AG1-427 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:58
Chase City-Drakes Branch 115 kV
71.136 MW Capacity / 118.56 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-427 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Mecklenburg County, Virginia. The installed facilities will have a total capability of 118.56 MW with 71.136 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-427 |
| Project Name | Chase City-Drakes Branch 115 kV |
| Developer Name | ACE Development Company II, LLC |
| State | Virginia |
| County | Mecklenburg |
| Transmission Owner | Dominion |
| MFO | 118.56 MW |
| MWE | 118.56 MW |
| MWC | 71.136 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-427 "Chase City-Drakes Branch 115 kV" will interconnect with the Dominion transmission system. The primary POI will be a newly constructed 115 kV three breaker ring bus located on the line between the Chase City substation and Drakes Branch substation.
Summer Peak Analysis
The Queue Project was evaluated as a 118.56 MW (Capacity 71.136 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 258.61 % | 293.15 % | 205.86 | B | 603.47 | 71.1 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 222.18 % | 256.72 % | 205.86 | B | 528.49 | 71.1 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 235-A
CONTINGENCY 'DVP_P1-2: LN 235-A' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Single | AC | 207.78 % | 217.25 % | 182.64 | B | 396.79 | 17.61 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 173.5 % | 191.6 % | 182.64 | B | 349.93 | 33.05 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 176.84 % | 180.27 % | 559.3 | B | 1008.26 | 18.22 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 174.35 % | 177.72 % | 571.52 | B | 1015.69 | 18.21 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 2201
CONTINGENCY 'DVP_P1-2: LN 2201' OPEN BRANCH FROM BUS 313725 TO BUS 314563 CKT 1 /*6DRY BREAD 230.0 - 6CLUBHSE 230.0 END |
Single | AC | 181.29 % | 186.0 % | 182.64 | B | 339.71 | 8.62 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
Base Case | Single | AC | 129.27 % | 135.74 % | 186.12 | A | 252.65 | 12.41 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 176.4 % | 179.79 % | 559.3 | B | 1005.57 | 18.22 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P1-2: LN 84
CONTINGENCY 'DVP_P1-2: LN 84' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Single | AC | 171.32 % | 196.96 % | 269.78 | B | 531.35 | 71.1 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 174.5 % | 177.88 % | 571.52 | B | 1016.59 | 18.21 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
DVP_P1-2: LN 254
CONTINGENCY 'DVP_P1-2: LN 254' OPEN BRANCH FROM BUS 313725 TO BUS 314583 CKT 1 /*6DRY BREAD 230.0 - 6LAKEVEW 230.0 END |
Single | AC | 169.94 % | 174.56 % | 182.64 | B | 318.81 | 8.62 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 298
CONTINGENCY 'DVP_P1-2: LN 298' OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Single | AC | 129.99 % | 137.48 % | 198.06 | B | 272.28 | 15.04 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 153.39 % | 155.86 % | 718.0 | B | 1119.1 | 16.25 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 150.99 % | 153.63 % | 674.92 | B | 1036.85 | 16.25 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P1-2: LN 84
CONTINGENCY 'DVP_P1-2: LN 84' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Single | AC | 144.7 % | 170.48 % | 269.78 | B | 459.91 | 71.1 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
Base Case | Single | AC | 121.69 % | 128.04 % | 176.81 | A | 226.39 | 11.24 | |
| CPLE/DVP |
AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line
927250 to 304070 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 153.52 % | 156.01 % | 718.0 | B | 1120.14 | 16.25 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 124.87 % | 138.31 % | 198.06 | B | 273.94 | 26.62 | |
| DVP |
3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line
314713 to 314726 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 143.26 % | 164.69 % | 331.82 | B | 546.46 | 71.1 | |
| DVP |
6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line
314697 to 927250 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 151.01 % | 153.64 % | 674.92 | B | 1036.93 | 16.25 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P1-2: LN 154-A
CONTINGENCY 'DVP_P1-2: LN 154-A' OPEN BRANCH FROM BUS 314713 TO BUS 314715 CKT 1 /*3PAMPLIN 115.0 - 3MADSONV 115.0 OPEN BRANCH FROM BUS 314715 TO BUS 959310 CKT 1 /*3MADSONV 115.0 - AF2-222 TAP 115.0 OPEN BUS 314715 /*3MADSONV 115.0 END |
Single | AC | 137.94 % | 163.46 % | 269.78 | B | 440.97 | 71.1 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
Base Case | Single | AC | 125.29 % | 148.27 % | 247.22 | A | 366.55 | 58.68 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 144.9 % | 146.45 % | 661.76 | B | 969.16 | 10.55 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 140.91 % | 142.47 % | 661.76 | B | 942.78 | 10.55 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 140.69 % | 142.25 % | 661.76 | B | 941.32 | 10.55 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 137.56 % | 139.11 % | 661.76 | B | 920.58 | 10.55 | |
| DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 129.51 % | 130.86 % | 678.68 | B | 888.13 | 9.29 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 136.71 % | 138.26 % | 661.76 | B | 914.94 | 10.55 | |
| DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 131.31 % | 132.49 % | 678.68 | B | 899.19 | 9.3 | |
| DVP |
3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line
314715 to 314713 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 126.94 % | 146.19 % | 369.42 | B | 540.05 | 71.1 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 133.7 % | 135.33 % | 678.68 | B | 918.48 | 11.5 | |
| DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 127.98 % | 129.33 % | 678.68 | B | 877.72 | 9.29 | |
| DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 129.77 % | 130.95 % | 678.68 | B | 888.72 | 9.3 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 133.69 % | 135.25 % | 661.76 | B | 895.0 | 10.55 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 131.6 % | 133.24 % | 678.68 | B | 904.26 | 11.5 | |
| DVP |
3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line
314713 to 314726 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 120.66 % | 142.09 % | 331.82 | B | 471.48 | 71.1 | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 129.59 % | 131.24 % | 678.68 | B | 890.71 | 11.5 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 127.5 % | 129.15 % | 678.68 | B | 876.52 | 11.5 | |
| DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
DVP_P1-2: LN 246
CONTINGENCY 'DVP_P1-2: LN 246' OPEN BRANCH FROM BUS 314537 TO BUS 314575 CKT 1 /*6SUFFOLK 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314569 TO BUS 314575 CKT 1 /*6EARLEYS 230.0 - 6NUCO TP 230.0 OPEN BRANCH FROM BUS 314575 TO BUS 314590 CKT 1 /*6NUCO TP 230.0 - 6NUCOR 230.0 OPEN BUS 314575 /*6NUCO TP 230.0 OPEN BUS 314590 /*6NUCOR 230.0 SET POSTCONTRATING 876 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 SET PRECONTRATING 813 BRANCH FROM BUS 314537 TO BUS 314648 CKT 1 /*6SUFFOLK 230.0 - 6SUNBURY 230.0 END |
Single | AC | 120.98 % | 122.41 % | 678.68 | B | 830.75 | 9.3 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P1-2: LN 298
CONTINGENCY 'DVP_P1-2: LN 298' OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Single | AC | 105.33 % | 127.56 % | 269.78 | B | 344.14 | 60.96 | |
| DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
314575 6NUCO TP 230 314537 6SUFFOLK 230 1
CONTINGENCY '314575 6NUCO TP 230 314537 6SUFFOLK 230 1' /* Auto-generated /* 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 END |
Single | AC | 119.44 % | 120.86 % | 678.68 | B | 820.25 | 9.3 | |
| DVP |
3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer
314562 to 314563 ckt 1 |
Base Case | Single | AC | 111.94 % | 116.65 % | 176.81 | A | 206.24 | 8.63 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
Base Case | Single | AC | 100.97 % | 123.97 % | 247.22 | A | 306.47 | 58.68 | |
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193
CONTINGENCY 'DVP_P1-2: LN 2193' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 123.16 % | 125.02 % | 269.78 | B | 337.29 | 5.27 | |
| DVP |
AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line
934330 to 313845 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 118.61 % | 119.78 % | 441.8 | B | 529.19 | 5.16 | |
| DVP |
AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line
934330 to 313845 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 118.58 % | 119.76 % | 441.8 | B | 529.1 | 5.16 | |
| DVP |
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer
314696 to 314697 ckt 1 |
DVP_P1-3: 6SEDGE HILL-TX#2
CONTINGENCY 'DVP_P1-3: 6SEDGE HILL-TX#2' OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 2 /*3SEDGE HILL 115.0 - 6SEDGE HILL 230.0 END |
Single | AC | 103.55 % | 109.43 % | 242.52 | B | 265.38 | 14.29 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P1-2: LN 140
CONTINGENCY 'DVP_P1-2: LN 140' OPEN BRANCH FROM BUS 313720 TO BUS 314526 CKT 1 /*3NEWSOMS 115.0 - 3HANDSOM 115.0 OPEN BRANCH FROM BUS 314526 TO BUS 314534 CKT 1 /*3HANDSOM 115.0 - 3S HAMPT 115.0 OPEN BUS 314526 /*3HANDSOM 115.0 END |
Single | AC | 110.03 % | 112.51 % | 239.89 | B | 269.91 | 6.18 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P1-2: LN 93
CONTINGENCY 'DVP_P1-2: LN 93' OPEN BRANCH FROM BUS 314524 TO BUS 314539 CKT 1 /*3FRNKLN 115.0 - 3UNCAMP 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314541 CKT 1 /*3FRNKLN 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 314541 CKT 1 /*3S HAMPT 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 315115 CKT 1 /*3S HAMPT 115.0 - 1S HAMPT1 13.8 OPEN BRANCH FROM BUS 314541 TO BUS 314826 CKT 1 /*3WATKINS 115.0 - 3WATKI_1 115.0 OPEN BRANCH FROM BUS 314541 TO BUS 314827 CKT 1 /*3WATKINS 115.0 - 3WATKI_2 115.0 OPEN BUS 314524 /*3FRNKLN 115.0 OPEN BUS 314541 /*3WATKINS 115.0 OPEN BUS 314826 /*3WATKI_1 115.0 OPEN BUS 314827 /*3WATKI_2 115.0 OPEN BUS 315115 /*1S HAMPT1 13.8 END |
Single | AC | 109.72 % | 112.2 % | 239.89 | B | 269.15 | 6.18 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 96.83 % | 117.96 % | 269.78 | B | 318.22 | 58.81 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
313868 6CARTERV 230 933500 AC2-165 TAP 230 1
CONTINGENCY '313868 6CARTERV 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 96.71 % | 117.85 % | 269.78 | B | 317.92 | 58.81 | |
| DVP |
3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line
314715 to 314713 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 106.64 % | 125.89 % | 369.42 | B | 465.06 | 71.1 | |
| DVP |
6SAPONY-6CARSON 230.0 kV Ckt 1 line
314435 to 314282 ckt 1 |
Base Case | Single | AC | 109.47 % | 110.74 % | 678.68 | A | 751.55 | 8.58 | |
| DVP |
AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line
959310 to 314715 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 103.83 % | 123.07 % | 369.42 | B | 454.66 | 71.1 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 101.93 % | 103.89 % | 285.76 | B | 296.88 | 5.42 | |
| DVP |
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
314696 to 314697 ckt 2 |
DVP_P1-3: 6SEDGE HILL-TX#1
CONTINGENCY 'DVP_P1-3: 6SEDGE HILL-TX#1' OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1 /*3SEDGE HILL 115.0 - 6SEDGE HILL 230.0 END |
Single | AC | 97.79 % | 103.34 % | 256.06 | B | 264.62 | 14.24 | |
| DVP |
6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line
314579 to 934330 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 110.49 % | 111.66 % | 441.8 | B | 493.31 | 5.16 | |
| DVP |
6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line
314579 to 934330 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 110.47 % | 111.64 % | 441.8 | B | 493.22 | 5.16 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 100.86 % | 102.83 % | 285.76 | B | 293.84 | 5.42 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 99.69 % | 101.77 % | 269.78 | B | 274.55 | 5.42 | |
| DVP |
AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line
940480 to 314435 ckt 1 |
Base Case | Single | AC | 109.54 % | 110.42 % | 678.68 | A | 749.42 | 8.58 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
Base Case | Single | AC | 98.04 % | 100.61 % | 559.3 | A | 562.72 | 14.44 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 101.78 % | 103.72 % | 285.76 | B | 296.4 | 5.42 | |
| DVP |
6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line
314563 to 940480 ckt 1 |
Base Case | Single | AC | 99.67 % | 100.96 % | 678.68 | A | 685.18 | 8.58 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 100.71 % | 102.66 % | 285.76 | B | 293.36 | 5.42 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 99.53 % | 101.59 % | 269.78 | B | 274.08 | 5.42 | |
| DVP |
AG1-181 TAP-3CENTRAL 115.0 kV Ckt 1 line
963320 to 314679 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | AC | 83.38 % | 109.83 % | 269.78 | B | 296.29 | 71.1 | |
| DVP |
3CENTRAL-3TWITTYS 115.0 kV Ckt 1 line
314679 to 314722 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | AC | 82.06 % | 108.6 % | 269.78 | B | 292.99 | 71.1 | |
| DVP |
3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line
314702 to 314673 ckt 1 |
DVP_P1-2: LN 22
CONTINGENCY 'DVP_P1-2: LN 22' OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Single | AC | 103.73 % | 108.5 % | 138.18 | B | 149.92 | 6.64 | |
| DVP |
3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line
314702 to 314673 ckt 1 |
DVP_P1-2: LN 556-A
CONTINGENCY 'DVP_P1-2: LN 556-A' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 2 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314906 TO BUS 945810 CKT 1 /*8CLOVER 500.0 - AF1-246 TAP 500.0 OPEN BUS 314906 /*8CLOVER 500.0 OPEN BUS 314915 /*8CLOVER_STC 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 965810 CKT 1 /*8CARSON 500.0 - AG1-449 TAP 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 965810 TO BUS 942930 CKT 1 /*AG1-449 TAP 500.0 - AE2-313 TAP 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 102.06 % | 106.42 % | 138.18 | B | 147.06 | 5.53 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 99.56 % | 100.29 % | 800.88 | B | 803.2 | 5.68 | |
| DVP |
6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line
314599 to 314266 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 100.17 % | 101.22 % | 559.3 | B | 566.13 | 5.88 | |
| DVP |
6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line
314561 to 314599 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 100.17 % | 101.22 % | 559.3 | B | 566.1 | 5.88 | |
| DVP |
6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line
314599 to 314266 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 100.16 % | 101.2 % | 559.3 | B | 566.03 | 5.88 | |
| DVP |
6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line
314561 to 314599 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 100.15 % | 101.2 % | 559.3 | B | 565.99 | 5.88 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P1-2: LN 2028-C
CONTINGENCY 'DVP_P1-2: LN 2028-C' OPEN BRANCH FROM BUS 313707 TO BUS 961060 CKT 1 /*6FORK UNION 230.0 - AF2-397 TAP 230.0 END |
Single | AC | 99.17 % | 100.14 % | 800.88 | B | 801.99 | 7.8 | |
| DVP |
6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line
314266 to 314569 ckt 1 |
DVP_P1-2: LN 238-A
CONTINGENCY 'DVP_P1-2: LN 238-A' OPEN BRANCH FROM BUS 314282 TO BUS 314435 CKT 1 /*6CARSON 230.0 - 6SAPONY 230.0 OPEN BRANCH FROM BUS 314435 TO BUS 940480 CKT 1 /*6SAPONY 230.0 - AE2-033 TAP 230.0 OPEN BUS 314435 /*6SAPONY 230.0 OPEN BUS 923852 /*AB2-025 E 230.0 END |
Single | AC | 99.68 % | 100.7 % | 571.52 | B | 575.54 | 5.88 | |
| DVP |
6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line
314266 to 314569 ckt 1 |
314435 6SAPONY 230 940480 AE2-033 TAP 230 1
CONTINGENCY '314435 6SAPONY 230 940480 AE2-033 TAP 230 1' /* Auto-generated /* 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 END |
Single | AC | 99.66 % | 100.69 % | 571.52 | B | 575.43 | 5.88 | |
| DVP |
AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line
959310 to 314715 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | AC | 85.26 % | 105.32 % | 369.42 | B | 389.06 | 71.1 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 99.54 % | 100.27 % | 800.88 | B | 803.03 | 5.68 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 339.56 % | 371.02 % | 208.7 | C | 774.33 | 65.66 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 231.5 % | 265.48 % | 349.0 | C | 926.51 | 118.59 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 231.5 % | 265.48 % | 349.0 | C | 926.51 | 118.59 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 257.8 % | 281.69 % | 221.4 | C | 623.66 | 52.89 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 195.68 % | 229.66 % | 349.0 | C | 801.52 | 118.59 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 195.68 % | 229.66 % | 349.0 | C | 801.52 | 118.59 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 194.16 % | 204.55 % | 221.4 | C | 452.88 | 25.09 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 207.62 % | 242.5 % | 349.0 | C | 846.32 | 118.59 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 198.86 % | 203.34 % | 684.0 | C | 1390.84 | 30.43 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 198.85 % | 203.34 % | 684.0 | C | 1390.83 | 30.43 | |
| DVP |
6FARMVIL-6BUCKING 230.0 kV Ckt 1 line
314692 to 314677 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 198.8 % | 203.28 % | 684.0 | C | 1390.47 | 30.43 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 196.12 % | 200.5 % | 699.0 | C | 1401.5 | 30.43 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 196.11 % | 200.5 % | 699.0 | C | 1401.49 | 30.43 | |
| DVP |
6BUCKING-6BREMO 230.0 kV Ckt 1 line
314677 to 314747 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 196.06 % | 200.45 % | 699.0 | C | 1401.14 | 30.43 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 171.33 % | 206.45 % | 349.0 | C | 720.5 | 118.59 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-6: CAROLIN T122
CONTINGENCY 'DVP_P4-6: CAROLIN T122' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314578 CKT 1 /*3CAROLNA 115.0 - 3HORNRTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 315126 CKT 1 /*3CAROLNA 115.0 - 1ROARAP2 14.4 OPEN BRANCH FROM BUS 314559 TO BUS 315128 CKT 1 /*3CAROLNA 115.0 - 1ROARAP4 14.4 OPEN BUS 314559 /*3CAROLNA 115.0 OPEN BUS 314835 /*3CAROL_1 115.0 OPEN BUS 315126 /*1ROARAP2 14.4 OPEN BUS 315128 /*1ROARAP4 14.4 END |
Breaker | AC | 151.83 % | 162.34 % | 199.0 | B | 323.06 | 21.65 | |
| DVP |
6CARSON-6CHRL249 230.0 kV Ckt 1 line
314282 to 314285 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 175.28 % | 176.29 % | 684.0 | C | 1205.82 | 8.36 | |
| DVP |
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
314696 to 314697 ckt 2 |
DVP_P4-2: 3202
CONTINGENCY 'DVP_P4-2: 3202' OPEN BRANCH FROM BUS 313852 TO BUS 314716 CKT 1 /*3WELCOTAP 115.0 - 3REEDY C 115.0 OPEN BRANCH FROM BUS 313852 TO BUS 314718 CKT 1 /*3WELCOTAP 115.0 - 3S BOSTN 115.0 OPEN BRANCH FROM BUS 313852 TO BUS 314724 CKT 1 /*3WELCOTAP 115.0 - 3WELCO 115.0 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1 /*3SEDGE HILL 115.0 - 6SEDGE HILL 230.0 OPEN BRANCH FROM BUS 314696 TO BUS 314717 CKT 1 /*3SEDGE HILL 115.0 - 3SINAI 115.0 OPEN BRANCH FROM BUS 314717 TO BUS 314718 CKT 1 /*3SINAI 115.0 - 3S BOSTN 115.0 OPEN BUS 313852 /*3WELCOTAP 115.0 OPEN BUS 314717 /*3SINAI 115.0 OPEN BUS 314718 /*3S BOSTN 115.0 OPEN BUS 314724 /*3WELCO 115.0 END |
Breaker | AC | 158.05 % | 166.51 % | 279.1 | C | 464.74 | 23.76 | |
| DVP |
6CHRL249-6LOCKS 230.0 kV Ckt 1 line
314285 to 314316 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 172.46 % | 173.47 % | 684.0 | C | 1186.53 | 8.36 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 130.62 % | 140.05 % | 199.0 | B | 278.71 | 18.9 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 130.62 % | 140.05 % | 199.0 | B | 278.7 | 18.9 | |
| DVP |
6LOCKS-6HARR205 230.0 kV Ckt 1 line
314316 to 314301 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 154.38 % | 155.36 % | 541.0 | C | 840.49 | 6.57 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 102952
CONTINGENCY 'DVP_P4-2: 102952' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314572 CKT 1 /*3METCATP 115.0 - 3EMPORIA 115.0 OPEN BRANCH FROM BUS 314570 TO BUS 314588 CKT 1 /*3METCATP 115.0 - 3METCALF 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 314863 CKT 1 /*3EMPORIA 115.0 - 3EMPOR_1 115.0 OPEN BRANCH FROM BUS 314572 TO BUS 316085 CKT 1 /*3EMPORIA 115.0 - 3IVORY LANE 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314570 /*3METCATP 115.0 OPEN BUS 314572 /*3EMPORIA 115.0 OPEN BUS 314588 /*3METCALF 115.0 OPEN BUS 314863 /*3EMPOR_1 115.0 END |
Breaker | AC | 139.53 % | 142.95 % | 288.6 | C | 412.55 | 11.65 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 124.87 % | 133.3 % | 406.0 | C | 541.18 | 35.15 | |
| DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 140.59 % | 141.57 % | 541.0 | C | 765.88 | 6.22 | |
| DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P4-2: 562T563
CONTINGENCY 'DVP_P4-2: 562T563' OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON 500.0 - AE2-051 TAP 500.0 END |
Breaker | AC | 140.58 % | 141.56 % | 541.0 | C | 765.82 | 6.22 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 122.71 % | 131.04 % | 406.0 | C | 532.01 | 35.02 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 121.31 % | 129.64 % | 406.0 | C | 526.33 | 35.02 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 14852
CONTINGENCY 'DVP_P4-2: 14852' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 END |
Breaker | AC | 128.36 % | 131.77 % | 288.6 | C | 380.29 | 11.65 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 7152
CONTINGENCY 'DVP_P4-2: 7152' OPEN BRANCH FROM BUS 314312 TO BUS 314325 CKT 1 /*3JARRATT 115.0 - 3PURDYSW 115.0 OPEN BRANCH FROM BUS 314325 TO BUS 314562 CKT 1 /*3PURDYSW 115.0 - 3CLUBHSE 115.0 OPEN BRANCH FROM BUS 314516 TO BUS 314676 CKT 1 /*3BRUNWICK_1 115.0 - 3BRUNWICK 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314563 CKT 1 /*3CLUBHSE 115.0 - 6CLUBHSE 230.0 OPEN BRANCH FROM BUS 314562 TO BUS 314565 CKT Z1 /*3CLUBHSE 115.0 - 3CLUBHSE71 115.0 OPEN BRANCH FROM BUS 314562 TO BUS 314570 CKT 1 /*3CLUBHSE 115.0 - 3METCATP 115.0 OPEN BRANCH FROM BUS 314565 TO BUS 314693 CKT 1 /*3CLUBHSE71 115.0 - 3FRMAN D 115.0 OPEN BRANCH FROM BUS 314565 TO BUS 314850 CKT 1 /*3CLUBHSE71 115.0 - 3CLUBHSE71_1 115.0 OPEN BRANCH FROM BUS 314675 TO BUS 314676 CKT 1 /*3BRODNAX 115.0 - 3BRUNWICK 115.0 OPEN BRANCH FROM BUS 314676 TO BUS 314704 CKT 1 /*3BRUNWICK 115.0 - 3LAWRENC 115.0 OPEN BRANCH FROM BUS 314693 TO BUS 314704 CKT 1 /*3FRMAN D 115.0 - 3LAWRENC 115.0 OPEN BUS 314312 /*3JARRATT 115.0 OPEN BUS 314325 /*3PURDYSW 115.0 OPEN BUS 314516 /*3BRUNWICK_1 115.0 OPEN BUS 314562 /*3CLUBHSE 115.0 OPEN BUS 314565 /*3CLUBHSE71 115.0 OPEN BUS 314676 /*3BRUNWICK 115.0 OPEN BUS 314693 /*3FRMAN D 115.0 OPEN BUS 314704 /*3LAWRENC 115.0 OPEN BUS 314782 /*2BRUNWICK 69.0 OPEN BUS 314785 /*2DANLTWN 69.0 OPEN BUS 314786 /*2GASBURG 69.0 OPEN BUS 314787 /*2BRUNWICK2 69.0 OPEN BUS 314850 /*3CLUBHSE71_1 115.0 OPEN BUS 314872 /*2BRUNSWICKDP 69.0 END |
Breaker | AC | 127.65 % | 131.06 % | 288.6 | C | 378.23 | 11.65 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P4-2: 93T140
CONTINGENCY 'DVP_P4-2: 93T140' OPEN BRANCH FROM BUS 313720 TO BUS 314526 CKT 1 /*3NEWSOMS 115.0 - 3HANDSOM 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314539 CKT 1 /*3FRNKLN 115.0 - 3UNCAMP 115.0 OPEN BRANCH FROM BUS 314524 TO BUS 314541 CKT 1 /*3FRNKLN 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314526 TO BUS 314534 CKT 1 /*3HANDSOM 115.0 - 3S HAMPT 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 314541 CKT 1 /*3S HAMPT 115.0 - 3WATKINS 115.0 OPEN BRANCH FROM BUS 314534 TO BUS 315115 CKT 1 /*3S HAMPT 115.0 - 1S HAMPT1 13.8 OPEN BRANCH FROM BUS 314541 TO BUS 314826 CKT 1 /*3WATKINS 115.0 - 3WATKI_1 115.0 OPEN BRANCH FROM BUS 314541 TO BUS 314827 CKT 1 /*3WATKINS 115.0 - 3WATKI_2 115.0 OPEN BUS 314524 /*3FRNKLN 115.0 OPEN BUS 314526 /*3HANDSOM 115.0 OPEN BUS 314541 /*3WATKINS 115.0 OPEN BUS 314826 /*3WATKI_1 115.0 OPEN BUS 314827 /*3WATKI_2 115.0 OPEN BUS 315115 /*1S HAMPT1 13.8 END |
Breaker | AC | 129.45 % | 132.24 % | 288.6 | C | 381.64 | 10.32 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 129.27 % | 131.31 % | 809.0 | C | 1062.3 | 16.84 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 129.27 % | 131.31 % | 809.0 | C | 1062.29 | 16.84 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 129.25 % | 131.29 % | 809.0 | C | 1062.14 | 16.84 | |
| DVP |
3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line
314684 to 316115 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 113.05 % | 121.42 % | 406.0 | C | 492.95 | 35.15 | |
| DVP |
6POE-6HARROWG 230.0 kV Ckt 1 line
314331 to 314299 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 131.65 % | 132.77 % | 541.0 | C | 718.26 | 9.17 | |
| DVP |
6HARROWG-6TYLER1 230.0 kV Ckt 1 line
314299 to 314263 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 131.57 % | 132.69 % | 541.0 | C | 717.83 | 9.17 | |
| DVP |
3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line
314684 to 316115 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 111.38 % | 119.71 % | 406.0 | C | 486.01 | 35.02 | |
| DVP |
3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line
314684 to 316115 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 109.97 % | 118.31 % | 406.0 | C | 480.33 | 35.02 | |
| DVP |
AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line
962560 to 314684 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 108.14 % | 116.48 % | 406.0 | C | 472.9 | 35.15 | |
| DVP |
AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line
962560 to 314684 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 106.48 % | 114.79 % | 406.0 | C | 466.04 | 35.02 | |
| DVP |
3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line
313825 to 314696 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | AC | 100.67 % | 108.38 % | 172.0 | C | 186.41 | 15.54 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 116.11 % | 118.29 % | 350.0 | C | 414.03 | 9.05 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 116.11 % | 118.29 % | 350.0 | C | 414.02 | 9.05 | |
| DVP |
AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line
942750 to 314694 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 116.1 % | 118.29 % | 350.0 | C | 414.01 | 9.05 | |
| DVP |
AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line
962560 to 314684 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 105.08 % | 113.39 % | 406.0 | C | 460.36 | 35.02 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 115.24 % | 117.43 % | 350.0 | C | 410.99 | 9.05 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 115.24 % | 117.43 % | 350.0 | C | 410.99 | 9.05 | |
| DVP |
3GRIT-3OTTER R 115.0 kV Ckt 1 line
314694 to 314712 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 115.24 % | 117.42 % | 350.0 | C | 410.97 | 9.05 | |
| DVP |
3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line
313825 to 314696 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | AC | 98.19 % | 105.84 % | 172.0 | C | 182.04 | 15.44 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 112.27 % | 114.51 % | 342.0 | C | 391.61 | 9.05 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 112.27 % | 114.51 % | 342.0 | C | 391.61 | 9.05 | |
| DVP |
3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line
314712 to 314666 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | AC | 112.27 % | 114.5 % | 342.0 | C | 391.6 | 9.05 | |
| DVP |
3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line
313825 to 314696 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | AC | 96.63 % | 104.28 % | 172.0 | C | 179.37 | 15.44 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 8432
CONTINGENCY 'DVP_P4-2: 8432' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | DC | 116.36 % | 124.66 % | 406.0 | C | 506.14 | 35.15 | |
| DVP |
3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line
314267 to 314669 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 96.03 % | 104.32 % | 406.0 | C | 423.54 | 35.15 | |
| DVP |
3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line
314669 to 962560 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 95.12 % | 103.41 % | 406.0 | C | 419.86 | 35.15 | |
| DVP |
3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line
314267 to 314669 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 94.4 % | 102.66 % | 406.0 | C | 416.79 | 35.02 | |
| DVP |
3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line
314669 to 962560 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 93.49 % | 101.75 % | 406.0 | C | 413.11 | 35.02 | |
| DVP |
3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line
314267 to 314669 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 93.0 % | 101.26 % | 406.0 | C | 411.11 | 35.02 | |
| DVP |
3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line
314669 to 962560 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 92.09 % | 100.35 % | 406.0 | C | 407.43 | 35.02 | |
| DVP |
3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line
314684 to 316115 ckt 1 |
DVP_P4-2: 8432
CONTINGENCY 'DVP_P4-2: 8432' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | DC | 105.02 % | 113.33 % | 406.0 | C | 460.1 | 35.15 | |
| DVP |
AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line
962490 to 314686 ckt 1 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 99.89 % | 106.97 % | 699.0 | C | 747.73 | 50.2 | |
| DVP |
AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line
962490 to 314686 ckt 1 |
DVP_P4-2: 219322
CONTINGENCY 'DVP_P4-2: 219322' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 96.2 % | 100.24 % | 699.0 | C | 700.66 | 28.0 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 109.7 % | 111.02 % | 980.0 | C | 1087.95 | 12.99 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 109.67 % | 110.98 % | 980.0 | C | 1087.58 | 12.99 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 109.33 % | 110.65 % | 980.0 | C | 1084.33 | 12.99 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 109.3 % | 110.61 % | 980.0 | C | 1083.99 | 12.99 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 108.49 % | 109.84 % | 980.0 | C | 1076.45 | 13.0 | |
| DVP |
AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line
962560 to 314684 ckt 1 |
DVP_P4-2: 8432
CONTINGENCY 'DVP_P4-2: 8432' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | DC | 100.08 % | 108.36 % | 406.0 | C | 439.93 | 35.15 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 108.11 % | 109.46 % | 980.0 | C | 1072.72 | 13.01 | |
| DVP |
6CARSON-6POE 230.0 kV Ckt 1 line
314282 to 314331 ckt 1 |
DVP_P4-2: 24972-4
CONTINGENCY 'DVP_P4-2: 24972-4' OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1 /*6CARSON 230.0 - 6CHRL249 230.0 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1 /*6CARSON 230.0 - 8CARSON 500.0 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1 /*6CHRL249 230.0 - 6LOCKS 230.0 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2 /*3LOCKS 115.0 - 6LOCKS 230.0 OPEN BUS 314285 /*6CHRL249 230.0 OPEN BUS 314455 /*6CARSO_1 230.0 END |
Breaker | AC | 101.89 % | 102.99 % | 830.0 | C | 854.85 | 11.54 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 101.92 % | 103.27 % | 980.0 | C | 1012.09 | 13.0 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 101.55 % | 102.9 % | 980.0 | C | 1008.45 | 13.01 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 3612
CONTINGENCY 'DVP_P4-2: 3612' OPEN BRANCH FROM BUS 313806 TO BUS 314681 CKT 1 /*3HERBERT 115.0 - 3CHASCTY 115.0 OPEN BRANCH FROM BUS 314681 TO BUS 314708 CKT 1 /*3CHASCTY 115.0 - 3NORVIEW 115.0 OPEN BRANCH FROM BUS 314681 TO BUS 314781 CKT 1 /*3CHASCTY 115.0 - 3BLACKBR 115.0 OPEN BRANCH FROM BUS 314682 TO BUS 314869 CKT 1 /*3BUGGS I 115.0 - 3BURLING 115.0 OPEN BRANCH FROM BUS 314683 TO BUS 314788 CKT 1 /*3CLRKVILLE 115.0 - 3JONESTO 115.0 OPEN BRANCH FROM BUS 314683 TO BUS 314869 CKT 1 /*3CLRKVILLE 115.0 - 3BURLING 115.0 OPEN BRANCH FROM BUS 314781 TO BUS 314788 CKT 1 /*3BLACKBR 115.0 - 3JONESTO 115.0 OPEN BRANCH FROM BUS 959310 TO BUS 314722 CKT 1 /*AF2-222 TAP 115.0 - 3TWITTYS 115.0 OPEN BUS 314683 /*3CLRKVILLE 115.0 OPEN BUS 314781 /*3BLACKBR 115.0 OPEN BUS 314788 /*3JONESTO 115.0 OPEN BUS 314869 /*3BURLING 115.0 OPEN BUS 924301 /*AB2-077 C O1 115.0 OPEN BUS 924302 /*AB2-077 E O1 115.0 OPEN BUS 924311 /*AB2-078 C O1 115.0 OPEN BUS 924312 /*AB2-078 E O1 115.0 OPEN BUS 924321 /*AB2-079 C O1 115.0 OPEN BUS 924322 /*AB2-079 E O1 115.0 END |
Breaker | AC | 94.77 % | 104.78 % | 406.0 | C | 425.41 | 46.37 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 100.85 % | 102.21 % | 980.0 | C | 1001.64 | 13.0 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 100.48 % | 101.84 % | 980.0 | C | 998.0 | 13.01 | |
| DVP |
6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer
314686 to 314906 ckt 2 |
DVP_P4-5: L912
CONTINGENCY 'DVP_P4-5: L912' OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 1 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BRANCH FROM BUS 314686 TO BUS 314906 CKT 3 /*6CLOVER 230.0 - 8CLOVER 500.0 OPEN BUS 313817 /*6CLOVER_1 230.0 END |
Breaker | AC | 99.84 % | 101.25 % | 1275.1 | C | 1291.0 | 18.34 | |
| DVP |
AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line
962490 to 314686 ckt 1 |
DVP_P2-2: BREMO B1
CONTINGENCY 'DVP_P2-2: BREMO B1' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Bus | AC | 96.2 % | 100.23 % | 699.0 | C | 700.61 | 28.0 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P7-1: LN 22-90
CONTINGENCY 'DVP_P7-1: LN 22-90' OPEN BRANCH FROM BUS 314265 TO BUS 314584 CKT 1 /*3FIVEFORKSDP 115.0 - 3LITTLTN 115.0 OPEN BRANCH FROM BUS 314265 TO BUS 314673 CKT 1 /*3FIVEFORKSDP 115.0 - 3PALMERSPRNG 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314584 TO BUS 314585 CKT 1 /*3LITTLTN 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314265 /*3FIVEFORKSDP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 314584 /*3LITTLTN 115.0 OPEN BUS 314585 /*3L GASTN 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Tower | AC | 149.38 % | 159.76 % | 199.0 | B | 317.92 | 21.4 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 110.08 % | 111.39 % | 980.0 | C | 1091.64 | 12.99 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 110.07 % | 111.39 % | 980.0 | C | 1091.57 | 12.99 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 110.04 % | 111.36 % | 980.0 | C | 1091.29 | 12.99 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 110.04 % | 111.35 % | 980.0 | C | 1091.22 | 12.99 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 108.85 % | 110.2 % | 980.0 | C | 1079.98 | 13.01 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 108.85 % | 110.19 % | 980.0 | C | 1079.9 | 13.01 | |
| DVP |
3KERRDP-3KERR 115.0 kV Ckt 1 line
313705 to 314702 ckt 1 |
DVP_P7-1: LN 171-1009
CONTINGENCY 'DVP_P7-1: LN 171-1009' OPEN BRANCH FROM BUS 313806 TO BUS 314681 CKT 1 /*3HERBERT 115.0 - 3CHASCTY 115.0 OPEN BRANCH FROM BUS 313849 TO BUS 314267 CKT 1 /*3RIDGERD 115.0 - 3CHASCTY2 115.0 END |
Tower | AC | 95.02 % | 103.1 % | 195.0 | C | 201.04 | 15.82 | |
| DVP |
3ISLND C-3KERRDP 115.0 kV Ckt 1 line
314699 to 313705 ckt 1 |
DVP_P7-1: LN 171-1009
CONTINGENCY 'DVP_P7-1: LN 171-1009' OPEN BRANCH FROM BUS 313806 TO BUS 314681 CKT 1 /*3HERBERT 115.0 - 3CHASCTY 115.0 OPEN BRANCH FROM BUS 313849 TO BUS 314267 CKT 1 /*3RIDGERD 115.0 - 3CHASCTY2 115.0 END |
Tower | AC | 92.55 % | 100.34 % | 202.0 | C | 202.7 | 15.82 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 102.42 % | 103.74 % | 980.0 | C | 1016.64 | 13.01 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 102.42 % | 103.73 % | 980.0 | C | 1016.57 | 13.01 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 101.36 % | 102.68 % | 980.0 | C | 1006.22 | 13.01 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 101.36 % | 102.67 % | 980.0 | C | 1006.17 | 13.01 | |
| AEP |
05EDAN 1-05DANVL2 138.0 kV Ckt 1 line
242631 to 242620 ckt 1 |
AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1
CONTINGENCY 'AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1' OPEN BRANCH FROM BUS 242520 TO BUS 242514 CKT 1 /*05J.FERR 500.0 - 05J.FERR 765.0 END |
Single | AC | 112.39 % | 113.43 % | 402.0 | B | 455.98 | 4.64 | |
| AEP |
05EDAN 1-05DANVL2 138.0 kV Ckt 1 line
242631 to 242620 ckt 1 |
AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1
CONTINGENCY 'AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1' OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1 /*05J.FERR 500.0 - 8ANTIOCH 500.0 END |
Single | AC | 112.34 % | 113.38 % | 402.0 | B | 455.78 | 4.64 | |
| AEP |
05EDAN 1-05DANVL2 138.0 kV Ckt 1 line
242631 to 242620 ckt 1 |
AEP_P4_#11112_05J.FERR 765_A1
CONTINGENCY 'AEP_P4_#11112_05J.FERR 765_A1' OPEN BRANCH FROM BUS 242511 TO BUS 242514 CKT 1 /*05BROADF 765.0 - 05J.FERR 765.0 OPEN BRANCH FROM BUS 242514 TO BUS 242520 CKT 1 /*05J.FERR 765.0 - 05J.FERR 500.0 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1 /*05J.FERR 500.0 - 8ANTIOCH 500.0 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB /*05BROADF 138.0 - 05BROADX 138.0 END |
Breaker | AC | 146.49 % | 148.0 % | 402.0 | B | 594.98 | 7.36 | |
| AEP |
AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line
941430 to 242544 ckt 1 |
AEP_P4_#11112_05J.FERR 765_A1
CONTINGENCY 'AEP_P4_#11112_05J.FERR 765_A1' OPEN BRANCH FROM BUS 242511 TO BUS 242514 CKT 1 /*05BROADF 765.0 - 05J.FERR 765.0 OPEN BRANCH FROM BUS 242514 TO BUS 242520 CKT 1 /*05J.FERR 765.0 - 05J.FERR 500.0 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1 /*05J.FERR 500.0 - 8ANTIOCH 500.0 OPEN BRANCH FROM BUS 242566 TO BUS 242567 CKT ZB /*05BROADF 138.0 - 05BROADX 138.0 END |
Breaker | AC | 114.57 % | 115.95 % | 388.0 | B | 449.88 | 6.31 | |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 120.0 MW | 120.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 20.0 MW | 20.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965641 | AG1-432 C O1 | 80/20 | 120.0 MW | 120.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965831 | AG1-451 | 80/20 | 20.0 MW | 20.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961791 | AG1-021 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961891 | AG1-030 C | 80/20 | 37.77 MW | 37.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963171 | AG1-166 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963181 | AG1-167 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963191 | AG1-168 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963201 | AG1-169 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963211 | AG1-170 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963301 | AG1-179 C | 80/20 | 3.87 MW | 3.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963311 | AG1-180 | 80/20 | 1.89 MW | 1.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963321 | AG1-181 C O1 | 80/20 | 32.77 MW | 32.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963361 | AG1-185 O1 | 80/20 | 15.86 MW | 15.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964111 | AG1-272 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964121 | AG1-273 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964131 | AG1-274 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964241 | AG1-285 C O1 | 80/20 | 18.39 MW | 18.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964791 | AG1-342 C | 80/20 | 3.1 MW | 3.1 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965191 | AG1-384 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965591 | AG1-427 C | 80/20 | 17.61 MW | 17.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965601 | AG1-428 C O2 | 80/20 | 3.23 MW | 3.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965641 | AG1-432 C O1 | 80/20 | 73.68 MW | 73.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965721 | AG1-440 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965731 | AG1-441 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965771 | AG1-445 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965781 | AG1-446 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965831 | AG1-451 | 80/20 | 12.28 MW | 12.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 966621 | AG1-532 C | 80/20 | 0.47 MW | 0.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313506 | AB1-173 C OP | 80/20 | 2.2 MW | 2.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314429 | 3JTRSVLE | 80/20 | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314704 | 3LAWRENC | 80/20 | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315158 | 1KERR 1 | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315159 | 1KERR 2 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315160 | 1KERR 3 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315161 | 1KERR 4 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315162 | 1KERR 5 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 927261 | AC1-222 C | 80/20 | 1.32 MW | 1.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 934311 | AD1-055 C | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 936265 | AD2-033 C | 80/20 | 24.79 MW | 24.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 942461 | AE2-259 C O1 | 80/20 | 36.84 MW | 36.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 943901 | AF1-058 C | 80/20 | 0.75 MW | 0.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958801 | AF2-171 C | 80/20 | 41.22 MW | 41.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 959311 | AF2-222 C | 80/20 | 36.05 MW | 36.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960061 | AF2-297 C | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960081 | AF2-299 C | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315163 | 1KERR 6 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315164 | 1KERR 7 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315266 | 1PLYWOOD A | 80/20 | 0.63 MW | 0.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316118 | AC1-105 C | 80/20 | 3.19 MW | 3.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316129 | AC1-054 C | 80/20 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316131 | AB2-060 C | 80/20 | 2.02 MW | 2.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924301 | AB2-077 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924311 | AB2-078 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924321 | AB2-079 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 925611 | AC1-036 C | 80/20 | 0.5 MW | 0.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 938371 | AE1-056 C | 80/20 | 19.46 MW | 19.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 939181 | AE1-148 C | 80/20 | 7.77 MW | 7.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 940661 | AE2-053 O1 | 80/20 | 2.88 MW | 2.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946281 | AF1-292 C | 80/20 | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946301 | AF1-294 C | 80/20 | 11.32 MW | 11.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958211 | AF2-115 C | 80/20 | 6.9 MW | 6.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316087 | AB2-174 C | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 962561 | AG1-105 C O1 | 80/20 | 7.36 MW | 7.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313527 | AB2-043 C | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.97 MW | 13.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.32 MW | 3.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.07 MW | 4.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.0 MW | 1.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.8 MW | 0.8 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 961791 | AG1-021 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 961891 | AG1-030 C | 80/20 | 24.36 MW | 24.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963171 | AG1-166 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963181 | AG1-167 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963191 | AG1-168 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963201 | AG1-169 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963211 | AG1-170 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963301 | AG1-179 C | 80/20 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963311 | AG1-180 | 80/20 | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 46.99 MW | 46.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 22.74 MW | 22.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 34.86 MW | 34.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964791 | AG1-342 C | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 33.05 MW | 33.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965601 | AG1-428 C O2 | 80/20 | 1.42 MW | 1.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 55.78 MW | 55.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965721 | AG1-440 C | 80/20 | 2.25 MW | 2.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965731 | AG1-441 C | 80/20 | 2.25 MW | 2.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965771 | AG1-445 | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965781 | AG1-446 | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 9.3 MW | 9.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 314429 | 3JTRSVLE | 80/20 | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315159 | 1KERR 2 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315160 | 1KERR 3 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 936265 | AD2-033 C | 80/20 | 14.45 MW | 14.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 27.89 MW | 27.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 41.84 MW | 41.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 46.48 MW | 46.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 316131 | AB2-060 C | 80/20 | 0.94 MW | 0.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924301 | AB2-077 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924311 | AB2-078 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924321 | AB2-079 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 0.68 MW | 0.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 18.04 MW | 18.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 939181 | AE1-148 C | 80/20 | 3.42 MW | 3.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 940661 | AE2-053 O1 | 80/20 | 1.27 MW | 1.27 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 946301 | AF1-294 C | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 958211 | AF2-115 C | 80/20 | 4.57 MW | 4.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 962561 | AG1-105 C O1 | 80/20 | 3.14 MW | 3.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.37 MW | 0.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 33.51 MW | 33.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 25.47 MW | 25.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 31.12 MW | 31.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 18.22 MW | 18.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 60.41 MW | 60.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 27.11 MW | 27.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 27.11 MW | 27.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313506 | AB1-173 C OP | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315128 | 1ROARAP4 | 80/20 | 0.53 MW | 0.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 22.65 MW | 22.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 23.68 MW | 23.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 6.74 MW | 6.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 8.39 MW | 8.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 33.24 MW | 33.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 9.36 MW | 9.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 90.36 MW | 90.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.95 MW | 41.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.23 MW | 12.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.5 MW | 13.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 33.5 MW | 33.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 25.46 MW | 25.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 1.69 MW | 1.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 18.21 MW | 18.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 60.4 MW | 60.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 27.1 MW | 27.1 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 27.1 MW | 27.1 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313506 | AB1-173 C OP | 80/20 | 2.68 MW | 2.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315128 | 1ROARAP4 | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 23.67 MW | 23.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 6.73 MW | 6.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 8.38 MW | 8.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 33.23 MW | 33.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 9.35 MW | 9.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 90.34 MW | 90.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 5.99 MW | 5.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.88 MW | 41.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.14 MW | 12.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.43 MW | 13.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.79 MW | 1.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961791 | AG1-021 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961891 | AG1-030 C | 80/20 | 7.72 MW | 7.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963171 | AG1-166 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963181 | AG1-167 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963191 | AG1-168 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963201 | AG1-169 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963211 | AG1-170 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963301 | AG1-179 C | 80/20 | 12.96 MW | 12.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963311 | AG1-180 | 80/20 | 6.32 MW | 6.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963321 | AG1-181 C O1 | 80/20 | 10.66 MW | 10.66 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 963361 | AG1-185 O1 | 80/20 | 5.16 MW | 5.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964111 | AG1-272 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964121 | AG1-273 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964131 | AG1-274 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964241 | AG1-285 C O1 | 80/20 | 9.13 MW | 9.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964791 | AG1-342 C | 80/20 | 1.94 MW | 1.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 964801 | AG1-343 C | 80/20 | 2.87 MW | 2.87 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 966811 | AG1-552 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965191 | AG1-384 C | 80/20 | 1.56 MW | 1.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965291 | AG1-394 C | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965591 | AG1-427 C | 80/20 | 8.62 MW | 8.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965601 | AG1-428 C O2 | 80/20 | 10.82 MW | 10.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965721 | AG1-440 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965731 | AG1-441 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965771 | AG1-445 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 965781 | AG1-446 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 966621 | AG1-532 C | 80/20 | 4.38 MW | 4.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313506 | AB1-173 C OP | 80/20 | 14.92 MW | 14.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313719 | 3CHESTNUT | 80/20 | 0.56 MW | 0.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314572 | 3EMPORIA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314704 | 3LAWRENC | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315126 | 1ROARAP2 | 80/20 | 1.29 MW | 1.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315128 | 1ROARAP4 | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315136 | 1ROSEMG1 | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315139 | 1GASTONA | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315159 | 1KERR 2 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315160 | 1KERR 3 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315161 | 1KERR 4 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315162 | 1KERR 5 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926070 | AC1-086 C | 80/20 | 10.02 MW | 10.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926201 | AC1-098 C | 80/20 | 3.11 MW | 3.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 926211 | AC1-099 C | 80/20 | 1.04 MW | 1.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 927145 | AC1-208 C | 80/20 | 5.26 MW | 5.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 934331 | AD1-057 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 936265 | AD2-033 C | 80/20 | 8.32 MW | 8.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 944141 | AF1-082 | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 958801 | AF2-171 C | 80/20 | 7.02 MW | 7.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 959311 | AF2-222 C | 80/20 | 9.8 MW | 9.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 960081 | AF2-299 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315163 | 1KERR 6 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315164 | 1KERR 7 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315266 | 1PLYWOOD A | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315606 | 3AA2-053SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316020 | AB2-059 C OP | 80/20 | 0.59 MW | 0.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316118 | AC1-105 C | 80/20 | 2.02 MW | 2.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316129 | AC1-054 C | 80/20 | 5.72 MW | 5.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 922922 | AB1-081 C OP | 80/20 | 0.5 MW | 0.5 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 923262 | AB1-132 C OP | 80/20 | 6.8 MW | 6.8 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 923991 | AB2-040 C O1 | 80/20 | 16.25 MW | 16.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 925591 | AC1-034 C | 80/20 | 2.25 MW | 2.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 932631 | AC2-084 C | 80/20 | 4.43 MW | 4.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 938371 | AE1-056 C | 80/20 | 2.68 MW | 2.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 939181 | AE1-148 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 940571 | AE2-044 C | 80/20 | 1.47 MW | 1.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 940661 | AE2-053 O1 | 80/20 | 2.29 MW | 2.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 946281 | AF1-292 C | 80/20 | 4.81 MW | 4.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 946301 | AF1-294 C | 80/20 | 1.91 MW | 1.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 957521 | AF2-046 C | 80/20 | 7.43 MW | 7.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 958211 | AF2-115 C | 80/20 | 1.16 MW | 1.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315115 | 1S HAMPT1 | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315141 | 1GASTONB | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 315608 | 3AA2-088SOLA | 80/20 | 0.51 MW | 0.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316087 | AB2-174 C | 80/20 | 2.96 MW | 2.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316096 | AB2-100 C1 | 80/20 | 0.46 MW | 0.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 316098 | AB2-100 C2 | 80/20 | 0.46 MW | 0.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962561 | AG1-105 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 961681 | AG1-008 C | 80/20 | 7.45 MW | 7.45 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 962571 | AG1-106 C | 80/20 | 2.79 MW | 2.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.91 MW | 13.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.92 MW | 4.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.96 MW | 4.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.15 MW | 1.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.69 MW | 0.69 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2201 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 1.88 MW | 1.88 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 0.92 MW | 0.92 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 31.57 MW | 31.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 15.27 MW | 15.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 12.75 MW | 12.75 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.43 MW | 1.43 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 12.41 MW | 12.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 1.57 MW | 1.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 100.11 MW | 100.11 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 16.68 MW | 16.68 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 4.15 MW | 4.15 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 50.05 MW | 50.05 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 49.79 MW | 49.79 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 37.78 MW | 37.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.51 MW | 0.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 24.51 MW | 24.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 3.78 MW | 3.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.4 MW | 1.4 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.51 MW | 4.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.2 MW | 1.2 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.38 MW | 1.38 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.41 MW | 0.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 33.51 MW | 33.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 25.47 MW | 25.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 31.12 MW | 31.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 18.22 MW | 18.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 60.41 MW | 60.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 2.69 MW | 2.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.53 MW | 0.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.65 MW | 22.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 23.68 MW | 23.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 6.74 MW | 6.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.39 MW | 8.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.24 MW | 33.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 9.36 MW | 9.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 1.88 MW | 1.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 90.36 MW | 90.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | Adder | -6.03 MW | -5.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.95 MW | 41.95 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.23 MW | 12.23 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.5 MW | 13.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 33.5 MW | 33.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 25.46 MW | 25.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 4.35 MW | 4.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 2.12 MW | 2.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 31.11 MW | 31.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 5.25 MW | 5.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 3.52 MW | 3.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 1.69 MW | 1.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966811 | AG1-552 C | 80/20 | 0.81 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 4.95 MW | 4.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 18.21 MW | 18.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.63 MW | 3.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 60.4 MW | 60.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 6.47 MW | 6.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.74 MW | 3.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966621 | AG1-532 C | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313506 | AB1-173 C OP | 80/20 | 2.68 MW | 2.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313719 | 3CHESTNUT | 80/20 | 0.39 MW | 0.39 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314572 | 3EMPORIA | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.22 MW | 0.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315126 | 1ROARAP2 | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315128 | 1ROARAP4 | 80/20 | 0.52 MW | 0.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 22.64 MW | 22.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 22.43 MW | 22.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 0.54 MW | 0.54 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 920591 | AA2-165 C | 80/20 | 0.05 MW | 0.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.29 MW | 0.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.17 MW | 0.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927145 | AC1-208 C | 80/20 | 2.98 MW | 2.98 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 1.68 MW | 1.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 4.12 MW | 4.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 2.86 MW | 2.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 4.22 MW | 4.22 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 13.12 MW | 13.12 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 28.52 MW | 28.52 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 1.38 MW | 1.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 12.28 MW | 12.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936161 | AD2-022 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936171 | AD2-023 C O1 | 80/20 | 2.44 MW | 2.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 23.67 MW | 23.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 30.2 MW | 30.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 2.06 MW | 2.06 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 6.73 MW | 6.73 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 8.38 MW | 8.38 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 2.32 MW | 2.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 12.65 MW | 12.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 35.83 MW | 35.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 33.23 MW | 33.23 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 9.29 MW | 9.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960081 | AF2-299 C | 80/20 | 1.02 MW | 1.02 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.42 MW | 0.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.5 MW | 1.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315606 | 3AA2-053SOLA | 80/20 | 0.55 MW | 0.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 6.93 MW | 6.93 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 5.21 MW | 5.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 923991 | AB2-040 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 0.83 MW | 0.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 3.87 MW | 3.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 16.59 MW | 16.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 9.35 MW | 9.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.46 MW | 3.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.63 MW | 4.63 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 1.87 MW | 1.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946281 | AF1-292 C | 80/20 | 0.61 MW | 0.61 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 9.83 MW | 9.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 90.34 MW | 90.34 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 5.99 MW | 5.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315607 | 3AA1-063SOLA | 80/20 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316087 | AB2-174 C | 80/20 | 0.48 MW | 0.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 41.88 MW | 41.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.14 MW | 12.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.43 MW | 13.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.6 MW | 0.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.79 MW | 1.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.29 MW | 0.29 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961791 | AG1-021 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961891 | AG1-030 C | 80/20 | 7.73 MW | 7.73 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961941 | AG1-037 C | 80/20 | 0.2 MW | 0.2 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962331 | AG1-082 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962341 | AG1-083 C | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963171 | AG1-166 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963181 | AG1-167 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963191 | AG1-168 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963201 | AG1-169 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963211 | AG1-170 C | 80/20 | 0.93 MW | 0.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963301 | AG1-179 C | 80/20 | 12.97 MW | 12.97 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963311 | AG1-180 | 80/20 | 6.32 MW | 6.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963321 | AG1-181 C O1 | 80/20 | 10.68 MW | 10.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 963361 | AG1-185 O1 | 80/20 | 5.17 MW | 5.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964111 | AG1-272 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964121 | AG1-273 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964131 | AG1-274 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964241 | AG1-285 C O1 | 80/20 | 9.14 MW | 9.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964791 | AG1-342 C | 80/20 | 1.95 MW | 1.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 964801 | AG1-343 C | 80/20 | 2.88 MW | 2.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 966811 | AG1-552 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965191 | AG1-384 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965291 | AG1-394 C | 80/20 | 1.0 MW | 1.0 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965591 | AG1-427 C | 80/20 | 8.62 MW | 8.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965601 | AG1-428 C O2 | 80/20 | 10.83 MW | 10.83 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965721 | AG1-440 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965731 | AG1-441 C | 80/20 | 5.28 MW | 5.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965771 | AG1-445 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 965781 | AG1-446 | 80/20 | 3.05 MW | 3.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 966621 | AG1-532 C | 80/20 | 4.38 MW | 4.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313506 | AB1-173 C OP | 80/20 | 14.93 MW | 14.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313719 | 3CHESTNUT | 80/20 | 0.56 MW | 0.56 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314572 | 3EMPORIA | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314582 | 3KELFORD | 80/20 | 0.16 MW | 0.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314623 | 3WITAKRS | 80/20 | 0.09 MW | 0.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314704 | 3LAWRENC | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315126 | 1ROARAP2 | 80/20 | 1.29 MW | 1.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315128 | 1ROARAP4 | 80/20 | 1.23 MW | 1.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315136 | 1ROSEMG1 | 80/20 | 1.01 MW | 1.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315137 | 1ROSEMS1 | 80/20 | 0.62 MW | 0.62 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315138 | 1ROSEMG2 | 80/20 | 0.47 MW | 0.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315139 | 1GASTONA | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315158 | 1KERR 1 | 80/20 | 0.28 MW | 0.28 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315159 | 1KERR 2 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315160 | 1KERR 3 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315161 | 1KERR 4 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315162 | 1KERR 5 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 920591 | AA2-165 C | 80/20 | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926070 | AC1-086 C | 80/20 | 10.03 MW | 10.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926201 | AC1-098 C | 80/20 | 3.11 MW | 3.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 926211 | AC1-099 C | 80/20 | 1.04 MW | 1.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 927145 | AC1-208 C | 80/20 | 5.27 MW | 5.27 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 934331 | AD1-057 C O1 | 80/20 | 3.81 MW | 3.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 936265 | AD2-033 C | 80/20 | 8.33 MW | 8.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 943171 | AE2-346 C | 80/20 | 0.55 MW | 0.55 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 944141 | AF1-082 | 80/20 | 0.95 MW | 0.95 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 958801 | AF2-171 C | 80/20 | 7.03 MW | 7.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 959311 | AF2-222 C | 80/20 | 9.81 MW | 9.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 960081 | AF2-299 C | 80/20 | 8.11 MW | 8.11 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315163 | 1KERR 6 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315164 | 1KERR 7 | 80/20 | 0.79 MW | 0.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315266 | 1PLYWOOD A | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315606 | 3AA2-053SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316020 | AB2-059 C OP | 80/20 | 0.59 MW | 0.59 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316118 | AC1-105 C | 80/20 | 2.02 MW | 2.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316129 | AC1-054 C | 80/20 | 5.72 MW | 5.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316140 | AB2-099 C | 80/20 | 0.23 MW | 0.23 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 922922 | AB1-081 C OP | 80/20 | 0.5 MW | 0.5 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 923262 | AB1-132 C OP | 80/20 | 6.81 MW | 6.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 923991 | AB2-040 C O1 | 80/20 | 16.26 MW | 16.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 925591 | AC1-034 C | 80/20 | 2.25 MW | 2.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 932631 | AC2-084 C | 80/20 | 4.43 MW | 4.43 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 938371 | AE1-056 C | 80/20 | 2.68 MW | 2.68 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 939181 | AE1-148 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 940571 | AE2-044 C | 80/20 | 1.47 MW | 1.47 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 940661 | AE2-053 O1 | 80/20 | 2.29 MW | 2.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 946281 | AF1-292 C | 80/20 | 4.81 MW | 4.81 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 946301 | AF1-294 C | 80/20 | 1.91 MW | 1.91 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 957521 | AF2-046 C | 80/20 | 7.44 MW | 7.44 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 958211 | AF2-115 C | 80/20 | 1.16 MW | 1.16 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 314589 | 3MURPHYS | 80/20 | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315115 | 1S HAMPT1 | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315141 | 1GASTONB | 80/20 | 1.52 MW | 1.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315607 | 3AA1-063SOLA | 80/20 | 1.08 MW | 1.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 315608 | 3AA2-088SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 316087 | AB2-174 C | 80/20 | 2.96 MW | 2.96 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962561 | AG1-105 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 961681 | AG1-008 C | 80/20 | 7.46 MW | 7.46 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 962571 | AG1-106 C | 80/20 | 2.79 MW | 2.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.01 MW | 14.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.06 MW | 5.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.05 MW | 5.05 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.17 MW | 1.17 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.25 MW | 0.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.71 MW | 0.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 254 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 961791 | AG1-021 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 961891 | AG1-030 C | 80/20 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963171 | AG1-166 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963181 | AG1-167 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963191 | AG1-168 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963201 | AG1-169 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963211 | AG1-170 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963301 | AG1-179 C | 80/20 | 3.09 MW | 3.09 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963311 | AG1-180 | 80/20 | 1.51 MW | 1.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963321 | AG1-181 C O1 | 80/20 | 28.69 MW | 28.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963361 | AG1-185 O1 | 80/20 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964111 | AG1-272 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964121 | AG1-273 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964131 | AG1-274 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964241 | AG1-285 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964791 | AG1-342 C | 80/20 | 2.21 MW | 2.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965191 | AG1-384 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965591 | AG1-427 C | 80/20 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965601 | AG1-428 C O2 | 80/20 | 2.58 MW | 2.58 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965641 | AG1-432 C O1 | 80/20 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965721 | AG1-440 C | 80/20 | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965731 | AG1-441 C | 80/20 | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965831 | AG1-451 | 80/20 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 314429 | 3JTRSVLE | 80/20 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315159 | 1KERR 2 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315160 | 1KERR 3 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315161 | 1KERR 4 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315162 | 1KERR 5 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 936265 | AD2-033 C | 80/20 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 942461 | AE2-259 C O1 | 80/20 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 958801 | AF2-171 C | 80/20 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 959311 | AF2-222 C | 80/20 | 31.82 MW | 31.