | AE1-056 C | Adder | 4.11 MW | 3.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938372 | AE1-056 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939181 | AE1-148 C | 50/50 | 17.39 MW | 17.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939182 | AE1-148 E | 50/50 | 11.59 MW | 11.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 940661 | AE2-053 O1 | 50/50 | 6.44 MW | 6.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946301 | AF1-294 C | Adder | 2.9 MW | 2.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946302 | AF1-294 E | Adder | 1.94 MW | 1.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958211 | AF2-115 C | Adder | 1.77 MW | 1.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962561 | AG1-105 C O1 | 50/50 | 6.74 MW | 6.74 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962562 | AG1-105 E O1 | 50/50 | 4.5 MW | 4.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924022 | AB2-043 E O1 | 50/50 | 3.25 MW | 3.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.43 MW | 0.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.36 MW | 0.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.34 MW | 1.34 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.8 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.23 MW | 1.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961791 | AG1-021 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961792 | AG1-021 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961891 | AG1-030 C | Adder | 8.71 MW | 7.41 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961892 | AG1-030 E | Adder | 5.81 MW | 4.94 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963171 | AG1-166 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963172 | AG1-166 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963181 | AG1-167 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963182 | AG1-167 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963191 | AG1-168 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963192 | AG1-168 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963201 | AG1-169 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963202 | AG1-169 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963211 | AG1-170 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963212 | AG1-170 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963301 | AG1-179 C | Adder | 1.7 MW | 1.44 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963311 | AG1-180 | Adder | 0.83 MW | 0.7 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963321 | AG1-181 C O1 | 50/50 | 11.84 MW | 11.84 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963361 | AG1-185 O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964111 | AG1-272 C | 50/50 | 1.74 MW | 1.74 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964112 | AG1-272 E | 50/50 | 0.52 MW | 0.52 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964121 | AG1-273 C | 50/50 | 1.74 MW | 1.74 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964122 | AG1-273 E | 50/50 | 0.52 MW | 0.52 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964131 | AG1-274 C | 50/50 | 1.74 MW | 1.74 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964132 | AG1-274 E | 50/50 | 0.52 MW | 0.52 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964241 | AG1-285 C O1 | 50/50 | 10.04 MW | 10.04 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964242 | AG1-285 E O1 | 50/50 | 6.7 MW | 6.7 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964791 | AG1-342 C | Adder | 2.5 MW | 2.13 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964792 | AG1-342 E | Adder | 1.97 MW | 1.67 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965191 | AG1-384 C | 50/50 | 1.74 MW | 1.74 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965192 | AG1-384 E | 50/50 | 0.52 MW | 0.52 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965591 | AG1-427 C | 50/50 | 9.48 MW | 9.48 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965592 | AG1-427 E | 50/50 | 6.34 MW | 6.34 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965601 | AG1-428 C O2 | Adder | 1.42 MW | 1.2 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965602 | AG1-428 E O2 | Adder | 0.94 MW | 0.8 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965641 | AG1-432 C O1 | Adder | 6.67 MW | 5.67 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965642 | AG1-432 E O1 | Adder | 4.44 MW | 3.78 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965831 | AG1-451 | Adder | 1.11 MW | 0.94 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313853 | 3PONTONDP | Adder | 0.35 MW | 0.3 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 314713 | 3PAMPLIN | Adder | 0.77 MW | 0.66 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 926274 | AC1-105 E | Adder | 1.39 MW | 1.18 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927261 | AC1-222 C | Adder | 1.47 MW | 1.25 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927262 | AC1-222 E | Adder | 1.4 MW | 1.19 