AG1-426 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:55
Bremo-Scottsville 138 kV
17.0 MW Capacity / 0.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-426 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC) has proposed an uprate to a planned/existing Storage generating facility located in the AEP zone — Buckingham County, Virginia. This project is an increase to the Interconnection Customer's AE1-108 project, which will share the same point of interconnection. The AG1-426 queue position is a 0.0 MW uprate (17.0 MW Capacity uprate) to the previous project. The total installed facilities will have a capability of 149.5 MW with 106.7 MW of this output being recognized by PJM as Capacity. The proposed in-service date for this project is Tuesday, October 31, 2023. This study does not imply a TO commitment to this in-service date.
Project Information | |
Queue Number | AG1-426 |
Project Name | Bremo-Scottsville 138 kV |
Developer Name | Riverstone Solar, LLC |
State | Virginia |
County | Buckingham |
Transmission Owner | AEP |
MFO | 149.5 MW |
MWE | 0.0 MW |
MWC | 17.0 MW |
Fuel Type | Storage |
Basecase Study Year | 2024 |
Point of Interconnection
AG1-426 will interconnect on the AEP transmission system as an uprate to AE1-108 tapping the Scottsville to Bremo Bluff 138 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 0.0 MW (Capacity 17.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
DVP_P1-2: LN 566
CONTINGENCY 'DVP_P1-2: LN 566' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 END |
Single | AC | 111.45 % | 118.79 % | 156.98 | B | 186.47 | 11.68 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
PJM_PLANT BEAR GARDEN
CONTINGENCY 'PJM_PLANT BEAR GARDEN' REMOVE MACHINE G1 FROM BUS 315191 /*1BEARGRDN G1 18.0 REMOVE MACHINE G2 FROM BUS 315192 /*1BEARGRDN G2 18.0 REMOVE MACHINE S1 FROM BUS 315193 /*1BEARGRDN S1 22.0 END |
Single | AC | 108.32 % | 115.62 % | 156.98 | B | 181.5 | 11.69 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 104.89 % | 106.08 % | 169.2 | B | 179.5 | 2.03 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 104.54 % | 105.74 % | 169.2 | B | 178.91 | 2.03 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
DVP_P1-2: LN 548
CONTINGENCY 'DVP_P1-2: LN 548' OPEN BRANCH FROM BUS 314901 TO BUS 314926 CKT 1 /*8BATH CO 500.0 - 8VALLEY 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 99.4 % | 106.77 % | 156.98 | B | 167.61 | 11.69 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
DVP_P1-1: G-S1 1BEARGRDN_S1
CONTINGENCY 'DVP_P1-1: G-S1 1BEARGRDN_S1' REMOVE MACHINE S1 FROM BUS 315193 /*1BEARGRDN S1 22.0 END |
Single | AC | 97.73 % | 105.1 % | 156.98 | B | 164.99 | 11.69 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 99.67 % | 100.12 % | 800.88 | B | 801.83 | 3.46 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P1-2: LN 556-C
CONTINGENCY 'DVP_P1-2: LN 556-C' OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 99.62 % | 100.06 % | 800.88 | B | 801.37 | 3.46 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 99.66 % | 100.1 % | 800.88 | B | 801.68 | 3.46 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P1-2: LN 556-B
CONTINGENCY 'DVP_P1-2: LN 556-B' OPEN BRANCH FROM BUS 945810 TO BUS 966360 CKT 1 /*AF1-246 TAP 500.0 - AG1-505 TAP 500.0 END |
Single | AC | 99.6 % | 100.04 % | 800.88 | B | 801.23 | 3.46 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
DVP_P4-2: 547T566
CONTINGENCY 'DVP_P4-2: 547T566' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 OPEN BRANCH FROM BUS 314901 TO BUS 314912 CKT 1 /*8BATH CO 500.0 - 8LEXNGTN 500.0 END |
Breaker | AC | 150.87 % | 157.0 % | 173.0 | C | 271.62 | 11.68 | |
| DVP |
AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line
938820 to 314746 ckt 1 |
DVP_P4-2: 56602
CONTINGENCY 'DVP_P4-2: 56602' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 OPEN BRANCH FROM BUS 314856 TO BUS 314912 CKT 1 /*6LEXNGT2 230.0 - 8LEXNGTN 500.0 END |
Breaker | AC | 149.6 % | 155.74 % | 173.0 | C | 269.43 | 11.68 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 210622
CONTINGENCY 'DVP_P4-2: 210622' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 95.61 % | 105.11 % | 167.0 | B | 175.53 | 16.2 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 95.59 % | 105.08 % | 167.0 | B | 175.49 | 16.2 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 202722
CONTINGENCY 'DVP_P4-2: 202722' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Breaker | AC | 95.58 % | 105.08 % | 167.0 | B | 175.48 | 16.2 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 547T566
CONTINGENCY 'DVP_P4-2: 547T566' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 OPEN BRANCH FROM BUS 314901 TO BUS 314912 CKT 1 /*8BATH CO 500.0 - 8LEXNGTN 500.0 END |
Breaker | AC | 98.34 % | 104.6 % | 167.0 | B | 174.68 | 13.31 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P4-2: 219322
CONTINGENCY 'DVP_P4-2: 219322' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 94.83 % | 104.37 % | 167.0 | B | 174.3 | 16.2 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 99.92 % | 100.48 % | 980.0 | C | 984.74 | 5.44 | |
| AEP/DVP |
05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line
242792 to 938820 ckt 1 |
DVP_P2-2: BREMO B1
CONTINGENCY 'DVP_P2-2: BREMO B1' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Bus | AC | 95.63 % | 105.12 % | 167.0 | B | 175.55 | 16.2 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 210622
CONTINGENCY 'DVP_P4-2: 210622' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 101.38 % | 110.93 % | 167.0 | B | 185.25 | 16.2 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 101.36 % | 110.91 % | 167.0 | B | 185.21 | 16.2 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 202722
CONTINGENCY 'DVP_P4-2: 202722' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Breaker | AC | 101.35 % | 110.9 % | 167.0 | B | 185.2 | 16.2 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 547T566
CONTINGENCY 'DVP_P4-2: 547T566' OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1 /*05CLOVRD 500.0 - 8LEXNGTN 500.0 OPEN BRANCH FROM BUS 314901 TO BUS 314912 CKT 1 /*8BATH CO 500.0 - 8LEXNGTN 500.0 END |
Breaker | AC | 104.09 % | 110.38 % | 167.0 | B | 184.34 | 13.31 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P4-2: 219322
CONTINGENCY 'DVP_P4-2: 219322' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Breaker | AC | 100.61 % | 110.15 % | 167.0 | B | 183.95 | 16.2 | |
| AEP |
AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line
946590 to 242792 ckt 1 |
DVP_P2-2: BREMO B1
CONTINGENCY 'DVP_P2-2: BREMO B1' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 END |
Bus | AC | 101.43 % | 110.97 % | 167.0 | B | 185.33 | 16.2 | |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 961801 | AG1-022 C | 80/20 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 962741 | AG1-123 C O1 | 80/20 | 5.64 MW | 5.64 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 962751 | AG1-124 C O1 | 80/20 | 7.19 MW | 7.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 966761 | AG1-547 C | 80/20 | 1.64 MW | 1.64 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 965581 | AG1-426 | 80/20 | 11.68 MW | 11.68 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 966251 | AG1-494 C | 80/20 | 3.38 MW | 3.38 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 926521 | AC1-123 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 926645 | AC1-145 C | 80/20 | 0.16 MW | 0.16 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 942671 | AE2-283 C | 80/20 | 1.99 MW | 1.99 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 960111 | AF2-302 C | 80/20 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 961121 | AF2-403 | 80/20 | 0.4 MW | 0.4 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 242889 | 05REUSENS | 80/20 | 0.06 MW | 0.06 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 925661 | AC1-042 C | 80/20 | 0.8 MW | 0.8 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 938821 | AE1-108 C O1 | 80/20 | 61.61 MW | 61.61 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 941801 | AE2-185 C | 80/20 | 1.81 MW | 1.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 941821 | AE2-187 C | 80/20 | 1.81 MW | 1.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 946591 | AF1-323 C | 80/20 | 20.19 MW | 20.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | 958131 | AF2-107 C | 80/20 | 9.19 MW | 9.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.88 MW | 7.88 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.86 MW | 12.86 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.17 MW | 9.