AG1-423 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:51
Byron-Wayne 345 kV
120.0 MW Capacity / 200.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-423 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the ComEd zone — DeKalb County, Illinois. The installed facilities will have a total capability of 200.0 MW with 120.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-423 |
| Project Name | Byron-Wayne 345 kV |
| Developer Name | Leeward Renewable Energy Development, LLC |
| State | Illinois |
| County | DeKalb |
| Transmission Owner | ComEd |
| MFO | 200.0 MW |
| MWE | 200.0 MW |
| MWC | 120.0 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-423 will interconnect on the ComEd transmission system tapping the Byron - Wayne 345 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 120.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 179.34 % | 180.36 % | 1409.0 | B | 2541.27 | 17.05 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 179.34 % | 180.36 % | 1409.0 | B | 2541.23 | 17.05 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P1-2_345-L18905__B-R-B-2
CONTINGENCY 'COMED_P1-2_345-L18905__B-R-B-2' TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Single | AC | 119.06 % | 121.15 % | 1568.0 | STE | 1899.63 | 30.71 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 120.47 % | 121.54 % | 971.0 | STE | 1180.14 | 11.88 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 120.47 % | 121.54 % | 971.0 | STE | 1180.14 | 11.88 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P1-2_345-L18905__B-R-B-2
CONTINGENCY 'COMED_P1-2_345-L18905__B-R-B-2' TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Single | AC | 113.24 % | 115.31 % | 1568.0 | STE | 1808.12 | 30.71 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 115.07 % | 115.54 % | 971.0 | B | 1121.91 | 11.88 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 115.07 % | 115.54 % | 971.0 | B | 1121.91 | 11.88 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | AC | 114.96 % | 116.04 % | 1399.0 | B | 1623.37 | 15.05 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | AC | 114.96 % | 116.03 % | 1399.0 | B | 1623.32 | 15.05 | |
| CE |
AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line
965553 to 270916 ckt 1 |
COMED_P1-2_345-L97104__-R
CONTINGENCY 'COMED_P1-2_345-L97104__-R' TRIP BRANCH FROM BUS 924470 TO BUS 270883 CKT 1 /*GARDEN PR; R 345.0 - SILVER LK; R 345.0 END |
Single | AC | 96.73 % | 100.07 % | 2107.0 | STE | 2108.46 | 67.97 | |
| CE |
AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line
965553 to 270916 ckt 1 |
Base Case | Single | AC | 96.24 % | 100.07 % | 1679.0 | A | 1680.11 | 64.82 | |
| AEP |
05DUMONT-05SORENS 765.0 kV Ckt 1 line
243206 to 246999 ckt 1 |
AEP_P1-2_#362_1680
CONTINGENCY 'AEP_P1-2_#362_1680' OPEN BRANCH FROM BUS 243207 TO BUS 243208 CKT 1 /*05GRNTWN 765.0 - 05JEFRSO 765.0 END |
Single | AC | 99.85 % | 100.21 % | 4142.0 | B | 4150.57 | 26.14 | |
| AEP |
AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line
958430 to 242928 ckt 1 |
AEP_P1-2_#6457_16758-A
CONTINGENCY 'AEP_P1-2_#6457_16758-A' OPEN BRANCH FROM BUS 242933 TO BUS 965420 CKT 1 /*05RPMONE 345.0 - AG1-410 TAP 345.0 END |
Single | AC | 100.0 % | 100.36 % | 4142.0 | B | 4156.7 | 25.28 | |
| AEP |
AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line
958430 to 242928 ckt 1 |
AEP_P1-2_#6463_16757
CONTINGENCY 'AEP_P1-2_#6463_16757' OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1 /*05E LIMA 345.0 - 05MADDOX 345.0 END |
Single | AC | 99.99 % | 100.34 % | 4142.0 | B | 4155.92 | 25.27 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 160.32 % | 161.14 % | 971.0 | B | 1564.66 | 19.8 | |
| AEP/CE |
AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line
960680 to 243229 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 160.32 % | 161.14 % | 971.0 | B | 1564.66 | 19.8 | |
| CE |
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
270927 to 275233 ckt 1 |
COMED_P4_112-65-BT2-3__
CONTINGENCY 'COMED_P4_112-65-BT2-3__' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 154.49 % | 154.58 % | 1469.0 | STE | 2270.77 | 30.08 | |
| CE |
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
275233 to 270644 ckt 1 |
COMED_P4_112-65-BT2-3__
CONTINGENCY 'COMED_P4_112-65-BT2-3__' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 154.49 % | 154.58 % | 1469.0 | STE | 2270.76 | 30.08 | |
| CE |
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
275232 to 270644 ckt 1 |
COMED_P4_112-65-BT5-6__
CONTINGENCY 'COMED_P4_112-65-BT5-6__' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 151.29 % | 151.38 % | 1469.0 | STE | 2223.76 | 29.45 | |
| CE |
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
270926 to 275232 ckt 1 |
COMED_P4_112-65-BT5-6__
CONTINGENCY 'COMED_P4_112-65-BT5-6__' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 151.29 % | 151.38 % | 1469.0 | STE | 2223.76 | 29.45 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 140.64 % | 143.94 % | 1568.0 | STE | 2256.95 | 50.37 | |
| CE |
GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line
924470 to 270883 ckt 1 |
COMED_P4_144-45-BT6-7__
CONTINGENCY 'COMED_P4_144-45-BT6-7__' DISCONNECT BUS 275228 /*WAYNE ;1M 138.0 TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1 /*WAYNE ; B 345.0 - TOLLWAY ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 END |
Breaker | AC | 140.63 % | 143.93 % | 1568.0 | STE | 2256.89 | 50.37 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 147.88 % | 148.21 % | 971.0 | STE | 1439.12 | 19.8 | |
| CE |
UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line
274804 to 960680 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 147.88 % | 148.21 % | 971.0 | STE | 1439.12 | 19.8 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 131.16 % | 134.45 % | 1568.0 | STE | 2108.17 | 50.37 | |
| CE |
CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line
270694 to 924470 ckt 1 |
COMED_P4_144-45-BT6-7__
CONTINGENCY 'COMED_P4_144-45-BT6-7__' DISCONNECT BUS 275228 /*WAYNE ;1M 138.0 TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1 /*WAYNE ; B 345.0 - TOLLWAY ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 END |
Breaker | AC | 131.16 % | 134.45 % | 1568.0 | STE | 2108.12 | 50.37 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 138.14 % | 138.23 % | 1399.0 | B | 1933.85 | 25.11 | |
| CE/NIPS |
CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line
274750 to 255112 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 138.12 % | 138.21 % | 1399.0 | B | 1933.6 | 25.1 | |
| CE |
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
270770 to 270766 ckt 1 |
COMED_P4_076-45-BT4-5__
CONTINGENCY 'COMED_P4_076-45-BT4-5__' TRIP BRANCH FROM BUS 270664 TO BUS 275162 CKT 1 /*BLUE ISL ; B 345.0 - BLUE ISL ;3M 138.0 TRIP BRANCH FROM BUS 270664 TO BUS 275181 CKT 1 /*BLUE ISL ; B 345.0 - BLUE ISL ;4M 138.0 TRIP BRANCH FROM BUS 270666 TO BUS 270664 CKT 1 /*BLUE ISL ;BT 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270666 TO BUS 270926 CKT 1 /*BLUE ISL ;BT 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 270674 TO BUS 270664 CKT 1 /*BURNHAM ; B 345.0 - BLUE ISL ; B 345.0 TRIP BRANCH FROM BUS 270770 TO BUS 270666 CKT 1 /*GOODINGS ;4B 345.0 - BLUE ISL ;BT 345.0 TRIP BRANCH FROM BUS 275162 TO BUS 271100 CKT 1 /*BLUE ISL ;3M 138.0 - BLUE ISL ; B 138.0 TRIP BRANCH FROM BUS 275181 TO BUS 271100 CKT 1 /*BLUE ISL ;4M 138.0 - BLUE ISL ; B 138.0 TRIP BRANCH FROM BUS 275262 TO BUS 275162 CKT 1 /*BLUE ISLA;3C 34.5 - BLUE ISL ;3M 138.0 TRIP BRANCH FROM BUS 275281 TO BUS 275181 CKT 1 /*BLUE ISLA;4C 34.5 - BLUE ISL ;4M 138.0 END |
Breaker | AC | 105.12 % | 106.01 % | 2083.0 | STE | 2208.12 | 21.21 | |
| CE |
PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275207 to 270630 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 116.27 % | 116.61 % | 1469.0 | STE | 1713.06 | 18.33 | |
| CE |
PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line
270846 to 275207 ckt 1 |
COMED_P4_167-45-BT5-6__
CONTINGENCY 'COMED_P4_167-45-BT5-6__' TRIP BRANCH FROM BUS 270846 TO BUS 270847 CKT 1 /*PLANO ; B 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 270847 TO BUS 270733 CKT 1 /*PLANO ; R 345.0 - ELECT JCT;3R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1 /*PLANO ;4M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1 /*PLANO ;4M 345.0 - PLANO ; R 345.0 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1 /*PLANO ;4M 345.0 - PLANO ;4C 33.0 END |
Breaker | AC | 116.14 % | 116.49 % | 1469.0 | STE | 1711.26 | 18.33 | |
| CE |
PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer
275208 to 270630 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 114.76 % | 115.0 % | 1469.0 | STE | 1689.41 | 16.96 | |
| CE |
PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line
270847 to 275208 ckt 1 |
COMED_P4_167-45-BT8-12_
CONTINGENCY 'COMED_P4_167-45-BT8-12_' TRIP BRANCH FROM BUS 270846 TO BUS 270730 CKT 1 /*PLANO ; B 345.0 - ELECT JCT; B 345.0 TRIP BRANCH FROM BUS 270846 TO BUS 272278 TO BUS 275354 CKT 1 /*PLANO ; B 345.0 - PLANO;1I 138.0 - PLANO;1C 34.5 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 1 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 272250 TO BUS 272278 CKT 2 /*PLANO ; B 138.0 - PLANO;1I 138.0 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1 /*PLANO ;3M 345.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1 /*PLANO ;3M 345.0 - PLANO ; B 345.0 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1 /*PLANO ;3M 345.0 - PLANO ;3C 33.0 END |
Breaker | AC | 114.34 % | 114.59 % | 1469.0 | STE | 1683.32 | 16.96 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 115.03 % | 115.1 % | 1483.0 | STE | 1706.92 | 25.42 | |
| CE |
E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line
270728 to 274750 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 115.02 % | 115.09 % | 1483.0 | STE | 1706.77 | 25.41 | |
| AEP |
05DUMONT-05SORENS 765.0 kV Ckt 1 line
243206 to 246999 ckt 1 |
AEP_P4_#7334_05JEFRSO 765_A2
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2' OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2 /*05JEFRSO 345.0 - 05JEFRSO 765.0 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT Z1 /*05JEFRSO 345.0 - 06CLIFTY 345.0 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 END |
Breaker | AC | 119.35 % | 119.39 % | 4142.0 | B | 4945.01 | 46.29 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 117.86 % | 117.94 % | 1091.0 | B | 1286.7 | 17.93 | |
| CE/NIPS |
17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line
255112 to 270886 ckt 1 |
COMED_P4_112-65-BT4-5__
CONTINGENCY 'COMED_P4_112-65-BT4-5__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1 /*WILTON ;4M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1 /*WILTON ;4M 345.0 - WILTON ; R 345.0 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1 /*WILTON ;4M 345.0 - WILTON ;4C 33.0 END |
Breaker | AC | 117.86 % | 117.94 % | 1091.0 | B | 1286.68 | 17.93 | |
| CE/NIPS |
ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line
270886 to 255104 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 117.85 % | 117.93 % | 1091.0 | B | 1286.65 | 17.93 | |
| CE/NIPS |
17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line
255112 to 270886 ckt 1 |
COMED_P4_112-65-BT3-4__
CONTINGENCY 'COMED_P4_112-65-BT3-4__' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1 /*WILTON ;3M 345.0 - WILTON ; 765.0 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1 /*WILTON ;3M 345.0 - WILTON ; B 345.0 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1 /*WILTON ;3M 345.0 - WILTON ;3C 33.0 END |
Breaker | AC | 117.85 % | 117.93 % | 1091.0 | B | 1286.64 | 17.93 | |
| AEP/CE |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line
270771 to 243229 ckt 1 |
AEP_P4_#1750_05DUMONT 765_B1
CONTINGENCY 'AEP_P4_#1750_05DUMONT 765_B1' OPEN BRANCH FROM BUS 243206 TO BUS 243219 CKT 3 /*05DUMONT 765.0 - 05DUMONT 345.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 112.37 % | 112.59 % | 971.0 | B | 1093.26 | 16.11 | |
| AEP/CE |
GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line
270771 to 243229 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 112.31 % | 112.53 % | 971.0 | B | 1092.67 | 16.05 | |
| AEP/CE |
WILTON ;-05DUMONT 765.0 kV Ckt 1 line
270644 to 243206 ckt 1 |
AEP_P5_#11277_05OLIV_05OLIV
CONTINGENCY 'AEP_P5_#11277_05OLIV_05OLIV' OPEN BRANCH FROM BUS 243215 TO BUS 243229 CKT 1 /*05COOK 345.0 - 05OLIVE 345.0 OPEN BRANCH FROM BUS 243229 TO BUS 243353 CKT 2 /*05OLIVE 345.0 - 05OLIVE 138.0 OPEN BRANCH FROM BUS 243229 TO BUS 270771 CKT 1 /*05OLIVE 345.0 - GREENACRE; T 345.0 OPEN BRANCH FROM BUS 243229 TO BUS 945500 CKT 2 /*05OLIVE 345.0 - AF1-215 TAP 345.0 OPEN BRANCH FROM BUS 243229 TO BUS 958380 CKT 1 /*05OLIVE 345.0 - AF2-132 TAP 345.0 OPEN BRANCH FROM BUS 243229 TO BUS 960680 CKT 1 /*05OLIVE 345.0 - AF2-359 TAP 345.0 OPEN BRANCH FROM BUS 243297 TO BUS 243352 CKT 1 /*05GERMAN 138.0 - 05NTRDAM 138.0 OPEN BRANCH FROM BUS 243297 TO BUS 243353 CKT 1 /*05GERMAN 138.0 - 05OLIVE 138.0 OPEN BRANCH FROM BUS 243353 TO BUS 244173 CKT 1 /*05OLIVE 138.0 - 05SILVER LAK 138.0 OPEN BRANCH FROM BUS 243353 TO BUS 246345 CKT 1 /*05OLIVE 138.0 - 05OLIVE 69.0 OPEN BRANCH FROM BUS 243918 TO BUS 243229 CKT 1 /*05ELDERBERRY 345.0 - 05OLIVE 345.0 OPEN BRANCH FROM BUS 244930 TO BUS 243349 CKT Z1 /*05NEW CARLI1 138.0 - 05NEW CARLI2 138.0 OPEN BRANCH FROM BUS 244930 TO BUS 243353 CKT 1 /*05NEW CARLI1 138.0 - 05OLIVE 138.0 OPEN BRANCH FROM BUS 246075 TO BUS 243286 CKT ZA /*05EDISON1 138.0 - 05EDISON2 138.0 OPEN BRANCH FROM BUS 246075 TO BUS 243353 CKT 1 /*05EDISON1 138.0 - 05OLIVE 138.0 OPEN BRANCH FROM BUS 246092 TO BUS 243353 CKT 1 /*05NEW CAR_BP 138.0 - 05OLIVE 138.0 OPEN BRANCH FROM BUS 246092 TO BUS 246994 CKT 1 /*05NEW CAR_BP 138.0 - 05RICKMN 138.0 OPEN BRANCH FROM BUS 246342 TO BUS 247599 CKT Z1 /*05MONOFRAX 69.0 - 05SNOWBRY SS 69.0 OPEN BRANCH FROM BUS 247599 TO BUS 246345 CKT 1 /*05SNOWBRY SS 69.0 - 05OLIVE 69.0 REMOVE LOAD C1 FROM BUS 243352 /*05NTRDAM 138.0 REMOVE LOAD C1 FROM BUS 246075 /*05EDISON1 138.0 REMOVE LOAD C1 FROM BUS 246342 /*05MONOFRAX 69.0 REMOVE LOAD D1 FROM BUS 243297 /*05GERMAN 138.0 REMOVE LOAD D1 FROM BUS 243349 /*05NEW CARLI2 138.0 REMOVE LOAD D1 FROM BUS 246994 /*05RICKMN 138.0 REMOVE LOAD D2 FROM BUS 243297 /*05GERMAN 138.0 REMOVE LOAD D2 FROM BUS 244173 /*05SILVER LAK 138.0 REMOVE LOAD D3 FROM BUS 244173 /*05SILVER LAK 138.0 REMOVE LOAD D4 FROM BUS 243353 /*05OLIVE 138.0 REMOVE LOAD D5 FROM BUS 243353 /*05OLIVE 138.0 END |
Breaker | AC | 110.5 % | 110.59 % | 4105.0 | B | 4539.68 | 63.61 | |
| CE |
NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line
270828 to 965660 ckt 1 |
COMED_P4_144-45-BT6-8__
CONTINGENCY 'COMED_P4_144-45-BT6-8__' TRIP BRANCH FROM BUS 270730 TO BUS 270916 CKT 1 /*ELECT JCT; B 345.0 - WAYNE ; B 345.0 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT 1 /*WAYNE ; B 345.0 - WAYNE ; R 345.0 TRIP BRANCH FROM BUS 965553 TO BUS 270916 CKT 1 /*AG1-423 TP 345.0 - WAYNE ; B 345.0 END |
Breaker | AC | 103.68 % | 105.2 % | 1656.0 | B | 1742.19 | 29.61 | |
| AEP |
05DUMONT-05SORENS 765.0 kV Ckt 1 line
243206 to 246999 ckt 1 |
AEP_P4_#6189_05HANG R 765_D1
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1' OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1 /*05CORNU 765.0 - 05HANG R 765.0 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1 /*05CORNU 765.0 - 05CORNU 345.0 OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 REMOVE UNIT 1A FROM BUS 247245 /*05HRKG1A 18.0 REMOVE UNIT 1B FROM BUS 247246 /*05HRKG1B 18.0 REMOVE UNIT 1S FROM BUS 247247 /*05HRKG1S 18.0 REMOVE UNIT 2A FROM BUS 247248 /*05HRKG2A 18.0 REMOVE UNIT 2B FROM BUS 247249 /*05HRKG2B 18.0 REMOVE UNIT 2S FROM BUS 247250 /*05HRKG2S 18.0 END |
Breaker | AC | 108.49 % | 108.53 % | 4142.0 | B | 4495.15 | 41.91 | |
| AEP |
05DUMONT-05SORENS 765.0 kV Ckt 1 line
243206 to 246999 ckt 1 |
AEP_P4_#1760_05JEFRSO 765_A
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A' OPEN BRANCH FROM BUS 242924 TO BUS 243208 CKT 1 /*05HANG R 765.0 - 05JEFRSO 765.0 OPEN BRANCH FROM BUS 243207 TO BUS 243208 CKT 1 /*05GRNTWN 765.0 - 05JEFRSO 765.0 END |
Breaker | AC | 107.95 % | 107.99 % | 4142.0 | B | 4472.86 | 45.19 | |
| CE |
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
275233 to 270644 ckt 1 |
COMED_P4_023-65-BT3-4__
CONTINGENCY 'COMED_P4_023-65-BT3-4__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; R 345.0 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ;2C 33.0 END |
Breaker | AC | 100.31 % | 100.37 % | 1469.0 | STE | 1474.47 | 19.43 | |
| CE |
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
270927 to 275233 ckt 1 |
COMED_P4_023-65-BT3-4__
CONTINGENCY 'COMED_P4_023-65-BT3-4__' TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1 /*COLLINS ; 765.0 - PLANO ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; 765.0 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ; R 345.0 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1 /*COLLINS ;2M 345.0 - COLLINS ;2C 33.0 END |
Breaker | AC | 100.28 % | 100.34 % | 1469.0 | STE | 1473.96 | 19.43 | |
| CE/NIPS |
17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line
255104 to 270771 ckt 1 |
AEP_P4_#1750_05DUMONT 765_B1
CONTINGENCY 'AEP_P4_#1750_05DUMONT 765_B1' OPEN BRANCH FROM BUS 243206 TO BUS 243219 CKT 3 /*05DUMONT 765.0 - 05DUMONT 345.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 100.01 % | 100.2 % | 1091.0 | B | 1093.2 | 16.11 | |
| CE/NIPS |
17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line
255104 to 270771 ckt 1 |
AEP_P4_#2978_05DUMONT 765_B
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B' OPEN BRANCH FROM BUS 243206 TO' BUS 243207 CKT 1 /*05DUMONT 765.0 - 05GRNTWN 765.0 OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Breaker | AC | 99.96 % | 100.15 % | 1091.0 | B | 1092.6 | 16.05 | |
| AEP/CE |
WILTON ;-05DUMONT 765.0 kV Ckt 1 line
270644 to 243206 ckt 1 |
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S
CONTINGENCY 'COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S' TRIP BRANCH FROM BUS 274750 TO BUS 255112 CKT 1 /*CRETE EC ;BP 345.0 - 17STJOHN 345.0 TRIP BRANCH FROM BUS 274804 TO BUS 960680 CKT 1 /*UNIV PK N;RP 345.0 - AF2-359 TAP 345.0 END |
Tower | AC | 114.01 % | 114.11 % | 4105.0 | B | 4684.01 | 64.47 | |
| AEP/CE |
WILTON ;-05DUMONT 765.0 kV Ckt 1 line
270644 to 243206 ckt 1 |
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A
CONTINGENCY 'COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A' TRIP BRANCH FROM BUS 270728 TO BUS 274750 CKT 1 /*E FRANKFO; B 345.0 - CRETE EC ;BP 345.0 TRIP BRANCH FROM BUS 274804 TO BUS 960680 CKT 1 /*UNIV PK N;RP 345.0 - AF2-359 TAP 345.0 END |
Tower | AC | 112.64 % | 112.73 % | 4105.0 | B | 4627.61 | 64.55 | |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 19.53 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 25.97 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 25.57 MW | 21.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 10.11 MW | 8.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 8.2 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 95.03 MW | 95.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 15.96 MW | 13.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 29.36 MW | 24.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 4.18 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.39 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965091 | AG1-374 C | Adder | 19.52 MW | 16.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 19.89 MW | 16.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 17.05 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.84 MW | 4.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 4.55 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 19.0 MW | 16.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.47 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 2.1 MW | 1.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 16.63 MW | 16.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 3.09 MW | 2.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 20.75 MW | 17.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 3.42 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 22.92 MW | 19.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.86 MW | 3.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 5.54 MW | 4.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 3.26 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 9.91 MW | 8.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 2.21 MW | 1.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.62 MW | 3.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 1.02 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 14.94 MW | 12.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 9.93 MW | 8.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 4.47 MW | 3.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 13.4 MW | 11.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 13.16 MW | 11.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 24.1 MW | 20.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 4.28 MW | 3.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 8.36 MW | 7.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 16.73 MW | 14.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 7.05 MW | 5.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 7.15 MW | 6.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 6.27 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 25.46 MW | 21.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 9.78 MW | 8.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 1.3 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 8.18 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.98 MW | 6.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 5.32 MW | 4.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 15.09 MW | 15.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274723 | RIVER EC ;12 | 80/20 | 5.49 MW | 5.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274724 | RIVER EC ;11 | 80/20 | 5.46 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | 80/20 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | 80/20 | 7.57 MW | 7.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274792 | SE CHICAG;9U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274793 | SE CHICAG;0U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274794 | SE CHICAG;1U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274795 | SE CHICAG;2U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274798 | UNIV PARK;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274799 | UNIV PARK;2U | 80/20 | 1.52 MW | 1.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274826 | FISK ;BP | 80/20 | 2.86 MW | 2.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274827 | FISK ;RP | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276164 | X3-005 C | 80/20 | 0.11 MW | 0.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276592 | O-012 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.68 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 42.84 MW | 36.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 34.06 MW | 28.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 80.68 MW | 68.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 86.94 MW | 73.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 3.1 MW | 2.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 10.72 MW | 9.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 9.8 MW | 8.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.61 MW | 3.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 7.16 MW | 6.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 12.06 MW | 10.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 9.54 MW | 8.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 7.7 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 13.91 MW | 11.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 5.68 MW | 4.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 18.34 MW | 15.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 5.1 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 6.86 MW | 5.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.34 MW | 1.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.65 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 25.1 MW | 21.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.28 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 22.18 MW | 18.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | Adder | 39.58 MW | 33.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.82 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 6.52 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 361.52 MW | 307.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 953871 | J847 | External Queue | 13.43 MW | 13.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 954751 | J351 | External Queue | 441.39 MW | 441.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 955741 | J1058 | External Queue | 24.2 MW | 24.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990541 | J1332 | External Queue | 26.68 MW | 26.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990646 | J1355 | External Queue | 43.02 MW | 43.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990661 | J1358 | External Queue | 15.6 MW | 15.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990761 | J1386 | External Queue | 13.07 MW | 13.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 990976 | J1447 | External Queue | 28.98 MW | 28.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 991271 | J1724 | External Queue | 41.93 MW | 41.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 991331 | J1785 | External Queue | 13.63 MW | 13.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.77 MW | 1.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 101.19 MW | 101.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.78 MW | 26.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.57 MW | 0.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.99 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.62 MW | 15.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.62 MW | 0.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.38 MW | 4.38 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 19.53 MW | 16.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 25.97 MW | 22.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 25.57 MW | 21.74 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 10.11 MW | 8.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 6.73 MW | 5.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 8.2 MW | 6.97 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 95.03 MW | 95.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 15.96 MW | 13.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 29.36 MW | 24.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 4.18 MW | 3.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.39 MW | 1.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965091 | AG1-374 C | Adder | 19.52 MW | 16.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 19.89 MW | 16.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 17.05 MW | 14.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.84 MW | 4.12 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 4.55 MW | 3.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 19.0 MW | 16.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.47 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 2.1 MW | 1.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.6 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 16.63 MW | 16.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 3.09 MW | 2.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 20.75 MW | 17.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 2.22 MW | 1.89 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.36 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | Adder | 4.94 MW | 4.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 2.16 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 1.08 MW | 0.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 3.42 MW | 2.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 22.92 MW | 19.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 1.06 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.86 MW | 3.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 5.54 MW | 4.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 3.26 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 9.91 MW | 8.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.97 MW | 2.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 9.12 MW | 7.75 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 2.21 MW | 1.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.62 MW | 3.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 1.02 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 14.94 MW | 12.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 9.93 MW | 8.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 4.47 MW | 3.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 13.4 MW | 11.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 13.16 MW | 11.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 24.1 MW | 20.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 4.28 MW | 3.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 8.36 MW | 7.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 16.73 MW | 14.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 7.05 MW | 5.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 7.15 MW | 6.08 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 3.03 MW | 2.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 6.27 MW | 5.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 25.46 MW | 21.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 9.78 MW | 8.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 1.3 MW | 1.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | Adder | 2.17 MW | 1.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.94 MW | 5.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 8.18 MW | 6.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.98 MW | 6.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 5.32 MW | 4.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 15.09 MW | 15.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274723 | RIVER EC ;12 | 80/20 | 5.49 MW | 5.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274724 | RIVER EC ;11 | 80/20 | 5.46 MW | 5.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | 80/20 | 7.55 MW | 7.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | 80/20 | 7.57 MW | 7.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | 80/20 | 7.67 MW | 7.67 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274792 | SE CHICAG;9U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274793 | SE CHICAG;0U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274794 | SE CHICAG;1U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274795 | SE CHICAG;2U | 80/20 | 7.62 MW | 7.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274798 | UNIV PARK;1U | 80/20 | 1.53 MW | 1.53 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274799 | UNIV PARK;2U | 80/20 | 1.52 MW | 1.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274826 | FISK ;BP | 80/20 | 2.86 MW | 2.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274827 | FISK ;RP | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276164 | X3-005 C | 80/20 | 0.11 MW | 0.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276592 | O-012 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 4.38 MW | 3.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.68 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 42.84 MW | 36.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 34.06 MW | 28.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 80.68 MW | 68.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 86.94 MW | 73.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 3.1 MW | 2.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 10.72 MW | 9.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 9.8 MW | 8.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 9.57 MW | 8.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.61 MW | 3.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.61 MW | 1.37 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 7.16 MW | 6.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 12.06 MW | 10.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 6.19 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 9.54 MW | 8.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.88 MW | 2.45 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 7.7 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 13.91 MW | 11.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 5.68 MW | 4.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 18.34 MW | 15.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.68 MW | 3.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 5.1 MW | 4.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 6.86 MW | 5.83 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.34 MW | 1.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.81 MW | 2.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.92 MW | 2.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.65 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 25.1 MW | 21.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.28 MW | 0.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.4 MW | 0.34 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 22.18 MW | 18.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | Adder | 39.58 MW | 33.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.82 MW | 1.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 6.52 MW | 5.55 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 7.03 MW | 5.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 361.52 MW | 307.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 953871 | J847 | External Queue | 13.43 MW | 13.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 954751 | J351 | External Queue | 441.39 MW | 441.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 955741 | J1058 | External Queue | 24.2 MW | 24.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990541 | J1332 | External Queue | 26.68 MW | 26.68 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990646 | J1355 | External Queue | 43.02 MW | 43.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990661 | J1358 | External Queue | 15.6 MW | 15.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990761 | J1386 | External Queue | 13.07 MW | 13.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 990976 | J1447 | External Queue | 28.98 MW | 28.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 991271 | J1724 | External Queue | 41.93 MW | 41.93 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 991331 | J1785 | External Queue | 13.63 MW | 13.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.77 MW | 1.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 101.19 MW | 101.19 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.78 MW | 26.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.57 MW | 0.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.99 MW | 4.99 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.29 MW | 0.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.62 MW | 15.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.62 MW | 0.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.01 MW | 2.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.38 MW | 4.38 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962691 | AG1-118 C O1 | 80/20 | 12.7 MW | 12.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962701 | AG1-119 C | 80/20 | 46.06 MW | 46.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962711 | AG1-120 C O1 | 80/20 | 11.09 MW | 11.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962781 | AG1-127 C | 80/20 | 5.18 MW | 5.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 966821 | AG1-553 C O1 | 80/20 | 23.73 MW | 23.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965551 | AG1-423 C O1 | 80/20 | 30.71 MW | 30.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965661 | AG1-434 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965931 | AG1-462 C O1 | 80/20 | 15.36 MW | 15.36 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 272364 | ESS H440N ;R | 80/20 | 2.14 MW | 2.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 295108 | WESTBROOK C | 80/20 | 0.12 MW | 0.12 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 295110 | SUBLETTE C | 80/20 | 0.07 MW | 0.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 919221 | AA1-146 | 80/20 | 3.41 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 919581 | AA2-030 C | 80/20 | 20.0 MW | 20.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 926431 | AC1-114 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 927511 | AC1-113 1 | 80/20 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 927521 | AC1-113 2 | 80/20 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 933911 | AD1-013 C | 80/20 | 1.49 MW | 1.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 933931 | AD1-016 C | 80/20 | 0.52 MW | 0.52 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 934971 | AD1-129 C | 80/20 | 1.33 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 937001 | AD2-134 C | 80/20 | 2.08 MW | 2.08 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 937311 | AD2-172 C | 80/20 | 4.49 MW | 4.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 942991 | AE2-321 C | 80/20 | 4.29 MW | 4.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 943801 | AF1-048 C | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 958911 | AF2-182 C | 80/20 | 29.28 MW | 29.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 958921 | AF2-183 C | 80/20 | 5.21 MW | 5.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 959101 | AF2-201 C O1 | 80/20 | 10.99 MW | 10.99 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960581 | AF2-349 C | 80/20 | 89.45 MW | 89.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960721 | AF2-363 C O1 | 80/20 | 7.71 MW | 7.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960751 | AF2-366 C | 80/20 | 5.17 MW | 5.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961011 | AF2-392 C O1 | 80/20 | 4.58 MW | 4.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961021 | AF2-393 O1 | 80/20 | 7.8 MW | 7.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961031 | AF2-394 O1 | 80/20 | 5.2 MW | 5.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274656 | BYRON ;1U | 80/20 | 50.94 MW | 50.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274657 | BYRON ;2U | 80/20 | 49.83 MW | 49.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274662 | QUAD CITI;1U | 80/20 | 15.55 MW | 15.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274663 | QUAD CITI;2U | 80/20 | 15.59 MW | 15.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274699 | CORDOVA ;1C | 80/20 | 2.73 MW | 2.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274700 | CORDOVA ;2C | 80/20 | 2.73 MW | 2.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274701 | CORDOVA ;1S | 80/20 | 3.07 MW | 3.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274715 | NELSON EC;1C | 80/20 | 3.65 MW | 3.65 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274716 | NELSON EC;1S | 80/20 | 2.67 MW | 2.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274717 | NELSON EC;2C | 80/20 | 3.68 MW | 3.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274718 | NELSON EC;2S | 80/20 | 2.69 MW | 2.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274760 | LEE CO EC;1U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274761 | LEE CO EC;2U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274762 | LEE CO EC;3U | 80/20 | 2.58 MW | 2.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274763 | LEE CO EC;4U | 80/20 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274764 | LEE CO EC;5U | 80/20 | 2.59 MW | 2.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274765 | LEE CO EC;6U | 80/20 | 2.59 MW | 2.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274766 | LEE CO EC;7U | 80/20 | 2.55 MW | 2.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274767 | LEE CO EC;8U | 80/20 | 2.55 MW | 2.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274822 | ROCKFORD ;11 | 80/20 | 4.76 MW | 4.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274823 | ROCKFORD ;21 | 80/20 | 4.89 MW | 4.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274824 | ROCKFORD ;12 | 80/20 | 4.72 MW | 4.72 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274855 | GSG-6 ;RU | 80/20 | 0.36 MW | 0.36 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.71 MW | 0.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274857 | BIG SKY ;U1 | 80/20 | 0.46 MW | 0.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274858 | BIG SKY ;U2 | 80/20 | 0.46 MW | 0.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276156 | O-029 C | 80/20 | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276157 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276158 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276162 | X1-087 | 80/20 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276590 | R-018 | 80/20 | 0.28 MW | 0.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293513 | O-009 C1 | 80/20 | 0.38 MW | 0.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293514 | O-009 C2 | 80/20 | 0.19 MW | 0.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293515 | O-009 C3 | 80/20 | 0.21 MW | 0.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 930482 | AB1-089 CT | 80/20 | 78.43 MW | 78.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 930483 | AB1-089 ST | 80/20 | 62.35 MW | 62.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932881 | AC2-115 1 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932891 | AC2-115 2 | 80/20 | 0.85 MW | 0.85 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932921 | AC2-116 | 80/20 | 0.3 MW | 0.3 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 938861 | AE1-114 C O1 | 80/20 | 6.14 MW | 6.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 939051 | AE1-134 1 | 80/20 | 1.55 MW | 1.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 939061 | AE1-134 2 | 80/20 | 1.55 MW | 1.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 940501 | AE2-035 C | 80/20 | 4.49 MW | 4.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 941131 | AE2-107 C | 80/20 | 4.58 MW | 4.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946151 | AF1-280 C O1 | 80/20 | 22.29 MW | 22.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946161 | AF1-281 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946321 | AF1-296 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946501 | AF1-314 C | 80/20 | 7.96 MW | 7.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946671 | AF1-331 | 80/20 | 1.94 MW | 1.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274872 | LEE DEKAL;1U | 80/20 | 0.58 MW | 0.58 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274850 | MENDOTA H;RU | 80/20 | 0.22 MW | 0.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 952431 | J760 | External Queue | 5.12 MW | 5.12 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953681 | J818 | External Queue | 13.14 MW | 13.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953901 | J850 | External Queue | 21.75 MW | 21.75 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953921 | J855 C | External Queue | 1.28 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954001 | J864 | External Queue | 4.23 MW | 4.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954061 | J870 | External Queue | 16.88 MW | 16.88 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954071 | J871 | External Queue | 8.44 MW | 8.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 955971 | J1084 | External Queue | 11.07 MW | 11.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990116 | J1214 | External Queue | 38.66 MW | 38.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990406 | J1304 | External Queue | 9.21 MW | 9.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990511 | J1326 | External Queue | 9.67 MW | 9.67 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990726 | J1377 | External Queue | 16.92 MW | 16.92 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 991201 | J1629 | External Queue | 13.05 MW | 13.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.34 MW | 0.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.43 MW | 47.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.53 MW | 9.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.5 MW | 2.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.71 MW | 9.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.01 MW | 1.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.49 MW | 0.49 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 13.52 MW | 11.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 4.66 MW | 3.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | Adder | 44.21 MW | 37.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 10.83 MW | 9.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 20.27 MW | 17.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 3.15 MW | 2.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 13.12 MW | 11.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | Adder | 6.98 MW | 5.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 14.38 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 0.95 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.36 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.48 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 2.97 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 4.78 MW | 4.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 3.25 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 5.53 MW | 4.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 3.69 MW | 3.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | Adder | 7.13 MW | 6.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 9.59 MW | 9.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274788 | SE CHICAG;5U | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274789 | SE CHICAG;6U | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274790 | SE CHICAG;7U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274791 | SE CHICAG;8U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274792 | SE CHICAG;9U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274793 | SE CHICAG;0U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274794 | SE CHICAG;1U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274795 | SE CHICAG;2U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.16 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 6.37 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 3.79 MW | 3.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 12.72 MW | 10.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.28 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | Adder | 0.65 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.28 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.26 MW | 1.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 13.52 MW | 11.5 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 4.66 MW | 3.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | Adder | 44.21 MW | 37.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 10.83 MW | 9.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 20.27 MW | 17.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 3.15 MW | 2.68 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 13.12 MW | 11.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | Adder | 6.98 MW | 5.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 14.38 MW | 12.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 0.95 MW | 0.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 3.48 MW | 3.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.36 MW | 2.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.48 MW | 1.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 16.72 MW | 14.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 2.97 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 4.78 MW | 4.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 3.25 MW | 2.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 5.53 MW | 4.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 3.69 MW | 3.13 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | Adder | 7.13 MW | 6.06 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 9.59 MW | 9.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274788 | SE CHICAG;5U | Adder | 3.03 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274789 | SE CHICAG;6U | Adder | 3.04 MW | 2.58 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274790 | SE CHICAG;7U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274791 | SE CHICAG;8U | Adder | 3.08 MW | 2.62 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274792 | SE CHICAG;9U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274793 | SE CHICAG;0U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274794 | SE CHICAG;1U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274795 | SE CHICAG;2U | Adder | 3.07 MW | 2.61 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.16 MW | 0.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.12 MW | 0.95 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 6.37 MW | 5.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 3.79 MW | 3.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 12.72 MW | 10.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.28 MW | 0.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 3.23 MW | 2.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 4.75 MW | 4.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | Adder | 0.65 MW | 0.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.28 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.26 MW | 1.07 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962691 | AG1-118 C O1 | 80/20 | 12.7 MW | 12.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962701 | AG1-119 C | 80/20 | 46.06 MW | 46.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962711 | AG1-120 C O1 | 80/20 | 11.09 MW | 11.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 962781 | AG1-127 C | 80/20 | 5.18 MW | 5.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 966821 | AG1-553 C O1 | 80/20 | 23.73 MW | 23.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965551 | AG1-423 C O1 | 80/20 | 30.71 MW | 30.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965661 | AG1-434 C O1 | 80/20 | 2.71 MW | 2.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 965931 | AG1-462 C O1 | 80/20 | 15.36 MW | 15.36 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 272364 | ESS H440N ;R | 80/20 | 2.14 MW | 2.