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934311 | AD1-055 C | Adder | 1.02 MW | 0.87 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936265 | AD2-033 C | 50/50 | 9.24 MW | 9.24 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936266 | AD2-033 E | 50/50 | 6.16 MW | 6.16 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942461 | AE2-259 C O1 | Adder | 3.33 MW | 2.83 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942462 | AE2-259 E O1 | Adder | 2.22 MW | 1.89 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943901 | AF1-058 C | Adder | 0.83 MW | 0.71 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943902 | AF1-058 E | Adder | 0.55 MW | 0.47 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958801 | AF2-171 C | Adder | 7.98 MW | 6.79 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958802 | AF2-171 E | Adder | 5.32 MW | 4.53 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959311 | AF2-222 C | 50/50 | 10.94 MW | 10.94 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959312 | AF2-222 E | 50/50 | 7.33 MW | 7.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960061 | AF2-297 C | Adder | 3.33 MW | 2.83 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960062 | AF2-297 E | Adder | 2.22 MW | 1.89 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 315266 | 1PLYWOOD A | 50/50 | 1.07 MW | 1.07 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316118 | AC1-105 C | Adder | 2.91 MW | 2.47 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316129 | AC1-054 C | Adder | -8.29 MW | -7.04 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316131 | AB2-060 C | 50/50 | 1.29 MW | 1.29 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924162 | AB2-060 E OP | 50/50 | 3.58 MW | 3.58 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925611 | AC1-036 C | 50/50 | 0.17 MW | 0.17 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925612 | AC1-036 E | 50/50 | 1.05 MW | 1.05 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938371 | AE1-056 C | Adder | 3.08 MW | 2.62 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938372 | AE1-056 E | Adder | 1.68 MW | 1.43 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946301 | AF1-294 C | Adder | 2.17 MW | 1.84 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946302 | AF1-294 E | Adder | 1.45 MW | 1.23 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958211 | AF2-115 C | Adder | 1.32 MW | 1.12 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958212 | AF2-115 E | Adder | 0.88 MW | 0.75 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962561 | AG1-105 C O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962562 | AG1-105 E O1 | 50/50 | 3.82 MW | 3.82 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313527 | AB2-043 C | 50/50 | 0.46 MW | 0.46 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924022 | AB2-043 E O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965782 | AG1-446 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965772 | AG1-445 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 940662 | AE2-053 BAT | 50/50 | 5.67 MW | 5.67 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.58 MW | 0.58 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.1 MW | 0.1 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.33 MW | 0.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.33 MW | 0.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 0.85 MW | 0.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 4.69 MW | 4.69 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | Adder | 6.79 MW | 5.78 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | Adder | 4.53 MW | 3.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | Adder | 1.13 MW | 0.96 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | Adder | 3.4 MW | 2.89 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | Adder | 2.26 MW | 1.93 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 2.33 MW | 2.33 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 0.85 MW | 0.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 20.37 MW | 20.37 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 4.85 MW | 4.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | Adder | 0.51 MW | 0.43 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | Adder | 3.4 MW | 2.89 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | Adder | 2.56 MW | 2.17 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 5.3 MW | 5.3 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | 0.52 MW | 0.45 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | Adder | 0.35 MW | 0.3 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | Adder | 0.32 MW | 0.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | Adder | 0.3 MW | 0.26 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966673 | AG1-537 BAT | Adder | 5.88 MW | 5.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.13 MW | 0.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.86 MW | 0.86 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 0.85 MW | 0.