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.81 MW | 1.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.57 MW | 1.57 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.52 MW | 1.52 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 566 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 961801 | AG1-022 C | 80/20 | 7.33 MW | 7.33 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 962741 | AG1-123 C O1 | 80/20 | 5.23 MW | 5.23 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 962751 | AG1-124 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 965581 | AG1-426 | 80/20 | 11.69 MW | 11.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 966251 | AG1-494 C | 80/20 | 3.18 MW | 3.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 960111 | AF2-302 C | 80/20 | 7.33 MW | 7.33 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 242889 | 05REUSENS | 80/20 | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 938821 | AE1-108 C O1 | 80/20 | 61.69 MW | 61.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 946591 | AF1-323 C | 80/20 | 20.17 MW | 20.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | 958131 | AF2-107 C | 80/20 | 8.94 MW | 8.94 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.21 MW | 0.21 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.36 MW | 3.36 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.83 MW | 6.83 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.71 MW | 4.71 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.91 MW | 0.91 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.77 MW | 0.77 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o PJM_PLANT BEAR GARDEN | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 6.79 MW | 6.79 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314333 | 6POWHATN | 80/20 | 0.12 MW | 0.12 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.18 MW | 0.18 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | 80/20 | 0.52 MW | 0.52 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 4.14 MW | 4.14 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938561 | AE1-075 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 6.79 MW | 6.79 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314333 | 6POWHATN | 80/20 | 0.12 MW | 0.12 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.18 MW | 0.18 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | 80/20 | 0.52 MW | 0.52 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 4.14 MW | 4.14 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938561 | AE1-075 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 961801 | AG1-022 C | 80/20 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 962741 | AG1-123 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 962751 | AG1-124 C O1 | 80/20 | 6.58 MW | 6.58 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 965581 | AG1-426 | 80/20 | 11.69 MW | 11.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 966251 | AG1-494 C | 80/20 | 3.19 MW | 3.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 960111 | AF2-302 C | 80/20 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 242889 | 05REUSENS | 80/20 | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 938821 | AE1-108 C O1 | 80/20 | 61.7 MW | 61.7 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 946591 | AF1-323 C | 80/20 | 20.18 MW | 20.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | 958131 | AF2-107 C | 80/20 | 8.96 MW | 8.96 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.7 MW | 3.7 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 7.16 MW | 7.16 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.98 MW | 4.98 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.08 MW | 0.08 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.97 MW | 0.97 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.36 MW | 0.36 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.86 MW | 0.86 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.81 MW | 0.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-2: LN 548 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.17 MW | 0.17 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 961801 | AG1-022 C | 80/20 | 7.33 MW | 7.33 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 962741 | AG1-123 C O1 | 80/20 | 5.23 MW | 5.23 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 962751 | AG1-124 C O1 | 80/20 | 6.53 MW | 6.53 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 965581 | AG1-426 | 80/20 | 11.69 MW | 11.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 966251 | AG1-494 C | 80/20 | 3.18 MW | 3.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 960111 | AF2-302 C | 80/20 | 7.33 MW | 7.33 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 242889 | 05REUSENS | 80/20 | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 938821 | AE1-108 C O1 | 80/20 | 61.69 MW | 61.69 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 946591 | AF1-323 C | 80/20 | 20.17 MW | 20.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | 958131 | AF2-107 C | 80/20 | 8.94 MW | 8.94 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.21 MW | 0.21 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.36 MW | 3.36 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.83 MW | 6.83 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.71 MW | 4.71 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.07 MW | 0.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.91 MW | 0.91 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.35 MW | 0.35 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.82 MW | 0.82 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.77 MW | 0.77 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P1-1: G-S1 1BEARGRDN_S1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.16 MW | 0.16 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 11.29 MW | 11.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 8.9 MW | 8.9 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962741 | AG1-123 C O1 | 80/20 | 2.1 MW | 2.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 10.12 MW | 10.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 4.89 MW | 4.89 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 10.64 MW | 10.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.93 MW | 5.93 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 1.67 MW | 1.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 3.46 MW | 3.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.67 MW | 5.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 21.25 MW | 21.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 3.54 MW | 3.54 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966251 | AG1-494 C | 80/20 | 1.22 MW | 1.22 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 9.25 MW | 9.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 9.25 MW | 9.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.37 MW | 0.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 7.73 MW | 7.73 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 7.65 MW | 7.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.11 MW | 0.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 1.41 MW | 1.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 0.98 MW | 0.98 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 4.48 MW | 4.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 9.97 MW | 9.97 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 7.67 MW | 7.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.31 MW | 1.31 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 12.21 MW | 12.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 10.97 MW | 10.97 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 3.07 MW | 3.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 0.48 MW | 0.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 2.24 MW | 2.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 5.71 MW | 5.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 18.23 MW | 18.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 16.7 MW | 16.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 25.2 MW | 25.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 3.35 MW | 3.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 30.83 MW | 30.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958131 | AF2-107 C | 80/20 | 2.99 MW | 2.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 2.04 MW | 2.04 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 33.05 MW | 33.