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315163 | 1KERR 6 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315164 | 1KERR 7 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316118 | AC1-105 C | 80/20 | 1.97 MW | 1.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316129 | AC1-054 C | 80/20 | 3.16 MW | 3.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316131 | AB2-060 C | 80/20 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924301 | AB2-077 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924311 | AB2-078 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924321 | AB2-079 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 925611 | AC1-036 C | 80/20 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 938371 | AE1-056 C | 80/20 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 939181 | AE1-148 C | 80/20 | 6.24 MW | 6.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 940661 | AE2-053 O1 | 80/20 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 946301 | AF1-294 C | 80/20 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 958211 | AF2-115 C | 80/20 | 6.19 MW | 6.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 962561 | AG1-105 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 313527 | AB2-043 C | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.01 MW | 1.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 46.07 MW | 46.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 46.07 MW | 46.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | 80/20 | 11.7 MW | 11.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | 80/20 | 29.34 MW | 29.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | 80/20 | 9.62 MW | 9.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | 80/20 | 26.93 MW | 26.93 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 46.07 MW | 46.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 46.07 MW | 46.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927251 | AC1-221 C | Adder | -2.9 MW | -2.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934341 | AD1-058 C | Adder | -7.26 MW | -6.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934991 | AD1-131 C | Adder | -2.38 MW | -2.02 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932761 | AC2-100 C | Adder | -6.67 MW | -5.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 961791 | AG1-021 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 961891 | AG1-030 C | 80/20 | 24.59 MW | 24.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963171 | AG1-166 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963181 | AG1-167 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963191 | AG1-168 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963201 | AG1-169 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963211 | AG1-170 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963301 | AG1-179 C | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963311 | AG1-180 | 80/20 | 1.17 MW | 1.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 21.16 MW | 21.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 10.24 MW | 10.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964111 | AG1-272 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964121 | AG1-273 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964131 | AG1-274 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 11.73 MW | 11.73 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.83 MW | 1.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965191 | AG1-384 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965591 | AG1-427 C | 80/20 | 11.24 MW | 11.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 48.39 MW | 48.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965721 | AG1-440 C | 80/20 | 3.18 MW | 3.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965731 | AG1-441 C | 80/20 | 3.18 MW | 3.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965771 | AG1-445 | 80/20 | 1.84 MW | 1.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965781 | AG1-446 | 80/20 | 1.84 MW | 1.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965831 | AG1-451 | 80/20 | 8.06 MW | 8.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.82 MW | 0.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 936265 | AD2-033 C | 80/20 | 15.99 MW | 15.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 24.2 MW | 24.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 958801 | AF2-171 C | 80/20 | 26.89 MW | 26.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 959311 | AF2-222 C | 80/20 | 23.37 MW | 23.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316118 | AC1-105 C | 80/20 | 1.78 MW | 1.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316129 | AC1-054 C | 80/20 | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.28 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 938371 | AE1-056 C | 80/20 | 12.73 MW | 12.73 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 939181 | AE1-148 C | 80/20 | 4.82 MW | 4.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.79 MW | 1.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 946301 | AF1-294 C | 80/20 | 7.39 MW | 7.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 958211 | AF2-115 C | 80/20 | 4.5 MW | 4.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 4.42 MW | 4.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.74 MW | 5.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.5 MW | 1.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.75 MW | 1.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.23 MW | 0.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | 80/20 | 11.7 MW | 11.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | 80/20 | 29.34 MW | 29.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | 80/20 | 9.62 MW | 9.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | 80/20 | 26.93 MW | 26.93 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| AC1-221 TAP-6PERSON230 T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 961791 | AG1-021 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 961891 | AG1-030 C | 80/20 | 19.62 MW | 19.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963171 | AG1-166 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963181 | AG1-167 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963191 | AG1-168 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963201 | AG1-169 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963211 | AG1-170 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 37.85 MW | 37.85 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 18.31 MW | 18.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 28.08 MW | 28.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 26.62 MW | 26.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 44.93 MW | 44.93 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 314429 | 3JTRSVLE | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 936265 | AD2-033 C | 80/20 | 11.64 MW | 11.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 22.46 MW | 22.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 33.7 MW | 33.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 37.44 MW | 37.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 316131 | AB2-060 C | 80/20 | 0.76 MW | 0.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924301 | AB2-077 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924311 | AB2-078 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924321 | AB2-079 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 0.55 MW | 0.55 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 14.53 MW | 14.53 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 939181 | AE1-148 C | 80/20 | 2.75 MW | 2.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 940661 | AE2-053 O1 | 80/20 | 1.02 MW | 1.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 946301 | AF1-294 C | 80/20 | 6.04 MW | 6.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 958211 | AF2-115 C | 80/20 | 3.68 MW | 3.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 313527 | AB2-043 C | 80/20 | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.26 MW | 3.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.98 MW | 0.98 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 21.26 MW | 21.26 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 27.28 MW | 27.28 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 2.86 MW | 2.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963301 | AG1-179 C | 80/20 | 3.81 MW | 3.81 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963311 | AG1-180 | 80/20 | 1.85 MW | 1.85 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 23.45 MW | 23.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 11.34 MW | 11.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 3.97 MW | 3.97 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 17.13 MW | 17.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 9.4 MW | 9.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 8.16 MW | 8.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966761 | AG1-547 C | 80/20 | 3.25 MW | 3.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 3.59 MW | 3.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 1.35 MW | 1.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 16.25 MW | 16.25 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965601 | AG1-428 C O2 | 80/20 | 3.18 MW | 3.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 29.38 MW | 29.38 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 5.46 MW | 5.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 3.15 MW | 3.15 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 247284 | 05LEESVG | 80/20 | 0.49 MW | 0.49 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.65 MW | 0.65 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 38.48 MW | 38.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 38.11 MW | 38.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.68 MW | 0.68 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926645 | AC1-145 C | 80/20 | 0.32 MW | 0.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927251 | AC1-221 C | Adder | -2.9 MW | -2.46 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 10.09 MW | 10.09 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934341 | AD1-058 C | Adder | -7.26 MW | -6.17 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 22.4 MW | 22.4 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 30.16 MW | 30.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934991 | AD1-131 C | Adder | -2.38 MW | -2.02 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 26.55 MW | 26.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 18.07 MW | 18.07 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 6.56 MW | 6.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 14.69 MW | 14.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942671 | AE2-283 C | 80/20 | 3.96 MW | 3.96 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 15.61 MW | 15.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 19.44 MW | 19.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 5.72 MW | 5.72 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 21.5 MW | 21.5 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 21.41 MW | 21.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 23.35 MW | 23.35 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 22.89 MW | 22.89 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 0.88 MW | 0.88 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961121 | AF2-403 | 80/20 | 0.8 MW | 0.8 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 3.29 MW | 3.29 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 14.67 MW | 14.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316129 | AC1-054 C | 80/20 | 4.01 MW | 4.01 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 2.11 MW | 2.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.34 MW | 0.34 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | 80/20 | 1.59 MW | 1.59 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932761 | AC2-100 C | Adder | -6.67 MW | -5.67 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 9.3 MW | 9.3 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 8.47 MW | 8.47 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 3.14 MW | 3.14 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 6.32 MW | 6.32 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 4.9 MW | 4.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941801 | AE2-185 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941821 | AE2-187 C | 80/20 | 3.6 MW | 3.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 9.45 MW | 9.45 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 5.86 MW | 5.86 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 2.41 MW | 2.41 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 153.55 MW | 153.55 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 3.69 MW | 3.69 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 7.12 MW | 7.12 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 0.13 MW | 0.13 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.43 MW | 0.43 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 0.56 MW | 0.56 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 3.57 MW | 3.57 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 4.62 MW | 4.62 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 0.11 MW | 0.11 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 18.9 MW | 18.9 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.73 MW | 0.73 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.03 MW | 2.03 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.6 MW | 1.6 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 5.33 MW | 5.33 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.36 MW | 2.36 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 1.44 MW | 1.44 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 1.7 MW | 1.7 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 1.48 MW | 1.48 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 5.21 MW | 5.21 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.52 MW | 0.52 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 3.22 MW | 3.22 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 4.61 MW | 4.61 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.75 MW | 0.75 MW |
| 6SEDGE HILL-AC1-221 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.39 MW | 1.39 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 154-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 69.52 MW | 69.52 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 33.63 MW | 33.63 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 62.24 MW | 62.24 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 58.68 MW | 58.68 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 19.89 MW | 19.89 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 3.31 MW | 3.31 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 9.95 MW | 9.95 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 40.21 MW | 40.21 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 62.22 MW | 62.22 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.95 MW | 0.95 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 14.29 MW | 14.29 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.12 MW | 0.12 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.41 MW | 0.41 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.34 MW | 0.34 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.51 MW | 0.51 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.44 MW | 2.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.44 MW | 2.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.29 MW | 9.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.76 MW | 25.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.72 MW | 14.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.2 MW | 0.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.2 MW | 43.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.39 MW | 12.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.51 MW | 42.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.69 MW | 5.69 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.28 MW | 9.28 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.56 MW | 11.56 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.18 MW | 8.18 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.76 MW | 18.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.2 MW | 8.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940481 | AE2-033 C | 80/20 | 63.95 MW | 63.95 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946011 | AF1-266 | 80/20 | 53.53 MW | 53.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314435 | 6SAPONY | 80/20 | 1.75 MW | 1.75 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.73 MW | 2.73 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940541 | AE2-040 | 80/20 | 11.72 MW | 11.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.85 MW | 7.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.8 MW | 18.8 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965281 | AG1-393 C | 80/20 | 8.96 MW | 8.96 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.87 MW | 1.87 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.11 MW | 40.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.23 MW | 13.23 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.7 MW | 13.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.88 MW | 1.88 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963361 | AG1-185 O1 | Adder | 5.53 MW | 4.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940481 | AE2-033 C | 80/20 | 63.96 MW | 63.96 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946011 | AF1-266 | 80/20 | 53.54 MW | 53.54 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.0 MW | 35.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.44 MW | 2.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.44 MW | 2.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.29 MW | 9.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.76 MW | 25.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.72 MW | 14.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.2 MW | 0.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.2 MW | 43.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.39 MW | 12.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.51 MW | 42.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.69 MW | 5.69 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.28 MW | 9.28 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.56 MW | 11.56 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.18 MW | 8.18 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.76 MW | 18.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.2 MW | 8.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940481 | AE2-033 C | 80/20 | 63.95 MW | 63.95 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946011 | AF1-266 | 80/20 | 53.53 MW | 53.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314435 | 6SAPONY | 80/20 | 1.75 MW | 1.75 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.73 MW | 2.73 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940541 | AE2-040 | 80/20 | 11.72 MW | 11.72 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.85 MW | 7.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.8 MW | 18.8 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965281 | AG1-393 C | 80/20 | 8.96 MW | 8.96 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.87 MW | 1.87 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.64 MW | 0.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.11 MW | 40.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.23 MW | 13.23 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.7 MW | 13.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.66 MW | 3.66 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.88 MW | 1.88 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.57 MW | 2.57 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963361 | AG1-185 O1 | Adder | 5.53 MW | 4.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940481 | AE2-033 C | 80/20 | 63.96 MW | 63.96 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946011 | AF1-266 | 80/20 | 53.54 MW | 53.54 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 35.0 MW | 35.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 22.04 MW | 22.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 13.16 MW | 13.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 3.17 MW | 3.17 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.99 MW | 2.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.46 MW | 1.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 20.09 MW | 20.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 9.72 MW | 9.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 12.04 MW | 12.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.79 MW | 2.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.72 MW | 1.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966811 | AG1-552 C | 80/20 | 0.65 MW | 0.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 3.21 MW | 3.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 2.04 MW | 2.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 11.5 MW | 11.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.5 MW | 2.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 40.65 MW | 40.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 4.13 MW | 4.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.78 MW | 6.78 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966361 | AG1-505 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966371 | AG1-506 C | 80/20 | 4.79 MW | 4.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.45 MW | 0.45 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313506 | AB1-173 C OP | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.72 MW | 0.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315126 | 1ROARAP2 | 80/20 | 0.44 MW | 0.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315128 | 1ROARAP4 | 80/20 | 0.42 MW | 0.42 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 8.13 MW | 8.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.31 MW | 1.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 2.01 MW | 2.01 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.72 MW | 4.72 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 14.84 MW | 14.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.66 MW | 0.66 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.64 MW | 4.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 15.26 MW | 15.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.38 MW | 1.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 20.33 MW | 20.33 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.3 MW | 3.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.1 MW | 4.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.06 MW | 1.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 23.7 MW | 23.7 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 21.63 MW | 21.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.24 MW | 4.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.84 MW | 0.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 1.29 MW | 1.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.71 MW | 0.71 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.73 MW | 0.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.48 MW | 3.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 923991 | AB2-040 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.67 MW | 1.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.85 MW | 1.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 11.04 MW | 11.04 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.83 MW | 5.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 2.16 MW | 2.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.41 MW | 2.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.5 MW | 0.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 6.25 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 3.54 MW | 3.54 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 26.24 MW | 26.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.97 MW | 3.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.14 MW | 1.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 19.98 MW | 19.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 25.83 MW | 25.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316087 | AB2-174 C | 80/20 | 0.39 MW | 0.39 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 6.26 MW | 6.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.41 MW | 0.41 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.56 MW | 1.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.3 MW | 0.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.16 MW | 26.16 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.56 MW | 2.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.84 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.15 MW | 0.15 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.59 MW | 0.59 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.26 MW | 1.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.07 MW | 0.07 MW |
| Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961891 | AG1-030 C | 80/20 | 8.19 MW | 8.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 963361 | AG1-185 O1 | 80/20 | 5.53 MW | 5.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964111 | AG1-272 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964121 | AG1-273 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964131 | AG1-274 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964791 | AG1-342 C | 80/20 | 2.24 MW | 2.24 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965191 | AG1-384 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 958801 | AF2-171 C | 80/20 | 7.4 MW | 7.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 959311 | AF2-222 C | 80/20 | 10.47 MW | 10.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940491 | AE2-034 C | 80/20 | 4.32 MW | 4.32 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957531 | AF2-047 C | 80/20 | 10.25 MW | 10.25 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962561 | AG1-105 C O1 | 80/20 | 5.23 MW | 5.23 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 246 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 961791 | AG1-021 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963171 | AG1-166 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963181 | AG1-167 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963191 | AG1-168 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963201 | AG1-169 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963211 | AG1-170 C | 80/20 | 0.81 MW | 0.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963321 | AG1-181 C O1 | 80/20 | 73.64 MW | 73.64 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 963361 | AG1-185 O1 | 80/20 | 35.63 MW | 35.63 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964111 | AG1-272 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964121 | AG1-273 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 964131 | AG1-274 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965191 | AG1-384 C | 80/20 | 10.72 MW | 10.72 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965591 | AG1-427 C | 80/20 | 60.96 MW | 60.96 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965641 | AG1-432 C O1 | 80/20 | 28.75 MW | 28.75 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 965831 | AG1-451 | 80/20 | 4.79 MW | 4.79 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 314429 | 3JTRSVLE | 80/20 | 0.18 MW | 0.18 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 942461 | AE2-259 C O1 | 80/20 | 14.38 MW | 14.38 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 958801 | AF2-171 C | 80/20 | 45.25 MW | 45.25 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 959311 | AF2-222 C | 80/20 | 66.71 MW | 66.71 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 925611 | AC1-036 C | 80/20 | 1.02 MW | 1.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 938371 | AE1-056 C | 80/20 | 16.65 MW | 16.65 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 946301 | AF1-294 C | 80/20 | 1.67 MW | 1.67 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | 958211 | AF2-115 C | 80/20 | 1.02 MW | 1.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.07 MW | 0.07 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.02 MW | 0.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.13 MW | 0.13 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.06 MW | 0.06 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.06 MW | 0.06 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.15 MW | 0.15 MW |
| Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961671 | AG1-007 C | 80/20 | 1.04 MW | 1.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961891 | AG1-030 C | 80/20 | 8.19 MW | 8.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961941 | AG1-037 C | 80/20 | 0.61 MW | 0.61 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962331 | AG1-082 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962341 | AG1-083 C | 80/20 | 2.45 MW | 2.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963301 | AG1-179 C | 80/20 | 10.85 MW | 10.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963311 | AG1-180 | 80/20 | 5.29 MW | 5.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963321 | AG1-181 C O1 | 80/20 | 11.44 MW | 11.44 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 963361 | AG1-185 O1 | 80/20 | 5.53 MW | 5.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964111 | AG1-272 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964121 | AG1-273 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964131 | AG1-274 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964241 | AG1-285 C O1 | 80/20 | 9.85 MW | 9.85 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964791 | AG1-342 C | 80/20 | 2.24 MW | 2.24 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 964801 | AG1-343 C | 80/20 | 6.12 MW | 6.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966801 | AG1-551 C | 80/20 | 2.21 MW | 2.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966811 | AG1-552 C | 80/20 | 3.49 MW | 3.49 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965191 | AG1-384 C | 80/20 | 1.67 MW | 1.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965291 | AG1-394 C | 80/20 | 2.07 MW | 2.07 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965591 | AG1-427 C | 80/20 | 9.3 MW | 9.3 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965601 | AG1-428 C O2 | 80/20 | 9.06 MW | 9.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965691 | AG1-437 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965701 | AG1-438 C O1 | 80/20 | 10.0 MW | 10.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965711 | AG1-439 C O1 | 80/20 | 25.77 MW | 25.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965721 | AG1-440 C | 80/20 | 7.84 MW | 7.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965731 | AG1-441 C | 80/20 | 7.84 MW | 7.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965741 | AG1-442 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965751 | AG1-443 O1 | 80/20 | 5.83 MW | 5.83 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965761 | AG1-444 O1 | 80/20 | 13.74 MW | 13.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965771 | AG1-445 | 80/20 | 4.53 MW | 4.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 965781 | AG1-446 | 80/20 | 4.53 MW | 4.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 966621 | AG1-532 C | 80/20 | 3.51 MW | 3.51 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313506 | AB1-173 C OP | 80/20 | 14.73 MW | 14.73 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313719 | 3CHESTNUT | 80/20 | 1.53 MW | 1.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314572 | 3EMPORIA | 80/20 | 1.03 MW | 1.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314582 | 3KELFORD | 80/20 | 0.49 MW | 0.49 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314623 | 3WITAKRS | 80/20 | 0.27 MW | 0.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314704 | 3LAWRENC | 80/20 | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315126 | 1ROARAP2 | 80/20 | 2.37 MW | 2.37 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315128 | 1ROARAP4 | 80/20 | 2.26 MW | 2.26 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315131 | 1EDGECMA | 80/20 | 8.99 MW | 8.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315132 | 1EDGECMB | 80/20 | 8.99 MW | 8.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.29 MW | 4.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.66 MW | 2.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.01 MW | 2.01 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315139 | 1GASTONA | 80/20 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 920591 | AA2-165 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926070 | AC1-086 C | 80/20 | 43.21 MW | 43.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926201 | AC1-098 C | 80/20 | 8.11 MW | 8.11 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 926211 | AC1-099 C | 80/20 | 2.72 MW | 2.72 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927024 | AC1-189 C | 80/20 | 9.03 MW | 9.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 927145 | AC1-208 C | 80/20 | 12.4 MW | 12.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934331 | AD1-057 C O1 | 80/20 | 15.41 MW | 15.41 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 934521 | AD1-076 C | 80/20 | 42.53 MW | 42.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 936265 | AD2-033 C | 80/20 | 8.94 MW | 8.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 943171 | AE2-346 C | 80/20 | 1.71 MW | 1.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 944141 | AF1-082 | 80/20 | 3.21 MW | 3.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 958801 | AF2-171 C | 80/20 | 7.4 MW | 7.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 959311 | AF2-222 C | 80/20 | 10.47 MW | 10.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960081 | AF2-299 C | 80/20 | 6.5 MW | 6.5 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315293 | 1DOMTR9 | 80/20 | 5.7 MW | 5.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315294 | 1DOMTR10 | 80/20 | 6.98 MW | 6.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315601 | 1CONETOE2SOL | 80/20 | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 2.47 MW | 2.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316020 | AB2-059 C OP | 80/20 | 2.0 MW | 2.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316129 | AC1-054 C | 80/20 | 9.29 MW | 9.29 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316131 | AB2-060 C | 80/20 | 1.27 MW | 1.27 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316140 | AB2-099 C | 80/20 | 0.71 MW | 0.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 922922 | AB1-081 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.34 MW | 29.34 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 923991 | AB2-040 C O1 | 80/20 | 16.04 MW | 16.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.66 MW | 1.66 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925121 | AB2-169 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925591 | AC1-034 C | 80/20 | 7.62 MW | 7.62 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 925611 | AC1-036 C | 80/20 | 0.16 MW | 0.16 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 932631 | AC2-084 C | 80/20 | 11.57 MW | 11.57 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 939181 | AE1-148 C | 80/20 | 8.19 MW | 8.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940491 | AE2-034 C | 80/20 | 4.32 MW | 4.32 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940571 | AE2-044 C | 80/20 | 4.99 MW | 4.99 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 940661 | AE2-053 O1 | 80/20 | 3.03 MW | 3.03 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 946281 | AF1-292 C | 80/20 | 3.86 MW | 3.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957521 | AF2-046 C | 80/20 | 18.77 MW | 18.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957531 | AF2-047 C | 80/20 | 10.25 MW | 10.25 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 957861 | AF2-080 C | 80/20 | 8.21 MW | 8.21 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 314589 | 3MURPHYS | 80/20 | 0.1 MW | 0.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315115 | 1S HAMPT1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315141 | 1GASTONB | 80/20 | 6.55 MW | 6.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315292 | 1DOMTR78 | 80/20 | 1.19 MW | 1.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 2.04 MW | 2.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 1.06 MW | 1.06 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316087 | AB2-174 C | 80/20 | 2.74 MW | 2.74 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316096 | AB2-100 C1 | 80/20 | 3.05 MW | 3.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 316098 | AB2-100 C2 | 80/20 | 3.05 MW | 3.05 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 938221 | AE1-035 C | 80/20 | 0.47 MW | 0.47 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 933981 | AD1-022 C | 80/20 | 7.86 MW | 7.86 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 960331 | AF2-324 C | 80/20 | 8.77 MW | 8.77 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.23 MW | 5.23 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 961681 | AG1-008 C | 80/20 | 18.81 MW | 18.81 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 962571 | AG1-106 C | 80/20 | 12.02 MW | 12.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 1.88 MW | 1.88 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 315614 | AA2-178 C | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | 313527 | AB2-043 C | 80/20 | 0.45 MW | 0.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.42 MW | 2.42 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 40.18 MW | 40.18 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 13.33 MW | 13.33 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.76 MW | 13.76 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.67 MW | 3.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.22 MW | 3.22 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.65 MW | 0.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.89 MW | 1.89 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.58 MW | 2.58 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o 314575 6NUCO TP 230 314537 6SUFFOLK 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.32 MW | 0.32 MW |
| Details for 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961791 | AG1-021 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 961891 | AG1-030 C | 80/20 | 7.79 MW | 7.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963171 | AG1-166 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963181 | AG1-167 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963191 | AG1-168 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963201 | AG1-169 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963211 | AG1-170 C | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963301 | AG1-179 C | 80/20 | 14.09 MW | 14.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963311 | AG1-180 | 80/20 | 6.87 MW | 6.87 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.71 MW | 10.71 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.18 MW | 5.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.14 MW | 9.14 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.9 MW | 1.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 964801 | AG1-343 C | 80/20 | 1.86 MW | 1.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 966811 | AG1-552 C | 80/20 | 1.38 MW | 1.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.57 MW | 1.57 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965291 | AG1-394 C | 80/20 | 0.66 MW | 0.66 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.63 MW | 8.63 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 11.77 MW | 11.77 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965721 | AG1-440 C | 80/20 | 4.51 MW | 4.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965731 | AG1-441 C | 80/20 | 4.51 MW | 4.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965771 | AG1-445 | 80/20 | 2.61 MW | 2.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 965781 | AG1-446 | 80/20 | 2.61 MW | 2.61 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 966621 | AG1-532 C | 80/20 | 4.82 MW | 4.82 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 15.41 MW | 15.41 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.21 MW | 0.21 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314572 | 3EMPORIA | 80/20 | 1.33 MW | 1.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.86 MW | 0.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 0.94 MW | 0.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 0.9 MW | 0.9 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.25 MW | 0.25 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 927145 | AC1-208 C | 80/20 | 3.01 MW | 3.01 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.36 MW | 8.36 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 958801 | AF2-171 C | 80/20 | 7.1 MW | 7.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 959311 | AF2-222 C | 80/20 | 9.86 MW | 9.86 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 960081 | AF2-299 C | 80/20 | 8.92 MW | 8.92 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.7 MW | 0.7 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315266 | 1PLYWOOD A | 80/20 | 0.4 MW | 0.4 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 0.88 MW | 0.88 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316118 | AC1-105 C | 80/20 | 1.94 MW | 1.94 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316129 | AC1-054 C | 80/20 | 4.6 MW | 4.6 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 16.79 MW | 16.79 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.51 MW | 1.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 938371 | AE1-056 C | 80/20 | 2.72 MW | 2.72 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 939181 | AE1-148 C | 80/20 | 5.65 MW | 5.65 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.09 MW | 2.09 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 946281 | AF1-292 C | 80/20 | 5.29 MW | 5.29 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 946301 | AF1-294 C | 80/20 | 1.93 MW | 1.93 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 958211 | AF2-115 C | 80/20 | 1.18 MW | 1.18 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 0.76 MW | 0.76 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.34 MW | 0.34 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 316087 | AB2-174 C | 80/20 | 3.13 MW | 3.13 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 4.53 MW | 4.53 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.32 MW | 0.32 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.1 MW | 0.1 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.38 MW | 2.38 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.26 MW | 2.26 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.51 MW | 0.51 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.12 MW | 0.12 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.33 MW | 0.33 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.42 MW | 0.42 MW |
| 3CLUBHSE-6CLUBHSE 115.0/230.0 kV Ckt 1 transformer l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.06 MW | 0.06 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 69.52 MW | 69.52 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 33.63 MW | 33.63 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 10.05 MW | 10.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 58.68 MW | 58.68 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 19.89 MW | 19.89 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 3.31 MW | 3.31 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 9.95 MW | 9.95 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 40.21 MW | 40.21 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 62.22 MW | 62.22 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | Adder | -1.19 MW | -1.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.95 MW | 0.95 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 14.29 MW | 14.29 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.12 MW | 0.12 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.41 MW | 0.41 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.19 MW | 0.19 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.06 MW | 0.06 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.34 MW | 0.34 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.51 MW | 0.51 MW |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961791 | AG1-021 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961891 | AG1-030 C | 80/20 | 9.77 MW | 9.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 962491 | AG1-098 C O1 | 80/20 | 6.05 MW | 6.05 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963171 | AG1-166 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963181 | AG1-167 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963191 | AG1-168 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963201 | AG1-169 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963211 | AG1-170 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963321 | AG1-181 C O1 | 80/20 | 9.04 MW | 9.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963361 | AG1-185 O1 | 80/20 | 4.37 MW | 4.37 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964111 | AG1-272 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964121 | AG1-273 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964131 | AG1-274 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964241 | AG1-285 C O1 | 80/20 | 5.52 MW | 5.52 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964791 | AG1-342 C | 80/20 | 1.28 MW | 1.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965191 | AG1-384 C | 80/20 | 1.44 MW | 1.44 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965591 | AG1-427 C | 80/20 | 5.27 MW | 5.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965641 | AG1-432 C O1 | 80/20 | 17.69 MW | 17.69 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965831 | AG1-451 | 80/20 | 2.95 MW | 2.95 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314429 | 3JTRSVLE | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315153 | 1CLOVER1 | 80/20 | 4.15 MW | 4.15 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315154 | 1CLOVER2 | 80/20 | 4.11 MW | 4.11 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934615 | AD1-087 C | 80/20 | 2.4 MW | 2.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 934625 | AD1-088 C | 80/20 | 6.81 MW | 6.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 936265 | AD2-033 C | 80/20 | 6.87 MW | 6.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 937481 | AD2-202 C O1 | 80/20 | 0.7 MW | 0.7 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 942461 | AE2-259 C O1 | 80/20 | 8.85 MW | 8.85 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958801 | AF2-171 C | 80/20 | 10.46 MW | 10.46 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 959311 | AF2-222 C | 80/20 | 9.67 MW | 9.67 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 316131 | AB2-060 C | 80/20 | 0.63 MW | 0.63 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924301 | AB2-077 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924311 | AB2-078 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 924321 | AB2-079 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 925611 | AC1-036 C | 80/20 | 0.14 MW | 0.14 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938371 | AE1-056 C | 80/20 | 4.85 MW | 4.85 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 939181 | AE1-148 C | 80/20 | 2.81 MW | 2.81 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940661 | AE2-053 O1 | 80/20 | 1.04 MW | 1.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941791 | AE2-182 C | 80/20 | 1.11 MW | 1.11 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 946301 | AF1-294 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958211 | AF2-115 C | 80/20 | 1.75 MW | 1.75 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 933501 | AC2-165 C | 80/20 | 9.02 MW | 9.02 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314333 | 6POWHATN | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 314677 | 6BUCKING | 80/20 | 0.49 MW | 0.49 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958501 | AF2-144 C | 80/20 | 1.4 MW | 1.4 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315191 | 1BEARGRDN G1 | 80/20 | 8.45 MW | 8.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315192 | 1BEARGRDN G2 | 80/20 | 8.45 MW | 8.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 315193 | 1BEARGRDN S1 | 80/20 | 10.93 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 938561 | AE1-075 C | 80/20 | 0.28 MW | 0.28 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 957911 | AF2-085 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 962561 | AG1-105 C O1 | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 313527 | AB2-043 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.79 MW | 0.79 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.27 MW | 0.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.2 MW | 1.2 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.19 MW | 0.19 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.08 MW | 0.08 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.56 MW | 0.56 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| Details for AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 4.73 MW | 4.73 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 37.04 MW | 37.04 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 28.55 MW | 28.55 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 23.89 MW | 23.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961891 | AG1-030 C | 80/20 | 4.74 MW | 4.74 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934331 | AD1-057 C O1 | 80/20 | 37.04 MW | 37.04 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 28.55 MW | 28.55 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 23.89 MW | 23.89 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| AD1-057 TAP-6HATHAWAY 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 961791 | AG1-021 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 961891 | AG1-030 C | 80/20 | 12.04 MW | 12.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963171 | AG1-166 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963181 | AG1-167 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963191 | AG1-168 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963201 | AG1-169 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963211 | AG1-170 C | 80/20 | 1.42 MW | 1.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963301 | AG1-179 C | 80/20 | 3.76 MW | 3.76 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963311 | AG1-180 | 80/20 | 1.83 MW | 1.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963321 | AG1-181 C O1 | 80/20 | 17.29 MW | 17.29 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 963361 | AG1-185 O1 | 80/20 | 8.37 MW | 8.37 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964111 | AG1-272 C | 80/20 | 2.52 MW | 2.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964121 | AG1-273 C | 80/20 | 2.52 MW | 2.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964131 | AG1-274 C | 80/20 | 2.52 MW | 2.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964241 | AG1-285 C O1 | 80/20 | 15.15 MW | 15.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 964791 | AG1-342 C | 80/20 | 10.69 MW | 10.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 966691 | AG1-539 C | 80/20 | 10.08 MW | 10.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 966761 | AG1-547 C | 80/20 | 4.43 MW | 4.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965191 | AG1-384 C | 80/20 | 2.52 MW | 2.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965591 | AG1-427 C | 80/20 | 14.29 MW | 14.29 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965601 | AG1-428 C O2 | 80/20 | 3.14 MW | 3.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965641 | AG1-432 C O1 | 80/20 | 6.93 MW | 6.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965721 | AG1-440 C | 80/20 | 6.18 MW | 6.18 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965731 | AG1-441 C | 80/20 | 6.18 MW | 6.18 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965771 | AG1-445 | 80/20 | 3.57 MW | 3.57 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965781 | AG1-446 | 80/20 | 3.57 MW | 3.57 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 965831 | AG1-451 | 80/20 | 1.16 MW | 1.16 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246843 | 05SMG1 | 80/20 | 0.62 MW | 0.62 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246844 | 05SMG2 | 80/20 | 1.7 MW | 1.7 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246845 | 05SMG3 | 80/20 | 1.06 MW | 1.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246846 | 05SMG4 | 80/20 | 1.67 MW | 1.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 246847 | 05SMG5 | 80/20 | 0.65 MW | 0.65 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 247284 | 05LEESVG | 80/20 | 0.79 MW | 0.79 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 314429 | 3JTRSVLE | 80/20 | 0.32 MW | 0.32 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315156 | 1HALLBR1 | 80/20 | 1.46 MW | 1.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315159 | 1KERR 2 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315160 | 1KERR 3 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315161 | 1KERR 4 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315162 | 1KERR 5 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 926023 | AC1-080 C | 80/20 | 0.83 MW | 0.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 926645 | AC1-145 C | 80/20 | 0.44 MW | 0.44 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 927261 | AC1-222 C | 80/20 | 12.12 MW | 12.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 934311 | AD1-055 C | 80/20 | 8.42 MW | 8.42 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 935171 | AD1-152 C O1 | Adder | -4.33 MW | -3.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 936265 | AD2-033 C | 80/20 | 13.55 MW | 13.55 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 942461 | AE2-259 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 942671 | AE2-283 C | 80/20 | 5.39 MW | 5.39 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 942751 | AE2-291 C | 80/20 | 19.28 MW | 19.28 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 942761 | AE2-292 C O1 | 80/20 | 24.0 MW | 24.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 943901 | AF1-058 C | 80/20 | 6.86 MW | 6.86 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 958801 | AF2-171 C | 80/20 | 10.69 MW | 10.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 959311 | AF2-222 C | 80/20 | 15.68 MW | 15.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 960061 | AF2-297 C | 80/20 | 27.43 MW | 27.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 961121 | AF2-403 | 80/20 | 1.09 MW | 1.09 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315163 | 1KERR 6 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315164 | 1KERR 7 | 80/20 | 1.12 MW | 1.12 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 315266 | 1PLYWOOD A | 80/20 | 3.89 MW | 3.89 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 316118 | AC1-105 C | 80/20 | 17.19 MW | 17.19 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 316129 | AC1-054 C | 80/20 | 4.67 MW | 4.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 316131 | AB2-060 C | 80/20 | 1.97 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 924301 | AB2-077 C O1 | 80/20 | 2.68 MW | 2.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 924311 | AB2-078 C O1 | 80/20 | 2.68 MW | 2.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 924321 | AB2-079 C O1 | 80/20 | 2.68 MW | 2.68 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 925611 | AC1-036 C | 80/20 | 0.24 MW | 0.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 925661 | AC1-042 C | 80/20 | 2.17 MW | 2.17 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 938371 | AE1-056 C | 80/20 | 3.95 MW | 3.95 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 939181 | AE1-148 C | 80/20 | 9.08 MW | 9.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 940661 | AE2-053 O1 | 80/20 | 3.36 MW | 3.36 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 941801 | AE2-185 C | 80/20 | 4.9 MW | 4.9 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 941821 | AE2-187 C | 80/20 | 4.9 MW | 4.9 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 946301 | AF1-294 C | 80/20 | 2.9 MW | 2.9 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 958211 | AF2-115 C | 80/20 | 1.77 MW | 1.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 962561 | AG1-105 C O1 | 80/20 | 21.13 MW | 21.13 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 313527 | AB2-043 C | 80/20 | 0.7 MW | 0.7 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | 316123 | AC1-075 C | 80/20 | 2.48 MW | 2.48 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.16 MW | 1.16 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.43 MW | 0.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.08 MW | 0.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961791 | AG1-021 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961891 | AG1-030 C | 80/20 | 5.6 MW | 5.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962331 | AG1-082 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962341 | AG1-083 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963171 | AG1-166 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963181 | AG1-167 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963191 | AG1-168 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963201 | AG1-169 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963211 | AG1-170 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963301 | AG1-179 C | 80/20 | 2.95 MW | 2.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963311 | AG1-180 | 80/20 | 1.44 MW | 1.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963321 | AG1-181 C O1 | 80/20 | 7.68 MW | 7.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963361 | AG1-185 O1 | 80/20 | 3.72 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964111 | AG1-272 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964121 | AG1-273 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964131 | AG1-274 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964241 | AG1-285 C O1 | 80/20 | 6.55 MW | 6.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964791 | AG1-342 C | 80/20 | 1.42 MW | 1.42 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964801 | AG1-343 C | 80/20 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 966811 | AG1-552 C | 80/20 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965191 | AG1-384 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965291 | AG1-394 C | 80/20 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965591 | AG1-427 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965601 | AG1-428 C O2 | 80/20 | 2.46 MW | 2.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965721 | AG1-440 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965731 | AG1-441 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965771 | AG1-445 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965781 | AG1-446 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 966621 | AG1-532 C | 80/20 | 0.69 MW | 0.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313506 | AB1-173 C OP | 80/20 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313719 | 3CHESTNUT | 80/20 | 0.72 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314429 | 3JTRSVLE | 80/20 | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314572 | 3EMPORIA | 80/20 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314582 | 3KELFORD | 80/20 | 0.22 MW | 0.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315126 | 1ROARAP2 | 80/20 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315128 | 1ROARAP4 | 80/20 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315158 | 1KERR 1 | 80/20 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315159 | 1KERR 2 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315160 | 1KERR 3 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315161 | 1KERR 4 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315162 | 1KERR 5 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 926201 | AC1-098 C | 80/20 | 5.16 MW | 5.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 926211 | AC1-099 C | 80/20 | 1.73 MW | 1.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 927145 | AC1-208 C | 80/20 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 936265 | AD2-033 C | 80/20 | 6.0 MW | 6.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 943171 | AE2-346 C | 80/20 | 0.9 MW | 0.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 958801 | AF2-171 C | 80/20 | 5.11 MW | 5.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 959311 | AF2-222 C | 80/20 | 7.08 MW | 7.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 960081 | AF2-299 C | 80/20 | 1.27 MW | 1.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315163 | 1KERR 6 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315164 | 1KERR 7 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315606 | 3AA2-053SOLA | 80/20 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316129 | AC1-054 C | 80/20 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316131 | AB2-060 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316140 | AB2-099 C | 80/20 | 0.38 MW | 0.38 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 923991 | AB2-040 C O1 | 80/20 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924301 | AB2-077 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924311 | AB2-078 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924321 | AB2-079 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 925611 | AC1-036 C | 80/20 | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 932631 | AC2-084 C | 80/20 | 7.36 MW | 7.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 938371 | AE1-056 C | 80/20 | 1.96 MW | 1.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 939181 | AE1-148 C | 80/20 | 7.6 MW | 7.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 940661 | AE2-053 O1 | 80/20 | 2.81 MW | 2.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 946281 | AF1-292 C | 80/20 | 0.75 MW | 0.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 946301 | AF1-294 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 957521 | AF2-046 C | 80/20 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 958211 | AF2-115 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314589 | 3MURPHYS | 80/20 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315607 | 3AA1-063SOLA | 80/20 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315608 | 3AA2-088SOLA | 80/20 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316087 | AB2-174 C | 80/20 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962561 | AG1-105 C O1 | 80/20 | 3.36 MW | 3.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961681 | AG1-008 C | 80/20 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 961791 | AG1-021 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 961891 | AG1-030 C | 80/20 | 5.6 MW | 5.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 962331 | AG1-082 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 962341 | AG1-083 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963171 | AG1-166 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963181 | AG1-167 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963191 | AG1-168 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963201 | AG1-169 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963211 | AG1-170 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963301 | AG1-179 C | 80/20 | 2.95 MW | 2.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963311 | AG1-180 | 80/20 | 1.44 MW | 1.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963321 | AG1-181 C O1 | 80/20 | 7.68 MW | 7.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 963361 | AG1-185 O1 | 80/20 | 3.72 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964111 | AG1-272 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964121 | AG1-273 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964131 | AG1-274 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964241 | AG1-285 C O1 | 80/20 | 6.55 MW | 6.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964791 | AG1-342 C | 80/20 | 1.42 MW | 1.42 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 964801 | AG1-343 C | 80/20 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 966811 | AG1-552 C | 80/20 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965191 | AG1-384 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965291 | AG1-394 C | 80/20 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965591 | AG1-427 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965601 | AG1-428 C O2 | 80/20 | 2.46 MW | 2.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965721 | AG1-440 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965731 | AG1-441 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965771 | AG1-445 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 965781 | AG1-446 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 966621 | AG1-532 C | 80/20 | 0.69 MW | 0.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 313506 | AB1-173 C OP | 80/20 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 313719 | 3CHESTNUT | 80/20 | 0.72 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314429 | 3JTRSVLE | 80/20 | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314572 | 3EMPORIA | 80/20 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314582 | 3KELFORD | 80/20 | 0.22 MW | 0.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315126 | 1ROARAP2 | 80/20 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315128 | 1ROARAP4 | 80/20 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315158 | 1KERR 1 | 80/20 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315159 | 1KERR 2 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315160 | 1KERR 3 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315161 | 1KERR 4 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315162 | 1KERR 5 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 926201 | AC1-098 C | 80/20 | 5.16 MW | 5.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 926211 | AC1-099 C | 80/20 | 1.73 MW | 1.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 927145 | AC1-208 C | 80/20 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 936265 | AD2-033 C | 80/20 | 6.0 MW | 6.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 943171 | AE2-346 C | 80/20 | 0.9 MW | 0.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 958801 | AF2-171 C | 80/20 | 5.11 MW | 5.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 959311 | AF2-222 C | 80/20 | 7.08 MW | 7.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 960081 | AF2-299 C | 80/20 | 1.27 MW | 1.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315163 | 1KERR 6 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315164 | 1KERR 7 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315606 | 3AA2-053SOLA | 80/20 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 316129 | AC1-054 C | 80/20 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 316131 | AB2-060 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 316140 | AB2-099 C | 80/20 | 0.38 MW | 0.38 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 923991 | AB2-040 C O1 | 80/20 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 924301 | AB2-077 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 924311 | AB2-078 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 924321 | AB2-079 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 925611 | AC1-036 C | 80/20 | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 932631 | AC2-084 C | 80/20 | 7.36 MW | 7.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 938371 | AE1-056 C | 80/20 | 1.96 MW | 1.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 939181 | AE1-148 C | 80/20 | 7.6 MW | 7.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 940661 | AE2-053 O1 | 80/20 | 2.81 MW | 2.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 946281 | AF1-292 C | 80/20 | 0.75 MW | 0.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 946301 | AF1-294 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 957521 | AF2-046 C | 80/20 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 958211 | AF2-115 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 314589 | 3MURPHYS | 80/20 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315607 | 3AA1-063SOLA | 80/20 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 315608 | 3AA2-088SOLA | 80/20 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 316087 | AB2-174 C | 80/20 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 962561 | AG1-105 C O1 | 80/20 | 3.36 MW | 3.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 961681 | AG1-008 C | 80/20 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 93 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 69.76 MW | 69.76 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 33.75 MW | 33.75 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 58.81 MW | 58.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 20.45 MW | 20.45 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 3.41 MW | 3.41 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 10.22 MW | 10.22 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 40.52 MW | 40.52 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 62.48 MW | 62.48 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.96 MW | 0.96 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 14.43 MW | 14.43 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.1 MW | 0.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.13 MW | 0.13 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.15 MW | 0.15 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.29 MW | 0.29 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.41 MW | 0.41 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 69.76 MW | 69.76 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 33.75 MW | 33.75 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 10.09 MW | 10.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 58.81 MW | 58.81 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 20.45 MW | 20.45 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 3.41 MW | 3.41 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 10.22 MW | 10.22 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 40.52 MW | 40.52 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 62.48 MW | 62.48 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | Adder | -1.17 MW | -1.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.96 MW | 0.96 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 14.43 MW | 14.43 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.1 MW | 0.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.45 MW | 0.45 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.13 MW | 0.13 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.11 MW | 0.11 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.11 MW | 0.11 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.37 MW | 0.37 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.15 MW | 0.15 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.29 MW | 0.29 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.04 MW | 0.04 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o 313868 6CARTERV 230 933500 AC2-165 TAP 230 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.41 MW | 0.41 MW |