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 4.69 MW | 4.69 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | Adder | 6.79 MW | 5.78 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | Adder | 4.53 MW | 3.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | Adder | 1.13 MW | 0.96 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | Adder | 3.4 MW | 2.89 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | Adder | 2.26 MW | 1.93 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 2.33 MW | 2.33 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 0.85 MW | 0.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 20.37 MW | 20.37 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 4.85 MW | 4.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | Adder | 0.51 MW | 0.43 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | Adder | 3.4 MW | 2.89 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | Adder | 2.56 MW | 2.17 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 5.3 MW | 5.3 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | 0.52 MW | 0.45 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | Adder | 0.35 MW | 0.3 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | Adder | 0.32 MW | 0.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | Adder | 0.3 MW | 0.26 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966673 | AG1-537 BAT | Adder | 5.88 MW | 5.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.13 MW | 0.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.86 MW | 0.86 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961791 | AG1-021 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961792 | AG1-021 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961891 | AG1-030 C | Adder | 8.71 MW | 7.41 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961892 | AG1-030 E | Adder | 5.81 MW | 4.94 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963171 | AG1-166 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963172 | AG1-166 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963181 | AG1-167 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963182 | AG1-167 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963191 | AG1-168 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963192 | AG1-168 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963201 | AG1-169 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963202 | AG1-169 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963211 | AG1-170 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963212 | AG1-170 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963301 | AG1-179 C | Adder | 1.7 MW | 1.44 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963311 | AG1-180 | Adder | 0.83 MW | 0.7 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963321 | AG1-181 C O1 | 50/50 | 11.84 MW | 11.84 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963361 | AG1-185 O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964111 | AG1-272 C | 50/50 | 1.74 MW | 1.74 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964112 | AG1-272 E | 50/50 | 0.52 MW | 0.52 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964121 | AG1-273 C | 50/50 | 1.74 MW | 1.74 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964122 | AG1-273 E | 50/50 | 0.52 MW | 0.52 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964131 | AG1-274 C | 50/50 | 1.74 MW | 1.74 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964132 | AG1-274 E | 50/50 | 0.52 MW | 0.52 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964241 | AG1-285 C O1 | 50/50 | 10.04 MW | 10.04 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964242 | AG1-285 E O1 | 50/50 | 6.7 MW | 6.7 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964791 | AG1-342 C | Adder | 2.5 MW | 2.13 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964792 | AG1-342 E | Adder | 1.97 MW | 1.67 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965191 | AG1-384 C | 50/50 | 1.74 MW | 1.74 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965192 | AG1-384 E | 50/50 | 0.52 MW | 0.52 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965591 | AG1-427 C | 50/50 | 9.48 MW | 9.48 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965592 | AG1-427 E | 50/50 | 6.34 MW | 6.34 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965601 | AG1-428 C O2 | Adder | 1.42 MW | 1.2 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965602 | AG1-428 E O2 | Adder | 0.94 MW | 0.8 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965641 | AG1-432 C O1 | Adder | 6.67 MW | 5.67 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965642 | AG1-432 E O1 | Adder | 4.44 MW | 3.78 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965831 | AG1-451 | Adder | 1.11 MW | 0.94 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313853 | 3PONTONDP | Adder | 0.35 MW | 0.3 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 314713 | 3PAMPLIN | Adder | 0.77 MW | 0.66 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 926274 | AC1-105 E | Adder | 1.39 MW | 1.18 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927261 | AC1-222 C | Adder | 1.47 MW | 1.25 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927262 | AC1-222 E | Adder | 1.4 MW | 1.19 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934311 | AD1-055 C | Adder | 1.02 MW | 0.87 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936265 | AD2-033 C | 50/50 | 9.24 MW | 9.24 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936266 | AD2-033 E | 50/50 | 6.16 MW | 6.16 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942461 | AE2-259 C O1 | Adder | 3.33 MW | 2.83 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942462 | AE2-259 E O1 | Adder | 2.22 MW | 1.89 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943901 | AF1-058 C | Adder | 0.83 MW | 0.71 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943902 | AF1-058 E | Adder | 0.55 MW | 0.47 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958801 | AF2-171 C | Adder | 7.98 MW | 6.79 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958802 | AF2-171 E | Adder | 5.32 MW | 4.53 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959311 | AF2-222 C | 50/50 | 10.94 MW | 10.94 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959312 | AF2-222 E | 50/50 | 7.33 MW | 7.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960061 | AF2-297 C | Adder | 3.33 MW | 2.83 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960062 | AF2-297 E | Adder | 2.22 MW | 1.89 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 315266 | 1PLYWOOD A | 50/50 | 1.07 MW | 1.07 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316118 | AC1-105 C | Adder | 2.91 MW | 2.47 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316129 | AC1-054 C | Adder | -8.29 MW | -7.04 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316131 | AB2-060 C | 50/50 | 1.29 MW | 1.29 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924162 | AB2-060 E OP | 50/50 | 3.58 MW | 3.58 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925611 | AC1-036 C | 50/50 | 0.17 MW | 0.17 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925612 | AC1-036 E | 50/50 | 1.05 MW | 1.05 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938371 | AE1-056 C | Adder | 3.08 MW | 2.62 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938372 | AE1-056 E | Adder | 1.68 MW | 1.43 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946301 | AF1-294 C | Adder | 2.17 MW | 1.84 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946302 | AF1-294 E | Adder | 1.45 MW | 1.23 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958211 | AF2-115 C | Adder | 1.32 MW | 1.12 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958212 | AF2-115 E | Adder | 0.88 MW | 0.75 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962561 | AG1-105 C O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962562 | AG1-105 E O1 | 50/50 | 3.82 MW | 3.82 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313527 | AB2-043 C | 50/50 | 0.46 MW | 0.46 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924022 | AB2-043 E O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965782 | AG1-446 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965772 | AG1-445 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 940662 | AE2-053 BAT | 50/50 | 5.67 MW | 5.67 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.58 MW | 0.58 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.1 MW | 0.1 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.33 MW | 0.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.33 MW | 0.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
| Details for 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961791 | AG1-021 C | Adder | 1.06 MW | 0.9 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961792 | AG1-021 E | Adder | 0.71 MW | 0.6 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961891 | AG1-030 C | Adder | 8.71 MW | 7.41 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961892 | AG1-030 E | Adder | 5.81 MW | 4.94 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963171 | AG1-166 C | Adder | 1.06 MW | 0.9 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963172 | AG1-166 E | Adder | 0.71 MW | 0.6 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963181 | AG1-167 C | Adder | 1.06 MW | 0.9 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963182 | AG1-167 E | Adder | 0.71 MW | 0.6 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963191 | AG1-168 C | Adder | 1.06 MW | 0.9 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963192 | AG1-168 E | Adder | 0.71 MW | 0.6 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963201 | AG1-169 C | Adder | 1.06 MW | 0.9 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963202 | AG1-169 E | Adder | 0.71 MW | 0.6 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963211 | AG1-170 C | Adder | 1.06 MW | 0.9 