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 19.09 MW | 19.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.58 MW | 0.58 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936761 | AD2-097 C | Adder | -0.9 MW | -0.76 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 6.52 MW | 6.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966671 | AG1-537 C | 80/20 | 1.83 MW | 1.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 9.74 MW | 9.74 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 9.74 MW | 9.74 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 12.59 MW | 12.59 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932854 | AC2-112 C | 80/20 | 5.89 MW | 5.89 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 1.31 MW | 1.31 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938625 | AE1-084 C | 80/20 | 2.84 MW | 2.84 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.22 MW | 0.22 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.34 MW | 0.34 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.12 MW | 8.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.44 MW | 10.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.35 MW | 7.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.46 MW | 0.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.46 MW | 1.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.26 MW | 1.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.21 MW | 1.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961791 | AG1-021 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961801 | AG1-022 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961891 | AG1-030 C | 80/20 | 11.29 MW | 11.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962491 | AG1-098 C O1 | 80/20 | 8.9 MW | 8.9 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962741 | AG1-123 C O1 | 80/20 | 2.1 MW | 2.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963171 | AG1-166 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963181 | AG1-167 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963191 | AG1-168 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963201 | AG1-169 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963211 | AG1-170 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963321 | AG1-181 C O1 | 80/20 | 10.12 MW | 10.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 963361 | AG1-185 O1 | 80/20 | 4.89 MW | 4.89 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964111 | AG1-272 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964121 | AG1-273 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964131 | AG1-274 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964231 | AG1-284 C O1 | 80/20 | 10.64 MW | 10.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964241 | AG1-285 C O1 | 80/20 | 5.93 MW | 5.93 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 964791 | AG1-342 C | 80/20 | 1.67 MW | 1.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965191 | AG1-384 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965581 | AG1-426 | 80/20 | 3.46 MW | 3.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965591 | AG1-427 C | 80/20 | 5.67 MW | 5.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965641 | AG1-432 C O1 | 80/20 | 21.25 MW | 21.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 965831 | AG1-451 | 80/20 | 3.54 MW | 3.54 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966251 | AG1-494 C | 80/20 | 1.22 MW | 1.22 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966361 | AG1-505 C | 80/20 | 9.25 MW | 9.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966371 | AG1-506 C | 80/20 | 9.25 MW | 9.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314429 | 3JTRSVLE | 80/20 | 0.37 MW | 0.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315153 | 1CLOVER1 | 80/20 | 7.73 MW | 7.73 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315154 | 1CLOVER2 | 80/20 | 7.65 MW | 7.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 926023 | AC1-080 C | 80/20 | 0.11 MW | 0.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 927261 | AC1-222 C | 80/20 | 1.41 MW | 1.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934311 | AD1-055 C | 80/20 | 0.98 MW | 0.98 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934615 | AD1-087 C | 80/20 | 4.48 MW | 4.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 934625 | AD1-088 C | 80/20 | 9.97 MW | 9.97 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 935171 | AD1-152 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936265 | AD2-033 C | 80/20 | 7.67 MW | 7.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 937481 | AD2-202 C O1 | 80/20 | 1.31 MW | 1.31 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 942461 | AE2-259 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 943901 | AF1-058 C | 80/20 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 945811 | AF1-246 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958801 | AF2-171 C | 80/20 | 12.21 MW | 12.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 959311 | AF2-222 C | 80/20 | 10.97 MW | 10.97 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960061 | AF2-297 C | 80/20 | 3.07 MW | 3.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 960111 | AF2-302 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315266 | 1PLYWOOD A | 80/20 | 0.48 MW | 0.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316118 | AC1-105 C | 80/20 | 2.24 MW | 2.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316131 | AB2-060 C | 80/20 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924301 | AB2-077 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924311 | AB2-078 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 924321 | AB2-079 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938371 | AE1-056 C | 80/20 | 5.71 MW | 5.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938821 | AE1-108 C O1 | 80/20 | 18.23 MW | 18.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941011 | AE2-092 C | 80/20 | 16.7 MW | 16.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 941791 | AE2-182 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946291 | AF1-293 C O1 | 80/20 | 25.2 MW | 25.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946301 | AF1-294 C | 80/20 | 3.35 MW | 3.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 946591 | AF1-323 C | 80/20 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 957481 | AF2-042 C | 80/20 | 30.83 MW | 30.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958131 | AF2-107 C | 80/20 | 2.99 MW | 2.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958211 | AF2-115 C | 80/20 | 2.04 MW | 2.04 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 933501 | AC2-165 C | 80/20 | 33.05 MW | 33.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 961061 | AF2-397 C | 80/20 | 19.09 MW | 19.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314333 | 6POWHATN | 80/20 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 314677 | 6BUCKING | 80/20 | 0.58 MW | 0.58 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 936761 | AD2-097 C | Adder | -0.9 MW | -0.76 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 958501 | AF2-144 C | 80/20 | 6.52 MW | 6.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 966671 | AG1-537 C | 80/20 | 1.83 MW | 1.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315191 | 1BEARGRDN G1 | 80/20 | 9.74 MW | 9.74 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315192 | 1BEARGRDN G2 | 80/20 | 9.74 MW | 9.74 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 315193 | 1BEARGRDN S1 | 80/20 | 12.59 MW | 12.59 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 932854 | AC2-112 C | 80/20 | 5.89 MW | 5.89 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938561 | AE1-075 C | 80/20 | 1.31 MW | 1.31 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 938625 | AE1-084 C | 80/20 | 2.84 MW | 2.84 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 962561 | AG1-105 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 313527 | AB2-043 C | 80/20 | 0.22 MW | 0.22 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | 316123 | AC1-075 C | 80/20 | 0.34 MW | 0.34 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.12 MW | 8.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.44 MW | 10.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.35 MW | 7.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.46 MW | 0.