| Details for 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3MADSONV-3PAMPLIN 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.84 MW | 0.84 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.46 MW | 0.46 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.82 MW | 1.82 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.82 MW | 1.82 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 10.29 MW | 10.29 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 5.02 MW | 5.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.55 MW | 10.55 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.11 MW | 5.11 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.09 MW | 9.09 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 5.27 MW | 5.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.62 MW | 1.62 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 3.12 MW | 3.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.81 MW | 1.81 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.58 MW | 8.58 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 8.6 MW | 8.6 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.77 MW | 6.77 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.77 MW | 6.77 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 20.5 MW | 20.5 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 7.07 MW | 7.07 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 7.07 MW | 7.07 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.95 MW | 3.95 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.95 MW | 3.95 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.93 MW | 10.93 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 4.09 MW | 4.09 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 4.09 MW | 4.09 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 3.35 MW | 3.35 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 13.76 MW | 13.76 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.3 MW | 1.3 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.98 MW | 0.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.62 MW | 0.62 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 2.12 MW | 2.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 2.02 MW | 2.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.64 MW | 7.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.64 MW | 7.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 3.87 MW | 3.87 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.4 MW | 2.4 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.81 MW | 1.81 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 5.94 MW | 5.94 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 39.19 MW | 39.19 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.67 MW | 6.67 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.24 MW | 2.24 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 7.01 MW | 7.01 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 10.58 MW | 10.58 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 13.64 MW | 13.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.24 MW | 8.24 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.27 MW | 1.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.73 MW | 2.73 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 6.2 MW | 6.2 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.23 MW | 1.23 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.15 MW | 2.15 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 8.34 MW | 8.34 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.53 MW | 0.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.44 MW | 1.44 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 26.61 MW | 26.61 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 14.98 MW | 14.98 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.71 MW | 0.71 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.47 MW | 6.47 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.51 MW | 9.51 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.43 MW | 7.43 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 4.24 MW | 4.24 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 3.68 MW | 3.68 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 15.09 MW | 15.09 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.37 MW | 6.37 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 80/20 | 63.14 MW | 63.14 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 | 80/20 | 52.85 MW | 52.85 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314435 | 6SAPONY | 80/20 | 1.74 MW | 1.74 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.96 MW | 0.96 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 5.94 MW | 5.94 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.81 MW | 1.81 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.93 MW | 0.93 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 2.57 MW | 2.57 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 2.94 MW | 2.94 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 2.94 MW | 2.94 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.31 MW | 0.31 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 940541 | AE2-040 | 80/20 | 11.6 MW | 11.6 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.39 MW | 5.39 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.46 MW | 7.46 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 15.12 MW | 15.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 10.9 MW | 10.9 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 965281 | AG1-393 C | 80/20 | 8.87 MW | 8.87 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.24 MW | 1.24 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.99 MW | 1.99 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.12 MW | 33.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.81 MW | 10.81 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.27 MW | 11.27 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.02 MW | 3.02 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.64 MW | 2.64 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.54 MW | 1.54 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.34 MW | 0.34 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.12 MW | 2.12 MW |
| 6SAPONY-6CARSON 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
| Details for AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 7.33 MW | 7.33 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 7.33 MW | 7.33 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 961791 | AG1-021 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 961891 | AG1-030 C | 80/20 | 12.01 MW | 12.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963171 | AG1-166 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963181 | AG1-167 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963191 | AG1-168 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963201 | AG1-169 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963211 | AG1-170 C | 80/20 | 1.41 MW | 1.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963301 | AG1-179 C | 80/20 | 3.75 MW | 3.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963311 | AG1-180 | 80/20 | 1.83 MW | 1.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963321 | AG1-181 C O1 | 80/20 | 17.24 MW | 17.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 963361 | AG1-185 O1 | 80/20 | 8.34 MW | 8.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964111 | AG1-272 C | 80/20 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964121 | AG1-273 C | 80/20 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964131 | AG1-274 C | 80/20 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964241 | AG1-285 C O1 | 80/20 | 15.1 MW | 15.1 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 964791 | AG1-342 C | 80/20 | 10.66 MW | 10.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 966691 | AG1-539 C | 80/20 | 10.05 MW | 10.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 966761 | AG1-547 C | 80/20 | 4.41 MW | 4.41 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965191 | AG1-384 C | 80/20 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965591 | AG1-427 C | 80/20 | 14.24 MW | 14.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965601 | AG1-428 C O2 | 80/20 | 3.13 MW | 3.13 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965641 | AG1-432 C O1 | 80/20 | 6.91 MW | 6.91 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965721 | AG1-440 C | 80/20 | 6.17 MW | 6.17 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965731 | AG1-441 C | 80/20 | 6.17 MW | 6.17 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965771 | AG1-445 | 80/20 | 3.56 MW | 3.56 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965781 | AG1-446 | 80/20 | 3.56 MW | 3.56 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 965831 | AG1-451 | 80/20 | 1.15 MW | 1.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246843 | 05SMG1 | 80/20 | 0.62 MW | 0.62 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246844 | 05SMG2 | 80/20 | 1.69 MW | 1.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246845 | 05SMG3 | 80/20 | 1.06 MW | 1.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246846 | 05SMG4 | 80/20 | 1.67 MW | 1.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 246847 | 05SMG5 | 80/20 | 0.65 MW | 0.65 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 247284 | 05LEESVG | 80/20 | 0.78 MW | 0.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 314429 | 3JTRSVLE | 80/20 | 0.32 MW | 0.32 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315156 | 1HALLBR1 | 80/20 | 1.46 MW | 1.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315158 | 1KERR 1 | 80/20 | 0.4 MW | 0.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315159 | 1KERR 2 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315160 | 1KERR 3 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315161 | 1KERR 4 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315162 | 1KERR 5 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 926023 | AC1-080 C | 80/20 | 0.83 MW | 0.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 926645 | AC1-145 C | 80/20 | 0.44 MW | 0.44 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 927261 | AC1-222 C | 80/20 | 12.09 MW | 12.09 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 934311 | AD1-055 C | 80/20 | 8.39 MW | 8.39 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 935171 | AD1-152 C O1 | Adder | -4.31 MW | -3.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 936265 | AD2-033 C | 80/20 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 942461 | AE2-259 C O1 | 80/20 | 3.45 MW | 3.45 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 942671 | AE2-283 C | 80/20 | 5.37 MW | 5.37 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 942751 | AE2-291 C | 80/20 | 19.22 MW | 19.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 942761 | AE2-292 C O1 | 80/20 | 23.93 MW | 23.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 943901 | AF1-058 C | 80/20 | 6.84 MW | 6.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 958801 | AF2-171 C | 80/20 | 10.66 MW | 10.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 959311 | AF2-222 C | 80/20 | 15.64 MW | 15.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 960061 | AF2-297 C | 80/20 | 27.34 MW | 27.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 961121 | AF2-403 | 80/20 | 1.08 MW | 1.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315163 | 1KERR 6 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315164 | 1KERR 7 | 80/20 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 315266 | 1PLYWOOD A | 80/20 | 3.88 MW | 3.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 316118 | AC1-105 C | 80/20 | 17.14 MW | 17.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 316129 | AC1-054 C | 80/20 | 4.66 MW | 4.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 316131 | AB2-060 C | 80/20 | 1.97 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 924301 | AB2-077 C O1 | 80/20 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 924311 | AB2-078 C O1 | 80/20 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 924321 | AB2-079 C O1 | 80/20 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 925611 | AC1-036 C | 80/20 | 0.24 MW | 0.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 925661 | AC1-042 C | 80/20 | 2.17 MW | 2.17 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 938371 | AE1-056 C | 80/20 | 3.93 MW | 3.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 939181 | AE1-148 C | 80/20 | 9.05 MW | 9.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 940661 | AE2-053 O1 | 80/20 | 3.35 MW | 3.35 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 941801 | AE2-185 C | 80/20 | 4.88 MW | 4.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 941821 | AE2-187 C | 80/20 | 4.88 MW | 4.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 946301 | AF1-294 C | 80/20 | 2.89 MW | 2.89 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 958211 | AF2-115 C | 80/20 | 1.76 MW | 1.76 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 962561 | AG1-105 C O1 | 80/20 | 21.07 MW | 21.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 313527 | AB2-043 C | 80/20 | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | 316123 | AC1-075 C | 80/20 | 2.47 MW | 2.47 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.15 MW | 1.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.43 MW | 0.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.08 MW | 0.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-3: 6SEDGE HILL-TX#1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 4.73 MW | 4.73 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 28.55 MW | 28.55 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 23.89 MW | 23.89 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961891 | AG1-030 C | 80/20 | 4.74 MW | 4.74 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962331 | AG1-082 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962341 | AG1-083 C | 80/20 | 1.26 MW | 1.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 6.4 MW | 6.4 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 3.12 MW | 3.12 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963321 | AG1-181 C O1 | 80/20 | 6.44 MW | 6.44 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963361 | AG1-185 O1 | 80/20 | 3.12 MW | 3.12 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964111 | AG1-272 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964121 | AG1-273 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964131 | AG1-274 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964241 | AG1-285 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964801 | AG1-343 C | 80/20 | 4.32 MW | 4.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966811 | AG1-552 C | 80/20 | 2.52 MW | 2.52 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965191 | AG1-384 C | 80/20 | 0.95 MW | 0.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965291 | AG1-394 C | 80/20 | 1.5 MW | 1.5 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965591 | AG1-427 C | 80/20 | 5.16 MW | 5.16 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 5.34 MW | 5.34 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965691 | AG1-437 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965701 | AG1-438 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965721 | AG1-440 C | 80/20 | 4.69 MW | 4.69 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965731 | AG1-441 C | 80/20 | 4.69 MW | 4.69 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965741 | AG1-442 O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965751 | AG1-443 O1 | 80/20 | 2.58 MW | 2.58 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965771 | AG1-445 | 80/20 | 2.71 MW | 2.71 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965781 | AG1-446 | 80/20 | 2.71 MW | 2.71 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 2.1 MW | 2.1 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 9.42 MW | 9.42 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.63 MW | 0.63 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314582 | 3KELFORD | 80/20 | 0.18 MW | 0.18 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315126 | 1ROARAP2 | 80/20 | 1.72 MW | 1.72 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315128 | 1ROARAP4 | 80/20 | 1.64 MW | 1.64 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 5.37 MW | 5.37 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 3.33 MW | 3.33 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 2.52 MW | 2.52 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 6.67 MW | 6.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315158 | 1KERR 1 | 80/20 | 0.22 MW | 0.22 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315159 | 1KERR 2 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315160 | 1KERR 3 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315161 | 1KERR 4 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315162 | 1KERR 5 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 44.02 MW | 44.02 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934521 | AD1-076 C | 80/20 | 17.88 MW | 17.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 936265 | AD2-033 C | 80/20 | 5.03 MW | 5.03 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 943171 | AE2-346 C | 80/20 | 0.88 MW | 0.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 959311 | AF2-222 C | 80/20 | 5.95 MW | 5.95 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.88 MW | 3.88 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315163 | 1KERR 6 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315164 | 1KERR 7 | 80/20 | 0.61 MW | 0.61 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315606 | 3AA2-053SOLA | 80/20 | 1.7 MW | 1.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | 80/20 | 6.08 MW | 6.08 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316131 | AB2-060 C | 80/20 | 0.7 MW | 0.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316140 | AB2-099 C | 80/20 | 0.37 MW | 0.37 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 29.89 MW | 29.89 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 10.26 MW | 10.26 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924301 | AB2-077 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924311 | AB2-078 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924321 | AB2-079 C O1 | 80/20 | 0.91 MW | 0.91 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 939181 | AE1-148 C | 80/20 | 4.54 MW | 4.54 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940661 | AE2-053 O1 | 80/20 | 1.68 MW | 1.68 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.31 MW | 2.31 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 957521 | AF2-046 C | 80/20 | 11.49 MW | 11.49 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938771 | AE1-103 C | 80/20 | 1.23 MW | 1.23 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 28.55 MW | 28.55 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 23.89 MW | 23.89 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314589 | 3MURPHYS | 80/20 | 0.07 MW | 0.07 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315115 | 1S HAMPT1 | 80/20 | 0.87 MW | 0.87 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 6.67 MW | 6.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315607 | 3AA1-063SOLA | 80/20 | 1.48 MW | 1.48 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315608 | 3AA2-088SOLA | 80/20 | 0.78 MW | 0.78 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 1.72 MW | 1.72 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 1.85 MW | 1.85 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 1.85 MW | 1.85 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 938221 | AE1-035 C | 80/20 | 0.21 MW | 0.21 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 933981 | AD1-022 C | 80/20 | 3.41 MW | 3.41 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961681 | AG1-008 C | 80/20 | 11.51 MW | 11.51 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 12.24 MW | 12.24 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315602 | 1HOLLOMANSOL | 80/20 | 0.86 MW | 0.86 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.81 MW | 0.81 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.25 MW | 2.25 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.24 MW | 1.24 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.65 MW | 0.65 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.09 MW | 0.09 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.67 MW | 0.67 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.43 MW | 2.43 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.32 MW | 0.32 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.4 MW | 0.4 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.44 MW | 1.44 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.27 MW | 2.27 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.39 MW | 0.39 MW |
| 6HORNRTN-AD1-057 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.84 MW | 0.84 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 7.33 MW | 7.33 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 7.33 MW | 7.33 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 7.33 MW | 7.33 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 7.33 MW | 7.33 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.84 MW | 0.84 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.46 MW | 0.46 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.82 MW | 1.82 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.82 MW | 1.82 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 10.3 MW | 10.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 5.02 MW | 5.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.56 MW | 10.56 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.11 MW | 5.11 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.09 MW | 9.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 5.28 MW | 5.28 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.62 MW | 1.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 3.12 MW | 3.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.81 MW | 1.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.58 MW | 8.58 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 8.6 MW | 8.6 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 20.51 MW | 20.51 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 7.08 MW | 7.08 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 7.08 MW | 7.08 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.95 MW | 3.95 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.95 MW | 3.95 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.94 MW | 10.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 4.09 MW | 4.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 4.09 MW | 4.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 3.35 MW | 3.35 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 13.76 MW | 13.76 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.3 MW | 1.3 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.98 MW | 0.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.62 MW | 0.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 2.12 MW | 2.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 2.02 MW | 2.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.64 MW | 7.64 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.64 MW | 7.64 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 3.87 MW | 3.87 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.4 MW | 2.4 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.81 MW | 1.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 5.94 MW | 5.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 39.2 MW | 39.2 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.67 MW | 6.67 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.24 MW | 2.24 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 7.02 MW | 7.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 10.59 MW | 10.59 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 13.64 MW | 13.64 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.25 MW | 8.25 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.28 MW | 1.28 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.73 MW | 2.73 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 6.2 MW | 6.2 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.23 MW | 1.23 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.15 MW | 2.15 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.7 MW | 1.7 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 8.35 MW | 8.35 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.53 MW | 0.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.45 MW | 1.45 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 26.62 MW | 26.62 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 14.98 MW | 14.98 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.71 MW | 0.71 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.48 MW | 6.48 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.52 MW | 9.52 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.43 MW | 7.43 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 4.24 MW | 4.24 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.75 MW | 2.75 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 3.68 MW | 3.68 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 15.09 MW | 15.09 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.37 MW | 6.37 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 940481 | AE2-033 C | 80/20 | 63.15 MW | 63.15 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 946011 | AF1-266 | 80/20 | 52.86 MW | 52.86 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 5.94 MW | 5.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.81 MW | 1.81 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.93 MW | 0.93 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 2.57 MW | 2.57 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 2.94 MW | 2.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 2.94 MW | 2.94 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.31 MW | 0.31 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.39 MW | 5.39 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.46 MW | 7.46 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 15.12 MW | 15.12 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 10.9 MW | 10.9 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.24 MW | 1.24 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.0 MW | 2.0 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.19 MW | 33.19 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.91 MW | 10.91 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.33 MW | 11.33 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.02 MW | 3.02 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.65 MW | 2.65 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.55 MW | 1.55 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.13 MW | 2.13 MW |
| AE2-033 TAP-6SAPONY 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 961791 | AG1-021 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 961891 | AG1-030 C | 80/20 | 28.04 MW | 28.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 962491 | AG1-098 C O1 | 80/20 | 16.65 MW | 16.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963171 | AG1-166 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963181 | AG1-167 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963191 | AG1-168 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963201 | AG1-169 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963211 | AG1-170 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 1.76 MW | 1.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 25.4 MW | 25.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 12.29 MW | 12.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 15.11 MW | 15.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 3.44 MW | 3.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966691 | AG1-539 C | 80/20 | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 0.75 MW | 0.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 4.07 MW | 4.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 14.44 MW | 14.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 3.02 MW | 3.02 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 52.09 MW | 52.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 5.04 MW | 5.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 5.04 MW | 5.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 2.91 MW | 2.91 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 2.91 MW | 2.91 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 8.68 MW | 8.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966361 | AG1-505 C | 80/20 | 5.44 MW | 5.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966371 | AG1-506 C | 80/20 | 5.44 MW | 5.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 2.51 MW | 2.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.92 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.16 MW | 0.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.18 MW | 0.18 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 0.51 MW | 0.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 0.48 MW | 0.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315153 | 1CLOVER1 | 80/20 | 9.98 MW | 9.98 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315154 | 1CLOVER2 | 80/20 | 9.89 MW | 9.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.31 MW | 0.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 926023 | AC1-080 C | 80/20 | 0.15 MW | 0.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 2.79 MW | 2.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 927251 | AC1-221 C | 80/20 | 0.96 MW | 0.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 927261 | AC1-222 C | 80/20 | 2.26 MW | 2.26 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934311 | AD1-055 C | 80/20 | 1.57 MW | 1.57 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934341 | AD1-058 C | 80/20 | 2.4 MW | 2.4 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934615 | AD1-087 C | 80/20 | 5.79 MW | 5.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934625 | AD1-088 C | 80/20 | 18.78 MW | 18.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 934991 | AD1-131 C | 80/20 | 0.79 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 935171 | AD1-152 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 19.29 MW | 19.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 937481 | AD2-202 C O1 | 80/20 | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 26.05 MW | 26.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 942751 | AE2-291 C | 80/20 | 3.53 MW | 3.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 942761 | AE2-292 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 943901 | AF1-058 C | 80/20 | 1.28 MW | 1.28 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 945811 | AF1-246 C O1 | 80/20 | 4.43 MW | 4.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 30.21 MW | 30.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 27.43 MW | 27.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 960061 | AF2-297 C | 80/20 | 5.12 MW | 5.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 0.97 MW | 0.97 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.87 MW | 0.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315266 | 1PLYWOOD A | 80/20 | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316118 | AC1-105 C | 80/20 | 4.19 MW | 4.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 4.2 MW | 4.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.71 MW | 1.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 2.73 MW | 2.73 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 2.08 MW | 2.08 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.39 MW | 0.39 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 932761 | AC2-100 C | 80/20 | 2.2 MW | 2.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 14.09 MW | 14.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.2 MW | 7.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.67 MW | 2.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 941791 | AE2-182 C | 80/20 | 3.05 MW | 3.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 0.57 MW | 0.57 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 946301 | AF1-294 C | 80/20 | 8.29 MW | 8.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 957481 | AF2-042 C | 80/20 | 31.67 MW | 31.67 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 958211 | AF2-115 C | 80/20 | 5.06 MW | 5.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 933501 | AC2-165 C | Adder | -6.54 MW | -5.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 958501 | AF2-144 C | Adder | -0.97 MW | -0.83 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 0.46 MW | 0.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 7.72 MW | 7.72 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.57 MW | 0.57 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | 316123 | AC1-075 C | 80/20 | 0.46 MW | 0.46 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.82 MW | 1.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 30.99 MW | 30.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.51 MW | 6.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.56 MW | 8.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.76 MW | 2.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.13 MW | 2.13 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.32 MW | 0.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.05 MW | 1.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.26 MW | 0.26 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.7 MW | 1.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 961671 | AG1-007 C | 80/20 | 0.84 MW | 0.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 961891 | AG1-030 C | 80/20 | 7.57 MW | 7.57 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 961941 | AG1-037 C | 80/20 | 0.46 MW | 0.46 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 962331 | AG1-082 C | 80/20 | 1.82 MW | 1.82 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 962341 | AG1-083 C | 80/20 | 1.82 MW | 1.82 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 10.3 MW | 10.3 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 5.02 MW | 5.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 10.56 MW | 10.56 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 5.11 MW | 5.11 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 9.09 MW | 9.09 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 2.04 MW | 2.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 964801 | AG1-343 C | 80/20 | 5.28 MW | 5.28 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 966801 | AG1-551 C | 80/20 | 1.62 MW | 1.62 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 966811 | AG1-552 C | 80/20 | 3.12 MW | 3.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965291 | AG1-394 C | 80/20 | 1.81 MW | 1.81 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 8.58 MW | 8.58 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 8.6 MW | 8.6 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965691 | AG1-437 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965701 | AG1-438 C O1 | 80/20 | 6.78 MW | 6.78 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965711 | AG1-439 C O1 | 80/20 | 20.51 MW | 20.51 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 7.08 MW | 7.08 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 7.08 MW | 7.08 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965741 | AG1-442 O1 | 80/20 | 3.95 MW | 3.95 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965751 | AG1-443 O1 | 80/20 | 3.95 MW | 3.95 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965761 | AG1-444 O1 | 80/20 | 10.94 MW | 10.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 4.09 MW | 4.09 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 4.09 MW | 4.09 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 966621 | AG1-532 C | 80/20 | 3.35 MW | 3.35 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 313506 | AB1-173 C OP | 80/20 | 13.76 MW | 13.76 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 313719 | 3CHESTNUT | 80/20 | 1.3 MW | 1.3 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314572 | 3EMPORIA | 80/20 | 0.98 MW | 0.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314582 | 3KELFORD | 80/20 | 0.37 MW | 0.37 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314623 | 3WITAKRS | 80/20 | 0.23 MW | 0.23 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.62 MW | 0.62 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315126 | 1ROARAP2 | 80/20 | 2.12 MW | 2.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315128 | 1ROARAP4 | 80/20 | 2.02 MW | 2.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315131 | 1EDGECMA | 80/20 | 7.64 MW | 7.64 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315132 | 1EDGECMB | 80/20 | 7.64 MW | 7.64 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315136 | 1ROSEMG1 | 80/20 | 3.87 MW | 3.87 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315137 | 1ROSEMS1 | 80/20 | 2.4 MW | 2.4 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315138 | 1ROSEMG2 | 80/20 | 1.81 MW | 1.81 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315139 | 1GASTONA | 80/20 | 5.94 MW | 5.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.36 MW | 0.36 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 1.0 MW | 1.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 1.0 MW | 1.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 1.0 MW | 1.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 1.0 MW | 1.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 920591 | AA2-165 C | 80/20 | 0.17 MW | 0.17 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 926070 | AC1-086 C | 80/20 | 39.2 MW | 39.2 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 926201 | AC1-098 C | 80/20 | 6.67 MW | 6.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 926211 | AC1-099 C | 80/20 | 2.24 MW | 2.24 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 927024 | AC1-189 C | 80/20 | 7.02 MW | 7.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 927145 | AC1-208 C | 80/20 | 10.59 MW | 10.59 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 934331 | AD1-057 C O1 | 80/20 | 13.64 MW | 13.64 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 934521 | AD1-076 C | 80/20 | 29.78 MW | 29.78 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 8.25 MW | 8.25 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 943171 | AE2-346 C | 80/20 | 1.28 MW | 1.28 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 944141 | AF1-082 | 80/20 | 2.73 MW | 2.73 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 6.84 MW | 6.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 9.67 MW | 9.67 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 960081 | AF2-299 C | 80/20 | 6.2 MW | 6.2 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 1.0 MW | 1.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 1.0 MW | 1.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315293 | 1DOMTR9 | 80/20 | 4.04 MW | 4.04 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315294 | 1DOMTR10 | 80/20 | 4.95 MW | 4.95 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315601 | 1CONETOE2SOL | 80/20 | 1.23 MW | 1.23 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315606 | 3AA2-053SOLA | 80/20 | 2.15 MW | 2.15 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316020 | AB2-059 C OP | 80/20 | 1.7 MW | 1.7 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316129 | AC1-054 C | 80/20 | 8.35 MW | 8.35 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.18 MW | 1.18 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316140 | AB2-099 C | 80/20 | 0.53 MW | 0.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 922922 | AB1-081 C OP | 80/20 | 1.45 MW | 1.45 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 923262 | AB1-132 C OP | 80/20 | 26.62 MW | 26.62 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 923991 | AB2-040 C O1 | 80/20 | 14.98 MW | 14.98 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 925121 | AB2-169 C | 80/20 | 0.71 MW | 0.71 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 925591 | AC1-034 C | 80/20 | 6.48 MW | 6.48 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 932631 | AC2-084 C | 80/20 | 9.52 MW | 9.52 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 7.43 MW | 7.43 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 940571 | AE2-044 C | 80/20 | 4.24 MW | 4.24 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 2.75 MW | 2.75 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 946281 | AF1-292 C | 80/20 | 3.68 MW | 3.68 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 957521 | AF2-046 C | 80/20 | 15.09 MW | 15.09 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 957861 | AF2-080 C | 80/20 | 6.37 MW | 6.37 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 314589 | 3MURPHYS | 80/20 | 0.08 MW | 0.08 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315115 | 1S HAMPT1 | 80/20 | 0.96 MW | 0.96 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315141 | 1GASTONB | 80/20 | 5.94 MW | 5.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315292 | 1DOMTR78 | 80/20 | 0.84 MW | 0.84 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315607 | 3AA1-063SOLA | 80/20 | 1.81 MW | 1.81 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315608 | 3AA2-088SOLA | 80/20 | 0.93 MW | 0.93 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316087 | AB2-174 C | 80/20 | 2.57 MW | 2.57 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316096 | AB2-100 C1 | 80/20 | 2.94 MW | 2.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 316098 | AB2-100 C2 | 80/20 | 2.94 MW | 2.94 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 938221 | AE1-035 C | 80/20 | 0.31 MW | 0.31 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 933981 | AD1-022 C | 80/20 | 5.39 MW | 5.39 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 960331 | AF2-324 C | 80/20 | 7.46 MW | 7.46 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 4.79 MW | 4.79 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 961681 | AG1-008 C | 80/20 | 15.12 MW | 15.12 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 962571 | AG1-106 C | 80/20 | 10.9 MW | 10.9 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 315602 | 1HOLLOMANSOL | 80/20 | 1.24 MW | 1.24 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.0 MW | 2.0 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.53 MW | 0.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 33.19 MW | 33.19 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.91 MW | 10.91 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 11.33 MW | 11.33 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.02 MW | 3.02 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.65 MW | 2.65 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.55 MW | 1.55 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.33 MW | 0.33 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.13 MW | 2.13 MW |
| 6CLUBHSE-AE2-033 TAP 230.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.26 MW | 0.26 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 5.89 MW | 5.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 0.75 MW | 0.75 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 7.22 MW | 7.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 3.5 MW | 3.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.73 MW | 5.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966691 | AG1-539 C | 80/20 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.08 MW | 1.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.42 MW | 5.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 6.38 MW | 6.38 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965721 | AG1-440 C | 80/20 | 2.58 MW | 2.58 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965731 | AG1-441 C | 80/20 | 2.58 MW | 2.58 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965771 | AG1-445 | 80/20 | 1.49 MW | 1.49 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965781 | AG1-446 | 80/20 | 1.49 MW | 1.49 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 1.06 MW | 1.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 6.12 MW | 6.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 6.06 MW | 6.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315159 | 1KERR 2 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315160 | 1KERR 3 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315161 | 1KERR 4 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315162 | 1KERR 5 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 3.56 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.18 MW | 4.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 5.61 MW | 5.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 3.19 MW | 3.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942751 | AE2-291 C | 80/20 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942761 | AE2-292 C O1 | 80/20 | 40.81 MW | 40.81 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 5.67 MW | 5.67 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 6.92 MW | 6.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315163 | 1KERR 6 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315164 | 1KERR 7 | 80/20 | 0.45 MW | 0.45 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 4.92 MW | 4.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.72 MW | 0.72 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925661 | AC1-042 C | Adder | -3.22 MW | -2.74 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 2.34 MW | 2.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 939181 | AE1-148 C | 80/20 | 3.56 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 940661 | AE2-053 O1 | 80/20 | 1.32 MW | 1.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 0.8 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 1.55 MW | 1.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 24.42 MW | 24.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 0.94 MW | 0.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.25 MW | 0.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.06 MW | 11.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.25 MW | 0.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.48 MW | 0.48 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.67 MW | 0.67 MW |
| Details for AG1-181 TAP-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| AG1-181 TAP-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| Details for 3CENTRAL-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3CENTRAL-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3CENTRAL-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3CENTRAL-3TWITTYS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| Details for 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 961791 | AG1-021 C | 80/20 | 0.73 MW | 0.73 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 961891 | AG1-030 C | 80/20 | 6.03 MW | 6.03 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 963171 | AG1-166 C | 80/20 | 0.73 MW | 0.73 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 963181 | AG1-167 C | 80/20 | 0.73 MW | 0.73 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 963191 | AG1-168 C | 80/20 | 0.73 MW | 0.73 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 963201 | AG1-169 C | 80/20 | 0.73 MW | 0.73 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 963211 | AG1-170 C | 80/20 | 0.73 MW | 0.73 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 963321 | AG1-181 C O1 | 80/20 | 8.25 MW | 8.25 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 963361 | AG1-185 O1 | 80/20 | 3.99 MW | 3.99 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 964111 | AG1-272 C | 80/20 | 1.21 MW | 1.21 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 964121 | AG1-273 C | 80/20 | 1.21 MW | 1.21 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 964131 | AG1-274 C | 80/20 | 1.21 MW | 1.21 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 964241 | AG1-285 C O1 | 80/20 | 7.03 MW | 7.03 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 964791 | AG1-342 C | 80/20 | 1.56 MW | 1.56 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 965191 | AG1-384 C | 80/20 | 1.21 MW | 1.21 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 965591 | AG1-427 C | 80/20 | 6.64 MW | 6.64 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 313506 | AB1-173 C OP | Adder | -2.7 MW | -2.29 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 314429 | 3JTRSVLE | 80/20 | 0.17 MW | 0.17 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 315158 | 1KERR 1 | 80/20 | 0.49 MW | 0.49 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 315159 | 1KERR 2 | 80/20 | 1.38 MW | 1.38 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 315160 | 1KERR 3 | 80/20 | 1.38 MW | 1.38 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 315161 | 1KERR 4 | 80/20 | 1.38 MW | 1.38 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 315162 | 1KERR 5 | 80/20 | 1.38 MW | 1.38 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 936265 | AD2-033 C | 80/20 | 6.45 MW | 6.45 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 958801 | AF2-171 C | 80/20 | 5.51 MW | 5.51 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 959311 | AF2-222 C | 80/20 | 7.61 MW | 7.61 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 315163 | 1KERR 6 | 80/20 | 1.38 MW | 1.38 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 315164 | 1KERR 7 | 80/20 | 1.38 MW | 1.38 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 315266 | 1PLYWOOD A | 80/20 | 0.43 MW | 0.43 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 923991 | AB2-040 C O1 | Adder | -2.94 MW | -2.5 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 924301 | AB2-077 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 924311 | AB2-078 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 924321 | AB2-079 C O1 | 80/20 | 1.23 MW | 1.23 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 925611 | AC1-036 C | 80/20 | 0.12 MW | 0.12 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 938371 | AE1-056 C | 80/20 | 2.12 MW | 2.12 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 939181 | AE1-148 C | 80/20 | 9.41 MW | 9.41 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 940661 | AE2-053 O1 | 80/20 | 3.49 MW | 3.49 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 946301 | AF1-294 C | 80/20 | 1.5 MW | 1.5 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 958211 | AF2-115 C | 80/20 | 0.91 MW | 0.91 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 962561 | AG1-105 C O1 | 80/20 | 3.67 MW | 3.67 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | 313527 | AB2-043 C | 80/20 | 0.32 MW | 0.32 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.14 MW | 0.14 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.92 MW | 2.92 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.83 MW | 1.83 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.49 MW | 1.49 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.09 MW | 0.09 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.23 MW | 0.23 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.26 MW | 0.26 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 22 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 961791 | AG1-021 C | 80/20 | 0.64 MW | 0.64 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 961891 | AG1-030 C | 80/20 | 5.22 MW | 5.22 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 963171 | AG1-166 C | 80/20 | 0.64 MW | 0.64 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 963181 | AG1-167 C | 80/20 | 0.64 MW | 0.64 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 963191 | AG1-168 C | 80/20 | 0.64 MW | 0.64 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 963201 | AG1-169 C | 80/20 | 0.64 MW | 0.64 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 963211 | AG1-170 C | 80/20 | 0.64 MW | 0.64 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 963321 | AG1-181 C O1 | 80/20 | 6.97 MW | 6.97 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 963361 | AG1-185 O1 | 80/20 | 3.37 MW | 3.37 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 964111 | AG1-272 C | 80/20 | 1.03 MW | 1.03 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 964121 | AG1-273 C | 80/20 | 1.03 MW | 1.03 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 964131 | AG1-274 C | 80/20 | 1.03 MW | 1.03 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 964241 | AG1-285 C O1 | 80/20 | 5.85 MW | 5.85 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 964791 | AG1-342 C | 80/20 | 1.39 MW | 1.39 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 965191 | AG1-384 C | 80/20 | 1.03 MW | 1.03 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 965591 | AG1-427 C | 80/20 | 5.53 MW | 5.53 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 314429 | 3JTRSVLE | 80/20 | 0.14 MW | 0.14 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315158 | 1KERR 1 | 80/20 | 0.39 MW | 0.39 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315159 | 1KERR 2 | 80/20 | 1.1 MW | 1.1 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315160 | 1KERR 3 | 80/20 | 1.1 MW | 1.1 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315161 | 1KERR 4 | 80/20 | 1.1 MW | 1.1 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315162 | 1KERR 5 | 80/20 | 1.1 MW | 1.1 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 936265 | AD2-033 C | 80/20 | 5.44 MW | 5.44 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 958801 | AF2-171 C | 80/20 | 4.82 MW | 4.82 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 959311 | AF2-222 C | 80/20 | 6.48 MW | 6.48 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315163 | 1KERR 6 | 80/20 | 1.1 MW | 1.1 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315164 | 1KERR 7 | 80/20 | 1.1 MW | 1.1 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 315266 | 1PLYWOOD A | 80/20 | 0.4 MW | 0.4 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 316131 | AB2-060 C | 80/20 | 0.75 MW | 0.75 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 924301 | AB2-077 C O1 | 80/20 | 1.01 MW | 1.01 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 924311 | AB2-078 C O1 | 80/20 | 1.01 MW | 1.01 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 924321 | AB2-079 C O1 | 80/20 | 1.01 MW | 1.01 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 939181 | AE1-148 C | 80/20 | 7.53 MW | 7.53 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 940661 | AE2-053 O1 | 80/20 | 2.79 MW | 2.79 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 946301 | AF1-294 C | 80/20 | 1.31 MW | 1.31 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 958211 | AF2-115 C | 80/20 | 0.8 MW | 0.8 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 962561 | AG1-105 C O1 | 80/20 | 3.21 MW | 3.21 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | 313527 | AB2-043 C | 80/20 | 0.27 MW | 0.27 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.33 MW | 3.33 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.97 MW | 1.97 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.64 MW | 1.64 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.25 MW | 0.25 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.35 MW | 0.35 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.1 MW | 0.1 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.25 MW | 0.25 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.29 MW | 0.29 MW |
| 3KERR-3PALMERSPRNG 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.05 MW | 0.05 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 2.19 MW | 2.19 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 11.3 MW | 11.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 8.91 MW | 8.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962741 | AG1-123 C O1 | 80/20 | 2.11 MW | 2.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 10.13 MW | 10.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 4.9 MW | 4.9 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.63 MW | 1.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.63 MW | 1.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.63 MW | 1.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 10.64 MW | 10.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 1.67 MW | 1.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.63 MW | 1.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 3.46 MW | 3.46 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.68 MW | 5.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 21.27 MW | 21.27 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 3.54 MW | 3.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966251 | AG1-494 C | 80/20 | 1.22 MW | 1.22 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 9.26 MW | 9.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 9.26 MW | 9.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.37 MW | 0.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 7.74 MW | 7.74 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 7.66 MW | 7.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.11 MW | 0.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 1.41 MW | 1.41 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 0.98 MW | 0.98 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 4.48 MW | 4.48 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 9.98 MW | 9.98 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 7.68 MW | 7.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 12.22 MW | 12.22 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 10.99 MW | 10.99 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 3.07 MW | 3.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 2.19 MW | 2.19 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 0.48 MW | 0.48 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 2.25 MW | 2.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 5.72 MW | 5.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 18.24 MW | 18.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 16.71 MW | 16.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 1.62 MW | 1.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 25.22 MW | 25.22 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 3.35 MW | 3.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 6.03 MW | 6.03 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 30.87 MW | 30.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958131 | AF2-107 C | 80/20 | 3.0 MW | 3.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 2.05 MW | 2.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 33.06 MW | 33.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 19.1 MW | 19.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.58 MW | 0.58 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936761 | AD2-097 C | Adder | -0.9 MW | -0.76 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | Adder | -3.68 MW | -3.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966671 | AG1-537 C | 80/20 | 1.83 MW | 1.83 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 9.74 MW | 9.74 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 9.74 MW | 9.74 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 12.6 MW | 12.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932854 | AC2-112 C | 80/20 | 5.9 MW | 5.9 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938625 | AE1-084 C | 80/20 | 2.85 MW | 2.85 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.22 MW | 0.22 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.26 MW | 8.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.62 MW | 10.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.47 MW | 7.47 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.47 MW | 0.47 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.48 MW | 1.48 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.28 MW | 1.28 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.23 MW | 1.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961791 | AG1-021 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961891 | AG1-030 C | 80/20 | 5.26 MW | 5.26 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963171 | AG1-166 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963181 | AG1-167 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963191 | AG1-168 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963201 | AG1-169 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963211 | AG1-170 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 6.49 MW | 6.49 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 3.16 MW | 3.16 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963321 | AG1-181 C O1 | 80/20 | 7.27 MW | 7.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963361 | AG1-185 O1 | 80/20 | 3.52 MW | 3.52 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964111 | AG1-272 C | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964121 | AG1-273 C | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964131 | AG1-274 C | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964241 | AG1-285 C O1 | 80/20 | 6.23 MW | 6.23 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964791 | AG1-342 C | 80/20 | 1.39 MW | 1.39 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966811 | AG1-552 C | 80/20 | 2.5 MW | 2.5 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965191 | AG1-384 C | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965291 | AG1-394 C | 80/20 | 0.72 MW | 0.72 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965591 | AG1-427 C | 80/20 | 5.88 MW | 5.88 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 5.42 MW | 5.42 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965721 | AG1-440 C | 80/20 | 5.27 MW | 5.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965731 | AG1-441 C | 80/20 | 5.27 MW | 5.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 2.08 MW | 2.08 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 9.33 MW | 9.33 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313719 | 3CHESTNUT | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314429 | 3JTRSVLE | 80/20 | 0.14 MW | 0.14 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.62 MW | 0.62 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314623 | 3WITAKRS | 80/20 | 0.14 MW | 0.14 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315126 | 1ROARAP2 | 80/20 | 1.7 MW | 1.7 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315128 | 1ROARAP4 | 80/20 | 1.62 MW | 1.62 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315131 | 1EDGECMA | 80/20 | 4.96 MW | 4.96 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315132 | 1EDGECMB | 80/20 | 4.96 MW | 4.96 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 4.16 MW | 4.16 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 2.58 MW | 2.58 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 1.95 MW | 1.95 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315159 | 1KERR 2 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315160 | 1KERR 3 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315161 | 1KERR 4 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315162 | 1KERR 5 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 43.16 MW | 43.16 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926201 | AC1-098 C | 80/20 | 2.27 MW | 2.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926211 | AC1-099 C | 80/20 | 0.76 MW | 0.76 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 927145 | AC1-208 C | 80/20 | 6.05 MW | 6.05 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934331 | AD1-057 C O1 | 80/20 | 12.73 MW | 12.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 936265 | AD2-033 C | 80/20 | 5.67 MW | 5.67 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 944141 | AF1-082 | 80/20 | 1.72 MW | 1.72 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 958801 | AF2-171 C | 80/20 | 4.78 MW | 4.78 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 959311 | AF2-222 C | 80/20 | 6.68 MW | 6.68 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.85 MW | 3.85 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315163 | 1KERR 6 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315164 | 1KERR 7 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315293 | 1DOMTR9 | Adder | -3.8 MW | -3.23 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315294 | 1DOMTR10 | Adder | -4.65 MW | -3.96 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315606 | 3AA2-053SOLA | 80/20 | 1.36 MW | 1.36 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316020 | AB2-059 C OP | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | 80/20 | 6.42 MW | 6.42 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316131 | AB2-060 C | 80/20 | 0.81 MW | 0.81 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 922922 | AB1-081 C OP | 80/20 | 0.91 MW | 0.91 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 29.31 MW | 29.31 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 10.16 MW | 10.16 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924301 | AB2-077 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924311 | AB2-078 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924321 | AB2-079 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925591 | AC1-034 C | 80/20 | 4.07 MW | 4.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 932631 | AC2-084 C | 80/20 | 3.23 MW | 3.23 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 939181 | AE1-148 C | 80/20 | 5.33 MW | 5.33 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940491 | AE2-034 C | Adder | -3.84 MW | -3.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940571 | AE2-044 C | 80/20 | 2.67 MW | 2.67 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940661 | AE2-053 O1 | 80/20 | 1.98 MW | 1.98 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.28 MW | 2.28 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946301 | AF1-294 C | 80/20 | 1.3 MW | 1.3 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 958211 | AF2-115 C | 80/20 | 0.79 MW | 0.79 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 28.07 MW | 28.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 23.5 MW | 23.5 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315607 | 3AA1-063SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315608 | 3AA2-088SOLA | 80/20 | 0.36 MW | 0.36 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 1.7 MW | 1.7 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 1.82 MW | 1.82 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 1.82 MW | 1.82 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960331 | AF2-324 C | 80/20 | 4.84 MW | 4.84 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962561 | AG1-105 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 12.0 MW | 12.0 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313527 | AB2-043 C | 80/20 | 0.28 MW | 0.28 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.4 MW | 14.4 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.96 MW | 4.96 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.09 MW | 5.09 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.18 MW | 1.18 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.7 MW | 0.7 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.95 MW | 0.95 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961791 | AG1-021 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961891 | AG1-030 C | 80/20 | 5.26 MW | 5.26 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963171 | AG1-166 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963181 | AG1-167 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963191 | AG1-168 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963201 | AG1-169 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963211 | AG1-170 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 6.49 MW | 6.49 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 3.16 MW | 3.16 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963321 | AG1-181 C O1 | 80/20 | 7.27 MW | 7.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963361 | AG1-185 O1 | 80/20 | 3.52 MW | 3.52 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964111 | AG1-272 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964121 | AG1-273 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964131 | AG1-274 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964241 | AG1-285 C O1 | 80/20 | 6.23 MW | 6.23 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964791 | AG1-342 C | 80/20 | 1.39 MW | 1.39 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966811 | AG1-552 C | 80/20 | 2.5 MW | 2.5 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965191 | AG1-384 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965291 | AG1-394 C | 80/20 | 0.72 MW | 0.72 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965591 | AG1-427 C | 80/20 | 5.88 MW | 5.88 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 5.42 MW | 5.42 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965721 | AG1-440 C | 80/20 | 5.27 MW | 5.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965731 | AG1-441 C | 80/20 | 5.27 MW | 5.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 2.08 MW | 2.08 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 9.33 MW | 9.33 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313719 | 3CHESTNUT | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314429 | 3JTRSVLE | 80/20 | 0.14 MW | 0.14 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.62 MW | 0.62 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314623 | 3WITAKRS | 80/20 | 0.14 MW | 0.14 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315126 | 1ROARAP2 | 80/20 | 1.7 MW | 1.7 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315128 | 1ROARAP4 | 80/20 | 1.62 MW | 1.62 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315131 | 1EDGECMA | 80/20 | 4.96 MW | 4.96 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315132 | 1EDGECMB | 80/20 | 4.96 MW | 4.96 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 4.16 MW | 4.16 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 2.58 MW | 2.58 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 1.95 MW | 1.95 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315159 | 1KERR 2 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315160 | 1KERR 3 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315161 | 1KERR 4 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315162 | 1KERR 5 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 43.16 MW | 43.16 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926201 | AC1-098 C | 80/20 | 2.27 MW | 2.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926211 | AC1-099 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 927145 | AC1-208 C | 80/20 | 6.05 MW | 6.05 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934331 | AD1-057 C O1 | 80/20 | 12.73 MW | 12.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 936265 | AD2-033 C | 80/20 | 5.67 MW | 5.67 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 944141 | AF1-082 | 80/20 | 1.72 MW | 1.72 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 958801 | AF2-171 C | 80/20 | 4.78 MW | 4.78 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 959311 | AF2-222 C | 80/20 | 6.68 MW | 6.68 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.85 MW | 3.85 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315163 | 1KERR 6 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315164 | 1KERR 7 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315293 | 1DOMTR9 | Adder | -3.8 MW | -3.23 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315294 | 1DOMTR10 | Adder | -4.65 MW | -3.96 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315606 | 3AA2-053SOLA | 80/20 | 1.36 MW | 1.36 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316020 | AB2-059 C OP | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | 80/20 | 6.42 MW | 6.42 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316131 | AB2-060 C | 80/20 | 0.81 MW | 0.81 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 922922 | AB1-081 C OP | 80/20 | 0.91 MW | 0.91 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 29.31 MW | 29.31 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 10.16 MW | 10.16 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924301 | AB2-077 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924311 | AB2-078 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924321 | AB2-079 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925591 | AC1-034 C | 80/20 | 4.07 MW | 4.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 932631 | AC2-084 C | 80/20 | 3.23 MW | 3.23 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 939181 | AE1-148 C | 80/20 | 5.33 MW | 5.33 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940491 | AE2-034 C | Adder | -3.84 MW | -3.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940571 | AE2-044 C | 80/20 | 2.67 MW | 2.67 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940661 | AE2-053 O1 | 80/20 | 1.98 MW | 1.98 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.28 MW | 2.28 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946301 | AF1-294 C | 80/20 | 1.3 MW | 1.3 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 958211 | AF2-115 C | 80/20 | 0.79 MW | 0.79 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 28.07 MW | 28.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 23.5 MW | 23.5 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315607 | 3AA1-063SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315608 | 3AA2-088SOLA | 80/20 | 0.36 MW | 0.36 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 1.7 MW | 1.7 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 1.82 MW | 1.82 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 1.82 MW | 1.82 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960331 | AF2-324 C | 80/20 | 4.84 MW | 4.84 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962561 | AG1-105 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 12.0 MW | 12.0 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313527 | AB2-043 C | 80/20 | 0.28 MW | 0.28 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.4 MW | 14.4 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.96 MW | 4.96 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.09 MW | 5.09 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.18 MW | 1.18 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.7 MW | 0.7 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.95 MW | 0.95 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 5.26 MW | 5.26 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 0.63 MW | 0.63 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 6.49 MW | 6.49 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 3.16 MW | 3.16 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 7.27 MW | 7.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 3.52 MW | 3.52 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 6.23 MW | 6.23 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.39 MW | 1.39 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 2.5 MW | 2.5 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965291 | AG1-394 C | 80/20 | 0.72 MW | 0.72 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 5.88 MW | 5.88 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 5.42 MW | 5.42 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 5.27 MW | 5.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 5.27 MW | 5.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 2.08 MW | 2.08 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 9.33 MW | 9.33 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313719 | 3CHESTNUT | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.14 MW | 0.14 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.62 MW | 0.62 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314623 | 3WITAKRS | 80/20 | 0.14 MW | 0.14 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.7 MW | 1.7 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.62 MW | 1.62 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315131 | 1EDGECMA | 80/20 | 4.96 MW | 4.96 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315132 | 1EDGECMB | 80/20 | 4.96 MW | 4.96 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.16 MW | 4.16 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.58 MW | 2.58 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 1.95 MW | 1.95 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 43.16 MW | 43.16 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926201 | AC1-098 C | 80/20 | 2.27 MW | 2.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926211 | AC1-099 C | 80/20 | 0.76 MW | 0.76 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 927145 | AC1-208 C | 80/20 | 6.05 MW | 6.05 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 12.73 MW | 12.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 5.67 MW | 5.67 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 944141 | AF1-082 | 80/20 | 1.72 MW | 1.72 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 4.78 MW | 4.78 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 6.68 MW | 6.68 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.85 MW | 3.85 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.73 MW | 0.73 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315293 | 1DOMTR9 | Adder | -3.8 MW | -3.23 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315294 | 1DOMTR10 | Adder | -4.65 MW | -3.96 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.36 MW | 1.36 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316020 | AB2-059 C OP | 80/20 | 1.07 MW | 1.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 6.42 MW | 6.42 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.81 MW | 0.81 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 922922 | AB1-081 C OP | 80/20 | 0.91 MW | 0.91 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.31 MW | 29.31 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 10.16 MW | 10.16 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925591 | AC1-034 C | 80/20 | 4.07 MW | 4.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 932631 | AC2-084 C | 80/20 | 3.23 MW | 3.23 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.33 MW | 5.33 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940491 | AE2-034 C | Adder | -3.84 MW | -3.27 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940571 | AE2-044 C | 80/20 | 2.67 MW | 2.67 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.98 MW | 1.98 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.28 MW | 2.28 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 1.3 MW | 1.3 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 0.79 MW | 0.79 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 28.07 MW | 28.07 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 23.5 MW | 23.5 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.36 MW | 0.36 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 1.7 MW | 1.7 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 1.82 MW | 1.82 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 1.82 MW | 1.82 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960331 | AF2-324 C | 80/20 | 4.84 MW | 4.84 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 12.0 MW | 12.0 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.28 MW | 0.28 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.4 MW | 14.4 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.96 MW | 4.96 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.09 MW | 5.09 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.18 MW | 1.18 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.7 MW | 0.7 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.95 MW | 0.95 MW |