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 295108 | WESTBROOK C | 80/20 | 0.12 MW | 0.12 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 295110 | SUBLETTE C | 80/20 | 0.07 MW | 0.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 919221 | AA1-146 | 80/20 | 3.41 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 919581 | AA2-030 C | 80/20 | 20.0 MW | 20.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 926431 | AC1-114 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 927511 | AC1-113 1 | 80/20 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 927521 | AC1-113 2 | 80/20 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 933911 | AD1-013 C | 80/20 | 1.49 MW | 1.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 933931 | AD1-016 C | 80/20 | 0.52 MW | 0.52 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 934971 | AD1-129 C | 80/20 | 1.33 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 937001 | AD2-134 C | 80/20 | 2.08 MW | 2.08 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 937311 | AD2-172 C | 80/20 | 4.49 MW | 4.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 942991 | AE2-321 C | 80/20 | 4.29 MW | 4.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 943801 | AF1-048 C | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 958911 | AF2-182 C | 80/20 | 29.28 MW | 29.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 958921 | AF2-183 C | 80/20 | 5.21 MW | 5.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 959101 | AF2-201 C O1 | 80/20 | 10.99 MW | 10.99 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960721 | AF2-363 C O1 | 80/20 | 7.71 MW | 7.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 960751 | AF2-366 C | 80/20 | 5.17 MW | 5.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961011 | AF2-392 C O1 | 80/20 | 4.58 MW | 4.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961021 | AF2-393 O1 | 80/20 | 7.8 MW | 7.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 961031 | AF2-394 O1 | 80/20 | 5.2 MW | 5.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274656 | BYRON ;1U | 80/20 | 50.94 MW | 50.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274657 | BYRON ;2U | 80/20 | 49.83 MW | 49.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274662 | QUAD CITI;1U | 80/20 | 15.55 MW | 15.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274663 | QUAD CITI;2U | 80/20 | 15.59 MW | 15.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274699 | CORDOVA ;1C | 80/20 | 2.73 MW | 2.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274700 | CORDOVA ;2C | 80/20 | 2.73 MW | 2.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274701 | CORDOVA ;1S | 80/20 | 3.07 MW | 3.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274715 | NELSON EC;1C | 80/20 | 3.65 MW | 3.65 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274716 | NELSON EC;1S | 80/20 | 2.67 MW | 2.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274717 | NELSON EC;2C | 80/20 | 3.68 MW | 3.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274718 | NELSON EC;2S | 80/20 | 2.69 MW | 2.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274760 | LEE CO EC;1U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274761 | LEE CO EC;2U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274762 | LEE CO EC;3U | 80/20 | 2.58 MW | 2.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274763 | LEE CO EC;4U | 80/20 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274764 | LEE CO EC;5U | 80/20 | 2.59 MW | 2.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274765 | LEE CO EC;6U | 80/20 | 2.59 MW | 2.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274766 | LEE CO EC;7U | 80/20 | 2.55 MW | 2.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274767 | LEE CO EC;8U | 80/20 | 2.55 MW | 2.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274822 | ROCKFORD ;11 | 80/20 | 4.76 MW | 4.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274823 | ROCKFORD ;21 | 80/20 | 4.89 MW | 4.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274824 | ROCKFORD ;12 | 80/20 | 4.72 MW | 4.72 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274855 | GSG-6 ;RU | 80/20 | 0.36 MW | 0.36 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274856 | ECOGROVE ;U1 | 80/20 | 0.71 MW | 0.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274857 | BIG SKY ;U1 | 80/20 | 0.46 MW | 0.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274858 | BIG SKY ;U2 | 80/20 | 0.46 MW | 0.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276156 | O-029 C | 80/20 | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276157 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276158 | O-029 C | 80/20 | 0.4 MW | 0.4 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276162 | X1-087 | 80/20 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 276590 | R-018 | 80/20 | 0.28 MW | 0.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293513 | O-009 C1 | 80/20 | 0.38 MW | 0.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293514 | O-009 C2 | 80/20 | 0.19 MW | 0.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 293515 | O-009 C3 | 80/20 | 0.21 MW | 0.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 930482 | AB1-089 CT | 80/20 | 78.43 MW | 78.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 930483 | AB1-089 ST | 80/20 | 62.35 MW | 62.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932881 | AC2-115 1 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932891 | AC2-115 2 | 80/20 | 0.85 MW | 0.85 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 932921 | AC2-116 | 80/20 | 0.3 MW | 0.3 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 938861 | AE1-114 C O1 | 80/20 | 6.14 MW | 6.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 939051 | AE1-134 1 | 80/20 | 1.55 MW | 1.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 939061 | AE1-134 2 | 80/20 | 1.55 MW | 1.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 940501 | AE2-035 C | 80/20 | 4.49 MW | 4.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 941131 | AE2-107 C | 80/20 | 4.58 MW | 4.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946151 | AF1-280 C O1 | 80/20 | 22.29 MW | 22.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946161 | AF1-281 C O1 | 80/20 | 0.49 MW | 0.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946321 | AF1-296 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946501 | AF1-314 C | 80/20 | 7.96 MW | 7.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 946671 | AF1-331 | 80/20 | 1.94 MW | 1.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274872 | LEE DEKAL;1U | 80/20 | 0.58 MW | 0.58 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 274850 | MENDOTA H;RU | 80/20 | 0.22 MW | 0.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 952431 | J760 | External Queue | 5.12 MW | 5.12 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953681 | J818 | External Queue | 13.14 MW | 13.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953901 | J850 | External Queue | 21.75 MW | 21.75 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 953921 | J855 C | External Queue | 1.28 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954001 | J864 | External Queue | 4.23 MW | 4.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954061 | J870 | External Queue | 16.88 MW | 16.88 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 954071 | J871 | External Queue | 8.44 MW | 8.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 955971 | J1084 | External Queue | 11.07 MW | 11.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990116 | J1214 | External Queue | 38.66 MW | 38.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990406 | J1304 | External Queue | 9.21 MW | 9.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990511 | J1326 | External Queue | 9.67 MW | 9.67 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 990726 | J1377 | External Queue | 16.92 MW | 16.92 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | 991201 | J1629 | External Queue | 13.05 MW | 13.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.34 MW | 0.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.43 MW | 47.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.53 MW | 9.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.5 MW | 2.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.71 MW | 9.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.01 MW | 1.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L18905__B-R-B-2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.49 MW | 0.49 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965681 | AG1-436 C | 80/20 | 64.08 MW | 64.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965791 | AG1-447 | 80/20 | 46.99 MW | 46.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | Adder | 3.48 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960681 | AF2-359 C | 80/20 | 64.08 MW | 64.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 17.81 MW | 15.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.98 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 5.71 MW | 4.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965681 | AG1-436 C | 80/20 | 64.08 MW | 64.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965791 | AG1-447 | 80/20 | 46.99 MW | 46.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 3.65 MW | 3.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 3.48 MW | 3.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | Adder | 3.48 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.74 MW | 0.62 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | 80/20 | 10.09 MW | 10.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 9.69 MW | 8.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 4.37 MW | 3.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 17.74 MW | 15.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960681 | AF2-359 C | 80/20 | 64.08 MW | 64.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 22.57 MW | 22.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 22.07 MW | 22.07 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 21.01 MW | 21.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 21.1 MW | 21.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 9.6 MW | 9.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274802 | UNIV PARK;5U | 80/20 | 1.29 MW | 1.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274803 | UNIV PARK;6U | 80/20 | 1.29 MW | 1.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 0.37 MW | 0.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 29.81 MW | 25.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 23.7 MW | 20.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 56.16 MW | 47.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 60.43 MW | 51.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 9.65 MW | 8.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 17.44 MW | 14.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 28.05 MW | 28.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274805 | UNIV PK N;1U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274806 | UNIV PK N;2U | 80/20 | 1.43 MW | 1.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274807 | UNIV PK N;3U | 80/20 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274808 | UNIV PK N;4U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274809 | UNIV PK N;5U | 80/20 | 1.43 MW | 1.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274810 | UNIV PK N;6U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274811 | UNIV PK N;7U | 80/20 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274812 | UNIV PK N;8U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274813 | UNIV PK N;9U | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274814 | UNIV PK N;0U | 80/20 | 1.43 MW | 1.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274815 | UNIV PK N;XU | 80/20 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274816 | UNIV PK N;YU | 80/20 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 252.02 MW | 214.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.21 MW | 54.21 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961651 | AG1-005 C O1 | Adder | 17.02 MW | 14.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962691 | AG1-118 C O1 | Adder | 22.84 MW | 19.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962701 | AG1-119 C | Adder | 22.56 MW | 19.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962711 | AG1-120 C O1 | Adder | 8.9 MW | 7.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C O1 | Adder | 5.89 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962781 | AG1-127 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964581 | AG1-321 C O1 | Adder | 13.52 MW | 11.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | Adder | 25.65 MW | 21.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 | Adder | 3.69 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965141 | AG1-379 C | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965551 | AG1-423 C O1 | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C O1 | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965931 | AG1-462 C O1 | Adder | 16.6 MW | 14.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 272364 | ESS H440N ;R | Adder | 2.71 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919581 | AA2-030 C | Adder | 18.22 MW | 15.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | Adder | 1.2 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927091 | AC1-204 GEN1 | 80/20 | 13.07 MW | 13.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927093 | AC1-204 GEN2 | 80/20 | 13.1 MW | 13.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927451 | AC1-142A 1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927461 | AC1-142A 2 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936461 | AD2-060 | Adder | 2.41 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937311 | AD2-172 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937401 | AD2-194 1 | Adder | 8.25 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937411 | AD2-194 2 | 80/20 | 8.27 MW | 8.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | Adder | 1.84 MW | 1.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942991 | AE2-321 C | Adder | 8.45 MW | 7.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943121 | AE2-341 C | Adder | 13.09 MW | 11.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943591 | AF1-030 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958481 | AF2-142 C | Adder | 11.16 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958491 | AF2-143 C | Adder | 11.17 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958911 | AF2-182 C | Adder | 21.18 MW | 18.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | Adder | 3.76 MW | 3.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959081 | AF2-199 C | Adder | 7.38 MW | 6.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959091 | AF2-200 C O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | Adder | 6.2 MW | 5.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959341 | AF2-225 C | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | Adder | 5.49 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960581 | AF2-349 C | Adder | 22.47 MW | 19.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960751 | AF2-366 C | Adder | 7.19 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | Adder | 4.11 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | Adder | 7.0 MW | 5.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | Adder | 4.67 MW | 3.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274654 | BRAIDWOOD;1U | 80/20 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274655 | BRAIDWOOD;2U | 80/20 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274660 | LASCO STA;1U | 80/20 | 26.96 MW | 26.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274661 | LASCO STA;2U | 80/20 | 27.07 MW | 27.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274675 | JOLIET 29;7U | 80/20 | 12.28 MW | 12.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274676 | JOLIET 29;8U | 80/20 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274687 | WILL CNTY;4U | 80/20 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274704 | KENDALL ;1C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274705 | KENDALL ;1S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274706 | KENDALL ;2C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274707 | KENDALL ;2S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274728 | ELWOOD EC;5P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274730 | ELWOOD EC;6P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274732 | ELWOOD EC;7P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274733 | ELWOOD EC;3P | 80/20 | 3.51 MW | 3.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274734 | ELWOOD EC;8P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274736 | ELWOOD EC;9P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274751 | CRETE EC ;1U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274752 | CRETE EC ;2U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274753 | CRETE EC ;3U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274754 | CRETE EC ;4U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930482 | AB1-089 CT | Adder | 37.77 MW | 32.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930483 | AB1-089 ST | Adder | 30.03 MW | 25.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930761 | AB1-122 CT1 | Adder | 70.93 MW | 60.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 930771 | AB1-122 CT2 | Adder | 78.7 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938511 | AE1-070 1 | 80/20 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939051 | AE1-134 1 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939061 | AE1-134 2 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939351 | AE1-166 C O1 | Adder | 10.51 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | Adder | 5.21 MW | 4.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939741 | AE1-205 C O1 | Adder | 7.93 MW | 6.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 940501 | AE2-035 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | Adder | 4.72 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946151 | AF1-280 C O1 | Adder | 16.12 MW | 13.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | Adder | 5.98 MW | 5.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957471 | AF2-041 C | Adder | 22.13 MW | 18.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | Adder | 16.36 MW | 13.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 40.19 MW | 40.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | Adder | 1.59 MW | 1.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | Adder | 317.97 MW | 270.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.01 MW | 62.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.89 MW | 18.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.41 MW | 13.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.87 MW | 3.87 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961651 | AG1-005 C O1 | Adder | 17.02 MW | 14.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962691 | AG1-118 C O1 | Adder | 22.84 MW | 19.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962701 | AG1-119 C | Adder | 22.56 MW | 19.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962711 | AG1-120 C O1 | Adder | 8.9 MW | 7.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C O1 | Adder | 5.89 MW | 5.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962781 | AG1-127 C | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964581 | AG1-321 C O1 | Adder | 13.52 MW | 11.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | Adder | 25.65 MW | 21.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 | Adder | 3.69 MW | 3.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 | Adder | 1.23 MW | 1.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965141 | AG1-379 C | Adder | 17.85 MW | 15.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965551 | AG1-423 C O1 | Adder | 15.05 MW | 12.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C O1 | Adder | 3.98 MW | 3.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965931 | AG1-462 C O1 | Adder | 16.6 MW | 14.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | Adder | 1.65 MW | 1.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 272364 | ESS H440N ;R | Adder | 2.71 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919581 | AA2-030 C | Adder | 18.22 MW | 15.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | Adder | 1.2 MW | 1.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927091 | AC1-204 GEN1 | 80/20 | 13.07 MW | 13.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927093 | AC1-204 GEN2 | 80/20 | 13.1 MW | 13.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927451 | AC1-142A 1 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927461 | AC1-142A 2 | 80/20 | 4.46 MW | 4.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934051 | AD1-031 C O1 | Adder | 2.98 MW | 2.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | Adder | 19.64 MW | 16.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936461 | AD2-060 | Adder | 2.41 MW | 2.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | Adder | 2.61 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937311 | AD2-172 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937401 | AD2-194 1 | Adder | 8.25 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937411 | AD2-194 2 | 80/20 | 8.27 MW | 8.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | Adder | 1.84 MW | 1.56 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942991 | AE2-321 C | Adder | 8.45 MW | 7.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943121 | AE2-341 C | Adder | 13.09 MW | 11.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943591 | AF1-030 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958481 | AF2-142 C | Adder | 11.16 MW | 9.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958491 | AF2-143 C | Adder | 11.17 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958911 | AF2-182 C | Adder | 21.18 MW | 18.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | Adder | 3.76 MW | 3.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959081 | AF2-199 C | Adder | 7.38 MW | 6.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959091 | AF2-200 C O1 | Adder | 14.75 MW | 12.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | Adder | 6.2 MW | 5.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959341 | AF2-225 C | Adder | 5.95 MW | 5.06 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | Adder | 5.49 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960581 | AF2-349 C | Adder | 22.47 MW | 19.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960591 | AF2-350 C O1 | Adder | 7.22 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | Adder | 0.96 MW | 0.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960751 | AF2-366 C | Adder | 7.19 MW | 6.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | Adder | 4.11 MW | 3.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | Adder | 7.0 MW | 5.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | Adder | 4.67 MW | 3.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274654 | BRAIDWOOD;1U | 80/20 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274655 | BRAIDWOOD;2U | 80/20 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274660 | LASCO STA;1U | 80/20 | 26.96 MW | 26.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274661 | LASCO STA;2U | 80/20 | 27.07 MW | 27.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274675 | JOLIET 29;7U | 80/20 | 12.28 MW | 12.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274676 | JOLIET 29;8U | 80/20 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274687 | WILL CNTY;4U | 80/20 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274704 | KENDALL ;1C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274705 | KENDALL ;1S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274706 | KENDALL ;2C | 80/20 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274707 | KENDALL ;2S | 80/20 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274728 | ELWOOD EC;5P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274730 | ELWOOD EC;6P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274732 | ELWOOD EC;7P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274733 | ELWOOD EC;3P | 80/20 | 3.51 MW | 3.51 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274734 | ELWOOD EC;8P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274736 | ELWOOD EC;9P | 80/20 | 3.52 MW | 3.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274751 | CRETE EC ;1U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274752 | CRETE EC ;2U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274753 | CRETE EC ;3U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274754 | CRETE EC ;4U | 80/20 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | Adder | 1.47 MW | 1.25 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930482 | AB1-089 CT | Adder | 37.77 MW | 32.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930483 | AB1-089 ST | Adder | 30.03 MW | 25.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930761 | AB1-122 CT1 | Adder | 70.93 MW | 60.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 930771 | AB1-122 CT2 | Adder | 78.7 MW | 66.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 933411 | AC2-154 C | Adder | 2.29 MW | 1.94 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938511 | AE1-070 1 | 80/20 | 9.71 MW | 9.71 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938521 | AE1-070 2 | Adder | 8.87 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | Adder | 4.06 MW | 3.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939051 | AE1-134 1 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939061 | AE1-134 2 | Adder | 1.42 MW | 1.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939351 | AE1-166 C O1 | Adder | 10.51 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | Adder | 5.21 MW | 4.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939741 | AE1-205 C O1 | Adder | 7.93 MW | 6.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 940501 | AE2-035 C | Adder | 2.54 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941131 | AE2-107 C | Adder | 6.76 MW | 5.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941551 | AE2-152 C O1 | Adder | 12.13 MW | 10.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | Adder | 4.72 MW | 4.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946151 | AF1-280 C O1 | Adder | 16.12 MW | 13.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | Adder | 4.09 MW | 3.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | Adder | 5.98 MW | 5.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 1.52 MW | 1.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957471 | AF2-041 C | Adder | 22.13 MW | 18.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | Adder | 0.25 MW | 0.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | Adder | 0.35 MW | 0.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | Adder | 16.36 MW | 13.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 40.19 MW | 40.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | Adder | 1.59 MW | 1.35 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934111 | AD2-000 2 | Adder | 6.36 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | Adder | 317.97 MW | 270.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.33 MW | 2.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.01 MW | 62.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.89 MW | 18.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.41 MW | 13.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.87 MW | 3.87 MW |
| Details for AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 962701 | AG1-119 C | 80/20 | 101.34 MW | 101.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 962711 | AG1-120 C O1 | 80/20 | 9.4 MW | 9.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 962781 | AG1-127 C | Adder | 4.3 MW | 3.66 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 966821 | AG1-553 C O1 | 80/20 | 26.62 MW | 26.62 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 965551 | AG1-423 C O1 | 80/20 | 67.97 MW | 67.97 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 965661 | AG1-434 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 965931 | AG1-462 C O1 | 80/20 | 17.23 MW | 17.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 272364 | ESS H440N ;R | 80/20 | 1.99 MW | 1.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 295108 | WESTBROOK C | 80/20 | 0.11 MW | 0.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 295110 | SUBLETTE C | 80/20 | 0.08 MW | 0.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 919221 | AA1-146 | 80/20 | 3.85 MW | 3.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 919581 | AA2-030 C | 80/20 | 22.58 MW | 22.58 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 926431 | AC1-114 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 927511 | AC1-113 1 | 80/20 | 0.38 MW | 0.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 927521 | AC1-113 2 | 80/20 | 0.38 MW | 0.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 933911 | AD1-013 C | 80/20 | 1.39 MW | 1.39 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 933931 | AD1-016 C | 80/20 | 0.66 MW | 0.66 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 934971 | AD1-129 C | 80/20 | 1.24 MW | 1.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 937001 | AD2-134 C | 80/20 | 1.94 MW | 1.94 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 937311 | AD2-172 C | 80/20 | 4.25 MW | 4.25 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 942991 | AE2-321 C | 80/20 | 5.53 MW | 5.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 958911 | AF2-182 C | 80/20 | 33.76 MW | 33.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 958921 | AF2-183 C | 80/20 | 6.0 MW | 6.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 959101 | AF2-201 C O1 | 80/20 | 10.4 MW | 10.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 960581 | AF2-349 C | 80/20 | 46.8 MW | 46.8 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 960721 | AF2-363 C O1 | 80/20 | 6.54 MW | 6.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 960751 | AF2-366 C | Adder | 4.29 MW | 3.65 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 961011 | AF2-392 C O1 | 80/20 | 4.91 MW | 4.91 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 961021 | AF2-393 O1 | 80/20 | 8.38 MW | 8.38 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 961031 | AF2-394 O1 | 80/20 | 5.58 MW | 5.58 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274656 | BYRON ;1U | 80/20 | 60.35 MW | 60.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274657 | BYRON ;2U | 80/20 | 58.8 MW | 58.8 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274662 | QUAD CITI;1U | 80/20 | 17.44 MW | 17.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274663 | QUAD CITI;2U | 80/20 | 17.49 MW | 17.49 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274699 | CORDOVA ;1C | 80/20 | 3.06 MW | 3.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274700 | CORDOVA ;2C | 80/20 | 3.06 MW | 3.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274701 | CORDOVA ;1S | 80/20 | 3.44 MW | 3.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274715 | NELSON EC;1C | 80/20 | 4.12 MW | 4.12 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274716 | NELSON EC;1S | 80/20 | 3.01 MW | 3.01 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274717 | NELSON EC;2C | 80/20 | 4.16 MW | 4.16 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274718 | NELSON EC;2S | 80/20 | 3.04 MW | 3.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274760 | LEE CO EC;1U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274761 | LEE CO EC;2U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274762 | LEE CO EC;3U | 80/20 | 2.99 MW | 2.99 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274763 | LEE CO EC;4U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274764 | LEE CO EC;5U | 80/20 | 3.0 MW | 3.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274765 | LEE CO EC;6U | 80/20 | 3.0 MW | 3.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274766 | LEE CO EC;7U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274767 | LEE CO EC;8U | 80/20 | 2.96 MW | 2.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274822 | ROCKFORD ;11 | 80/20 | 4.24 MW | 4.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274823 | ROCKFORD ;21 | 80/20 | 4.36 MW | 4.36 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274824 | ROCKFORD ;12 | 80/20 | 4.21 MW | 4.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274855 | GSG-6 ;RU | 80/20 | 0.34 MW | 0.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274856 | ECOGROVE ;U1 | 80/20 | 0.67 MW | 0.67 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274857 | BIG SKY ;U1 | 80/20 | 0.54 MW | 0.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274858 | BIG SKY ;U2 | 80/20 | 0.54 MW | 0.54 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276156 | O-029 C | 80/20 | 0.22 MW | 0.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276157 | O-029 C | 80/20 | 0.24 MW | 0.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276158 | O-029 C | 80/20 | 0.44 MW | 0.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276162 | X1-087 | 80/20 | 0.32 MW | 0.32 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 276590 | R-018 | 80/20 | 0.24 MW | 0.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 293513 | O-009 C1 | 80/20 | 0.41 MW | 0.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 293514 | O-009 C2 | 80/20 | 0.21 MW | 0.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 293515 | O-009 C3 | 80/20 | 0.23 MW | 0.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 930482 | AB1-089 CT | 80/20 | 123.96 MW | 123.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 930483 | AB1-089 ST | 80/20 | 98.56 MW | 98.56 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 932881 | AC2-115 1 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 932891 | AC2-115 2 | 80/20 | 0.76 MW | 0.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 932921 | AC2-116 | 80/20 | 0.27 MW | 0.27 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 938861 | AE1-114 C O1 | 80/20 | 6.0 MW | 6.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 939051 | AE1-134 1 | 80/20 | 1.75 MW | 1.75 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 939061 | AE1-134 2 | 80/20 | 1.75 MW | 1.75 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 940501 | AE2-035 C | 80/20 | 4.25 MW | 4.25 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 941131 | AE2-107 C | Adder | 4.0 MW | 3.4 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946151 | AF1-280 C O1 | 80/20 | 25.7 MW | 25.7 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946161 | AF1-281 C O1 | 80/20 | 0.56 MW | 0.56 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946321 | AF1-296 C O1 | 80/20 | 4.32 MW | 4.32 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946501 | AF1-314 C | 80/20 | 7.53 MW | 7.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946661 | AF1-330 C | Adder | 1.31 MW | 1.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 946671 | AF1-331 | 80/20 | 1.8 MW | 1.8 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 274850 | MENDOTA H;RU | 80/20 | 0.21 MW | 0.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 952431 | J760 | External Queue | 5.1 MW | 5.1 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 953681 | J818 | External Queue | 14.04 MW | 14.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 953901 | J850 | External Queue | 23.48 MW | 23.48 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 953921 | J855 C | External Queue | 1.36 MW | 1.36 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 954001 | J864 | External Queue | 4.48 MW | 4.48 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 954061 | J870 | External Queue | 17.88 MW | 17.88 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 954071 | J871 | External Queue | 8.94 MW | 8.94 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 955971 | J1084 | External Queue | 12.21 MW | 12.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 990116 | J1214 | External Queue | 39.41 MW | 39.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 990406 | J1304 | External Queue | 9.34 MW | 9.34 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 990511 | J1326 | External Queue | 9.85 MW | 9.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 990726 | J1377 | External Queue | 16.85 MW | 16.85 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | 991201 | J1629 | External Queue | 14.55 MW | 14.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.09 MW | 0.09 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.67 MW | 0.67 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.11 MW | 0.11 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 55.88 MW | 55.88 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.46 MW | 10.46 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.12 MW | 0.12 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.76 MW | 2.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.89 MW | 10.89 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.3 MW | 0.3 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.23 MW | 0.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.09 MW | 1.09 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L97104__-R | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.11 MW | 1.11 MW |
| Details for AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 962701 | AG1-119 C | 80/20 | 96.55 MW | 96.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 962711 | AG1-120 C O1 | 80/20 | 6.65 MW | 6.65 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 21.43 MW | 21.43 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 965551 | AG1-423 C O1 | 80/20 | 64.82 MW | 64.82 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C O1 | Adder | 2.36 MW | 2.01 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 13.87 MW | 13.87 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 272364 | ESS H440N ;R | Adder | 1.48 MW | 1.25 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.06 MW | 0.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 3.1 MW | 3.1 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 18.22 MW | 18.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 926431 | AC1-114 | 80/20 | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 927511 | AC1-113 1 | 80/20 | 0.28 MW | 0.28 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 927521 | AC1-113 2 | 80/20 | 0.28 MW | 0.28 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 933911 | AD1-013 C | Adder | 1.03 MW | 0.87 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 933931 | AD1-016 C | 80/20 | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 934971 | AD1-129 C | 80/20 | 0.92 MW | 0.92 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | Adder | 1.44 MW | 1.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | 80/20 | 3.18 MW | 3.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 942991 | AE2-321 C | 80/20 | 4.67 MW | 4.67 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | Adder | 2.18 MW | 1.86 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 27.45 MW | 27.45 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 4.88 MW | 4.88 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 7.79 MW | 7.79 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 960581 | AF2-349 C | 80/20 | 21.53 MW | 21.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 960721 | AF2-363 C O1 | 80/20 | 4.63 MW | 4.63 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 6.63 MW | 6.63 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 4.42 MW | 4.42 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274656 | BYRON ;1U | 80/20 | 49.55 MW | 49.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274657 | BYRON ;2U | 80/20 | 48.21 MW | 48.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 14.04 MW | 14.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 14.08 MW | 14.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 2.47 MW | 2.47 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 2.47 MW | 2.47 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.77 MW | 2.77 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 3.33 MW | 3.33 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 2.43 MW | 2.43 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 3.35 MW | 3.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 2.45 MW | 2.45 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 2.44 MW | 2.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 2.44 MW | 2.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 2.44 MW | 2.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274763 | LEE CO EC;4U | 80/20 | 2.42 MW | 2.42 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 2.45 MW | 2.45 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 2.45 MW | 2.45 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274766 | LEE CO EC;7U | 80/20 | 2.41 MW | 2.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274767 | LEE CO EC;8U | 80/20 | 2.41 MW | 2.41 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274822 | ROCKFORD ;11 | 80/20 | 3.08 MW | 3.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274823 | ROCKFORD ;21 | 80/20 | 3.17 MW | 3.17 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274824 | ROCKFORD ;12 | 80/20 | 3.06 MW | 3.06 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.5 MW | 0.5 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.44 MW | 0.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.44 MW | 0.44 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.18 MW | 0.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.35 MW | 0.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276162 | X1-087 | 80/20 | 0.23 MW | 0.23 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 276590 | R-018 | 80/20 | 0.18 MW | 0.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.33 MW | 0.33 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.17 MW | 0.17 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.18 MW | 0.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 930482 | AB1-089 CT | 80/20 | 110.64 MW | 110.64 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 930483 | AB1-089 ST | 80/20 | 87.96 MW | 87.96 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 932881 | AC2-115 1 | 80/20 | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 932891 | AC2-115 2 | 80/20 | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 932921 | AC2-116 | 80/20 | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 1.42 MW | 1.42 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 1.42 MW | 1.42 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | 80/20 | 3.18 MW | 3.18 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 20.89 MW | 20.89 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.46 MW | 0.46 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 5.63 MW | 5.63 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946661 | AF1-330 C | Adder | 1.12 MW | 0.95 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 946671 | AF1-331 | Adder | 1.34 MW | 1.14 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 952431 | J760 | External Queue | 3.92 MW | 3.92 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 953681 | J818 | External Queue | 11.09 MW | 11.09 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 953901 | J850 | External Queue | 18.62 MW | 18.62 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 953921 | J855 C | External Queue | 1.07 MW | 1.07 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 954001 | J864 | External Queue | 3.52 MW | 3.52 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 954061 | J870 | External Queue | 14.08 MW | 14.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 954071 | J871 | External Queue | 7.04 MW | 7.04 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 955971 | J1084 | External Queue | 9.77 MW | 9.77 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 990116 | J1214 | External Queue | 30.53 MW | 30.53 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 990406 | J1304 | External Queue | 7.22 MW | 7.22 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 990511 | J1326 | External Queue | 7.63 MW | 7.63 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 990726 | J1377 | External Queue | 12.92 MW | 12.92 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | 991201 | J1629 | External Queue | 11.69 MW | 11.69 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.55 MW | 0.55 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.17 MW | 0.17 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.0 MW | 0.0 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.79 MW | 45.79 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.35 MW | 8.35 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.1 MW | 0.1 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.03 MW | 0.03 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.21 MW | 2.21 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.76 MW | 8.76 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.19 MW | 0.19 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.87 MW | 0.87 MW |
| AG1-423 TP-WAYNE ; B 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.06 MW | 1.06 MW |
| Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 961651 | AG1-005 C O1 | Adder | 30.84 MW | 26.22 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 962691 | AG1-118 C O1 | Adder | 39.84 MW | 33.86 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 962701 | AG1-119 C | Adder | 39.2 MW | 33.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 962711 | AG1-120 C O1 | Adder | 15.53 MW | 13.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 962721 | AG1-121 C O1 | Adder | 10.63 MW | 9.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 962781 | AG1-127 C | Adder | 12.59 MW | 10.7 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 964361 | AG1-298 O1 | Adder | 114.53 MW | 97.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 964401 | AG1-302 C O1 | Adder | 37.63 MW | 31.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 964581 | AG1-321 C O1 | Adder | 25.83 MW | 21.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 964861 | AG1-349 C O1 | Adder | 32.5 MW | 27.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 966821 | AG1-553 C O1 | Adder | 24.7 MW | 21.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 965061 | AG1-371 | Adder | 6.45 MW | 5.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 965081 | AG1-373 | Adder | 2.15 MW | 1.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 965141 | AG1-379 C | Adder | 30.08 MW | 25.57 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 965551 | AG1-423 C O1 | Adder | 26.14 MW | 22.22 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 965661 | AG1-434 C O1 | Adder | 7.48 MW | 6.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 965671 | AG1-435 C O1 | Adder | 7.18 MW | 6.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 965681 | AG1-436 C | 80/20 | 17.39 MW | 17.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 965791 | AG1-447 | 80/20 | 12.76 MW | 12.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 966091 | AG1-478 C | Adder | 3.6 MW | 3.06 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 966431 | AG1-512 C | Adder | 3.67 MW | 3.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 966441 | AG1-513 C | Adder | 0.91 MW | 0.77 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 966651 | AG1-535 O1 | Adder | 19.44 MW | 16.52 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 272364 | ESS H440N ;R | Adder | 4.76 MW | 4.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 919581 | AA2-030 C | Adder | 32.32 MW | 27.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 926331 | AC1-110 1 | Adder | 3.39 MW | 2.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 926341 | AC1-110 2 | Adder | 3.39 MW | 2.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 926821 | AC1-168 C O1 | Adder | 2.13 MW | 1.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 927451 | AC1-142A 1 | Adder | 7.28 MW | 6.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 927461 | AC1-142A 2 | Adder | 7.28 MW | 6.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 933911 | AD1-013 C | Adder | 3.33 MW | 2.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 933931 | AD1-016 C | Adder | 1.66 MW | 1.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 934051 | AD1-031 C O1 | Adder | 5.4 MW | 4.59 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 934721 | AD1-100 C | Adder | 34.38 MW | 29.22 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 934971 | AD1-129 C | Adder | 1.62 MW | 1.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 936291 | AD2-038 C O1 | Adder | 5.81 MW | 4.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 936371 | AD2-047 C O1 | Adder | 7.79 MW | 6.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 936461 | AD2-060 | Adder | 4.58 MW | 3.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 936511 | AD2-066 C O1 | Adder | 15.1 MW | 12.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 937001 | AD2-134 C | Adder | 4.58 MW | 3.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 937311 | AD2-172 C | Adder | 4.44 MW | 3.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 937401 | AD2-194 1 | Adder | 13.54 MW | 11.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 937411 | AD2-194 2 | Adder | 13.54 MW | 11.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 942421 | AE2-255 C O1 | Adder | 5.48 MW | 4.66 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 942651 | AE2-281 C O1 | Adder | 1.54 MW | 1.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 942991 | AE2-321 C | Adder | 14.63 MW | 12.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 943121 | AE2-341 C | Adder | 22.94 MW | 19.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 943591 | AF1-030 C O1 | Adder | 15.26 MW | 12.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 943801 | AF1-048 C | Adder | 6.84 MW | 5.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 944161 | AF1-084 C | Adder | 10.66 MW | 9.06 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 944931 | AF1-158 C O1 | Adder | 19.45 MW | 16.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 945421 | AF1-207 C O1 | Adder | 6.68 MW | 5.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 945501 | AF1-215 C O1 | Adder | 38.48 MW | 32.7 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958481 | AF2-142 C | Adder | 20.03 MW | 17.02 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958491 | AF2-143 C | Adder | 19.81 MW | 16.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958911 | AF2-182 C | Adder | 37.41 MW | 31.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958921 | AF2-183 C | Adder | 6.65 MW | 5.65 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 959001 | AF2-191 C O1 | Adder | 14.34 MW | 12.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 959081 | AF2-199 C | Adder | 12.89 MW | 10.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 959091 | AF2-200 C O1 | Adder | 25.78 MW | 21.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 959101 | AF2-201 C O1 | Adder | 10.88 MW | 9.24 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 959141 | AF2-205 C | Adder | 24.58 MW | 20.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 959351 | AF2-226 C | Adder | 4.45 MW | 3.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 960281 | AF2-319 C | Adder | 4.45 MW | 3.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 960381 | AF2-329 | Adder | 9.62 MW | 8.18 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 960581 | AF2-349 C | Adder | 38.99 MW | 33.14 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 960591 | AF2-350 C O1 | Adder | 13.74 MW | 11.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 960601 | AF2-351 C O1 | Adder | 1.83 MW | 1.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 960681 | AF2-359 C | 80/20 | 17.39 MW | 17.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 960721 | AF2-363 C O1 | Adder | 10.65 MW | 9.06 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 960751 | AF2-366 C | Adder | 12.56 MW | 10.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 961011 | AF2-392 C O1 | Adder | 7.28 MW | 6.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 961021 | AF2-393 O1 | Adder | 12.41 MW | 10.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 961031 | AF2-394 O1 | Adder | 8.28 MW | 7.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 961501 | AF2-441 C O1 | Adder | 18.35 MW | 15.6 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 243441 | 05CKG2 | 80/20 | 59.96 MW | 59.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 244415 | 05OLIV SLR C | Adder | 0.55 MW | 0.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 270100 | X2-052 CT1 | 80/20 | 9.21 MW | 9.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 270101 | X2-052 CT2 | 80/20 | 9.21 MW | 9.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 270102 | X2-052 ST | 80/20 | 9.96 MW | 9.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274654 | BRAIDWOOD;1U | 80/20 | 46.31 MW | 46.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274655 | BRAIDWOOD;2U | 80/20 | 45.18 MW | 45.18 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274660 | LASCO STA;1U | 80/20 | 44.75 MW | 44.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274661 | LASCO STA;2U | 80/20 | 44.94 MW | 44.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274708 | KENDALL ;3C | 80/20 | 7.24 MW | 7.24 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274709 | KENDALL ;3S | 80/20 | 4.79 MW | 4.79 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274710 | KENDALL ;4C | 80/20 | 7.16 MW | 7.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274711 | KENDALL ;4S | 80/20 | 4.79 MW | 4.79 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274770 | LINCOLN ;1U | 80/20 | 3.2 MW | 3.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274771 | LINCOLN ;2U | 80/20 | 3.2 MW | 3.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274772 | LINCOLN ;3U | 80/20 | 3.2 MW | 3.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274773 | LINCOLN ;4U | 80/20 | 3.2 MW | 3.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274774 | LINCOLN ;5U | 80/20 | 3.2 MW | 3.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274775 | LINCOLN ;6U | 80/20 | 3.2 MW | 3.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274776 | LINCOLN ;7U | 80/20 | 3.2 MW | 3.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274777 | LINCOLN ;8U | 80/20 | 3.2 MW | 3.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274788 | SE CHICAG;5U | Adder | 8.67 MW | 7.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274789 | SE CHICAG;6U | Adder | 8.69 MW | 7.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274790 | SE CHICAG;7U | Adder | 8.81 MW | 7.49 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274791 | SE CHICAG;8U | Adder | 8.81 MW | 7.49 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274792 | SE CHICAG;9U | Adder | 8.8 MW | 7.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274793 | SE CHICAG;0U | Adder | 8.8 MW | 7.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274794 | SE CHICAG;1U | Adder | 8.8 MW | 7.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274795 | SE CHICAG;2U | Adder | 8.8 MW | 7.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 276164 | X3-005 C | 80/20 | 0.13 MW | 0.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 915011 | Y3-013 1 | Adder | 6.62 MW | 5.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 915021 | Y3-013 2 | Adder | 6.62 MW | 5.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 915031 | Y3-013 3 | Adder | 6.62 MW | 5.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 925581 | AC1-033 C | Adder | 2.66 MW | 2.26 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 930482 | AB1-089 CT | Adder | 65.85 MW | 55.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 930483 | AB1-089 ST | Adder | 52.35 MW | 44.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 930761 | AB1-122 CT1 | Adder | 124.79 MW | 106.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 930771 | AB1-122 CT2 | Adder | 129.44 MW | 110.02 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 933281 | AC2-140 C | 80/20 | 1.99 MW | 1.99 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 933411 | AC2-154 C | Adder | 4.35 MW | 3.7 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 938511 | AE1-070 1 | Adder | 15.91 MW | 13.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 938521 | AE1-070 2 | Adder | 14.56 MW | 12.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 938851 | AE1-113 C O1 | Adder | 14.47 MW | 12.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 938861 | AE1-114 C O1 | Adder | 7.14 MW | 6.07 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 939051 | AE1-134 1 | Adder | 2.51 MW | 2.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 939061 | AE1-134 2 | Adder | 2.51 MW | 2.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 939321 | AE1-163 C O1 | Adder | 10.79 MW | 9.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 939351 | AE1-166 C O1 | Adder | 17.89 MW | 15.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 939395 | AE1-170 C | Adder | 12.61 MW | 10.72 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 939401 | AE1-172 C O1 | Adder | 9.69 MW | 8.23 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 940501 | AE2-035 C | Adder | 4.44 MW | 3.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 940581 | AE2-045 C O1 | Adder | 17.08 MW | 14.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 941131 | AE2-107 C | Adder | 11.84 MW | 10.06 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 941551 | AE2-152 C O1 | Adder | 20.65 MW | 17.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 946151 | AF1-280 C O1 | Adder | 28.47 MW | 24.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 946161 | AF1-281 C O1 | Adder | 0.62 MW | 0.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 946321 | AF1-296 C O1 | Adder | 7.37 MW | 6.27 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 946501 | AF1-314 C | Adder | 7.87 MW | 6.69 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 946541 | AF1-318 C O1 | Adder | 10.84 MW | 9.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 946661 | AF1-330 C | Adder | 3.58 MW | 3.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 946671 | AF1-331 | Adder | 4.33 MW | 3.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 957331 | AF2-027 C | Adder | 4.42 MW | 3.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 957371 | AF2-031 C O1 | Adder | 1.83 MW | 1.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 957401 | AF2-034 C | Adder | 2.44 MW | 2.07 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 957471 | AF2-041 C | Adder | 38.67 MW | 32.87 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 957751 | AF2-069 C | Adder | 0.45 MW | 0.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 957761 | AF2-070 C | Adder | 0.63 MW | 0.54 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 957841 | AF2-078 C O1 | Adder | 23.58 MW | 20.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958011 | AF2-095 C O1 | Adder | 31.14 MW | 26.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958021 | AF2-096 C | 80/20 | 58.55 MW | 58.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958341 | AF2-128 C O1 | Adder | 2.88 MW | 2.44 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958381 | AF2-132 C O1 | Adder | 37.63 MW | 31.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958391 | AF2-133 C O1 | Adder | 37.19 MW | 31.61 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 958401 | AF2-134 C O1 | Adder | 12.83 MW | 10.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 934101 | AD2-000 1 | Adder | 10.09 MW | 8.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 934111 | AD2-000 2 | Adder | 10.47 MW | 8.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274805 | UNIV PK N;1U | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274807 | UNIV PK N;3U | 80/20 | 1.46 MW | 1.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274808 | UNIV PK N;4U | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274810 | UNIV PK N;6U | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274811 | UNIV PK N;7U | 80/20 | 1.46 MW | 1.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274815 | UNIV PK N;XU | 80/20 | 1.45 MW | 1.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 274816 | UNIV PK N;YU | 80/20 | 1.46 MW | 1.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | 945351 | AF1-200 FTIR | 80/20 | 483.81 MW | 483.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.86 MW | 1.86 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.59 MW | 0.59 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.19 MW | 1.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 212.5 MW | 212.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 65.19 MW | 65.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.21 MW | 1.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 10.1 MW | 10.1 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.8 MW | 0.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 25.76 MW | 25.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.78 MW | 2.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.51 MW | 0.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.94 MW | 4.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P1-2_#362_1680 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 6.7 MW | 6.7 MW |
| Details for AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 961631 | AG1-003 C | 80/20 | 157.28 MW | 157.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 961641 | AG1-004 | 80/20 | 139.19 MW | 139.19 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 962601 | AG1-109 | 80/20 | 5.79 MW | 5.79 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 962691 | AG1-118 C O1 | Adder | 38.35 MW | 32.59 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 962701 | AG1-119 C | Adder | 37.92 MW | 32.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 962711 | AG1-120 C O1 | Adder | 15.01 MW | 12.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 962781 | AG1-127 C | Adder | 12.13 MW | 10.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 963701 | AG1-222 C | 80/20 | 21.47 MW | 21.47 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 964361 | AG1-298 O1 | Adder | 112.02 MW | 95.22 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 964401 | AG1-302 C O1 | Adder | 38.28 MW | 32.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 964861 | AG1-349 C O1 | Adder | 33.07 MW | 28.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965011 | AG1-365 C | 80/20 | 14.98 MW | 14.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965021 | AG1-366 C | 80/20 | 4.99 MW | 4.99 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965141 | AG1-379 C | Adder | 29.23 MW | 24.85 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965491 | AG1-417 C O1 | 80/20 | 7.56 MW | 7.56 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965501 | AG1-418 C O1 | 80/20 | 7.56 MW | 7.56 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965551 | AG1-423 C O1 | Adder | 25.28 MW | 21.49 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965651 | AG1-433 C | Adder | 3.71 MW | 3.15 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965681 | AG1-436 C | 80/20 | 17.54 MW | 17.54 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965791 | AG1-447 | 80/20 | 12.86 MW | 12.86 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965841 | AG1-453 C O1 | 80/20 | 20.05 MW | 20.05 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 965851 | AG1-454 O1 | 80/20 | 11.93 MW | 11.93 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 966091 | AG1-478 C | Adder | 3.48 MW | 2.95 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 966431 | AG1-512 C | Adder | 3.56 MW | 3.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 966441 | AG1-513 C | Adder | 0.87 MW | 0.74 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 966651 | AG1-535 O1 | Adder | 19.1 MW | 16.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 246397 | 05ELKHART HY | 80/20 | 0.1 MW | 0.1 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 246416 | 05TWIN BRCH1 | 80/20 | 0.16 MW | 0.16 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 246422 | 05MAYFLWER | 80/20 | 0.23 MW | 0.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 246431 | 05BUCHANAN | 80/20 | 0.11 MW | 0.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 246536 | 05MOTTVILL | 80/20 | 0.06 MW | 0.06 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 247270 | 05RPMNG1 | 80/20 | 6.37 MW | 6.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 247271 | 05RPMNG2 | 80/20 | 6.36 MW | 6.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 247272 | 05RPMNG3 | 80/20 | 6.37 MW | 6.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 247295 | 05KEY G4 | 80/20 | 2.3 MW | 2.3 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 247604 | X1-042 | 80/20 | 0.12 MW | 0.12 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 247620 | Y3-023 | 80/20 | 0.18 MW | 0.18 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 247643 | Z2-116 C | 80/20 | 0.05 MW | 0.05 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 272364 | ESS H440N ;R | Adder | 4.61 MW | 3.92 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 926331 | AC1-110 1 | Adder | 3.25 MW | 2.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 926341 | AC1-110 2 | Adder | 3.25 MW | 2.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 927451 | AC1-142A 1 | Adder | 7.01 MW | 5.96 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 927461 | AC1-142A 2 | Adder | 7.01 MW | 5.96 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 933911 | AD1-013 C | Adder | 3.23 MW | 2.74 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 933931 | AD1-016 C | Adder | 1.6 MW | 1.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 934721 | AD1-100 C | Adder | 32.98 MW | 28.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 934971 | AD1-129 C | Adder | 1.57 MW | 1.33 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 936141 | AD2-020 C O1 | 80/20 | 14.34 MW | 14.34 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 936291 | AD2-038 C O1 | Adder | 5.65 MW | 4.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 936371 | AD2-047 C O1 | Adder | 7.52 MW | 6.39 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 936461 | AD2-060 | Adder | 4.42 MW | 3.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 936511 | AD2-066 C O1 | Adder | 14.73 MW | 12.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 936631 | AD2-079 C O1 | 80/20 | 2.85 MW | 2.85 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 937001 | AD2-134 C | Adder | 4.44 MW | 3.77 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 937401 | AD2-194 1 | Adder | 13.07 MW | 11.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 937411 | AD2-194 2 | Adder | 13.07 MW | 11.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 938261 | AE1-039 | 80/20 | 0.03 MW | 0.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 942241 | AE2-236 C O1 | 80/20 | 9.71 MW | 9.71 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 942421 | AE2-255 C O1 | Adder | 5.33 MW | 4.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 942651 | AE2-281 C O1 | Adder | 1.5 MW | 1.27 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 942991 | AE2-321 C | Adder | 14.14 MW | 12.02 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 943001 | AE2-323 C | 80/20 | 16.01 MW | 16.01 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 943021 | AE2-325 C | 80/20 | 7.26 MW | 7.26 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 943121 | AE2-341 C | Adder | 21.88 MW | 18.6 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 943591 | AF1-030 C O1 | Adder | 14.55 MW | 12.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 943801 | AF1-048 C | Adder | 6.61 MW | 5.62 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944161 | AF1-084 C | 80/20 | 12.45 MW | 12.45 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944231 | AF1-091 C O1 | Adder | 30.43 MW | 25.86 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944241 | AF1-092 C O1 | 80/20 | 27.82 MW | 27.82 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944531 | AF1-118 C O1 | 80/20 | 62.47 MW | 62.47 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944541 | AF1-119 C O1 | Adder | 29.5 MW | 25.08 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944761 | AF1-141 C O1 | 80/20 | 14.84 MW | 14.84 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944831 | AF1-148 C O1 | 80/20 | 21.73 MW | 21.73 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944931 | AF1-158 C O1 | 80/20 | 21.13 MW | 21.13 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 944961 | AF1-161 C | 80/20 | 5.79 MW | 5.79 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 945111 | AF1-176 C O1 | 80/20 | 36.37 MW | 36.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 945501 | AF1-215 C O1 | Adder | 39.1 MW | 33.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958481 | AF2-142 C | Adder | 19.43 MW | 16.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958491 | AF2-143 C | Adder | 19.26 MW | 16.38 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958711 | AF2-162 C | Adder | 6.32 MW | 5.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 959001 | AF2-191 C O1 | 80/20 | 15.45 MW | 15.45 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 959131 | AF2-204 C | Adder | 15.44 MW | 13.12 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 959331 | AF2-224 C O1 | 80/20 | 10.49 MW | 10.49 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 959351 | AF2-226 C | Adder | 4.32 MW | 3.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960281 | AF2-319 C | Adder | 4.32 MW | 3.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960381 | AF2-329 | Adder | 9.18 MW | 7.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960581 | AF2-349 C | Adder | 37.78 MW | 32.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960591 | AF2-350 C O1 | Adder | 13.27 MW | 11.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960601 | AF2-351 C O1 | Adder | 1.77 MW | 1.5 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960681 | AF2-359 C | 80/20 | 17.54 MW | 17.54 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960721 | AF2-363 C O1 | Adder | 10.3 MW | 8.75 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960751 | AF2-366 C | Adder | 12.1 MW | 10.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960971 | AF2-388 C | Adder | 7.42 MW | 6.3 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 960981 | AF2-389 C | 80/20 | 7.03 MW | 7.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 961051 | AF2-396 O1 | 80/20 | 46.48 MW | 46.48 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 961501 | AF2-441 C O1 | Adder | 17.91 MW | 15.22 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 243071 | 05BERRINSP G | 80/20 | 0.24 MW | 0.24 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 243440 | 05CKG1 | 80/20 | 40.77 MW | 40.77 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 243441 | 05CKG2 | 80/20 | 50.67 MW | 50.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 244412 | 05WTRV SLR C | 80/20 | 0.09 MW | 0.09 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 244415 | 05OLIV SLR C | 80/20 | 0.59 MW | 0.59 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 270100 | X2-052 CT1 | 80/20 | 9.31 MW | 9.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 270101 | X2-052 CT2 | 80/20 | 9.31 MW | 9.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 270102 | X2-052 ST | 80/20 | 10.07 MW | 10.07 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 270142 | AA2-116_CT1 | 80/20 | 15.2 MW | 15.2 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 270143 | AA2-116_CT2 | 80/20 | 15.2 MW | 15.2 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 270144 | AA2-116_ST | 80/20 | 13.46 MW | 13.46 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274770 | LINCOLN ;1U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274771 | LINCOLN ;2U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274772 | LINCOLN ;3U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274773 | LINCOLN ;4U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274774 | LINCOLN ;5U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274775 | LINCOLN ;6U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274776 | LINCOLN ;7U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274777 | LINCOLN ;8U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274788 | SE CHICAG;5U | Adder | 8.52 MW | 7.24 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274789 | SE CHICAG;6U | Adder | 8.54 MW | 7.26 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274790 | SE CHICAG;7U | Adder | 8.65 MW | 7.35 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274791 | SE CHICAG;8U | Adder | 8.65 MW | 7.35 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274792 | SE CHICAG;9U | Adder | 8.66 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274793 | SE CHICAG;0U | Adder | 8.66 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274794 | SE CHICAG;1U | Adder | 8.66 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 274795 | SE CHICAG;2U | Adder | 8.66 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 915011 | Y3-013 1 | Adder | 6.4 MW | 5.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 915021 | Y3-013 2 | Adder | 6.4 MW | 5.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 915031 | Y3-013 3 | Adder | 6.4 MW | 5.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 930482 | AB1-089 CT | Adder | 63.91 MW | 54.32 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 930483 | AB1-089 ST | Adder | 12.65 MW | 10.75 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 930761 | AB1-122 CT1 | Adder | 121.35 MW | 103.15 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 930771 | AB1-122 CT2 | Adder | 124.9 MW | 106.17 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 933281 | AC2-140 C | 80/20 | 1.68 MW | 1.68 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 933411 | AC2-154 C | Adder | 4.2 MW | 3.57 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 938511 | AE1-070 1 | Adder | 15.36 MW | 13.06 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 938521 | AE1-070 2 | Adder | 14.05 MW | 11.95 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 938851 | AE1-113 C O1 | Adder | 14.06 MW | 11.95 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 939321 | AE1-163 C O1 | Adder | 10.49 MW | 8.91 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 939351 | AE1-166 C O1 | Adder | 17.19 MW | 14.61 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 939395 | AE1-170 C | 80/20 | 14.78 MW | 14.78 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 939401 | AE1-172 C O1 | Adder | 9.46 MW | 8.04 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 941131 | AE2-107 C | Adder | 11.42 MW | 9.71 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 941551 | AE2-152 C O1 | Adder | 19.84 MW | 16.86 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 946661 | AF1-330 C | Adder | 3.46 MW | 2.94 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 946671 | AF1-331 | Adder | 4.19 MW | 3.56 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 957331 | AF2-027 C | Adder | 4.26 MW | 3.62 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 957371 | AF2-031 C O1 | Adder | 1.8 MW | 1.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 957401 | AF2-034 C | Adder | 2.35 MW | 2.0 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 957891 | AF2-083 C O1 | 80/20 | 23.41 MW | 23.41 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958001 | AF2-094 C | 80/20 | 6.39 MW | 6.39 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958011 | AF2-095 C O1 | Adder | 30.08 MW | 25.57 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958021 | AF2-096 C | Adder | 56.38 MW | 47.92 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958311 | AF2-125 C | 80/20 | 8.39 MW | 8.39 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958381 | AF2-132 C O1 | Adder | 38.28 MW | 32.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958391 | AF2-133 C O1 | Adder | 37.85 MW | 32.17 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958401 | AF2-134 C O1 | Adder | 13.03 MW | 11.08 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 958431 | AF2-137 C | 80/20 | 146.15 MW | 146.15 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 934101 | AD2-000 1 | Adder | 9.81 MW | 8.34 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 934111 | AD2-000 2 | Adder | 10.1 MW | 8.59 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | 945351 | AF1-200 FTIR | Adder | 533.31 MW | 453.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.43 MW | 1.43 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.29 MW | 2.29 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 227.74 MW | 227.74 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 90.46 MW | 90.46 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.8 MW | 0.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.52 MW | 13.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.5 MW | 4.5 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 26.78 MW | 26.78 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.23 MW | 3.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 1.09 MW | 1.09 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.09 MW | 8.09 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 6.52 MW | 6.52 MW |
| Details for AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 961631 | AG1-003 C | 80/20 | 157.27 MW | 157.27 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 961641 | AG1-004 | 80/20 | 139.17 MW | 139.17 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 962601 | AG1-109 | 80/20 | 5.79 MW | 5.79 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 962691 | AG1-118 C O1 | Adder | 38.33 MW | 32.58 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 962701 | AG1-119 C | Adder | 37.9 MW | 32.22 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 962711 | AG1-120 C O1 | Adder | 15.0 MW | 12.75 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 962781 | AG1-127 C | Adder | 12.13 MW | 10.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 963701 | AG1-222 C | 80/20 | 21.46 MW | 21.46 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 964361 | AG1-298 O1 | Adder | 111.98 MW | 95.19 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 964401 | AG1-302 C O1 | Adder | 38.26 MW | 32.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 964861 | AG1-349 C O1 | Adder | 33.06 MW | 28.1 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965011 | AG1-365 C | 80/20 | 14.98 MW | 14.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965021 | AG1-366 C | 80/20 | 4.99 MW | 4.99 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965141 | AG1-379 C | Adder | 29.22 MW | 24.84 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965421 | AG1-410 C O1 | 80/20 | 44.88 MW | 44.88 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965431 | AG1-411 O1 | 80/20 | 24.93 MW | 24.93 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965491 | AG1-417 C O1 | 80/20 | 7.55 MW | 7.55 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965501 | AG1-418 C O1 | 80/20 | 7.55 MW | 7.55 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965551 | AG1-423 C O1 | Adder | 25.27 MW | 21.48 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965651 | AG1-433 C | Adder | 3.71 MW | 3.15 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965681 | AG1-436 C | 80/20 | 17.53 MW | 17.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965791 | AG1-447 | 80/20 | 12.86 MW | 12.86 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965841 | AG1-453 C O1 | 80/20 | 20.04 MW | 20.04 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 965851 | AG1-454 O1 | 80/20 | 11.93 MW | 11.93 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 966091 | AG1-478 C | Adder | 3.47 MW | 2.95 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 966431 | AG1-512 C | Adder | 3.56 MW | 3.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 966441 | AG1-513 C | Adder | 0.87 MW | 0.74 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 966651 | AG1-535 O1 | Adder | 19.09 MW | 16.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 246397 | 05ELKHART HY | 80/20 | 0.1 MW | 0.1 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 246416 | 05TWIN BRCH1 | 80/20 | 0.16 MW | 0.16 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 246422 | 05MAYFLWER | 80/20 | 0.23 MW | 0.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 246431 | 05BUCHANAN | 80/20 | 0.11 MW | 0.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 246536 | 05MOTTVILL | 80/20 | 0.06 MW | 0.06 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 246936 | 05BLCK-1 C | 80/20 | 0.7 MW | 0.7 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 246937 | 05BLCK-2 C | 80/20 | 0.7 MW | 0.7 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 246938 | 05BLCK-3 C | 80/20 | 0.7 MW | 0.7 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 247270 | 05RPMNG1 | 80/20 | 6.36 MW | 6.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 247271 | 05RPMNG2 | 80/20 | 6.36 MW | 6.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 247272 | 05RPMNG3 | 80/20 | 6.36 MW | 6.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 247295 | 05KEY G4 | 80/20 | 2.3 MW | 2.3 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 247604 | X1-042 | 80/20 | 0.12 MW | 0.12 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 247620 | Y3-023 | 80/20 | 0.18 MW | 0.18 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 247643 | Z2-116 C | 80/20 | 0.05 MW | 0.05 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 926331 | AC1-110 1 | Adder | 3.24 MW | 2.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 926341 | AC1-110 2 | Adder | 3.24 MW | 2.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 927451 | AC1-142A 1 | Adder | 7.01 MW | 5.96 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 927461 | AC1-142A 2 | Adder | 7.01 MW | 5.96 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 933931 | AD1-016 C | Adder | 1.6 MW | 1.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 934721 | AD1-100 C | Adder | 32.97 MW | 28.02 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 936141 | AD2-020 C O1 | 80/20 | 14.34 MW | 14.34 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 936291 | AD2-038 C O1 | Adder | 5.65 MW | 4.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 936371 | AD2-047 C O1 | Adder | 7.52 MW | 6.39 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 936461 | AD2-060 | Adder | 4.42 MW | 3.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 936511 | AD2-066 C O1 | Adder | 14.72 MW | 12.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 936631 | AD2-079 C O1 | 80/20 | 2.85 MW | 2.85 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 937401 | AD2-194 1 | Adder | 13.07 MW | 11.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 937411 | AD2-194 2 | Adder | 13.07 MW | 11.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 938261 | AE1-039 | 80/20 | 0.03 MW | 0.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 942241 | AE2-236 C O1 | 80/20 | 9.71 MW | 9.71 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 942421 | AE2-255 C O1 | Adder | 5.32 MW | 4.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 942651 | AE2-281 C O1 | Adder | 1.5 MW | 1.27 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 942991 | AE2-321 C | Adder | 14.14 MW | 12.02 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 943001 | AE2-323 C | 80/20 | 16.0 MW | 16.0 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 943021 | AE2-325 C | 80/20 | 7.25 MW | 7.25 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 943121 | AE2-341 C | Adder | 21.87 MW | 18.59 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 943591 | AF1-030 C O1 | Adder | 14.54 MW | 12.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 943801 | AF1-048 C | Adder | 6.61 MW | 5.62 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944161 | AF1-084 C | 80/20 | 12.44 MW | 12.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944231 | AF1-091 C O1 | Adder | 30.42 MW | 25.86 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944241 | AF1-092 C O1 | 80/20 | 27.81 MW | 27.81 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944531 | AF1-118 C O1 | 80/20 | 62.45 MW | 62.45 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944541 | AF1-119 C O1 | Adder | 29.49 MW | 25.07 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944761 | AF1-141 C O1 | 80/20 | 14.83 MW | 14.83 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944831 | AF1-148 C O1 | 80/20 | 21.73 MW | 21.73 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944931 | AF1-158 C O1 | 80/20 | 21.13 MW | 21.13 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 944961 | AF1-161 C | 80/20 | 5.79 MW | 5.79 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 945111 | AF1-176 C O1 | 80/20 | 36.36 MW | 36.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 945501 | AF1-215 C O1 | Adder | 39.09 MW | 33.22 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958481 | AF2-142 C | Adder | 19.42 MW | 16.51 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958491 | AF2-143 C | Adder | 19.26 MW | 16.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958711 | AF2-162 C | Adder | 6.32 MW | 5.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 959001 | AF2-191 C O1 | 80/20 | 15.44 MW | 15.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 959131 | AF2-204 C | Adder | 15.43 MW | 13.12 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 959331 | AF2-224 C O1 | 80/20 | 10.48 MW | 10.48 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 959351 | AF2-226 C | Adder | 4.32 MW | 3.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960281 | AF2-319 C | Adder | 4.32 MW | 3.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960381 | AF2-329 | Adder | 9.18 MW | 7.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960591 | AF2-350 C O1 | Adder | 13.27 MW | 11.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960601 | AF2-351 C O1 | Adder | 1.77 MW | 1.5 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960681 | AF2-359 C | 80/20 | 17.53 MW | 17.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960721 | AF2-363 C O1 | Adder | 10.29 MW | 8.75 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960751 | AF2-366 C | Adder | 12.09 MW | 10.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960971 | AF2-388 C | Adder | 7.42 MW | 6.3 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 960981 | AF2-389 C | 80/20 | 7.02 MW | 7.02 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 961051 | AF2-396 O1 | 80/20 | 46.46 MW | 46.46 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 961501 | AF2-441 C O1 | Adder | 17.9 MW | 15.21 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 243071 | 05BERRINSP G | 80/20 | 0.24 MW | 0.24 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 243440 | 05CKG1 | 80/20 | 40.76 MW | 40.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 243441 | 05CKG2 | 80/20 | 50.66 MW | 50.66 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 244412 | 05WTRV SLR C | 80/20 | 0.09 MW | 0.09 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 244415 | 05OLIV SLR C | 80/20 | 0.59 MW | 0.59 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 270100 | X2-052 CT1 | 80/20 | 9.31 MW | 9.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 270101 | X2-052 CT2 | 80/20 | 9.31 MW | 9.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 270102 | X2-052 ST | 80/20 | 10.07 MW | 10.07 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 270142 | AA2-116_CT1 | 80/20 | 15.19 MW | 15.19 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 270143 | AA2-116_CT2 | 80/20 | 15.19 MW | 15.19 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 270144 | AA2-116_ST | 80/20 | 13.45 MW | 13.45 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274770 | LINCOLN ;1U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274771 | LINCOLN ;2U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274772 | LINCOLN ;3U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274773 | LINCOLN ;4U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274774 | LINCOLN ;5U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274775 | LINCOLN ;6U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274776 | LINCOLN ;7U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274777 | LINCOLN ;8U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274788 | SE CHICAG;5U | Adder | 8.51 MW | 7.24 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274789 | SE CHICAG;6U | Adder | 8.54 MW | 7.26 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274790 | SE CHICAG;7U | Adder | 8.65 MW | 7.35 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274791 | SE CHICAG;8U | Adder | 8.65 MW | 7.35 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274792 | SE CHICAG;9U | Adder | 8.65 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274793 | SE CHICAG;0U | Adder | 8.65 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274794 | SE CHICAG;1U | Adder | 8.65 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 274795 | SE CHICAG;2U | Adder | 8.65 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 915011 | Y3-013 1 | Adder | 6.39 MW | 5.43 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 915021 | Y3-013 2 | Adder | 6.39 MW | 5.43 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 915031 | Y3-013 3 | Adder | 6.39 MW | 5.43 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 930761 | AB1-122 CT1 | Adder | 121.31 MW | 103.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 930771 | AB1-122 CT2 | Adder | 124.86 MW | 106.13 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 932301 | AC2-044 C | 80/20 | 1.9 MW | 1.9 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 933281 | AC2-140 C | 80/20 | 1.68 MW | 1.68 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 933411 | AC2-154 C | Adder | 4.2 MW | 3.57 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 938511 | AE1-070 1 | Adder | 15.36 MW | 13.05 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 938521 | AE1-070 2 | Adder | 14.05 MW | 11.94 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 938761 | AE1-102 C | 80/20 | 3.89 MW | 3.89 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 938851 | AE1-113 C O1 | Adder | 14.06 MW | 11.95 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 939321 | AE1-163 C O1 | Adder | 10.48 MW | 8.91 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 939351 | AE1-166 C O1 | Adder | 17.18 MW | 14.61 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 939395 | AE1-170 C | 80/20 | 14.78 MW | 14.78 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 939401 | AE1-172 C O1 | Adder | 9.46 MW | 8.04 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 941131 | AE2-107 C | Adder | 11.42 MW | 9.71 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 941551 | AE2-152 C O1 | Adder | 19.83 MW | 16.85 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 946661 | AF1-330 C | Adder | 3.46 MW | 2.94 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 957201 | AF2-014 C | 80/20 | 22.44 MW | 22.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 957331 | AF2-027 C | Adder | 4.26 MW | 3.62 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 957371 | AF2-031 C O1 | Adder | 1.8 MW | 1.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 957401 | AF2-034 C | Adder | 2.35 MW | 2.0 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 957891 | AF2-083 C O1 | 80/20 | 23.41 MW | 23.41 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958001 | AF2-094 C | 80/20 | 6.38 MW | 6.38 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958011 | AF2-095 C O1 | Adder | 30.08 MW | 25.56 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958021 | AF2-096 C | Adder | 56.36 MW | 47.9 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958311 | AF2-125 C | 80/20 | 8.38 MW | 8.38 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958381 | AF2-132 C O1 | Adder | 38.26 MW | 32.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958391 | AF2-133 C O1 | Adder | 37.84 MW | 32.16 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958401 | AF2-134 C O1 | Adder | 13.03 MW | 11.07 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 958431 | AF2-137 C | 80/20 | 146.13 MW | 146.13 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 934101 | AD2-000 1 | Adder | 9.81 MW | 8.34 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 934111 | AD2-000 2 | Adder | 10.1 MW | 8.58 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | 945351 | AF1-200 FTIR | Adder | 533.14 MW | 453.17 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.44 MW | 1.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.29 MW | 2.29 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 227.64 MW | 227.64 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 90.4 MW | 90.4 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.8 MW | 0.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.51 MW | 13.51 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.5 MW | 4.5 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 26.77 MW | 26.77 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.23 MW | 3.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 1.09 MW | 1.09 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.08 MW | 8.08 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6463_16757 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 6.52 MW | 6.52 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 12.06 MW | 10.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962701 | AG1-119 C | Adder | 17.82 MW | 15.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962702 | AG1-119 E | Adder | 11.88 MW | 10.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.69 MW | 3.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962781 | AG1-127 C | Adder | 5.71 MW | 4.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962782 | AG1-127 E | Adder | 3.8 MW | 3.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965142 | AG1-379 E | Adder | 6.33 MW | 5.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 7.92 MW | 6.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 15.75 MW | 13.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965681 | AG1-436 C | 50/50 | 64.08 MW | 64.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965682 | AG1-436 E | 50/50 | 42.72 MW | 42.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965791 | AG1-447 | 50/50 | 46.99 MW | 46.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966092 | AG1-478 E | Adder | 0.43 MW | 0.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966431 | AG1-512 C | Adder | 3.65 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966432 | AG1-512 E | Adder | 5.48 MW | 4.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966442 | AG1-513 E | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 16.13 MW | 13.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 14.63 MW | 12.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 3.48 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 3.48 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.23 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 73.34 MW | 62.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 13.32 MW | 11.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 17.81 MW | 15.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.63 MW | 3.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 2.76 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 7.56 MW | 6.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 4.63 MW | 3.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 3.29 MW | 2.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 5.12 MW | 4.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 3.43 MW | 2.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.08 MW | 1.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.09 MW | 8.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 6.73 MW | 5.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 9.7 MW | 8.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 6.46 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 2.91 MW | 2.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 7.75 MW | 6.59 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 14.07 MW | 11.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 2.98 MW | 2.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 2.98 MW | 2.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 4.37 MW | 3.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 17.74 MW | 15.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 11.83 MW | 10.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.29 MW | 3.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960681 | AF2-359 C | 50/50 | 64.08 MW | 64.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960682 | AF2-359 E | 50/50 | 42.72 MW | 42.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.22 MW | 2.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 3.8 MW | 3.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 15.02 MW | 12.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.03 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276591 | L-013 2 | Adder | 2.99 MW | 2.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 12.75 MW | 10.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | Adder | 8.1 MW | 6.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | Adder | 15.73 MW | 13.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293799 | PILOT HIL;1E | Adder | 15.02 MW | 12.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 16.19 MW | 13.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 7.63 MW | 6.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 4.44 MW | 3.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930482 | AB1-089 CT | Adder | 29.82 MW | 25.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930483 | AB1-089 ST | Adder | 23.71 MW | 20.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 56.18 MW | 47.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 60.44 MW | 51.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933412 | AC2-154 E | Adder | 3.33 MW | 2.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 23.59 MW | 20.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 10.93 MW | 9.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 32.42 MW | 27.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 7.72 MW | 6.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 2.76 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 3.57 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 9.64 MW | 8.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 6.43 MW | 5.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 16.66 MW | 14.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 17.44 MW | 14.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 8.72 MW | 7.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 6.87 MW | 5.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | Adder | 28.05 MW | 23.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | Adder | 13.2 MW | 11.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.85 MW | 16.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274805 | UNIV PK N;1U | 50/50 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274807 | UNIV PK N;3U | 50/50 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274808 | UNIV PK N;4U | 50/50 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274810 | UNIV PK N;6U | 50/50 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274811 | UNIV PK N;7U | 50/50 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274815 | UNIV PK N;XU | 50/50 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274816 | UNIV PK N;YU | 50/50 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 252.18 MW | 214.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.23 MW | 54.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.7 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.91 MW | 10.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962692 | AG1-118 E O1 | Adder | 12.06 MW | 10.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962701 | AG1-119 C | Adder | 17.82 MW | 15.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962702 | AG1-119 E | Adder | 11.88 MW | 10.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962712 | AG1-120 E O1 | Adder | 4.69 MW | 3.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962781 | AG1-127 C | Adder | 5.71 MW | 4.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962782 | AG1-127 E | Adder | 3.8 MW | 3.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965142 | AG1-379 E | Adder | 6.33 MW | 5.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965552 | AG1-423 E O1 | Adder | 7.92 MW | 6.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965662 | AG1-434 E O1 | Adder | 15.75 MW | 13.