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.46 MW | 1.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.26 MW | 1.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.21 MW | 1.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 11.29 MW | 11.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 8.9 MW | 8.9 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962741 | AG1-123 C O1 | 80/20 | 2.1 MW | 2.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 10.12 MW | 10.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 4.89 MW | 4.89 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 10.64 MW | 10.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.93 MW | 5.93 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 1.67 MW | 1.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 3.46 MW | 3.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.67 MW | 5.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 21.25 MW | 21.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 3.54 MW | 3.54 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966251 | AG1-494 C | 80/20 | 1.22 MW | 1.22 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.37 MW | 0.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 7.73 MW | 7.73 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 7.65 MW | 7.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.11 MW | 0.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 1.41 MW | 1.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 0.98 MW | 0.98 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 4.48 MW | 4.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 9.97 MW | 9.97 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 7.67 MW | 7.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.31 MW | 1.31 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 12.21 MW | 12.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 10.97 MW | 10.97 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 3.07 MW | 3.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 0.48 MW | 0.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 2.24 MW | 2.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 5.71 MW | 5.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 18.23 MW | 18.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 16.7 MW | 16.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 1.62 MW | 1.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 25.2 MW | 25.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 3.35 MW | 3.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 30.83 MW | 30.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958131 | AF2-107 C | 80/20 | 2.99 MW | 2.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 2.04 MW | 2.04 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 33.05 MW | 33.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 19.09 MW | 19.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.58 MW | 0.58 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936761 | AD2-097 C | Adder | -0.9 MW | -0.76 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 6.52 MW | 6.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966671 | AG1-537 C | 80/20 | 1.83 MW | 1.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 9.74 MW | 9.74 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 9.74 MW | 9.74 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 12.59 MW | 12.59 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932854 | AC2-112 C | 80/20 | 5.89 MW | 5.89 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 1.31 MW | 1.31 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938625 | AE1-084 C | 80/20 | 2.84 MW | 2.84 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.22 MW | 0.22 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.34 MW | 0.34 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.12 MW | 8.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.44 MW | 10.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.35 MW | 7.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.46 MW | 0.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.46 MW | 1.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.26 MW | 1.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.21 MW | 1.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961791 | AG1-021 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961801 | AG1-022 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961891 | AG1-030 C | 80/20 | 11.29 MW | 11.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962491 | AG1-098 C O1 | 80/20 | 8.9 MW | 8.9 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962741 | AG1-123 C O1 | 80/20 | 2.1 MW | 2.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963171 | AG1-166 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963181 | AG1-167 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963191 | AG1-168 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963201 | AG1-169 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963211 | AG1-170 C | 80/20 | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963321 | AG1-181 C O1 | 80/20 | 10.12 MW | 10.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 963361 | AG1-185 O1 | 80/20 | 4.89 MW | 4.89 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964111 | AG1-272 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964121 | AG1-273 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964131 | AG1-274 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964231 | AG1-284 C O1 | 80/20 | 10.64 MW | 10.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964241 | AG1-285 C O1 | 80/20 | 5.93 MW | 5.93 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 964791 | AG1-342 C | 80/20 | 1.67 MW | 1.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965191 | AG1-384 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965581 | AG1-426 | 80/20 | 3.46 MW | 3.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965591 | AG1-427 C | 80/20 | 5.67 MW | 5.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965641 | AG1-432 C O1 | 80/20 | 21.25 MW | 21.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 965831 | AG1-451 | 80/20 | 3.54 MW | 3.54 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966251 | AG1-494 C | 80/20 | 1.22 MW | 1.22 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314429 | 3JTRSVLE | 80/20 | 0.37 MW | 0.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315153 | 1CLOVER1 | 80/20 | 7.73 MW | 7.73 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315154 | 1CLOVER2 | 80/20 | 7.65 MW | 7.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 926023 | AC1-080 C | 80/20 | 0.11 MW | 0.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 927261 | AC1-222 C | 80/20 | 1.41 MW | 1.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934311 | AD1-055 C | 80/20 | 0.98 MW | 0.98 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934615 | AD1-087 C | 80/20 | 4.48 MW | 4.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 934625 | AD1-088 C | 80/20 | 9.97 MW | 9.97 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 935171 | AD1-152 C O1 | 80/20 | 4.12 MW | 4.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936265 | AD2-033 C | 80/20 | 7.67 MW | 7.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 937481 | AD2-202 C O1 | 80/20 | 1.31 MW | 1.31 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 942461 | AE2-259 C O1 | 80/20 | 10.63 MW | 10.63 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 943901 | AF1-058 C | 80/20 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 945811 | AF1-246 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958801 | AF2-171 C | 80/20 | 12.21 MW | 12.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 959311 | AF2-222 C | 80/20 | 10.97 MW | 10.97 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960061 | AF2-297 C | 80/20 | 3.07 MW | 3.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 960111 | AF2-302 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315266 | 1PLYWOOD A | 80/20 | 0.48 MW | 0.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316118 | AC1-105 C | 80/20 | 2.24 MW | 2.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316131 | AB2-060 C | 80/20 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924301 | AB2-077 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924311 | AB2-078 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 924321 | AB2-079 C O1 | 80/20 | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 925611 | AC1-036 C | 80/20 | 0.15 MW | 0.