| 6ROA VAL-6NORTHAMPTON 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 5.26 MW | 5.26 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 6.49 MW | 6.49 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 3.16 MW | 3.16 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 7.27 MW | 7.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 3.52 MW | 3.52 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 6.23 MW | 6.23 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.39 MW | 1.39 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 2.5 MW | 2.5 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965291 | AG1-394 C | 80/20 | 0.72 MW | 0.72 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 5.88 MW | 5.88 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 5.42 MW | 5.42 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 5.27 MW | 5.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 5.27 MW | 5.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 2.08 MW | 2.08 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 9.33 MW | 9.33 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313719 | 3CHESTNUT | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.14 MW | 0.14 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.62 MW | 0.62 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314623 | 3WITAKRS | 80/20 | 0.14 MW | 0.14 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.7 MW | 1.7 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.62 MW | 1.62 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315131 | 1EDGECMA | 80/20 | 4.96 MW | 4.96 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315132 | 1EDGECMB | 80/20 | 4.96 MW | 4.96 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.16 MW | 4.16 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.58 MW | 2.58 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 1.95 MW | 1.95 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 43.16 MW | 43.16 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926201 | AC1-098 C | 80/20 | 2.27 MW | 2.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926211 | AC1-099 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 927145 | AC1-208 C | 80/20 | 6.05 MW | 6.05 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 12.73 MW | 12.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 5.67 MW | 5.67 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 944141 | AF1-082 | 80/20 | 1.72 MW | 1.72 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 4.78 MW | 4.78 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 6.68 MW | 6.68 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.85 MW | 3.85 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.73 MW | 0.73 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315293 | 1DOMTR9 | Adder | -3.8 MW | -3.23 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315294 | 1DOMTR10 | Adder | -4.65 MW | -3.96 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.36 MW | 1.36 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316020 | AB2-059 C OP | 80/20 | 1.07 MW | 1.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 6.42 MW | 6.42 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.81 MW | 0.81 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 922922 | AB1-081 C OP | 80/20 | 0.91 MW | 0.91 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.31 MW | 29.31 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 10.16 MW | 10.16 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925591 | AC1-034 C | 80/20 | 4.07 MW | 4.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 932631 | AC2-084 C | 80/20 | 3.23 MW | 3.23 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.33 MW | 5.33 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940491 | AE2-034 C | Adder | -3.84 MW | -3.27 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940571 | AE2-044 C | 80/20 | 2.67 MW | 2.67 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.98 MW | 1.98 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.28 MW | 2.28 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 1.3 MW | 1.3 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 0.79 MW | 0.79 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 28.07 MW | 28.07 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 23.5 MW | 23.5 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.36 MW | 0.36 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 1.7 MW | 1.7 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 1.82 MW | 1.82 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 1.82 MW | 1.82 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960331 | AF2-324 C | 80/20 | 4.84 MW | 4.84 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 12.0 MW | 12.0 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.28 MW | 0.28 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.4 MW | 14.4 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.96 MW | 4.96 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.09 MW | 5.09 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.18 MW | 1.18 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.7 MW | 0.7 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.95 MW | 0.95 MW |
| 6CAROLNA-6ROA VAL 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961791 | AG1-021 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 961891 | AG1-030 C | 80/20 | 5.26 MW | 5.26 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963171 | AG1-166 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963181 | AG1-167 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963191 | AG1-168 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963201 | AG1-169 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963211 | AG1-170 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963301 | AG1-179 C | 80/20 | 6.49 MW | 6.49 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963311 | AG1-180 | 80/20 | 3.16 MW | 3.16 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963321 | AG1-181 C O1 | 80/20 | 7.27 MW | 7.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 963361 | AG1-185 O1 | 80/20 | 3.52 MW | 3.52 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964111 | AG1-272 C | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964121 | AG1-273 C | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964131 | AG1-274 C | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964241 | AG1-285 C O1 | 80/20 | 6.23 MW | 6.23 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964791 | AG1-342 C | 80/20 | 1.39 MW | 1.39 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966811 | AG1-552 C | 80/20 | 2.5 MW | 2.5 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965191 | AG1-384 C | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965291 | AG1-394 C | 80/20 | 0.72 MW | 0.72 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965591 | AG1-427 C | 80/20 | 5.88 MW | 5.88 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965601 | AG1-428 C O2 | 80/20 | 5.42 MW | 5.42 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965721 | AG1-440 C | 80/20 | 5.27 MW | 5.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965731 | AG1-441 C | 80/20 | 5.27 MW | 5.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 966621 | AG1-532 C | 80/20 | 2.08 MW | 2.08 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313506 | AB1-173 C OP | 80/20 | 9.33 MW | 9.33 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313719 | 3CHESTNUT | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314429 | 3JTRSVLE | 80/20 | 0.14 MW | 0.14 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314572 | 3EMPORIA | 80/20 | 0.62 MW | 0.62 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314623 | 3WITAKRS | 80/20 | 0.14 MW | 0.14 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315126 | 1ROARAP2 | 80/20 | 1.7 MW | 1.7 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315128 | 1ROARAP4 | 80/20 | 1.62 MW | 1.62 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315131 | 1EDGECMA | 80/20 | 4.96 MW | 4.96 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315132 | 1EDGECMB | 80/20 | 4.96 MW | 4.96 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315136 | 1ROSEMG1 | 80/20 | 4.16 MW | 4.16 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315137 | 1ROSEMS1 | 80/20 | 2.58 MW | 2.58 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315138 | 1ROSEMG2 | 80/20 | 1.95 MW | 1.95 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315159 | 1KERR 2 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315160 | 1KERR 3 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315161 | 1KERR 4 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315162 | 1KERR 5 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926070 | AC1-086 C | 80/20 | 43.16 MW | 43.16 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926201 | AC1-098 C | 80/20 | 2.27 MW | 2.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 926211 | AC1-099 C | 80/20 | 0.76 MW | 0.76 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 927145 | AC1-208 C | 80/20 | 6.05 MW | 6.05 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 934331 | AD1-057 C O1 | 80/20 | 12.73 MW | 12.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 936265 | AD2-033 C | 80/20 | 5.67 MW | 5.67 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 944141 | AF1-082 | 80/20 | 1.72 MW | 1.72 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 958801 | AF2-171 C | 80/20 | 4.78 MW | 4.78 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 959311 | AF2-222 C | 80/20 | 6.68 MW | 6.68 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960081 | AF2-299 C | 80/20 | 3.85 MW | 3.85 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315163 | 1KERR 6 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315164 | 1KERR 7 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315293 | 1DOMTR9 | Adder | -3.8 MW | -3.23 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315294 | 1DOMTR10 | Adder | -4.65 MW | -3.96 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315606 | 3AA2-053SOLA | 80/20 | 1.36 MW | 1.36 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316020 | AB2-059 C OP | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316129 | AC1-054 C | 80/20 | 6.42 MW | 6.42 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316131 | AB2-060 C | 80/20 | 0.81 MW | 0.81 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 922922 | AB1-081 C OP | 80/20 | 0.91 MW | 0.91 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923262 | AB1-132 C OP | 80/20 | 29.31 MW | 29.31 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 923991 | AB2-040 C O1 | 80/20 | 10.16 MW | 10.16 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924301 | AB2-077 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924311 | AB2-078 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 924321 | AB2-079 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925591 | AC1-034 C | 80/20 | 4.07 MW | 4.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 932631 | AC2-084 C | 80/20 | 3.23 MW | 3.23 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 939181 | AE1-148 C | 80/20 | 5.33 MW | 5.33 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940491 | AE2-034 C | Adder | -3.84 MW | -3.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940571 | AE2-044 C | 80/20 | 2.67 MW | 2.67 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940661 | AE2-053 O1 | 80/20 | 1.98 MW | 1.98 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946281 | AF1-292 C | 80/20 | 2.28 MW | 2.28 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946301 | AF1-294 C | 80/20 | 1.3 MW | 1.3 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 958211 | AF2-115 C | 80/20 | 0.79 MW | 0.79 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 940481 | AE2-033 C | 80/20 | 28.07 MW | 28.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 946011 | AF1-266 | 80/20 | 23.5 MW | 23.5 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315607 | 3AA1-063SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 315608 | 3AA2-088SOLA | 80/20 | 0.36 MW | 0.36 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316087 | AB2-174 C | 80/20 | 1.7 MW | 1.7 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316096 | AB2-100 C1 | 80/20 | 1.82 MW | 1.82 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 316098 | AB2-100 C2 | 80/20 | 1.82 MW | 1.82 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 960331 | AF2-324 C | 80/20 | 4.84 MW | 4.84 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962561 | AG1-105 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 962571 | AG1-106 C | 80/20 | 12.0 MW | 12.0 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | 313527 | AB2-043 C | 80/20 | 0.28 MW | 0.28 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.4 MW | 14.4 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.96 MW | 4.96 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.09 MW | 5.09 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.18 MW | 1.18 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.7 MW | 0.7 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.95 MW | 0.95 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 238-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 5.26 MW | 5.26 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 0.63 MW | 0.63 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 6.49 MW | 6.49 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963311 | AG1-180 | 80/20 | 3.16 MW | 3.16 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 7.27 MW | 7.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 3.52 MW | 3.52 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 6.23 MW | 6.23 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.39 MW | 1.39 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 964801 | AG1-343 C | 80/20 | 1.83 MW | 1.83 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966811 | AG1-552 C | 80/20 | 2.5 MW | 2.5 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965291 | AG1-394 C | 80/20 | 0.72 MW | 0.72 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 5.88 MW | 5.88 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 5.42 MW | 5.42 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 5.27 MW | 5.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 5.27 MW | 5.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 2.08 MW | 2.08 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313506 | AB1-173 C OP | 80/20 | 9.33 MW | 9.33 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313719 | 3CHESTNUT | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.14 MW | 0.14 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.62 MW | 0.62 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314623 | 3WITAKRS | 80/20 | 0.14 MW | 0.14 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.39 MW | 0.39 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315126 | 1ROARAP2 | 80/20 | 1.7 MW | 1.7 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315128 | 1ROARAP4 | 80/20 | 1.62 MW | 1.62 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315131 | 1EDGECMA | 80/20 | 4.96 MW | 4.96 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315132 | 1EDGECMB | 80/20 | 4.96 MW | 4.96 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315136 | 1ROSEMG1 | 80/20 | 4.16 MW | 4.16 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315137 | 1ROSEMS1 | 80/20 | 2.58 MW | 2.58 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315138 | 1ROSEMG2 | 80/20 | 1.95 MW | 1.95 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315139 | 1GASTONA | 80/20 | 6.54 MW | 6.54 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926070 | AC1-086 C | 80/20 | 43.16 MW | 43.16 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926201 | AC1-098 C | 80/20 | 2.27 MW | 2.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 926211 | AC1-099 C | 80/20 | 0.76 MW | 0.76 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 927145 | AC1-208 C | 80/20 | 6.05 MW | 6.05 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 934331 | AD1-057 C O1 | 80/20 | 12.73 MW | 12.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 5.67 MW | 5.67 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 944141 | AF1-082 | 80/20 | 1.72 MW | 1.72 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 4.78 MW | 4.78 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 6.68 MW | 6.68 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 3.85 MW | 3.85 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.73 MW | 0.73 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315293 | 1DOMTR9 | Adder | -3.8 MW | -3.23 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315294 | 1DOMTR10 | Adder | -4.65 MW | -3.96 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315606 | 3AA2-053SOLA | 80/20 | 1.36 MW | 1.36 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316020 | AB2-059 C OP | 80/20 | 1.07 MW | 1.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 6.42 MW | 6.42 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.81 MW | 0.81 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 922922 | AB1-081 C OP | 80/20 | 0.91 MW | 0.91 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923262 | AB1-132 C OP | 80/20 | 29.31 MW | 29.31 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 923991 | AB2-040 C O1 | 80/20 | 10.16 MW | 10.16 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.05 MW | 1.05 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925591 | AC1-034 C | 80/20 | 4.07 MW | 4.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.1 MW | 0.1 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 932631 | AC2-084 C | 80/20 | 3.23 MW | 3.23 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.33 MW | 5.33 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940491 | AE2-034 C | Adder | -3.84 MW | -3.27 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940571 | AE2-044 C | 80/20 | 2.67 MW | 2.67 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.98 MW | 1.98 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 2.28 MW | 2.28 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 1.3 MW | 1.3 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 0.79 MW | 0.79 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 940481 | AE2-033 C | 80/20 | 28.07 MW | 28.07 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 946011 | AF1-266 | 80/20 | 23.5 MW | 23.5 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315141 | 1GASTONB | 80/20 | 6.54 MW | 6.54 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315607 | 3AA1-063SOLA | 80/20 | 1.25 MW | 1.25 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 315608 | 3AA2-088SOLA | 80/20 | 0.36 MW | 0.36 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316087 | AB2-174 C | 80/20 | 1.7 MW | 1.7 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316096 | AB2-100 C1 | 80/20 | 1.82 MW | 1.82 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 316098 | AB2-100 C2 | 80/20 | 1.82 MW | 1.82 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 960331 | AF2-324 C | 80/20 | 4.84 MW | 4.84 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 962571 | AG1-106 C | 80/20 | 12.0 MW | 12.0 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.28 MW | 0.28 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.82 MW | 0.82 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.24 MW | 0.24 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.4 MW | 14.4 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.96 MW | 4.96 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.09 MW | 5.09 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.24 MW | 1.24 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.18 MW | 1.18 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.24 MW | 0.24 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.7 MW | 0.7 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.17 MW | 0.17 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.95 MW | 0.95 MW |
| 6NORTHAMPTON-6EARLEYS 230.0 kV Ckt 1 line l/o 314435 6SAPONY 230 940480 AE2-033 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.12 MW | 0.12 MW |
| Details for AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AF2-222 TAP-3MADSONV 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 2.19 MW | 2.19 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 11.3 MW | 11.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 8.91 MW | 8.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962741 | AG1-123 C O1 | 80/20 | 2.11 MW | 2.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 1.64 MW | 1.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 10.13 MW | 10.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 4.9 MW | 4.9 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.63 MW | 1.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.63 MW | 1.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.63 MW | 1.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 10.64 MW | 10.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.94 MW | 5.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 1.67 MW | 1.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.63 MW | 1.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 3.46 MW | 3.46 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.68 MW | 5.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 21.27 MW | 21.27 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 3.54 MW | 3.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966251 | AG1-494 C | 80/20 | 1.22 MW | 1.22 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.37 MW | 0.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 7.74 MW | 7.74 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 7.66 MW | 7.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.11 MW | 0.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 1.41 MW | 1.41 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 0.98 MW | 0.98 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 4.48 MW | 4.48 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 9.98 MW | 9.98 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 7.68 MW | 7.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 12.22 MW | 12.22 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 10.99 MW | 10.99 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 3.07 MW | 3.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 2.19 MW | 2.19 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 0.48 MW | 0.48 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 2.25 MW | 2.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 5.72 MW | 5.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 18.24 MW | 18.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 16.71 MW | 16.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 1.62 MW | 1.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 25.22 MW | 25.22 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 3.35 MW | 3.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 6.03 MW | 6.03 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 30.87 MW | 30.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958131 | AF2-107 C | 80/20 | 3.0 MW | 3.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 2.05 MW | 2.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 33.06 MW | 33.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 19.1 MW | 19.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.58 MW | 0.58 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936761 | AD2-097 C | Adder | -0.9 MW | -0.76 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | Adder | -3.68 MW | -3.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966671 | AG1-537 C | 80/20 | 1.83 MW | 1.83 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 9.74 MW | 9.74 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 9.74 MW | 9.74 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 12.6 MW | 12.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932854 | AC2-112 C | 80/20 | 5.9 MW | 5.9 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938625 | AE1-084 C | 80/20 | 2.85 MW | 2.85 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.22 MW | 0.22 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.26 MW | 8.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.62 MW | 10.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.47 MW | 7.47 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.47 MW | 0.47 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.48 MW | 1.48 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.53 MW | 0.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.28 MW | 1.28 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.23 MW | 1.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.25 MW | 0.25 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 55.97 MW | 55.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 27.08 MW | 27.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 41.52 MW | 41.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 27.68 MW | 27.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 39.37 MW | 39.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 26.3 MW | 26.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 66.44 MW | 66.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 44.29 MW | 44.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 11.07 MW | 11.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 2.21 MW | 2.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.51 MW | 1.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 5.39 MW | 5.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 43.19 MW | 43.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 28.79 MW | 28.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 22.15 MW | 22.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 55.37 MW | 55.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 37.09 MW | 37.09 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 5.13 MW | 5.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 14.17 MW | 14.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.81 MW | 0.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 5.15 MW | 5.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 21.48 MW | 21.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 11.74 MW | 11.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 13.62 MW | 13.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 9.08 MW | 9.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 8.3 MW | 8.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 5.54 MW | 5.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 45.08 MW | 45.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 21.81 MW | 21.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 33.45 MW | 33.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 22.3 MW | 22.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 31.71 MW | 31.71 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 21.18 MW | 21.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 53.51 MW | 53.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 35.67 MW | 35.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 8.92 MW | 8.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 1.78 MW | 1.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 4.34 MW | 4.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 34.78 MW | 34.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 23.19 MW | 23.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 17.84 MW | 17.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 44.59 MW | 44.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 29.88 MW | 29.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 4.13 MW | 4.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 11.42 MW | 11.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.65 MW | 0.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 17.3 MW | 17.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 9.45 MW | 9.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 10.97 MW | 10.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 7.31 MW | 7.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 6.69 MW | 6.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 4.46 MW | 4.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961791 | AG1-021 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961792 | AG1-021 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961891 | AG1-030 C | 50/50 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961892 | AG1-030 E | 50/50 | 22.44 MW | 22.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963171 | AG1-166 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963172 | AG1-166 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963181 | AG1-167 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963182 | AG1-167 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963191 | AG1-168 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963192 | AG1-168 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963201 | AG1-169 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963202 | AG1-169 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963211 | AG1-170 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963212 | AG1-170 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963301 | AG1-179 C | Adder | 3.09 MW | 2.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963311 | AG1-180 | Adder | 1.5 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963321 | AG1-181 C O1 | 50/50 | 28.68 MW | 28.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963361 | AG1-185 O1 | 50/50 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964111 | AG1-272 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964112 | AG1-272 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964121 | AG1-273 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964122 | AG1-273 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964131 | AG1-274 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964132 | AG1-274 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964241 | AG1-285 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964242 | AG1-285 E O1 | 50/50 | 10.46 MW | 10.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964791 | AG1-342 C | Adder | 2.21 MW | 1.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964792 | AG1-342 E | Adder | 1.74 MW | 1.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965191 | AG1-384 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965192 | AG1-384 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965591 | AG1-427 C | 50/50 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965592 | AG1-427 E | 50/50 | 10.05 MW | 10.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965601 | AG1-428 C O2 | Adder | 2.58 MW | 2.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965602 | AG1-428 E O2 | Adder | 1.72 MW | 1.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965641 | AG1-432 C O1 | 50/50 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965642 | AG1-432 E O1 | 50/50 | 44.61 MW | 44.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965721 | AG1-440 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965722 | AG1-440 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965731 | AG1-441 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965732 | AG1-441 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965771 | AG1-445 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965781 | AG1-446 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965831 | AG1-451 | 50/50 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313853 | 3PONTONDP | 50/50 | 1.65 MW | 1.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314429 | 3JTRSVLE | 50/50 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314713 | 3PAMPLIN | 50/50 | 4.39 MW | 4.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315159 | 1KERR 2 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315160 | 1KERR 3 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315161 | 1KERR 4 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315162 | 1KERR 5 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936265 | AD2-033 C | 50/50 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936266 | AD2-033 E | 50/50 | 14.44 MW | 14.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942461 | AE2-259 C O1 | 50/50 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942462 | AE2-259 E O1 | 50/50 | 22.31 MW | 22.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958801 | AF2-171 C | 50/50 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958802 | AF2-171 E | 50/50 | 24.61 MW | 24.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959311 | AF2-222 C | 50/50 | 31.81 MW | 31.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959312 | AF2-222 E | 50/50 | 21.32 MW | 21.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315163 | 1KERR 6 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 316131 | AB2-060 C | 50/50 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924162 | AB2-060 E OP | 50/50 | 4.68 MW | 4.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925611 | AC1-036 C | 50/50 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925612 | AC1-036 E | 50/50 | 2.81 MW | 2.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938371 | AE1-056 C | 50/50 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938372 | AE1-056 E | 50/50 | 9.57 MW | 9.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939181 | AE1-148 C | 50/50 | 6.23 MW | 6.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939182 | AE1-148 E | 50/50 | 4.16 MW | 4.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 940661 | AE2-053 O1 | 50/50 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946301 | AF1-294 C | 50/50 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946302 | AF1-294 E | 50/50 | 6.76 MW | 6.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958211 | AF2-115 C | 50/50 | 6.18 MW | 6.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958212 | AF2-115 E | 50/50 | 4.12 MW | 4.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962561 | AG1-105 C O1 | 50/50 | 5.47 MW | 5.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962562 | AG1-105 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313527 | AB2-043 C | 50/50 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924022 | AB2-043 E O1 | 50/50 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 22.36 MW | 22.36 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 31.15 MW | 31.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 19.12 MW | 19.12 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 4.76 MW | 4.04 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.06 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 60.44 MW | 60.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 40.29 MW | 40.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.52 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 4.33 MW | 3.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.48 MW | 22.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315160 | 1KERR 3 | 50/50 | 1.14 MW | 1.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925785 | AC1-054 E | Adder | 2.41 MW | 2.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 4.14 MW | 4.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 28.56 MW | 28.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.81 MW | 1.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 6.77 MW | 5.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.43 MW | 7.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.78 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.68 MW | 12.68 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.51 MW | 17.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.27 MW | 33.27 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 9.33 MW | 9.33 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 6.22 MW | 6.22 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 6.96 MW | 6.96 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 9.38 MW | 9.38 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 90.55 MW | 90.55 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 60.37 MW | 60.37 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 11.47 MW | 11.47 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 5.6 MW | 4.76 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 13.13 MW | 11.16 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.2 MW | 7.82 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.48 MW | 2.48 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.99 MW | 42.99 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.58 MW | 12.58 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.87 MW | 13.87 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.3 MW | 3.3 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.85 MW | 1.85 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.65 MW | 5.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6FARMVIL-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 33.53 MW | 33.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 22.35 MW | 22.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 25.5 MW | 25.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 4.8 MW | 4.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 3.2 MW | 3.2 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 4.35 MW | 3.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 2.12 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 31.14 MW | 31.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 15.07 MW | 15.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 19.11 MW | 19.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 12.74 MW | 12.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 5.27 MW | 5.27 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 4.14 MW | 4.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | Adder | 3.54 MW | 3.01 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | Adder | 4.75 MW | 4.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 4.96 MW | 4.96 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 1.47 MW | 1.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 18.24 MW | 18.24 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 12.19 MW | 12.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 3.63 MW | 3.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 2.42 MW | 2.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 60.43 MW | 60.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 40.28 MW | 40.28 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 6.49 MW | 5.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 4.32 MW | 3.68 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 3.75 MW | 3.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 10.07 MW | 10.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 27.16 MW | 27.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 18.11 MW | 18.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 1.6 MW | 1.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 1.09 MW | 1.09 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 4.16 MW | 4.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 22.69 MW | 22.69 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 22.47 MW | 22.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315159 | 1KERR 2 | 50/50 | 1.14 MW | 1.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925785 | AC1-054 E | Adder | 2.4 MW | 2.04 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 3.33 MW | 3.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927251 | AC1-221 C | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927252 | AC1-221 E | Adder | 1.7 MW | 1.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 4.13 MW | 4.13 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 3.94 MW | 3.94 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934341 | AD1-058 C | Adder | 4.26 MW | 3.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934342 | AD1-058 E | Adder | 1.08 MW | 0.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 13.15 MW | 13.15 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 6.17 MW | 6.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 28.55 MW | 28.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 13.44 MW | 13.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934991 | AD1-131 C | Adder | 1.4 MW | 1.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934992 | AD1-131 E | Adder | 0.93 MW | 0.79 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 23.7 MW | 23.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 15.8 MW | 15.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 3.85 MW | 3.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 30.21 MW | 30.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 20.14 MW | 20.14 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | Adder | 6.76 MW | 5.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | Adder | 4.51 MW | 3.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | Adder | 8.42 MW | 7.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | Adder | 5.62 MW | 4.77 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 2.33 MW | 2.33 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.55 MW | 1.55 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 12.67 MW | 12.67 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 17.5 MW | 17.5 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 35.85 MW | 35.85 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 23.9 MW | 23.9 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 33.26 MW | 33.26 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 22.29 MW | 22.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 9.32 MW | 9.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 6.21 MW | 6.21 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.51 MW | 1.51 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 6.95 MW | 6.95 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316129 | AC1-054 C | Adder | 5.22 MW | 4.44 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 2.19 MW | 2.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 6.05 MW | 6.05 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 2.71 MW | 2.71 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.47 MW | 0.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 2.99 MW | 2.99 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932761 | AC2-100 C | Adder | 3.91 MW | 3.32 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 932762 | AC2-100 E | Adder | 1.91 MW | 1.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 16.6 MW | 16.6 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 9.07 MW | 9.07 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 9.37 MW | 9.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 6.25 MW | 6.25 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 3.47 MW | 3.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 4.64 MW | 4.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 2.16 MW | 2.16 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 9.84 MW | 9.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 6.56 MW | 6.56 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 90.53 MW | 90.53 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 60.35 MW | 60.35 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 6.0 MW | 6.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 4.0 MW | 4.0 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 4.37 MW | 4.37 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 1.59 MW | 1.59 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 11.46 MW | 11.46 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 7.64 MW | 7.64 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.74 MW | 0.74 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | Adder | 2.86 MW | 2.43 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | Adder | 0.95 MW | 0.81 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965582 | AG1-426 BAT | Adder | 5.61 MW | 4.76 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946293 | AF1-293 BAT | Adder | 13.14 MW | 11.17 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | Adder | 9.21 MW | 7.83 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.47 MW | 2.47 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 42.92 MW | 42.92 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.48 MW | 12.48 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.8 MW | 13.8 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.75 MW | 3.75 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.29 MW | 3.29 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.62 MW | 0.62 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.7 MW | 5.7 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.65 MW | 2.65 MW |
| 6BUCKING-6BREMO 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961791 | AG1-021 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961792 | AG1-021 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961891 | AG1-030 C | 50/50 | 11.84 MW | 11.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961892 | AG1-030 E | 50/50 | 7.89 MW | 7.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963171 | AG1-166 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963172 | AG1-166 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963181 | AG1-167 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963182 | AG1-167 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963191 | AG1-168 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963192 | AG1-168 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963201 | AG1-169 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963202 | AG1-169 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963211 | AG1-170 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963212 | AG1-170 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963301 | AG1-179 C | Adder | 3.43 MW | 2.92 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963311 | AG1-180 | Adder | 1.67 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963321 | AG1-181 C O1 | 50/50 | 16.16 MW | 16.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963361 | AG1-185 O1 | 50/50 | 7.82 MW | 7.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964111 | AG1-272 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964121 | AG1-273 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964131 | AG1-274 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964241 | AG1-285 C O1 | 50/50 | 13.75 MW | 13.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964242 | AG1-285 E O1 | 50/50 | 9.16 MW | 9.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964791 | AG1-342 C | Adder | 2.86 MW | 2.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964792 | AG1-342 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965191 | AG1-384 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965591 | AG1-427 C | 50/50 | 12.98 MW | 12.98 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965592 | AG1-427 E | 50/50 | 8.67 MW | 8.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965601 | AG1-428 C O2 | Adder | 2.87 MW | 2.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965602 | AG1-428 E O2 | Adder | 1.91 MW | 1.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965641 | AG1-432 C O1 | Adder | 8.86 MW | 7.53 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965642 | AG1-432 E O1 | Adder | 5.91 MW | 5.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965721 | AG1-440 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965722 | AG1-440 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965731 | AG1-441 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965732 | AG1-441 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965771 | AG1-445 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965781 | AG1-446 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965831 | AG1-451 | Adder | 1.48 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313853 | 3PONTONDP | Adder | 0.48 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 314713 | 3PAMPLIN | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315159 | 1KERR 2 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315160 | 1KERR 3 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315161 | 1KERR 4 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315162 | 1KERR 5 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925785 | AC1-054 E | 50/50 | 7.3 MW | 7.3 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 926274 | AC1-105 E | Adder | 1.4 MW | 1.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936265 | AD2-033 C | 50/50 | 12.62 MW | 12.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936266 | AD2-033 E | 50/50 | 8.41 MW | 8.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942461 | AE2-259 C O1 | Adder | 4.43 MW | 3.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942462 | AE2-259 E O1 | Adder | 2.95 MW | 2.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958801 | AF2-171 C | 50/50 | 10.81 MW | 10.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958802 | AF2-171 E | 50/50 | 7.21 MW | 7.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959311 | AF2-222 C | 50/50 | 14.91 MW | 14.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959312 | AF2-222 E | 50/50 | 9.99 MW | 9.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315163 | 1KERR 6 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315164 | 1KERR 7 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316118 | AC1-105 C | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316129 | AC1-054 C | 50/50 | 15.84 MW | 15.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316131 | AB2-060 C | 50/50 | 1.77 MW | 1.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924162 | AB2-060 E OP | 50/50 | 4.9 MW | 4.9 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924301 | AB2-077 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924302 | AB2-077 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924311 | AB2-078 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924312 | AB2-078 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924321 | AB2-079 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924322 | AB2-079 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925611 | AC1-036 C | 50/50 | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925612 | AC1-036 E | 50/50 | 1.43 MW | 1.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938371 | AE1-056 C | Adder | 4.16 MW | 3.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938372 | AE1-056 E | Adder | 2.27 MW | 1.93 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939181 | AE1-148 C | 50/50 | 17.48 MW | 17.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939182 | AE1-148 E | 50/50 | 11.65 MW | 11.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 940661 | AE2-053 O1 | 50/50 | 6.47 MW | 6.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946301 | AF1-294 C | Adder | 2.94 MW | 2.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946302 | AF1-294 E | Adder | 1.96 MW | 1.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958211 | AF2-115 C | Adder | 1.79 MW | 1.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958212 | AF2-115 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962561 | AG1-105 C O1 | 50/50 | 6.82 MW | 6.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962562 | AG1-105 E O1 | 50/50 | 4.55 MW | 4.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313527 | AB2-043 C | 50/50 | 0.63 MW | 0.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.44 MW | 0.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.66 MW | 0.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.42 MW | 0.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.06 MW | 0.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.18 MW | 0.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.81 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.24 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.47 MW | 0.47 MW |
| Details for 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.45 MW | 0.38 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.26 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.21 MW | 0.18 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.14 MW | 0.12 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.85 MW | 0.72 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.56 MW | 0.48 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.85 MW | 0.72 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.56 MW | 0.48 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962491 | AG1-098 C O1 | Adder | 4.07 MW | 3.46 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962492 | AG1-098 E O1 | Adder | 2.71 MW | 2.31 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.98 MW | 2.53 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 4.47 MW | 3.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | 50/50 | 3.02 MW | 3.02 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | 50/50 | 4.53 MW | 4.53 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 31.21 MW | 26.53 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | 50/50 | 3.75 MW | 3.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | 50/50 | 1.83 MW | 1.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963321 | AG1-181 C O1 | Adder | 6.53 MW | 5.55 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 16.82 MW | 14.29 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963361 | AG1-185 O1 | Adder | 3.16 MW | 2.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964111 | AG1-272 C | Adder | 0.97 MW | 0.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964112 | AG1-272 E | Adder | 0.29 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964121 | AG1-273 C | Adder | 0.97 MW | 0.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964122 | AG1-273 E | Adder | 0.29 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964131 | AG1-274 C | Adder | 0.97 MW | 0.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964132 | AG1-274 E | Adder | 0.29 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 5.3 MW | 4.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 3.53 MW | 3.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.74 MW | 1.48 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.37 MW | 1.17 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.41 MW | 2.05 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.9 MW | 1.61 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.92 MW | 0.78 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.39 MW | 0.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 1.21 MW | 1.03 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.52 MW | 0.44 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965191 | AG1-384 C | Adder | 0.97 MW | 0.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965192 | AG1-384 E | Adder | 0.29 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.83 MW | 0.7 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.55 MW | 0.47 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 5.01 MW | 4.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 3.35 MW | 2.85 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | 50/50 | 3.13 MW | 3.13 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | 50/50 | 2.08 MW | 2.08 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 11.05 MW | 9.39 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 7.37 MW | 6.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 5.9 MW | 5.01 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | 50/50 | 12.52 MW | 12.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 8.75 MW | 7.44 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 5.83 MW | 4.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 8.75 MW | 7.44 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 5.83 MW | 4.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | 50/50 | 1.09 MW | 1.09 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | 50/50 | 0.73 MW | 0.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | 50/50 | 4.76 MW | 4.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.32 MW | 0.32 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.22 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.97 MW | 3.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.97 MW | 3.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315136 | 1ROSEMG1 | 50/50 | 1.41 MW | 1.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315137 | 1ROSEMS1 | 50/50 | 0.88 MW | 0.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315138 | 1ROSEMG2 | 50/50 | 0.66 MW | 0.66 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315139 | 1GASTONA | 50/50 | 2.1 MW | 2.1 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 3.66 MW | 3.11 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 2.05 MW | 1.74 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.31 MW | 0.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 2.06 MW | 1.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.72 MW | 1.46 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.15 MW | 3.53 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.24 MW | 0.2 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.75 MW | 1.49 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | 50/50 | 13.88 MW | 13.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | 50/50 | 6.32 MW | 6.32 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 3.04 MW | 2.58 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.81 MW | 1.54 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 1.02 MW | 0.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.6 MW | 0.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 1.12 MW | 0.95 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.84 MW | 3.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.91 MW | 1.62 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 4.7 MW | 4.0 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 2.09 MW | 1.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.9 MW | 0.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.9 MW | 0.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.43 MW | 1.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.36 MW | 1.16 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.0 MW | 0.85 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 5.69 MW | 4.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 3.04 MW | 2.58 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.26 MW | 1.92 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.58 MW | 0.49 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 3.43 MW | 2.92 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.61 MW | 1.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934625 | AD1-088 C | Adder | 4.49 MW | 3.82 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934626 | AD1-088 E | Adder | 2.11 MW | 1.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.74 MW | 0.63 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.5 MW | 0.42 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.56 MW | 3.02 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.37 MW | 2.02 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936265 | AD2-033 C | Adder | 5.08 MW | 4.32 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936266 | AD2-033 E | Adder | 3.38 MW | 2.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 1.0 MW | 0.85 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.47 MW | 0.4 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 19.3 MW | 19.3 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 12.87 MW | 12.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.25 MW | 0.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.79 MW | 0.68 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.53 MW | 0.45 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 7.03 MW | 7.03 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 2.73 MW | 2.73 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.42 MW | 1.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.6 MW | 3.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 4.97 MW | 4.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 6.18 MW | 5.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 4.14 MW | 3.52 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.18 MW | 2.7 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.12 MW | 1.8 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 2.02 MW | 2.02 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | 50/50 | 4.64 MW | 4.64 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 2.59 MW | 2.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 2.59 MW | 2.59 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 2.34 MW | 1.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 3.79 MW | 3.23 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.25 MW | 0.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.11 MW | 0.09 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.12 MW | 0.1 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.48 MW | 0.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.9 MW | 1.61 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | 50/50 | 9.42 MW | 9.42 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | 50/50 | 4.04 MW | 4.04 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 2.26 MW | 2.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 5.18 MW | 5.18 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 4.24 MW | 4.24 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.69 MW | 2.28 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.86 MW | 1.58 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.88 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.88 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.88 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 2.13 MW | 1.81 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 3.38 MW | 2.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.55 MW | 2.17 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.59 MW | 0.5 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 4.34 MW | 3.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 2.14 MW | 1.81 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.08 MW | 1.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.01 MW | 0.86 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.44 MW | 0.37 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.73 MW | 2.32 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 2.21 MW | 1.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.95 MW | 0.81 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 21.51 MW | 21.51 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 9.63 MW | 9.63 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941791 | AE2-182 C | Adder | 0.73 MW | 0.62 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941792 | AE2-182 E | Adder | 0.34 MW | 0.29 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.2 MW | 1.2 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 25.68 MW | 21.83 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 17.12 MW | 14.55 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.96 MW | 5.92 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.5 MW | 2.98 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 3.48 MW | 2.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.54 MW | 1.31 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 17.91 MW | 17.91 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 12.07 MW | 12.07 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 14.99 MW | 14.99 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | Adder | 0.96 MW | 0.82 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.49 MW | 0.49 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.84 MW | -2.41 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.82 MW | -0.69 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -4.08 MW | -3.47 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315141 | 1GASTONB | 50/50 | 2.1 MW | 2.1 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315241 | 1Z1-086 GT1 | 50/50 | 5.9 MW | 5.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315242 | 1Z1-086 GT2 | 50/50 | 5.9 MW | 5.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315243 | 1Z1-086 GT3 | 50/50 | 5.9 MW | 5.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315244 | 1Z1-086 ST | 50/50 | 10.26 MW | 10.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316087 | AB2-174 C | 50/50 | 0.87 MW | 0.87 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.9 MW | 0.9 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.29 MW | 1.29 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 12.81 MW | 10.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 10.98 MW | 9.33 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 12.81 MW | 10.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 8.54 MW | 7.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 7.32 MW | 6.22 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 8.54 MW | 7.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 3.26 MW | 3.26 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 3.87 MW | 3.29 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 2.08 MW | 1.77 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 3.78 MW | 3.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 2.52 MW | 2.14 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | 50/50 | 1.75 MW | 1.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 6.97 MW | 5.93 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 3.49 MW | 2.96 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | 50/50 | 3.86 MW | 3.86 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 2.49 MW | 2.49 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.66 MW | 1.66 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.59 MW | 1.35 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.24 MW | 1.06 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.56 MW | 2.56 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.76 MW | 0.76 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 46.15 MW | 46.15 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 15.21 MW | 15.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.13 MW | 16.13 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.88 MW | 3.88 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.17 MW | 1.17 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.79 MW | 3.79 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.21 MW | 0.21 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.75 MW | 0.75 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.19 MW | 2.19 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.53 MW | 0.53 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.43 MW | 7.43 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.05 MW | 3.05 MW |
| 6CARSON-6CHRL249 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.36 MW | 0.36 MW |
| Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961791 | AG1-021 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961891 | AG1-030 C | Adder | 12.01 MW | 10.21 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961892 | AG1-030 E | Adder | 8.0 MW | 6.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963171 | AG1-166 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963181 | AG1-167 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963191 | AG1-168 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963201 | AG1-169 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963211 | AG1-170 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963301 | AG1-179 C | Adder | 3.75 MW | 3.19 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963311 | AG1-180 | Adder | 1.83 MW | 1.55 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963321 | AG1-181 C O1 | 50/50 | 17.24 MW | 17.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963361 | AG1-185 O1 | 50/50 | 8.34 MW | 8.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964111 | AG1-272 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964112 | AG1-272 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964121 | AG1-273 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964122 | AG1-273 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964131 | AG1-274 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964132 | AG1-274 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964241 | AG1-285 C O1 | 50/50 | 15.1 MW | 15.1 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964242 | AG1-285 E O1 | 50/50 | 10.07 MW | 10.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964791 | AG1-342 C | 50/50 | 10.66 MW | 10.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964792 | AG1-342 E | 50/50 | 8.37 MW | 8.37 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966691 | AG1-539 C | 50/50 | 10.05 MW | 10.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966692 | AG1-539 E | 50/50 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966761 | AG1-547 C | Adder | 4.41 MW | 3.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966762 | AG1-547 E | Adder | 2.37 MW | 2.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965191 | AG1-384 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965192 | AG1-384 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965591 | AG1-427 C | 50/50 | 14.24 MW | 14.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965592 | AG1-427 E | 50/50 | 9.52 MW | 9.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965601 | AG1-428 C O2 | Adder | 3.13 MW | 2.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965602 | AG1-428 E O2 | Adder | 2.08 MW | 1.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965721 | AG1-440 C | Adder | 6.17 MW | 5.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965722 | AG1-440 E | Adder | 4.11 MW | 3.49 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965731 | AG1-441 C | Adder | 6.17 MW | 5.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965732 | AG1-441 E | Adder | 4.11 MW | 3.49 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965771 | AG1-445 | Adder | 3.56 MW | 3.03 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965781 | AG1-446 | Adder | 3.56 MW | 3.03 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 314713 | 3PAMPLIN | Adder | 0.99 MW | 0.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315156 | 1HALLBR1 | 50/50 | 1.46 MW | 1.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315159 | 1KERR 2 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315161 | 1KERR 4 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315162 | 1KERR 5 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925785 | AC1-054 E | Adder | 2.15 MW | 1.82 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926023 | AC1-080 C | 50/50 | 0.83 MW | 0.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926274 | AC1-105 E | 50/50 | 8.2 MW | 8.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926646 | AC1-145 E | Adder | 2.31 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 927261 | AC1-222 C | 50/50 | 12.09 MW | 12.09 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 927262 | AC1-222 E | 50/50 | 11.51 MW | 11.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 934311 | AD1-055 C | 50/50 | 8.39 MW | 8.39 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 934312 | AD1-055 E | 50/50 | 2.16 MW | 2.16 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 935171 | AD1-152 C O1 | Adder | -4.31 MW | -3.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 936265 | AD2-033 C | 50/50 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 936266 | AD2-033 E | 50/50 | 9.0 MW | 9.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942671 | AE2-283 C | Adder | 5.37 MW | 4.57 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942672 | AE2-283 E | Adder | 2.82 MW | 2.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942751 | AE2-291 C | 50/50 | 19.22 MW | 19.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942752 | AE2-291 E | 50/50 | 12.81 MW | 12.81 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942761 | AE2-292 C O1 | 50/50 | 23.93 MW | 23.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942762 | AE2-292 E O1 | 50/50 | 15.96 MW | 15.96 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958801 | AF2-171 C | Adder | 10.66 MW | 9.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958802 | AF2-171 E | Adder | 7.1 MW | 6.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 959311 | AF2-222 C | 50/50 | 15.64 MW | 15.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 959312 | AF2-222 E | 50/50 | 10.48 MW | 10.48 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 960061 | AF2-297 C | 50/50 | 27.34 MW | 27.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 960062 | AF2-297 E | 50/50 | 18.23 MW | 18.23 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961121 | AF2-403 | Adder | 1.08 MW | 0.92 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315164 | 1KERR 7 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315266 | 1PLYWOOD A | 50/50 | 3.88 MW | 3.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316118 | AC1-105 C | 50/50 | 17.14 MW | 17.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316129 | AC1-054 C | Adder | 4.66 MW | 3.96 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316131 | AB2-060 C | 50/50 | 1.97 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924162 | AB2-060 E OP | 50/50 | 5.43 MW | 5.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924301 | AB2-077 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924302 | AB2-077 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924311 | AB2-078 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924312 | AB2-078 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924321 | AB2-079 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924322 | AB2-079 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925611 | AC1-036 C | 50/50 | 0.24 MW | 0.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925612 | AC1-036 E | 50/50 | 1.51 MW | 1.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925661 | AC1-042 C | Adder | 2.16 MW | 1.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925662 | AC1-042 E | Adder | 3.53 MW | 3.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 938371 | AE1-056 C | Adder | 3.93 MW | 3.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 938372 | AE1-056 E | Adder | 2.15 MW | 1.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 939181 | AE1-148 C | 50/50 | 9.05 MW | 9.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 939182 | AE1-148 E | 50/50 | 6.04 MW | 6.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 940661 | AE2-053 O1 | 50/50 | 3.35 MW | 3.35 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941801 | AE2-185 C | Adder | 4.88 MW | 4.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941802 | AE2-185 E | Adder | 3.26 MW | 2.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941821 | AE2-187 C | Adder | 4.88 MW | 4.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941822 | AE2-187 E | Adder | 2.17 MW | 1.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 946301 | AF1-294 C | Adder | 2.89 MW | 2.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 946302 | AF1-294 E | Adder | 1.93 MW | 1.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958211 | AF2-115 C | Adder | 1.76 MW | 1.5 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 962561 | AG1-105 C O1 | 50/50 | 21.07 MW | 21.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 962562 | AG1-105 E O1 | 50/50 | 14.04 MW | 14.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 313527 | AB2-043 C | 50/50 | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924022 | AB2-043 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316123 | AC1-075 C | 50/50 | 2.47 MW | 2.47 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925997 | AC1-075 E | 50/50 | 8.22 MW | 8.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926024 | AC1-080 E | 50/50 | 2.73 MW | 2.73 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.15 MW | 1.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.43 MW | 0.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.13 MW | 0.13 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.84 MW | 0.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.08 MW | 0.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.45 MW | 0.38 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.26 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.21 MW | 0.18 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.14 MW | 0.12 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.85 MW | 0.72 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.56 MW | 0.48 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.85 MW | 0.72 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.56 MW | 0.48 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962491 | AG1-098 C O1 | Adder | 4.07 MW | 3.46 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962492 | AG1-098 E O1 | Adder | 2.71 MW | 2.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.98 MW | 2.53 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 4.47 MW | 3.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | 50/50 | 3.02 MW | 3.02 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | 50/50 | 4.53 MW | 4.53 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 31.21 MW | 26.53 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | 50/50 | 3.75 MW | 3.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | 50/50 | 1.83 MW | 1.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963321 | AG1-181 C O1 | Adder | 6.53 MW | 5.55 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 16.82 MW | 14.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963361 | AG1-185 O1 | Adder | 3.16 MW | 2.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964111 | AG1-272 C | Adder | 0.97 MW | 0.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964112 | AG1-272 E | Adder | 0.29 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964121 | AG1-273 C | Adder | 0.97 MW | 0.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964122 | AG1-273 E | Adder | 0.29 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964131 | AG1-274 C | Adder | 0.97 MW | 0.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964132 | AG1-274 E | Adder | 0.29 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 5.3 MW | 4.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 3.53 MW | 3.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.74 MW | 1.48 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.37 MW | 1.17 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.41 MW | 2.05 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.9 MW | 1.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.92 MW | 0.78 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.39 MW | 0.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 1.21 MW | 1.03 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.52 MW | 0.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965191 | AG1-384 C | Adder | 0.97 MW | 0.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965192 | AG1-384 E | Adder | 0.29 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.83 MW | 0.7 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.55 MW | 0.47 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 5.01 MW | 4.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 3.35 MW | 2.85 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | 50/50 | 3.13 MW | 3.13 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | 50/50 | 2.08 MW | 2.08 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 11.05 MW | 9.39 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 7.37 MW | 6.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 3.59 MW | 3.05 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 2.39 MW | 2.03 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 3.59 MW | 3.05 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 2.39 MW | 2.03 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 5.9 MW | 5.01 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 2.07 MW | 1.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 2.07 MW | 1.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | 50/50 | 12.52 MW | 12.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 8.75 MW | 7.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 5.83 MW | 4.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 8.75 MW | 7.44 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 5.83 MW | 4.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | 50/50 | 1.09 MW | 1.09 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | 50/50 | 0.73 MW | 0.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | 50/50 | 4.76 MW | 4.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.32 MW | 0.32 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314704 | 3LAWRENC | 50/50 | 0.22 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.97 MW | 3.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.97 MW | 3.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315136 | 1ROSEMG1 | 50/50 | 1.41 MW | 1.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315137 | 1ROSEMS1 | 50/50 | 0.88 MW | 0.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315138 | 1ROSEMG2 | 50/50 | 0.66 MW | 0.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315139 | 1GASTONA | 50/50 | 2.1 MW | 2.1 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 3.66 MW | 3.11 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 2.05 MW | 1.74 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.31 MW | 0.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 2.06 MW | 1.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.72 MW | 1.46 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.15 MW | 3.53 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.24 MW | 0.2 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.75 MW | 1.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | 50/50 | 13.88 MW | 13.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | 50/50 | 6.32 MW | 6.32 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 3.04 MW | 2.58 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.81 MW | 1.54 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 1.02 MW | 0.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.6 MW | 0.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 1.12 MW | 0.95 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.84 MW | 3.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.91 MW | 1.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 4.7 MW | 4.0 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 2.09 MW | 1.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927251 | AC1-221 C | Adder | 0.9 MW | 0.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927252 | AC1-221 E | Adder | 0.9 MW | 0.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927261 | AC1-222 C | Adder | 1.43 MW | 1.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927262 | AC1-222 E | Adder | 1.36 MW | 1.16 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934311 | AD1-055 C | Adder | 1.0 MW | 0.85 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 5.69 MW | 4.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 3.04 MW | 2.58 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934341 | AD1-058 C | Adder | 2.26 MW | 1.92 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934342 | AD1-058 E | Adder | 0.58 MW | 0.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 3.43 MW | 2.92 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.61 MW | 1.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934625 | AD1-088 C | Adder | 4.49 MW | 3.82 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934626 | AD1-088 E | Adder | 2.11 MW | 1.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934991 | AD1-131 C | Adder | 0.74 MW | 0.63 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934992 | AD1-131 E | Adder | 0.5 MW | 0.42 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 3.56 MW | 3.02 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 2.37 MW | 2.02 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936265 | AD2-033 C | Adder | 5.08 MW | 4.32 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936266 | AD2-033 E | Adder | 3.38 MW | 2.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 1.0 MW | 0.85 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.47 MW | 0.4 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | 50/50 | 19.3 MW | 19.3 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | 50/50 | 12.87 MW | 12.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.25 MW | 0.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943901 | AF1-058 C | Adder | 0.79 MW | 0.68 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943902 | AF1-058 E | Adder | 0.53 MW | 0.45 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | 50/50 | 7.03 MW | 7.03 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | 50/50 | 2.73 MW | 2.73 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.42 MW | 1.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 3.6 MW | 3.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 4.97 MW | 4.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959311 | AF2-222 C | Adder | 6.18 MW | 5.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 959312 | AF2-222 E | Adder | 4.14 MW | 3.52 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960061 | AF2-297 C | Adder | 3.18 MW | 2.7 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960062 | AF2-297 E | Adder | 2.12 MW | 1.8 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 2.02 MW | 2.02 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | 50/50 | 4.64 MW | 4.64 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 2.59 MW | 2.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 2.59 MW | 2.59 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 2.34 MW | 1.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 3.79 MW | 3.23 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.25 MW | 0.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.11 MW | 0.09 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.12 MW | 0.1 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.48 MW | 0.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.29 MW | 0.25 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.9 MW | 1.61 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | 50/50 | 9.42 MW | 9.42 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | 50/50 | 4.04 MW | 4.04 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | 50/50 | 2.26 MW | 2.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | 50/50 | 5.18 MW | 5.18 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | 50/50 | 4.24 MW | 4.24 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.69 MW | 2.28 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.86 MW | 1.58 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.88 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.88 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.88 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 2.13 MW | 1.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 3.38 MW | 2.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.55 MW | 2.17 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925612 | AC1-036 E | Adder | 0.59 MW | 0.5 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 4.34 MW | 3.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 2.14 MW | 1.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932761 | AC2-100 C | Adder | 2.08 MW | 1.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932762 | AC2-100 E | Adder | 1.01 MW | 0.86 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.44 MW | 0.37 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 4.1 MW | 3.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.73 MW | 2.32 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 2.21 MW | 1.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.95 MW | 0.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.52 MW | 1.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | 50/50 | 21.51 MW | 21.51 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | 50/50 | 9.63 MW | 9.63 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941791 | AE2-182 C | Adder | 0.73 MW | 0.62 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941792 | AE2-182 E | Adder | 0.34 MW | 0.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 1.2 MW | 1.2 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.81 MW | 0.81 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 25.68 MW | 21.83 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 17.12 MW | 14.55 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.96 MW | 5.92 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.5 MW | 2.98 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 3.48 MW | 2.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.54 MW | 1.31 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 17.91 MW | 17.91 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 12.07 MW | 12.07 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 14.99 MW | 14.99 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | Adder | 0.96 MW | 0.82 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.49 MW | 0.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.84 MW | -2.41 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.82 MW | -0.69 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -4.08 MW | -3.47 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315141 | 1GASTONB | 50/50 | 2.1 MW | 2.1 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315241 | 1Z1-086 GT1 | 50/50 | 5.9 MW | 5.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315242 | 1Z1-086 GT2 | 50/50 | 5.9 MW | 5.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315243 | 1Z1-086 GT3 | 50/50 | 5.9 MW | 5.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315244 | 1Z1-086 ST | 50/50 | 10.26 MW | 10.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316087 | AB2-174 C | 50/50 | 0.87 MW | 0.87 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.9 MW | 0.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.9 MW | 0.9 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.29 MW | 1.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 12.81 MW | 10.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 10.98 MW | 9.33 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 12.81 MW | 10.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 8.54 MW | 7.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 7.32 MW | 6.22 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 8.54 MW | 7.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 3.26 MW | 3.26 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 3.87 MW | 3.29 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 2.08 MW | 1.77 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 3.78 MW | 3.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 2.52 MW | 2.14 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | 50/50 | 1.75 MW | 1.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 6.97 MW | 5.93 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 3.49 MW | 2.96 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | 50/50 | 3.86 MW | 3.86 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 2.49 MW | 2.49 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.66 MW | 1.66 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.59 MW | 1.35 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 1.24 MW | 1.06 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.56 MW | 2.56 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.76 MW | 0.76 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 46.15 MW | 46.15 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 15.21 MW | 15.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.13 MW | 16.13 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.88 MW | 3.88 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.17 MW | 1.17 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.79 MW | 3.79 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.21 MW | 0.21 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.75 MW | 0.75 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.19 MW | 2.19 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.53 MW | 0.53 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.43 MW | 7.43 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.05 MW | 3.05 MW |
| 6CHRL249-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.36 MW | 0.36 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.36 MW | 0.31 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.17 MW | 0.15 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.7 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.46 MW | 0.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.7 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.46 MW | 0.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.34 MW | 1.99 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 3.51 MW | 2.98 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 2.38 MW | 2.02 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 3.56 MW | 3.03 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 24.66 MW | 20.96 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | Adder | 2.94 MW | 2.5 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | Adder | 1.43 MW | 1.22 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 13.29 MW | 11.29 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 4.17 MW | 3.54 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 2.78 MW | 2.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.37 MW | 1.17 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.08 MW | 0.92 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.04 MW | 1.73 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.6 MW | 1.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.74 MW | 0.63 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.32 MW | 0.27 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 0.97 MW | 0.82 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.41 MW | 0.35 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.7 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.47 MW | 0.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 3.94 MW | 3.35 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 2.63 MW | 2.24 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | Adder | 2.46 MW | 2.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | Adder | 1.63 MW | 1.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 8.83 MW | 7.51 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 5.89 MW | 5.01 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 2.84 MW | 2.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 1.89 MW | 1.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 2.84 MW | 2.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 1.89 MW | 1.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 4.71 MW | 4.0 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 1.64 MW | 1.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 1.64 MW | 1.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 9.84 MW | 8.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 6.87 MW | 5.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 4.58 MW | 3.9 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 6.87 MW | 5.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 4.58 MW | 3.9 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | 50/50 | 0.85 MW | 0.85 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | 50/50 | 0.57 MW | 0.57 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | 3.75 MW | 3.18 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | 50/50 | 0.25 MW | 0.25 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.15 MW | 2.68 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.15 MW | 2.68 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.92 MW | 2.48 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.67 MW | 1.42 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.65 MW | 1.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.37 MW | 1.17 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 3.54 MW | 3.01 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.19 MW | 0.16 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.39 MW | 1.18 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | Adder | 10.95 MW | 9.3 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | Adder | 4.98 MW | 4.24 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.44 MW | 2.07 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.45 MW | 1.23 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.82 MW | 0.69 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 0.88 MW | 0.75 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.07 MW | 2.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.53 MW | 1.3 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 3.75 MW | 3.19 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 1.67 MW | 1.42 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.5 MW | 3.83 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.41 MW | 2.04 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 2.7 MW | 2.29 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.26 MW | 1.07 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.8 MW | 2.38 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.86 MW | 1.58 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.79 MW | 0.67 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.37 MW | 0.32 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 15.17 MW | 12.89 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 10.11 MW | 8.6 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.49 MW | 0.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.21 MW | 0.18 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.52 MW | 4.7 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.15 MW | 1.82 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.13 MW | 0.96 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.82 MW | 2.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.9 MW | 3.32 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | 50/50 | 1.58 MW | 1.58 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | 50/50 | 1.05 MW | 1.05 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | Adder | 3.65 MW | 3.1 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 2.02 MW | 2.02 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 2.02 MW | 2.02 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 1.84 MW | 1.56 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 3.01 MW | 2.56 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.2 MW | 0.17 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.09 MW | 0.07 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.1 MW | 0.09 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.39 MW | 0.33 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.23 MW | 0.2 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.51 MW | 1.28 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.43 MW | 6.32 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.19 MW | 2.71 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 1.78 MW | 1.51 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 4.08 MW | 3.47 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.34 MW | 2.84 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.13 MW | 1.81 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.46 MW | 1.25 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.69 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.46 MW | 0.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.69 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.46 MW | 0.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.69 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.46 MW | 0.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.68 MW | 2.28 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 2.02 MW | 1.72 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.47 MW | 2.95 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.71 MW | 1.45 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.36 MW | 0.3 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 3.24 MW | 2.75 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.16 MW | 1.83 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.76 MW | 1.49 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.75 MW | 0.64 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.2 MW | 1.02 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 16.9 MW | 14.37 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.57 MW | 6.44 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | 50/50 | 0.94 MW | 0.94 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | 50/50 | 0.63 MW | 0.63 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 20.18 MW | 17.15 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 13.45 MW | 11.43 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 5.8 MW | 4.93 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 2.92 MW | 2.48 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.79 MW | 2.37 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.24 MW | 1.05 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 13.88 MW | 13.88 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 9.36 MW | 9.36 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 11.62 MW | 11.62 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314314 | 3LOCKS | 50/50 | 0.44 MW | 0.44 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | Adder | 0.71 MW | 0.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.38 MW | 0.38 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -2.43 MW | -2.06 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | Adder | 2.42 MW | 2.05 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934576 | AD1-082 E | Adder | 1.38 MW | 1.17 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.73 MW | -0.62 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.67 MW | -3.12 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942371 | AE2-250 C O1 | 50/50 | 14.0 MW | 14.0 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942372 | AE2-250 E O1 | 50/50 | 7.39 MW | 7.39 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.7 MW | 0.7 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.7 MW | 0.7 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316108 | AB2-160 C | 50/50 | 7.88 MW | 7.88 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316109 | AB2-160 E | 50/50 | 12.86 MW | 12.86 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 1.0 MW | 1.0 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939195 | AE1-149 C | Adder | 3.62 MW | 3.08 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939196 | AE1-149 E | Adder | 2.42 MW | 2.05 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 10.25 MW | 8.71 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 8.78 MW | 7.47 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 10.25 MW | 8.71 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 6.83 MW | 5.81 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 5.86 MW | 4.98 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 6.83 MW | 5.81 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940431 | AE2-027 C O1 | 50/50 | 11.69 MW | 11.69 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940432 | AE2-027 E O1 | 50/50 | 7.79 MW | 7.79 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 2.53 MW | 2.53 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | Adder | 1.21 MW | 1.03 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 3.07 MW | 2.61 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 1.65 MW | 1.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 2.97 MW | 2.52 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 1.98 MW | 1.68 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | Adder | 1.38 MW | 1.17 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 5.81 MW | 4.94 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 2.91 MW | 2.47 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962271 | AG1-075 C O1 | 50/50 | 24.16 MW | 24.16 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962272 | AG1-075 E O1 | 50/50 | 14.72 MW | 14.72 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | Adder | 3.04 MW | 2.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 1.93 MW | 1.93 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.29 MW | 1.29 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.3 MW | 1.11 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.98 MW | 0.83 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | Adder | 1.06 MW | 0.9 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316084 | AB2-161 E | Adder | 1.73 MW | 1.47 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 2.02 MW | 2.02 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.6 MW | 0.6 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 36.41 MW | 36.41 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.9 MW | 11.9 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 12.67 MW | 12.67 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 3.06 MW | 3.06 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.93 MW | 0.93 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.98 MW | 2.98 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.59 MW | 0.59 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.72 MW | 1.72 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.42 MW | 0.42 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.92 MW | 5.92 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.4 MW | 2.4 MW |
| 6LOCKS-6HARR205 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.28 MW | 0.28 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961891 | AG1-030 C | Adder | 6.32 MW | 5.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961892 | AG1-030 E | Adder | 4.21 MW | 3.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963301 | AG1-179 C | Adder | 3.52 MW | 3.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963311 | AG1-180 | Adder | 1.72 MW | 1.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965601 | AG1-428 C O2 | Adder | 2.94 MW | 2.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965602 | AG1-428 E O2 | Adder | 1.96 MW | 1.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962561 | AG1-105 C O1 | Adder | 3.79 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 962562 | AG1-105 E O1 | Adder | 2.53 MW | 2.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.31 MW | 2.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.91 MW | 0.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 102952 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 16.45 MW | 16.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 12.93 MW | 12.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | 50/50 | 12.87 MW | 12.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | 50/50 | 26.91 MW | 26.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.35 MW | 0.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.73 MW | 0.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.49 MW | 0.41 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.73 MW | 0.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.49 MW | 0.41 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.2 MW | 1.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 3.3 MW | 2.8 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 2.23 MW | 1.9 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 3.34 MW | 2.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 23.42 MW | 19.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | Adder | 2.75 MW | 2.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | Adder | 1.34 MW | 1.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 12.62 MW | 10.72 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 3.95 MW | 3.35 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 2.63 MW | 2.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.3 MW | 1.1 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.02 MW | 0.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.3 MW | 1.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.81 MW | 1.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.75 MW | 0.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.32 MW | 0.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 0.94 MW | 0.8 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.4 MW | 0.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.79 MW | 0.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.53 MW | 0.45 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 3.73 MW | 3.17 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 2.49 MW | 2.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | Adder | 2.3 MW | 1.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | Adder | 1.53 MW | 1.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965691 | AG1-437 C O1 | Adder | 3.13 MW | 2.66 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965692 | AG1-437 E O1 | Adder | 2.09 MW | 1.77 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965701 | AG1-438 C O1 | Adder | 3.13 MW | 2.66 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965702 | AG1-438 E O1 | Adder | 2.09 MW | 1.77 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 8.7 MW | 7.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 5.8 MW | 4.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 2.73 MW | 2.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 1.82 MW | 1.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 2.73 MW | 2.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 1.82 MW | 1.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965741 | AG1-442 O1 | Adder | 1.83 MW | 1.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965751 | AG1-443 O1 | Adder | 1.83 MW | 1.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 4.64 MW | 3.94 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 1.58 MW | 1.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 1.58 MW | 1.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 9.23 MW | 7.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 6.45 MW | 5.48 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 4.3 MW | 3.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 6.45 MW | 5.48 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 4.3 MW | 3.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | Adder | 0.8 MW | 0.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | Adder | 0.53 MW | 0.45 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | 3.56 MW | 3.02 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.25 MW | 0.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | Adder | 0.24 MW | 0.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.05 MW | 2.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.05 MW | 2.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.88 MW | 2.45 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.71 MW | 1.46 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.62 MW | 1.38 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.34 MW | 1.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.07 MW | 3.46 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.18 MW | 0.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.34 MW | 1.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | Adder | 10.42 MW | 8.86 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | Adder | 4.74 MW | 4.03 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.42 MW | 2.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.44 MW | 1.22 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.81 MW | 0.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 0.83 MW | 0.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.05 MW | 2.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.52 MW | 1.29 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 3.68 MW | 3.13 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 1.64 MW | 1.39 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.32 MW | 3.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.31 MW | 1.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 2.53 MW | 2.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.19 MW | 1.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.63 MW | 2.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.76 MW | 1.49 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.74 MW | 0.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.35 MW | 0.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 14.22 MW | 12.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 9.48 MW | 8.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.51 MW | 0.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.22 MW | 0.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.18 MW | 4.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.01 MW | 1.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.1 MW | 0.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.65 MW | 2.25 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.66 MW | 3.11 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | Adder | 1.47 MW | 1.25 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | Adder | 0.98 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | Adder | 3.44 MW | 2.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 1.87 MW | 1.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 1.87 MW | 1.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 1.74 MW | 1.48 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 2.91 MW | 2.48 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.21 MW | 0.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.11 MW | 0.1 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.39 MW | 0.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.46 MW | 1.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.08 MW | 6.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.03 MW | 2.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 1.69 MW | 1.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 3.87 MW | 3.29 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.17 MW | 2.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.07 MW | 1.76 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.39 MW | 1.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 1.81 MW | 1.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.6 MW | 2.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 1.96 MW | 1.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.45 MW | 2.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.7 MW | 1.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.37 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 3.09 MW | 2.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.06 MW | 1.75 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.7 MW | 1.45 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.73 MW | 0.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.15 MW | 0.97 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 15.85 MW | 13.48 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.1 MW | 6.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | Adder | 0.87 MW | 0.74 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | Adder | 0.59 MW | 0.5 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 18.95 MW | 16.11 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 12.63 MW | 10.74 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.34 MW | 5.39 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.19 MW | 2.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.77 MW | 2.35 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.23 MW | 1.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314539 | 3UNCAMP | Adder | 2.18 MW | 1.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938771 | AE1-103 C | Adder | 1.03 MW | 0.88 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938772 | AE1-103 E | Adder | 1.43 MW | 1.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 12.59 MW | 12.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 8.49 MW | 8.49 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 10.54 MW | 10.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | 50/50 | 4.81 MW | 4.81 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.34 MW | 0.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -1.94 MW | -1.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | 50/50 | 8.21 MW | 8.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934576 | AD1-082 E | 50/50 | 4.68 MW | 4.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936661 | AD2-085 C | Adder | 1.91 MW | 1.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936662 | AD2-085 E | Adder | 3.12 MW | 2.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.7 MW | -0.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.52 MW | -3.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942341 | AE2-247 C | Adder | 0.83 MW | 0.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942342 | AE2-247 E | Adder | 1.15 MW | 0.98 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943461 | AF1-017 C | Adder | 0.75 MW | 0.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943462 | AF1-017 E | Adder | 1.23 MW | 1.05 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.65 MW | 0.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.65 MW | 0.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 0.9 MW | 0.9 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932591 | AC2-079 C O1 | 50/50 | 4.15 MW | 4.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932592 | AC2-079 E O1 | 50/50 | 6.78 MW | 6.78 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939195 | AE1-149 C | 50/50 | 12.93 MW | 12.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939196 | AE1-149 E | 50/50 | 8.62 MW | 8.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 10.02 MW | 8.52 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 8.59 MW | 7.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 10.02 MW | 8.52 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 6.68 MW | 5.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 5.73 MW | 4.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 6.68 MW | 5.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 2.29 MW | 2.29 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | 50/50 | 4.31 MW | 4.31 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941101 | AE2-104 C O1 | Adder | 1.1 MW | 0.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941102 | AE2-104 E O1 | Adder | 1.74 MW | 1.48 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958161 | AF2-110 C | Adder | 0.45 MW | 0.39 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958162 | AF2-110 E | Adder | 0.71 MW | 0.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933981 | AD1-022 C | Adder | 2.62 MW | 2.23 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933982 | AD1-022 E | Adder | 1.42 MW | 1.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 2.98 MW | 2.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 1.6 MW | 1.36 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 2.81 MW | 2.39 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 1.87 MW | 1.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | Adder | 1.31 MW | 1.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 6.35 MW | 5.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 3.18 MW | 2.7 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | Adder | 2.9 MW | 2.46 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 1.75 MW | 1.75 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.17 MW | 1.17 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.35 MW | 1.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.93 MW | 0.79 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | 50/50 | 3.6 MW | 3.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316084 | AB2-161 E | 50/50 | 5.88 MW | 5.88 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.93 MW | 1.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 34.67 MW | 34.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.22 MW | 11.22 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 12.01 MW | 12.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.92 MW | 2.92 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.9 MW | 0.9 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.83 MW | 2.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.55 MW | 0.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.62 MW | 1.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.72 MW | 5.72 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.28 MW | 2.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| Details for 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961671 | AG1-007 C | Adder | 0.35 MW | 0.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961672 | AG1-007 E | Adder | 0.2 MW | 0.17 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961941 | AG1-037 C | Adder | 0.18 MW | 0.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961942 | AG1-037 E | Adder | 0.12 MW | 0.1 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962331 | AG1-082 C | Adder | 0.73 MW | 0.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962332 | AG1-082 E | Adder | 0.49 MW | 0.41 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962341 | AG1-083 C | Adder | 0.73 MW | 0.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962342 | AG1-083 E | Adder | 0.49 MW | 0.41 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963041 | AG1-153 C | Adder | 2.2 MW | 1.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963042 | AG1-153 E | Adder | 3.3 MW | 2.8 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963111 | AG1-160 C | Adder | 2.23 MW | 1.9 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963112 | AG1-160 E | Adder | 3.34 MW | 2.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963291 | AG1-178 C O2 | Adder | 23.42 MW | 19.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963301 | AG1-179 C | Adder | 2.75 MW | 2.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963311 | AG1-180 | Adder | 1.34 MW | 1.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 963351 | AG1-184 O2 | Adder | 12.62 MW | 10.72 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964241 | AG1-285 C O1 | Adder | 3.95 MW | 3.35 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964242 | AG1-285 E O1 | Adder | 2.63 MW | 2.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964791 | AG1-342 C | Adder | 1.3 MW | 1.1 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964792 | AG1-342 E | Adder | 1.02 MW | 0.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964801 | AG1-343 C | Adder | 2.3 MW | 1.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 964802 | AG1-343 E | Adder | 1.81 MW | 1.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966801 | AG1-551 C | Adder | 0.75 MW | 0.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966802 | AG1-551 E | Adder | 0.32 MW | 0.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966811 | AG1-552 C | Adder | 0.94 MW | 0.8 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966812 | AG1-552 E | Adder | 0.4 MW | 0.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965291 | AG1-394 C | Adder | 0.79 MW | 0.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965292 | AG1-394 E | Adder | 0.53 MW | 0.45 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965591 | AG1-427 C | Adder | 3.73 MW | 3.17 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965592 | AG1-427 E | Adder | 2.49 MW | 2.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965601 | AG1-428 C O2 | Adder | 2.3 MW | 1.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965602 | AG1-428 E O2 | Adder | 1.53 MW | 1.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965691 | AG1-437 C O1 | Adder | 3.13 MW | 2.66 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965692 | AG1-437 E O1 | Adder | 2.09 MW | 1.77 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965701 | AG1-438 C O1 | Adder | 3.13 MW | 2.66 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965702 | AG1-438 E O1 | Adder | 2.09 MW | 1.77 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965711 | AG1-439 C O1 | Adder | 8.7 MW | 7.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965712 | AG1-439 E O1 | Adder | 5.8 MW | 4.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965721 | AG1-440 C | Adder | 2.73 MW | 2.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965722 | AG1-440 E | Adder | 1.82 MW | 1.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965731 | AG1-441 C | Adder | 2.73 MW | 2.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965732 | AG1-441 E | Adder | 1.82 MW | 1.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965741 | AG1-442 O1 | Adder | 1.83 MW | 1.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965751 | AG1-443 O1 | Adder | 1.83 MW | 1.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965761 | AG1-444 O1 | Adder | 4.64 MW | 3.94 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965771 | AG1-445 | Adder | 1.58 MW | 1.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965781 | AG1-446 | Adder | 1.58 MW | 1.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965811 | AG1-449 | Adder | 9.23 MW | 7.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966361 | AG1-505 C | Adder | 6.45 MW | 5.48 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966362 | AG1-505 E | Adder | 4.3 MW | 3.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966371 | AG1-506 C | Adder | 6.45 MW | 5.48 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966372 | AG1-506 E | Adder | 4.3 MW | 3.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966621 | AG1-532 C | Adder | 0.8 MW | 0.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 966622 | AG1-532 E | Adder | 0.53 MW | 0.45 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 313506 | AB1-173 C OP | Adder | 3.56 MW | 3.02 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314541 | 3WATKINS | Adder | 0.25 MW | 0.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314572 | 3EMPORIA | Adder | 0.24 MW | 0.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315131 | 1EDGECMA | Adder | 3.05 MW | 2.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315132 | 1EDGECMB | Adder | 3.05 MW | 2.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917512 | Z2-088 E OP1 | Adder | 2.88 MW | 2.45 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918492 | AA1-063AE OP | Adder | 1.71 MW | 1.46 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919692 | AA2-053 E OP | Adder | 1.62 MW | 1.38 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 919702 | AA2-057 E OP | Adder | 1.34 MW | 1.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920042 | AA2-088 E OP | Adder | 4.07 MW | 3.46 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 920592 | AA2-165 E | Adder | 0.18 MW | 0.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925785 | AC1-054 E | Adder | 1.34 MW | 1.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926070 | AC1-086 C | Adder | 10.42 MW | 8.86 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926071 | AC1-086 E | Adder | 4.74 MW | 4.03 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926201 | AC1-098 C | Adder | 2.42 MW | 2.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926202 | AC1-098 E | Adder | 1.44 MW | 1.22 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926211 | AC1-099 C | Adder | 0.81 MW | 0.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 926274 | AC1-105 E | Adder | 0.83 MW | 0.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927024 | AC1-189 C | Adder | 3.05 MW | 2.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927025 | AC1-189 E | Adder | 1.52 MW | 1.29 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927145 | AC1-208 C | Adder | 3.68 MW | 3.13 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 927146 | AC1-208 E | Adder | 1.64 MW | 1.39 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934331 | AD1-057 C O1 | Adder | 4.32 MW | 3.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934332 | AD1-057 E O1 | Adder | 2.31 MW | 1.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934615 | AD1-087 C | Adder | 2.53 MW | 2.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934616 | AD1-087 E | Adder | 1.19 MW | 1.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935171 | AD1-152 C O1 | Adder | 2.63 MW | 2.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 935172 | AD1-152 E O1 | Adder | 1.76 MW | 1.49 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937481 | AD2-202 C O1 | Adder | 0.74 MW | 0.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 937482 | AD2-202 E O1 | Adder | 0.35 MW | 0.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942931 | AE2-313 C | Adder | 14.22 MW | 12.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942932 | AE2-313 E | Adder | 9.48 MW | 8.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943171 | AE2-346 C | Adder | 0.51 MW | 0.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943172 | AE2-346 E | Adder | 0.22 MW | 0.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944011 | AF1-069 C | Adder | 5.18 MW | 4.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944012 | AF1-069 E | Adder | 2.01 MW | 1.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 944141 | AF1-082 | Adder | 1.1 MW | 0.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945811 | AF1-246 C O1 | Adder | 2.65 MW | 2.25 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 945812 | AF1-246 E O1 | Adder | 3.66 MW | 3.11 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960081 | AF2-299 C | Adder | 1.47 MW | 1.25 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960082 | AF2-299 E | Adder | 0.98 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316088 | AB2-174 E | Adder | 3.44 MW | 2.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316097 | AB2-100 E1 | 50/50 | 1.87 MW | 1.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316099 | AB2-100 E2 | 50/50 | 1.87 MW | 1.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316118 | AC1-105 C | Adder | 1.74 MW | 1.48 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316129 | AC1-054 C | Adder | 2.91 MW | 2.48 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316140 | AB2-099 C | Adder | 0.21 MW | 0.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316141 | AB2-099 E | Adder | 0.09 MW | 0.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 900672 | V4-068 E | Adder | 0.11 MW | 0.1 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917332 | Z2-043 E | Adder | 0.39 MW | 0.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 922923 | AB1-081 E OP | Adder | 1.46 MW | 1.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923262 | AB1-132 C OP | Adder | 7.08 MW | 6.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923263 | AB1-132 E OP | Adder | 3.03 MW | 2.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923573 | AB1-173 E OP | Adder | 1.69 MW | 1.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923991 | AB2-040 C O1 | Adder | 3.87 MW | 3.29 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923992 | AB2-040 E O1 | Adder | 3.17 MW | 2.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924152 | AB2-059 E OP | Adder | 2.07 MW | 1.76 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924162 | AB2-060 E OP | Adder | 1.39 MW | 1.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924301 | AB2-077 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924302 | AB2-077 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924311 | AB2-078 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924312 | AB2-078 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924321 | AB2-079 C O1 | Adder | 0.66 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924322 | AB2-079 E O1 | Adder | 0.44 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925122 | AB2-169 E | Adder | 1.81 MW | 1.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925591 | AC1-034 C | Adder | 2.6 MW | 2.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 925592 | AC1-034 E | Adder | 1.96 MW | 1.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932631 | AC2-084 C | Adder | 3.45 MW | 2.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932632 | AC2-084 E | Adder | 1.7 MW | 1.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938222 | AE1-035 E | Adder | 0.37 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939181 | AE1-148 C | Adder | 3.09 MW | 2.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939182 | AE1-148 E | Adder | 2.06 MW | 1.75 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940571 | AE2-044 C | Adder | 1.7 MW | 1.45 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940572 | AE2-044 E | Adder | 0.73 MW | 0.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940661 | AE2-053 O1 | Adder | 1.15 MW | 0.97 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941031 | AE2-094 C | Adder | 15.85 MW | 13.48 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941032 | AE2-094 E | Adder | 7.1 MW | 6.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946281 | AF1-292 C | Adder | 0.87 MW | 0.74 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946282 | AF1-292 E | Adder | 0.59 MW | 0.5 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957481 | AF2-042 C | Adder | 18.95 MW | 16.11 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957482 | AF2-042 E | Adder | 12.63 MW | 10.74 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957521 | AF2-046 C | Adder | 6.34 MW | 5.39 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957522 | AF2-046 E | Adder | 3.19 MW | 2.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957861 | AF2-080 C | Adder | 2.77 MW | 2.35 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 957862 | AF2-080 E | Adder | 1.23 MW | 1.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314539 | 3UNCAMP | Adder | 2.18 MW | 1.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938771 | AE1-103 C | Adder | 1.03 MW | 0.88 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 938772 | AE1-103 E | Adder | 1.43 MW | 1.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940481 | AE2-033 C | 50/50 | 12.59 MW | 12.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940482 | AE2-033 E | 50/50 | 8.49 MW | 8.49 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 946011 | AF1-266 | 50/50 | 10.54 MW | 10.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314331 | 6POE | 50/50 | 4.81 MW | 4.81 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 314435 | 6SAPONY | 50/50 | 0.34 MW | 0.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 315073 | 1STONECA | Adder | -1.94 MW | -1.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934575 | AD1-082 C | 50/50 | 8.21 MW | 8.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 934576 | AD1-082 E | 50/50 | 4.68 MW | 4.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936661 | AD2-085 C | Adder | 1.91 MW | 1.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936662 | AD2-085 E | Adder | 3.12 MW | 2.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936761 | AD2-097 C | Adder | -0.7 MW | -0.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 936762 | AD2-097 E | Adder | -3.52 MW | -3.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942341 | AE2-247 C | Adder | 0.83 MW | 0.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 942342 | AE2-247 E | Adder | 1.15 MW | 0.98 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943461 | AF1-017 C | Adder | 0.75 MW | 0.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 943462 | AF1-017 E | Adder | 1.23 MW | 1.05 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316096 | AB2-100 C1 | 50/50 | 0.65 MW | 0.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316098 | AB2-100 C2 | 50/50 | 0.65 MW | 0.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 923852 | AB2-025 E | 50/50 | 0.9 MW | 0.9 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932591 | AC2-079 C O1 | 50/50 | 4.15 MW | 4.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 932592 | AC2-079 E O1 | 50/50 | 6.78 MW | 6.78 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939195 | AE1-149 C | 50/50 | 12.93 MW | 12.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939196 | AE1-149 E | 50/50 | 8.62 MW | 8.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939414 | AE1-173_C1 | Adder | 10.02 MW | 8.52 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939415 | AE1-173_C2 | Adder | 8.59 MW | 7.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939416 | AE1-173_C3 | Adder | 10.02 MW | 8.52 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939423 | AE1-173_E1 | Adder | 6.68 MW | 5.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939424 | AE1-173_E2 | Adder | 5.73 MW | 4.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 939425 | AE1-173_E3 | Adder | 6.68 MW | 5.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940541 | AE2-040 | 50/50 | 2.29 MW | 2.29 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 940651 | AE2-052 | 50/50 | 4.31 MW | 4.31 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941101 | AE2-104 C O1 | Adder | 1.1 MW | 0.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 941102 | AE2-104 E O1 | Adder | 1.74 MW | 1.48 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958161 | AF2-110 C | Adder | 0.45 MW | 0.39 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 958162 | AF2-110 E | Adder | 0.71 MW | 0.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933981 | AD1-022 C | Adder | 2.62 MW | 2.23 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 933982 | AD1-022 E | Adder | 1.42 MW | 1.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960331 | AF2-324 C | Adder | 2.98 MW | 2.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 960332 | AF2-324 E | Adder | 1.6 MW | 1.36 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962561 | AG1-105 C O1 | Adder | 2.81 MW | 2.39 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962562 | AG1-105 E O1 | Adder | 1.87 MW | 1.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962572 | AG1-106 E | Adder | 1.31 MW | 1.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961681 | AG1-008 C | Adder | 6.35 MW | 5.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 961682 | AG1-008 E | Adder | 3.18 MW | 2.7 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 962571 | AG1-106 C | Adder | 2.9 MW | 2.46 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965281 | AG1-393 C | 50/50 | 1.75 MW | 1.75 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 965282 | AG1-393 E | 50/50 | 1.17 MW | 1.17 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 918512 | AA1-065 E OP | Adder | 1.35 MW | 1.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 924022 | AB2-043 E O1 | Adder | 0.93 MW | 0.79 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316083 | AB2-161 C | 50/50 | 3.6 MW | 3.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | 316084 | AB2-161 E | 50/50 | 5.88 MW | 5.88 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.93 MW | 1.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 34.67 MW | 34.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 11.22 MW | 11.22 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 12.01 MW | 12.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.92 MW | 2.92 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.9 MW | 0.9 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.83 MW | 2.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.55 MW | 0.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.62 MW | 1.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.72 MW | 5.72 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.28 MW | 2.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | 50/50 | 12.85 MW | 12.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | 50/50 | 26.86 MW | 26.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 926274 | AC1-105 E | 50/50 | 12.85 MW | 12.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | 50/50 | 26.86 MW | 26.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963301 | AG1-179 C | Adder | 3.52 MW | 3.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963311 | AG1-180 | Adder | 1.72 MW | 1.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965601 | AG1-428 C O2 | Adder | 2.94 MW | 2.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965602 | AG1-428 E O2 | Adder | 1.96 MW | 1.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314572 | 3EMPORIA | 50/50 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.31 MW | 2.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.91 MW | 0.91 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 14852 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961941 | AG1-037 C | Adder | 0.29 MW | 0.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961942 | AG1-037 E | Adder | 0.19 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962331 | AG1-082 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962332 | AG1-082 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962341 | AG1-083 C | Adder | 1.14 MW | 0.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 962342 | AG1-083 E | Adder | 0.76 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 963321 | AG1-181 C O1 | Adder | 8.67 MW | 7.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 963361 | AG1-185 O1 | Adder | 4.2 MW | 3.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964111 | AG1-272 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964112 | AG1-272 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964121 | AG1-273 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964122 | AG1-273 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964131 | AG1-274 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964132 | AG1-274 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964241 | AG1-285 C O1 | Adder | 7.4 MW | 6.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964242 | AG1-285 E O1 | Adder | 4.93 MW | 4.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964801 | AG1-343 C | 50/50 | 7.55 MW | 7.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 964802 | AG1-343 E | 50/50 | 5.93 MW | 5.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 966811 | AG1-552 C | 50/50 | 5.68 MW | 5.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 966812 | AG1-552 E | 50/50 | 2.44 MW | 2.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965191 | AG1-384 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965192 | AG1-384 E | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965291 | AG1-394 C | 50/50 | 2.69 MW | 2.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965292 | AG1-394 E | 50/50 | 1.79 MW | 1.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965591 | AG1-427 C | Adder | 6.98 MW | 5.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965592 | AG1-427 E | Adder | 4.67 MW | 3.97 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965721 | AG1-440 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965722 | AG1-440 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965731 | AG1-441 C | 50/50 | 9.71 MW | 9.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965732 | AG1-441 E | 50/50 | 6.47 MW | 6.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965771 | AG1-445 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 965781 | AG1-446 | 50/50 | 5.61 MW | 5.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 313506 | AB1-173 C OP | 50/50 | 18.23 MW | 18.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314541 | 3WATKINS | Adder | 0.61 MW | 0.52 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314572 | 3EMPORIA | 50/50 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315126 | 1ROARAP2 | 50/50 | 3.87 MW | 3.87 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315128 | 1ROARAP4 | 50/50 | 3.69 MW | 3.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315159 | 1KERR 2 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315160 | 1KERR 3 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315161 | 1KERR 4 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315162 | 1KERR 5 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 918492 | AA1-063AE OP | 50/50 | 8.68 MW | 8.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 919692 | AA2-053 E OP | 50/50 | 8.57 MW | 8.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 919702 | AA2-057 E OP | Adder | 2.22 MW | 1.89 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920042 | AA2-088 E OP | 50/50 | 13.28 MW | 13.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 920592 | AA2-165 E | Adder | 0.31 MW | 0.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925785 | AC1-054 E | 50/50 | 6.04 MW | 6.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926201 | AC1-098 C | Adder | 5.64 MW | 4.