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965681 | AG1-436 C | 50/50 | 64.08 MW | 64.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965682 | AG1-436 E | 50/50 | 42.72 MW | 42.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965791 | AG1-447 | 50/50 | 46.99 MW | 46.99 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966092 | AG1-478 E | Adder | 0.43 MW | 0.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966431 | AG1-512 C | Adder | 3.65 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966432 | AG1-512 E | Adder | 5.48 MW | 4.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966442 | AG1-513 E | Adder | 0.62 MW | 0.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 16.13 MW | 13.71 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 14.63 MW | 12.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.48 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.48 MW | 2.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.23 MW | 1.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 73.34 MW | 62.34 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 13.32 MW | 11.32 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 17.81 MW | 15.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.63 MW | 3.93 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.03 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 2.76 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 7.56 MW | 6.43 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 4.63 MW | 3.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 3.29 MW | 2.79 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 5.12 MW | 4.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.43 MW | 2.92 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.08 MW | 1.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 10.09 MW | 8.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 6.73 MW | 5.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 9.7 MW | 8.24 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 6.46 MW | 5.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 2.91 MW | 2.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.75 MW | 6.59 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.17 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 14.07 MW | 11.96 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | Adder | 2.98 MW | 2.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | Adder | 2.98 MW | 2.53 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 4.37 MW | 3.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 17.74 MW | 15.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 11.83 MW | 10.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 4.29 MW | 3.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960681 | AF2-359 C | 50/50 | 64.08 MW | 64.08 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960682 | AF2-359 E | 50/50 | 42.72 MW | 42.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 3.22 MW | 2.74 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.8 MW | 3.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 15.02 MW | 12.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.03 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276591 | L-013 2 | Adder | 2.99 MW | 2.54 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 12.75 MW | 10.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | Adder | 8.1 MW | 6.89 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | Adder | 15.73 MW | 13.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293799 | PILOT HIL;1E | Adder | 15.02 MW | 12.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 16.19 MW | 13.76 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 7.63 MW | 6.48 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.44 MW | 3.77 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930482 | AB1-089 CT | Adder | 29.82 MW | 25.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930483 | AB1-089 ST | Adder | 23.71 MW | 20.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930761 | AB1-122 CT1 | Adder | 56.18 MW | 47.75 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930771 | AB1-122 CT2 | Adder | 60.44 MW | 51.37 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.33 MW | 2.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E O1 | Adder | 23.59 MW | 20.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 10.93 MW | 9.29 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 32.42 MW | 27.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 7.72 MW | 6.56 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 2.76 MW | 2.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.57 MW | 3.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 9.64 MW | 8.2 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 6.43 MW | 5.46 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 16.66 MW | 14.16 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.3 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.06 MW | 2.6 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 17.44 MW | 14.83 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 8.72 MW | 7.41 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 6.87 MW | 5.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | Adder | 28.05 MW | 23.84 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | Adder | 13.2 MW | 11.22 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 19.85 MW | 16.87 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274805 | UNIV PK N;1U | 50/50 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274807 | UNIV PK N;3U | 50/50 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274808 | UNIV PK N;4U | 50/50 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274810 | UNIV PK N;6U | 50/50 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274811 | UNIV PK N;7U | 50/50 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274815 | UNIV PK N;XU | 50/50 | 1.44 MW | 1.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274816 | UNIV PK N;YU | 50/50 | 1.45 MW | 1.45 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 252.18 MW | 214.35 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.23 MW | 54.23 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.7 MW | 1.7 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.91 MW | 10.91 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| AF2-359 TAP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 962691 | AG1-118 C O1 | Adder | 27.48 MW | 23.36 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 962692 | AG1-118 E O1 | Adder | 18.32 MW | 15.57 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 962701 | AG1-119 C | Adder | 27.06 MW | 23.0 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 962702 | AG1-119 E | Adder | 18.04 MW | 15.34 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 962711 | AG1-120 C O1 | Adder | 10.7 MW | 9.1 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 962712 | AG1-120 E O1 | Adder | 7.14 MW | 6.07 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 962781 | AG1-127 C | Adder | 8.68 MW | 7.38 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 962782 | AG1-127 E | Adder | 5.78 MW | 4.91 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 964361 | AG1-298 O1 | Adder | 76.6 MW | 65.11 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 964581 | AG1-321 C O1 | Adder | 19.06 MW | 16.2 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 964582 | AG1-321 E O1 | Adder | 11.1 MW | 9.43 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 965061 | AG1-371 | Adder | 4.43 MW | 3.77 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 965081 | AG1-373 | Adder | 1.48 MW | 1.26 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 965141 | AG1-379 C | Adder | 21.1 MW | 17.94 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 965142 | AG1-379 E | Adder | 9.66 MW | 8.21 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 965551 | AG1-423 C O1 | Adder | 18.05 MW | 15.34 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 965552 | AG1-423 E O1 | Adder | 12.03 MW | 10.23 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 965662 | AG1-434 E O1 | Adder | 10.55 MW | 8.97 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 966091 | AG1-478 C | Adder | 2.6 MW | 2.21 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 966092 | AG1-478 E | Adder | 0.65 MW | 0.56 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 966441 | AG1-513 C | Adder | 0.63 MW | 0.54 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 966442 | AG1-513 E | Adder | 0.94 MW | 0.8 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 272364 | ESS H440N ;R | Adder | 3.27 MW | 2.78 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 290021 | O50 E | Adder | 24.61 MW | 20.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 290051 | GSG-6; E | Adder | 13.02 MW | 11.07 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 295109 | WESTBROOK E | Adder | 6.97 MW | 5.93 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 910542 | X3-005 E | Adder | 0.91 MW | 0.77 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 918052 | AA1-018 E OP | Adder | 20.73 MW | 17.62 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 920272 | AA2-123 E | Adder | 3.02 MW | 2.57 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 926331 | AC1-110 1 | Adder | 2.35 MW | 2.0 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 926341 | AC1-110 2 | Adder | 2.35 MW | 2.0 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 927451 | AC1-142A 1 | Adder | 5.18 MW | 4.4 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 927461 | AC1-142A 2 | Adder | 5.18 MW | 4.4 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 933911 | AD1-013 C | Adder | 2.29 MW | 1.95 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 933912 | AD1-013 E | Adder | 3.66 MW | 3.11 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 933931 | AD1-016 C | Adder | 1.15 MW | 0.97 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 933932 | AD1-016 E | Adder | 1.87 MW | 1.59 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.69 MW | 0.58 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934721 | AD1-100 C | Adder | 29.81 MW | 25.34 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934722 | AD1-100 E | Adder | 139.1 MW | 118.23 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934971 | AD1-129 C | Adder | 1.12 MW | 0.95 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934972 | AD1-129 E | Adder | 0.74 MW | 0.63 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 4.12 MW | 3.5 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 19.29 MW | 16.39 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936371 | AD2-047 C O1 | Adder | 5.81 MW | 4.94 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936372 | AD2-047 E O1 | Adder | 28.35 MW | 24.1 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936461 | AD2-060 | Adder | 3.42 MW | 2.9 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936511 | AD2-066 C O1 | Adder | 10.57 MW | 8.98 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 936512 | AD2-066 E O1 | Adder | 7.04 MW | 5.99 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 937001 | AD2-134 C | Adder | 3.15 MW | 2.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 937002 | AD2-134 E | Adder | 12.59 MW | 10.7 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 937401 | AD2-194 1 | Adder | 9.64 MW | 8.19 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 937411 | AD2-194 2 | Adder | 9.64 MW | 8.2 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 3.84 MW | 3.27 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 11.54 MW | 9.8 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 1.09 MW | 0.93 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 6.71 MW | 5.7 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942991 | AE2-321 C | Adder | 10.12 MW | 8.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 942992 | AE2-321 E | Adder | 4.98 MW | 4.24 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 943121 | AE2-341 C | Adder | 15.81 MW | 13.44 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 943122 | AE2-341 E | Adder | 7.77 MW | 6.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 943591 | AF1-030 C O1 | Adder | 10.52 MW | 8.94 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 943592 | AF1-030 E O1 | Adder | 5.2 MW | 4.42 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 943801 | AF1-048 C | Adder | 4.73 MW | 4.02 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 943802 | AF1-048 E | Adder | 3.15 MW | 2.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958481 | AF2-142 C | Adder | 14.3 MW | 12.15 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958482 | AF2-142 E | Adder | 9.53 MW | 8.1 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958491 | AF2-143 C | Adder | 14.04 MW | 11.94 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958492 | AF2-143 E | Adder | 9.36 MW | 7.96 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959081 | AF2-199 C | Adder | 8.86 MW | 7.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959082 | AF2-199 E | Adder | 4.43 MW | 3.77 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959091 | AF2-200 C O1 | Adder | 17.73 MW | 15.07 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959092 | AF2-200 E O1 | Adder | 11.82 MW | 10.04 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959351 | AF2-226 C | Adder | 3.17 MW | 2.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 959352 | AF2-226 E | Adder | 4.75 MW | 4.04 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960281 | AF2-319 C | Adder | 3.17 MW | 2.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960282 | AF2-319 E | Adder | 4.75 MW | 4.04 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960381 | AF2-329 | Adder | 6.63 MW | 5.64 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960581 | AF2-349 C | Adder | 26.93 MW | 22.89 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960582 | AF2-349 E | Adder | 17.95 MW | 15.26 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960591 | AF2-350 C O1 | Adder | 10.25 MW | 8.71 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960592 | AF2-350 E O1 | Adder | 6.83 MW | 5.81 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 1.37 MW | 1.16 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 2.05 MW | 1.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960721 | AF2-363 C O1 | Adder | 7.34 MW | 6.24 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960722 | AF2-363 E O1 | Adder | 4.9 MW | 4.16 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960751 | AF2-366 C | Adder | 8.66 MW | 7.36 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 960752 | AF2-366 E | Adder | 5.77 MW | 4.91 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 961501 | AF2-441 C O1 | Adder | 12.42 MW | 10.55 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 961502 | AF2-441 E O1 | Adder | 18.63 MW | 15.83 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274770 | LINCOLN ;1U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274771 | LINCOLN ;2U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274772 | LINCOLN ;3U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274773 | LINCOLN ;4U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274774 | LINCOLN ;5U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274775 | LINCOLN ;6U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 274777 | LINCOLN ;8U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 275149 | KELLYCK ;1E | Adder | 23.91 MW | 20.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 276170 | Z1-108 E | Adder | 3.07 MW | 2.61 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 276591 | L-013 2 | Adder | 4.53 MW | 3.85 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293061 | N-015 E | Adder | 19.72 MW | 16.76 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293644 | O22 E1 | Adder | 12.92 MW | 10.98 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293645 | O22 E2 | Adder | 25.09 MW | 21.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293777 | CAYUG;1U E | Adder | 20.48 MW | 17.41 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293778 | CAYUG;2U E | Adder | 20.48 MW | 17.41 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 293799 | PILOT HIL;1E | Adder | 23.91 MW | 20.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 294392 | P-010 E | Adder | 25.04 MW | 21.29 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 915011 | Y3-013 1 | Adder | 4.62 MW | 3.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 915021 | Y3-013 2 | Adder | 4.62 MW | 3.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 915031 | Y3-013 3 | Adder | 4.62 MW | 3.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 916221 | Z1-073 E | Adder | 6.76 MW | 5.75 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 930482 | AB1-089 CT | Adder | 45.36 MW | 38.55 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 930483 | AB1-089 ST | Adder | 36.06 MW | 30.65 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 930761 | AB1-122 CT1 | Adder | 86.65 MW | 73.65 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 930771 | AB1-122 CT2 | Adder | 91.59 MW | 77.85 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 933411 | AC2-154 C | Adder | 3.24 MW | 2.76 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 933412 | AC2-154 E | Adder | 5.3 MW | 4.5 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 938511 | AE1-070 1 | Adder | 11.33 MW | 9.63 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 938521 | AE1-070 2 | Adder | 10.36 MW | 8.81 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 938851 | AE1-113 C O1 | Adder | 10.15 MW | 8.63 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 938852 | AE1-113 E O1 | Adder | 35.99 MW | 30.59 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 7.65 MW | 6.5 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 46.97 MW | 39.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939351 | AE1-166 C O1 | Adder | 14.7 MW | 12.5 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939352 | AE1-166 E O1 | Adder | 13.57 MW | 11.54 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 8.17 MW | 6.95 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 38.34 MW | 32.59 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.16 MW | 0.14 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 941131 | AE2-107 C | Adder | 8.15 MW | 6.93 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 941132 | AE2-107 E | Adder | 5.43 MW | 4.62 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 941551 | AE2-152 C O1 | Adder | 16.97 MW | 14.42 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 941552 | AE2-152 E O1 | Adder | 11.31 MW | 9.62 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946661 | AF1-330 C | Adder | 2.48 MW | 2.11 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946662 | AF1-330 E | Adder | 0.54 MW | 0.46 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 946671 | AF1-331 | Adder | 2.98 MW | 2.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957331 | AF2-027 C | Adder | 3.08 MW | 2.62 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957332 | AF2-027 E | Adder | 4.62 MW | 3.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.73 MW | 1.47 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957402 | AF2-034 E | Adder | 1.48 MW | 1.25 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957471 | AF2-041 C | Adder | 26.59 MW | 22.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 957472 | AF2-041 E | Adder | 13.29 MW | 11.3 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958011 | AF2-095 C O1 | Adder | 23.23 MW | 19.75 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958012 | AF2-095 E O1 | Adder | 10.93 MW | 9.29 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958021 | AF2-096 C | Adder | 44.2 MW | 37.57 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 958022 | AF2-096 E | Adder | 20.8 MW | 17.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934101 | AD2-000 1 | Adder | 7.01 MW | 5.96 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 934111 | AD2-000 2 | Adder | 7.41 MW | 6.3 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 290108 | LEEDK;1U E | Adder | 30.19 MW | 25.66 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 385.83 MW | 327.96 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.01 MW | 1.01 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.41 MW | 2.41 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.35 MW | 0.35 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 91.45 MW | 91.45 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 27.45 MW | 27.45 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.69 MW | 2.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.68 MW | 0.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.15 MW | 5.15 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.37 MW | 0.37 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.62 MW | 16.62 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.44 MW | 1.44 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 17.28 MW | 17.28 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.83 MW | 0.83 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.97 MW | 1.97 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.63 MW | 4.63 MW |
| Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 962691 | AG1-118 C O1 | Adder | 27.48 MW | 23.36 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 962692 | AG1-118 E O1 | Adder | 18.32 MW | 15.57 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 962701 | AG1-119 C | Adder | 27.06 MW | 23.0 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 962702 | AG1-119 E | Adder | 18.04 MW | 15.34 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 962711 | AG1-120 C O1 | Adder | 10.7 MW | 9.1 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 962712 | AG1-120 E O1 | Adder | 7.14 MW | 6.07 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 962781 | AG1-127 C | Adder | 8.68 MW | 7.38 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 962782 | AG1-127 E | Adder | 5.78 MW | 4.91 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 964361 | AG1-298 O1 | Adder | 76.6 MW | 65.11 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 964581 | AG1-321 C O1 | Adder | 19.06 MW | 16.2 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 964582 | AG1-321 E O1 | Adder | 11.1 MW | 9.43 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 965061 | AG1-371 | Adder | 4.43 MW | 3.77 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 965081 | AG1-373 | Adder | 1.48 MW | 1.26 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 965141 | AG1-379 C | Adder | 21.1 MW | 17.94 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 965142 | AG1-379 E | Adder | 9.66 MW | 8.21 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 965551 | AG1-423 C O1 | Adder | 18.05 MW | 15.34 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 965552 | AG1-423 E O1 | Adder | 12.03 MW | 10.23 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 965662 | AG1-434 E O1 | Adder | 10.55 MW | 8.97 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 966091 | AG1-478 C | Adder | 2.6 MW | 2.21 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 966092 | AG1-478 E | Adder | 0.65 MW | 0.56 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 966441 | AG1-513 C | Adder | 0.63 MW | 0.54 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 966442 | AG1-513 E | Adder | 0.94 MW | 0.8 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 272364 | ESS H440N ;R | Adder | 3.27 MW | 2.78 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 290021 | O50 E | Adder | 24.61 MW | 20.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 290051 | GSG-6; E | Adder | 13.02 MW | 11.07 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 295109 | WESTBROOK E | Adder | 6.97 MW | 5.93 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 910542 | X3-005 E | Adder | 0.91 MW | 0.77 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 918052 | AA1-018 E OP | Adder | 20.73 MW | 17.62 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 920272 | AA2-123 E | Adder | 3.02 MW | 2.57 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 926331 | AC1-110 1 | Adder | 2.35 MW | 2.0 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 926341 | AC1-110 2 | Adder | 2.35 MW | 2.0 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 927451 | AC1-142A 1 | Adder | 5.18 MW | 4.4 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 927461 | AC1-142A 2 | Adder | 5.18 MW | 4.4 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 933911 | AD1-013 C | Adder | 2.29 MW | 1.95 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 933912 | AD1-013 E | Adder | 3.66 MW | 3.11 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 933931 | AD1-016 C | Adder | 1.15 MW | 0.97 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 933932 | AD1-016 E | Adder | 1.87 MW | 1.59 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934432 | AD1-067 E | Adder | 0.69 MW | 0.58 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934721 | AD1-100 C | Adder | 29.81 MW | 25.34 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934722 | AD1-100 E | Adder | 139.1 MW | 118.23 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934971 | AD1-129 C | Adder | 1.12 MW | 0.95 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934972 | AD1-129 E | Adder | 0.74 MW | 0.63 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936291 | AD2-038 C O1 | Adder | 4.12 MW | 3.5 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936292 | AD2-038 E O1 | Adder | 19.29 MW | 16.39 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936371 | AD2-047 C O1 | Adder | 5.81 MW | 4.94 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936372 | AD2-047 E O1 | Adder | 28.35 MW | 24.1 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936461 | AD2-060 | Adder | 3.42 MW | 2.9 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936511 | AD2-066 C O1 | Adder | 10.57 MW | 8.98 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 936512 | AD2-066 E O1 | Adder | 7.04 MW | 5.99 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 937001 | AD2-134 C | Adder | 3.15 MW | 2.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 937002 | AD2-134 E | Adder | 12.59 MW | 10.7 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 937401 | AD2-194 1 | Adder | 9.64 MW | 8.19 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 937411 | AD2-194 2 | Adder | 9.64 MW | 8.2 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942421 | AE2-255 C O1 | Adder | 3.84 MW | 3.27 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942422 | AE2-255 E O1 | Adder | 11.54 MW | 9.8 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942651 | AE2-281 C O1 | Adder | 1.09 MW | 0.93 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942652 | AE2-281 E O1 | Adder | 6.71 MW | 5.7 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942991 | AE2-321 C | Adder | 10.12 MW | 8.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 942992 | AE2-321 E | Adder | 4.98 MW | 4.24 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 943121 | AE2-341 C | Adder | 15.81 MW | 13.44 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 943122 | AE2-341 E | Adder | 7.77 MW | 6.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 943591 | AF1-030 C O1 | Adder | 10.52 MW | 8.94 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 943592 | AF1-030 E O1 | Adder | 5.2 MW | 4.42 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 943801 | AF1-048 C | Adder | 4.73 MW | 4.02 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 943802 | AF1-048 E | Adder | 3.15 MW | 2.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958481 | AF2-142 C | Adder | 14.3 MW | 12.15 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958482 | AF2-142 E | Adder | 9.53 MW | 8.1 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958491 | AF2-143 C | Adder | 14.04 MW | 11.94 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958492 | AF2-143 E | Adder | 9.36 MW | 7.96 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959081 | AF2-199 C | Adder | 8.86 MW | 7.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959082 | AF2-199 E | Adder | 4.43 MW | 3.77 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959091 | AF2-200 C O1 | Adder | 17.73 MW | 15.07 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959092 | AF2-200 E O1 | Adder | 11.82 MW | 10.04 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959351 | AF2-226 C | Adder | 3.17 MW | 2.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 959352 | AF2-226 E | Adder | 4.75 MW | 4.04 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960281 | AF2-319 C | Adder | 3.17 MW | 2.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960282 | AF2-319 E | Adder | 4.75 MW | 4.04 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960381 | AF2-329 | Adder | 6.63 MW | 5.64 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960581 | AF2-349 C | Adder | 26.93 MW | 22.89 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960582 | AF2-349 E | Adder | 17.95 MW | 15.26 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960591 | AF2-350 C O1 | Adder | 10.25 MW | 8.71 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960592 | AF2-350 E O1 | Adder | 6.83 MW | 5.81 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960601 | AF2-351 C O1 | Adder | 1.37 MW | 1.16 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960602 | AF2-351 E O1 | Adder | 2.05 MW | 1.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960721 | AF2-363 C O1 | Adder | 7.34 MW | 6.24 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960722 | AF2-363 E O1 | Adder | 4.9 MW | 4.16 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960751 | AF2-366 C | Adder | 8.66 MW | 7.36 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 960752 | AF2-366 E | Adder | 5.77 MW | 4.91 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 961501 | AF2-441 C O1 | Adder | 12.42 MW | 10.55 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 961502 | AF2-441 E O1 | Adder | 18.63 MW | 15.83 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274770 | LINCOLN ;1U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274771 | LINCOLN ;2U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274772 | LINCOLN ;3U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274773 | LINCOLN ;4U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274774 | LINCOLN ;5U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274775 | LINCOLN ;6U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 274777 | LINCOLN ;8U | 50/50 | 3.82 MW | 3.82 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 275149 | KELLYCK ;1E | Adder | 23.91 MW | 20.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 276170 | Z1-108 E | Adder | 3.07 MW | 2.61 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 276591 | L-013 2 | Adder | 4.53 MW | 3.85 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293061 | N-015 E | Adder | 19.72 MW | 16.76 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293644 | O22 E1 | Adder | 12.92 MW | 10.98 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293645 | O22 E2 | Adder | 25.09 MW | 21.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293777 | CAYUG;1U E | Adder | 20.48 MW | 17.41 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293778 | CAYUG;2U E | Adder | 20.48 MW | 17.41 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 293799 | PILOT HIL;1E | Adder | 23.91 MW | 20.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 294392 | P-010 E | Adder | 25.04 MW | 21.29 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 915011 | Y3-013 1 | Adder | 4.62 MW | 3.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 915021 | Y3-013 2 | Adder | 4.62 MW | 3.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 915031 | Y3-013 3 | Adder | 4.62 MW | 3.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 916221 | Z1-073 E | Adder | 6.76 MW | 5.75 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 930482 | AB1-089 CT | Adder | 45.36 MW | 38.55 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 930483 | AB1-089 ST | Adder | 36.06 MW | 30.65 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 930761 | AB1-122 CT1 | Adder | 86.65 MW | 73.65 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 930771 | AB1-122 CT2 | Adder | 91.59 MW | 77.85 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 933411 | AC2-154 C | Adder | 3.24 MW | 2.76 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 933412 | AC2-154 E | Adder | 5.3 MW | 4.5 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 938511 | AE1-070 1 | Adder | 11.33 MW | 9.63 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 938521 | AE1-070 2 | Adder | 10.36 MW | 8.81 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 938851 | AE1-113 C O1 | Adder | 10.15 MW | 8.63 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 938852 | AE1-113 E O1 | Adder | 35.99 MW | 30.59 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939321 | AE1-163 C O1 | Adder | 7.65 MW | 6.5 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939322 | AE1-163 E O1 | Adder | 46.97 MW | 39.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939351 | AE1-166 C O1 | Adder | 14.7 MW | 12.5 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939352 | AE1-166 E O1 | Adder | 13.57 MW | 11.54 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939401 | AE1-172 C O1 | Adder | 8.17 MW | 6.95 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 939402 | AE1-172 E O1 | Adder | 38.34 MW | 32.59 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 940752 | AE2-062 E | Adder | 0.16 MW | 0.14 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 941131 | AE2-107 C | Adder | 8.15 MW | 6.93 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 941132 | AE2-107 E | Adder | 5.43 MW | 4.62 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 941551 | AE2-152 C O1 | Adder | 16.97 MW | 14.42 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 941552 | AE2-152 E O1 | Adder | 11.31 MW | 9.62 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946661 | AF1-330 C | Adder | 2.48 MW | 2.11 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946662 | AF1-330 E | Adder | 0.54 MW | 0.46 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 946671 | AF1-331 | Adder | 2.98 MW | 2.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957331 | AF2-027 C | Adder | 3.08 MW | 2.62 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957332 | AF2-027 E | Adder | 4.62 MW | 3.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957401 | AF2-034 C | Adder | 1.73 MW | 1.47 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957402 | AF2-034 E | Adder | 1.48 MW | 1.25 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957471 | AF2-041 C | Adder | 26.59 MW | 22.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 957472 | AF2-041 E | Adder | 13.29 MW | 11.3 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958011 | AF2-095 C O1 | Adder | 23.23 MW | 19.75 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958012 | AF2-095 E O1 | Adder | 10.93 MW | 9.29 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958021 | AF2-096 C | Adder | 44.2 MW | 37.57 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 958022 | AF2-096 E | Adder | 20.8 MW | 17.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934101 | AD2-000 1 | Adder | 7.01 MW | 5.96 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 934111 | AD2-000 2 | Adder | 7.41 MW | 6.3 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 290108 | LEEDK;1U E | Adder | 30.19 MW | 25.66 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | 945351 | AF1-200 FTIR | Adder | 385.83 MW | 327.96 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.01 MW | 1.01 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.41 MW | 2.41 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.35 MW | 0.35 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 91.45 MW | 91.45 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 27.45 MW | 27.45 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.69 MW | 2.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.68 MW | 0.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.15 MW | 5.15 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.37 MW | 0.37 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.62 MW | 16.62 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.44 MW | 1.44 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 17.28 MW | 17.28 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.83 MW | 0.83 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.97 MW | 1.97 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT2-3__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.63 MW | 4.63 MW |
| Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 962691 | AG1-118 C O1 | Adder | 26.91 MW | 22.87 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 962692 | AG1-118 E O1 | Adder | 17.94 MW | 15.25 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 962701 | AG1-119 C | Adder | 26.5 MW | 22.52 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 962702 | AG1-119 E | Adder | 17.67 MW | 15.02 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 962711 | AG1-120 C O1 | Adder | 10.48 MW | 8.91 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 962712 | AG1-120 E O1 | Adder | 6.99 MW | 5.94 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 962781 | AG1-127 C | Adder | 8.5 MW | 7.22 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 962782 | AG1-127 E | Adder | 5.66 MW | 4.81 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 964361 | AG1-298 O1 | Adder | 74.92 MW | 63.68 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 964581 | AG1-321 C O1 | Adder | 18.68 MW | 15.87 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 964582 | AG1-321 E O1 | Adder | 10.87 MW | 9.24 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 965061 | AG1-371 | Adder | 4.34 MW | 3.69 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 965081 | AG1-373 | Adder | 1.45 MW | 1.23 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 965141 | AG1-379 C | Adder | 20.66 MW | 17.56 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 965142 | AG1-379 E | Adder | 9.46 MW | 8.04 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 17.67 MW | 15.02 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 11.78 MW | 10.01 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 10.33 MW | 8.78 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 966091 | AG1-478 C | Adder | 2.54 MW | 2.16 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 966092 | AG1-478 E | Adder | 0.64 MW | 0.54 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 966441 | AG1-513 C | Adder | 0.62 MW | 0.52 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 966442 | AG1-513 E | Adder | 0.92 MW | 0.79 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 272364 | ESS H440N ;R | Adder | 3.2 MW | 2.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 290021 | O50 E | Adder | 24.09 MW | 20.48 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 290051 | GSG-6; E | Adder | 12.75 MW | 10.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 295109 | WESTBROOK E | Adder | 6.83 MW | 5.8 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 910542 | X3-005 E | Adder | 0.89 MW | 0.76 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 918052 | AA1-018 E OP | Adder | 20.29 MW | 17.25 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 920272 | AA2-123 E | Adder | 2.96 MW | 2.52 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 926331 | AC1-110 1 | Adder | 2.3 MW | 1.96 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 926341 | AC1-110 2 | Adder | 2.3 MW | 1.96 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 927451 | AC1-142A 1 | Adder | 5.07 MW | 4.31 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 927461 | AC1-142A 2 | Adder | 5.07 MW | 4.31 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 933911 | AD1-013 C | Adder | 2.24 MW | 1.91 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 933912 | AD1-013 E | Adder | 3.58 MW | 3.05 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 933931 | AD1-016 C | Adder | 1.12 MW | 0.95 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 933932 | AD1-016 E | Adder | 1.83 MW | 1.56 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934432 | AD1-067 E | Adder | 0.67 MW | 0.57 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934721 | AD1-100 C | Adder | 29.23 MW | 24.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934722 | AD1-100 E | Adder | 136.39 MW | 115.94 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934971 | AD1-129 C | Adder | 1.09 MW | 0.93 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934972 | AD1-129 E | Adder | 0.73 MW | 0.62 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936291 | AD2-038 C O1 | Adder | 4.03 MW | 3.43 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936292 | AD2-038 E O1 | Adder | 18.88 MW | 16.05 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936371 | AD2-047 C O1 | Adder | 5.69 MW | 4.83 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 27.77 MW | 23.61 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936461 | AD2-060 | Adder | 3.35 MW | 2.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 10.35 MW | 8.8 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 6.9 MW | 5.86 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 937001 | AD2-134 C | Adder | 3.09 MW | 2.62 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 937002 | AD2-134 E | Adder | 12.33 MW | 10.48 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 937401 | AD2-194 1 | Adder | 9.44 MW | 8.02 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 937411 | AD2-194 2 | Adder | 9.44 MW | 8.02 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942421 | AE2-255 C O1 | Adder | 3.76 MW | 3.2 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942422 | AE2-255 E O1 | Adder | 11.29 MW | 9.6 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942651 | AE2-281 C O1 | Adder | 1.07 MW | 0.91 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942652 | AE2-281 E O1 | Adder | 6.57 MW | 5.58 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942991 | AE2-321 C | Adder | 9.91 MW | 8.42 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 942992 | AE2-321 E | Adder | 4.88 MW | 4.15 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 943121 | AE2-341 C | Adder | 15.48 MW | 13.16 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 943122 | AE2-341 E | Adder | 7.6 MW | 6.46 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 943591 | AF1-030 C O1 | Adder | 10.3 MW | 8.75 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 943592 | AF1-030 E O1 | Adder | 5.1 MW | 4.33 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 943801 | AF1-048 C | Adder | 4.63 MW | 3.94 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 943802 | AF1-048 E | Adder | 3.09 MW | 2.62 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958481 | AF2-142 C | Adder | 13.99 MW | 11.89 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958482 | AF2-142 E | Adder | 9.33 MW | 7.93 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958491 | AF2-143 C | Adder | 13.75 MW | 11.68 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958492 | AF2-143 E | Adder | 9.16 MW | 7.79 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959081 | AF2-199 C | Adder | 8.68 MW | 7.38 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959082 | AF2-199 E | Adder | 4.34 MW | 3.69 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959091 | AF2-200 C O1 | Adder | 17.36 MW | 14.75 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959092 | AF2-200 E O1 | Adder | 11.57 MW | 9.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959351 | AF2-226 C | Adder | 3.1 MW | 2.64 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 959352 | AF2-226 E | Adder | 4.65 MW | 3.96 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960281 | AF2-319 C | Adder | 3.1 MW | 2.64 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960282 | AF2-319 E | Adder | 4.65 MW | 3.96 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960381 | AF2-329 | Adder | 6.5 MW | 5.52 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960581 | AF2-349 C | Adder | 26.37 MW | 22.41 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960582 | AF2-349 E | Adder | 17.58 MW | 14.94 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960591 | AF2-350 C O1 | Adder | 10.04 MW | 8.53 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960592 | AF2-350 E O1 | Adder | 6.69 MW | 5.69 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960601 | AF2-351 C O1 | Adder | 1.34 MW | 1.14 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960602 | AF2-351 E O1 | Adder | 2.01 MW | 1.71 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960721 | AF2-363 C O1 | Adder | 7.19 MW | 6.11 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960722 | AF2-363 E O1 | Adder | 4.79 MW | 4.07 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960751 | AF2-366 C | Adder | 8.48 MW | 7.21 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 960752 | AF2-366 E | Adder | 5.65 MW | 4.8 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 961501 | AF2-441 C O1 | Adder | 12.16 MW | 10.34 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 961502 | AF2-441 E O1 | Adder | 18.24 MW | 15.5 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274770 | LINCOLN ;1U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274771 | LINCOLN ;2U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274772 | LINCOLN ;3U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274773 | LINCOLN ;4U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274775 | LINCOLN ;6U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274776 | LINCOLN ;7U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 274777 | LINCOLN ;8U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 275149 | KELLYCK ;1E | Adder | 23.42 MW | 19.91 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 276170 | Z1-108 E | Adder | 3.01 MW | 2.56 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 276591 | L-013 2 | Adder | 4.44 MW | 3.77 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293061 | N-015 E | Adder | 19.32 MW | 16.42 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293644 | O22 E1 | Adder | 12.66 MW | 10.76 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293645 | O22 E2 | Adder | 24.57 MW | 20.88 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293777 | CAYUG;1U E | Adder | 20.08 MW | 17.07 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293778 | CAYUG;2U E | Adder | 20.08 MW | 17.07 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 293799 | PILOT HIL;1E | Adder | 23.42 MW | 19.91 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 294392 | P-010 E | Adder | 24.53 MW | 20.85 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 915011 | Y3-013 1 | Adder | 4.52 MW | 3.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 915021 | Y3-013 2 | Adder | 4.52 MW | 3.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 915031 | Y3-013 3 | Adder | 4.52 MW | 3.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 916221 | Z1-073 E | Adder | 6.62 MW | 5.63 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 930482 | AB1-089 CT | Adder | 44.41 MW | 37.75 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 930483 | AB1-089 ST | Adder | 35.31 MW | 30.01 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 930761 | AB1-122 CT1 | Adder | 84.85 MW | 72.12 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 89.67 MW | 76.22 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 933411 | AC2-154 C | Adder | 3.18 MW | 2.7 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 933412 | AC2-154 E | Adder | 5.19 MW | 4.41 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 938511 | AE1-070 1 | Adder | 11.09 MW | 9.43 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 938521 | AE1-070 2 | Adder | 10.15 MW | 8.62 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 938851 | AE1-113 C O1 | Adder | 9.94 MW | 8.45 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 938852 | AE1-113 E O1 | Adder | 35.24 MW | 29.95 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939321 | AE1-163 C O1 | Adder | 7.48 MW | 6.36 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939322 | AE1-163 E O1 | Adder | 45.97 MW | 39.08 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 14.42 MW | 12.25 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 13.31 MW | 11.31 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939401 | AE1-172 C O1 | Adder | 8.01 MW | 6.81 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 939402 | AE1-172 E O1 | Adder | 37.6 MW | 31.96 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 940752 | AE2-062 E | Adder | 0.16 MW | 0.13 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 941131 | AE2-107 C | Adder | 7.98 MW | 6.78 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 941132 | AE2-107 E | Adder | 5.32 MW | 4.52 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 16.63 MW | 14.14 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 11.09 MW | 9.43 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946661 | AF1-330 C | Adder | 2.43 MW | 2.06 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946662 | AF1-330 E | Adder | 0.53 MW | 0.45 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 946671 | AF1-331 | Adder | 2.91 MW | 2.48 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957331 | AF2-027 C | Adder | 3.01 MW | 2.56 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957332 | AF2-027 E | Adder | 4.52 MW | 3.84 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957401 | AF2-034 C | Adder | 1.7 MW | 1.44 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957402 | AF2-034 E | Adder | 1.44 MW | 1.23 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957471 | AF2-041 C | Adder | 26.04 MW | 22.13 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 957472 | AF2-041 E | Adder | 13.02 MW | 11.06 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958011 | AF2-095 C O1 | Adder | 22.76 MW | 19.34 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958012 | AF2-095 E O1 | Adder | 10.71 MW | 9.1 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958021 | AF2-096 C | Adder | 43.31 MW | 36.81 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 958022 | AF2-096 E | Adder | 20.38 MW | 17.32 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934101 | AD2-000 1 | Adder | 6.86 MW | 5.83 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 934111 | AD2-000 2 | Adder | 7.25 MW | 6.16 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 290108 | LEEDK;1U E | Adder | 29.56 MW | 25.12 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | 945351 | AF1-200 FTIR | Adder | 377.85 MW | 321.18 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.99 MW | 0.99 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.35 MW | 2.35 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.34 MW | 0.34 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 89.54 MW | 89.54 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.9 MW | 26.9 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.64 MW | 2.64 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.67 MW | 0.67 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.05 MW | 5.05 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.28 MW | 16.28 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.41 MW | 1.41 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 16.91 MW | 16.91 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.81 MW | 0.81 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.93 MW | 1.93 MW |
| WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_112-65-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.53 MW | 4.53 MW |
| Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 962691 | AG1-118 C O1 | Adder | 26.91 MW | 22.87 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 962692 | AG1-118 E O1 | Adder | 17.94 MW | 15.25 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 962701 | AG1-119 C | Adder | 26.5 MW | 22.52 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 962702 | AG1-119 E | Adder | 17.67 MW | 15.02 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 962711 | AG1-120 C O1 | Adder | 10.48 MW | 8.91 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 962712 | AG1-120 E O1 | Adder | 6.99 MW | 5.94 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 962781 | AG1-127 C | Adder | 8.5 MW | 7.22 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 962782 | AG1-127 E | Adder | 5.66 MW | 4.81 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 964361 | AG1-298 O1 | Adder | 74.92 MW | 63.68 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 964581 | AG1-321 C O1 | Adder | 18.68 MW | 15.87 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 964582 | AG1-321 E O1 | Adder | 10.87 MW | 9.24 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 965061 | AG1-371 | Adder | 4.34 MW | 3.69 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 965081 | AG1-373 | Adder | 1.45 MW | 1.23 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 965141 | AG1-379 C | Adder | 20.66 MW | 17.56 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 965142 | AG1-379 E | Adder | 9.46 MW | 8.04 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 17.67 MW | 15.02 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 11.78 MW | 10.01 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 10.33 MW | 8.78 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 966091 | AG1-478 C | Adder | 2.54 MW | 2.16 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 966092 | AG1-478 E | Adder | 0.64 MW | 0.54 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 966441 | AG1-513 C | Adder | 0.62 MW | 0.52 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 966442 | AG1-513 E | Adder | 0.92 MW | 0.79 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 272364 | ESS H440N ;R | Adder | 3.2 MW | 2.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 290021 | O50 E | Adder | 24.09 MW | 20.48 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 290051 | GSG-6; E | Adder | 12.75 MW | 10.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 295109 | WESTBROOK E | Adder | 6.83 MW | 5.8 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 910542 | X3-005 E | Adder | 0.89 MW | 0.76 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 918052 | AA1-018 E OP | Adder | 20.29 MW | 17.25 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 920272 | AA2-123 E | Adder | 2.96 MW | 2.52 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 926331 | AC1-110 1 | Adder | 2.3 MW | 1.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 926341 | AC1-110 2 | Adder | 2.3 MW | 1.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 927451 | AC1-142A 1 | Adder | 5.07 MW | 4.31 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 927461 | AC1-142A 2 | Adder | 5.07 MW | 4.31 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 933911 | AD1-013 C | Adder | 2.24 MW | 1.91 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 933912 | AD1-013 E | Adder | 3.58 MW | 3.05 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 933931 | AD1-016 C | Adder | 1.12 MW | 0.95 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 933932 | AD1-016 E | Adder | 1.83 MW | 1.56 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934432 | AD1-067 E | Adder | 0.67 MW | 0.57 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934721 | AD1-100 C | Adder | 29.23 MW | 24.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934722 | AD1-100 E | Adder | 136.39 MW | 115.94 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934971 | AD1-129 C | Adder | 1.09 MW | 0.93 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934972 | AD1-129 E | Adder | 0.73 MW | 0.62 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936291 | AD2-038 C O1 | Adder | 4.03 MW | 3.43 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936292 | AD2-038 E O1 | Adder | 18.88 MW | 16.05 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936371 | AD2-047 C O1 | Adder | 5.69 MW | 4.83 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 27.77 MW | 23.61 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936461 | AD2-060 | Adder | 3.35 MW | 2.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 10.35 MW | 8.8 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 6.9 MW | 5.86 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 937001 | AD2-134 C | Adder | 3.09 MW | 2.62 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 937002 | AD2-134 E | Adder | 12.33 MW | 10.48 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 937401 | AD2-194 1 | Adder | 9.44 MW | 8.02 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 937411 | AD2-194 2 | Adder | 9.44 MW | 8.02 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942421 | AE2-255 C O1 | Adder | 3.76 MW | 3.2 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942422 | AE2-255 E O1 | Adder | 11.29 MW | 9.6 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942651 | AE2-281 C O1 | Adder | 1.07 MW | 0.91 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942652 | AE2-281 E O1 | Adder | 6.57 MW | 5.58 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942991 | AE2-321 C | Adder | 9.91 MW | 8.42 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 942992 | AE2-321 E | Adder | 4.88 MW | 4.15 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 943121 | AE2-341 C | Adder | 15.48 MW | 13.16 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 943122 | AE2-341 E | Adder | 7.6 MW | 6.46 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 943591 | AF1-030 C O1 | Adder | 10.3 MW | 8.75 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 943592 | AF1-030 E O1 | Adder | 5.1 MW | 4.33 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 943801 | AF1-048 C | Adder | 4.63 MW | 3.94 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 943802 | AF1-048 E | Adder | 3.09 MW | 2.62 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958481 | AF2-142 C | Adder | 13.99 MW | 11.89 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958482 | AF2-142 E | Adder | 9.33 MW | 7.93 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958491 | AF2-143 C | Adder | 13.75 MW | 11.68 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958492 | AF2-143 E | Adder | 9.16 MW | 7.79 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959081 | AF2-199 C | Adder | 8.68 MW | 7.38 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959082 | AF2-199 E | Adder | 4.34 MW | 3.69 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959091 | AF2-200 C O1 | Adder | 17.36 MW | 14.75 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959092 | AF2-200 E O1 | Adder | 11.57 MW | 9.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959351 | AF2-226 C | Adder | 3.1 MW | 2.64 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 959352 | AF2-226 E | Adder | 4.65 MW | 3.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960281 | AF2-319 C | Adder | 3.1 MW | 2.64 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960282 | AF2-319 E | Adder | 4.65 MW | 3.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960381 | AF2-329 | Adder | 6.5 MW | 5.52 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960581 | AF2-349 C | Adder | 26.37 MW | 22.41 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960582 | AF2-349 E | Adder | 17.58 MW | 14.94 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960591 | AF2-350 C O1 | Adder | 10.04 MW | 8.53 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960592 | AF2-350 E O1 | Adder | 6.69 MW | 5.69 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960601 | AF2-351 C O1 | Adder | 1.34 MW | 1.14 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960602 | AF2-351 E O1 | Adder | 2.01 MW | 1.71 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960721 | AF2-363 C O1 | Adder | 7.19 MW | 6.11 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960722 | AF2-363 E O1 | Adder | 4.79 MW | 4.07 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960751 | AF2-366 C | Adder | 8.48 MW | 7.21 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 960752 | AF2-366 E | Adder | 5.65 MW | 4.8 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 961501 | AF2-441 C O1 | Adder | 12.16 MW | 10.34 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 961502 | AF2-441 E O1 | Adder | 18.24 MW | 15.5 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274770 | LINCOLN ;1U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274771 | LINCOLN ;2U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274772 | LINCOLN ;3U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274773 | LINCOLN ;4U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274775 | LINCOLN ;6U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274776 | LINCOLN ;7U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 274777 | LINCOLN ;8U | 50/50 | 3.72 MW | 3.72 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 275149 | KELLYCK ;1E | Adder | 23.42 MW | 19.91 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 276170 | Z1-108 E | Adder | 3.01 MW | 2.56 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 276591 | L-013 2 | Adder | 4.44 MW | 3.77 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293061 | N-015 E | Adder | 19.32 MW | 16.42 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293644 | O22 E1 | Adder | 12.66 MW | 10.76 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293645 | O22 E2 | Adder | 24.57 MW | 20.88 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293777 | CAYUG;1U E | Adder | 20.08 MW | 17.07 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293778 | CAYUG;2U E | Adder | 20.08 MW | 17.07 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 293799 | PILOT HIL;1E | Adder | 23.42 MW | 19.91 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 294392 | P-010 E | Adder | 24.53 MW | 20.85 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 915011 | Y3-013 1 | Adder | 4.52 MW | 3.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 915021 | Y3-013 2 | Adder | 4.52 MW | 3.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 915031 | Y3-013 3 | Adder | 4.52 MW | 3.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 916221 | Z1-073 E | Adder | 6.62 MW | 5.63 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 930482 | AB1-089 CT | Adder | 44.41 MW | 37.75 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 930483 | AB1-089 ST | Adder | 35.31 MW | 30.01 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 930761 | AB1-122 CT1 | Adder | 84.85 MW | 72.12 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 89.67 MW | 76.22 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 933411 | AC2-154 C | Adder | 3.18 MW | 2.7 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 933412 | AC2-154 E | Adder | 5.19 MW | 4.41 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 938511 | AE1-070 1 | Adder | 11.09 MW | 9.43 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 938521 | AE1-070 2 | Adder | 10.15 MW | 8.62 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 938851 | AE1-113 C O1 | Adder | 9.94 MW | 8.45 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 938852 | AE1-113 E O1 | Adder | 35.24 MW | 29.95 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939321 | AE1-163 C O1 | Adder | 7.48 MW | 6.36 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939322 | AE1-163 E O1 | Adder | 45.97 MW | 39.08 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 14.42 MW | 12.25 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 13.31 MW | 11.31 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939401 | AE1-172 C O1 | Adder | 8.01 MW | 6.81 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 939402 | AE1-172 E O1 | Adder | 37.6 MW | 31.96 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 940752 | AE2-062 E | Adder | 0.16 MW | 0.13 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 941131 | AE2-107 C | Adder | 7.98 MW | 6.78 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 941132 | AE2-107 E | Adder | 5.32 MW | 4.52 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 16.63 MW | 14.14 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 11.09 MW | 9.43 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946661 | AF1-330 C | Adder | 2.43 MW | 2.06 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946662 | AF1-330 E | Adder | 0.53 MW | 0.45 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 946671 | AF1-331 | Adder | 2.91 MW | 2.48 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957331 | AF2-027 C | Adder | 3.01 MW | 2.56 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957332 | AF2-027 E | Adder | 4.52 MW | 3.84 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957401 | AF2-034 C | Adder | 1.7 MW | 1.44 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957402 | AF2-034 E | Adder | 1.44 MW | 1.23 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957471 | AF2-041 C | Adder | 26.04 MW | 22.13 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 957472 | AF2-041 E | Adder | 13.02 MW | 11.06 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958011 | AF2-095 C O1 | Adder | 22.76 MW | 19.34 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958012 | AF2-095 E O1 | Adder | 10.71 MW | 9.1 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958021 | AF2-096 C | Adder | 43.31 MW | 36.81 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 958022 | AF2-096 E | Adder | 20.38 MW | 17.32 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934101 | AD2-000 1 | Adder | 6.86 MW | 5.83 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 934111 | AD2-000 2 | Adder | 7.25 MW | 6.16 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 290108 | LEEDK;1U E | Adder | 29.56 MW | 25.12 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | 945351 | AF1-200 FTIR | Adder | 377.85 MW | 321.18 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.99 MW | 0.99 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.35 MW | 2.35 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.02 MW | 0.02 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.34 MW | 0.34 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 89.54 MW | 89.54 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.9 MW | 26.9 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.03 MW | 0.03 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.64 MW | 2.64 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.67 MW | 0.67 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.05 MW | 5.05 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.36 MW | 0.36 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 16.28 MW | 16.28 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.41 MW | 1.41 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 16.91 MW | 16.91 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.81 MW | 0.81 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.93 MW | 1.93 MW |
| WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 4.53 MW | 4.53 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960581 | AF2-349 C | 50/50 | 87.91 MW | 87.91 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960582 | AF2-349 E | 50/50 | 58.6 MW | 58.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274761 | LEE CO EC;2U | 50/50 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960581 | AF2-349 C | 50/50 | 87.91 MW | 87.91 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960582 | AF2-349 E | 50/50 | 58.6 MW | 58.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274761 | LEE CO EC;2U | 50/50 | 2.56 MW | 2.56 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| GARDEN PR; R-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 12.06 MW | 10.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962701 | AG1-119 C | Adder | 17.82 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962702 | AG1-119 E | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.69 MW | 3.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962781 | AG1-127 C | Adder | 5.71 MW | 4.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962782 | AG1-127 E | Adder | 3.8 MW | 3.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965142 | AG1-379 E | Adder | 6.33 MW | 5.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 7.92 MW | 6.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 15.75 MW | 13.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966092 | AG1-478 E | Adder | 0.43 MW | 0.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966431 | AG1-512 C | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966432 | AG1-512 E | Adder | 5.48 MW | 4.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966442 | AG1-513 E | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 16.13 MW | 13.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.12 MW | 1.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 14.63 MW | 12.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 3.48 MW | 2.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 3.48 MW | 2.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.23 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 73.34 MW | 62.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 13.32 MW | 11.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.63 MW | 3.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 2.76 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 7.56 MW | 6.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 4.63 MW | 3.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 3.29 MW | 2.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 5.12 MW | 4.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 3.43 MW | 2.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.08 MW | 1.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 10.09 MW | 8.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 6.73 MW | 5.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 9.7 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 6.46 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958911 | AF2-182 C | Adder | 14.64 MW | 12.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 7.75 MW | 6.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 14.07 MW | 11.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | Adder | 2.98 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | Adder | 2.98 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 4.37 MW | 3.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 17.74 MW | 15.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 11.83 MW | 10.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 4.29 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.22 MW | 2.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 3.8 MW | 3.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274859 | EASYR;U1 E | Adder | 8.97 MW | 7.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274860 | EASYR;U2 E | Adder | 8.97 MW | 7.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 15.02 MW | 12.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.03 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276591 | L-013 2 | Adder | 2.99 MW | 2.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 12.75 MW | 10.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | Adder | 8.1 MW | 6.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | Adder | 15.73 MW | 13.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293799 | PILOT HIL;1E | Adder | 15.02 MW | 12.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 16.19 MW | 13.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 7.63 MW | 6.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 4.44 MW | 3.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930482 | AB1-089 CT | Adder | 29.82 MW | 25.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930483 | AB1-089 ST | Adder | 23.71 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 56.18 MW | 47.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 60.44 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933412 | AC2-154 E | Adder | 3.33 MW | 2.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 23.59 MW | 20.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 10.93 MW | 9.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 32.42 MW | 27.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 7.72 MW | 6.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939402 | AE1-172 E O1 | Adder | 19.65 MW | 16.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 2.76 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 3.57 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 9.64 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 6.43 MW | 5.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 16.66 MW | 14.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 17.44 MW | 14.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 8.72 MW | 7.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 6.87 MW | 5.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | Adder | 28.05 MW | 23.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | Adder | 13.2 MW | 11.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.85 MW | 16.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274805 | UNIV PK N;1U | 50/50 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274807 | UNIV PK N;3U | 50/50 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274808 | UNIV PK N;4U | 50/50 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274810 | UNIV PK N;6U | 50/50 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274811 | UNIV PK N;7U | 50/50 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274815 | UNIV PK N;XU | 50/50 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274816 | UNIV PK N;YU | 50/50 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 252.18 MW | 214.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965792 | AG1-447 BAT | Adder | 9.42 MW | 8.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.23 MW | 54.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.91 MW | 10.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962691 | AG1-118 C O1 | Adder | 18.09 MW | 15.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962692 | AG1-118 E O1 | Adder | 12.06 MW | 10.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962701 | AG1-119 C | Adder | 17.82 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962702 | AG1-119 E | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962711 | AG1-120 C O1 | Adder | 7.04 MW | 5.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962712 | AG1-120 E O1 | Adder | 4.69 MW | 3.99 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962781 | AG1-127 C | Adder | 5.71 MW | 4.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962782 | AG1-127 E | Adder | 3.8 MW | 3.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965061 | AG1-371 | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965081 | AG1-373 | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965141 | AG1-379 C | Adder | 13.83 MW | 11.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965142 | AG1-379 E | Adder | 6.33 MW | 5.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965551 | AG1-423 C O1 | Adder | 11.88 MW | 10.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965552 | AG1-423 E O1 | Adder | 7.92 MW | 6.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965661 | AG1-434 C O1 | Adder | 3.36 MW | 2.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965662 | AG1-434 E O1 | Adder | 15.75 MW | 13.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966091 | AG1-478 C | Adder | 1.7 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966092 | AG1-478 E | Adder | 0.43 MW | 0.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966431 | AG1-512 C | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966432 | AG1-512 E | Adder | 5.48 MW | 4.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966441 | AG1-513 C | Adder | 0.42 MW | 0.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966442 | AG1-513 E | Adder | 0.62 MW | 0.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 16.13 MW | 13.71 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 8.55 MW | 7.26 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295111 | SUBLETTE E | Adder | 2.12 MW | 1.8 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 14.63 MW | 12.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.55 MW | 1.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.48 MW | 2.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.48 MW | 2.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.76 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.23 MW | 1.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 15.72 MW | 13.36 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 73.34 MW | 62.34 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.74 MW | 0.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.49 MW | 0.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 2.84 MW | 2.42 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 13.32 MW | 11.32 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.65 MW | 3.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 17.81 MW | 15.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.15 MW | 1.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.94 MW | 5.9 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.63 MW | 3.93 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 8.26 MW | 7.03 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 2.76 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 6.4 MW | 5.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.52 MW | 2.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 7.56 MW | 6.43 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.75 MW | 0.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 4.63 MW | 3.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.67 MW | 5.67 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 3.29 MW | 2.79 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 10.42 MW | 8.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 5.12 MW | 4.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.93 MW | 5.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.43 MW | 2.92 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.12 MW | 2.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.08 MW | 1.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 10.09 MW | 8.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 6.73 MW | 5.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 9.7 MW | 8.24 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 6.46 MW | 5.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958911 | AF2-182 C | Adder | 14.64 MW | 12.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.81 MW | 4.94 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 2.91 MW | 2.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 11.63 MW | 9.88 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.75 MW | 6.59 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 4.9 MW | 4.17 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 14.07 MW | 11.96 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | Adder | 2.98 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | Adder | 1.99 MW | 1.69 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | Adder | 2.98 MW | 2.53 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 4.37 MW | 3.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 17.74 MW | 15.08 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 11.83 MW | 10.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 6.44 MW | 5.47 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 4.29 MW | 3.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.86 MW | 0.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.29 MW | 1.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.83 MW | 4.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 3.22 MW | 2.74 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.7 MW | 4.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.8 MW | 3.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274859 | EASYR;U1 E | Adder | 8.97 MW | 7.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274860 | EASYR;U2 E | Adder | 8.97 MW | 7.63 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 15.02 MW | 12.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.03 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276591 | L-013 2 | Adder | 2.99 MW | 2.54 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 12.75 MW | 10.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | Adder | 8.1 MW | 6.89 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | Adder | 15.73 MW | 13.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293799 | PILOT HIL;1E | Adder | 15.02 MW | 12.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 16.19 MW | 13.76 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 7.63 MW | 6.48 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.44 MW | 3.77 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930482 | AB1-089 CT | Adder | 29.82 MW | 25.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930483 | AB1-089 ST | Adder | 23.71 MW | 20.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930761 | AB1-122 CT1 | Adder | 56.18 MW | 47.75 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930771 | AB1-122 CT2 | Adder | 60.44 MW | 51.37 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.33 MW | 2.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 7.52 MW | 6.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.88 MW | 5.85 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C O1 | Adder | 6.65 MW | 5.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E O1 | Adder | 23.59 MW | 20.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938861 | AE1-114 C O1 | Adder | 3.2 MW | 2.72 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938862 | AE1-114 E O1 | Adder | 10.93 MW | 9.29 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 5.28 MW | 4.49 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 32.42 MW | 27.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 8.36 MW | 7.11 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 7.72 MW | 6.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939401 | AE1-172 C O1 | Adder | 4.19 MW | 3.56 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939402 | AE1-172 E O1 | Adder | 19.65 MW | 16.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.0 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 2.76 MW | 2.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.11 MW | 0.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 5.36 MW | 4.55 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.57 MW | 3.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 9.64 MW | 8.2 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 6.43 MW | 5.46 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 3.55 MW | 3.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 16.66 MW | 14.16 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.63 MW | 1.39 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.36 MW | 0.3 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.04 MW | 1.73 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.06 MW | 2.6 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.14 MW | 0.97 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.97 MW | 0.82 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 17.44 MW | 14.83 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 8.72 MW | 7.41 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 14.59 MW | 12.4 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 6.87 MW | 5.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | Adder | 28.05 MW | 23.84 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | Adder | 13.2 MW | 11.22 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.54 MW | 3.86 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.89 MW | 4.15 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 19.85 MW | 16.87 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274805 | UNIV PK N;1U | 50/50 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274807 | UNIV PK N;3U | 50/50 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274808 | UNIV PK N;4U | 50/50 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274810 | UNIV PK N;6U | 50/50 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274811 | UNIV PK N;7U | 50/50 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274815 | UNIV PK N;XU | 50/50 | 1.44 MW | 1.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274816 | UNIV PK N;YU | 50/50 | 1.45 MW | 1.45 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 252.18 MW | 214.35 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965792 | AG1-447 BAT | Adder | 9.42 MW | 8.01 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 54.23 MW | 54.23 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 15.64 MW | 15.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.7 MW | 1.7 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.09 MW | 3.09 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.64 MW | 10.64 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 10.91 MW | 10.91 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.57 MW | 0.57 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.1 MW | 1.1 MW |
| UNIV PK N;RP-AF2-359 TAP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.05 MW | 3.05 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274762 | LEE CO EC;3U | 50/50 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962012 | AG1-044 E | Adder | 0.07 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962691 | AG1-118 C O1 | Adder | 13.02 MW | 11.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962692 | AG1-118 E O1 | Adder | 8.68 MW | 7.38 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962701 | AG1-119 C | 50/50 | 45.34 MW | 45.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962702 | AG1-119 E | 50/50 | 30.23 MW | 30.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962711 | AG1-120 C O1 | Adder | 10.99 MW | 9.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962712 | AG1-120 E O1 | Adder | 7.32 MW | 6.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962781 | AG1-127 C | Adder | 5.23 MW | 4.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 962782 | AG1-127 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966821 | AG1-553 C O1 | Adder | 23.74 MW | 20.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 966822 | AG1-553 E O1 | Adder | 4.78 MW | 4.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965061 | AG1-371 | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965081 | AG1-373 | Adder | 0.67 MW | 0.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965551 | AG1-423 C O1 | 50/50 | 30.22 MW | 30.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965552 | AG1-423 E O1 | 50/50 | 20.15 MW | 20.15 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965661 | AG1-434 C O1 | Adder | 2.89 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965662 | AG1-434 E O1 | Adder | 13.52 MW | 11.5 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965931 | AG1-462 C O1 | Adder | 15.36 MW | 13.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 965932 | AG1-462 E O1 | Adder | 10.24 MW | 8.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290051 | GSG-6; E | Adder | 8.64 MW | 7.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295109 | WESTBROOK E | Adder | 4.63 MW | 3.93 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 295111 | SUBLETTE E | Adder | 3.06 MW | 2.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 919581 | AA2-030 C | Adder | 20.11 MW | 17.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 926431 | AC1-114 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927511 | AC1-113 1 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 927521 | AC1-113 2 | 50/50 | 0.42 MW | 0.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934432 | AD1-067 E | Adder | 0.46 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934971 | AD1-129 C | Adder | 1.28 MW | 1.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 934972 | AD1-129 E | Adder | 0.85 MW | 0.73 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937001 | AD2-134 C | Adder | 2.09 MW | 1.78 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937002 | AD2-134 E | Adder | 8.36 MW | 7.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937311 | AD2-172 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 937312 | AD2-172 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958911 | AF2-182 C | Adder | 29.17 MW | 24.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958912 | AF2-182 E | Adder | 19.45 MW | 16.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958921 | AF2-183 C | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 958922 | AF2-183 E | Adder | 7.78 MW | 6.61 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959081 | AF2-199 C | Adder | 4.01 MW | 3.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959082 | AF2-199 E | Adder | 2.0 MW | 1.7 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959091 | AF2-200 C O1 | Adder | 8.02 MW | 6.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959092 | AF2-200 E O1 | Adder | 5.34 MW | 4.54 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959101 | AF2-201 C O1 | 50/50 | 10.81 MW | 10.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 959102 | AF2-201 E O1 | 50/50 | 31.04 MW | 31.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960721 | AF2-363 C O1 | Adder | 7.64 MW | 6.49 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960722 | AF2-363 E O1 | Adder | 5.09 MW | 4.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960751 | AF2-366 C | Adder | 5.22 MW | 4.44 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 960752 | AF2-366 E | Adder | 3.48 MW | 2.96 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961011 | AF2-392 C O1 | Adder | 4.58 MW | 3.9 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961012 | AF2-392 E O1 | Adder | 21.45 MW | 18.23 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961021 | AF2-393 O1 | Adder | 7.81 MW | 6.64 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 961031 | AF2-394 O1 | Adder | 5.21 MW | 4.43 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274656 | BYRON ;1U | 50/50 | 50.14 MW | 50.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274657 | BYRON ;2U | 50/50 | 49.04 MW | 49.04 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274762 | LEE CO EC;3U | 50/50 | 2.56 MW | 2.56 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274764 | LEE CO EC;5U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274765 | LEE CO EC;6U | 50/50 | 2.57 MW | 2.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274822 | ROCKFORD ;11 | 50/50 | 4.66 MW | 4.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274823 | ROCKFORD ;21 | 50/50 | 4.79 MW | 4.79 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274824 | ROCKFORD ;12 | 50/50 | 4.62 MW | 4.62 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274856 | ECOGROVE ;U1 | 50/50 | 0.69 MW | 0.69 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274859 | EASYR;U1 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 274860 | EASYR;U2 E | Adder | 17.01 MW | 14.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276162 | X1-087 | 50/50 | 0.35 MW | 0.35 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276590 | R-018 | 50/50 | 0.27 MW | 0.27 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293516 | O-009 E1 | Adder | 8.85 MW | 7.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293517 | O-009 E2 | Adder | 4.5 MW | 3.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293518 | O-009 E3 | Adder | 4.95 MW | 4.21 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293715 | O-029 E | Adder | 9.47 MW | 8.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293716 | O-029 E | Adder | 5.19 MW | 4.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 293717 | O-029 E | Adder | 4.77 MW | 4.05 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 294763 | P-046 E | 50/50 | 16.82 MW | 16.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 916221 | Z1-073 E | Adder | 4.49 MW | 3.81 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930482 | AB1-089 CT | 50/50 | 77.19 MW | 77.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 930483 | AB1-089 ST | 50/50 | 61.37 MW | 61.37 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932881 | AC2-115 1 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932891 | AC2-115 2 | 50/50 | 0.83 MW | 0.83 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 932921 | AC2-116 | 50/50 | 0.29 MW | 0.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938861 | AE1-114 C O1 | 50/50 | 6.07 MW | 6.07 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 938862 | AE1-114 E O1 | 50/50 | 20.71 MW | 20.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939051 | AE1-134 1 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 939061 | AE1-134 2 | Adder | 1.56 MW | 1.33 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940501 | AE2-035 C | 50/50 | 4.42 MW | 4.42 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 940502 | AE2-035 E | 50/50 | 6.1 MW | 6.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941131 | AE2-107 C | Adder | 4.64 MW | 3.94 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 941132 | AE2-107 E | Adder | 3.09 MW | 2.63 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946151 | AF1-280 C O1 | Adder | 22.2 MW | 18.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946152 | AF1-280 E O1 | Adder | 10.21 MW | 8.68 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946161 | AF1-281 C O1 | Adder | 0.49 MW | 0.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946162 | AF1-281 E O1 | Adder | 2.76 MW | 2.34 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946321 | AF1-296 C O1 | Adder | 3.89 MW | 3.31 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946322 | AF1-296 E O1 | Adder | 18.2 MW | 15.47 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946501 | AF1-314 C | 50/50 | 7.82 MW | 7.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946502 | AF1-314 E | 50/50 | 36.76 MW | 36.76 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957471 | AF2-041 C | Adder | 12.02 MW | 10.22 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 957472 | AF2-041 E | Adder | 6.01 MW | 5.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 290108 | LEEDK;1U E | Adder | 17.17 MW | 14.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 276172 | Z1-108 BAT | Adder | 2.47 MW | 2.1 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 952431 | J760 | External Queue | 5.02 MW | 5.02 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953681 | J818 | External Queue | 12.71 MW | 12.71 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953901 | J850 | External Queue | 20.95 MW | 20.95 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 953922 | J855 E | External Queue | 6.8 MW | 6.8 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954001 | J864 | External Queue | 4.14 MW | 4.14 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954061 | J870 | External Queue | 16.57 MW | 16.57 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 954071 | J871 | External Queue | 8.29 MW | 8.29 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 955971 | J1084 | External Queue | 11.19 MW | 11.19 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990116 | J1214 | External Queue | 37.82 MW | 37.82 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990406 | J1304 | External Queue | 9.0 MW | 9.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990511 | J1326 | External Queue | 9.45 MW | 9.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990726 | J1377 | External Queue | 16.6 MW | 16.6 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | 990947 | J1432 E | External Queue | 18.11 MW | 18.11 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.06 MW | 0.06 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.53 MW | 0.53 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.39 MW | 0.39 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.77 MW | 45.77 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.41 MW | 9.41 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.45 MW | 0.45 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.09 MW | 0.09 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.46 MW | 2.46 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.17 MW | 0.17 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.59 MW | 9.59 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.87 MW | 2.87 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.18 MW | 0.18 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| CHERRY VA; B-GARDEN PR; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-7__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.37 MW | 0.37 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 22.86 MW | 19.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 15.24 MW | 12.96 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962701 | AG1-119 C | Adder | 22.59 MW | 19.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962702 | AG1-119 E | Adder | 15.06 MW | 12.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 8.91 MW | 7.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 5.94 MW | 5.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962781 | AG1-127 C | Adder | 7.22 MW | 6.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962782 | AG1-127 E | Adder | 4.8 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965061 | AG1-371 | Adder | 3.69 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965081 | AG1-373 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965141 | AG1-379 C | Adder | 17.86 MW | 15.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965142 | AG1-379 E | Adder | 8.18 MW | 6.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 15.06 MW | 12.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 10.04 MW | 8.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 20.0 MW | 17.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966092 | AG1-478 E | Adder | 0.51 MW | 0.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966442 | AG1-513 E | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.72 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 20.83 MW | 17.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 10.81 MW | 9.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 5.79 MW | 4.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 16.18 MW | 13.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.53 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 4.46 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 4.46 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 3.04 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.56 MW | 1.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 19.62 MW | 16.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 91.58 MW | 77.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 15.35 MW | 13.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 19.96 MW | 16.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 5.76 MW | 4.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.62 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 10.45 MW | 8.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937311 | AD2-172 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937312 | AD2-172 E | Adder | 3.5 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 8.26 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 8.27 MW | 7.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 9.76 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 5.34 MW | 4.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 8.46 MW | 7.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 4.17 MW | 3.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 13.11 MW | 11.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 6.44 MW | 5.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 8.72 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 4.31 MW | 3.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.64 MW | 2.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 11.16 MW | 9.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 7.44 MW | 6.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 11.18 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 7.45 MW | 6.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 7.38 MW | 6.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 3.69 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 14.77 MW | 12.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 9.85 MW | 8.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 6.21 MW | 5.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 17.83 MW | 15.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | 50/50 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | 50/50 | 4.52 MW | 4.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | 50/50 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | 50/50 | 4.52 MW | 4.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 5.5 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 22.49 MW | 19.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 15.0 MW | 12.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 4.08 MW | 3.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 7.2 MW | 6.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 4.8 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274655 | BRAIDWOOD;2U | 50/50 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274687 | WILL CNTY;4U | 50/50 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274751 | CRETE EC ;1U | 50/50 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274752 | CRETE EC ;2U | 50/50 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274753 | CRETE EC ;3U | 50/50 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274754 | CRETE EC ;4U | 50/50 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 16.83 MW | 14.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.58 MW | 2.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276591 | L-013 2 | Adder | 3.79 MW | 3.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 16.23 MW | 13.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | 50/50 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | 50/50 | 23.86 MW | 23.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293799 | PILOT HIL;1E | Adder | 16.83 MW | 14.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 20.62 MW | 17.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 9.67 MW | 8.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 5.61 MW | 4.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930482 | AB1-089 CT | Adder | 37.81 MW | 32.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930483 | AB1-089 ST | Adder | 30.06 MW | 25.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 70.99 MW | 60.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 78.74 MW | 66.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 9.72 MW | 8.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 8.88 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 30.46 MW | 25.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 37.38 MW | 31.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 10.5 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 9.7 MW | 8.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940501 | AE2-035 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940502 | AE2-035 E | Adder | 3.5 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 6.77 MW | 5.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 4.52 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 12.12 MW | 10.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 8.08 MW | 6.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946501 | AF1-314 C | Adder | 4.5 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 21.12 MW | 17.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.45 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.89 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 1.3 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 22.16 MW | 18.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 11.08 MW | 9.42 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 8.71 MW | 7.4 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | 50/50 | 40.18 MW | 40.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | 50/50 | 18.91 MW | 18.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 6.37 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 25.08 MW | 21.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 318.72 MW | 270.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.34 MW | 2.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.07 MW | 62.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.91 MW | 18.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.19 MW | 2.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.43 MW | 13.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 14.05 MW | 14.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.88 MW | 3.88 MW |