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938371 | AE1-056 C | 80/20 | 5.71 MW | 5.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938821 | AE1-108 C O1 | 80/20 | 18.23 MW | 18.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941011 | AE2-092 C | 80/20 | 16.7 MW | 16.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 941791 | AE2-182 C | 80/20 | 1.62 MW | 1.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946291 | AF1-293 C O1 | 80/20 | 25.2 MW | 25.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946301 | AF1-294 C | 80/20 | 3.35 MW | 3.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 946591 | AF1-323 C | 80/20 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 957481 | AF2-042 C | 80/20 | 30.83 MW | 30.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958131 | AF2-107 C | 80/20 | 2.99 MW | 2.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958211 | AF2-115 C | 80/20 | 2.04 MW | 2.04 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 933501 | AC2-165 C | 80/20 | 33.05 MW | 33.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 961061 | AF2-397 C | 80/20 | 19.09 MW | 19.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314333 | 6POWHATN | 80/20 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 314677 | 6BUCKING | 80/20 | 0.58 MW | 0.58 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 936761 | AD2-097 C | Adder | -0.9 MW | -0.76 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 958501 | AF2-144 C | 80/20 | 6.52 MW | 6.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 966671 | AG1-537 C | 80/20 | 1.83 MW | 1.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315191 | 1BEARGRDN G1 | 80/20 | 9.74 MW | 9.74 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315192 | 1BEARGRDN G2 | 80/20 | 9.74 MW | 9.74 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 315193 | 1BEARGRDN S1 | 80/20 | 12.59 MW | 12.59 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 932854 | AC2-112 C | 80/20 | 5.89 MW | 5.89 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938561 | AE1-075 C | 80/20 | 1.31 MW | 1.31 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 938625 | AE1-084 C | 80/20 | 2.84 MW | 2.84 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 962561 | AG1-105 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 313527 | AB2-043 C | 80/20 | 0.22 MW | 0.22 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | 316123 | AC1-075 C | 80/20 | 0.34 MW | 0.34 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.12 MW | 8.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.44 MW | 10.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.35 MW | 7.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.46 MW | 0.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.46 MW | 1.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.26 MW | 1.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.27 MW | 0.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.21 MW | 1.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 556-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.24 MW | 0.24 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961801 | AG1-022 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961802 | AG1-022 E | 50/50 | 4.89 MW | 4.89 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962741 | AG1-123 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962742 | AG1-123 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962751 | AG1-124 C O1 | 50/50 | 7.19 MW | 7.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962752 | AG1-124 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 965581 | AG1-426 | 50/50 | 11.68 MW | 11.68 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966251 | AG1-494 C | 50/50 | 3.38 MW | 3.38 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966252 | AG1-494 E | 50/50 | 5.07 MW | 5.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946592 | AF1-323 E | 50/50 | 13.46 MW | 13.46 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960111 | AF2-302 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960112 | AF2-302 E | 50/50 | 4.89 MW | 4.89 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 938821 | AE1-108 C O1 | 50/50 | 61.6 MW | 61.6 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 938822 | AE1-108 E O1 | 50/50 | 41.07 MW | 41.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946591 | AF1-323 C | 50/50 | 20.19 MW | 20.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958131 | AF2-107 C | 50/50 | 9.19 MW | 9.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958132 | AF2-107 E | 50/50 | 5.04 MW | 5.04 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946293 | AF1-293 BAT | 50/50 | 8.39 MW | 8.39 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.85 MW | 7.85 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.85 MW | 12.85 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.8 MW | 1.8 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.56 MW | 1.56 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.65 MW | 3.65 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.51 MW | 1.51 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 961801 | AG1-022 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 961802 | AG1-022 E | 50/50 | 4.89 MW | 4.89 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 962741 | AG1-123 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 962742 | AG1-123 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 962751 | AG1-124 C O1 | 50/50 | 7.19 MW | 7.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 962752 | AG1-124 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 965581 | AG1-426 | 50/50 | 11.68 MW | 11.68 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 966251 | AG1-494 C | 50/50 | 3.38 MW | 3.38 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 966252 | AG1-494 E | 50/50 | 5.07 MW | 5.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 946592 | AF1-323 E | 50/50 | 13.46 MW | 13.46 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 960111 | AF2-302 C | 50/50 | 7.34 MW | 7.34 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 960112 | AF2-302 E | 50/50 | 4.89 MW | 4.89 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 938821 | AE1-108 C O1 | 50/50 | 61.61 MW | 61.61 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 938822 | AE1-108 E O1 | 50/50 | 41.07 MW | 41.07 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 946591 | AF1-323 C | 50/50 | 20.19 MW | 20.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 958131 | AF2-107 C | 50/50 | 9.19 MW | 9.19 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 958132 | AF2-107 E | 50/50 | 5.04 MW | 5.04 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | 946293 | AF1-293 BAT | 50/50 | 8.38 MW | 8.38 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.88 MW | 7.88 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.86 MW | 12.86 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.17 MW | 9.17 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.57 MW | 0.57 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.81 MW | 1.81 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.57 MW | 1.57 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.65 MW | 3.65 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.52 MW | 1.52 MW |