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926202 | AC1-098 E | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926211 | AC1-099 C | Adder | 1.89 MW | 1.61 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 926212 | AC1-099 E | Adder | 1.11 MW | 0.94 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 927145 | AC1-208 C | 50/50 | 11.18 MW | 11.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 927146 | AC1-208 E | 50/50 | 4.96 MW | 4.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 936265 | AD2-033 C | Adder | 6.77 MW | 5.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 936266 | AD2-033 E | Adder | 4.51 MW | 3.84 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 943171 | AE2-346 C | Adder | 0.8 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 943172 | AE2-346 E | Adder | 0.34 MW | 0.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 959311 | AF2-222 C | Adder | 7.99 MW | 6.79 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 959312 | AF2-222 E | Adder | 5.35 MW | 4.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315163 | 1KERR 6 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315164 | 1KERR 7 | 50/50 | 1.22 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315606 | 3AA2-053SOLA | 50/50 | 3.56 MW | 3.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316088 | AB2-174 E | 50/50 | 17.14 MW | 17.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316129 | AC1-054 C | 50/50 | 13.12 MW | 13.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316140 | AB2-099 C | Adder | 0.33 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316141 | AB2-099 E | Adder | 0.14 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 900672 | V4-068 E | 50/50 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 917332 | Z2-043 E | Adder | 0.63 MW | 0.54 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923262 | AB1-132 C OP | Adder | -13.3 MW | -11.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923573 | AB1-173 E OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923991 | AB2-040 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 923992 | AB2-040 E O1 | 50/50 | 16.24 MW | 16.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924162 | AB2-060 E OP | Adder | 2.64 MW | 2.24 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924301 | AB2-077 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924302 | AB2-077 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924311 | AB2-078 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924312 | AB2-078 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924321 | AB2-079 C O1 | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924322 | AB2-079 E O1 | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 925612 | AC1-036 E | Adder | 0.77 MW | 0.65 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 932631 | AC2-084 C | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 932632 | AC2-084 E | Adder | 3.96 MW | 3.37 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 939181 | AE1-148 C | Adder | 8.49 MW | 7.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 939182 | AE1-148 E | Adder | 5.66 MW | 4.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 940661 | AE2-053 O1 | Adder | 3.15 MW | 2.67 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 957521 | AF2-046 C | Adder | 16.04 MW | 13.63 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 957522 | AF2-046 E | Adder | 8.07 MW | 6.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314539 | 3UNCAMP | Adder | 4.36 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 938771 | AE1-103 C | Adder | 1.78 MW | 1.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 938772 | AE1-103 E | Adder | 2.46 MW | 2.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 314589 | 3MURPHYS | 50/50 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 315608 | 3AA2-088SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 316087 | AB2-174 C | 50/50 | 3.23 MW | 3.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961681 | AG1-008 C | Adder | 16.07 MW | 13.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 961682 | AG1-008 E | Adder | 8.04 MW | 6.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | 924022 | AB2-043 E O1 | Adder | 1.77 MW | 1.5 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.32 MW | 2.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.92 MW | 0.92 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.93 MW | 0.93 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.18 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.21 MW | 0.21 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.95 MW | 0.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 7152 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961891 | AG1-030 C | Adder | 5.6 MW | 4.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961892 | AG1-030 E | Adder | 3.74 MW | 3.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961941 | AG1-037 C | Adder | 0.32 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961942 | AG1-037 E | Adder | 0.22 MW | 0.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962331 | AG1-082 C | Adder | 1.29 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962332 | AG1-082 E | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962341 | AG1-083 C | Adder | 1.29 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962342 | AG1-083 E | Adder | 0.86 MW | 0.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963301 | AG1-179 C | Adder | 2.95 MW | 2.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963311 | AG1-180 | Adder | 1.44 MW | 1.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963321 | AG1-181 C O1 | Adder | 7.68 MW | 6.53 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 963361 | AG1-185 O1 | Adder | 3.72 MW | 3.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964111 | AG1-272 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964112 | AG1-272 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964121 | AG1-273 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964122 | AG1-273 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964131 | AG1-274 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964132 | AG1-274 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964241 | AG1-285 C O1 | Adder | 6.55 MW | 5.57 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964242 | AG1-285 E O1 | Adder | 4.37 MW | 3.71 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964801 | AG1-343 C | 50/50 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 964802 | AG1-343 E | 50/50 | 7.66 MW | 7.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966811 | AG1-552 C | 50/50 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966812 | AG1-552 E | 50/50 | 2.2 MW | 2.2 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965191 | AG1-384 C | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965192 | AG1-384 E | Adder | 0.34 MW | 0.28 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965291 | AG1-394 C | 50/50 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965292 | AG1-394 E | 50/50 | 2.32 MW | 2.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965591 | AG1-427 C | Adder | 6.18 MW | 5.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965592 | AG1-427 E | Adder | 4.13 MW | 3.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965601 | AG1-428 C O2 | Adder | 2.46 MW | 2.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965602 | AG1-428 E O2 | Adder | 1.64 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965721 | AG1-440 C | 50/50 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965722 | AG1-440 E | 50/50 | 5.81 MW | 5.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965731 | AG1-441 C | 50/50 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965732 | AG1-441 E | 50/50 | 5.81 MW | 5.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965771 | AG1-445 | 50/50 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 965781 | AG1-446 | 50/50 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966621 | AG1-532 C | Adder | 0.69 MW | 0.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 966622 | AG1-532 E | Adder | 0.46 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 313506 | AB1-173 C OP | 50/50 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 314572 | 3EMPORIA | Adder | 0.31 MW | 0.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315126 | 1ROARAP2 | 50/50 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315128 | 1ROARAP4 | 50/50 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315159 | 1KERR 2 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315160 | 1KERR 3 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315161 | 1KERR 4 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315162 | 1KERR 5 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 918492 | AA1-063AE OP | 50/50 | 8.66 MW | 8.66 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 919692 | AA2-053 E OP | 50/50 | 7.76 MW | 7.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 919702 | AA2-057 E OP | Adder | 2.0 MW | 1.7 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 920042 | AA2-088 E OP | 50/50 | 18.01 MW | 18.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 920592 | AA2-165 E | Adder | 0.28 MW | 0.23 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 925785 | AC1-054 E | 50/50 | 5.44 MW | 5.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926201 | AC1-098 C | Adder | 5.16 MW | 4.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926202 | AC1-098 E | Adder | 3.08 MW | 2.62 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926211 | AC1-099 C | Adder | 1.73 MW | 1.47 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 926212 | AC1-099 E | Adder | 1.02 MW | 0.86 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 927145 | AC1-208 C | 50/50 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 927146 | AC1-208 E | 50/50 | 4.49 MW | 4.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 936265 | AD2-033 C | Adder | 6.0 MW | 5.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 936266 | AD2-033 E | Adder | 4.0 MW | 3.4 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 943171 | AE2-346 C | Adder | 0.9 MW | 0.77 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 943172 | AE2-346 E | Adder | 0.39 MW | 0.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 959311 | AF2-222 C | Adder | 7.08 MW | 6.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 959312 | AF2-222 E | Adder | 4.74 MW | 4.03 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 960081 | AF2-299 C | Adder | 1.27 MW | 1.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 960082 | AF2-299 E | Adder | 0.85 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315163 | 1KERR 6 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315164 | 1KERR 7 | 50/50 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315606 | 3AA2-053SOLA | 50/50 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316088 | AB2-174 E | 50/50 | 7.19 MW | 7.19 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316129 | AC1-054 C | 50/50 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316140 | AB2-099 C | Adder | 0.38 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316141 | AB2-099 E | Adder | 0.16 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 900672 | V4-068 E | 50/50 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 917332 | Z2-043 E | Adder | 0.6 MW | 0.51 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923573 | AB1-173 E OP | 50/50 | 4.34 MW | 4.34 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923991 | AB2-040 C O1 | 50/50 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 923992 | AB2-040 E O1 | 50/50 | 8.15 MW | 8.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924162 | AB2-060 E OP | Adder | 2.34 MW | 1.99 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924301 | AB2-077 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924302 | AB2-077 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924311 | AB2-078 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924312 | AB2-078 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924321 | AB2-079 C O1 | Adder | 1.13 MW | 0.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924322 | AB2-079 E O1 | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 925612 | AC1-036 E | Adder | 0.68 MW | 0.58 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 932631 | AC2-084 C | Adder | 7.36 MW | 6.26 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 932632 | AC2-084 E | Adder | 3.62 MW | 3.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 939181 | AE1-148 C | Adder | 7.6 MW | 6.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 939182 | AE1-148 E | Adder | 5.06 MW | 4.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 940661 | AE2-053 O1 | Adder | 2.81 MW | 2.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 946281 | AF1-292 C | Adder | 0.75 MW | 0.64 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 946282 | AF1-292 E | Adder | 0.51 MW | 0.43 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 957521 | AF2-046 C | 50/50 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 957522 | AF2-046 E | 50/50 | 10.06 MW | 10.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 314589 | 3MURPHYS | 50/50 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315607 | 3AA1-063SOLA | 50/50 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 315608 | 3AA2-088SOLA | 50/50 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 316087 | AB2-174 C | 50/50 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962561 | AG1-105 C O1 | Adder | 3.36 MW | 2.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 962562 | AG1-105 E O1 | Adder | 2.24 MW | 1.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961681 | AG1-008 C | 50/50 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 961682 | AG1-008 E | 50/50 | 10.02 MW | 10.02 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | 924022 | AB2-043 E O1 | Adder | 1.57 MW | 1.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.76 MW | 0.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 93T140 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 16.45 MW | 16.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 12.93 MW | 12.93 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961671 | AG1-007 C | Adder | 0.56 MW | 0.47 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961672 | AG1-007 E | Adder | 0.32 MW | 0.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961941 | AG1-037 C | 50/50 | 0.32 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961942 | AG1-037 E | 50/50 | 0.21 MW | 0.21 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962331 | AG1-082 C | 50/50 | 1.27 MW | 1.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962332 | AG1-082 E | 50/50 | 0.85 MW | 0.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962341 | AG1-083 C | 50/50 | 1.27 MW | 1.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962342 | AG1-083 E | 50/50 | 0.85 MW | 0.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963301 | AG1-179 C | 50/50 | 6.08 MW | 6.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963311 | AG1-180 | 50/50 | 2.96 MW | 2.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964241 | AG1-285 C O1 | Adder | 5.82 MW | 4.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964242 | AG1-285 E O1 | Adder | 3.88 MW | 3.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964801 | AG1-343 C | 50/50 | 4.02 MW | 4.02 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964802 | AG1-343 E | 50/50 | 3.16 MW | 3.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966801 | AG1-551 C | Adder | 1.13 MW | 0.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966802 | AG1-551 E | Adder | 0.49 MW | 0.41 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966811 | AG1-552 C | 50/50 | 1.94 MW | 1.94 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966812 | AG1-552 E | 50/50 | 0.83 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965291 | AG1-394 C | 50/50 | 1.39 MW | 1.39 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965292 | AG1-394 E | 50/50 | 0.92 MW | 0.92 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965591 | AG1-427 C | Adder | 5.5 MW | 4.67 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965592 | AG1-427 E | Adder | 3.67 MW | 3.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965601 | AG1-428 C O2 | 50/50 | 5.08 MW | 5.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965602 | AG1-428 E O2 | 50/50 | 3.38 MW | 3.38 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965691 | AG1-437 C O1 | Adder | 4.92 MW | 4.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965692 | AG1-437 E O1 | Adder | 3.28 MW | 2.79 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965701 | AG1-438 C O1 | Adder | 4.92 MW | 4.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965702 | AG1-438 E O1 | Adder | 3.28 MW | 2.79 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965711 | AG1-439 C O1 | Adder | 13.64 MW | 11.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965712 | AG1-439 E O1 | Adder | 9.1 MW | 7.73 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965721 | AG1-440 C | 50/50 | 4.51 MW | 4.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965722 | AG1-440 E | 50/50 | 3.01 MW | 3.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965731 | AG1-441 C | 50/50 | 4.51 MW | 4.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965732 | AG1-441 E | 50/50 | 3.01 MW | 3.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965741 | AG1-442 O1 | Adder | 2.87 MW | 2.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965751 | AG1-443 O1 | Adder | 2.87 MW | 2.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965761 | AG1-444 O1 | Adder | 7.28 MW | 6.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965771 | AG1-445 | 50/50 | 2.61 MW | 2.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965781 | AG1-446 | 50/50 | 2.61 MW | 2.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966621 | AG1-532 C | 50/50 | 1.95 MW | 1.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966622 | AG1-532 E | 50/50 | 1.3 MW | 1.3 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313506 | AB1-173 C OP | 50/50 | 8.18 MW | 8.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313719 | 3CHESTNUT | 50/50 | 0.84 MW | 0.84 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314541 | 3WATKINS | Adder | 0.4 MW | 0.34 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314572 | 3EMPORIA | 50/50 | 0.57 MW | 0.57 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314582 | 3KELFORD | 50/50 | 0.25 MW | 0.25 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314623 | 3WITAKRS | 50/50 | 0.15 MW | 0.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314704 | 3LAWRENC | 50/50 | 0.36 MW | 0.36 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315126 | 1ROARAP2 | 50/50 | 1.32 MW | 1.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315128 | 1ROARAP4 | 50/50 | 1.26 MW | 1.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315131 | 1EDGECMA | Adder | 4.93 MW | 4.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315132 | 1EDGECMB | Adder | 4.93 MW | 4.19 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315136 | 1ROSEMG1 | 50/50 | 2.33 MW | 2.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315137 | 1ROSEMS1 | 50/50 | 1.44 MW | 1.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315138 | 1ROSEMG2 | 50/50 | 1.09 MW | 1.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315139 | 1GASTONA | 50/50 | 3.55 MW | 3.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917512 | Z2-088 E OP1 | Adder | 4.51 MW | 3.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918492 | AA1-063AE OP | 50/50 | 3.33 MW | 3.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918532 | AA1-067 E | Adder | 0.37 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919692 | AA2-053 E OP | 50/50 | 3.26 MW | 3.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919702 | AA2-057 E OP | 50/50 | 2.32 MW | 2.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920042 | AA2-088 E OP | 50/50 | 7.02 MW | 7.02 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920591 | AA2-165 C | 50/50 | 0.11 MW | 0.11 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920592 | AA2-165 E | 50/50 | 0.32 MW | 0.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925785 | AC1-054 E | 50/50 | 2.42 MW | 2.42 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926070 | AC1-086 C | 50/50 | 23.43 MW | 23.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926071 | AC1-086 E | 50/50 | 10.66 MW | 10.66 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926201 | AC1-098 C | 50/50 | 4.33 MW | 4.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926202 | AC1-098 E | 50/50 | 2.58 MW | 2.58 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926211 | AC1-099 C | 50/50 | 1.45 MW | 1.45 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926212 | AC1-099 E | 50/50 | 0.85 MW | 0.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927024 | AC1-189 C | Adder | 4.72 MW | 4.01 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927025 | AC1-189 E | Adder | 2.35 MW | 2.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927145 | AC1-208 C | 50/50 | 6.76 MW | 6.76 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927146 | AC1-208 E | 50/50 | 3.0 MW | 3.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934331 | AD1-057 C O1 | 50/50 | 8.4 MW | 8.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934332 | AD1-057 E O1 | 50/50 | 4.49 MW | 4.49 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943171 | AE2-346 C | 50/50 | 0.89 MW | 0.89 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943172 | AE2-346 E | 50/50 | 0.38 MW | 0.38 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 944141 | AF1-082 | Adder | 1.77 MW | 1.5 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960081 | AF2-299 C | 50/50 | 3.61 MW | 3.61 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960082 | AF2-299 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315606 | 3AA2-053SOLA | 50/50 | 1.35 MW | 1.35 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316088 | AB2-174 E | 50/50 | 8.07 MW | 8.07 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316097 | AB2-100 E1 | 50/50 | 4.87 MW | 4.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316099 | AB2-100 E2 | 50/50 | 4.87 MW | 4.87 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316129 | AC1-054 C | 50/50 | 5.26 MW | 5.26 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316140 | AB2-099 C | 50/50 | 0.37 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316141 | AB2-099 E | 50/50 | 0.16 MW | 0.16 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 900672 | V4-068 E | 50/50 | 0.2 MW | 0.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917332 | Z2-043 E | 50/50 | 0.69 MW | 0.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917342 | Z2-044 E | 50/50 | 0.37 MW | 0.37 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922923 | AB1-081 E OP | Adder | 2.35 MW | 2.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923262 | AB1-132 C OP | 50/50 | 15.91 MW | 15.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923263 | AB1-132 E OP | 50/50 | 6.82 MW | 6.82 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923573 | AB1-173 E OP | 50/50 | 3.89 MW | 3.89 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923991 | AB2-040 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923992 | AB2-040 E O1 | 50/50 | 7.29 MW | 7.29 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924152 | AB2-059 E OP | Adder | 3.34 MW | 2.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924162 | AB2-060 E OP | Adder | 2.08 MW | 1.77 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924301 | AB2-077 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924302 | AB2-077 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924311 | AB2-078 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924312 | AB2-078 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924321 | AB2-079 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924322 | AB2-079 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925122 | AB2-169 E | Adder | 2.7 MW | 2.29 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925591 | AC1-034 C | Adder | 4.19 MW | 3.56 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925592 | AC1-034 E | Adder | 3.16 MW | 2.69 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932631 | AC2-084 C | 50/50 | 6.18 MW | 6.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932632 | AC2-084 E | 50/50 | 3.04 MW | 3.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938222 | AE1-035 E | Adder | 0.62 MW | 0.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939181 | AE1-148 C | Adder | 4.77 MW | 4.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939182 | AE1-148 E | Adder | 3.18 MW | 2.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940571 | AE2-044 C | Adder | 2.75 MW | 2.33 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940572 | AE2-044 E | Adder | 1.18 MW | 1.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940661 | AE2-053 O1 | Adder | 1.77 MW | 1.5 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946281 | AF1-292 C | 50/50 | 2.14 MW | 2.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946282 | AF1-292 E | 50/50 | 1.44 MW | 1.44 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957521 | AF2-046 C | 50/50 | 11.06 MW | 11.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957522 | AF2-046 E | 50/50 | 5.57 MW | 5.57 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957861 | AF2-080 C | Adder | 4.29 MW | 3.65 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957862 | AF2-080 E | Adder | 1.9 MW | 1.62 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314539 | 3UNCAMP | Adder | 3.26 MW | 2.77 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938771 | AE1-103 C | Adder | 1.5 MW | 1.27 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938772 | AE1-103 E | Adder | 2.06 MW | 1.75 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940481 | AE2-033 C | 50/50 | 35.53 MW | 35.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940482 | AE2-033 E | 50/50 | 23.95 MW | 23.95 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946011 | AF1-266 | 50/50 | 29.74 MW | 29.74 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314331 | 6POE | 50/50 | 7.0 MW | 7.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314435 | 6SAPONY | 50/50 | 0.97 MW | 0.97 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314589 | 3MURPHYS | 50/50 | 0.06 MW | 0.06 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934575 | AD1-082 C | 50/50 | 11.71 MW | 11.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934576 | AD1-082 E | 50/50 | 6.68 MW | 6.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936661 | AD2-085 C | 50/50 | 2.54 MW | 2.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936662 | AD2-085 E | 50/50 | 4.14 MW | 4.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942341 | AE2-247 C | 50/50 | 1.11 MW | 1.11 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942342 | AE2-247 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943461 | AF1-017 C | 50/50 | 1.0 MW | 1.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943462 | AF1-017 E | 50/50 | 1.64 MW | 1.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315115 | 1S HAMPT1 | 50/50 | 0.91 MW | 0.91 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315141 | 1GASTONB | 50/50 | 3.55 MW | 3.55 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315607 | 3AA1-063SOLA | 50/50 | 1.2 MW | 1.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315608 | 3AA2-088SOLA | 50/50 | 0.73 MW | 0.73 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316087 | AB2-174 C | 50/50 | 1.52 MW | 1.52 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316096 | AB2-100 C1 | 50/50 | 1.68 MW | 1.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316098 | AB2-100 C2 | 50/50 | 1.68 MW | 1.68 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923852 | AB2-025 E | 50/50 | 2.57 MW | 2.57 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932591 | AC2-079 C O1 | 50/50 | 5.71 MW | 5.71 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932592 | AC2-079 E O1 | 50/50 | 9.32 MW | 9.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939195 | AE1-149 C | 50/50 | 18.6 MW | 18.6 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939196 | AE1-149 E | 50/50 | 12.4 MW | 12.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940541 | AE2-040 | 50/50 | 6.51 MW | 6.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940651 | AE2-052 | 50/50 | 6.2 MW | 6.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933981 | AD1-022 C | Adder | 4.0 MW | 3.4 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933982 | AD1-022 E | Adder | 2.18 MW | 1.85 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960331 | AF2-324 C | Adder | 4.82 MW | 4.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960332 | AF2-324 E | Adder | 2.58 MW | 2.2 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962572 | AG1-106 E | 50/50 | 2.96 MW | 2.96 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961681 | AG1-008 C | 50/50 | 11.09 MW | 11.09 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961682 | AG1-008 E | 50/50 | 5.54 MW | 5.54 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962571 | AG1-106 C | 50/50 | 6.51 MW | 6.51 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965281 | AG1-393 C | 50/50 | 4.98 MW | 4.98 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965282 | AG1-393 E | 50/50 | 3.32 MW | 3.32 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918512 | AA1-065 E OP | Adder | 2.27 MW | 1.93 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924022 | AB2-043 E O1 | Adder | 1.39 MW | 1.18 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316083 | AB2-161 C | 50/50 | 5.14 MW | 5.14 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316084 | AB2-161 E | 50/50 | 8.38 MW | 8.38 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.59 MW | 1.59 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.43 MW | 0.43 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 27.04 MW | 27.04 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.64 MW | 8.64 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.41 MW | 2.41 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.63 MW | 0.63 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.15 MW | 2.15 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.28 MW | 0.28 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.0 MW | 4.0 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.73 MW | 1.73 MW |
| 6POE-6HARROWG 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961671 | AG1-007 C | Adder | 0.56 MW | 0.47 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961672 | AG1-007 E | Adder | 0.32 MW | 0.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961941 | AG1-037 C | 50/50 | 0.32 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961942 | AG1-037 E | 50/50 | 0.21 MW | 0.21 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962331 | AG1-082 C | 50/50 | 1.27 MW | 1.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962332 | AG1-082 E | 50/50 | 0.85 MW | 0.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962341 | AG1-083 C | 50/50 | 1.27 MW | 1.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962342 | AG1-083 E | 50/50 | 0.85 MW | 0.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963301 | AG1-179 C | 50/50 | 6.08 MW | 6.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963311 | AG1-180 | 50/50 | 2.96 MW | 2.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964241 | AG1-285 C O1 | Adder | 5.82 MW | 4.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964242 | AG1-285 E O1 | Adder | 3.88 MW | 3.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964801 | AG1-343 C | 50/50 | 4.02 MW | 4.02 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964802 | AG1-343 E | 50/50 | 3.16 MW | 3.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966801 | AG1-551 C | Adder | 1.13 MW | 0.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966802 | AG1-551 E | Adder | 0.49 MW | 0.41 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966811 | AG1-552 C | 50/50 | 1.94 MW | 1.94 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966812 | AG1-552 E | 50/50 | 0.83 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965291 | AG1-394 C | 50/50 | 1.39 MW | 1.39 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965292 | AG1-394 E | 50/50 | 0.92 MW | 0.92 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965591 | AG1-427 C | Adder | 5.5 MW | 4.67 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965592 | AG1-427 E | Adder | 3.67 MW | 3.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965601 | AG1-428 C O2 | 50/50 | 5.08 MW | 5.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965602 | AG1-428 E O2 | 50/50 | 3.38 MW | 3.38 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965691 | AG1-437 C O1 | Adder | 4.92 MW | 4.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965692 | AG1-437 E O1 | Adder | 3.28 MW | 2.79 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965701 | AG1-438 C O1 | Adder | 4.92 MW | 4.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965702 | AG1-438 E O1 | Adder | 3.28 MW | 2.79 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965711 | AG1-439 C O1 | Adder | 13.64 MW | 11.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965712 | AG1-439 E O1 | Adder | 9.1 MW | 7.73 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965721 | AG1-440 C | 50/50 | 4.51 MW | 4.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965722 | AG1-440 E | 50/50 | 3.01 MW | 3.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965731 | AG1-441 C | 50/50 | 4.51 MW | 4.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965732 | AG1-441 E | 50/50 | 3.01 MW | 3.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965741 | AG1-442 O1 | Adder | 2.87 MW | 2.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965751 | AG1-443 O1 | Adder | 2.87 MW | 2.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965761 | AG1-444 O1 | Adder | 7.28 MW | 6.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965771 | AG1-445 | 50/50 | 2.61 MW | 2.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965781 | AG1-446 | 50/50 | 2.61 MW | 2.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966621 | AG1-532 C | 50/50 | 1.95 MW | 1.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966622 | AG1-532 E | 50/50 | 1.3 MW | 1.3 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313506 | AB1-173 C OP | 50/50 | 8.18 MW | 8.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313719 | 3CHESTNUT | 50/50 | 0.84 MW | 0.84 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314541 | 3WATKINS | Adder | 0.4 MW | 0.34 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314572 | 3EMPORIA | 50/50 | 0.57 MW | 0.57 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314582 | 3KELFORD | 50/50 | 0.25 MW | 0.25 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314623 | 3WITAKRS | 50/50 | 0.15 MW | 0.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314704 | 3LAWRENC | 50/50 | 0.36 MW | 0.36 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315126 | 1ROARAP2 | 50/50 | 1.32 MW | 1.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315128 | 1ROARAP4 | 50/50 | 1.26 MW | 1.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315131 | 1EDGECMA | Adder | 4.93 MW | 4.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315132 | 1EDGECMB | Adder | 4.93 MW | 4.19 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315136 | 1ROSEMG1 | 50/50 | 2.33 MW | 2.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315137 | 1ROSEMS1 | 50/50 | 1.44 MW | 1.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315138 | 1ROSEMG2 | 50/50 | 1.09 MW | 1.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315139 | 1GASTONA | 50/50 | 3.55 MW | 3.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917512 | Z2-088 E OP1 | Adder | 4.51 MW | 3.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918492 | AA1-063AE OP | 50/50 | 3.33 MW | 3.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918532 | AA1-067 E | Adder | 0.37 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919692 | AA2-053 E OP | 50/50 | 3.26 MW | 3.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919702 | AA2-057 E OP | 50/50 | 2.32 MW | 2.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920042 | AA2-088 E OP | 50/50 | 7.02 MW | 7.02 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920591 | AA2-165 C | 50/50 | 0.11 MW | 0.11 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920592 | AA2-165 E | 50/50 | 0.32 MW | 0.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925785 | AC1-054 E | 50/50 | 2.42 MW | 2.42 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926070 | AC1-086 C | 50/50 | 23.43 MW | 23.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926071 | AC1-086 E | 50/50 | 10.66 MW | 10.66 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926201 | AC1-098 C | 50/50 | 4.33 MW | 4.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926202 | AC1-098 E | 50/50 | 2.58 MW | 2.58 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926211 | AC1-099 C | 50/50 | 1.45 MW | 1.45 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926212 | AC1-099 E | 50/50 | 0.85 MW | 0.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927024 | AC1-189 C | Adder | 4.72 MW | 4.01 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927025 | AC1-189 E | Adder | 2.35 MW | 2.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927145 | AC1-208 C | 50/50 | 6.76 MW | 6.76 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927146 | AC1-208 E | 50/50 | 3.0 MW | 3.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934331 | AD1-057 C O1 | 50/50 | 8.4 MW | 8.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934332 | AD1-057 E O1 | 50/50 | 4.49 MW | 4.49 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943171 | AE2-346 C | 50/50 | 0.89 MW | 0.89 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943172 | AE2-346 E | 50/50 | 0.38 MW | 0.38 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 944141 | AF1-082 | Adder | 1.77 MW | 1.5 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960081 | AF2-299 C | 50/50 | 3.61 MW | 3.61 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960082 | AF2-299 E | 50/50 | 2.4 MW | 2.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315606 | 3AA2-053SOLA | 50/50 | 1.35 MW | 1.35 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316088 | AB2-174 E | 50/50 | 8.07 MW | 8.07 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316097 | AB2-100 E1 | 50/50 | 4.87 MW | 4.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316099 | AB2-100 E2 | 50/50 | 4.87 MW | 4.87 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316129 | AC1-054 C | 50/50 | 5.26 MW | 5.26 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316140 | AB2-099 C | 50/50 | 0.37 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316141 | AB2-099 E | 50/50 | 0.16 MW | 0.16 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 900672 | V4-068 E | 50/50 | 0.2 MW | 0.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917332 | Z2-043 E | 50/50 | 0.69 MW | 0.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917342 | Z2-044 E | 50/50 | 0.37 MW | 0.37 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922923 | AB1-081 E OP | Adder | 2.35 MW | 2.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923262 | AB1-132 C OP | 50/50 | 15.91 MW | 15.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923263 | AB1-132 E OP | 50/50 | 6.82 MW | 6.82 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923573 | AB1-173 E OP | 50/50 | 3.89 MW | 3.89 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923991 | AB2-040 C O1 | 50/50 | 8.91 MW | 8.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923992 | AB2-040 E O1 | 50/50 | 7.29 MW | 7.29 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924152 | AB2-059 E OP | Adder | 3.34 MW | 2.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924162 | AB2-060 E OP | Adder | 2.08 MW | 1.77 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924301 | AB2-077 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924302 | AB2-077 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924311 | AB2-078 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924312 | AB2-078 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924321 | AB2-079 C O1 | Adder | 0.98 MW | 0.83 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924322 | AB2-079 E O1 | Adder | 0.65 MW | 0.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925122 | AB2-169 E | Adder | 2.7 MW | 2.29 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925591 | AC1-034 C | Adder | 4.19 MW | 3.56 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925592 | AC1-034 E | Adder | 3.16 MW | 2.69 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932631 | AC2-084 C | 50/50 | 6.18 MW | 6.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932632 | AC2-084 E | 50/50 | 3.04 MW | 3.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938222 | AE1-035 E | Adder | 0.62 MW | 0.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939181 | AE1-148 C | Adder | 4.77 MW | 4.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939182 | AE1-148 E | Adder | 3.18 MW | 2.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940571 | AE2-044 C | Adder | 2.75 MW | 2.33 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940572 | AE2-044 E | Adder | 1.18 MW | 1.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940661 | AE2-053 O1 | Adder | 1.77 MW | 1.5 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946281 | AF1-292 C | 50/50 | 2.14 MW | 2.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946282 | AF1-292 E | 50/50 | 1.44 MW | 1.44 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957521 | AF2-046 C | 50/50 | 11.06 MW | 11.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957522 | AF2-046 E | 50/50 | 5.57 MW | 5.57 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957861 | AF2-080 C | Adder | 4.29 MW | 3.65 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957862 | AF2-080 E | Adder | 1.9 MW | 1.62 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314539 | 3UNCAMP | Adder | 3.26 MW | 2.77 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938771 | AE1-103 C | Adder | 1.5 MW | 1.27 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938772 | AE1-103 E | Adder | 2.06 MW | 1.75 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940481 | AE2-033 C | 50/50 | 35.53 MW | 35.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940482 | AE2-033 E | 50/50 | 23.95 MW | 23.95 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946011 | AF1-266 | 50/50 | 29.74 MW | 29.74 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314331 | 6POE | 50/50 | 7.0 MW | 7.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314435 | 6SAPONY | 50/50 | 0.97 MW | 0.97 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314589 | 3MURPHYS | 50/50 | 0.06 MW | 0.06 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934575 | AD1-082 C | 50/50 | 11.71 MW | 11.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934576 | AD1-082 E | 50/50 | 6.68 MW | 6.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936661 | AD2-085 C | 50/50 | 2.54 MW | 2.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 936662 | AD2-085 E | 50/50 | 4.14 MW | 4.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942341 | AE2-247 C | 50/50 | 1.11 MW | 1.11 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 942342 | AE2-247 E | 50/50 | 1.53 MW | 1.53 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943461 | AF1-017 C | 50/50 | 1.0 MW | 1.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943462 | AF1-017 E | 50/50 | 1.64 MW | 1.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315115 | 1S HAMPT1 | 50/50 | 0.91 MW | 0.91 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315141 | 1GASTONB | 50/50 | 3.55 MW | 3.55 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315607 | 3AA1-063SOLA | 50/50 | 1.2 MW | 1.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315608 | 3AA2-088SOLA | 50/50 | 0.73 MW | 0.73 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316087 | AB2-174 C | 50/50 | 1.52 MW | 1.52 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316096 | AB2-100 C1 | 50/50 | 1.68 MW | 1.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316098 | AB2-100 C2 | 50/50 | 1.68 MW | 1.68 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923852 | AB2-025 E | 50/50 | 2.57 MW | 2.57 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932591 | AC2-079 C O1 | 50/50 | 5.71 MW | 5.71 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932592 | AC2-079 E O1 | 50/50 | 9.32 MW | 9.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939195 | AE1-149 C | 50/50 | 18.6 MW | 18.6 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939196 | AE1-149 E | 50/50 | 12.4 MW | 12.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940541 | AE2-040 | 50/50 | 6.51 MW | 6.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940651 | AE2-052 | 50/50 | 6.2 MW | 6.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933981 | AD1-022 C | Adder | 4.0 MW | 3.4 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 933982 | AD1-022 E | Adder | 2.18 MW | 1.85 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960331 | AF2-324 C | Adder | 4.82 MW | 4.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960332 | AF2-324 E | Adder | 2.58 MW | 2.2 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962572 | AG1-106 E | 50/50 | 2.96 MW | 2.96 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961681 | AG1-008 C | 50/50 | 11.09 MW | 11.09 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961682 | AG1-008 E | 50/50 | 5.54 MW | 5.54 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962571 | AG1-106 C | 50/50 | 6.51 MW | 6.51 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965281 | AG1-393 C | 50/50 | 4.98 MW | 4.98 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965282 | AG1-393 E | 50/50 | 3.32 MW | 3.32 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918512 | AA1-065 E OP | Adder | 2.27 MW | 1.93 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924022 | AB2-043 E O1 | Adder | 1.39 MW | 1.18 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316083 | AB2-161 C | 50/50 | 5.14 MW | 5.14 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316084 | AB2-161 E | 50/50 | 8.38 MW | 8.38 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.59 MW | 1.59 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.43 MW | 0.43 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 27.04 MW | 27.04 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.64 MW | 8.64 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.41 MW | 2.41 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.63 MW | 0.63 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.15 MW | 2.15 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.24 MW | 1.24 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.28 MW | 0.28 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.0 MW | 4.0 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.73 MW | 1.73 MW |
| 6HARROWG-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964793 | AG1-342 BAT | 50/50 | 3.12 MW | 3.12 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | Adder | 11.78 MW | 10.01 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | Adder | 7.85 MW | 6.67 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | Adder | 1.57 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | Adder | 1.05 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 2.51 MW | 2.13 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 1.22 MW | 1.04 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | Adder | 13.24 MW | 11.26 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | Adder | 6.41 MW | 5.45 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | Adder | 2.02 MW | 1.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | Adder | 2.02 MW | 1.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | Adder | 2.02 MW | 1.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | Adder | 9.83 MW | 8.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | Adder | 6.55 MW | 5.57 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | Adder | 2.02 MW | 1.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | Adder | 9.32 MW | 7.92 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | Adder | 6.22 MW | 5.29 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 2.09 MW | 1.78 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 1.39 MW | 1.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | Adder | 15.72 MW | 13.36 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | Adder | 10.48 MW | 8.91 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 5.57 MW | 4.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 3.72 MW | 3.16 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 5.57 MW | 4.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 3.72 MW | 3.16 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.22 MW | 2.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.22 MW | 2.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | Adder | 2.62 MW | 2.23 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | Adder | 0.52 MW | 0.45 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | Adder | 1.28 MW | 1.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315158 | 1KERR 1 | 50/50 | 0.36 MW | 0.36 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 1.98 MW | 1.68 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -1.45 MW | -1.23 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.01 MW | -0.85 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | Adder | 10.21 MW | 8.68 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | Adder | 6.81 MW | 5.79 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | Adder | 7.86 MW | 6.68 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | Adder | 5.24 MW | 4.45 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -0.82 MW | -0.69 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | Adder | 11.79 MW | 10.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | Adder | 7.86 MW | 6.68 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | Adder | 13.1 MW | 11.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | Adder | 8.78 MW | 7.46 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.0 MW | 1.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315266 | 1PLYWOOD A | 50/50 | 6.11 MW | 6.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 4.29 MW | 3.65 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | Adder | 3.35 MW | 2.85 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 1.83 MW | 1.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 1.83 MW | 1.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 1.83 MW | 1.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | Adder | 1.22 MW | 1.04 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | Adder | 5.08 MW | 4.32 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | Adder | 2.78 MW | 2.36 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 7.45 MW | 7.45 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 4.96 MW | 4.96 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | Adder | 2.76 MW | 2.34 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | Adder | 3.22 MW | 2.74 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | Adder | 2.15 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | Adder | 1.96 MW | 1.67 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | Adder | 1.31 MW | 1.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | Adder | 2.21 MW | 1.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.08 MW | 0.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.08 MW | 0.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.16 MW | 0.16 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.57 MW | 0.57 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.11 MW | 0.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.12 MW | 0.12 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.05 MW | 0.05 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.19 MW | 0.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.19 MW | 0.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| AE2-291 TAP-3GRIT 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3GRIT-3OTTER R 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | Adder | 11.71 MW | 9.95 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | Adder | 7.8 MW | 6.63 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | Adder | 1.04 MW | 0.88 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 2.49 MW | 2.12 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 1.21 MW | 1.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | Adder | 13.16 MW | 11.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | Adder | 6.37 MW | 5.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | Adder | 9.76 MW | 8.3 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | Adder | 6.51 MW | 5.53 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | Adder | 9.26 MW | 7.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | Adder | 6.18 MW | 5.26 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 2.08 MW | 1.77 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 1.38 MW | 1.18 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | Adder | 15.62 MW | 13.28 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | Adder | 10.42 MW | 8.85 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 5.54 MW | 4.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 3.7 MW | 3.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 5.54 MW | 4.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 3.7 MW | 3.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | Adder | 2.6 MW | 2.21 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | Adder | 0.52 MW | 0.44 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | Adder | 1.27 MW | 1.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315158 | 1KERR 1 | 50/50 | 0.35 MW | 0.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 1.97 MW | 1.67 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -1.47 MW | -1.25 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.02 MW | -0.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | Adder | 10.14 MW | 8.62 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | Adder | 6.76 MW | 5.75 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | Adder | 7.81 MW | 6.64 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | Adder | 5.21 MW | 4.43 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -0.83 MW | -0.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | Adder | 11.72 MW | 9.96 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | Adder | 7.81 MW | 6.64 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | Adder | 13.02 MW | 11.07 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.42 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315266 | 1PLYWOOD A | 50/50 | 6.1 MW | 6.1 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 4.27 MW | 3.63 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | Adder | 3.33 MW | 2.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | Adder | 1.21 MW | 1.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | Adder | 5.05 MW | 4.29 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | Adder | 2.76 MW | 2.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 7.41 MW | 7.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 4.94 MW | 4.94 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | Adder | 2.74 MW | 2.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | Adder | 2.13 MW | 1.81 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | Adder | 1.95 MW | 1.66 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | Adder | 1.3 MW | 1.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | Adder | 2.2 MW | 1.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.09 MW | 0.09 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.18 MW | 0.18 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.08 MW | 0.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.05 MW | 0.05 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.22 MW | 0.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | Adder | 5.89 MW | 5.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | Adder | 3.93 MW | 3.34 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | Adder | 4.46 MW | 3.79 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | Adder | 2.97 MW | 2.53 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | Adder | 0.76 MW | 0.64 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | Adder | 0.5 MW | 0.43 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | Adder | 7.23 MW | 6.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | Adder | 3.5 MW | 2.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | Adder | 5.74 MW | 4.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | Adder | 3.82 MW | 3.25 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.5 MW | 2.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966691 | AG1-539 C | 50/50 | 17.14 MW | 17.14 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966692 | AG1-539 E | 50/50 | 23.04 MW | 23.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | Adder | 1.08 MW | 0.92 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | Adder | 0.32 MW | 0.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | Adder | 5.43 MW | 4.61 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | Adder | 3.63 MW | 3.08 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | Adder | 7.33 MW | 6.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | Adder | 4.89 MW | 4.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | Adder | 0.25 MW | 0.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | Adder | 0.59 MW | 0.5 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926023 | AC1-080 C | 50/50 | 0.96 MW | 0.96 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 2.36 MW | 2.36 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 5.06 MW | 5.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 4.82 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 3.51 MW | 3.51 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.91 MW | 0.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | Adder | 3.57 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | Adder | 1.67 MW | 1.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | Adder | 4.93 MW | 4.19 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | Adder | 2.32 MW | 1.97 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | Adder | 4.19 MW | 3.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | Adder | 2.79 MW | 2.37 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | Adder | 5.61 MW | 4.77 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | Adder | 3.74 MW | 3.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | Adder | 1.04 MW | 0.89 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | Adder | 0.49 MW | 0.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942751 | AE2-291 C | 50/50 | 32.78 MW | 32.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942752 | AE2-291 E | 50/50 | 21.86 MW | 21.86 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942761 | AE2-292 C O1 | 50/50 | 40.82 MW | 40.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942762 | AE2-292 E O1 | 50/50 | 27.21 MW | 27.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.91 MW | 1.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 1.28 MW | 1.28 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | Adder | 3.42 MW | 2.91 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | Adder | 4.73 MW | 4.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | Adder | 5.67 MW | 4.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | Adder | 3.78 MW | 3.21 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | Adder | 6.92 MW | 5.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | Adder | 4.64 MW | 3.94 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 7.65 MW | 7.65 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 5.1 MW | 5.1 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 1.11 MW | 1.11 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 4.93 MW | 4.93 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | Adder | 2.0 MW | 1.7 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | Adder | 0.96 MW | 0.82 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | Adder | 0.64 MW | 0.55 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | Adder | 0.65 MW | 0.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925661 | AC1-042 C | Adder | -3.22 MW | -2.73 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | Adder | 2.34 MW | 1.99 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | Adder | 1.28 MW | 1.09 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | Adder | 3.56 MW | 3.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | Adder | 2.38 MW | 2.02 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | Adder | 1.32 MW | 1.12 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | Adder | 0.8 MW | 0.68 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | Adder | 0.37 MW | 0.32 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | Adder | 1.55 MW | 1.31 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | Adder | 1.03 MW | 0.88 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | Adder | 24.45 MW | 20.78 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | Adder | 16.3 MW | 13.85 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | Adder | 0.94 MW | 0.8 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | Adder | 0.63 MW | 0.54 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.4 MW | 6.4 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.27 MW | 4.27 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | Adder | 1.33 MW | 1.13 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316123 | AC1-075 C | 50/50 | 2.87 MW | 2.87 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925997 | AC1-075 E | 50/50 | 9.56 MW | 9.56 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926024 | AC1-080 E | 50/50 | 3.17 MW | 3.17 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961131 | AF2-404 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966763 | AG1-547 BAT | 50/50 | 2.42 MW | 2.42 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961122 | AF2-403 BAT | 50/50 | 4.03 MW | 4.03 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.23 MW | 0.23 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.57 MW | 0.57 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.07 MW | 0.07 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.22 MW | 11.22 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.24 MW | 0.24 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.06 MW | 0.06 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.46 MW | 0.46 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.01 MW | 0.01 MW |
| 3OTTER R-3ALTVSTA 115.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.64 MW | 0.64 MW |
| Details for 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | Adder | 11.71 MW | 9.95 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | Adder | 7.81 MW | 6.63 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | Adder | 1.56 MW | 1.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | Adder | 1.04 MW | 0.89 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 2.49 MW | 2.12 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 1.21 MW | 1.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | Adder | 13.16 MW | 11.19 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | Adder | 6.37 MW | 5.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | Adder | 9.76 MW | 8.3 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | Adder | 6.51 MW | 5.53 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | Adder | 2.01 MW | 1.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | Adder | 0.6 MW | 0.51 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | Adder | 9.26 MW | 7.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | Adder | 6.18 MW | 5.26 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 2.08 MW | 1.77 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 1.38 MW | 1.18 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | Adder | 15.62 MW | 13.27 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | Adder | 10.41 MW | 8.85 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 5.54 MW | 4.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 3.7 MW | 3.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 5.54 MW | 4.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 3.7 MW | 3.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | Adder | 2.6 MW | 2.21 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | Adder | 0.52 MW | 0.44 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | Adder | 1.27 MW | 1.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315158 | 1KERR 1 | 50/50 | 0.35 MW | 0.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 1.97 MW | 1.67 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -1.47 MW | -1.25 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.02 MW | -0.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | Adder | 10.15 MW | 8.62 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | Adder | 6.76 MW | 5.75 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | Adder | 7.81 MW | 6.64 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | Adder | 5.21 MW | 4.42 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -0.83 MW | -0.71 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | Adder | 11.71 MW | 9.96 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | Adder | 7.81 MW | 6.64 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | Adder | 13.02 MW | 11.06 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 0.99 MW | 0.99 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315266 | 1PLYWOOD A | 50/50 | 6.1 MW | 6.1 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 4.27 MW | 3.63 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | Adder | 3.33 MW | 2.83 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 1.82 MW | 1.82 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 1.22 MW | 1.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | Adder | 1.21 MW | 1.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | Adder | 5.05 MW | 4.29 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | Adder | 2.76 MW | 2.35 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 7.41 MW | 7.41 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 4.94 MW | 4.94 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | Adder | 2.74 MW | 2.33 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | Adder | 3.2 MW | 2.72 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | Adder | 2.13 MW | 1.81 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | Adder | 1.95 MW | 1.66 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | Adder | 1.3 MW | 1.11 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | Adder | 2.2 MW | 1.87 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.09 MW | 0.09 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.17 MW | 0.17 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.18 MW | 0.18 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.08 MW | 0.08 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.05 MW | 0.05 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.02 MW | 0.02 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.22 MW | 0.22 MW |
| 3PLYWOOD-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.05 MW | 0.05 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964791 | AG1-342 C | 50/50 | 16.45 MW | 16.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964792 | AG1-342 E | 50/50 | 12.93 MW | 12.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 926274 | AC1-105 E | 50/50 | 12.87 MW | 12.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316118 | AC1-105 C | 50/50 | 26.91 MW | 26.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964793 | AG1-342 BAT | 50/50 | 3.12 MW | 3.12 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964793 | AG1-342 BAT | 50/50 | 3.12 MW | 3.12 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3CHASCTY2-3BARNS J 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315162 | 1KERR 5 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | Adder | -7.64 MW | -6.5 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964793 | AG1-342 BAT | 50/50 | 3.14 MW | 3.14 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| 3BARNS J-AG1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964791 | AG1-342 C | 50/50 | 16.45 MW | 16.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964792 | AG1-342 E | 50/50 | 12.93 MW | 12.93 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| 3MT LREL-AC1-105 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961801 | AG1-022 C | 50/50 | 1.23 MW | 1.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961802 | AG1-022 E | 50/50 | 0.82 MW | 0.82 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 38.1 MW | 38.1 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 25.4 MW | 25.4 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 962491 | AG1-098 C O1 | 50/50 | 46.0 MW | 46.0 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 962492 | AG1-098 E O1 | 50/50 | 30.66 MW | 30.66 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 5.08 MW | 5.08 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 3.39 MW | 3.39 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 42.79 MW | 42.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 20.7 MW | 20.7 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 6.53 MW | 6.53 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 1.94 MW | 1.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 6.53 MW | 6.53 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 1.94 MW | 1.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 6.53 MW | 6.53 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 1.94 MW | 1.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964231 | AG1-284 C O1 | 50/50 | 6.34 MW | 6.34 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964232 | AG1-284 E O1 | 50/50 | 4.23 MW | 4.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 31.75 MW | 31.75 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 21.17 MW | 21.17 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 6.53 MW | 6.53 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 1.94 MW | 1.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965581 | AG1-426 | 50/50 | 1.98 MW | 1.98 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 30.1 MW | 30.1 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 20.11 MW | 20.11 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 50.8 MW | 50.8 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 33.87 MW | 33.87 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 8.47 MW | 8.47 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 1.69 MW | 1.69 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.15 MW | 1.15 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 4.12 MW | 4.12 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934615 | AD1-087 C | Adder | -6.0 MW | -5.1 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934625 | AD1-088 C | 50/50 | 50.85 MW | 50.85 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 934626 | AD1-088 E | 50/50 | 23.93 MW | 23.93 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 935171 | AD1-152 C O1 | Adder | -5.61 MW | -4.77 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 33.02 MW | 33.02 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 22.01 MW | 22.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 937481 | AD2-202 C O1 | Adder | -1.76 MW | -1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 25.4 MW | 25.4 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 16.93 MW | 16.93 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946592 | AF1-323 E | 50/50 | 2.25 MW | 2.25 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 38.1 MW | 38.1 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 25.4 MW | 25.4 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 42.33 MW | 42.33 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 28.36 MW | 28.36 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 960111 | AF2-302 C | 50/50 | 1.23 MW | 1.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 960112 | AF2-302 E | 50/50 | 0.82 MW | 0.82 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 3.92 MW | 3.92 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 10.84 MW | 10.84 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.62 MW | 0.62 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 3.94 MW | 3.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 16.43 MW | 16.43 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 8.97 MW | 8.97 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938821 | AE1-108 C O1 | 50/50 | 10.45 MW | 10.45 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 938822 | AE1-108 E O1 | 50/50 | 6.96 MW | 6.96 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941011 | AE2-092 C | 50/50 | 10.07 MW | 10.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941012 | AE2-092 E | 50/50 | 6.71 MW | 6.71 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941791 | AE2-182 C | 50/50 | 8.26 MW | 8.26 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 941792 | AE2-182 E | 50/50 | 3.85 MW | 3.85 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946291 | AF1-293 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946292 | AF1-293 E O1 | 50/50 | 2.71 MW | 2.71 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 10.41 MW | 10.41 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 6.94 MW | 6.94 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 946591 | AF1-323 C | 50/50 | 3.38 MW | 3.38 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 6.35 MW | 6.35 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 4.23 MW | 4.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 924032 | AB2-045 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961061 | AF2-397 C | 50/50 | 11.54 MW | 11.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 961062 | AF2-397 E | 50/50 | 7.7 MW | 7.7 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 314677 | 6BUCKING | 50/50 | 0.72 MW | 0.72 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315191 | 1BEARGRDN G1 | 50/50 | 5.83 MW | 5.83 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315192 | 1BEARGRDN G2 | 50/50 | 5.83 MW | 5.83 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | 315193 | 1BEARGRDN S1 | 50/50 | 7.54 MW | 7.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.54 MW | 0.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.51 MW | 2.51 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.71 MW | 0.71 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.61 MW | 0.61 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.79 MW | 0.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.42 MW | 0.42 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.64 MW | 0.64 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.14 MW | 2.14 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.92 MW | 0.92 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.24 MW | 0.24 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.63 MW | 1.63 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.66 MW | 1.66 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.22 MW | 0.22 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-6: CHASE C T342 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 2.46 MW | 2.46 MW |