| Details for CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962691 | AG1-118 C O1 | Adder | 22.86 MW | 19.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962692 | AG1-118 E O1 | Adder | 15.24 MW | 12.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962701 | AG1-119 C | Adder | 22.58 MW | 19.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962702 | AG1-119 E | Adder | 15.06 MW | 12.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962711 | AG1-120 C O1 | Adder | 8.91 MW | 7.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962712 | AG1-120 E O1 | Adder | 5.94 MW | 5.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962781 | AG1-127 C | Adder | 7.22 MW | 6.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962782 | AG1-127 E | Adder | 4.8 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965061 | AG1-371 | Adder | 3.69 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965081 | AG1-373 | Adder | 1.23 MW | 1.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965141 | AG1-379 C | Adder | 17.86 MW | 15.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965142 | AG1-379 E | Adder | 8.17 MW | 6.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965551 | AG1-423 C O1 | Adder | 15.06 MW | 12.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965552 | AG1-423 E O1 | Adder | 10.04 MW | 8.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965661 | AG1-434 C O1 | Adder | 4.27 MW | 3.63 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965662 | AG1-434 E O1 | Adder | 20.0 MW | 17.0 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966091 | AG1-478 C | Adder | 2.03 MW | 1.73 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966092 | AG1-478 E | Adder | 0.51 MW | 0.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966441 | AG1-513 C | Adder | 0.52 MW | 0.45 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966442 | AG1-513 E | Adder | 0.79 MW | 0.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 272364 | ESS H440N ;R | Adder | 2.72 MW | 2.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 20.83 MW | 17.7 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 10.81 MW | 9.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 5.79 MW | 4.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 16.18 MW | 13.75 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 2.53 MW | 2.15 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.96 MW | 1.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 4.46 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 4.46 MW | 3.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.9 MW | 1.62 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 3.04 MW | 2.58 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.96 MW | 0.81 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.56 MW | 1.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.57 MW | 0.48 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 19.63 MW | 16.68 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 91.59 MW | 77.85 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.93 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.62 MW | 0.53 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 3.28 MW | 2.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 15.35 MW | 13.04 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 19.96 MW | 16.97 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 8.63 MW | 7.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 5.76 MW | 4.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.62 MW | 2.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 10.45 MW | 8.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937311 | AD2-172 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937312 | AD2-172 E | Adder | 3.5 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 8.26 MW | 7.02 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 8.27 MW | 7.03 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 3.25 MW | 2.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 9.76 MW | 8.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.87 MW | 0.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 5.34 MW | 4.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 8.46 MW | 7.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 4.17 MW | 3.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 13.11 MW | 11.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 6.44 MW | 5.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 8.72 MW | 7.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 4.31 MW | 3.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.95 MW | 3.36 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.64 MW | 2.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 11.16 MW | 9.49 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 7.44 MW | 6.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 11.18 MW | 9.5 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 7.45 MW | 6.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 7.38 MW | 6.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 3.69 MW | 3.14 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 14.77 MW | 12.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 9.85 MW | 8.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 6.21 MW | 5.28 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 17.83 MW | 15.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | 50/50 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | 50/50 | 4.52 MW | 4.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | 50/50 | 3.01 MW | 3.01 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | 50/50 | 4.52 MW | 4.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 5.5 MW | 4.67 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 22.49 MW | 19.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 14.99 MW | 12.74 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 7.21 MW | 6.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 1.49 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 6.11 MW | 5.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 4.07 MW | 3.46 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 7.2 MW | 6.12 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 4.8 MW | 4.08 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.37 MW | 29.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274655 | BRAIDWOOD;2U | 50/50 | 28.57 MW | 28.57 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274687 | WILL CNTY;4U | 50/50 | 12.33 MW | 12.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274704 | KENDALL ;1C | 50/50 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274705 | KENDALL ;1S | 50/50 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274706 | KENDALL ;2C | 50/50 | 4.37 MW | 4.37 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274707 | KENDALL ;2S | 50/50 | 2.92 MW | 2.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274751 | CRETE EC ;1U | 50/50 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274752 | CRETE EC ;2U | 50/50 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274753 | CRETE EC ;3U | 50/50 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274754 | CRETE EC ;4U | 50/50 | 6.38 MW | 6.38 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274861 | TOP CROP ;1U | 50/50 | 0.47 MW | 0.47 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274862 | TOP CROP ;2U | 50/50 | 0.9 MW | 0.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 16.83 MW | 14.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.58 MW | 2.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276591 | L-013 2 | Adder | 3.78 MW | 3.22 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 16.23 MW | 13.8 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | 50/50 | 12.29 MW | 12.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | 50/50 | 23.86 MW | 23.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293799 | PILOT HIL;1E | Adder | 16.83 MW | 14.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 20.62 MW | 17.52 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 9.66 MW | 8.21 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 5.61 MW | 4.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930482 | AB1-089 CT | Adder | 37.8 MW | 32.13 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930483 | AB1-089 ST | Adder | 30.05 MW | 25.55 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930761 | AB1-122 CT1 | Adder | 70.98 MW | 60.33 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930771 | AB1-122 CT2 | Adder | 78.74 MW | 66.92 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 9.72 MW | 8.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 8.88 MW | 7.54 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C O1 | Adder | 8.59 MW | 7.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E O1 | Adder | 30.46 MW | 25.89 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 6.08 MW | 5.17 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 37.37 MW | 31.77 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 10.5 MW | 8.93 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 9.7 MW | 8.24 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940501 | AE2-035 C | Adder | 2.54 MW | 2.16 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940502 | AE2-035 E | Adder | 3.5 MW | 2.98 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 6.77 MW | 5.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 4.51 MW | 3.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 12.12 MW | 10.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 8.08 MW | 6.87 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946501 | AF1-314 C | Adder | 4.49 MW | 3.82 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 21.12 MW | 17.95 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 2.07 MW | 1.76 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.45 MW | 0.39 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 2.47 MW | 2.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.59 MW | 2.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.88 MW | 3.3 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.52 MW | 1.29 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 1.3 MW | 1.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 22.15 MW | 18.83 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 11.08 MW | 9.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | 50/50 | 40.18 MW | 40.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | 50/50 | 18.91 MW | 18.91 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 5.74 MW | 4.88 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 6.37 MW | 5.41 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 25.08 MW | 21.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 318.63 MW | 270.84 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.86 MW | 0.86 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.34 MW | 2.34 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.07 MW | 62.07 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.9 MW | 18.9 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.19 MW | 2.19 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.26 MW | 0.26 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.59 MW | 0.59 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.78 MW | 3.78 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.43 MW | 13.43 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.18 MW | 1.18 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 14.05 MW | 14.05 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.79 MW | 0.79 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| CRETE EC ;BP-17STJOHN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.88 MW | 3.88 MW |
| Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961651 | AG1-005 C O1 | Adder | 12.71 MW | 10.8 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961652 | AG1-005 E O1 | Adder | 8.47 MW | 7.2 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962012 | AG1-044 E | Adder | 0.06 MW | 0.05 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 17.56 MW | 14.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 11.71 MW | 9.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962701 | AG1-119 C | Adder | 19.08 MW | 16.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962702 | AG1-119 E | Adder | 12.72 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 7.14 MW | 6.07 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.76 MW | 4.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962721 | AG1-121 C O1 | Adder | 4.61 MW | 3.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962722 | AG1-121 E O1 | Adder | 21.58 MW | 18.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962781 | AG1-127 C | Adder | 5.57 MW | 4.73 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 962782 | AG1-127 E | Adder | 3.71 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966821 | AG1-553 C O1 | Adder | 22.49 MW | 19.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966822 | AG1-553 E O1 | Adder | 4.53 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965061 | AG1-371 | Adder | 3.13 MW | 2.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965081 | AG1-373 | Adder | 1.04 MW | 0.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965141 | AG1-379 C | Adder | 22.42 MW | 19.06 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965142 | AG1-379 E | Adder | 10.26 MW | 8.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 12.72 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 8.48 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.64 MW | 3.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 17.03 MW | 14.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965671 | AG1-435 C O1 | Adder | 3.19 MW | 2.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965672 | AG1-435 E O1 | Adder | 14.96 MW | 12.71 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965931 | AG1-462 C O1 | Adder | 14.56 MW | 12.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 965932 | AG1-462 E O1 | Adder | 9.7 MW | 8.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966441 | AG1-513 C | Adder | 0.4 MW | 0.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 966442 | AG1-513 E | Adder | 0.6 MW | 0.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.15 MW | 1.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290021 | O50 E | Adder | 26.14 MW | 22.22 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290051 | GSG-6; E | Adder | 8.56 MW | 7.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.58 MW | 3.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 295111 | SUBLETTE E | Adder | 2.27 MW | 1.93 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 919581 | AA2-030 C | Adder | 15.68 MW | 13.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 920272 | AA2-123 E | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.58 MW | 1.34 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927093 | AC1-204 GEN2 | 50/50 | 18.42 MW | 18.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927202 | AC1-214 E O1 | Adder | 5.46 MW | 4.64 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927451 | AC1-142A 1 | Adder | 5.49 MW | 4.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 927461 | AC1-142A 2 | Adder | 5.52 MW | 4.69 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933911 | AD1-013 C | Adder | 1.5 MW | 1.28 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933912 | AD1-013 E | Adder | 2.4 MW | 2.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933931 | AD1-016 C | Adder | 0.82 MW | 0.7 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 933932 | AD1-016 E | Adder | 1.34 MW | 1.14 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934051 | AD1-031 C O1 | Adder | 2.5 MW | 2.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934052 | AD1-031 E O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934432 | AD1-067 E | Adder | 0.45 MW | 0.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934971 | AD1-129 C | Adder | 0.8 MW | 0.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934972 | AD1-129 E | Adder | 0.53 MW | 0.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.39 MW | 2.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.17 MW | 9.49 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 7.28 MW | 6.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.86 MW | 4.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937001 | AD2-134 C | Adder | 2.07 MW | 1.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937002 | AD2-134 E | Adder | 8.28 MW | 7.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937311 | AD2-172 C | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937312 | AD2-172 E | Adder | 3.0 MW | 2.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937401 | AD2-194 1 | Adder | 11.49 MW | 9.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 937411 | AD2-194 2 | 50/50 | 11.63 MW | 11.63 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 4.08 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 12.26 MW | 10.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.89 MW | 3.3 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942991 | AE2-321 C | Adder | 7.24 MW | 6.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 942992 | AE2-321 E | Adder | 3.57 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943121 | AE2-341 C | Adder | 8.48 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943122 | AE2-341 E | Adder | 4.16 MW | 3.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 5.64 MW | 4.79 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 2.79 MW | 2.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943801 | AF1-048 C | Adder | 3.39 MW | 2.88 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 943802 | AF1-048 E | Adder | 2.26 MW | 1.92 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946542 | AF1-318 E O1 | Adder | 21.19 MW | 18.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958491 | AF2-143 C | Adder | 8.13 MW | 6.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958492 | AF2-143 E | Adder | 5.42 MW | 4.61 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958911 | AF2-182 C | Adder | 18.2 MW | 15.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958912 | AF2-182 E | Adder | 12.13 MW | 10.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958921 | AF2-183 C | Adder | 3.24 MW | 2.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958922 | AF2-183 E | Adder | 4.85 MW | 4.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959081 | AF2-199 C | Adder | 6.27 MW | 5.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959082 | AF2-199 E | Adder | 3.13 MW | 2.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 12.54 MW | 10.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 8.36 MW | 7.11 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 5.31 MW | 4.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 15.24 MW | 12.96 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959351 | AF2-226 C | 50/50 | 7.21 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 959352 | AF2-226 E | 50/50 | 10.81 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960281 | AF2-319 C | 50/50 | 7.21 MW | 7.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960282 | AF2-319 E | 50/50 | 10.81 MW | 10.81 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960381 | AF2-329 | Adder | 3.56 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960581 | AF2-349 C | Adder | 19.33 MW | 16.43 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960582 | AF2-349 E | Adder | 12.89 MW | 10.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.9 MW | 4.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 3.27 MW | 2.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960751 | AF2-366 C | Adder | 5.55 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 960752 | AF2-366 E | Adder | 3.7 MW | 3.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961011 | AF2-392 C O1 | Adder | 3.5 MW | 2.98 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961012 | AF2-392 E O1 | Adder | 16.4 MW | 13.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961021 | AF2-393 O1 | Adder | 5.97 MW | 5.08 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 961031 | AF2-394 O1 | Adder | 3.98 MW | 3.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 6.46 MW | 6.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 4.32 MW | 4.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 6.46 MW | 6.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 4.32 MW | 4.32 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274728 | ELWOOD EC;5P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274730 | ELWOOD EC;6P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274732 | ELWOOD EC;7P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274734 | ELWOOD EC;8P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274736 | ELWOOD EC;9P | 50/50 | 4.95 MW | 4.95 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274859 | EASYR;U1 E | Adder | 9.76 MW | 8.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274860 | EASYR;U2 E | Adder | 9.76 MW | 8.29 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 1.13 MW | 1.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 2.15 MW | 2.15 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 276170 | Z1-108 E | Adder | 2.22 MW | 1.89 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 276591 | L-013 2 | Adder | 3.05 MW | 2.59 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293516 | O-009 E1 | Adder | 8.05 MW | 6.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293517 | O-009 E2 | Adder | 4.09 MW | 3.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293518 | O-009 E3 | Adder | 4.5 MW | 3.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293644 | O22 E1 | 50/50 | 29.41 MW | 29.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293645 | O22 E2 | 50/50 | 57.09 MW | 57.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293715 | O-029 E | Adder | 8.6 MW | 7.31 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293716 | O-029 E | Adder | 4.72 MW | 4.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293717 | O-029 E | Adder | 4.33 MW | 3.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 293771 | O-035 E | Adder | 5.36 MW | 4.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294401 | BSHIL;1U E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294410 | BSHIL;2U E | Adder | 7.51 MW | 6.38 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 294763 | P-046 E | Adder | 8.26 MW | 7.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 916211 | Z1-072 E | Adder | 4.05 MW | 3.44 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 916221 | Z1-073 E | Adder | 4.45 MW | 3.78 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 925581 | AC1-033 C | Adder | 1.23 MW | 1.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 925582 | AC1-033 E | Adder | 8.23 MW | 7.0 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930482 | AB1-089 CT | Adder | 32.18 MW | 27.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930483 | AB1-089 ST | Adder | 25.58 MW | 21.75 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 71.38 MW | 60.68 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 103.64 MW | 88.09 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938511 | AE1-070 1 | 50/50 | 13.67 MW | 13.67 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938521 | AE1-070 2 | Adder | 12.35 MW | 10.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 10.78 MW | 9.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 38.24 MW | 32.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938861 | AE1-114 C O1 | Adder | 3.46 MW | 2.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 938862 | AE1-114 E O1 | Adder | 11.81 MW | 10.04 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939051 | AE1-134 1 | Adder | 1.22 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939061 | AE1-134 2 | Adder | 1.22 MW | 1.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.43 MW | 3.76 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 27.2 MW | 23.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 940501 | AE2-035 C | Adder | 2.17 MW | 1.84 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 940502 | AE2-035 E | Adder | 3.0 MW | 2.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 941131 | AE2-107 C | Adder | 5.24 MW | 4.45 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 941132 | AE2-107 E | Adder | 3.49 MW | 2.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946151 | AF1-280 C O1 | Adder | 13.85 MW | 11.77 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946152 | AF1-280 E O1 | Adder | 6.37 MW | 5.41 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946161 | AF1-281 C O1 | Adder | 0.3 MW | 0.26 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946162 | AF1-281 E O1 | Adder | 1.72 MW | 1.46 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946321 | AF1-296 C O1 | Adder | 3.56 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946322 | AF1-296 E O1 | Adder | 16.69 MW | 14.19 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946501 | AF1-314 C | Adder | 3.84 MW | 3.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946502 | AF1-314 E | Adder | 18.05 MW | 15.35 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946541 | AF1-318 C O1 | Adder | 4.53 MW | 3.85 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946661 | AF1-330 C | Adder | 1.78 MW | 1.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946662 | AF1-330 E | Adder | 0.39 MW | 0.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 946671 | AF1-331 | Adder | 1.95 MW | 1.66 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957331 | AF2-027 C | Adder | 2.37 MW | 2.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957332 | AF2-027 E | Adder | 3.55 MW | 3.02 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957401 | AF2-034 C | 50/50 | 2.25 MW | 2.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.91 MW | 1.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957471 | AF2-041 C | Adder | 18.81 MW | 15.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957472 | AF2-041 E | Adder | 9.4 MW | 7.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957751 | AF2-069 C | Adder | 0.2 MW | 0.17 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957752 | AF2-069 E | Adder | 0.64 MW | 0.55 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957761 | AF2-070 C | Adder | 0.28 MW | 0.24 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 957762 | AF2-070 E | Adder | 1.36 MW | 1.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958341 | AF2-128 C O1 | Adder | 1.19 MW | 1.01 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958342 | AF2-128 E O1 | Adder | 5.55 MW | 4.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 990901 | L-005 E | Adder | 11.75 MW | 9.99 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.77 MW | 4.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 934111 | AD2-000 2 | Adder | 8.38 MW | 7.12 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 290108 | LEEDK;1U E | Adder | 19.41 MW | 16.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 958023 | AF2-096 BAT | Adder | 7.3 MW | 6.21 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 953151 | J831 | External Queue | 3.03 MW | 3.03 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 953491 | J947 | External Queue | 15.9 MW | 15.9 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954141 | J878 | External Queue | 15.94 MW | 15.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954981 | J974 C | External Queue | 2.94 MW | 2.94 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 954982 | J974 E | External Queue | 15.91 MW | 15.91 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | 991321 | J1778 | External Queue | 7.97 MW | 7.97 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.42 MW | 0.42 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.4 MW | 1.4 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.13 MW | 0.13 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 57.54 MW | 57.54 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.5 MW | 16.5 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.27 MW | 0.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.51 MW | 3.51 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.27 MW | 0.27 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 11.83 MW | 11.83 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.53 MW | 8.53 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_076-45-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.5 MW | 3.5 MW |
| Details for PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ;3M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961651 | AG1-005 C O1 | Adder | 10.22 MW | 8.69 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961652 | AG1-005 E O1 | Adder | 6.81 MW | 5.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962012 | AG1-044 E | Adder | 0.05 MW | 0.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962691 | AG1-118 C O1 | 50/50 | 21.43 MW | 21.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962692 | AG1-118 E O1 | 50/50 | 14.29 MW | 14.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962701 | AG1-119 C | Adder | 16.49 MW | 14.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962702 | AG1-119 E | Adder | 10.99 MW | 9.34 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962711 | AG1-120 C O1 | 50/50 | 7.6 MW | 7.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962712 | AG1-120 E O1 | 50/50 | 5.07 MW | 5.07 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962721 | AG1-121 C O1 | Adder | 3.55 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962722 | AG1-121 E O1 | Adder | 16.61 MW | 14.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962781 | AG1-127 C | 50/50 | 6.7 MW | 6.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 962782 | AG1-127 E | 50/50 | 4.46 MW | 4.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966821 | AG1-553 C O1 | Adder | 17.36 MW | 14.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966822 | AG1-553 E O1 | Adder | 3.5 MW | 2.97 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965061 | AG1-371 | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965081 | AG1-373 | 50/50 | 1.03 MW | 1.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965551 | AG1-423 C O1 | Adder | 11.0 MW | 9.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965552 | AG1-423 E O1 | Adder | 7.33 MW | 6.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965661 | AG1-434 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965662 | AG1-434 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965671 | AG1-435 C O1 | Adder | 2.38 MW | 2.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965672 | AG1-435 E O1 | Adder | 11.13 MW | 9.46 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965931 | AG1-462 C O1 | Adder | 11.24 MW | 9.55 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 965932 | AG1-462 E O1 | Adder | 7.49 MW | 6.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966091 | AG1-478 C | Adder | 1.03 MW | 0.87 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966092 | AG1-478 E | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 272364 | ESS H440N ;R | 50/50 | 2.39 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290051 | GSG-6; E | 50/50 | 9.48 MW | 9.48 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295108 | WESTBROOK C | 50/50 | 0.13 MW | 0.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295109 | WESTBROOK E | 50/50 | 5.08 MW | 5.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 295111 | SUBLETTE E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 919581 | AA2-030 C | Adder | 13.36 MW | 11.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 920272 | AA2-123 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926331 | AC1-110 1 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926341 | AC1-110 2 | 50/50 | 1.73 MW | 1.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 927202 | AC1-214 E O1 | Adder | 4.04 MW | 3.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933911 | AD1-013 C | 50/50 | 1.68 MW | 1.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933912 | AD1-013 E | 50/50 | 2.68 MW | 2.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 933932 | AD1-016 E | Adder | 1.11 MW | 0.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934051 | AD1-031 C O1 | Adder | 1.75 MW | 1.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934052 | AD1-031 E O1 | Adder | 2.86 MW | 2.43 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934431 | AD1-067 C | 50/50 | 0.02 MW | 0.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934432 | AD1-067 E | 50/50 | 0.5 MW | 0.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934972 | AD1-129 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936372 | AD2-047 E O1 | Adder | 5.89 MW | 5.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.71 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937001 | AD2-134 C | 50/50 | 2.29 MW | 2.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937002 | AD2-134 E | 50/50 | 9.17 MW | 9.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937311 | AD2-172 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 937312 | AD2-172 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942991 | AE2-321 C | Adder | 6.02 MW | 5.11 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 942992 | AE2-321 E | Adder | 2.96 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943121 | AE2-341 C | 50/50 | 16.01 MW | 16.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943122 | AE2-341 E | 50/50 | 7.86 MW | 7.86 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943591 | AF1-030 C O1 | 50/50 | 10.65 MW | 10.65 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943592 | AF1-030 E O1 | 50/50 | 5.27 MW | 5.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943801 | AF1-048 C | Adder | 2.81 MW | 2.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 943802 | AF1-048 E | Adder | 1.87 MW | 1.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946542 | AF1-318 E O1 | Adder | 16.79 MW | 14.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958911 | AF2-182 C | Adder | 15.46 MW | 13.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958912 | AF2-182 E | Adder | 10.3 MW | 8.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958921 | AF2-183 C | Adder | 2.75 MW | 2.33 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958922 | AF2-183 E | Adder | 4.12 MW | 3.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959081 | AF2-199 C | 50/50 | 6.16 MW | 6.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959082 | AF2-199 E | 50/50 | 3.08 MW | 3.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959091 | AF2-200 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959092 | AF2-200 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959101 | AF2-201 C O1 | Adder | 4.49 MW | 3.82 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 959102 | AF2-201 E O1 | Adder | 12.9 MW | 10.96 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960381 | AF2-329 | 50/50 | 6.72 MW | 6.72 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960581 | AF2-349 C | Adder | 15.91 MW | 13.53 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960582 | AF2-349 E | Adder | 10.61 MW | 9.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960721 | AF2-363 C O1 | 50/50 | 5.2 MW | 5.2 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960722 | AF2-363 E O1 | 50/50 | 3.47 MW | 3.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960751 | AF2-366 C | 50/50 | 6.68 MW | 6.68 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 960752 | AF2-366 E | 50/50 | 4.45 MW | 4.45 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961011 | AF2-392 C O1 | Adder | 3.03 MW | 2.57 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961012 | AF2-392 E O1 | Adder | 14.17 MW | 12.04 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961021 | AF2-393 O1 | Adder | 5.16 MW | 4.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 961031 | AF2-394 O1 | Adder | 3.44 MW | 2.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274660 | LASCO STA;1U | 50/50 | 30.7 MW | 30.7 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274661 | LASCO STA;2U | 50/50 | 30.84 MW | 30.84 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274738 | AURORA EC;3P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274740 | AURORA EC;4P | 50/50 | 2.98 MW | 2.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274847 | GR RIDGE ;BU | 50/50 | 0.63 MW | 0.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274855 | GSG-6 ;RU | 50/50 | 0.4 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274859 | EASYR;U1 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274860 | EASYR;U2 E | Adder | 8.28 MW | 7.03 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274871 | GR RIDGE ;2U | 50/50 | 0.23 MW | 0.23 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276170 | Z1-108 E | Adder | 1.79 MW | 1.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276173 | Z2-081 | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 276591 | L-013 2 | 50/50 | 2.91 MW | 2.91 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293061 | N-015 E | 50/50 | 16.25 MW | 16.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293516 | O-009 E1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293517 | O-009 E2 | Adder | 3.35 MW | 2.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293518 | O-009 E3 | Adder | 3.69 MW | 3.14 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293715 | O-029 E | Adder | 7.06 MW | 6.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293716 | O-029 E | Adder | 3.87 MW | 3.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293717 | O-029 E | Adder | 3.56 MW | 3.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 293771 | O-035 E | Adder | 3.96 MW | 3.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294392 | P-010 E | 50/50 | 20.63 MW | 20.63 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294401 | BSHIL;1U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294410 | BSHIL;2U E | Adder | 5.28 MW | 4.49 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 294763 | P-046 E | Adder | 6.99 MW | 5.94 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915011 | Y3-013 1 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915021 | Y3-013 2 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 915031 | Y3-013 3 | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916211 | Z1-072 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 916221 | Z1-073 E | 50/50 | 4.92 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925581 | AC1-033 C | Adder | 0.86 MW | 0.73 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 925582 | AC1-033 E | Adder | 5.79 MW | 4.92 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930482 | AB1-089 CT | Adder | 27.37 MW | 23.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930483 | AB1-089 ST | Adder | 21.76 MW | 18.5 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 930771 | AB1-122 CT2 | Adder | 38.35 MW | 32.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938861 | AE1-114 C O1 | Adder | 2.97 MW | 2.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 938862 | AE1-114 E O1 | Adder | 10.12 MW | 8.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939051 | AE1-134 1 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939061 | AE1-134 2 | Adder | 1.04 MW | 0.88 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939351 | AE1-166 C O1 | Adder | 5.12 MW | 4.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 939352 | AE1-166 E O1 | Adder | 4.72 MW | 4.01 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940501 | AE2-035 C | Adder | 1.84 MW | 1.56 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940502 | AE2-035 E | Adder | 2.53 MW | 2.15 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 940752 | AE2-062 E | Adder | 0.07 MW | 0.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941131 | AE2-107 C | 50/50 | 6.25 MW | 6.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941132 | AE2-107 E | 50/50 | 4.16 MW | 4.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941551 | AE2-152 C O1 | Adder | 5.9 MW | 5.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 941552 | AE2-152 E O1 | Adder | 3.94 MW | 3.35 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946151 | AF1-280 C O1 | Adder | 11.76 MW | 10.0 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946152 | AF1-280 E O1 | Adder | 5.41 MW | 4.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946161 | AF1-281 C O1 | Adder | 0.26 MW | 0.22 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946162 | AF1-281 E O1 | Adder | 1.46 MW | 1.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946321 | AF1-296 C O1 | Adder | 2.8 MW | 2.38 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946322 | AF1-296 E O1 | Adder | 13.13 MW | 11.16 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946501 | AF1-314 C | Adder | 3.25 MW | 2.76 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946502 | AF1-314 E | Adder | 15.28 MW | 12.98 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946541 | AF1-318 C O1 | Adder | 3.59 MW | 3.05 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946661 | AF1-330 C | Adder | 1.47 MW | 1.25 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.27 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 946671 | AF1-331 | 50/50 | 2.18 MW | 2.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957331 | AF2-027 C | Adder | 1.61 MW | 1.37 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957332 | AF2-027 E | Adder | 2.42 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957401 | AF2-034 C | Adder | 0.7 MW | 0.59 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957402 | AF2-034 E | Adder | 0.6 MW | 0.51 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957471 | AF2-041 C | 50/50 | 18.47 MW | 18.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957472 | AF2-041 E | 50/50 | 9.24 MW | 9.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957752 | AF2-069 E | Adder | 0.47 MW | 0.4 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 957762 | AF2-070 E | Adder | 1.01 MW | 0.85 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958021 | AF2-096 C | Adder | 21.16 MW | 17.99 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958022 | AF2-096 E | Adder | 9.96 MW | 8.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958341 | AF2-128 C O1 | Adder | 0.95 MW | 0.81 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 958342 | AF2-128 E O1 | Adder | 4.46 MW | 3.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 934111 | AD2-000 2 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274872 | LEE DEKAL;1U | 50/50 | 0.79 MW | 0.79 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 290108 | LEEDK;1U E | 50/50 | 23.13 MW | 23.13 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 274850 | MENDOTA H;RU | 50/50 | 0.24 MW | 0.24 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | 945351 | AF1-200 FTIR | 50/50 | 582.02 MW | 582.02 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.39 MW | 1.39 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.19 MW | 0.19 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.26 MW | 47.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 9.6 MW | 9.6 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.26 MW | 1.26 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.17 MW | 0.17 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.06 MW | 2.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.18 MW | 0.18 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.29 MW | 8.29 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.67 MW | 0.67 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.06 MW | 8.06 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.47 MW | 0.47 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.61 MW | 0.61 MW |
| PLANO ; B-PLANO ;3M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT5-6__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.46 MW | 2.46 MW |