| AE1-108 TAP-4BREMO 138.0 kV Ckt 1 line l/o DVP_P4-2: 56602 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961801 | AG1-022 C | 50/50 | 7.34 MW | 7.34 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961802 | AG1-022 E | 50/50 | 4.89 MW | 4.89 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962741 | AG1-123 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962742 | AG1-123 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962751 | AG1-124 C O1 | 50/50 | 7.19 MW | 7.19 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962752 | AG1-124 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966251 | AG1-494 C | 50/50 | 3.38 MW | 3.38 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966252 | AG1-494 E | 50/50 | 5.07 MW | 5.07 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 926522 | AC1-123 E O1 | Adder | 1.34 MW | 1.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946592 | AF1-323 E | 50/50 | 13.46 MW | 13.46 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960111 | AF2-302 C | 50/50 | 7.34 MW | 7.34 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960112 | AF2-302 E | 50/50 | 4.89 MW | 4.89 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946591 | AF1-323 C | 50/50 | 20.19 MW | 20.19 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958131 | AF2-107 C | 50/50 | 9.19 MW | 9.19 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958132 | AF2-107 E | 50/50 | 5.04 MW | 5.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 965582 | AG1-426 BAT | 50/50 | 13.31 MW | 13.31 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946293 | AF1-293 BAT | 50/50 | 8.39 MW | 8.39 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961063 | AF2-397 BAT | Adder | 3.4 MW | 2.89 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.85 MW | 7.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.85 MW | 12.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.8 MW | 1.8 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.56 MW | 1.56 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.65 MW | 3.65 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.51 MW | 1.51 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.01 MW | 17.01 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966252 | AG1-494 E | Adder | 2.48 MW | 2.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.3 MW | 25.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.87 MW | 16.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.56 MW | 39.56 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.12 MW | 7.12 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.59 MW | 14.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.39 MW | 8.39 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.36 MW | 7.36 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.6 MW | 1.6 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.11 MW | 1.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.03 MW | 5.03 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.32 MW | 1.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| 05SCOTSV-AE1-108 TAP 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 210622 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 202722 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961801 | AG1-022 C | 50/50 | 7.34 MW | 7.34 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961802 | AG1-022 E | 50/50 | 4.89 MW | 4.89 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962741 | AG1-123 C O1 | 50/50 | 5.64 MW | 5.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962742 | AG1-123 E O1 | 50/50 | 3.88 MW | 3.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962751 | AG1-124 C O1 | 50/50 | 7.19 MW | 7.19 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 962752 | AG1-124 E O1 | 50/50 | 3.8 MW | 3.8 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966251 | AG1-494 C | 50/50 | 3.38 MW | 3.38 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 966252 | AG1-494 E | 50/50 | 5.07 MW | 5.07 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 926522 | AC1-123 E O1 | Adder | 1.34 MW | 1.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946592 | AF1-323 E | 50/50 | 13.46 MW | 13.46 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960111 | AF2-302 C | 50/50 | 7.34 MW | 7.34 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 960112 | AF2-302 E | 50/50 | 4.89 MW | 4.89 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946591 | AF1-323 C | 50/50 | 20.19 MW | 20.19 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958131 | AF2-107 C | 50/50 | 9.19 MW | 9.19 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 958132 | AF2-107 E | 50/50 | 5.04 MW | 5.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 965582 | AG1-426 BAT | 50/50 | 13.31 MW | 13.31 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 946293 | AF1-293 BAT | 50/50 | 8.39 MW | 8.39 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | 961063 | AF2-397 BAT | Adder | 3.4 MW | 2.89 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.17 MW | 0.17 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.41 MW | 0.41 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 7.85 MW | 7.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 12.85 MW | 12.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.15 MW | 9.15 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.8 MW | 1.8 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.66 MW | 0.66 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.56 MW | 1.56 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.65 MW | 3.65 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.11 MW | 0.11 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.51 MW | 1.51 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 547T566 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.3 MW | 0.3 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P4-2: 219322 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
| Details for AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961801 | AG1-022 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961802 | AG1-022 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962741 | AG1-123 C O1 | 50/50 | 4.69 MW | 4.69 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962742 | AG1-123 E O1 | 50/50 | 3.23 MW | 3.23 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962751 | AG1-124 C O1 | Adder | 5.85 MW | 4.98 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 962752 | AG1-124 E O1 | Adder | 3.09 MW | 2.63 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 966251 | AG1-494 C | 50/50 | 2.85 MW | 2.85 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 966252 | AG1-494 E | 50/50 | 4.28 MW | 4.28 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946592 | AF1-323 E | 50/50 | 12.1 MW | 12.1 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 960111 | AF2-302 C | 50/50 | 6.6 MW | 6.6 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 960112 | AF2-302 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946591 | AF1-323 C | 50/50 | 18.14 MW | 18.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958131 | AF2-107 C | 50/50 | 8.04 MW | 8.04 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 958132 | AF2-107 E | 50/50 | 4.4 MW | 4.4 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 965582 | AG1-426 BAT | 50/50 | 16.2 MW | 16.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 946293 | AF1-293 BAT | 50/50 | 13.64 MW | 13.64 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | 961063 | AF2-397 BAT | Adder | 5.05 MW | 4.29 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.21 MW | 0.21 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.75 MW | 5.75 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.88 MW | 5.88 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.53 MW | 4.53 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.32 MW | 0.32 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.93 MW | 0.93 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.3 MW | 0.3 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.14 MW | 0.14 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.05 MW | 2.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.78 MW | 0.78 MW |
| AF1-323 TAP-05SCOTSV 138.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.14 MW | 0.14 MW |
Light Load Analysis
The Queue Project was evaluated as a 0.0 MW (Capacity 17.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer
314747 to 314744 ckt 1 |
DVP_P1-2: LN 2193
CONTINGENCY 'DVP_P1-2: LN 2193' OPEN BRANCH FROM BUS 313707 TO BUS 313867 CKT 1 /*6FORK UNION 230.0 - 6BREMODIST 230.0 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BUS 313867 /*6BREMODIST 230.0 END |
Single | AC | 129.55 % | 134.86 % | 269.78 | B | 363.83 | 14.15 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 111.78 % | 113.09 % | 661.76 | B | 748.38 | 11.29 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 105.44 % | 106.49 % | 661.76 | B | 704.71 | 11.91 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 111.77 % | 113.08 % | 661.76 | B | 748.32 | 11.29 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 109.71 % | 111.01 % | 661.76 | B | 734.62 | 11.29 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576' OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN 500.0 - 8NO ANNA 500.0 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON 500.0 - 8MDLTHAN 500.0 END |
Single | AC | 103.21 % | 104.25 % | 661.76 | B | 689.88 | 11.91 | |