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963212 | AG1-170 E | Adder | 0.71 MW | 0.6 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963301 | AG1-179 C | Adder | 1.7 MW | 1.44 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963311 | AG1-180 | Adder | 0.83 MW | 0.7 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963321 | AG1-181 C O1 | 50/50 | 11.84 MW | 11.84 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963361 | AG1-185 O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964111 | AG1-272 C | 50/50 | 1.74 MW | 1.74 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964112 | AG1-272 E | 50/50 | 0.52 MW | 0.52 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964121 | AG1-273 C | 50/50 | 1.74 MW | 1.74 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964122 | AG1-273 E | 50/50 | 0.52 MW | 0.52 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964131 | AG1-274 C | 50/50 | 1.74 MW | 1.74 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964132 | AG1-274 E | 50/50 | 0.52 MW | 0.52 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964241 | AG1-285 C O1 | 50/50 | 10.04 MW | 10.04 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964242 | AG1-285 E O1 | 50/50 | 6.7 MW | 6.7 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964791 | AG1-342 C | Adder | 2.5 MW | 2.13 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964792 | AG1-342 E | Adder | 1.97 MW | 1.67 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965191 | AG1-384 C | 50/50 | 1.74 MW | 1.74 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965192 | AG1-384 E | 50/50 | 0.52 MW | 0.52 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965591 | AG1-427 C | 50/50 | 9.48 MW | 9.48 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965592 | AG1-427 E | 50/50 | 6.34 MW | 6.34 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965601 | AG1-428 C O2 | Adder | 1.42 MW | 1.2 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965602 | AG1-428 E O2 | Adder | 0.94 MW | 0.8 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965641 | AG1-432 C O1 | Adder | 6.67 MW | 5.67 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965642 | AG1-432 E O1 | Adder | 4.44 MW | 3.78 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965831 | AG1-451 | Adder | 1.11 MW | 0.94 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313853 | 3PONTONDP | Adder | 0.35 MW | 0.3 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 314713 | 3PAMPLIN | Adder | 0.77 MW | 0.66 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 926274 | AC1-105 E | Adder | 1.39 MW | 1.18 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927261 | AC1-222 C | Adder | 1.47 MW | 1.25 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927262 | AC1-222 E | Adder | 1.4 MW | 1.19 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934311 | AD1-055 C | Adder | 1.02 MW | 0.87 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936265 | AD2-033 C | 50/50 | 9.24 MW | 9.24 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936266 | AD2-033 E | 50/50 | 6.16 MW | 6.16 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942461 | AE2-259 C O1 | Adder | 3.33 MW | 2.83 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942462 | AE2-259 E O1 | Adder | 2.22 MW | 1.89 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943901 | AF1-058 C | Adder | 0.83 MW | 0.71 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943902 | AF1-058 E | Adder | 0.55 MW | 0.47 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958801 | AF2-171 C | Adder | 7.98 MW | 6.79 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958802 | AF2-171 E | Adder | 5.32 MW | 4.53 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959311 | AF2-222 C | 50/50 | 10.94 MW | 10.94 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959312 | AF2-222 E | 50/50 | 7.33 MW | 7.33 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960061 | AF2-297 C | Adder | 3.33 MW | 2.83 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960062 | AF2-297 E | Adder | 2.22 MW | 1.89 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 315266 | 1PLYWOOD A | 50/50 | 1.07 MW | 1.07 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316118 | AC1-105 C | Adder | 2.91 MW | 2.47 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316129 | AC1-054 C | Adder | -8.29 MW | -7.04 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316131 | AB2-060 C | 50/50 | 1.29 MW | 1.29 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924162 | AB2-060 E OP | 50/50 | 3.58 MW | 3.58 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925611 | AC1-036 C | 50/50 | 0.17 MW | 0.17 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925612 | AC1-036 E | 50/50 | 1.05 MW | 1.05 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938371 | AE1-056 C | Adder | 3.08 MW | 2.62 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938372 | AE1-056 E | Adder | 1.68 MW | 1.43 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946301 | AF1-294 C | Adder | 2.17 