| Details for PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ;4M-PLANO ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961651 | AG1-005 C O1 | Adder | 9.9 MW | 8.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961652 | AG1-005 E O1 | Adder | 6.6 MW | 5.61 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962012 | AG1-044 E | Adder | 0.04 MW | 0.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962691 | AG1-118 C O1 | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962692 | AG1-118 E O1 | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962701 | AG1-119 C | Adder | 15.25 MW | 12.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962702 | AG1-119 E | Adder | 10.17 MW | 8.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962711 | AG1-120 C O1 | Adder | 5.69 MW | 4.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962712 | AG1-120 E O1 | Adder | 3.79 MW | 3.22 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962721 | AG1-121 C O1 | Adder | 3.38 MW | 2.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962722 | AG1-121 E O1 | Adder | 15.82 MW | 13.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962781 | AG1-127 C | Adder | 4.6 MW | 3.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 962782 | AG1-127 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966821 | AG1-553 C O1 | Adder | 14.68 MW | 12.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966822 | AG1-553 E O1 | Adder | 2.96 MW | 2.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965061 | AG1-371 | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965081 | AG1-373 | Adder | 0.74 MW | 0.63 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965551 | AG1-423 C O1 | Adder | 10.18 MW | 8.65 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965552 | AG1-423 E O1 | Adder | 6.78 MW | 5.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965661 | AG1-434 C O1 | Adder | 2.56 MW | 2.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965662 | AG1-434 E O1 | Adder | 12.01 MW | 10.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965671 | AG1-435 C O1 | Adder | 2.24 MW | 1.91 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965672 | AG1-435 E O1 | Adder | 10.49 MW | 8.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965931 | AG1-462 C O1 | Adder | 9.5 MW | 8.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 965932 | AG1-462 E O1 | Adder | 6.33 MW | 5.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966091 | AG1-478 C | Adder | 0.98 MW | 0.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966092 | AG1-478 E | Adder | 0.25 MW | 0.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966441 | AG1-513 C | Adder | 0.43 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 966442 | AG1-513 E | Adder | 0.64 MW | 0.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 272364 | ESS H440N ;R | Adder | 1.7 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290051 | GSG-6; E | Adder | 6.76 MW | 5.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295109 | WESTBROOK E | Adder | 3.62 MW | 3.08 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 295111 | SUBLETTE E | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 919581 | AA2-030 C | Adder | 10.91 MW | 9.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 920272 | AA2-123 E | Adder | 1.66 MW | 1.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926311 | AC1-109 1 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926321 | AC1-109 2 | 50/50 | 0.31 MW | 0.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 926822 | AC1-168 E O1 | Adder | 5.34 MW | 4.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 927202 | AC1-214 E O1 | Adder | 3.81 MW | 3.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933911 | AD1-013 C | Adder | 1.19 MW | 1.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933912 | AD1-013 E | Adder | 1.9 MW | 1.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933931 | AD1-016 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933932 | AD1-016 E | Adder | 1.02 MW | 0.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934051 | AD1-031 C O1 | Adder | 1.62 MW | 1.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934052 | AD1-031 E O1 | Adder | 2.65 MW | 2.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934432 | AD1-067 E | Adder | 0.36 MW | 0.3 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936371 | AD2-047 C O1 | Adder | 2.19 MW | 1.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936372 | AD2-047 E O1 | Adder | 10.69 MW | 9.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936461 | AD2-060 | Adder | 1.29 MW | 1.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936511 | AD2-066 C O1 | Adder | 4.54 MW | 3.86 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 936512 | AD2-066 E O1 | Adder | 3.02 MW | 2.57 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937001 | AD2-134 C | Adder | 1.64 MW | 1.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937002 | AD2-134 E | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937311 | AD2-172 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 937312 | AD2-172 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942991 | AE2-321 C | Adder | 5.54 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 942992 | AE2-321 E | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943121 | AE2-341 C | Adder | 8.38 MW | 7.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943122 | AE2-341 E | Adder | 4.11 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943591 | AF1-030 C O1 | Adder | 5.57 MW | 4.74 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943592 | AF1-030 E O1 | Adder | 2.76 MW | 2.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943801 | AF1-048 C | Adder | 2.59 MW | 2.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 943802 | AF1-048 E | Adder | 1.73 MW | 1.47 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946542 | AF1-318 E O1 | Adder | 16.19 MW | 13.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958911 | AF2-182 C | Adder | 12.94 MW | 11.0 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958912 | AF2-182 E | Adder | 8.63 MW | 7.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958921 | AF2-183 C | Adder | 2.3 MW | 1.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958922 | AF2-183 E | Adder | 3.45 MW | 2.93 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959081 | AF2-199 C | Adder | 4.44 MW | 3.77 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959082 | AF2-199 E | Adder | 2.22 MW | 1.89 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959091 | AF2-200 C O1 | Adder | 8.88 MW | 7.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959092 | AF2-200 E O1 | Adder | 5.92 MW | 5.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959101 | AF2-201 C O1 | Adder | 3.9 MW | 3.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 959102 | AF2-201 E O1 | Adder | 11.2 MW | 9.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960381 | AF2-329 | Adder | 3.52 MW | 2.99 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960581 | AF2-349 C | Adder | 14.58 MW | 12.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960582 | AF2-349 E | Adder | 9.72 MW | 8.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960591 | AF2-350 C O1 | Adder | 3.86 MW | 3.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960592 | AF2-350 E O1 | Adder | 2.58 MW | 2.19 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960601 | AF2-351 C O1 | Adder | 0.52 MW | 0.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960602 | AF2-351 E O1 | Adder | 0.77 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960721 | AF2-363 C O1 | Adder | 3.9 MW | 3.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960722 | AF2-363 E O1 | Adder | 2.6 MW | 2.21 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960751 | AF2-366 C | Adder | 4.59 MW | 3.9 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 960752 | AF2-366 E | Adder | 3.06 MW | 2.6 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961011 | AF2-392 C O1 | Adder | 2.47 MW | 2.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961012 | AF2-392 E O1 | Adder | 11.57 MW | 9.84 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961021 | AF2-393 O1 | Adder | 4.21 MW | 3.58 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 961031 | AF2-394 O1 | Adder | 2.81 MW | 2.39 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274660 | LASCO STA;1U | 50/50 | 32.88 MW | 32.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274661 | LASCO STA;2U | 50/50 | 33.02 MW | 33.02 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274737 | AURORA EC;1P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274739 | AURORA EC;2P | 50/50 | 3.15 MW | 3.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274741 | AURORA EC;5P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274742 | AURORA EC;6P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274746 | AURORA EC;0P | 50/50 | 0.62 MW | 0.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274847 | GR RIDGE ;BU | 50/50 | 0.67 MW | 0.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274859 | EASYR;U1 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274860 | EASYR;U2 E | Adder | 7.0 MW | 5.95 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 274871 | GR RIDGE ;2U | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 275149 | KELLYCK ;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276170 | Z1-108 E | Adder | 1.71 MW | 1.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276173 | Z2-081 | 50/50 | 0.25 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 276591 | L-013 2 | Adder | 2.73 MW | 2.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293061 | N-015 E | 50/50 | 17.26 MW | 17.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293516 | O-009 E1 | Adder | 5.55 MW | 4.71 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293517 | O-009 E2 | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293518 | O-009 E3 | Adder | 3.1 MW | 2.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293715 | O-029 E | Adder | 5.93 MW | 5.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293716 | O-029 E | Adder | 3.25 MW | 2.76 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293717 | O-029 E | Adder | 2.99 MW | 2.54 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293771 | O-035 E | Adder | 3.73 MW | 3.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 293799 | PILOT HIL;1E | Adder | 9.02 MW | 7.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294392 | P-010 E | 50/50 | 21.92 MW | 21.92 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294401 | BSHIL;1U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294410 | BSHIL;2U E | Adder | 4.9 MW | 4.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 294763 | P-046 E | Adder | 6.07 MW | 5.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915011 | Y3-013 1 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915021 | Y3-013 2 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 915031 | Y3-013 3 | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916211 | Z1-072 E | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 916221 | Z1-073 E | Adder | 3.51 MW | 2.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925581 | AC1-033 C | Adder | 0.8 MW | 0.68 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 925582 | AC1-033 E | Adder | 5.37 MW | 4.56 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930482 | AB1-089 CT | Adder | 24.74 MW | 21.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930483 | AB1-089 ST | Adder | 19.67 MW | 16.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 930771 | AB1-122 CT2 | Adder | 6.53 MW | 5.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933411 | AC2-154 C | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 933412 | AC2-154 E | Adder | 2.0 MW | 1.7 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938861 | AE1-114 C O1 | Adder | 2.51 MW | 2.13 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 938862 | AE1-114 E O1 | Adder | 8.56 MW | 7.28 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939051 | AE1-134 1 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939061 | AE1-134 2 | Adder | 0.85 MW | 0.72 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939351 | AE1-166 C O1 | Adder | 5.43 MW | 4.62 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 939352 | AE1-166 E O1 | Adder | 5.02 MW | 4.26 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940501 | AE2-035 C | Adder | 1.59 MW | 1.35 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940502 | AE2-035 E | Adder | 2.2 MW | 1.87 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 940752 | AE2-062 E | Adder | 0.06 MW | 0.05 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941131 | AE2-107 C | Adder | 4.28 MW | 3.64 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941132 | AE2-107 E | Adder | 2.85 MW | 2.43 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941551 | AE2-152 C O1 | Adder | 6.27 MW | 5.33 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 941552 | AE2-152 E O1 | Adder | 4.18 MW | 3.55 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946151 | AF1-280 C O1 | Adder | 9.85 MW | 8.37 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946152 | AF1-280 E O1 | Adder | 4.53 MW | 3.85 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946321 | AF1-296 C O1 | Adder | 2.37 MW | 2.01 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946322 | AF1-296 E O1 | Adder | 11.08 MW | 9.41 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946501 | AF1-314 C | Adder | 2.82 MW | 2.4 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946502 | AF1-314 E | Adder | 13.26 MW | 11.27 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946541 | AF1-318 C O1 | Adder | 3.46 MW | 2.94 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946661 | AF1-330 C | Adder | 1.36 MW | 1.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946662 | AF1-330 E | Adder | 0.3 MW | 0.25 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 946671 | AF1-331 | Adder | 1.55 MW | 1.31 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957331 | AF2-027 C | Adder | 1.55 MW | 1.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957332 | AF2-027 E | Adder | 2.33 MW | 1.98 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957401 | AF2-034 C | Adder | 0.63 MW | 0.53 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957402 | AF2-034 E | Adder | 0.53 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957471 | AF2-041 C | Adder | 13.31 MW | 11.32 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957472 | AF2-041 E | Adder | 6.66 MW | 5.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957751 | AF2-069 C | Adder | 0.14 MW | 0.12 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957752 | AF2-069 E | Adder | 0.45 MW | 0.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957761 | AF2-070 C | Adder | 0.2 MW | 0.17 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 957762 | AF2-070 E | Adder | 0.95 MW | 0.81 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958011 | AF2-095 C O1 | Adder | 8.76 MW | 7.44 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958012 | AF2-095 E O1 | Adder | 4.12 MW | 3.5 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958021 | AF2-096 C | Adder | 22.39 MW | 19.03 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958022 | AF2-096 E | Adder | 10.54 MW | 8.96 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958341 | AF2-128 C O1 | Adder | 0.92 MW | 0.79 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 958342 | AF2-128 E O1 | Adder | 4.32 MW | 3.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 990901 | L-005 E | Adder | 7.24 MW | 6.15 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 290108 | LEEDK;1U E | Adder | 15.86 MW | 13.48 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | 945351 | AF1-200 FTIR | 50/50 | 627.1 MW | 627.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.34 MW | 1.34 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.09 MW | 0.09 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.2 MW | 0.2 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 42.67 MW | 42.67 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 8.83 MW | 8.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.1 MW | 0.1 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.23 MW | 1.23 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.36 MW | 0.36 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.83 MW | 1.83 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.16 MW | 0.16 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 7.38 MW | 7.38 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.66 MW | 0.66 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.88 MW | 7.88 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.45 MW | 0.45 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.52 MW | 0.52 MW |
| PLANO ; R-PLANO ;4M 345.0 kV Ckt 1 line l/o COMED_P4_167-45-BT8-12_ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.32 MW | 2.32 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 23.14 MW | 19.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 15.43 MW | 13.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962701 | AG1-119 C | Adder | 22.87 MW | 19.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962702 | AG1-119 E | Adder | 15.24 MW | 12.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 9.02 MW | 7.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 6.01 MW | 5.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962781 | AG1-127 C | Adder | 7.31 MW | 6.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962782 | AG1-127 E | Adder | 4.86 MW | 4.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965061 | AG1-371 | Adder | 3.74 MW | 3.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965081 | AG1-373 | Adder | 1.25 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965141 | AG1-379 C | Adder | 18.07 MW | 15.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965142 | AG1-379 E | Adder | 8.27 MW | 7.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 15.25 MW | 12.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 10.17 MW | 8.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 4.33 MW | 3.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 20.26 MW | 17.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966091 | AG1-478 C | Adder | 2.06 MW | 1.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966092 | AG1-478 E | Adder | 0.52 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966441 | AG1-513 C | Adder | 0.53 MW | 0.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966442 | AG1-513 E | Adder | 0.8 MW | 0.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 272364 | ESS H440N ;R | Adder | 2.75 MW | 2.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 21.08 MW | 17.92 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 10.94 MW | 9.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 5.86 MW | 4.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 16.38 MW | 13.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 2.56 MW | 2.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.99 MW | 1.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.99 MW | 1.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927093 | AC1-204 GEN2 | 50/50 | 13.25 MW | 13.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | 50/50 | 4.51 MW | 4.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | 50/50 | 4.51 MW | 4.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.93 MW | 1.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 3.08 MW | 2.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.97 MW | 0.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.58 MW | 1.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.58 MW | 0.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 19.86 MW | 16.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 92.67 MW | 78.77 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.63 MW | 0.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 3.32 MW | 2.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 15.54 MW | 13.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 8.74 MW | 7.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 5.83 MW | 4.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 2.65 MW | 2.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 10.58 MW | 8.99 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 8.35 MW | 7.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 8.36 MW | 7.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 3.29 MW | 2.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 9.88 MW | 8.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.88 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 5.41 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 8.56 MW | 7.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 4.22 MW | 3.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 13.27 MW | 11.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 6.51 MW | 5.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 8.82 MW | 7.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 4.36 MW | 3.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 4.0 MW | 3.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 2.67 MW | 2.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 11.3 MW | 9.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 7.53 MW | 6.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 11.32 MW | 9.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 7.54 MW | 6.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 7.48 MW | 6.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 3.74 MW | 3.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 14.96 MW | 12.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 9.97 MW | 8.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | 50/50 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | 50/50 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | 50/50 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | 50/50 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 5.56 MW | 4.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 22.77 MW | 19.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 15.18 MW | 12.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 6.19 MW | 5.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 4.13 MW | 3.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 7.29 MW | 6.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 4.86 MW | 4.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.68 MW | 29.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274655 | BRAIDWOOD;2U | 50/50 | 28.88 MW | 28.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274660 | LASCO STA;1U | 50/50 | 27.28 MW | 27.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274661 | LASCO STA;2U | 50/50 | 27.39 MW | 27.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274675 | JOLIET 29;7U | 50/50 | 12.42 MW | 12.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274676 | JOLIET 29;8U | 50/50 | 12.43 MW | 12.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274687 | WILL CNTY;4U | 50/50 | 12.47 MW | 12.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274704 | KENDALL ;1C | 50/50 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274705 | KENDALL ;1S | 50/50 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274706 | KENDALL ;2C | 50/50 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274707 | KENDALL ;2S | 50/50 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 0.48 MW | 0.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 2.61 MW | 2.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276591 | L-013 2 | Adder | 3.83 MW | 3.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 16.42 MW | 13.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | 50/50 | 12.42 MW | 12.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | 50/50 | 24.11 MW | 24.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 20.85 MW | 17.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 5.68 MW | 4.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930482 | AB1-089 CT | Adder | 38.28 MW | 32.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930483 | AB1-089 ST | Adder | 30.44 MW | 25.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 71.88 MW | 61.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 79.63 MW | 67.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 9.83 MW | 8.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 8.98 MW | 7.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 8.69 MW | 7.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 30.83 MW | 26.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 6.16 MW | 5.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 37.84 MW | 32.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 10.62 MW | 9.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 9.81 MW | 8.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 6.86 MW | 5.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 4.57 MW | 3.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 12.26 MW | 10.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 8.17 MW | 6.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 13.08 MW | 11.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 2.1 MW | 1.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 2.5 MW | 2.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 2.62 MW | 2.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | 50/50 | 1.54 MW | 1.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | 50/50 | 1.31 MW | 1.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 22.44 MW | 19.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 11.22 MW | 9.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | 50/50 | 40.58 MW | 40.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | 50/50 | 19.1 MW | 19.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 5.81 MW | 4.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 6.44 MW | 5.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 25.39 MW | 21.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 322.44 MW | 274.08 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.07 MW | 2.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.26 MW | 0.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.25 MW | 64.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 20.3 MW | 20.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.03 MW | 2.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.18 MW | 0.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.05 MW | 4.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.67 MW | 13.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.09 MW | 1.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 13.01 MW | 13.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.92 MW | 3.92 MW |
| Details for E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962691 | AG1-118 C O1 | Adder | 23.14 MW | 19.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962692 | AG1-118 E O1 | Adder | 15.43 MW | 13.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962701 | AG1-119 C | Adder | 22.86 MW | 19.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962702 | AG1-119 E | Adder | 15.24 MW | 12.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962711 | AG1-120 C O1 | Adder | 9.02 MW | 7.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962712 | AG1-120 E O1 | Adder | 6.01 MW | 5.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962781 | AG1-127 C | Adder | 7.31 MW | 6.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962782 | AG1-127 E | Adder | 4.86 MW | 4.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965061 | AG1-371 | Adder | 3.74 MW | 3.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965081 | AG1-373 | Adder | 1.25 MW | 1.06 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965141 | AG1-379 C | Adder | 18.07 MW | 15.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965142 | AG1-379 E | Adder | 8.27 MW | 7.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965551 | AG1-423 C O1 | Adder | 15.25 MW | 12.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965552 | AG1-423 E O1 | Adder | 10.17 MW | 8.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965661 | AG1-434 C O1 | Adder | 4.33 MW | 3.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965662 | AG1-434 E O1 | Adder | 20.25 MW | 17.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966091 | AG1-478 C | Adder | 2.06 MW | 1.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966092 | AG1-478 E | Adder | 0.52 MW | 0.44 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966441 | AG1-513 C | Adder | 0.53 MW | 0.45 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966442 | AG1-513 E | Adder | 0.8 MW | 0.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 272364 | ESS H440N ;R | Adder | 2.75 MW | 2.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 21.08 MW | 17.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 10.94 MW | 9.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 5.86 MW | 4.98 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 16.38 MW | 13.93 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 2.56 MW | 2.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.99 MW | 1.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.99 MW | 1.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927093 | AC1-204 GEN2 | 50/50 | 13.25 MW | 13.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | 50/50 | 4.51 MW | 4.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | 50/50 | 4.51 MW | 4.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.93 MW | 1.64 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 3.08 MW | 2.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.97 MW | 0.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.58 MW | 1.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.58 MW | 0.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 19.86 MW | 16.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 92.68 MW | 78.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.94 MW | 0.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.63 MW | 0.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 3.32 MW | 2.82 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 15.54 MW | 13.21 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 8.74 MW | 7.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 5.83 MW | 4.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.65 MW | 2.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 10.58 MW | 8.99 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 8.35 MW | 7.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 8.36 MW | 7.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 3.29 MW | 2.8 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 9.88 MW | 8.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.88 MW | 0.75 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 5.41 MW | 4.59 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 8.56 MW | 7.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 4.22 MW | 3.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 13.26 MW | 11.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 6.51 MW | 5.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 8.82 MW | 7.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 4.36 MW | 3.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 4.0 MW | 3.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.67 MW | 2.27 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 11.3 MW | 9.61 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 7.53 MW | 6.4 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 11.32 MW | 9.62 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 7.54 MW | 6.41 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 7.48 MW | 6.36 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 3.74 MW | 3.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 14.96 MW | 12.71 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 9.97 MW | 8.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | 50/50 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | 50/50 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | 50/50 | 3.04 MW | 3.04 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | 50/50 | 4.57 MW | 4.57 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 5.56 MW | 4.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 22.77 MW | 19.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 15.18 MW | 12.9 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 6.19 MW | 5.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 4.12 MW | 3.51 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 7.29 MW | 6.19 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 4.86 MW | 4.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274654 | BRAIDWOOD;1U | 50/50 | 29.68 MW | 29.68 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274655 | BRAIDWOOD;2U | 50/50 | 28.88 MW | 28.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274660 | LASCO STA;1U | 50/50 | 27.28 MW | 27.28 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274661 | LASCO STA;2U | 50/50 | 27.39 MW | 27.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274675 | JOLIET 29;7U | 50/50 | 12.42 MW | 12.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274676 | JOLIET 29;8U | 50/50 | 12.43 MW | 12.43 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274687 | WILL CNTY;4U | 50/50 | 12.46 MW | 12.46 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274704 | KENDALL ;1C | 50/50 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274705 | KENDALL ;1S | 50/50 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274706 | KENDALL ;2C | 50/50 | 4.42 MW | 4.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274707 | KENDALL ;2S | 50/50 | 2.95 MW | 2.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274861 | TOP CROP ;1U | 50/50 | 0.48 MW | 0.48 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274862 | TOP CROP ;2U | 50/50 | 0.91 MW | 0.91 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 2.61 MW | 2.22 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276591 | L-013 2 | Adder | 3.83 MW | 3.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 16.42 MW | 13.96 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | 50/50 | 12.42 MW | 12.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | 50/50 | 24.11 MW | 24.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 20.85 MW | 17.73 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 5.68 MW | 4.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930482 | AB1-089 CT | Adder | 38.28 MW | 32.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930483 | AB1-089 ST | Adder | 30.43 MW | 25.87 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930761 | AB1-122 CT1 | Adder | 71.88 MW | 61.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930771 | AB1-122 CT2 | Adder | 79.63 MW | 67.69 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 9.83 MW | 8.35 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 8.98 MW | 7.63 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C O1 | Adder | 8.69 MW | 7.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E O1 | Adder | 30.82 MW | 26.2 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 6.16 MW | 5.24 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 37.84 MW | 32.17 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 10.62 MW | 9.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 9.81 MW | 8.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.13 MW | 0.11 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 6.86 MW | 5.83 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 4.57 MW | 3.88 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 12.26 MW | 10.42 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 8.17 MW | 6.95 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 13.08 MW | 11.12 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 2.1 MW | 1.78 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.46 MW | 0.39 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 2.5 MW | 2.13 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 2.62 MW | 2.23 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 3.93 MW | 3.34 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | 50/50 | 1.54 MW | 1.54 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | 50/50 | 1.31 MW | 1.31 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 22.43 MW | 19.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 11.22 MW | 9.53 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | 50/50 | 40.58 MW | 40.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | 50/50 | 19.1 MW | 19.1 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 5.81 MW | 4.94 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 6.44 MW | 5.47 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 25.39 MW | 21.58 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 322.35 MW | 274.0 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.74 MW | 0.74 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.07 MW | 2.07 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.26 MW | 0.26 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.25 MW | 0.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.25 MW | 64.25 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 20.3 MW | 20.3 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.03 MW | 2.03 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.18 MW | 0.18 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.5 MW | 0.5 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.05 MW | 4.05 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.32 MW | 0.32 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.67 MW | 13.67 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.09 MW | 1.09 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 13.01 MW | 13.01 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.7 MW | 0.7 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| E FRANKFO; B-CRETE EC ;BP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 3.92 MW | 3.92 MW |
| Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 962691 | AG1-118 C O1 | Adder | 42.24 MW | 35.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 962692 | AG1-118 E O1 | Adder | 28.16 MW | 23.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 962701 | AG1-119 C | Adder | 41.65 MW | 35.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 962702 | AG1-119 E | Adder | 27.77 MW | 23.6 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 962711 | AG1-120 C O1 | Adder | 16.5 MW | 14.02 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 962712 | AG1-120 E O1 | Adder | 11.0 MW | 9.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 962781 | AG1-127 C | Adder | 13.36 MW | 11.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 962782 | AG1-127 E | Adder | 8.89 MW | 7.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 964361 | AG1-298 O1 | Adder | 120.19 MW | 102.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 965061 | AG1-371 | Adder | 3.22 MW | 2.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 965141 | AG1-379 C | Adder | 31.99 MW | 27.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 965142 | AG1-379 E | Adder | 14.64 MW | 12.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 965551 | AG1-423 C O1 | Adder | 27.77 MW | 23.61 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 965552 | AG1-423 E O1 | Adder | 18.52 MW | 15.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 965681 | AG1-436 C | Adder | 17.98 MW | 15.29 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 965682 | AG1-436 E | Adder | 11.99 MW | 10.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 965791 | AG1-447 | Adder | 13.19 MW | 11.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 966091 | AG1-478 C | Adder | 3.8 MW | 3.23 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 966092 | AG1-478 E | Adder | 0.96 MW | 0.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 966431 | AG1-512 C | Adder | 3.86 MW | 3.28 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 966432 | AG1-512 E | Adder | 5.78 MW | 4.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 966441 | AG1-513 C | Adder | 0.96 MW | 0.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 966442 | AG1-513 E | Adder | 1.44 MW | 1.22 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 966651 | AG1-535 O1 | Adder | 20.38 MW | 17.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 272364 | ESS H440N ;R | Adder | 5.07 MW | 4.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 290021 | O50 E | Adder | 37.31 MW | 31.71 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 290051 | GSG-6; E | Adder | 20.16 MW | 17.14 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 295109 | WESTBROOK E | Adder | 10.79 MW | 9.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 910542 | X3-005 E | Adder | 1.35 MW | 1.15 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 918052 | AA1-018 E OP | Adder | 30.77 MW | 26.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 920272 | AA2-123 E | Adder | 4.64 MW | 3.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 926331 | AC1-110 1 | Adder | 3.58 MW | 3.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 926341 | AC1-110 2 | Adder | 3.58 MW | 3.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 927451 | AC1-142A 1 | Adder | 7.68 MW | 6.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 927461 | AC1-142A 2 | Adder | 7.68 MW | 6.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 933911 | AD1-013 C | Adder | 3.55 MW | 3.02 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 933912 | AD1-013 E | Adder | 5.67 MW | 4.82 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 933931 | AD1-016 C | Adder | 1.76 MW | 1.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 933932 | AD1-016 E | Adder | 2.87 MW | 2.44 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 934432 | AD1-067 E | Adder | 1.06 MW | 0.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 934721 | AD1-100 C | Adder | 36.32 MW | 30.87 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 934722 | AD1-100 E | Adder | 169.49 MW | 144.07 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 934971 | AD1-129 C | Adder | 1.72 MW | 1.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 934972 | AD1-129 E | Adder | 1.15 MW | 0.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 936291 | AD2-038 C O1 | Adder | 6.17 MW | 5.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 936292 | AD2-038 E O1 | Adder | 28.9 MW | 24.57 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 936371 | AD2-047 C O1 | Adder | 8.2 MW | 6.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 936372 | AD2-047 E O1 | Adder | 40.05 MW | 34.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 936461 | AD2-060 | Adder | 4.82 MW | 4.1 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 936511 | AD2-066 C O1 | Adder | 16.1 MW | 13.69 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 936512 | AD2-066 E O1 | Adder | 10.73 MW | 9.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 937001 | AD2-134 C | Adder | 4.88 MW | 4.15 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 937002 | AD2-134 E | Adder | 19.49 MW | 16.57 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 937401 | AD2-194 1 | Adder | 14.32 MW | 12.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 937411 | AD2-194 2 | Adder | 14.32 MW | 12.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 942421 | AE2-255 C O1 | Adder | 5.83 MW | 4.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 942422 | AE2-255 E O1 | Adder | 17.49 MW | 14.87 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 942651 | AE2-281 C O1 | Adder | 1.64 MW | 1.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 942652 | AE2-281 E O1 | Adder | 10.06 MW | 8.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 942991 | AE2-321 C | Adder | 15.53 MW | 13.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 942992 | AE2-321 E | Adder | 7.65 MW | 6.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 943121 | AE2-341 C | Adder | 24.22 MW | 20.59 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 943122 | AE2-341 E | Adder | 11.9 MW | 10.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 943591 | AF1-030 C O1 | Adder | 16.11 MW | 13.69 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 943592 | AF1-030 E O1 | Adder | 7.97 MW | 6.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 943801 | AF1-048 C | Adder | 7.26 MW | 6.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 943802 | AF1-048 E | Adder | 4.84 MW | 4.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 958481 | AF2-142 C | Adder | 21.22 MW | 18.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 958482 | AF2-142 E | Adder | 14.15 MW | 12.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 958491 | AF2-143 C | Adder | 21.05 MW | 17.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 958492 | AF2-143 E | Adder | 14.03 MW | 11.93 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 959081 | AF2-199 C | Adder | 13.73 MW | 11.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 959082 | AF2-199 E | Adder | 6.86 MW | 5.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 959091 | AF2-200 C O1 | Adder | 27.46 MW | 23.34 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 959092 | AF2-200 E O1 | Adder | 18.3 MW | 15.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 959351 | AF2-226 C | Adder | 4.71 MW | 4.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 959352 | AF2-226 E | Adder | 7.07 MW | 6.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960281 | AF2-319 C | Adder | 4.71 MW | 4.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960282 | AF2-319 E | Adder | 7.07 MW | 6.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960381 | AF2-329 | Adder | 10.16 MW | 8.64 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960581 | AF2-349 C | Adder | 41.46 MW | 35.24 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960582 | AF2-349 E | Adder | 27.64 MW | 23.49 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960591 | AF2-350 C O1 | Adder | 14.47 MW | 12.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960592 | AF2-350 E O1 | Adder | 9.65 MW | 8.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960601 | AF2-351 C O1 | Adder | 1.93 MW | 1.64 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960602 | AF2-351 E O1 | Adder | 2.9 MW | 2.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960681 | AF2-359 C | Adder | 17.98 MW | 15.29 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960682 | AF2-359 E | Adder | 11.99 MW | 10.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960721 | AF2-363 C O1 | Adder | 11.32 MW | 9.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960722 | AF2-363 E O1 | Adder | 7.55 MW | 6.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960751 | AF2-366 C | Adder | 13.32 MW | 11.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 960752 | AF2-366 E | Adder | 8.88 MW | 7.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 961501 | AF2-441 C O1 | Adder | 19.26 MW | 16.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 961502 | AF2-441 E O1 | Adder | 28.89 MW | 24.55 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 243441 | 05CKG2 | 50/50 | 60.83 MW | 60.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274770 | LINCOLN ;1U | 50/50 | 3.35 MW | 3.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274771 | LINCOLN ;2U | 50/50 | 3.35 MW | 3.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274772 | LINCOLN ;3U | 50/50 | 3.35 MW | 3.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274773 | LINCOLN ;4U | 50/50 | 3.35 MW | 3.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274774 | LINCOLN ;5U | 50/50 | 3.35 MW | 3.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274776 | LINCOLN ;7U | 50/50 | 3.35 MW | 3.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274777 | LINCOLN ;8U | 50/50 | 3.35 MW | 3.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274788 | SE CHICAG;5U | Adder | 9.09 MW | 7.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274789 | SE CHICAG;6U | Adder | 9.11 MW | 7.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274790 | SE CHICAG;7U | Adder | 9.23 MW | 7.85 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274791 | SE CHICAG;8U | Adder | 9.23 MW | 7.85 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274792 | SE CHICAG;9U | Adder | 9.22 MW | 7.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274793 | SE CHICAG;0U | Adder | 9.22 MW | 7.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274794 | SE CHICAG;1U | Adder | 9.22 MW | 7.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 274795 | SE CHICAG;2U | Adder | 9.22 MW | 7.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 275149 | KELLYCK ;1E | Adder | 33.77 MW | 28.71 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 276170 | Z1-108 E | Adder | 4.69 MW | 3.99 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 276591 | L-013 2 | Adder | 6.9 MW | 5.87 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 293061 | N-015 E | Adder | 28.92 MW | 24.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 293644 | O22 E1 | Adder | 19.22 MW | 16.34 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 293645 | O22 E2 | Adder | 37.31 MW | 31.71 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 293799 | PILOT HIL;1E | Adder | 33.77 MW | 28.71 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 294392 | P-010 E | Adder | 36.72 MW | 31.22 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 915011 | Y3-013 1 | Adder | 7.02 MW | 5.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 915021 | Y3-013 2 | Adder | 7.02 MW | 5.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 915031 | Y3-013 3 | Adder | 7.02 MW | 5.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 916221 | Z1-073 E | Adder | 10.47 MW | 8.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 930761 | AB1-122 CT1 | Adder | 133.16 MW | 113.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 930771 | AB1-122 CT2 | Adder | 136.89 MW | 116.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 933281 | AC2-140 C | 50/50 | 2.01 MW | 2.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 933282 | AC2-140 E | 50/50 | 0.62 MW | 0.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 933411 | AC2-154 C | Adder | 4.58 MW | 3.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 933412 | AC2-154 E | Adder | 7.48 MW | 6.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 938511 | AE1-070 1 | Adder | 16.82 MW | 14.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 938521 | AE1-070 2 | Adder | 15.39 MW | 13.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 938851 | AE1-113 C O1 | Adder | 15.39 MW | 13.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 938852 | AE1-113 E O1 | Adder | 54.56 MW | 46.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 939321 | AE1-163 C O1 | Adder | 11.46 MW | 9.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 939322 | AE1-163 E O1 | Adder | 70.39 MW | 59.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 939351 | AE1-166 C O1 | Adder | 18.89 MW | 16.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 939352 | AE1-166 E O1 | Adder | 17.43 MW | 14.82 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 939401 | AE1-172 C O1 | Adder | 10.38 MW | 8.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 939402 | AE1-172 E O1 | Adder | 48.73 MW | 41.42 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 940752 | AE2-062 E | Adder | 0.24 MW | 0.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 941131 | AE2-107 C | Adder | 12.57 MW | 10.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 941132 | AE2-107 E | Adder | 8.38 MW | 7.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 941551 | AE2-152 C O1 | Adder | 21.79 MW | 18.52 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 941552 | AE2-152 E O1 | Adder | 14.53 MW | 12.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 946661 | AF1-330 C | Adder | 3.8 MW | 3.23 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 946662 | AF1-330 E | Adder | 0.84 MW | 0.71 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 946671 | AF1-331 | Adder | 4.61 MW | 3.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 957331 | AF2-027 C | Adder | 4.68 MW | 3.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 957332 | AF2-027 E | Adder | 7.02 MW | 5.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 957371 | AF2-031 C O1 | Adder | 1.92 MW | 1.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 957372 | AF2-031 E O1 | Adder | 2.88 MW | 2.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 957401 | AF2-034 C | Adder | 2.58 MW | 2.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 957402 | AF2-034 E | Adder | 2.2 MW | 1.87 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 957471 | AF2-041 C | Adder | 41.19 MW | 35.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 957472 | AF2-041 E | Adder | 20.59 MW | 17.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 958011 | AF2-095 C O1 | Adder | 32.81 MW | 27.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 958012 | AF2-095 E O1 | Adder | 15.44 MW | 13.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 958021 | AF2-096 C | Adder | 61.7 MW | 52.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 958022 | AF2-096 E | Adder | 29.04 MW | 24.