| Details for 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 940661 | AE2-053 O1 | 80/20 | 1.03 MW | 1.03 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941281 | AE2-122 C O1 | Adder | 3.34 MW | 2.84 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941282 | AE2-122 E O1 | Adder | 13.48 MW | 11.45 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941291 | AE2-123 C O1 | Adder | 3.43 MW | 2.92 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941292 | AE2-123 E O1 | Adder | 13.38 MW | 11.38 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941301 | AE2-124 C O1 | Adder | 3.12 MW | 2.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 941302 | AE2-124 E O1 | Adder | 13.69 MW | 11.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 957911 | AF2-085 | 80/20 | 1.09 MW | 1.09 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 958502 | AF2-144 E | 80/20 | 1.36 MW | 1.36 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964111 | AG1-272 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964112 | AG1-272 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964121 | AG1-273 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964122 | AG1-273 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964131 | AG1-274 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964132 | AG1-274 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964791 | AG1-342 C | 80/20 | 0.18 MW | 0.18 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 964792 | AG1-342 E | 80/20 | 0.27 MW | 0.27 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965191 | AG1-384 C | 80/20 | 0.32 MW | 0.32 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965192 | AG1-384 E | 80/20 | 0.48 MW | 0.48 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965831 | AG1-451 | 80/20 | 2.94 MW | 2.94 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944581 | AF1-123 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944582 | AF1-123 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944591 | AF1-124 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944592 | AF1-124 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944601 | AF1-125 C O1 | Adder | 5.62 MW | 4.77 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 944602 | AF1-125 E O1 | Adder | 12.86 MW | 10.93 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963361 | AG1-185 C | 80/20 | 4.34 MW | 4.34 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 963362 | AG1-185 E | 80/20 | 3.64 MW | 3.64 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 946293 | AF1-293 BAT | 80/20 | 27.71 MW | 27.71 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 961063 | AF2-397 BAT | 80/20 | 8.65 MW | 8.65 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 965583 | AG1-426 BAT | 80/20 | 14.15 MW | 14.15 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 966253 | AG1-494 BAT | 80/20 | 3.94 MW | 3.94 MW |
| 6BREMO-3BREMO 230.0/115.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 2193 | 966673 | AG1-537 BAT | 80/20 | 4.39 MW | 4.39 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315065 | 1CHESTF6 | Adder | 22.19 MW | 18.86 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315083 | 1SPRUNCA | 80/20 | 1.74 MW | 1.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315084 | 1SPRUNCB | 80/20 | 1.74 MW | 1.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315131 | 1EDGECMA | Adder | 1.47 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315132 | 1EDGECMB | Adder | 1.47 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 916042 | Z1-036 E | Adder | 7.44 MW | 6.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | 80/20 | 0.99 MW | 0.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | 80/20 | 1.14 MW | 1.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940661 | AE2-053 O1 | 80/20 | 2.0 MW | 2.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941032 | AE2-094 E | 80/20 | 14.25 MW | 14.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | Adder | 7.09 MW | 6.03 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941282 | AE2-122 E O1 | Adder | 28.62 MW | 24.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | Adder | 7.29 MW | 6.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941292 | AE2-123 E O1 | Adder | 28.43 MW | 24.16 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | Adder | 6.63 MW | 5.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941302 | AE2-124 E O1 | Adder | 29.1 MW | 24.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | Adder | 5.57 MW | 4.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | Adder | 7.96 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | 80/20 | 4.66 MW | 4.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944012 | AF1-069 E | 80/20 | 1.81 MW | 1.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944141 | AF1-082 | Adder | 1.02 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | 80/20 | 4.71 MW | 4.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946291 | AF1-293 C O1 | 80/20 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946292 | AF1-293 E O1 | 80/20 | 15.15 MW | 15.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | Adder | 1.11 MW | 0.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957911 | AF2-085 | 80/20 | 2.09 MW | 2.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958502 | AF2-144 E | 80/20 | 2.27 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | Adder | 8.49 MW | 7.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962332 | AG1-082 E | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962342 | AG1-083 E | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | 80/20 | 2.09 MW | 2.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963042 | AG1-153 E | 80/20 | 3.13 MW | 3.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963102 | AG1-159 E | 80/20 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963112 | AG1-160 E | 80/20 | 3.12 MW | 3.12 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964112 | AG1-272 E | 80/20 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964122 | AG1-273 E | 80/20 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964132 | AG1-274 E | 80/20 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964791 | AG1-342 C | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964792 | AG1-342 E | 80/20 | 0.55 MW | 0.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 | Adder | 7.13 MW | 6.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | Adder | 2.23 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965002 | AG1-364 E O1 | Adder | 3.34 MW | 2.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965192 | AG1-384 E | 80/20 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965761 | AG1-444 O1 | Adder | 4.48 MW | 3.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | 80/20 | 8.7 MW | 8.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965831 | AG1-451 | 80/20 | 4.87 MW | 4.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966251 | AG1-494 C | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966252 | AG1-494 E | 80/20 | 2.0 MW | 2.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966691 | AG1-539 C | 80/20 | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966692 | AG1-539 E | 80/20 | 2.49 MW | 2.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315292 | 1DOMTR78 | Adder | 2.84 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944582 | AF1-123 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944592 | AF1-124 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944602 | AF1-125 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963311 | AG1-180 C | 80/20 | 1.5 MW | 1.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963312 | AG1-180 E | 80/20 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 C | 80/20 | 11.59 MW | 11.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963352 | AG1-184 E | 80/20 | 8.27 MW | 8.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963361 | AG1-185 C | 80/20 | 7.65 MW | 7.65 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963362 | AG1-185 E | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965581 | AG1-426 C | 80/20 | 4.76 MW | 4.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965582 | AG1-426 E | 80/20 | 7.15 MW | 7.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961063 | AF2-397 BAT | 80/20 | 25.66 MW | 25.