| Details for AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961791 | AG1-021 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961792 | AG1-021 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961891 | AG1-030 C | 50/50 | 37.57 MW | 37.57 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961892 | AG1-030 E | 50/50 | 25.05 MW | 25.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962491 | AG1-098 C O1 | 50/50 | 57.29 MW | 57.29 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962492 | AG1-098 E O1 | 50/50 | 38.19 MW | 38.19 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963171 | AG1-166 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963172 | AG1-166 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963181 | AG1-167 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963182 | AG1-167 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963191 | AG1-168 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963192 | AG1-168 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963201 | AG1-169 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963202 | AG1-169 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963211 | AG1-170 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963212 | AG1-170 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963321 | AG1-181 C O1 | 50/50 | 32.02 MW | 32.02 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 963361 | AG1-185 O1 | 50/50 | 15.49 MW | 15.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964111 | AG1-272 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964112 | AG1-272 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964121 | AG1-273 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964122 | AG1-273 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964131 | AG1-274 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964132 | AG1-274 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964241 | AG1-285 C O1 | 50/50 | 17.5 MW | 17.5 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 964242 | AG1-285 E O1 | 50/50 | 11.67 MW | 11.67 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965191 | AG1-384 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965192 | AG1-384 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965591 | AG1-427 C | 50/50 | 16.79 MW | 16.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965592 | AG1-427 E | 50/50 | 11.21 MW | 11.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965641 | AG1-432 C O1 | 50/50 | 74.7 MW | 74.7 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965642 | AG1-432 E O1 | 50/50 | 49.8 MW | 49.8 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965831 | AG1-451 | 50/50 | 12.45 MW | 12.45 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 313853 | 3PONTONDP | 50/50 | 1.84 MW | 1.84 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 314429 | 3JTRSVLE | 50/50 | 1.25 MW | 1.25 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 314713 | 3PAMPLIN | 50/50 | 4.9 MW | 4.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315160 | 1KERR 3 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315161 | 1KERR 4 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315162 | 1KERR 5 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 934625 | AD1-088 C | 50/50 | 63.57 MW | 63.57 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 934626 | AD1-088 E | 50/50 | 29.92 MW | 29.92 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 936265 | AD2-033 C | 50/50 | 24.18 MW | 24.18 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 936266 | AD2-033 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 942461 | AE2-259 C O1 | 50/50 | 37.35 MW | 37.35 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 942462 | AE2-259 E O1 | 50/50 | 24.9 MW | 24.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958801 | AF2-171 C | 50/50 | 41.21 MW | 41.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958802 | AF2-171 E | 50/50 | 27.47 MW | 27.47 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 959311 | AF2-222 C | 50/50 | 35.51 MW | 35.51 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 959312 | AF2-222 E | 50/50 | 23.79 MW | 23.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315163 | 1KERR 6 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 315164 | 1KERR 7 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 316131 | AB2-060 C | 50/50 | 1.89 MW | 1.89 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924162 | AB2-060 E OP | 50/50 | 5.23 MW | 5.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924301 | AB2-077 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924302 | AB2-077 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924311 | AB2-078 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924312 | AB2-078 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924321 | AB2-079 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924322 | AB2-079 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 925611 | AC1-036 C | 50/50 | 0.49 MW | 0.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 925612 | AC1-036 E | 50/50 | 3.14 MW | 3.14 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 938371 | AE1-056 C | 50/50 | 19.55 MW | 19.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 938372 | AE1-056 E | 50/50 | 10.68 MW | 10.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 939181 | AE1-148 C | 50/50 | 6.96 MW | 6.96 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 939182 | AE1-148 E | 50/50 | 4.64 MW | 4.64 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 940661 | AE2-053 O1 | 50/50 | 2.58 MW | 2.58 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 941791 | AE2-182 C | 50/50 | 10.33 MW | 10.33 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 941792 | AE2-182 E | 50/50 | 4.81 MW | 4.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946301 | AF1-294 C | 50/50 | 11.32 MW | 11.32 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946302 | AF1-294 E | 50/50 | 7.55 MW | 7.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958211 | AF2-115 C | 50/50 | 6.9 MW | 6.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958212 | AF2-115 E | 50/50 | 4.6 MW | 4.6 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924032 | AB2-045 E | 50/50 | 4.76 MW | 4.76 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 314677 | 6BUCKING | 50/50 | 1.74 MW | 1.74 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962561 | AG1-105 C O1 | 50/50 | 6.11 MW | 6.11 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962562 | AG1-105 E O1 | 50/50 | 4.07 MW | 4.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.76 MW | 2.76 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.07 MW | 1.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.03 MW | 1.03 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.54 MW | 0.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.04 MW | 9.04 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.22 MW | 10.22 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.74 MW | 28.74 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.16 MW | 19.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.39 MW | 25.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.92 MW | 16.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.62 MW | 39.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.44 MW | 9.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.23 MW | 39.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.52 MW | 29.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.71 MW | 14.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.69 MW | 8.69 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.56 MW | 7.56 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.83 MW | 0.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.15 MW | 1.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.3 MW | 5.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.35 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.04 MW | 9.04 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.22 MW | 10.22 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.74 MW | 28.74 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.16 MW | 19.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.39 MW | 25.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.92 MW | 16.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.62 MW | 39.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.44 MW | 9.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.23 MW | 39.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.52 MW | 29.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.71 MW | 14.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.69 MW | 8.69 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.56 MW | 7.56 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.83 MW | 0.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.15 MW | 1.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.3 MW | 5.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.35 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.45 MW | 14.45 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.21 MW | 8.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.24 MW | 7.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.09 MW | 1.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.12 MW | 5.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.45 MW | 14.45 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.21 MW | 8.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.24 MW | 7.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.09 MW | 1.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.12 MW | 5.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.44 MW | 3.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.06 MW | 14.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.08 MW | 20.08 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966251 | AG1-494 C | Adder | 1.67 MW | 1.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966252 | AG1-494 E | Adder | 2.5 MW | 2.12 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.3 MW | 6.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.44 MW | 3.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.76 MW | 28.76 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.17 MW | 19.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.4 MW | 25.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.93 MW | 16.93 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.64 MW | 39.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.45 MW | 9.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.67 MW | 36.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.45 MW | 24.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | Adder | -2.72 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.92 MW | 19.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.73 MW | 0.73 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.85 MW | 14.85 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.88 MW | 8.88 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.68 MW | 7.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.82 MW | 0.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.67 MW | 1.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.45 MW | 0.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.17 MW | 1.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 927261 | AC1-222 C | Adder | -2.01 MW | -1.71 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 934311 | AD1-055 C | Adder | -1.39 MW | -1.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 315164 | 1KERR 7 | 50/50 | 1.16 MW | 1.16 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316118 | AC1-105 C | Adder | -7.59 MW | -6.45 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | 964793 | AG1-342 BAT | 50/50 | 3.12 MW | 3.12 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| AG1-105 TAP-3MT LREL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.01 MW | 17.01 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966252 | AG1-494 E | Adder | 2.48 MW | 2.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.3 MW | 25.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.87 MW | 16.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.56 MW | 39.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.12 MW | 7.12 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.59 MW | 14.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.39 MW | 8.39 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.36 MW | 7.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.6 MW | 1.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.11 MW | 1.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.03 MW | 5.03 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.32 MW | 1.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961671 | AG1-007 C | Adder | 0.67 MW | 0.57 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961672 | AG1-007 E | Adder | 0.38 MW | 0.32 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961941 | AG1-037 C | Adder | 0.35 MW | 0.3 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961942 | AG1-037 E | Adder | 0.23 MW | 0.2 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962331 | AG1-082 C | Adder | 1.4 MW | 1.19 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962332 | AG1-082 E | Adder | 0.93 MW | 0.79 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962341 | AG1-083 C | Adder | 1.4 MW | 1.19 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962342 | AG1-083 E | Adder | 0.93 MW | 0.79 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963301 | AG1-179 C | 50/50 | 7.96 MW | 7.96 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 963311 | AG1-180 | 50/50 | 3.88 MW | 3.88 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964241 | AG1-285 C O1 | Adder | 7.33 MW | 6.23 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964242 | AG1-285 E O1 | Adder | 4.89 MW | 4.16 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964801 | AG1-343 C | Adder | 3.95 MW | 3.36 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 964802 | AG1-343 E | Adder | 3.1 MW | 2.64 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966801 | AG1-551 C | Adder | 1.28 MW | 1.09 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966802 | AG1-551 E | Adder | 0.55 MW | 0.47 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966811 | AG1-552 C | 50/50 | 2.4 MW | 2.4 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966812 | AG1-552 E | 50/50 | 1.03 MW | 1.03 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965291 | AG1-394 C | Adder | 1.35 MW | 1.15 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965292 | AG1-394 E | Adder | 0.9 MW | 0.77 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965591 | AG1-427 C | Adder | 6.92 MW | 5.88 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965592 | AG1-427 E | Adder | 4.62 MW | 3.93 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965601 | AG1-428 C O2 | 50/50 | 6.65 MW | 6.65 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965602 | AG1-428 E O2 | 50/50 | 4.42 MW | 4.42 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965711 | AG1-439 C O1 | Adder | 16.25 MW | 13.81 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965712 | AG1-439 E O1 | Adder | 10.83 MW | 9.21 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965721 | AG1-440 C | 50/50 | 5.6 MW | 5.6 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965722 | AG1-440 E | 50/50 | 3.73 MW | 3.73 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965731 | AG1-441 C | 50/50 | 5.6 MW | 5.6 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965732 | AG1-441 E | 50/50 | 3.73 MW | 3.73 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965761 | AG1-444 O1 | Adder | 8.67 MW | 7.37 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965771 | AG1-445 | 50/50 | 3.24 MW | 3.24 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965781 | AG1-446 | 50/50 | 3.24 MW | 3.24 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966621 | AG1-532 C | 50/50 | 2.57 MW | 2.57 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 966622 | AG1-532 E | 50/50 | 1.71 MW | 1.71 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313506 | AB1-173 C OP | 50/50 | 10.57 MW | 10.57 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 313719 | 3CHESTNUT | 50/50 | 1.02 MW | 1.02 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314572 | 3EMPORIA | 50/50 | 0.75 MW | 0.75 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314582 | 3KELFORD | 50/50 | 0.29 MW | 0.29 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314623 | 3WITAKRS | 50/50 | 0.18 MW | 0.18 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314704 | 3LAWRENC | 50/50 | 0.48 MW | 0.48 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315126 | 1ROARAP2 | 50/50 | 1.64 MW | 1.64 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315128 | 1ROARAP4 | 50/50 | 1.56 MW | 1.56 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315131 | 1EDGECMA | 50/50 | 6.06 MW | 6.06 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315132 | 1EDGECMB | 50/50 | 6.06 MW | 6.06 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315136 | 1ROSEMG1 | 50/50 | 2.99 MW | 2.99 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315137 | 1ROSEMS1 | 50/50 | 1.85 MW | 1.85 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315138 | 1ROSEMG2 | 50/50 | 1.4 MW | 1.4 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315139 | 1GASTONA | 50/50 | 4.57 MW | 4.57 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917512 | Z2-088 E OP1 | Adder | 5.37 MW | 4.57 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918492 | AA1-063AE OP | 50/50 | 3.84 MW | 3.84 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918532 | AA1-067 E | Adder | 0.43 MW | 0.36 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919692 | AA2-053 E OP | 50/50 | 3.99 MW | 3.99 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 919702 | AA2-057 E OP | 50/50 | 2.82 MW | 2.82 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920042 | AA2-088 E OP | Adder | 6.65 MW | 5.65 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920591 | AA2-165 C | 50/50 | 0.14 MW | 0.14 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 920592 | AA2-165 E | 50/50 | 0.39 MW | 0.39 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925785 | AC1-054 E | 50/50 | 3.01 MW | 3.01 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926070 | AC1-086 C | 50/50 | 30.17 MW | 30.17 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926071 | AC1-086 E | 50/50 | 13.73 MW | 13.73 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926201 | AC1-098 C | 50/50 | 5.2 MW | 5.2 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926202 | AC1-098 E | 50/50 | 3.1 MW | 3.1 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926211 | AC1-099 C | 50/50 | 1.74 MW | 1.74 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 926212 | AC1-099 E | 50/50 | 1.02 MW | 1.02 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927024 | AC1-189 C | Adder | 5.56 MW | 4.72 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927025 | AC1-189 E | Adder | 2.77 MW | 2.35 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927145 | AC1-208 C | 50/50 | 8.24 MW | 8.24 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 927146 | AC1-208 E | 50/50 | 3.66 MW | 3.66 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934331 | AD1-057 C O1 | 50/50 | 10.62 MW | 10.62 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934332 | AD1-057 E O1 | 50/50 | 5.68 MW | 5.68 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943171 | AE2-346 C | Adder | 0.98 MW | 0.83 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 943172 | AE2-346 E | Adder | 0.42 MW | 0.36 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 944141 | AF1-082 | Adder | 2.16 MW | 1.84 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960081 | AF2-299 C | 50/50 | 4.76 MW | 4.76 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960082 | AF2-299 E | 50/50 | 3.17 MW | 3.17 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315606 | 3AA2-053SOLA | 50/50 | 1.66 MW | 1.66 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316020 | AB2-059 C OP | 50/50 | 1.35 MW | 1.35 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316088 | AB2-174 E | 50/50 | 10.5 MW | 10.5 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316097 | AB2-100 E1 | 50/50 | 6.5 MW | 6.5 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316099 | AB2-100 E2 | 50/50 | 6.5 MW | 6.5 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316129 | AC1-054 C | 50/50 | 6.53 MW | 6.53 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316140 | AB2-099 C | Adder | 0.41 MW | 0.35 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316141 | AB2-099 E | Adder | 0.18 MW | 0.15 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 900672 | V4-068 E | Adder | 0.2 MW | 0.17 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917332 | Z2-043 E | 50/50 | 0.8 MW | 0.8 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 917342 | Z2-044 E | 50/50 | 0.46 MW | 0.46 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922922 | AB1-081 C OP | 50/50 | 1.15 MW | 1.15 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 922923 | AB1-081 E OP | 50/50 | 2.88 MW | 2.88 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923262 | AB1-132 C OP | 50/50 | 20.49 MW | 20.49 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923263 | AB1-132 E OP | 50/50 | 8.78 MW | 8.78 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923573 | AB1-173 E OP | 50/50 | 5.03 MW | 5.03 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923991 | AB2-040 C O1 | 50/50 | 11.52 MW | 11.52 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923992 | AB2-040 E O1 | 50/50 | 9.42 MW | 9.42 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924152 | AB2-059 E OP | 50/50 | 4.08 MW | 4.08 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924162 | AB2-060 E OP | Adder | 2.62 MW | 2.22 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924301 | AB2-077 C O1 | Adder | 1.23 MW | 1.05 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924302 | AB2-077 E O1 | Adder | 0.82 MW | 0.7 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924311 | AB2-078 C O1 | Adder | 1.23 MW | 1.05 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924312 | AB2-078 E O1 | Adder | 0.82 MW | 0.7 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924321 | AB2-079 C O1 | Adder | 1.23 MW | 1.05 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924322 | AB2-079 E O1 | Adder | 0.82 MW | 0.7 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925591 | AC1-034 C | 50/50 | 5.13 MW | 5.13 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 925592 | AC1-034 E | 50/50 | 3.87 MW | 3.87 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932631 | AC2-084 C | 50/50 | 7.41 MW | 7.41 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 932632 | AC2-084 E | 50/50 | 3.65 MW | 3.65 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 938222 | AE1-035 E | Adder | 0.69 MW | 0.59 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939181 | AE1-148 C | Adder | 5.94 MW | 5.05 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 939182 | AE1-148 E | Adder | 3.96 MW | 3.37 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940571 | AE2-044 C | 50/50 | 3.36 MW | 3.36 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940572 | AE2-044 E | Adder | 1.44 MW | 1.23 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940661 | AE2-053 O1 | Adder | 2.2 MW | 1.87 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946281 | AF1-292 C | 50/50 | 2.82 MW | 2.82 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946282 | AF1-292 E | 50/50 | 1.9 MW | 1.9 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957521 | AF2-046 C | Adder | 11.44 MW | 9.72 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957522 | AF2-046 E | Adder | 5.75 MW | 4.89 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957861 | AF2-080 C | Adder | 5.05 MW | 4.29 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 957862 | AF2-080 E | Adder | 2.24 MW | 1.9 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940481 | AE2-033 C | 50/50 | 48.2 MW | 48.2 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940482 | AE2-033 E | 50/50 | 32.5 MW | 32.5 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 946011 | AF1-266 | 50/50 | 40.35 MW | 40.35 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 314435 | 6SAPONY | 50/50 | 1.32 MW | 1.32 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 934575 | AD1-082 C | Adder | -4.88 MW | -4.15 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315141 | 1GASTONB | 50/50 | 4.57 MW | 4.57 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 315607 | 3AA1-063SOLA | 50/50 | 1.39 MW | 1.39 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316087 | AB2-174 C | 50/50 | 1.98 MW | 1.98 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316096 | AB2-100 C1 | 50/50 | 2.25 MW | 2.25 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316098 | AB2-100 C2 | 50/50 | 2.25 MW | 2.25 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 923852 | AB2-025 E | 50/50 | 3.5 MW | 3.5 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940541 | AE2-040 | 50/50 | 8.85 MW | 8.85 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960331 | AF2-324 C | 50/50 | 5.91 MW | 5.91 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 960332 | AF2-324 E | 50/50 | 3.17 MW | 3.17 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962572 | AG1-106 E | 50/50 | 3.81 MW | 3.81 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961681 | AG1-008 C | Adder | 11.46 MW | 9.74 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 961682 | AG1-008 E | Adder | 5.73 MW | 4.87 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 962571 | AG1-106 C | 50/50 | 8.39 MW | 8.39 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965281 | AG1-393 C | 50/50 | 6.77 MW | 6.77 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 965282 | AG1-393 E | 50/50 | 4.51 MW | 4.51 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 918512 | AA1-065 E OP | Adder | 2.52 MW | 2.14 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 924022 | AB2-043 E O1 | Adder | 1.76 MW | 1.49 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 316083 | AB2-161 C | Adder | -2.14 MW | -1.82 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | 940652 | AE2-052 BAT | 50/50 | 2.69 MW | 2.69 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.83 MW | 1.83 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.5 MW | 0.5 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 30.99 MW | 30.99 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.25 MW | 10.25 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.66 MW | 10.66 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.77 MW | 2.77 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.69 MW | 0.69 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.5 MW | 2.5 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.5 MW | 0.5 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.46 MW | 1.46 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.31 MW | 0.31 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.35 MW | 4.35 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.0 MW | 2.0 MW |
| 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-4 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.44 MW | 3.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.06 MW | 14.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.08 MW | 20.08 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966251 | AG1-494 C | Adder | 1.67 MW | 1.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966252 | AG1-494 E | Adder | 2.5 MW | 2.12 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.3 MW | 6.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.44 MW | 3.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.76 MW | 28.76 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.17 MW | 19.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.4 MW | 25.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.93 MW | 16.93 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.64 MW | 39.64 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.45 MW | 9.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | Adder | -17.76 MW | -15.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.67 MW | 36.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.45 MW | 24.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | Adder | -2.72 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.92 MW | 19.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.73 MW | 0.73 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.85 MW | 14.85 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.88 MW | 8.88 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.68 MW | 7.68 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.82 MW | 0.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.67 MW | 1.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.45 MW | 0.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.17 MW | 1.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.01 MW | 17.01 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966252 | AG1-494 E | Adder | 2.48 MW | 2.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.3 MW | 25.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.87 MW | 16.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.56 MW | 39.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.12 MW | 7.12 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.59 MW | 14.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.39 MW | 8.39 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.36 MW | 7.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.6 MW | 1.6 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.11 MW | 1.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.03 MW | 5.03 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.32 MW | 1.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 961791 | AG1-021 C | 50/50 | 2.5 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 961792 | AG1-021 E | 50/50 | 1.67 MW | 1.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 961891 | AG1-030 C | 50/50 | 21.4 MW | 21.4 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 961892 | AG1-030 E | 50/50 | 14.27 MW | 14.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963171 | AG1-166 C | 50/50 | 2.5 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963172 | AG1-166 E | 50/50 | 1.67 MW | 1.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963181 | AG1-167 C | 50/50 | 2.5 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963182 | AG1-167 E | 50/50 | 1.67 MW | 1.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963191 | AG1-168 C | 50/50 | 2.5 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963192 | AG1-168 E | 50/50 | 1.67 MW | 1.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963201 | AG1-169 C | 50/50 | 2.5 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963202 | AG1-169 E | 50/50 | 1.67 MW | 1.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963211 | AG1-170 C | 50/50 | 2.5 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963212 | AG1-170 E | 50/50 | 1.67 MW | 1.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963321 | AG1-181 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 963361 | AG1-185 O1 | 50/50 | 19.12 MW | 19.12 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964111 | AG1-272 C | 50/50 | 6.03 MW | 6.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964112 | AG1-272 E | 50/50 | 1.79 MW | 1.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964121 | AG1-273 C | 50/50 | 6.03 MW | 6.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964122 | AG1-273 E | 50/50 | 1.79 MW | 1.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964131 | AG1-274 C | 50/50 | 6.03 MW | 6.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964132 | AG1-274 E | 50/50 | 1.79 MW | 1.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964241 | AG1-285 C O1 | 50/50 | 29.33 MW | 29.33 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964242 | AG1-285 E O1 | 50/50 | 19.55 MW | 19.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964791 | AG1-342 C | 50/50 | 17.47 MW | 17.47 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 964792 | AG1-342 E | 50/50 | 13.73 MW | 13.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965191 | AG1-384 C | 50/50 | 6.03 MW | 6.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965192 | AG1-384 E | 50/50 | 1.79 MW | 1.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965591 | AG1-427 C | 50/50 | 27.8 MW | 27.8 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965592 | AG1-427 E | 50/50 | 18.57 MW | 18.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965721 | AG1-440 C | Adder | 4.54 MW | 3.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965722 | AG1-440 E | Adder | 3.02 MW | 2.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965731 | AG1-441 C | Adder | 4.54 MW | 3.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965732 | AG1-441 E | Adder | 3.02 MW | 2.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965771 | AG1-445 | Adder | 2.62 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 965781 | AG1-446 | Adder | 2.62 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 313853 | 3PONTONDP | 50/50 | 0.83 MW | 0.83 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 315159 | 1KERR 2 | 50/50 | 0.82 MW | 0.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 315160 | 1KERR 3 | 50/50 | 0.82 MW | 0.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 315161 | 1KERR 4 | 50/50 | 0.82 MW | 0.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 926274 | AC1-105 E | 50/50 | 13.22 MW | 13.22 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 927261 | AC1-222 C | Adder | -1.96 MW | -1.66 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 934311 | AD1-055 C | Adder | -1.36 MW | -1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 936265 | AD2-033 C | 50/50 | 24.3 MW | 24.3 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 936266 | AD2-033 E | 50/50 | 16.2 MW | 16.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 943901 | AF1-058 C | Adder | -1.11 MW | -0.94 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 315163 | 1KERR 6 | 50/50 | 0.82 MW | 0.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 315164 | 1KERR 7 | 50/50 | 0.82 MW | 0.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 316118 | AC1-105 C | 50/50 | 27.64 MW | 27.64 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 316131 | AB2-060 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 924162 | AB2-060 E OP | 50/50 | 9.83 MW | 9.83 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 925611 | AC1-036 C | 50/50 | 0.57 MW | 0.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 925612 | AC1-036 E | 50/50 | 3.64 MW | 3.64 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 939181 | AE1-148 C | 50/50 | 9.17 MW | 9.17 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 939182 | AE1-148 E | 50/50 | 6.11 MW | 6.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 940661 | AE2-053 O1 | 50/50 | 3.4 MW | 3.4 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 946301 | AF1-294 C | 50/50 | 5.13 MW | 5.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 946302 | AF1-294 E | 50/50 | 3.42 MW | 3.42 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 958211 | AF2-115 C | 50/50 | 3.13 MW | 3.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 958212 | AF2-115 E | 50/50 | 2.08 MW | 2.08 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 962561 | AG1-105 C O1 | 50/50 | 34.86 MW | 34.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 962562 | AG1-105 E O1 | 50/50 | 23.24 MW | 23.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 313527 | AB2-043 C | 50/50 | 1.26 MW | 1.26 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | 924022 | AB2-043 E O1 | 50/50 | 6.61 MW | 6.61 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.16 MW | 0.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.18 MW | 0.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.27 MW | 0.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.1 MW | 0.1 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.09 MW | 0.09 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.03 MW | 0.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.39 MW | 0.39 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.08 MW | 0.08 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.08 MW | 0.08 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.13 MW | 0.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.09 MW | 0.09 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 3612 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.22 MW | 0.22 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.44 MW | 3.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.06 MW | 14.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.08 MW | 20.08 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966251 | AG1-494 C | Adder | 1.67 MW | 1.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966252 | AG1-494 E | Adder | 2.5 MW | 2.12 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.3 MW | 6.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.44 MW | 3.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.76 MW | 28.76 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.17 MW | 19.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.4 MW | 25.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.93 MW | 16.93 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.64 MW | 39.64 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.45 MW | 9.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | Adder | -17.76 MW | -15.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.67 MW | 36.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.45 MW | 24.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | Adder | -2.72 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.92 MW | 19.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.73 MW | 0.73 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.85 MW | 14.85 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.88 MW | 8.88 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.68 MW | 7.68 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.82 MW | 0.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.67 MW | 1.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.45 MW | 0.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.17 MW | 1.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.01 MW | 17.01 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966252 | AG1-494 E | Adder | 2.48 MW | 2.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.3 MW | 25.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.87 MW | 16.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.56 MW | 39.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.12 MW | 7.12 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.59 MW | 14.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.39 MW | 8.39 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.36 MW | 7.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.6 MW | 1.6 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.11 MW | 1.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.03 MW | 5.03 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.32 MW | 1.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961791 | AG1-021 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961792 | AG1-021 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961891 | AG1-030 C | 50/50 | 15.91 MW | 15.91 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 961892 | AG1-030 E | 50/50 | 10.61 MW | 10.61 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962491 | AG1-098 C O1 | 50/50 | 25.66 MW | 25.66 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962492 | AG1-098 E O1 | 50/50 | 17.11 MW | 17.11 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963171 | AG1-166 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963172 | AG1-166 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963181 | AG1-167 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963182 | AG1-167 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963191 | AG1-168 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963192 | AG1-168 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963201 | AG1-169 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963202 | AG1-169 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963211 | AG1-170 C | 50/50 | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963212 | AG1-170 E | 50/50 | 1.46 MW | 1.46 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963321 | AG1-181 C O1 | 50/50 | 16.63 MW | 16.63 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963361 | AG1-185 O1 | 50/50 | 8.04 MW | 8.04 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964111 | AG1-272 C | 50/50 | 2.58 MW | 2.58 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964112 | AG1-272 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964121 | AG1-273 C | 50/50 | 2.58 MW | 2.58 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964122 | AG1-273 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964131 | AG1-274 C | 50/50 | 2.58 MW | 2.58 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964132 | AG1-274 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964241 | AG1-285 C O1 | 50/50 | 11.57 MW | 11.57 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964242 | AG1-285 E O1 | 50/50 | 7.72 MW | 7.72 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964791 | AG1-342 C | 50/50 | 5.29 MW | 5.29 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 964792 | AG1-342 E | 50/50 | 4.16 MW | 4.16 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 966691 | AG1-539 C | 50/50 | 4.88 MW | 4.88 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 966692 | AG1-539 E | 50/50 | 6.56 MW | 6.56 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965191 | AG1-384 C | 50/50 | 2.58 MW | 2.58 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965192 | AG1-384 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965591 | AG1-427 C | 50/50 | 10.99 MW | 10.99 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965592 | AG1-427 E | 50/50 | 7.35 MW | 7.35 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965641 | AG1-432 C O1 | 50/50 | 24.21 MW | 24.21 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965642 | AG1-432 E O1 | 50/50 | 16.14 MW | 16.14 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965721 | AG1-440 C | Adder | 4.18 MW | 3.55 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965722 | AG1-440 E | Adder | 2.79 MW | 2.37 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965731 | AG1-441 C | Adder | 4.18 MW | 3.55 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965732 | AG1-441 E | Adder | 2.79 MW | 2.37 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965771 | AG1-445 | Adder | 2.42 MW | 2.05 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965781 | AG1-446 | Adder | 2.42 MW | 2.05 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965831 | AG1-451 | 50/50 | 4.04 MW | 4.04 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 313853 | 3PONTONDP | 50/50 | 0.73 MW | 0.73 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314429 | 3JTRSVLE | 50/50 | 0.5 MW | 0.5 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314713 | 3PAMPLIN | 50/50 | 1.82 MW | 1.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315153 | 1CLOVER1 | 50/50 | 36.85 MW | 36.85 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315154 | 1CLOVER2 | 50/50 | 36.49 MW | 36.49 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926023 | AC1-080 C | 50/50 | 0.39 MW | 0.39 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926274 | AC1-105 E | 50/50 | 3.82 MW | 3.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927251 | AC1-221 C | 50/50 | 2.11 MW | 2.11 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927252 | AC1-221 E | 50/50 | 2.11 MW | 2.11 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927261 | AC1-222 C | 50/50 | 5.42 MW | 5.42 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 927262 | AC1-222 E | 50/50 | 5.16 MW | 5.16 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934311 | AD1-055 C | 50/50 | 3.76 MW | 3.76 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934312 | AD1-055 E | 50/50 | 0.97 MW | 0.97 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934341 | AD1-058 C | 50/50 | 5.3 MW | 5.3 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934342 | AD1-058 E | 50/50 | 1.35 MW | 1.35 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934615 | AD1-087 C | 50/50 | 21.34 MW | 21.34 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934616 | AD1-087 E | 50/50 | 10.01 MW | 10.01 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934625 | AD1-088 C | 50/50 | 28.35 MW | 28.35 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934626 | AD1-088 E | 50/50 | 13.34 MW | 13.34 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934991 | AD1-131 C | 50/50 | 1.74 MW | 1.74 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 934992 | AD1-131 E | 50/50 | 1.16 MW | 1.16 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 935171 | AD1-152 C O1 | 50/50 | 19.21 MW | 19.21 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 935172 | AD1-152 E O1 | 50/50 | 12.81 MW | 12.81 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 936265 | AD2-033 C | 50/50 | 12.77 MW | 12.77 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 936266 | AD2-033 E | 50/50 | 8.51 MW | 8.51 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 937481 | AD2-202 C O1 | 50/50 | 6.25 MW | 6.25 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 937482 | AD2-202 E O1 | 50/50 | 2.93 MW | 2.93 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942461 | AE2-259 C O1 | 50/50 | 12.11 MW | 12.11 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942462 | AE2-259 E O1 | 50/50 | 8.07 MW | 8.07 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942751 | AE2-291 C | 50/50 | 9.33 MW | 9.33 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942752 | AE2-291 E | 50/50 | 6.22 MW | 6.22 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942761 | AE2-292 C O1 | 50/50 | 11.62 MW | 11.62 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 942762 | AE2-292 E O1 | 50/50 | 7.75 MW | 7.75 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 943901 | AF1-058 C | 50/50 | 3.04 MW | 3.04 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 943902 | AF1-058 E | 50/50 | 2.02 MW | 2.02 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958801 | AF2-171 C | 50/50 | 16.35 MW | 16.35 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958802 | AF2-171 E | 50/50 | 10.9 MW | 10.9 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 959311 | AF2-222 C | 50/50 | 16.92 MW | 16.92 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 959312 | AF2-222 E | 50/50 | 11.33 MW | 11.33 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 960061 | AF2-297 C | 50/50 | 12.14 MW | 12.14 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 960062 | AF2-297 E | 50/50 | 8.09 MW | 8.09 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 315266 | 1PLYWOOD A | 50/50 | 1.79 MW | 1.79 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316118 | AC1-105 C | 50/50 | 7.99 MW | 7.99 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316131 | AB2-060 C | 50/50 | 1.4 MW | 1.4 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924162 | AB2-060 E OP | 50/50 | 3.86 MW | 3.86 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924301 | AB2-077 C O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924302 | AB2-077 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924311 | AB2-078 C O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924312 | AB2-078 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924321 | AB2-079 C O1 | 50/50 | 1.8 MW | 1.8 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924322 | AB2-079 E O1 | 50/50 | 1.2 MW | 1.2 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925611 | AC1-036 C | 50/50 | 0.24 MW | 0.24 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925612 | AC1-036 E | 50/50 | 1.55 MW | 1.55 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 932761 | AC2-100 C | 50/50 | 4.86 MW | 4.86 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 932762 | AC2-100 E | 50/50 | 2.37 MW | 2.37 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 938371 | AE1-056 C | 50/50 | 7.27 MW | 7.27 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 938372 | AE1-056 E | 50/50 | 3.97 MW | 3.97 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 939181 | AE1-148 C | 50/50 | 6.28 MW | 6.28 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 939182 | AE1-148 E | 50/50 | 4.19 MW | 4.19 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 940661 | AE2-053 O1 | 50/50 | 2.33 MW | 2.33 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 941791 | AE2-182 C | 50/50 | 4.61 MW | 4.61 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 941792 | AE2-182 E | 50/50 | 2.14 MW | 2.14 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 946301 | AF1-294 C | 50/50 | 4.48 MW | 4.48 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 946302 | AF1-294 E | 50/50 | 2.98 MW | 2.98 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958211 | AF2-115 C | 50/50 | 2.73 MW | 2.73 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 958212 | AF2-115 E | 50/50 | 1.82 MW | 1.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924032 | AB2-045 E | 50/50 | 0.98 MW | 0.98 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 314677 | 6BUCKING | 50/50 | 0.36 MW | 0.36 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962561 | AG1-105 C O1 | 50/50 | 10.82 MW | 10.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 962562 | AG1-105 E O1 | 50/50 | 7.22 MW | 7.22 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 313527 | AB2-043 C | 50/50 | 0.48 MW | 0.48 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 924022 | AB2-043 E O1 | 50/50 | 2.53 MW | 2.53 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 316123 | AC1-075 C | 50/50 | 1.16 MW | 1.16 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 925997 | AC1-075 E | 50/50 | 3.86 MW | 3.86 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 926024 | AC1-080 E | 50/50 | 1.28 MW | 1.28 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963043 | AG1-153 BAT | Adder | 8.71 MW | 7.4 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 963113 | AG1-160 BAT | Adder | 8.5 MW | 7.22 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | 965812 | AG1-449 BAT | 50/50 | 13.37 MW | 13.37 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.75 MW | 1.75 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.66 MW | 0.66 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 31.9 MW | 31.9 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 16.65 MW | 16.65 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.36 MW | 14.36 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.65 MW | 2.65 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.97 MW | 0.97 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.13 MW | 3.13 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.82 MW | 0.82 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.18 MW | 2.18 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.42 MW | 0.42 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.15 MW | 6.15 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.14 MW | 0.14 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.56 MW | 2.56 MW |
| 6CLOVER-8CLOVER 230.0/500.0 kV Ckt 2 transformer l/o DVP_P4-5: L912 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.39 MW | 0.39 MW |
| Details for AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961791 | AG1-021 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961792 | AG1-021 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961891 | AG1-030 C | 50/50 | 37.57 MW | 37.57 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961892 | AG1-030 E | 50/50 | 25.05 MW | 25.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962491 | AG1-098 C O1 | 50/50 | 57.29 MW | 57.29 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962492 | AG1-098 E O1 | 50/50 | 38.19 MW | 38.19 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963171 | AG1-166 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963172 | AG1-166 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963181 | AG1-167 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963182 | AG1-167 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963191 | AG1-168 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963192 | AG1-168 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963201 | AG1-169 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963202 | AG1-169 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963211 | AG1-170 C | 50/50 | 5.52 MW | 5.52 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963212 | AG1-170 E | 50/50 | 3.68 MW | 3.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963321 | AG1-181 C O1 | 50/50 | 32.02 MW | 32.02 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 963361 | AG1-185 O1 | 50/50 | 15.49 MW | 15.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964111 | AG1-272 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964112 | AG1-272 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964121 | AG1-273 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964122 | AG1-273 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964131 | AG1-274 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964132 | AG1-274 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964241 | AG1-285 C O1 | 50/50 | 17.5 MW | 17.5 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 964242 | AG1-285 E O1 | 50/50 | 11.67 MW | 11.67 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965191 | AG1-384 C | 50/50 | 5.21 MW | 5.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965192 | AG1-384 E | 50/50 | 1.55 MW | 1.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965591 | AG1-427 C | 50/50 | 16.79 MW | 16.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965592 | AG1-427 E | 50/50 | 11.21 MW | 11.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965641 | AG1-432 C O1 | 50/50 | 74.7 MW | 74.7 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965642 | AG1-432 E O1 | 50/50 | 49.8 MW | 49.8 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965831 | AG1-451 | 50/50 | 12.45 MW | 12.45 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 313853 | 3PONTONDP | 50/50 | 1.84 MW | 1.84 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314429 | 3JTRSVLE | 50/50 | 1.25 MW | 1.25 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314713 | 3PAMPLIN | 50/50 | 4.9 MW | 4.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315160 | 1KERR 3 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315161 | 1KERR 4 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315162 | 1KERR 5 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 934625 | AD1-088 C | 50/50 | 63.57 MW | 63.57 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 934626 | AD1-088 E | 50/50 | 29.92 MW | 29.92 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 936265 | AD2-033 C | 50/50 | 24.18 MW | 24.18 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 936266 | AD2-033 E | 50/50 | 16.12 MW | 16.12 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 942461 | AE2-259 C O1 | 50/50 | 37.35 MW | 37.35 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 942462 | AE2-259 E O1 | 50/50 | 24.9 MW | 24.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958801 | AF2-171 C | 50/50 | 41.21 MW | 41.21 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958802 | AF2-171 E | 50/50 | 27.47 MW | 27.47 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 959311 | AF2-222 C | 50/50 | 35.51 MW | 35.51 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 959312 | AF2-222 E | 50/50 | 23.79 MW | 23.79 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315163 | 1KERR 6 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 315164 | 1KERR 7 | 50/50 | 0.81 MW | 0.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 316131 | AB2-060 C | 50/50 | 1.89 MW | 1.89 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924162 | AB2-060 E OP | 50/50 | 5.23 MW | 5.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924301 | AB2-077 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924302 | AB2-077 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924311 | AB2-078 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924312 | AB2-078 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924321 | AB2-079 C O1 | 50/50 | 2.23 MW | 2.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924322 | AB2-079 E O1 | 50/50 | 1.49 MW | 1.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 925611 | AC1-036 C | 50/50 | 0.49 MW | 0.49 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 925612 | AC1-036 E | 50/50 | 3.14 MW | 3.14 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 938371 | AE1-056 C | 50/50 | 19.55 MW | 19.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 938372 | AE1-056 E | 50/50 | 10.68 MW | 10.68 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 939181 | AE1-148 C | 50/50 | 6.96 MW | 6.96 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 939182 | AE1-148 E | 50/50 | 4.64 MW | 4.64 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 940661 | AE2-053 O1 | 50/50 | 2.58 MW | 2.58 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 941791 | AE2-182 C | 50/50 | 10.33 MW | 10.33 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 941792 | AE2-182 E | 50/50 | 4.81 MW | 4.81 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946301 | AF1-294 C | 50/50 | 11.32 MW | 11.32 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946302 | AF1-294 E | 50/50 | 7.55 MW | 7.55 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958211 | AF2-115 C | 50/50 | 6.9 MW | 6.9 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958212 | AF2-115 E | 50/50 | 4.6 MW | 4.6 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924032 | AB2-045 E | 50/50 | 4.76 MW | 4.76 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 314677 | 6BUCKING | 50/50 | 1.74 MW | 1.74 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962561 | AG1-105 C O1 | 50/50 | 6.11 MW | 6.11 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962562 | AG1-105 E O1 | 50/50 | 4.07 MW | 4.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.76 MW | 2.76 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.07 MW | 1.07 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.03 MW | 1.03 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.09 MW | 0.09 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.23 MW | 0.23 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.15 MW | 0.15 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.54 MW | 0.54 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| AG1-098 TAP-6CLOVER 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961791 | AG1-021 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961891 | AG1-030 C | 50/50 | 11.7 MW | 11.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961892 | AG1-030 E | 50/50 | 7.8 MW | 7.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963171 | AG1-166 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963181 | AG1-167 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963191 | AG1-168 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963201 | AG1-169 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963211 | AG1-170 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963301 | AG1-179 C | Adder | 3.17 MW | 2.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963311 | AG1-180 | Adder | 1.55 MW | 1.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963321 | AG1-181 C O1 | 50/50 | 15.97 MW | 15.97 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963361 | AG1-185 O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964111 | AG1-272 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964121 | AG1-273 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964131 | AG1-274 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964241 | AG1-285 C O1 | 50/50 | 13.59 MW | 13.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964242 | AG1-285 E O1 | 50/50 | 9.06 MW | 9.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964791 | AG1-342 C | Adder | 2.83 MW | 2.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964792 | AG1-342 E | Adder | 2.22 MW | 1.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965191 | AG1-384 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965591 | AG1-427 C | 50/50 | 12.83 MW | 12.83 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965592 | AG1-427 E | 50/50 | 8.57 MW | 8.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965601 | AG1-428 C O2 | Adder | 2.65 MW | 2.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965602 | AG1-428 E O2 | Adder | 1.76 MW | 1.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965641 | AG1-432 C O1 | Adder | 8.76 MW | 7.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965642 | AG1-432 E O1 | Adder | 5.84 MW | 4.96 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965721 | AG1-440 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965722 | AG1-440 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965731 | AG1-441 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965732 | AG1-441 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965771 | AG1-445 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965781 | AG1-446 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965831 | AG1-451 | Adder | 1.46 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 314713 | 3PAMPLIN | Adder | 1.03 MW | 0.88 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315159 | 1KERR 2 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315160 | 1KERR 3 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315161 | 1KERR 4 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315162 | 1KERR 5 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 926274 | AC1-105 E | Adder | 1.38 MW | 1.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936265 | AD2-033 C | 50/50 | 12.47 MW | 12.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936266 | AD2-033 E | 50/50 | 8.31 MW | 8.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942461 | AE2-259 C O1 | Adder | 4.38 MW | 3.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942462 | AE2-259 E O1 | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958801 | AF2-171 C | 50/50 | 10.69 MW | 10.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958802 | AF2-171 E | 50/50 | 7.13 MW | 7.13 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959311 | AF2-222 C | 50/50 | 14.73 MW | 14.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959312 | AF2-222 E | 50/50 | 9.87 MW | 9.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315163 | 1KERR 6 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315164 | 1KERR 7 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316118 | AC1-105 C | Adder | 2.89 MW | 2.46 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316131 | AB2-060 C | 50/50 | 1.75 MW | 1.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924162 | AB2-060 E OP | 50/50 | 4.84 MW | 4.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924301 | AB2-077 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924302 | AB2-077 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924311 | AB2-078 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924312 | AB2-078 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924321 | AB2-079 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924322 | AB2-079 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925611 | AC1-036 C | 50/50 | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925612 | AC1-036 E | 50/50 | 1.42 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938371 | AE1-056 C | Adder | 4.11 MW | 3.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938372 | AE1-056 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939181 | AE1-148 C | 50/50 | 17.39 MW | 17.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939182 | AE1-148 E | 50/50 | 11.59 MW | 11.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 940661 | AE2-053 O1 | 50/50 | 6.44 MW | 6.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946301 | AF1-294 C | Adder | 2.9 MW | 2.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946302 | AF1-294 E | Adder | 1.94 MW | 1.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958211 | AF2-115 C | Adder | 1.77 MW | 1.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962561 | AG1-105 C O1 | 50/50 | 6.74 MW | 6.74 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962562 | AG1-105 E O1 | 50/50 | 4.5 MW | 4.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924022 | AB2-043 E O1 | 50/50 | 3.25 MW | 3.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.43 MW | 0.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.36 MW | 0.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.34 MW | 1.34 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.8 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.23 MW | 1.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961791 | AG1-021 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961792 | AG1-021 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961891 | AG1-030 C | Adder | 8.71 MW | 7.41 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961892 | AG1-030 E | Adder | 5.81 MW | 4.94 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963171 | AG1-166 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963172 | AG1-166 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963181 | AG1-167 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963182 | AG1-167 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963191 | AG1-168 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963192 | AG1-168 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963201 | AG1-169 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963202 | AG1-169 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963211 | AG1-170 C | Adder | 1.06 MW | 0.9 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963212 | AG1-170 E | Adder | 0.71 MW | 0.6 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963301 | AG1-179 C | Adder | 1.7 MW | 1.44 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963311 | AG1-180 | Adder | 0.83 MW | 0.7 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963321 | AG1-181 C O1 | 50/50 | 11.84 MW | 11.84 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963361 | AG1-185 O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964111 | AG1-272 C | 50/50 | 1.74 MW | 1.74 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964112 | AG1-272 E | 50/50 | 0.52 MW | 0.52 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964121 | AG1-273 C | 50/50 | 1.74 MW | 1.74 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964122 | AG1-273 E | 50/50 | 0.52 MW | 0.52 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964131 | AG1-274 C | 50/50 | 1.74 MW | 1.74 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964132 | AG1-274 E | 50/50 | 0.52 MW | 0.52 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964241 | AG1-285 C O1 | 50/50 | 10.04 MW | 10.04 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964242 | AG1-285 E O1 | 50/50 | 6.7 MW | 6.7 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964791 | AG1-342 C | Adder | 2.5 MW | 2.13 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964792 | AG1-342 E | Adder | 1.97 MW | 1.67 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965191 | AG1-384 C | 50/50 | 1.74 MW | 1.74 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965192 | AG1-384 E | 50/50 | 0.52 MW | 0.52 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965591 | AG1-427 C | 50/50 | 9.48 MW | 9.48 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965592 | AG1-427 E | 50/50 | 6.34 MW | 6.34 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965601 | AG1-428 C O2 | Adder | 1.42 MW | 1.2 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965602 | AG1-428 E O2 | Adder | 0.94 MW | 0.8 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965641 | AG1-432 C O1 | Adder | 6.67 MW | 5.67 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965642 | AG1-432 E O1 | Adder | 4.44 MW | 3.78 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965831 | AG1-451 | Adder | 1.11 MW | 0.94 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313853 | 3PONTONDP | Adder | 0.35 MW | 0.3 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 314713 | 3PAMPLIN | Adder | 0.77 MW | 0.66 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 926274 | AC1-105 E | Adder | 1.39 MW | 1.18 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927261 | AC1-222 C | Adder | 1.47 MW | 1.25 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927262 | AC1-222 E | Adder | 1.4 MW | 1.19 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934311 | AD1-055 C | Adder | 1.02 MW | 0.87 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936265 | AD2-033 C | 50/50 | 9.24 MW | 9.24 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936266 | AD2-033 E | 50/50 | 6.16 MW | 6.16 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942461 | AE2-259 C O1 | Adder | 3.33 MW | 2.83 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942462 | AE2-259 E O1 | Adder | 2.22 MW | 1.89 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943901 | AF1-058 C | Adder | 0.83 MW | 0.71 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943902 | AF1-058 E | Adder | 0.55 MW | 0.47 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958801 | AF2-171 C | Adder | 7.98 MW | 6.79 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958802 | AF2-171 E | Adder | 5.32 MW | 4.53 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959311 | AF2-222 C | 50/50 | 10.94 MW | 10.94 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959312 | AF2-222 E | 50/50 | 7.33 MW | 7.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960061 | AF2-297 C | Adder | 3.33 MW | 2.83 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960062 | AF2-297 E | Adder | 2.22 MW | 1.89 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 315266 | 1PLYWOOD A | 50/50 | 1.07 MW | 1.07 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316118 | AC1-105 C | Adder | 2.91 MW | 2.47 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316129 | AC1-054 C | Adder | -8.29 MW | -7.04 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316131 | AB2-060 C | 50/50 | 1.29 MW | 1.29 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924162 | AB2-060 E OP | 50/50 | 3.58 MW | 3.58 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925611 | AC1-036 C | 50/50 | 0.17 MW | 0.17 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925612 | AC1-036 E | 50/50 | 1.05 MW | 1.05 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938371 | AE1-056 C | Adder | 3.08 MW | 2.62 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938372 | AE1-056 E | Adder | 1.68 MW | 1.43 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946301 | AF1-294 C | Adder | 2.17 MW | 1.84 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946302 | AF1-294 E | Adder | 1.45 MW | 1.23 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958211 | AF2-115 C | Adder | 1.32 MW | 1.12 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958212 | AF2-115 E | Adder | 0.88 MW | 0.75 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962561 | AG1-105 C O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962562 | AG1-105 E O1 | 50/50 | 3.82 MW | 3.82 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313527 | AB2-043 C | 50/50 | 0.46 MW | 0.46 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924022 | AB2-043 E O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965782 | AG1-446 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965772 | AG1-445 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 940662 | AE2-053 BAT | 50/50 | 5.67 MW | 5.67 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.58 MW | 0.58 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.1 MW | 0.1 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.33 MW | 0.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.33 MW | 0.33 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 3KERRDP-3KERR 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