MW | 1.84 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946302 | AF1-294 E | Adder | 1.45 MW | 1.23 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958211 | AF2-115 C | Adder | 1.32 MW | 1.12 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958212 | AF2-115 E | Adder | 0.88 MW | 0.75 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962561 | AG1-105 C O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962562 | AG1-105 E O1 | 50/50 | 3.82 MW | 3.82 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313527 | AB2-043 C | 50/50 | 0.46 MW | 0.46 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924022 | AB2-043 E O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965782 | AG1-446 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965772 | AG1-445 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 940662 | AE2-053 BAT | 50/50 | 5.67 MW | 5.67 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.58 MW | 0.58 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.1 MW | 0.1 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.33 MW | 0.33 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.33 MW | 0.33 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 3BUGGS I-3CLRK TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961791 | AG1-021 C | Adder | 1.06 MW | 0.9 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961792 | AG1-021 E | Adder | 0.71 MW | 0.6 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961891 | AG1-030 C | Adder | 8.71 MW | 7.41 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961892 | AG1-030 E | Adder | 5.81 MW | 4.94 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963171 | AG1-166 C | Adder | 1.06 MW | 0.9 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963172 | AG1-166 E | Adder | 0.71 MW | 0.6 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963181 | AG1-167 C | Adder | 1.06 MW | 0.9 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963182 | AG1-167 E | Adder | 0.71 MW | 0.6 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963191 | AG1-168 C | Adder | 1.06 MW | 0.9 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963192 | AG1-168 E | Adder | 0.71 MW | 0.6 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963201 | AG1-169 C | Adder | 1.06 MW | 0.9 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963202 | AG1-169 E | Adder | 0.71 MW | 0.6 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963211 | AG1-170 C | Adder | 1.06 MW | 0.9 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963212 | AG1-170 E | Adder | 0.71 MW | 0.6 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963301 | AG1-179 C | Adder | 1.7 MW | 1.44 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963311 | AG1-180 | Adder | 0.83 MW | 0.7 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963321 | AG1-181 C O1 | 50/50 | 11.84 MW | 11.84 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963361 | AG1-185 O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964111 | AG1-272 C | 50/50 | 1.74 MW | 1.74 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964112 | AG1-272 E | 50/50 | 0.52 MW | 0.52 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964121 | AG1-273 C | 50/50 | 1.74 MW | 1.74 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964122 | AG1-273 E | 50/50 | 0.52 MW | 0.52 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964131 | AG1-274 C | 50/50 | 1.74 MW | 1.74 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964132 | AG1-274 E | 50/50 | 0.52 MW | 0.52 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964241 | AG1-285 C O1 | 50/50 | 10.04 MW | 10.04 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964242 | AG1-285 E O1 | 50/50 | 6.7 MW | 6.7 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964791 | AG1-342 C | Adder | 2.5 MW | 2.13 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964792 | AG1-342 E | Adder | 1.97 MW | 1.67 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965191 | AG1-384 C | 50/50 | 1.74 MW | 1.74 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965192 | AG1-384 E | 50/50 | 0.52 MW | 0.52 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965591 | AG1-427 C | 50/50 | 9.48 MW | 9.48 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965592 | AG1-427 E | 50/50 | 6.34 MW | 6.34 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965601 | AG1-428 C O2 | Adder | 1.42 MW | 1.2 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965602 | AG1-428 E O2 | Adder | 0.94 MW | 0.8 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965641 | AG1-432 C O1 | Adder | 6.67 MW | 5.67 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965642 | AG1-432 E O1 | Adder | 4.44 MW | 3.78 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965831 | AG1-451 | Adder | 1.11 MW | 0.94 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313853 | 3PONTONDP | Adder | 0.35 MW | 0.3 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 314713 | 3PAMPLIN | Adder | 0.77 MW | 0.66 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 