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963473 | AG1-196 BAT | 80/20 | 10.03 MW | 10.03 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965542 | AG1-422 BAT | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966673 | AG1-537 BAT | 80/20 | 4.53 MW | 4.53 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315065 | 1CHESTF6 | Adder | 22.19 MW | 18.86 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315083 | 1SPRUNCA | 80/20 | 1.74 MW | 1.74 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315084 | 1SPRUNCB | 80/20 | 1.74 MW | 1.74 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315131 | 1EDGECMA | Adder | 1.47 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315132 | 1EDGECMB | Adder | 1.47 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 916042 | Z1-036 E | Adder | 7.44 MW | 6.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940541 | AE2-040 | 80/20 | 0.99 MW | 0.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940651 | AE2-052 | Adder | 1.14 MW | 0.97 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 940661 | AE2-053 O1 | 80/20 | 2.0 MW | 2.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941032 | AE2-094 E | 80/20 | 14.25 MW | 14.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941281 | AE2-122 C O1 | Adder | 7.09 MW | 6.03 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941282 | AE2-122 E O1 | Adder | 28.62 MW | 24.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941291 | AE2-123 C O1 | Adder | 7.29 MW | 6.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941292 | AE2-123 E O1 | Adder | 28.43 MW | 24.16 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941301 | AE2-124 C O1 | Adder | 6.63 MW | 5.64 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941302 | AE2-124 E O1 | Adder | 29.1 MW | 24.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 941591 | AE2-156 O1 | Adder | 5.57 MW | 4.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 942551 | AE2-270 | Adder | 7.96 MW | 6.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944011 | AF1-069 C | 80/20 | 4.66 MW | 4.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944012 | AF1-069 E | 80/20 | 1.81 MW | 1.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944141 | AF1-082 | Adder | 1.02 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946011 | AF1-266 | 80/20 | 4.71 MW | 4.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946291 | AF1-293 C O1 | 80/20 | 10.1 MW | 10.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 946292 | AF1-293 E O1 | 80/20 | 15.15 MW | 15.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957631 | AF2-057 | Adder | 1.11 MW | 0.95 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 957911 | AF2-085 | 80/20 | 2.09 MW | 2.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 958502 | AF2-144 E | 80/20 | 2.27 MW | 2.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961062 | AF2-397 E | 80/20 | 26.99 MW | 26.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961711 | AG1-011 | Adder | 8.49 MW | 7.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962332 | AG1-082 E | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 962342 | AG1-083 E | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963041 | AG1-153 C | 80/20 | 2.09 MW | 2.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963042 | AG1-153 E | 80/20 | 3.13 MW | 3.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963102 | AG1-159 E | 80/20 | 1.24 MW | 1.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963111 | AG1-160 C | 80/20 | 2.08 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963112 | AG1-160 E | 80/20 | 3.12 MW | 3.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964112 | AG1-272 E | 80/20 | 0.84 MW | 0.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964122 | AG1-273 E | 80/20 | 0.84 MW | 0.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964132 | AG1-274 E | 80/20 | 0.84 MW | 0.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964791 | AG1-342 C | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964792 | AG1-342 E | 80/20 | 0.55 MW | 0.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964802 | AG1-343 E | 80/20 | 0.47 MW | 0.47 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 964951 | AG1-359 | Adder | 7.13 MW | 6.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965001 | AG1-364 C O1 | Adder | 2.23 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965002 | AG1-364 E O1 | Adder | 3.34 MW | 2.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965192 | AG1-384 E | 80/20 | 0.84 MW | 0.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965741 | AG1-442 O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965751 | AG1-443 O1 | 80/20 | 2.02 MW | 2.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965761 | AG1-444 O1 | Adder | 4.48 MW | 3.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965811 | AG1-449 | 80/20 | 8.7 MW | 8.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965831 | AG1-451 | 80/20 | 4.87 MW | 4.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966251 | AG1-494 C | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966252 | AG1-494 E | 80/20 | 2.0 MW | 2.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966691 | AG1-539 C | 80/20 | 1.85 MW | 1.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966692 | AG1-539 E | 80/20 | 2.49 MW | 2.49 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 315292 | 1DOMTR78 | Adder | 2.84 MW | 2.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944581 | AF1-123 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944582 | AF1-123 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944591 | AF1-124 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944592 | AF1-124 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944601 | AF1-125 C O1 | Adder | 11.97 MW | 10.18 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 944602 | AF1-125 E O1 | Adder | 27.42 MW | 23.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963311 | AG1-180 C | 80/20 | 1.5 MW | 1.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963312 | AG1-180 E | 80/20 | 1.24 MW | 1.24 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963351 | AG1-184 C | 80/20 | 11.59 MW | 11.59 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963352 | AG1-184 E | 80/20 | 8.27 MW | 8.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963361 | AG1-185 C | 80/20 | 7.65 MW | 7.65 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963362 | AG1-185 E | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965581 | AG1-426 C | 80/20 | 4.76 MW | 4.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965582 | AG1-426 E | 80/20 | 7.15 MW | 7.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 961611 | AG1-000B C | Adder | 4.0 MW | 3.4 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 963473 | AG1-196 BAT | 80/20 | 10.03 MW | 10.03 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 965542 | AG1-422 BAT | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576 | 966673 | AG1-537 BAT | 80/20 | 4.53 MW | 4.53 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n8347.2 | Replace 7.21 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK, Conductor Section 1 | $9,750,000 | |
| n8347.1 | A sag study will be required on the 6.5 miles of ACSR ~ 397.5 ~ 30/7 ~ LARK ~ Conductor | $39,000 | |
| n7811 | A sag study will be required on the 0.85 miles of ACSR ~ 397.5 ~ 30/7 | $3,400 | |
| n6852 | Add an additional 2 miles single circuit 230 kV line from Fork Union to Bremo parallel to existing line. Add a breaker at Fork Union 230 kV and Bremo 230 kV | $3,500,000 | |
| n6378 | Rebuild 6.42 miles of 115 kV Line 91 from AE2-092 Tap to Sherwood with 2-636 ACSR. | $16,050,000 | |
| n7812 | Reconductor 8.502 miles of 138 kV line 8 from AE1-108 Tap to Bremo with 636 ACSR 150 C | $5,101,200 | |
| n8256 | Rebuild 230 kV Line #2027 from Carterville to AC2-165 Tap. | $19,175,000 | |
| n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
| n8453 | Rebuild 5 miles of 230 kV Line 2028 from Fork Union to AF2-397 Tap with 2-636 ACSR. | $7,500,000 | |
| n7796 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Midlothian with 2-795 ACSR 150 C. | $17,725,000 | |
| n7797 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Powhatan with 2-795 ACSR 150 C | $17,725,000 | |
| n8156 | Rebuild 12.1 miles of 230 kV Line 2028 from Mount Eagle to AF2-397 Tap with 2-636 ACSR. | $18,150,000 | |
Attachments
Download all tables in report
| Uprate Chain | |||||
|---|---|---|---|---|---|
| Project | Project Status | MFO | MWE | MWC | Disposition |
| AE1-108 | Engineering & Procurement | 149.5 | 149.5 | 89.7 | Not Part of Transition |
| AG1-426 | Active | 149.5 | 0.0 | 17.0 | Transition Cycle 1 |
Conclusion
The Transition Sort load flow retool results indicate that AG1-426 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.