| Details for 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961791 | AG1-021 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961792 | AG1-021 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961891 | AG1-030 C | Adder | 8.71 MW | 7.41 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 961892 | AG1-030 E | Adder | 5.81 MW | 4.94 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963171 | AG1-166 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963172 | AG1-166 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963181 | AG1-167 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963182 | AG1-167 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963191 | AG1-168 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963192 | AG1-168 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963201 | AG1-169 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963202 | AG1-169 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963211 | AG1-170 C | Adder | 1.06 MW | 0.9 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963212 | AG1-170 E | Adder | 0.71 MW | 0.6 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963301 | AG1-179 C | Adder | 1.7 MW | 1.44 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963311 | AG1-180 | Adder | 0.83 MW | 0.7 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963321 | AG1-181 C O1 | 50/50 | 11.84 MW | 11.84 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 963361 | AG1-185 O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964111 | AG1-272 C | 50/50 | 1.74 MW | 1.74 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964112 | AG1-272 E | 50/50 | 0.52 MW | 0.52 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964121 | AG1-273 C | 50/50 | 1.74 MW | 1.74 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964122 | AG1-273 E | 50/50 | 0.52 MW | 0.52 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964131 | AG1-274 C | 50/50 | 1.74 MW | 1.74 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964132 | AG1-274 E | 50/50 | 0.52 MW | 0.52 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964241 | AG1-285 C O1 | 50/50 | 10.04 MW | 10.04 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964242 | AG1-285 E O1 | 50/50 | 6.7 MW | 6.7 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964791 | AG1-342 C | Adder | 2.5 MW | 2.13 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 964792 | AG1-342 E | Adder | 1.97 MW | 1.67 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965191 | AG1-384 C | 50/50 | 1.74 MW | 1.74 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965192 | AG1-384 E | 50/50 | 0.52 MW | 0.52 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965591 | AG1-427 C | 50/50 | 9.48 MW | 9.48 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965592 | AG1-427 E | 50/50 | 6.34 MW | 6.34 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965601 | AG1-428 C O2 | Adder | 1.42 MW | 1.2 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965602 | AG1-428 E O2 | Adder | 0.94 MW | 0.8 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965641 | AG1-432 C O1 | Adder | 6.67 MW | 5.67 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965642 | AG1-432 E O1 | Adder | 4.44 MW | 3.78 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965831 | AG1-451 | Adder | 1.11 MW | 0.94 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313853 | 3PONTONDP | Adder | 0.35 MW | 0.3 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 314713 | 3PAMPLIN | Adder | 0.77 MW | 0.66 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 926274 | AC1-105 E | Adder | 1.39 MW | 1.18 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927261 | AC1-222 C | Adder | 1.47 MW | 1.25 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 927262 | AC1-222 E | Adder | 1.4 MW | 1.19 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934311 | AD1-055 C | Adder | 1.02 MW | 0.87 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 934312 | AD1-055 E | Adder | 0.26 MW | 0.22 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936265 | AD2-033 C | 50/50 | 9.24 MW | 9.24 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 936266 | AD2-033 E | 50/50 | 6.16 MW | 6.16 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942461 | AE2-259 C O1 | Adder | 3.33 MW | 2.83 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 942462 | AE2-259 E O1 | Adder | 2.22 MW | 1.89 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943901 | AF1-058 C | Adder | 0.83 MW | 0.71 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 943902 | AF1-058 E | Adder | 0.55 MW | 0.47 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958801 | AF2-171 C | Adder | 7.98 MW | 6.79 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958802 | AF2-171 E | Adder | 5.32 MW | 4.53 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959311 | AF2-222 C | 50/50 | 10.94 MW | 10.94 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 959312 | AF2-222 E | 50/50 | 7.33 MW | 7.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960061 | AF2-297 C | Adder | 3.33 MW | 2.83 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 960062 | AF2-297 E | Adder | 2.22 MW | 1.89 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 315266 | 1PLYWOOD A | 50/50 | 1.07 MW | 1.07 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316118 | AC1-105 C | Adder | 2.91 MW | 2.47 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316129 | AC1-054 C | Adder | -8.29 MW | -7.04 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 316131 | AB2-060 C | 50/50 | 1.29 MW | 1.29 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924162 | AB2-060 E OP | 50/50 | 3.58 MW | 3.58 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925611 | AC1-036 C | 50/50 | 0.17 MW | 0.17 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 925612 | AC1-036 E | 50/50 | 1.05 MW | 1.05 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938371 | AE1-056 C | Adder | 3.08 MW | 2.62 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 938372 | AE1-056 E | Adder | 1.68 MW | 1.43 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946301 | AF1-294 C | Adder | 2.17 MW | 1.84 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 946302 | AF1-294 E | Adder | 1.45 MW | 1.23 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958211 | AF2-115 C | Adder | 1.32 MW | 1.12 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 958212 | AF2-115 E | Adder | 0.88 MW | 0.75 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962561 | AG1-105 C O1 | 50/50 | 5.73 MW | 5.73 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 962562 | AG1-105 E O1 | 50/50 | 3.82 MW | 3.82 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 313527 | AB2-043 C | 50/50 | 0.46 MW | 0.46 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 924022 | AB2-043 E O1 | 50/50 | 2.4 MW | 2.4 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965782 | AG1-446 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 965772 | AG1-445 BAT | 50/50 | 6.45 MW | 6.45 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | 940662 | AE2-053 BAT | 50/50 | 5.67 MW | 5.67 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.06 MW | 0.06 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.58 MW | 0.58 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.06 MW | 0.06 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.1 MW | 0.1 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.08 MW | 0.08 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.33 MW | 0.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.02 MW | 0.02 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.33 MW | 0.33 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.21 MW | 0.21 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.02 MW | 0.02 MW |
| 3ISLND C-3KERRDP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 171-1009 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 961671 | AG1-007 C | 80/20 | 0.44 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 961791 | AG1-021 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 961891 | AG1-030 C | Adder | 5.15 MW | 4.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 961941 | AG1-037 C | 80/20 | 0.17 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 962331 | AG1-082 C | 80/20 | 0.7 MW | 0.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 962341 | AG1-083 C | 80/20 | 0.7 MW | 0.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 962491 | AG1-098 C O1 | Adder | 3.6 MW | 3.06 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963171 | AG1-166 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963181 | AG1-167 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963191 | AG1-168 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963201 | AG1-169 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963211 | AG1-170 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963301 | AG1-179 C | 80/20 | 2.06 MW | 2.06 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963311 | AG1-180 | 80/20 | 1.0 MW | 1.0 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963321 | AG1-181 C O1 | 80/20 | 6.24 MW | 6.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 963361 | AG1-185 O1 | 80/20 | 3.02 MW | 3.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 964111 | AG1-272 C | 80/20 | 0.94 MW | 0.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 964121 | AG1-273 C | 80/20 | 0.94 MW | 0.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 964131 | AG1-274 C | 80/20 | 0.94 MW | 0.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 964241 | AG1-285 C O1 | 80/20 | 4.9 MW | 4.9 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 964791 | AG1-342 C | 80/20 | 1.81 MW | 1.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 964801 | AG1-343 C | Adder | 1.96 MW | 1.67 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 966801 | AG1-551 C | 80/20 | 0.92 MW | 0.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 966811 | AG1-552 C | 80/20 | 0.79 MW | 0.79 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965191 | AG1-384 C | 80/20 | 0.94 MW | 0.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965291 | AG1-394 C | Adder | 0.67 MW | 0.57 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965591 | AG1-427 C | 80/20 | 4.64 MW | 4.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965601 | AG1-428 C O2 | 80/20 | 1.72 MW | 1.72 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965691 | AG1-437 C O1 | Adder | 3.37 MW | 2.87 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965701 | AG1-438 C O1 | Adder | 3.37 MW | 2.87 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965711 | AG1-439 C O1 | 80/20 | 10.82 MW | 10.82 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965721 | AG1-440 C | 80/20 | 3.25 MW | 3.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965731 | AG1-441 C | 80/20 | 3.25 MW | 3.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965741 | AG1-442 O1 | Adder | 1.97 MW | 1.67 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965751 | AG1-443 O1 | Adder | 1.97 MW | 1.67 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965761 | AG1-444 O1 | 80/20 | 5.77 MW | 5.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965771 | AG1-445 | 80/20 | 1.88 MW | 1.88 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 965781 | AG1-446 | 80/20 | 1.88 MW | 1.88 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 966621 | AG1-532 C | 80/20 | 0.47 MW | 0.47 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 313506 | AB1-173 C OP | 80/20 | 2.42 MW | 2.42 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 313719 | 3CHESTNUT | 80/20 | 0.55 MW | 0.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 314572 | 3EMPORIA | 80/20 | 0.15 MW | 0.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 314582 | 3KELFORD | 80/20 | 0.14 MW | 0.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 314704 | 3LAWRENC | 80/20 | 0.11 MW | 0.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315126 | 1ROARAP2 | 80/20 | 0.54 MW | 0.54 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315128 | 1ROARAP4 | 80/20 | 0.51 MW | 0.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315131 | 1EDGECMA | 80/20 | 3.83 MW | 3.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315132 | 1EDGECMB | 80/20 | 3.83 MW | 3.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315136 | 1ROSEMG1 | 80/20 | 0.82 MW | 0.82 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315137 | 1ROSEMS1 | 80/20 | 0.51 MW | 0.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315138 | 1ROSEMG2 | 80/20 | 0.39 MW | 0.39 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315139 | 1GASTONA | 80/20 | 1.15 MW | 1.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315153 | 1CLOVER1 | 80/20 | 4.73 MW | 4.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315154 | 1CLOVER2 | 80/20 | 4.69 MW | 4.69 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315158 | 1KERR 1 | 80/20 | 0.19 MW | 0.19 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315159 | 1KERR 2 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315160 | 1KERR 3 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315161 | 1KERR 4 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315162 | 1KERR 5 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 920591 | AA2-165 C | 80/20 | 0.07 MW | 0.07 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 926051 | AC1-083 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 926070 | AC1-086 C | 80/20 | 7.58 MW | 7.58 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 926201 | AC1-098 C | 80/20 | 2.51 MW | 2.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 926211 | AC1-099 C | 80/20 | 0.84 MW | 0.84 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 927024 | AC1-189 C | 80/20 | 3.77 MW | 3.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 927145 | AC1-208 C | 80/20 | 3.77 MW | 3.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 927251 | AC1-221 C | 80/20 | 1.65 MW | 1.65 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 927261 | AC1-222 C | 80/20 | 1.62 MW | 1.62 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 933941 | AD1-017 C | 80/20 | 0.89 MW | 0.89 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 934311 | AD1-055 C | 80/20 | 1.13 MW | 1.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 934331 | AD1-057 C O1 | 80/20 | 4.24 MW | 4.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 934341 | AD1-058 C | 80/20 | 4.13 MW | 4.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 934521 | AD1-076 C | Adder | 17.56 MW | 14.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 934615 | AD1-087 C | 80/20 | 2.76 MW | 2.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 934625 | AD1-088 C | Adder | 3.99 MW | 3.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 934991 | AD1-131 C | 80/20 | 1.35 MW | 1.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 935171 | AD1-152 C O1 | 80/20 | 3.49 MW | 3.49 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 936161 | AD2-022 C O1 | 80/20 | 11.06 MW | 11.06 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 936171 | AD2-023 C O1 | 80/20 | 6.45 MW | 6.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 936265 | AD2-033 C | 80/20 | 4.83 MW | 4.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 937481 | AD2-202 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 943171 | AE2-346 C | 80/20 | 0.49 MW | 0.49 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 943901 | AF1-058 C | 80/20 | 0.9 MW | 0.9 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 944141 | AF1-082 | 80/20 | 1.38 MW | 1.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 945811 | AF1-246 C O1 | 80/20 | 2.48 MW | 2.48 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 958801 | AF2-171 C | Adder | 5.0 MW | 4.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 959311 | AF2-222 C | 80/20 | 6.0 MW | 6.0 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 960061 | AF2-297 C | 80/20 | 3.61 MW | 3.61 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 960081 | AF2-299 C | 80/20 | 0.87 MW | 0.87 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315163 | 1KERR 6 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315164 | 1KERR 7 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315266 | 1PLYWOOD A | 80/20 | 0.58 MW | 0.58 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315293 | 1DOMTR9 | Adder | 2.35 MW | 2.0 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315294 | 1DOMTR10 | Adder | 2.88 MW | 2.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.65 MW | 0.65 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315606 | 3AA2-053SOLA | 80/20 | 0.58 MW | 0.58 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 316020 | AB2-059 C OP | 80/20 | 0.86 MW | 0.86 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 316118 | AC1-105 C | 80/20 | 2.54 MW | 2.54 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 316129 | AC1-054 C | 80/20 | 3.07 MW | 3.07 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 316131 | AB2-060 C | 80/20 | 0.62 MW | 0.62 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 316140 | AB2-099 C | 80/20 | 0.2 MW | 0.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 922922 | AB1-081 C OP | 80/20 | 0.73 MW | 0.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 923262 | AB1-132 C OP | 80/20 | 5.15 MW | 5.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 923991 | AB2-040 C O1 | 80/20 | 2.64 MW | 2.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 924301 | AB2-077 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 924311 | AB2-078 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 924321 | AB2-079 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 925121 | AB2-169 C | 80/20 | 0.41 MW | 0.41 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 925591 | AC1-034 C | 80/20 | 3.27 MW | 3.27 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 932631 | AC2-084 C | 80/20 | 3.57 MW | 3.57 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 932761 | AC2-100 C | 80/20 | 3.79 MW | 3.79 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 938371 | AE1-056 C | Adder | 2.08 MW | 1.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 939181 | AE1-148 C | 80/20 | 3.92 MW | 3.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 940081 | AE1-250 C | 80/20 | 15.15 MW | 15.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 940571 | AE2-044 C | 80/20 | 2.14 MW | 2.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 940661 | AE2-053 O1 | 80/20 | 1.45 MW | 1.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 941791 | AE2-182 C | Adder | 0.65 MW | 0.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 946281 | AF1-292 C | 80/20 | 0.51 MW | 0.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 946301 | AF1-294 C | Adder | 1.36 MW | 1.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 957481 | AF2-042 C | 80/20 | 17.71 MW | 17.71 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 957521 | AF2-046 C | Adder | 5.7 MW | 4.84 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 957861 | AF2-080 C | 80/20 | 3.43 MW | 3.43 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 958211 | AF2-115 C | Adder | 0.83 MW | 0.71 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315141 | 1GASTONB | 80/20 | 1.15 MW | 1.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315607 | 3AA1-063SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 316087 | AB2-174 C | 80/20 | 0.42 MW | 0.42 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 938221 | AE1-035 C | 80/20 | 0.13 MW | 0.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 938741 | AE1-100 C O1 | Adder | -10.28 MW | -8.74 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 933981 | AD1-022 C | Adder | 2.88 MW | 2.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 960331 | AF2-324 C | 80/20 | 3.73 MW | 3.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 962561 | AG1-105 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 961681 | AG1-008 C | Adder | 5.71 MW | 4.86 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 962571 | AG1-106 C | 80/20 | 2.11 MW | 2.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 315602 | 1HOLLOMANSOL | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | 313527 | AB2-043 C | 80/20 | 0.22 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.01 MW | 4.01 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.55 MW | 0.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.94 MW | 1.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.31 MW | 0.31 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 69.03 MW | 69.03 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.54 MW | 2.54 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 6.09 MW | 6.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.02 MW | 1.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.51 MW | 0.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.79 MW | 1.79 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.63 MW | 0.63 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.64 MW | 0.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.22 MW | 1.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 242514 05J.FERR 765 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 2.7 MW | 2.7 MW |
| Details for 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 961671 | AG1-007 C | 80/20 | 0.44 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 961791 | AG1-021 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 961891 | AG1-030 C | Adder | 5.15 MW | 4.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 961941 | AG1-037 C | 80/20 | 0.17 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 962331 | AG1-082 C | 80/20 | 0.7 MW | 0.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 962341 | AG1-083 C | 80/20 | 0.7 MW | 0.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 962491 | AG1-098 C O1 | Adder | 3.6 MW | 3.06 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963171 | AG1-166 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963181 | AG1-167 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963191 | AG1-168 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963201 | AG1-169 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963211 | AG1-170 C | Adder | 0.66 MW | 0.56 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963301 | AG1-179 C | 80/20 | 2.06 MW | 2.06 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963311 | AG1-180 | 80/20 | 1.0 MW | 1.0 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963321 | AG1-181 C O1 | 80/20 | 6.24 MW | 6.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 963361 | AG1-185 O1 | 80/20 | 3.02 MW | 3.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 964111 | AG1-272 C | 80/20 | 0.94 MW | 0.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 964121 | AG1-273 C | 80/20 | 0.94 MW | 0.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 964131 | AG1-274 C | 80/20 | 0.94 MW | 0.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 964241 | AG1-285 C O1 | 80/20 | 4.9 MW | 4.9 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 964791 | AG1-342 C | 80/20 | 1.81 MW | 1.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 964801 | AG1-343 C | Adder | 1.96 MW | 1.67 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 966801 | AG1-551 C | 80/20 | 0.92 MW | 0.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 966811 | AG1-552 C | 80/20 | 0.79 MW | 0.79 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965191 | AG1-384 C | 80/20 | 0.94 MW | 0.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965291 | AG1-394 C | Adder | 0.67 MW | 0.57 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965591 | AG1-427 C | 80/20 | 4.64 MW | 4.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965601 | AG1-428 C O2 | 80/20 | 1.72 MW | 1.72 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965691 | AG1-437 C O1 | Adder | 3.37 MW | 2.87 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965701 | AG1-438 C O1 | Adder | 3.37 MW | 2.87 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965711 | AG1-439 C O1 | 80/20 | 10.82 MW | 10.82 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965721 | AG1-440 C | 80/20 | 3.25 MW | 3.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965731 | AG1-441 C | 80/20 | 3.25 MW | 3.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965741 | AG1-442 O1 | Adder | 1.97 MW | 1.67 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965751 | AG1-443 O1 | Adder | 1.97 MW | 1.67 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965761 | AG1-444 O1 | 80/20 | 5.77 MW | 5.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965771 | AG1-445 | 80/20 | 1.88 MW | 1.88 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 965781 | AG1-446 | 80/20 | 1.88 MW | 1.88 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 966621 | AG1-532 C | 80/20 | 0.47 MW | 0.47 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 313506 | AB1-173 C OP | 80/20 | 2.42 MW | 2.42 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 313719 | 3CHESTNUT | 80/20 | 0.55 MW | 0.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 314572 | 3EMPORIA | 80/20 | 0.15 MW | 0.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 314582 | 3KELFORD | 80/20 | 0.14 MW | 0.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 314623 | 3WITAKRS | 80/20 | 0.11 MW | 0.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 314704 | 3LAWRENC | 80/20 | 0.11 MW | 0.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315126 | 1ROARAP2 | 80/20 | 0.54 MW | 0.54 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315128 | 1ROARAP4 | 80/20 | 0.51 MW | 0.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315131 | 1EDGECMA | 80/20 | 3.83 MW | 3.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315132 | 1EDGECMB | 80/20 | 3.83 MW | 3.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315136 | 1ROSEMG1 | 80/20 | 0.82 MW | 0.82 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315137 | 1ROSEMS1 | 80/20 | 0.51 MW | 0.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315138 | 1ROSEMG2 | 80/20 | 0.39 MW | 0.39 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315139 | 1GASTONA | 80/20 | 1.15 MW | 1.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315153 | 1CLOVER1 | 80/20 | 4.73 MW | 4.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315154 | 1CLOVER2 | 80/20 | 4.69 MW | 4.69 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315158 | 1KERR 1 | 80/20 | 0.19 MW | 0.19 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315159 | 1KERR 2 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315160 | 1KERR 3 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315161 | 1KERR 4 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315162 | 1KERR 5 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 920591 | AA2-165 C | 80/20 | 0.07 MW | 0.07 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 926051 | AC1-083 C O1 | 80/20 | 4.45 MW | 4.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 926070 | AC1-086 C | 80/20 | 7.58 MW | 7.58 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 926201 | AC1-098 C | 80/20 | 2.51 MW | 2.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 926211 | AC1-099 C | 80/20 | 0.84 MW | 0.84 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 927024 | AC1-189 C | 80/20 | 3.77 MW | 3.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 927145 | AC1-208 C | 80/20 | 3.77 MW | 3.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 927251 | AC1-221 C | 80/20 | 1.65 MW | 1.65 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 927261 | AC1-222 C | 80/20 | 1.62 MW | 1.62 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 933941 | AD1-017 C | 80/20 | 0.89 MW | 0.89 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 934311 | AD1-055 C | 80/20 | 1.13 MW | 1.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 934331 | AD1-057 C O1 | 80/20 | 4.24 MW | 4.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 934341 | AD1-058 C | 80/20 | 4.13 MW | 4.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 934521 | AD1-076 C | Adder | 17.56 MW | 14.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 934615 | AD1-087 C | 80/20 | 2.76 MW | 2.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 934625 | AD1-088 C | Adder | 3.99 MW | 3.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 934991 | AD1-131 C | 80/20 | 1.35 MW | 1.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 935171 | AD1-152 C O1 | 80/20 | 3.49 MW | 3.49 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 936161 | AD2-022 C O1 | 80/20 | 11.06 MW | 11.06 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 936171 | AD2-023 C O1 | 80/20 | 6.45 MW | 6.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 936265 | AD2-033 C | 80/20 | 4.83 MW | 4.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 937481 | AD2-202 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 943171 | AE2-346 C | 80/20 | 0.49 MW | 0.49 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 943901 | AF1-058 C | 80/20 | 0.9 MW | 0.9 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 944141 | AF1-082 | 80/20 | 1.38 MW | 1.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 945811 | AF1-246 C O1 | 80/20 | 2.48 MW | 2.48 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 958801 | AF2-171 C | Adder | 5.0 MW | 4.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 959311 | AF2-222 C | 80/20 | 6.0 MW | 6.0 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 960061 | AF2-297 C | 80/20 | 3.61 MW | 3.61 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 960081 | AF2-299 C | 80/20 | 0.87 MW | 0.87 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315163 | 1KERR 6 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315164 | 1KERR 7 | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315266 | 1PLYWOOD A | 80/20 | 0.58 MW | 0.58 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315293 | 1DOMTR9 | Adder | 2.35 MW | 2.0 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315294 | 1DOMTR10 | Adder | 2.88 MW | 2.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315601 | 1CONETOE2SOL | 80/20 | 0.65 MW | 0.65 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315606 | 3AA2-053SOLA | 80/20 | 0.58 MW | 0.58 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 316020 | AB2-059 C OP | 80/20 | 0.86 MW | 0.86 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 316118 | AC1-105 C | 80/20 | 2.54 MW | 2.54 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 316129 | AC1-054 C | 80/20 | 3.07 MW | 3.07 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 316131 | AB2-060 C | 80/20 | 0.62 MW | 0.62 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 316140 | AB2-099 C | 80/20 | 0.2 MW | 0.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 922922 | AB1-081 C OP | 80/20 | 0.73 MW | 0.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 923262 | AB1-132 C OP | 80/20 | 5.15 MW | 5.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 923991 | AB2-040 C O1 | 80/20 | 2.64 MW | 2.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 924301 | AB2-077 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 924311 | AB2-078 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 924321 | AB2-079 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 925121 | AB2-169 C | 80/20 | 0.41 MW | 0.41 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 925591 | AC1-034 C | 80/20 | 3.27 MW | 3.27 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 925611 | AC1-036 C | 80/20 | 0.09 MW | 0.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 932631 | AC2-084 C | 80/20 | 3.57 MW | 3.57 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 932761 | AC2-100 C | 80/20 | 3.79 MW | 3.79 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 938371 | AE1-056 C | Adder | 2.08 MW | 1.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 939181 | AE1-148 C | 80/20 | 3.92 MW | 3.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 940081 | AE1-250 C | 80/20 | 15.15 MW | 15.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 940571 | AE2-044 C | 80/20 | 2.14 MW | 2.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 940661 | AE2-053 O1 | 80/20 | 1.45 MW | 1.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 941791 | AE2-182 C | Adder | 0.65 MW | 0.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 946281 | AF1-292 C | 80/20 | 0.51 MW | 0.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 946301 | AF1-294 C | Adder | 1.36 MW | 1.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 957481 | AF2-042 C | 80/20 | 17.71 MW | 17.71 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 957521 | AF2-046 C | Adder | 5.7 MW | 4.84 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 957861 | AF2-080 C | 80/20 | 3.43 MW | 3.43 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 958211 | AF2-115 C | Adder | 0.83 MW | 0.71 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315141 | 1GASTONB | 80/20 | 1.15 MW | 1.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315607 | 3AA1-063SOLA | 80/20 | 0.52 MW | 0.52 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 316087 | AB2-174 C | 80/20 | 0.42 MW | 0.42 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 938221 | AE1-035 C | 80/20 | 0.13 MW | 0.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 938741 | AE1-100 C O1 | Adder | -10.28 MW | -8.74 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 933981 | AD1-022 C | Adder | 2.88 MW | 2.45 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 960331 | AF2-324 C | 80/20 | 3.73 MW | 3.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 962561 | AG1-105 C O1 | 80/20 | 3.84 MW | 3.84 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 961681 | AG1-008 C | Adder | 5.71 MW | 4.86 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 962571 | AG1-106 C | 80/20 | 2.11 MW | 2.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 315602 | 1HOLLOMANSOL | 80/20 | 0.53 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | 313527 | AB2-043 C | 80/20 | 0.22 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 4.01 MW | 4.01 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.55 MW | 0.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.94 MW | 1.94 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.31 MW | 0.31 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 69.03 MW | 69.03 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 2.54 MW | 2.54 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 6.09 MW | 6.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.02 MW | 1.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.51 MW | 0.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.79 MW | 1.79 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.63 MW | 0.63 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.64 MW | 0.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.22 MW | 1.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P2-1_242520 05J.FERR 500 306719 8ANTIOCH 500 1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 2.7 MW | 2.7 MW |
| Details for 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961671 | AG1-007 C | Adder | 0.43 MW | 0.36 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961672 | AG1-007 E | Adder | 0.24 MW | 0.21 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961791 | AG1-021 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961792 | AG1-021 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961891 | AG1-030 C | Adder | 4.85 MW | 4.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961892 | AG1-030 E | Adder | 3.24 MW | 2.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961941 | AG1-037 C | Adder | 0.17 MW | 0.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961942 | AG1-037 E | Adder | 0.11 MW | 0.1 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962331 | AG1-082 C | Adder | 0.67 MW | 0.57 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962332 | AG1-082 E | Adder | 0.45 MW | 0.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962341 | AG1-083 C | Adder | 0.67 MW | 0.57 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962342 | AG1-083 E | Adder | 0.45 MW | 0.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962491 | AG1-098 C O1 | Adder | 3.4 MW | 2.89 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962492 | AG1-098 E O1 | Adder | 2.27 MW | 1.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963171 | AG1-166 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963172 | AG1-166 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963181 | AG1-167 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963182 | AG1-167 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963191 | AG1-168 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963192 | AG1-168 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963201 | AG1-169 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963202 | AG1-169 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963211 | AG1-170 C | Adder | 0.62 MW | 0.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963212 | AG1-170 E | Adder | 0.42 MW | 0.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963301 | AG1-179 C | Adder | 1.97 MW | 1.67 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963311 | AG1-180 | Adder | 0.96 MW | 0.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963321 | AG1-181 C O1 | Adder | 5.91 MW | 5.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 963361 | AG1-185 O1 | Adder | 2.86 MW | 2.43 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964111 | AG1-272 C | Adder | 0.89 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964112 | AG1-272 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964121 | AG1-273 C | Adder | 0.89 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964122 | AG1-273 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964131 | AG1-274 C | Adder | 0.89 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964132 | AG1-274 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964241 | AG1-285 C O1 | Adder | 4.66 MW | 3.96 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964242 | AG1-285 E O1 | Adder | 3.11 MW | 2.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964791 | AG1-342 C | Adder | 1.72 MW | 1.47 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964792 | AG1-342 E | Adder | 1.36 MW | 1.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964801 | AG1-343 C | Adder | 1.87 MW | 1.59 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964802 | AG1-343 E | Adder | 1.47 MW | 1.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966801 | AG1-551 C | Adder | 0.88 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966802 | AG1-551 E | Adder | 0.38 MW | 0.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966811 | AG1-552 C | Adder | 0.76 MW | 0.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966812 | AG1-552 E | Adder | 0.32 MW | 0.28 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965191 | AG1-384 C | Adder | 0.89 MW | 0.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965192 | AG1-384 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965291 | AG1-394 C | Adder | 0.64 MW | 0.54 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965292 | AG1-394 E | Adder | 0.43 MW | 0.36 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965591 | AG1-427 C | Adder | 4.41 MW | 3.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965592 | AG1-427 E | Adder | 2.95 MW | 2.5 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965601 | AG1-428 C O2 | Adder | 1.64 MW | 1.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965602 | AG1-428 E O2 | Adder | 1.09 MW | 0.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965691 | AG1-437 C O1 | Adder | 3.22 MW | 2.74 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965692 | AG1-437 E O1 | Adder | 2.15 MW | 1.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965701 | AG1-438 C O1 | Adder | 3.22 MW | 2.74 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965702 | AG1-438 E O1 | Adder | 2.15 MW | 1.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965711 | AG1-439 C O1 | Adder | 10.5 MW | 8.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965712 | AG1-439 E O1 | Adder | 7.0 MW | 5.95 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965721 | AG1-440 C | Adder | 3.12 MW | 2.65 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965722 | AG1-440 E | Adder | 2.08 MW | 1.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965731 | AG1-441 C | Adder | 3.12 MW | 2.65 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965732 | AG1-441 E | Adder | 2.08 MW | 1.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965741 | AG1-442 O1 | Adder | 1.88 MW | 1.6 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965751 | AG1-443 O1 | Adder | 1.88 MW | 1.6 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965761 | AG1-444 O1 | Adder | 5.6 MW | 4.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965771 | AG1-445 | Adder | 1.8 MW | 1.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965781 | AG1-446 | Adder | 1.8 MW | 1.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966621 | AG1-532 C | Adder | 0.45 MW | 0.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966622 | AG1-532 E | Adder | 0.3 MW | 0.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 313506 | AB1-173 C OP | Adder | 2.31 MW | 1.97 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 313853 | 3PONTONDP | Adder | 0.21 MW | 0.18 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 314572 | 3EMPORIA | Adder | 0.14 MW | 0.12 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 314594 | 6PLYMOTH | Adder | 0.03 MW | 0.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315131 | 1EDGECMA | Adder | 3.72 MW | 3.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315132 | 1EDGECMB | Adder | 3.72 MW | 3.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917512 | Z2-088 E OP1 | Adder | 3.47 MW | 2.95 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 918492 | AA1-063AE OP | Adder | 1.38 MW | 1.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 918532 | AA1-067 E | Adder | 0.3 MW | 0.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 919692 | AA2-053 E OP | Adder | 1.34 MW | 1.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 919702 | AA2-057 E OP | Adder | 1.47 MW | 1.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 920042 | AA2-088 E OP | Adder | 3.26 MW | 2.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 920592 | AA2-165 E | Adder | 0.2 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925785 | AC1-054 E | Adder | 1.36 MW | 1.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926051 | AC1-083 C O1 | 50/50 | 4.16 MW | 4.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926052 | AC1-083 E O1 | 50/50 | 6.79 MW | 6.79 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926070 | AC1-086 C | Adder | 7.28 MW | 6.19 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926071 | AC1-086 E | Adder | 3.31 MW | 2.82 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926201 | AC1-098 C | Adder | 2.42 MW | 2.06 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926202 | AC1-098 E | Adder | 1.44 MW | 1.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926211 | AC1-099 C | Adder | 0.81 MW | 0.69 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926212 | AC1-099 E | Adder | 0.48 MW | 0.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926274 | AC1-105 E | Adder | 1.16 MW | 0.98 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927024 | AC1-189 C | Adder | 3.66 MW | 3.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927025 | AC1-189 E | Adder | 1.82 MW | 1.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927145 | AC1-208 C | Adder | 3.64 MW | 3.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927146 | AC1-208 E | Adder | 1.61 MW | 1.37 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927251 | AC1-221 C | 50/50 | 1.61 MW | 1.61 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927252 | AC1-221 E | 50/50 | 1.61 MW | 1.61 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927261 | AC1-222 C | Adder | 1.53 MW | 1.3 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927262 | AC1-222 E | Adder | 1.46 MW | 1.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933941 | AD1-017 C | 50/50 | 0.83 MW | 0.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933942 | AD1-017 E | 50/50 | 1.36 MW | 1.36 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934311 | AD1-055 C | Adder | 1.06 MW | 0.9 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934312 | AD1-055 E | Adder | 0.27 MW | 0.23 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934331 | AD1-057 C O1 | Adder | 4.1 MW | 3.48 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934332 | AD1-057 E O1 | Adder | 2.19 MW | 1.86 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934341 | AD1-058 C | 50/50 | 4.03 MW | 4.03 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934342 | AD1-058 E | 50/50 | 1.02 MW | 1.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934521 | AD1-076 C | Adder | 16.75 MW | 14.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934522 | AD1-076 E | Adder | 8.53 MW | 7.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934615 | AD1-087 C | Adder | 2.63 MW | 2.23 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934616 | AD1-087 E | Adder | 1.23 MW | 1.05 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934625 | AD1-088 C | Adder | 3.77 MW | 3.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934626 | AD1-088 E | Adder | 1.77 MW | 1.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934991 | AD1-131 C | 50/50 | 1.32 MW | 1.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934992 | AD1-131 E | 50/50 | 0.88 MW | 0.88 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 935171 | AD1-152 C O1 | Adder | 3.35 MW | 2.84 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 935172 | AD1-152 E O1 | Adder | 2.23 MW | 1.9 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936161 | AD2-022 C O1 | 50/50 | 10.83 MW | 10.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936162 | AD2-022 E O1 | 50/50 | 6.5 MW | 6.5 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936171 | AD2-023 C O1 | 50/50 | 6.32 MW | 6.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936172 | AD2-023 E O1 | 50/50 | 3.43 MW | 3.43 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936265 | AD2-033 C | Adder | 4.58 MW | 3.89 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936266 | AD2-033 E | Adder | 3.05 MW | 2.6 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 937481 | AD2-202 C O1 | Adder | 0.77 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 937482 | AD2-202 E O1 | Adder | 0.36 MW | 0.31 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943171 | AE2-346 C | Adder | 0.47 MW | 0.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943172 | AE2-346 E | Adder | 0.2 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943901 | AF1-058 C | Adder | 0.86 MW | 0.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943902 | AF1-058 E | Adder | 0.57 MW | 0.49 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 944141 | AF1-082 | Adder | 1.34 MW | 1.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 945811 | AF1-246 C O1 | Adder | 2.36 MW | 2.0 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 945812 | AF1-246 E O1 | Adder | 3.26 MW | 2.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 958801 | AF2-171 C | Adder | 4.69 MW | 3.99 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 958802 | AF2-171 E | Adder | 3.13 MW | 2.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 959311 | AF2-222 C | Adder | 5.67 MW | 4.82 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 959312 | AF2-222 E | Adder | 3.8 MW | 3.23 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960061 | AF2-297 C | Adder | 3.44 MW | 2.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960062 | AF2-297 E | Adder | 2.29 MW | 1.95 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960081 | AF2-299 C | Adder | 0.83 MW | 0.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960082 | AF2-299 E | Adder | 0.55 MW | 0.47 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 244012 | 05PINNACLE | Adder | -2.07 MW | -1.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 244165 | 05FRIES | Adder | -0.27 MW | -0.23 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315293 | 1DOMTR9 | Adder | 2.25 MW | 1.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315294 | 1DOMTR10 | Adder | 2.76 MW | 2.35 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316088 | AB2-174 E | Adder | 2.15 MW | 1.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316097 | AB2-100 E1 | Adder | 0.86 MW | 0.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316099 | AB2-100 E2 | Adder | 0.86 MW | 0.73 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316118 | AC1-105 C | Adder | 2.42 MW | 2.05 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316129 | AC1-054 C | Adder | 2.95 MW | 2.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316140 | AB2-099 C | Adder | 0.2 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316141 | AB2-099 E | Adder | 0.08 MW | 0.07 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 900672 | V4-068 E | Adder | 0.1 MW | 0.08 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917332 | Z2-043 E | Adder | 0.38 MW | 0.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917342 | Z2-044 E | Adder | 0.26 MW | 0.22 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 922923 | AB1-081 E OP | Adder | 1.78 MW | 1.51 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923262 | AB1-132 C OP | Adder | 4.94 MW | 4.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923263 | AB1-132 E OP | Adder | 2.12 MW | 1.8 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923573 | AB1-173 E OP | Adder | 1.1 MW | 0.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923991 | AB2-040 C O1 | Adder | 2.52 MW | 2.14 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923992 | AB2-040 E O1 | Adder | 2.06 MW | 1.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924152 | AB2-059 E OP | Adder | 2.53 MW | 2.15 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924162 | AB2-060 E OP | Adder | 1.62 MW | 1.38 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924301 | AB2-077 C O1 | Adder | 0.77 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924302 | AB2-077 E O1 | Adder | 0.52 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924311 | AB2-078 C O1 | Adder | 0.77 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924312 | AB2-078 E O1 | Adder | 0.52 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924321 | AB2-079 C O1 | Adder | 0.77 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924322 | AB2-079 E O1 | Adder | 0.52 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925122 | AB2-169 E | Adder | 2.06 MW | 1.75 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925591 | AC1-034 C | Adder | 3.18 MW | 2.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925592 | AC1-034 E | Adder | 2.4 MW | 2.04 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925612 | AC1-036 E | Adder | 0.54 MW | 0.46 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932631 | AC2-084 C | Adder | 3.45 MW | 2.93 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932632 | AC2-084 E | Adder | 1.7 MW | 1.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932761 | AC2-100 C | 50/50 | 3.7 MW | 3.7 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932762 | AC2-100 E | 50/50 | 1.81 MW | 1.81 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 938222 | AE1-035 E | Adder | 0.37 MW | 0.31 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 939181 | AE1-148 C | Adder | 3.76 MW | 3.2 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 939182 | AE1-148 E | Adder | 2.51 MW | 2.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940081 | AE1-250 C | 50/50 | 14.53 MW | 14.53 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940082 | AE1-250 E | 50/50 | 9.69 MW | 9.69 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940571 | AE2-044 C | Adder | 2.08 MW | 1.77 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940572 | AE2-044 E | Adder | 0.89 MW | 0.76 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940661 | AE2-053 O1 | Adder | 1.39 MW | 1.19 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 941791 | AE2-182 C | Adder | 0.61 MW | 0.52 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 941792 | AE2-182 E | Adder | 0.28 MW | 0.24 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 946281 | AF1-292 C | Adder | 0.49 MW | 0.42 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 946282 | AF1-292 E | Adder | 0.33 MW | 0.28 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 946301 | AF1-294 C | Adder | 1.28 MW | 1.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 946302 | AF1-294 E | Adder | 0.85 MW | 0.72 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957481 | AF2-042 C | Adder | 16.85 MW | 14.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957482 | AF2-042 E | Adder | 11.23 MW | 9.55 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957521 | AF2-046 C | Adder | 5.44 MW | 4.63 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957522 | AF2-046 E | Adder | 2.74 MW | 2.33 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957861 | AF2-080 C | Adder | 3.32 MW | 2.83 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957862 | AF2-080 E | Adder | 1.47 MW | 1.25 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 958211 | AF2-115 C | Adder | 0.78 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 958212 | AF2-115 E | Adder | 0.52 MW | 0.44 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 938741 | AE1-100 C O1 | Adder | -10.74 MW | -9.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933981 | AD1-022 C | Adder | 2.75 MW | 2.34 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933982 | AD1-022 E | Adder | 1.5 MW | 1.27 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960331 | AF2-324 C | Adder | 3.63 MW | 3.09 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960332 | AF2-324 E | Adder | 1.95 MW | 1.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962561 | AG1-105 C O1 | Adder | 3.66 MW | 3.11 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962562 | AG1-105 E O1 | Adder | 2.44 MW | 2.07 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962572 | AG1-106 E | Adder | 0.92 MW | 0.78 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961681 | AG1-008 C | Adder | 5.46 MW | 4.64 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961682 | AG1-008 E | Adder | 2.73 MW | 2.32 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962571 | AG1-106 C | Adder | 2.02 MW | 1.72 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 918512 | AA1-065 E OP | Adder | 1.33 MW | 1.13 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924022 | AB2-043 E O1 | Adder | 1.08 MW | 0.92 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 937493 | AD2-205 BAT | Adder | 0.25 MW | 0.21 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943033 | AE2-326 BAT | Adder | 3.48 MW | 2.96 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.96 MW | 3.96 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.17 MW | 0.17 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.29 MW | 1.29 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.16 MW | 0.16 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.4 MW | 0.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 70.03 MW | 70.03 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.4 MW | 6.4 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 6.02 MW | 6.02 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.66 MW | 0.66 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.31 MW | 0.31 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.62 MW | 2.62 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.37 MW | 0.37 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.43 MW | 0.43 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 05EDAN 1-05DANVL2 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.75 MW | 1.75 MW |
| Details for AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961671 | AG1-007 C | Adder | 0.37 MW | 0.31 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 961672 | AG1-007 E | Adder | 0.21 MW | 0.18 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964241 | AG1-285 C O1 | Adder | 4.0 MW | 3.4 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964242 | AG1-285 E O1 | Adder | 2.66 MW | 2.27 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964791 | AG1-342 C | Adder | 1.48 MW | 1.26 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 964792 | AG1-342 E | Adder | 1.16 MW | 0.99 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966801 | AG1-551 C | Adder | 0.76 MW | 0.65 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966802 | AG1-551 E | Adder | 0.32 MW | 0.28 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966811 | AG1-552 C | Adder | 0.65 MW | 0.55 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 966812 | AG1-552 E | Adder | 0.28 MW | 0.24 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965591 | AG1-427 C | Adder | 3.78 MW | 3.21 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965592 | AG1-427 E | Adder | 2.53 MW | 2.15 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965711 | AG1-439 C O1 | Adder | 9.01 MW | 7.66 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965712 | AG1-439 E O1 | Adder | 6.0 MW | 5.1 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965721 | AG1-440 C | Adder | 2.68 MW | 2.27 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965722 | AG1-440 E | Adder | 1.78 MW | 1.52 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965731 | AG1-441 C | Adder | 2.68 MW | 2.27 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965732 | AG1-441 E | Adder | 1.78 MW | 1.52 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965761 | AG1-444 O1 | Adder | 4.8 MW | 4.08 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965771 | AG1-445 | Adder | 1.55 MW | 1.31 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 965781 | AG1-446 | Adder | 1.55 MW | 1.31 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315131 | 1EDGECMA | Adder | 3.19 MW | 2.71 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 315132 | 1EDGECMB | Adder | 3.19 MW | 2.71 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917512 | Z2-088 E OP1 | Adder | 2.98 MW | 2.53 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 918532 | AA1-067 E | Adder | 0.25 MW | 0.21 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 919692 | AA2-053 E OP | Adder | 1.15 MW | 0.97 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 919702 | AA2-057 E OP | Adder | 1.26 MW | 1.07 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 920592 | AA2-165 E | Adder | 0.17 MW | 0.15 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925785 | AC1-054 E | Adder | 1.16 MW | 0.99 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926051 | AC1-083 C O1 | Adder | 3.58 MW | 3.04 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926052 | AC1-083 E O1 | Adder | 5.84 MW | 4.97 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926070 | AC1-086 C | Adder | 6.24 MW | 5.31 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926071 | AC1-086 E | Adder | 2.84 MW | 2.42 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926201 | AC1-098 C | Adder | 2.07 MW | 1.76 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926202 | AC1-098 E | Adder | 1.24 MW | 1.05 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926211 | AC1-099 C | Adder | 0.7 MW | 0.59 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926212 | AC1-099 E | Adder | 0.41 MW | 0.35 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 926274 | AC1-105 E | Adder | 0.99 MW | 0.84 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927024 | AC1-189 C | Adder | 3.14 MW | 2.67 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927025 | AC1-189 E | Adder | 1.56 MW | 1.33 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927145 | AC1-208 C | Adder | 3.12 MW | 2.65 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927146 | AC1-208 E | Adder | 1.38 MW | 1.18 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927251 | AC1-221 C | Adder | 1.38 MW | 1.17 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927252 | AC1-221 E | Adder | 1.38 MW | 1.17 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927261 | AC1-222 C | Adder | 1.31 MW | 1.12 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 927262 | AC1-222 E | Adder | 1.25 MW | 1.06 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933941 | AD1-017 C | Adder | 0.72 MW | 0.61 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 933942 | AD1-017 E | Adder | 1.17 MW | 0.99 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934311 | AD1-055 C | Adder | 0.91 MW | 0.78 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934312 | AD1-055 E | Adder | 0.24 MW | 0.2 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934331 | AD1-057 C O1 | Adder | 3.52 MW | 2.99 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934332 | AD1-057 E O1 | Adder | 1.88 MW | 1.6 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934341 | AD1-058 C | Adder | 3.45 MW | 2.94 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934342 | AD1-058 E | Adder | 0.88 MW | 0.75 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934615 | AD1-087 C | Adder | 2.25 MW | 1.92 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934616 | AD1-087 E | Adder | 1.06 MW | 0.9 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934991 | AD1-131 C | Adder | 1.13 MW | 0.96 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 934992 | AD1-131 E | Adder | 0.76 MW | 0.64 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 935171 | AD1-152 C O1 | Adder | 2.87 MW | 2.44 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 935172 | AD1-152 E O1 | Adder | 1.91 MW | 1.62 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936161 | AD2-022 C O1 | 50/50 | 9.24 MW | 9.24 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936162 | AD2-022 E O1 | 50/50 | 5.55 MW | 5.55 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936171 | AD2-023 C O1 | 50/50 | 5.39 MW | 5.39 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936172 | AD2-023 E O1 | 50/50 | 2.93 MW | 2.93 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936265 | AD2-033 C | Adder | 3.93 MW | 3.34 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 936266 | AD2-033 E | Adder | 2.62 MW | 2.23 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 937481 | AD2-202 C O1 | Adder | 0.66 MW | 0.56 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 937482 | AD2-202 E O1 | Adder | 0.31 MW | 0.26 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943901 | AF1-058 C | Adder | 0.74 MW | 0.63 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 943902 | AF1-058 E | Adder | 0.49 MW | 0.42 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 944141 | AF1-082 | Adder | 1.15 MW | 0.97 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960061 | AF2-297 C | Adder | 2.95 MW | 2.51 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960062 | AF2-297 E | Adder | 1.97 MW | 1.67 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 244012 | 05PINNACLE | 50/50 | 2.66 MW | 2.66 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316118 | AC1-105 C | Adder | 2.07 MW | 1.76 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 316129 | AC1-054 C | Adder | 2.53 MW | 2.15 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917332 | Z2-043 E | Adder | 0.33 MW | 0.28 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 917342 | Z2-044 E | Adder | 0.22 MW | 0.19 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 922923 | AB1-081 E OP | Adder | 1.53 MW | 1.3 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923262 | AB1-132 C OP | Adder | 4.24 MW | 3.6 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 923263 | AB1-132 E OP | Adder | 1.82 MW | 1.54 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924152 | AB2-059 E OP | Adder | 2.17 MW | 1.84 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924162 | AB2-060 E OP | Adder | 1.39 MW | 1.18 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924301 | AB2-077 C O1 | Adder | 0.66 MW | 0.56 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924302 | AB2-077 E O1 | Adder | 0.44 MW | 0.38 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924311 | AB2-078 C O1 | Adder | 0.66 MW | 0.56 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924312 | AB2-078 E O1 | Adder | 0.44 MW | 0.38 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924321 | AB2-079 C O1 | Adder | 0.66 MW | 0.56 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924322 | AB2-079 E O1 | Adder | 0.44 MW | 0.38 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925122 | AB2-169 E | Adder | 1.76 MW | 1.5 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925591 | AC1-034 C | Adder | 2.72 MW | 2.31 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 925592 | AC1-034 E | Adder | 2.05 MW | 1.75 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932631 | AC2-084 C | Adder | 2.96 MW | 2.51 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932632 | AC2-084 E | Adder | 1.46 MW | 1.24 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932761 | AC2-100 C | Adder | 3.17 MW | 2.69 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 932762 | AC2-100 E | Adder | 1.55 MW | 1.31 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 939181 | AE1-148 C | Adder | 3.23 MW | 2.74 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 939182 | AE1-148 E | Adder | 2.15 MW | 1.83 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940081 | AE1-250 C | 50/50 | 12.45 MW | 12.45 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940082 | AE1-250 E | 50/50 | 8.3 MW | 8.3 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940571 | AE2-044 C | Adder | 1.78 MW | 1.52 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940572 | AE2-044 E | Adder | 0.76 MW | 0.65 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 940661 | AE2-053 O1 | Adder | 1.2 MW | 1.02 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 941431 | AE2-140 C O1 | 50/50 | 85.35 MW | 85.35 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 941432 | AE2-140 E O1 | 50/50 | 56.9 MW | 56.9 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957861 | AF2-080 C | Adder | 2.85 MW | 2.42 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 957862 | AF2-080 E | Adder | 1.26 MW | 1.07 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 938741 | AE1-100 C O1 | Adder | -9.45 MW | -8.03 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960331 | AF2-324 C | Adder | 3.12 MW | 2.65 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 960332 | AF2-324 E | Adder | 1.67 MW | 1.42 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962561 | AG1-105 C O1 | Adder | 3.14 MW | 2.67 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962562 | AG1-105 E O1 | Adder | 2.09 MW | 1.78 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962572 | AG1-106 E | Adder | 0.79 MW | 0.67 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 962571 | AG1-106 C | Adder | 1.74 MW | 1.48 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | 924022 | AB2-043 E O1 | Adder | 0.93 MW | 0.79 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 3.4 MW | 3.4 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.15 MW | 0.15 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.11 MW | 1.11 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.14 MW | 0.14 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 60.33 MW | 60.33 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 5.53 MW | 5.53 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 5.17 MW | 5.17 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.57 MW | 0.57 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.26 MW | 2.26 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.37 MW | 0.37 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.74 MW | 1.74 MW |
| AE2-140 TAP-05AXTON 138.0 kV Ckt 1 line l/o AEP_P4_#11112_05J.FERR 765_A1 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.5 MW | 1.5 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| (TBD) | Current Station Rating: S/N: 439, S/E: 439 1) Replace Axton - Danville Line, ACSR/SSAC ~ 795 ~ 26/7 ~ DRAKE/S Conductor Section 3, 2.5 Miles. $3.75M | $3,750,000 | |
| n6124 | PJM Network Upgrade n6124. Increasing the Danville East Danville 138 kV ci [...] e line. | $8,249,851 | |
| n7754.1 | AEPA0021g : Replace 5 Sub cond 2000 AAC 91 Str at Danville2 138kV station | $0 | |
| n7754.2 | AEPA0021h : Replace 3 Sub cond 2000 AAC 91 Str at East Danville 138kV station | $0 | |
| s2143.2 | Replace 2000A non-oil breaker on the 05EDAN 1-05DANVL2 138 kV line | $0 | |
| n7754.3 | The Danville - East Danville 138 kV Circuit will require higher capacity conductor to obtain a rating higher than the 482 MVA achieved by the initial rebuild to 1272 ACSR by AD1-152 . | $456,572 | |
| n8245 | Reconductor 115 kV Line #31 | $700,000 | |
| n7692 | Rebuild 115 kV Line#33 from Barnes Junction D.P. to AG1-105 Tap. | $8,155,000 | |
| n6852 | Add an additional 2 miles single circuit 230 kV line from Fork Union to Bremo parallel to existing line. Add a breaker at Fork Union 230 kV and Bremo 230 kV | $3,500,000 | |
| n6113 | Add additional 230/115 kV transformer at Carolina substation. | $6,000,000 | |
| n7766 | Rebuild 115 kV Line #1012 From AD2-063 Tap-AG1-181 Tap-Central-Twitty's Creek-AF2-222 Tap-Madsonav | $24,835,000 | |
| n7821 | Wreck and rebuild 115 kV line #1012 from Chase City to AG1-285 Tap | $13,400,000 | |
| n7678 | Rebuild 7.46 mi miles of 115 kV Line 33 from Chase City to Barnes Junction. Replace line switch at Branes Junction DP. Replace breaker switch, wave trap, relay trip at Chase City terminal. | $11,890,000 | |
| n6114 | Add additional 230/115 kV transformer at Clubhouse substation. Cost changed during facility study phase. | $13,653,448 | |
| n7819 | Wreck and rebuild 115 kV line #84 from Willis to Farmville to a double circuit. | $20,050,000 | |
| n6246 | Add additional 230/115 kV transformer (#3) for Circuit 1 at Farmville substation | $6,000,000 | |
| n7550 | Add additional 230/115 kV transformer (#4) for Circuit 2 at Farmville substation. | $6,000,000 | |
| n7016 | Reconductor 3.9 miles of 115 kV Line 31 from Grit DP to Otter River with 768.2 ACSS 250 | $2,340,000 | |
| n7015 | Reconductor 8.5 miles of 115 kV Line 31 from Grit to AE2-291 Tap with 768.2 ACSS 250 C. | $5,100,000 | |
| (TBD) | Reconductor 20 miles with single 795 ACSS-TW per phase, replace breaker, disconnect switches, wave trap, line switch | $60,000,000 | |
| s2614 | For DEV portion, rebuild 4.7 miles of 115 kV Line 45 from Kerr Dam to GW King Tap with 768 ACSS. | $6,123,000 | |
| n8269 | Reconductor 115 kV line 193 from Kerr DP to Island Creek DP. | $1,314,000 | |
| n8267 | Reconductor 9.4 miles of 115 kV line 193 from Kerr DP to Kerr Dam with 636 ACSR 150 C | $5,640,000 | |
| n7667 | Rebuild 115 kV Line #33 from Mt. Laurel -AC1-105 Tap -Sedge Hill. | $16,590,000 | |
| n7664 | Rebuild 115 kV Line#33 From AG1-105 Tap -Mt. Laurel. | $3,850,000 | |
| n8257 | Reconductor 115 kV line #1019 from Kerr Dam to Palmer Springs. | $204,000 | |
| n7827 | Rebuild 115 kV line #154 from Madisonville to Pamplin. | $7,905,000 | |
| n7826 | Rebuild 115 kV line #84 from Willis Mountain to Pamplin. | $20,730,000 | |
| n7680 | Rebuild 6.65 miles of 115 kV Line 151 from Plywood to Sedge Hill with 636 ACSR. | $8,645,000 | |
| n7687 | Add additional 230/115 kV transformer at Sedge Hill substation. | $6,000,000 | |
| n5873 | Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. | $500,000 | |
| n7570 | Wreck and Rebuild 230 kV Line #298 From Buckingham to Bremo | $47,675,000 | |
| n6245 | Rebuild 12.76 miles of 230 kV Line 298 from Buckingham to Farmville with 2-768.2 ACSS 250 C. Replace Line Lead, Line Switch, Relay (CT), Wave trap at Farmville terminal | $19,710,000 | |
| n8254 | Rebuild 4.06 miles of 230 kV Line 2060 from Carolina to Roanoke Valley with 2-636 ACSR. | $10,150,000 | |
| n7610 | Rebuild Line 230 kV Line #249 from Carson to Chaparral | $19,125,000 | |
| b3694.8 | Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1047 MVA. | $15,365,000 | |
| n6581 | Rebuild 12.68 miles of 230 kV Line 2002 from Carson to Poe with 2-636 ACSR. | $31,700,000 | |
| n6221 | Rebuild 11.79 miles of 230 kV Line 238 from Sapony to Carson with 2-795 150C ACSR. | $17,685,000 | |
| n7785 | Rebuild 9.46 miles of 230 kV Line 2027 from Bremo to Cartersville with 2-795 ACSR 150 C. Replace breaker lead at Bremo terminal. | $23,650,000 | |
| n8256 | Rebuild 230 kV Line #2027 from Carterville to AC2-165 Tap. | $19,175,000 | |
| n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
| n8249 | Clover Substation: 230/500 kV Transformer Addition | $22,000,000 | |
| n7019 | Rebuild 33.36 miles of 230 kV line 235 from Clover to AD1-088 Tap with 2-636 ACSR. | $50,040,000 | |
| n8303 | Wreck and rebuild 230 kV Line 238 from Clubhouse to AE2-033 TAP. | $22,620,000 | |
| n7567 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $2,445,000 | |
| n6185.2 | Rebuild 17.42 miles of 230 kV Line 2028 from Fork Union to Mount Eagle with 2-636 ACSR. | $26,130,000 | |
| s2609.8 | Rebuild approximately 10 miles segment of 230kV Line #205 from Locks to Tyler and upgrade the terminal equipment. The minimum summer normal rating of the line segment will be 1572MVA. | $27,000,000 | |
| n6179 | Rebuild 12.3 miles of 230 kV Line 2003 from Poe to Harrowgate with 2-636 ACSR. | $30,750,000 | |
| s2824 | Rebuild 230 kV Line #2056 from Hornertown to Hathaway. | $49,100,000 | |
| n7796 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Midlothian with 2-795 ACSR 150 C. | $17,725,000 | |
| n7797 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Powhatan with 2-795 ACSR 150 C | $17,725,000 | |
| n8252 | Rebuild 34.83 miles of 230 kV Line 2012 from Northampton to Earleys with 2-636 ACSR. | $87,075,000 | |
| n8253 | Rebuild 2.87 miles of 230 kV Line 2012 from Roanoke Valley to Northampton with 2-636 ACSR. | $7,175,000 | |
| (TBD) | Reconductor 5 miles with double 795 ACSS-TW per phase, replace disconnect switches | $22,500,000 | |
| n7083 | For DEV portion, rebuild 2 miles of 230 kV Line 296 from AC1-221 Tap to Persons DEP with 2-795 ACSR. | $3,000,000 | |
| n8320 | Dominion and AEP build new Axton-Clover 765 kV line | $600,000,000 | |
| n8243 | Rebuild 4.01 miles of 230 kV Line 2027 from Powhatan to AC2-165 Tap with 2-795 ACSR (26/7) 150 C | $10,025,000 | |
| n6452 | Rebuild 2.47 miles of 230 kV Line 238 from AE2-033 TAP to Sapony with 2-795 150C ACSR. | $3,705,000 | |
| n6178 | Rebuild 4.5 miles of 230 kV Line 2003 from Harrowgate to Tyler with 2-636 ACSR. | $11,250,000 | |
| n7823 | Wreck and rebuild 115 kV line#1012 from AG1-427 Tap to AG1-285 Tap | $3,150,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-427 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.