926274 | AC1-105 E | Adder | 1.39 MW | 1.18 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927261 | AC1-222 C | Adder | 1.47 MW | 1.25 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927262 | AC1-222 E | Adder | 1.4 MW | 1.19 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934311 | AD1-055 C | Adder | 1.02 MW | 0.87 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936265 | AD2-033 C | 50/50 | 9.24 MW | 9.24 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936266 | AD2-033 E | 50/50 | 6.16 MW | 6.16 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942461 | AE2-259 C O1 | Adder | 3.33 MW | 2.83 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942462 | AE2-259 E O1 | Adder | 2.22 MW | 1.89 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943901 | AF1-058 C | Adder | 0.83 MW | 0.71 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943902 | AF1-058 E | Adder | 0.55 MW | 0.47 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958801 | AF2-171 C | Adder | 7.98 MW | 6.79 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958802 | AF2-171 E | Adder | 5.32 MW | 4.53 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959311 | AF2-222 C | 50/50 | 10.94 MW | 10.94 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959312 | AF2-222 E | 50/50 | 7.33 MW | 7.33 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960061 | AF2-297 C | Adder | 3.33 MW | 2.83 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960062 | AF2-297 E | Adder | 2.22 MW | 1.89 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 315266 | 1PLYWOOD A | 50/50 | 1.07 MW | 1.07 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316118 | AC1-105 C | Adder | 2.91 MW | 2.47 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316129 | AC1-054 C | Adder | -8.29 MW | -7.04 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316131 | AB2-060 C | 50/50 | 1.29 MW | 1.29 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924162 | AB2-060 E OP | 50/50 | 3.58 MW | 3.58 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925611 | AC1-036 C | 50/50 | 0.17 MW | 0.17 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925612 | AC1-036 E | 50/50 | 1.05 MW | 1.05 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938371 | AE1-056 C | Adder | 3.08 MW | 2.62 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938372 | AE1-056 E | Adder | 1.68 MW | 1.43 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946301 | AF1-294 C | Adder | 2.17 MW | 1.84 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946302 | AF1-294 E | Adder | 1.45 MW | 1.23 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958211 | AF2-115 C | Adder | 1.32 MW | 1.12 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958212 | AF2-115 E | Adder | 0.88 MW | 0.75 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962561 | AG1-105 C O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962562 | AG1-105 E O1 | 50/50 | 3.82 MW | 3.82 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313527 | AB2-043 C | 50/50 | 0.46 MW | 0.46 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924022 | AB2-043 E O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965782 | AG1-446 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965772 | AG1-445 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 940662 | AE2-053 BAT | 50/50 | 5.67 MW | 5.67 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.58 MW | 0.58 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.1 MW | 0.1 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.33 MW | 0.33 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.33 MW | 0.33 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 3CLRK TAP-3ISLND C 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n6464 | Replace circuit breaker switch at Altavista. | $200,000 | |
| n7014 | Reconductor 0.05 miles of 115 kV Line 31 from Otter River to Altavista with 768.2 ACSS 250. Replace breaker switch at Altavista terminal. | $230,000 | |
| n7692 | Rebuild 115 kV Line#33 from Barnes Junction D.P. to AG1-105 Tap. | $8,155,000 | |
| n6852 | Add an additional 2 miles single circuit 230 kV line from Fork Union to Bremo parallel to existing line. Add a breaker at Fork Union 230 kV and Bremo 230 kV | $3,500,000 | |
| n8265 | Reconductor 4.32 miles of 115 kV Line 71 from Brunswick to Lawrence with 768.2 ACSS 250 | $2,592,000 | |
| n7543 | Rebuild 115 kV Line 1045 | $3,445,000 | |
| n7675 | Reconductor 115 kV Line#98 from AD2-033 Tap to Butcher Creek. | $19,220,000 | |
| n7766 | Rebuild 115 kV Line #1012 From AD2-063 Tap-AG1-181 Tap-Central-Twitty's Creek-AF2-222 Tap-Madsonav | $24,835,000 | |
| n7658 | Rebuild 115 kV Line #40 from Chase City to Norview. | $21,515,000 | |
| n7821 | Wreck and rebuild 115 kV line #1012 from Chase City to AG1-285 Tap | $13,400,000 | |
| n7678 | Rebuild 7.46 mi miles of 115 kV Line 33 from Chase City to Barnes Junction. Replace line switch at Branes Junction DP. Replace breaker switch, wave trap, relay trip at Chase City terminal. | $11,890,000 | |
| n8270 | Reconductor 0.39 miles of 115 kV Line 193 from Clarksville to Buggs Island P.S. with 636 ACSR 150 C | $234,000 | |
| n8271 | Reconductor 5.28 miles of 115 kV Line 193 from Clarksville to Island Creek D.P with 636 ACSR 150 C | $3,168,000 | |
| n6114 | Add additional 230/115 kV transformer at Clubhouse substation. Cost changed during facility study phase. | $13,653,448 | |
| n8268 | Reconductor 115 kV Line 71 from Clubhouse to Freeman D.P. | $4,476,000 | |
| n7819 | Wreck and rebuild 115 kV line #84 from Willis to Farmville to a double circuit. | $20,050,000 | |
| n6246 | Add additional 230/115 kV transformer (#3) for Circuit 1 at Farmville substation | $6,000,000 | |
| n7550 | Add additional 230/115 kV transformer (#4) for Circuit 2 at Farmville substation. | $6,000,000 | |
| n8266 | Reconductor 8.35 miles of 115 kV Line 71 from Lawrence to Freeman D.P. with 768.2 ACSS 250. | $5,010,000 | |
| n7016 | Reconductor 3.9 miles of 115 kV Line 31 from Grit DP to Otter River with 768.2 ACSS 250 | $2,340,000 | |
| n7015 | Reconductor 8.5 miles of 115 kV Line 31 from Grit to AE2-291 Tap with 768.2 ACSS 250 C. | $5,100,000 | |
| (TBD) | Reconductor 20 miles with single 795 ACSS-TW per phase, replace breaker, disconnect switches, wave trap, line switch | $60,000,000 | |
| s2614 | For DEV portion, rebuild 4.7 miles of 115 kV Line 45 from Kerr Dam to GW King Tap with 768 ACSS. | $6,123,000 | |
| n8269 | Reconductor 115 kV line 193 from Kerr DP to Island Creek DP. | $1,314,000 | |
| n8267 | Reconductor 9.4 miles of 115 kV line 193 from Kerr DP to Kerr Dam with 636 ACSR 150 C | $5,640,000 | |
| n7661 | Rebuild 115 kV Line #1034 from Victoria to Lunenburg | $3,690,000 | |
| n7681 | Rebuild 115 kV line #98 | $4,550,000 | |
| n7667 | Rebuild 115 kV Line #33 from Mt. Laurel -AC1-105 Tap -Sedge Hill. | $16,590,000 | |
| n7664 | Rebuild 115 kV Line#33 From AG1-105 Tap -Mt. Laurel. | $3,850,000 | |
| n8261 | Reconductor 115 kV Line #40 from South Hill to Northview. | $3,792,000 | |
| n7680 | Rebuild 6.65 miles of 115 kV Line 151 from Plywood to Sedge Hill with 636 ACSR. | $8,645,000 | |
| n7687 | Add additional 230/115 kV transformer at Sedge Hill substation. | $6,000,000 | |
| n6378 | Rebuild 6.42 miles of 115 kV Line 91 from AE2-092 Tap to Sherwood with 2-636 ACSR. | $16,050,000 | |
| n7662 | Rebuild 115 kV Line #1034 from AG1-030 Tap to Victoria DP | $9,115,000 | |
| n7688 | Rebuild 115 kV Line #1034 | $3,830,000 | |
| n8244 | Rebuild 230 kV Line #2068 | $25,450,000 | |
| n5873 | Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. | $500,000 | |
| n7570 | Wreck and Rebuild 230 kV Line #298 From Buckingham to Bremo | $47,675,000 | |
| n6245 | Rebuild 12.76 miles of 230 kV Line 298 from Buckingham to Farmville with 2-768.2 ACSS 250 C. Replace Line Lead, Line Switch, Relay (CT), Wave trap at Farmville terminal | $19,710,000 | |
| n7785 | Rebuild 9.46 miles of 230 kV Line 2027 from Bremo to Cartersville with 2-795 ACSR 150 C. Replace breaker lead at Bremo terminal. | $23,650,000 | |
| n8256 | Rebuild 230 kV Line #2027 from Carterville to AC2-165 Tap. | $19,175,000 | |
| n7574 | Rebuild 12.83 miles of 230 kV Line 2135 from Cashs Corner D.P. to Gordonsville with 2-636 ACSR 150 C. | $32,075,000 | |
| n7581 | Rebuild 4.27 miles of 230 kV Line 2135 from Hollymead to Cashs Corner D.P. with 2-636 ACSR 150 C | $10,675,000 | |
| n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
| n7580 | Rebuild 8.72 miles of 230 kV Line 2054 from Charlottesville to Profit D.P. with 2-636 ACSR 150 C | $21,800,000 | |
| n8249 | Clover Substation: 230/500 kV Transformer Addition | $22,000,000 | |
| n7019 | Rebuild 33.36 miles of 230 kV line 235 from Clover to AD1-088 Tap with 2-636 ACSR. | $50,040,000 | |
| n7567 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $2,445,000 | |
| n8453 | Rebuild 5 miles of 230 kV Line 2028 from Fork Union to AF2-397 Tap with 2-636 ACSR. | $7,500,000 | |
| n7796 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Midlothian with 2-795 ACSR 150 C. | $17,725,000 | |
| n7797 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Powhatan with 2-795 ACSR 150 C | $17,725,000 | |
| n7569 | Rebuild 230 kV Line#2028 from Mount Eagle to AF2-397 Tap. | $30,250,000 | |
| (TBD) | Reconductor 5 miles with double 795 ACSS-TW per phase, replace disconnect switches | $22,500,000 | |
| n7083 | For DEV portion, rebuild 2 miles of 230 kV Line 296 from AC1-221 Tap to Persons DEP with 2-795 ACSR. | $3,000,000 | |
| n8320 | Dominion and AEP build new Axton-Clover 765 kV line | $600,000,000 | |
| n8243 | Rebuild 4.01 miles of 230 kV Line 2027 from Powhatan to AC2-165 Tap with 2-795 ACSR (26/7) 150 C | $10,025,000 | |
| n6514 | Rebuild 16.71 miles of 230 kV Line 2068 from AD1-087 Tap to Sedge Hill with 2-795 ACSR. | $25,065,000 | |
| n7823 | Wreck and rebuild 115 kV line#1012 from AG1-427 Tap to AG1-285 Tap | $3,150,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-432 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.