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 934101 | AD2-000 1 | Adder | 10.77 MW | 9.15 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 934111 | AD2-000 2 | Adder | 11.07 MW | 9.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 290108 | LEEDK;1U E | Adder | 46.55 MW | 39.57 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | 945351 | AF1-200 FTIR | Adder | 597.83 MW | 508.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.07 MW | 2.07 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.65 MW | 0.65 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.56 MW | 1.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 227.79 MW | 227.79 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 81.91 MW | 81.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 5.89 MW | 5.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.34 MW | 1.34 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.28 MW | 12.28 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.37 MW | 1.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 28.51 MW | 28.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.09 MW | 3.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 37.77 MW | 37.77 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.76 MW | 0.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.36 MW | 6.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 7.13 MW | 7.13 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 16.34 MW | 13.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 10.89 MW | 9.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962701 | AG1-119 C | Adder | 16.13 MW | 13.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962702 | AG1-119 E | Adder | 10.75 MW | 9.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.24 MW | 3.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962781 | AG1-127 C | Adder | 5.16 MW | 4.39 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962782 | AG1-127 E | Adder | 3.43 MW | 2.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965142 | AG1-379 E | Adder | 5.81 MW | 4.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 10.76 MW | 9.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 7.17 MW | 6.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 14.28 MW | 12.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966092 | AG1-478 E | Adder | 0.37 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 14.81 MW | 12.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 7.72 MW | 6.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.14 MW | 3.52 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 11.73 MW | 9.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 1.8 MW | 1.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 3.17 MW | 2.69 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 3.17 MW | 2.69 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 2.17 MW | 1.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.12 MW | 0.95 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.41 MW | 0.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 66.08 MW | 56.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.07 MW | 9.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 15.06 MW | 12.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.12 MW | 3.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 7.47 MW | 6.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 5.87 MW | 4.99 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 6.94 MW | 5.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.85 MW | 3.27 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 2.97 MW | 2.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 9.38 MW | 7.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 4.6 MW | 3.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 6.24 MW | 5.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 3.09 MW | 2.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 1.88 MW | 1.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 5.39 MW | 4.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 5.37 MW | 4.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 2.64 MW | 2.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 7.03 MW | 5.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 0.5 MW | 0.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 12.74 MW | 10.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | 50/50 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | 50/50 | 3.14 MW | 3.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | 50/50 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | 50/50 | 3.14 MW | 3.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 16.06 MW | 13.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 10.71 MW | 9.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 3.63 MW | 3.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.09 MW | 0.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.37 MW | 3.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 2.91 MW | 2.47 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 3.43 MW | 2.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274654 | BRAIDWOOD;1U | 50/50 | 20.63 MW | 20.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274655 | BRAIDWOOD;2U | 50/50 | 20.08 MW | 20.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274687 | WILL CNTY;4U | 50/50 | 8.78 MW | 8.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274751 | CRETE EC ;1U | 50/50 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274752 | CRETE EC ;2U | 50/50 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274753 | CRETE EC ;3U | 50/50 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274754 | CRETE EC ;4U | 50/50 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 0.33 MW | 0.33 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 0.62 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 12.7 MW | 10.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 1.84 MW | 1.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276591 | L-013 2 | Adder | 2.7 MW | 2.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 11.52 MW | 9.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | 50/50 | 8.54 MW | 8.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | 50/50 | 16.57 MW | 16.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293799 | PILOT HIL;1E | Adder | 12.7 MW | 10.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 14.63 MW | 12.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 6.9 MW | 5.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 4.01 MW | 3.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930482 | AB1-089 CT | Adder | 27.0 MW | 22.95 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 50.71 MW | 43.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 55.89 MW | 47.51 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933412 | AC2-154 E | Adder | 2.81 MW | 2.39 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 6.9 MW | 5.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 21.66 MW | 18.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 26.95 MW | 22.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 6.96 MW | 5.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.09 MW | 0.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 3.23 MW | 2.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 5.8 MW | 4.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 15.08 MW | 12.82 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 1.77 MW | 1.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 2.77 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.07 MW | 0.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.92 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 15.82 MW | 13.45 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 7.91 MW | 6.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 5.81 MW | 4.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | 50/50 | 27.74 MW | 27.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | 50/50 | 13.05 MW | 13.05 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 17.93 MW | 15.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 227.71 MW | 193.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.56 MW | 1.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.96 MW | 47.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.54 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.86 MW | 9.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962691 | AG1-118 C O1 | Adder | 16.34 MW | 13.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962692 | AG1-118 E O1 | Adder | 10.89 MW | 9.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962701 | AG1-119 C | Adder | 16.13 MW | 13.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962702 | AG1-119 E | Adder | 10.75 MW | 9.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962712 | AG1-120 E O1 | Adder | 4.24 MW | 3.61 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962781 | AG1-127 C | Adder | 5.16 MW | 4.39 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 962782 | AG1-127 E | Adder | 3.43 MW | 2.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965142 | AG1-379 E | Adder | 5.81 MW | 4.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965551 | AG1-423 C O1 | Adder | 10.76 MW | 9.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965552 | AG1-423 E O1 | Adder | 7.17 MW | 6.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 965662 | AG1-434 E O1 | Adder | 14.28 MW | 12.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966092 | AG1-478 E | Adder | 0.37 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290021 | O50 E | Adder | 14.81 MW | 12.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290051 | GSG-6; E | Adder | 7.72 MW | 6.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 295109 | WESTBROOK E | Adder | 4.14 MW | 3.52 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 918052 | AA1-018 E OP | Adder | 11.73 MW | 9.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 920272 | AA2-123 E | Adder | 1.8 MW | 1.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927451 | AC1-142A 1 | Adder | 3.17 MW | 2.69 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 927461 | AC1-142A 2 | Adder | 3.17 MW | 2.69 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933912 | AD1-013 E | Adder | 2.17 MW | 1.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933932 | AD1-016 E | Adder | 1.12 MW | 0.95 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934432 | AD1-067 E | Adder | 0.41 MW | 0.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934722 | AD1-100 E | Adder | 66.08 MW | 56.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936292 | AD2-038 E O1 | Adder | 11.07 MW | 9.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936372 | AD2-047 E O1 | Adder | 15.06 MW | 12.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936461 | AD2-060 | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 936512 | AD2-066 E O1 | Adder | 4.12 MW | 3.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937002 | AD2-134 E | Adder | 7.47 MW | 6.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 937411 | AD2-194 2 | Adder | 5.87 MW | 4.99 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942422 | AE2-255 E O1 | Adder | 6.94 MW | 5.9 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942652 | AE2-281 E O1 | Adder | 3.85 MW | 3.27 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 942992 | AE2-321 E | Adder | 2.97 MW | 2.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943121 | AE2-341 C | Adder | 9.38 MW | 7.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943122 | AE2-341 E | Adder | 4.6 MW | 3.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943591 | AF1-030 C O1 | Adder | 6.24 MW | 5.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943592 | AF1-030 E O1 | Adder | 3.09 MW | 2.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 943802 | AF1-048 E | Adder | 1.88 MW | 1.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958482 | AF2-142 E | Adder | 5.39 MW | 4.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958492 | AF2-143 E | Adder | 5.37 MW | 4.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959082 | AF2-199 E | Adder | 2.64 MW | 2.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959092 | AF2-200 E O1 | Adder | 7.03 MW | 5.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959101 | AF2-201 C O1 | Adder | 0.5 MW | 0.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959102 | AF2-201 E O1 | Adder | 12.74 MW | 10.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959351 | AF2-226 C | 50/50 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 959352 | AF2-226 E | 50/50 | 3.14 MW | 3.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960281 | AF2-319 C | 50/50 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960282 | AF2-319 E | 50/50 | 3.14 MW | 3.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960581 | AF2-349 C | Adder | 16.06 MW | 13.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960582 | AF2-349 E | Adder | 10.71 MW | 9.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960592 | AF2-350 E O1 | Adder | 3.63 MW | 3.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960602 | AF2-351 E O1 | Adder | 1.09 MW | 0.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960721 | AF2-363 C O1 | Adder | 4.37 MW | 3.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960722 | AF2-363 E O1 | Adder | 2.91 MW | 2.47 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 960752 | AF2-366 E | Adder | 3.43 MW | 2.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274654 | BRAIDWOOD;1U | 50/50 | 20.63 MW | 20.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274655 | BRAIDWOOD;2U | 50/50 | 20.08 MW | 20.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274687 | WILL CNTY;4U | 50/50 | 8.78 MW | 8.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274751 | CRETE EC ;1U | 50/50 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274752 | CRETE EC ;2U | 50/50 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274753 | CRETE EC ;3U | 50/50 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274754 | CRETE EC ;4U | 50/50 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274861 | TOP CROP ;1U | 50/50 | 0.33 MW | 0.33 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 274862 | TOP CROP ;2U | 50/50 | 0.62 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 275149 | KELLYCK ;1E | Adder | 12.7 MW | 10.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276170 | Z1-108 E | Adder | 1.84 MW | 1.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 276591 | L-013 2 | Adder | 2.7 MW | 2.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293061 | N-015 E | Adder | 11.52 MW | 9.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293644 | O22 E1 | 50/50 | 8.54 MW | 8.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293645 | O22 E2 | 50/50 | 16.57 MW | 16.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 293799 | PILOT HIL;1E | Adder | 12.7 MW | 10.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294392 | P-010 E | Adder | 14.63 MW | 12.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 294763 | P-046 E | Adder | 6.9 MW | 5.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 916221 | Z1-073 E | Adder | 4.01 MW | 3.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930482 | AB1-089 CT | Adder | 27.0 MW | 22.95 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930761 | AB1-122 CT1 | Adder | 50.71 MW | 43.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 930771 | AB1-122 CT2 | Adder | 55.89 MW | 47.51 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 933412 | AC2-154 E | Adder | 2.81 MW | 2.39 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938511 | AE1-070 1 | Adder | 6.9 MW | 5.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 938852 | AE1-113 E O1 | Adder | 21.66 MW | 18.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939322 | AE1-163 E O1 | Adder | 26.95 MW | 22.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 939352 | AE1-166 E O1 | Adder | 6.96 MW | 5.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 940752 | AE2-062 E | Adder | 0.09 MW | 0.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941132 | AE2-107 E | Adder | 3.23 MW | 2.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 941552 | AE2-152 E O1 | Adder | 5.8 MW | 4.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946502 | AF1-314 E | Adder | 15.08 MW | 12.82 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 946671 | AF1-331 | Adder | 1.77 MW | 1.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957332 | AF2-027 E | Adder | 2.77 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957401 | AF2-034 C | Adder | 1.07 MW | 0.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957402 | AF2-034 E | Adder | 0.92 MW | 0.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957471 | AF2-041 C | Adder | 15.82 MW | 13.45 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 957472 | AF2-041 E | Adder | 7.91 MW | 6.72 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958012 | AF2-095 E O1 | Adder | 5.81 MW | 4.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958021 | AF2-096 C | 50/50 | 27.74 MW | 27.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 958022 | AF2-096 E | 50/50 | 13.05 MW | 13.05 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 290108 | LEEDK;1U E | Adder | 17.93 MW | 15.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | 945351 | AF1-200 FTIR | Adder | 227.71 MW | 193.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.56 MW | 1.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.96 MW | 47.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.54 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.86 MW | 9.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962691 | AG1-118 C O1 | Adder | 16.34 MW | 13.89 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962692 | AG1-118 E O1 | Adder | 10.89 MW | 9.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962701 | AG1-119 C | Adder | 16.13 MW | 13.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962702 | AG1-119 E | Adder | 10.75 MW | 9.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962712 | AG1-120 E O1 | Adder | 4.24 MW | 3.61 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962782 | AG1-127 E | Adder | 3.43 MW | 2.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965142 | AG1-379 E | Adder | 5.81 MW | 4.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965552 | AG1-423 E O1 | Adder | 7.17 MW | 6.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965662 | AG1-434 E O1 | Adder | 14.28 MW | 12.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966092 | AG1-478 E | Adder | 0.37 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 14.81 MW | 12.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 7.72 MW | 6.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.14 MW | 3.52 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 11.73 MW | 9.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 1.8 MW | 1.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.17 MW | 2.69 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.17 MW | 2.69 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.17 MW | 1.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.12 MW | 0.95 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.41 MW | 0.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 66.08 MW | 56.17 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 11.07 MW | 9.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 15.06 MW | 12.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 1.81 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.12 MW | 3.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 7.47 MW | 6.35 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 5.87 MW | 4.99 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 6.94 MW | 5.9 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 3.85 MW | 3.27 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 2.97 MW | 2.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 9.38 MW | 7.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 4.6 MW | 3.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.24 MW | 5.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.09 MW | 2.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 1.88 MW | 1.6 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 5.39 MW | 4.58 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 5.37 MW | 4.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 2.64 MW | 2.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.03 MW | 5.97 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 0.5 MW | 0.42 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 12.74 MW | 10.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | 50/50 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | 50/50 | 3.14 MW | 3.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | 50/50 | 2.09 MW | 2.09 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | 50/50 | 3.14 MW | 3.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 16.06 MW | 13.65 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 10.7 MW | 9.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 3.63 MW | 3.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.09 MW | 0.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.37 MW | 3.71 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 2.91 MW | 2.47 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.43 MW | 2.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274654 | BRAIDWOOD;1U | 50/50 | 20.63 MW | 20.63 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274655 | BRAIDWOOD;2U | 50/50 | 20.08 MW | 20.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274687 | WILL CNTY;4U | 50/50 | 8.78 MW | 8.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274751 | CRETE EC ;1U | 50/50 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274752 | CRETE EC ;2U | 50/50 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274753 | CRETE EC ;3U | 50/50 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274754 | CRETE EC ;4U | 50/50 | 3.73 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274861 | TOP CROP ;1U | 50/50 | 0.33 MW | 0.33 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274862 | TOP CROP ;2U | 50/50 | 0.62 MW | 0.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 12.7 MW | 10.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 1.84 MW | 1.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276591 | L-013 2 | Adder | 2.7 MW | 2.3 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 11.52 MW | 9.79 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | 50/50 | 8.54 MW | 8.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | 50/50 | 16.57 MW | 16.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293799 | PILOT HIL;1E | Adder | 12.7 MW | 10.8 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 14.63 MW | 12.43 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 6.9 MW | 5.87 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.01 MW | 3.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.95 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930761 | AB1-122 CT1 | Adder | 50.71 MW | 43.1 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930771 | AB1-122 CT2 | Adder | 55.89 MW | 47.51 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 2.81 MW | 2.39 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 6.9 MW | 5.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E O1 | Adder | 21.66 MW | 18.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 26.95 MW | 22.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 6.96 MW | 5.92 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.09 MW | 0.08 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.23 MW | 2.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 5.8 MW | 4.93 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 15.08 MW | 12.82 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.28 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.77 MW | 1.5 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 2.77 MW | 2.36 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.07 MW | 0.91 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.92 MW | 0.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 15.82 MW | 13.44 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 7.91 MW | 6.72 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 5.81 MW | 4.94 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | 50/50 | 27.74 MW | 27.74 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | 50/50 | 13.05 MW | 13.05 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.49 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 17.92 MW | 15.24 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 227.68 MW | 193.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.56 MW | 1.56 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.96 MW | 47.96 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.54 MW | 1.54 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.86 MW | 9.86 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| ST JOHN ; T-17GREEN_ACRE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962691 | AG1-118 C O1 | Adder | 16.34 MW | 13.89 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962692 | AG1-118 E O1 | Adder | 10.89 MW | 9.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962701 | AG1-119 C | Adder | 16.13 MW | 13.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962702 | AG1-119 E | Adder | 10.75 MW | 9.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962711 | AG1-120 C O1 | Adder | 6.36 MW | 5.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962712 | AG1-120 E O1 | Adder | 4.24 MW | 3.61 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962781 | AG1-127 C | Adder | 5.16 MW | 4.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 962782 | AG1-127 E | Adder | 3.43 MW | 2.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965061 | AG1-371 | Adder | 2.64 MW | 2.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965081 | AG1-373 | Adder | 0.88 MW | 0.75 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965141 | AG1-379 C | Adder | 12.7 MW | 10.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965142 | AG1-379 E | Adder | 5.81 MW | 4.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965551 | AG1-423 C O1 | Adder | 10.75 MW | 9.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965552 | AG1-423 E O1 | Adder | 7.17 MW | 6.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965661 | AG1-434 C O1 | Adder | 3.05 MW | 2.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 965662 | AG1-434 E O1 | Adder | 14.28 MW | 12.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966091 | AG1-478 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966092 | AG1-478 E | Adder | 0.37 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966441 | AG1-513 C | Adder | 0.37 MW | 0.32 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 966442 | AG1-513 E | Adder | 0.56 MW | 0.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 272364 | ESS H440N ;R | Adder | 1.94 MW | 1.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290021 | O50 E | Adder | 14.81 MW | 12.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290051 | GSG-6; E | Adder | 7.72 MW | 6.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.14 MW | 3.52 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 11.73 MW | 9.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 920272 | AA2-123 E | Adder | 1.8 MW | 1.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.4 MW | 1.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.17 MW | 2.69 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.17 MW | 2.69 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.36 MW | 1.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.17 MW | 1.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.68 MW | 0.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.12 MW | 0.95 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.41 MW | 0.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934721 | AD1-100 C | Adder | 14.16 MW | 12.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934722 | AD1-100 E | Adder | 66.08 MW | 56.17 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 2.36 MW | 2.01 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 11.07 MW | 9.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.08 MW | 2.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 15.06 MW | 12.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936461 | AD2-060 | Adder | 1.81 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.18 MW | 5.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.12 MW | 3.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937001 | AD2-134 C | Adder | 1.87 MW | 1.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937002 | AD2-134 E | Adder | 7.47 MW | 6.35 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 5.86 MW | 4.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 5.87 MW | 4.99 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.31 MW | 1.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 6.94 MW | 5.9 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.63 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 3.85 MW | 3.27 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.04 MW | 5.13 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 942992 | AE2-321 E | Adder | 2.97 MW | 2.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943121 | AE2-341 C | Adder | 9.38 MW | 7.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943122 | AE2-341 E | Adder | 4.6 MW | 3.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.24 MW | 5.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.09 MW | 2.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943801 | AF1-048 C | Adder | 2.82 MW | 2.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 943802 | AF1-048 E | Adder | 1.88 MW | 1.6 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958481 | AF2-142 C | Adder | 8.09 MW | 6.88 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958482 | AF2-142 E | Adder | 5.39 MW | 4.58 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958491 | AF2-143 C | Adder | 8.06 MW | 6.85 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958492 | AF2-143 E | Adder | 5.37 MW | 4.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.27 MW | 4.48 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959082 | AF2-199 E | Adder | 2.64 MW | 2.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 10.54 MW | 8.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.03 MW | 5.97 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959101 | AF2-201 C O1 | Adder | 0.5 MW | 0.42 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959102 | AF2-201 E O1 | Adder | 12.74 MW | 10.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959351 | AF2-226 C | 50/50 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 959352 | AF2-226 E | 50/50 | 3.14 MW | 3.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960281 | AF2-319 C | 50/50 | 2.09 MW | 2.09 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960282 | AF2-319 E | 50/50 | 3.14 MW | 3.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960381 | AF2-329 | Adder | 3.93 MW | 3.34 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960581 | AF2-349 C | Adder | 16.06 MW | 13.65 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960582 | AF2-349 E | Adder | 10.7 MW | 9.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 5.44 MW | 4.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 3.63 MW | 3.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.73 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.09 MW | 0.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.37 MW | 3.71 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 2.91 MW | 2.47 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.14 MW | 4.37 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.43 MW | 2.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274654 | BRAIDWOOD;1U | 50/50 | 20.63 MW | 20.63 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274655 | BRAIDWOOD;2U | 50/50 | 20.08 MW | 20.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274687 | WILL CNTY;4U | 50/50 | 8.78 MW | 8.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274751 | CRETE EC ;1U | 50/50 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274752 | CRETE EC ;2U | 50/50 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274753 | CRETE EC ;3U | 50/50 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274754 | CRETE EC ;4U | 50/50 | 3.73 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274861 | TOP CROP ;1U | 50/50 | 0.33 MW | 0.33 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 274862 | TOP CROP ;2U | 50/50 | 0.62 MW | 0.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 12.7 MW | 10.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276170 | Z1-108 E | Adder | 1.84 MW | 1.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 276591 | L-013 2 | Adder | 2.7 MW | 2.3 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293061 | N-015 E | Adder | 11.52 MW | 9.79 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293644 | O22 E1 | 50/50 | 8.54 MW | 8.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293645 | O22 E2 | 50/50 | 16.57 MW | 16.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 293799 | PILOT HIL;1E | Adder | 12.7 MW | 10.8 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294392 | P-010 E | Adder | 14.63 MW | 12.43 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 294763 | P-046 E | Adder | 6.9 MW | 5.87 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 2.77 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 2.77 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 2.77 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.01 MW | 3.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930482 | AB1-089 CT | Adder | 26.99 MW | 22.95 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930483 | AB1-089 ST | Adder | 21.46 MW | 18.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930761 | AB1-122 CT1 | Adder | 50.71 MW | 43.1 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 930771 | AB1-122 CT2 | Adder | 55.89 MW | 47.51 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933411 | AC2-154 C | Adder | 1.72 MW | 1.47 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 933412 | AC2-154 E | Adder | 2.81 MW | 2.39 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 6.9 MW | 5.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.3 MW | 5.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938851 | AE1-113 C O1 | Adder | 6.11 MW | 5.19 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 938852 | AE1-113 E O1 | Adder | 21.66 MW | 18.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 4.39 MW | 3.73 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 26.95 MW | 22.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 7.54 MW | 6.41 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 6.96 MW | 5.92 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.09 MW | 0.08 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941131 | AE2-107 C | Adder | 4.84 MW | 4.11 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.23 MW | 2.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 8.7 MW | 7.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 5.8 MW | 4.93 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946502 | AF1-314 E | Adder | 15.08 MW | 12.82 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.48 MW | 1.26 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.32 MW | 0.28 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.77 MW | 1.5 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957331 | AF2-027 C | Adder | 1.85 MW | 1.57 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957332 | AF2-027 E | Adder | 2.77 MW | 2.36 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.07 MW | 0.91 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.92 MW | 0.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957471 | AF2-041 C | Adder | 15.82 MW | 13.44 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 957472 | AF2-041 E | Adder | 7.91 MW | 6.72 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 12.34 MW | 10.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 5.81 MW | 4.94 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958021 | AF2-096 C | 50/50 | 27.74 MW | 27.74 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 958022 | AF2-096 E | 50/50 | 13.05 MW | 13.05 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.1 MW | 3.49 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.52 MW | 3.84 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 17.92 MW | 15.24 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 227.68 MW | 193.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.59 MW | 0.59 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.56 MW | 1.56 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.21 MW | 0.21 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.16 MW | 0.16 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.96 MW | 47.96 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.04 MW | 14.04 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.05 MW | 0.05 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.54 MW | 1.54 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.4 MW | 0.4 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.78 MW | 2.78 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.22 MW | 0.22 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.62 MW | 9.62 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.83 MW | 0.83 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 9.86 MW | 9.86 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.53 MW | 0.53 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.98 MW | 0.98 MW |
| 17STJOHN-ST JOHN ; T 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.77 MW | 2.77 MW |
| Details for GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962691 | AG1-118 C O1 | Adder | 14.7 MW | 12.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962692 | AG1-118 E O1 | Adder | 9.8 MW | 8.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962701 | AG1-119 C | Adder | 14.49 MW | 12.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962702 | AG1-119 E | Adder | 9.66 MW | 8.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962711 | AG1-120 C O1 | Adder | 5.72 MW | 4.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962712 | AG1-120 E O1 | Adder | 3.82 MW | 3.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962781 | AG1-127 C | Adder | 4.64 MW | 3.95 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962782 | AG1-127 E | Adder | 3.09 MW | 2.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 964361 | AG1-298 O1 | Adder | 47.49 MW | 40.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965061 | AG1-371 | Adder | 2.37 MW | 2.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965081 | AG1-373 | Adder | 0.79 MW | 0.67 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965141 | AG1-379 C | Adder | 11.33 MW | 9.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965142 | AG1-379 E | Adder | 5.19 MW | 4.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965551 | AG1-423 C O1 | Adder | 9.66 MW | 8.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965552 | AG1-423 E O1 | Adder | 6.44 MW | 5.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965661 | AG1-434 C O1 | Adder | 2.74 MW | 2.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965662 | AG1-434 E O1 | Adder | 12.84 MW | 10.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966091 | AG1-478 C | Adder | 1.38 MW | 1.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966092 | AG1-478 E | Adder | 0.35 MW | 0.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966441 | AG1-513 C | Adder | 0.34 MW | 0.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966442 | AG1-513 E | Adder | 0.51 MW | 0.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966651 | AG1-535 O1 | Adder | 8.08 MW | 6.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 272364 | ESS H440N ;R | Adder | 1.75 MW | 1.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 290021 | O50 E | Adder | 13.21 MW | 11.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 290051 | GSG-6; E | Adder | 6.95 MW | 5.91 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 295109 | WESTBROOK E | Adder | 3.72 MW | 3.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 910542 | X3-005 E | Adder | 0.52 MW | 0.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 918052 | AA1-018 E OP | Adder | 10.77 MW | 9.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 920272 | AA2-123 E | Adder | 1.62 MW | 1.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 927451 | AC1-142A 1 | Adder | 2.82 MW | 2.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 927461 | AC1-142A 2 | Adder | 2.82 MW | 2.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933911 | AD1-013 C | Adder | 1.22 MW | 1.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933912 | AD1-013 E | Adder | 1.95 MW | 1.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933931 | AD1-016 C | Adder | 0.62 MW | 0.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933932 | AD1-016 E | Adder | 1.0 MW | 0.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934432 | AD1-067 E | Adder | 0.37 MW | 0.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934721 | AD1-100 C | Adder | 12.91 MW | 10.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934722 | AD1-100 E | Adder | 60.26 MW | 51.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936291 | AD2-038 C O1 | Adder | 2.15 MW | 1.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936292 | AD2-038 E O1 | Adder | 10.08 MW | 8.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936371 | AD2-047 C O1 | Adder | 3.01 MW | 2.56 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936372 | AD2-047 E O1 | Adder | 14.69 MW | 12.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936461 | AD2-060 | Adder | 1.77 MW | 1.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936511 | AD2-066 C O1 | Adder | 5.58 MW | 4.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936512 | AD2-066 E O1 | Adder | 3.72 MW | 3.17 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 937001 | AD2-134 C | Adder | 1.68 MW | 1.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 937002 | AD2-134 E | Adder | 6.72 MW | 5.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 937401 | AD2-194 1 | Adder | 5.21 MW | 4.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 937411 | AD2-194 2 | Adder | 5.22 MW | 4.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942421 | AE2-255 C O1 | Adder | 2.06 MW | 1.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942422 | AE2-255 E O1 | Adder | 6.19 MW | 5.26 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942651 | AE2-281 C O1 | Adder | 0.57 MW | 0.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942652 | AE2-281 E O1 | Adder | 3.51 MW | 2.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942991 | AE2-321 C | Adder | 5.42 MW | 4.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942992 | AE2-321 E | Adder | 2.67 MW | 2.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943121 | AE2-341 C | Adder | 8.46 MW | 7.19 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943122 | AE2-341 E | Adder | 4.15 MW | 3.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943591 | AF1-030 C O1 | Adder | 5.62 MW | 4.78 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943592 | AF1-030 E O1 | Adder | 2.78 MW | 2.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943801 | AF1-048 C | Adder | 2.54 MW | 2.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943802 | AF1-048 E | Adder | 1.69 MW | 1.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958481 | AF2-142 C | Adder | 7.43 MW | 6.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958482 | AF2-142 E | Adder | 4.95 MW | 4.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958491 | AF2-143 C | Adder | 7.34 MW | 6.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958492 | AF2-143 E | Adder | 4.89 MW | 4.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959081 | AF2-199 C | Adder | 4.74 MW | 4.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959082 | AF2-199 E | Adder | 2.37 MW | 2.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959091 | AF2-200 C O1 | Adder | 9.48 MW | 8.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959092 | AF2-200 E O1 | Adder | 6.32 MW | 5.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959102 | AF2-201 E O1 | Adder | 8.64 MW | 7.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959351 | AF2-226 C | Adder | 1.8 MW | 1.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959352 | AF2-226 E | Adder | 2.69 MW | 2.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960281 | AF2-319 C | Adder | 1.8 MW | 1.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960282 | AF2-319 E | Adder | 2.69 MW | 2.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960381 | AF2-329 | Adder | 3.55 MW | 3.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960581 | AF2-349 C | Adder | 14.43 MW | 12.26 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960582 | AF2-349 E | Adder | 9.62 MW | 8.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960591 | AF2-350 C O1 | Adder | 5.31 MW | 4.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960592 | AF2-350 E O1 | Adder | 3.54 MW | 3.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960601 | AF2-351 C O1 | Adder | 0.71 MW | 0.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960602 | AF2-351 E O1 | Adder | 1.06 MW | 0.9 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960721 | AF2-363 C O1 | Adder | 3.93 MW | 3.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960722 | AF2-363 E O1 | Adder | 2.62 MW | 2.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960751 | AF2-366 C | Adder | 4.63 MW | 3.94 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960752 | AF2-366 E | Adder | 3.09 MW | 2.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 961501 | AF2-441 C O1 | Adder | 7.4 MW | 6.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 961502 | AF2-441 E O1 | Adder | 11.11 MW | 9.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274751 | CRETE EC ;1U | 50/50 | 2.15 MW | 2.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274752 | CRETE EC ;2U | 50/50 | 2.15 MW | 2.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274753 | CRETE EC ;3U | 50/50 | 2.15 MW | 2.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274754 | CRETE EC ;4U | 50/50 | 2.15 MW | 2.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274788 | SE CHICAG;5U | Adder | 3.56 MW | 3.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274789 | SE CHICAG;6U | Adder | 3.57 MW | 3.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274790 | SE CHICAG;7U | Adder | 3.62 MW | 3.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274791 | SE CHICAG;8U | Adder | 3.62 MW | 3.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274792 | SE CHICAG;9U | Adder | 3.68 MW | 3.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274793 | SE CHICAG;0U | Adder | 3.68 MW | 3.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274794 | SE CHICAG;1U | Adder | 3.68 MW | 3.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274795 | SE CHICAG;2U | Adder | 3.68 MW | 3.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 275149 | KELLYCK ;1E | Adder | 12.39 MW | 10.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 276170 | Z1-108 E | Adder | 1.65 MW | 1.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 276591 | L-013 2 | Adder | 2.43 MW | 2.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 293061 | N-015 E | Adder | 10.24 MW | 8.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 293644 | O22 E1 | Adder | 7.32 MW | 6.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 293645 | O22 E2 | Adder | 14.22 MW | 12.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 293799 | PILOT HIL;1E | Adder | 12.39 MW | 10.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 294392 | P-010 E | Adder | 13.0 MW | 11.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 915011 | Y3-013 1 | Adder | 2.49 MW | 2.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 915021 | Y3-013 2 | Adder | 2.49 MW | 2.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 915031 | Y3-013 3 | Adder | 2.49 MW | 2.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 916221 | Z1-073 E | Adder | 3.61 MW | 3.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 930482 | AB1-089 CT | Adder | 24.26 MW | 20.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 930483 | AB1-089 ST | Adder | 19.29 MW | 16.39 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 930761 | AB1-122 CT1 | Adder | 45.6 MW | 38.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 930771 | AB1-122 CT2 | Adder | 49.73 MW | 42.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933411 | AC2-154 C | Adder | 1.68 MW | 1.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933412 | AC2-154 E | Adder | 2.74 MW | 2.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 938511 | AE1-070 1 | Adder | 6.13 MW | 5.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 938521 | AE1-070 2 | Adder | 5.6 MW | 4.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 938851 | AE1-113 C O1 | Adder | 5.45 MW | 4.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 938852 | AE1-113 E O1 | Adder | 19.32 MW | 16.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 939321 | AE1-163 C O1 | Adder | 4.0 MW | 3.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 939322 | AE1-163 E O1 | Adder | 24.55 MW | 20.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 939351 | AE1-166 C O1 | Adder | 6.83 MW | 5.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 939352 | AE1-166 E O1 | Adder | 6.3 MW | 5.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 940752 | AE2-062 E | Adder | 0.09 MW | 0.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 941131 | AE2-107 C | Adder | 4.36 MW | 3.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 941132 | AE2-107 E | Adder | 2.9 MW | 2.47 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 941551 | AE2-152 C O1 | Adder | 7.88 MW | 6.7 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 941552 | AE2-152 E O1 | Adder | 5.25 MW | 4.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 946502 | AF1-314 E | Adder | 13.56 MW | 11.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 946661 | AF1-330 C | Adder | 1.33 MW | 1.13 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 946662 | AF1-330 E | Adder | 0.29 MW | 0.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 946671 | AF1-331 | Adder | 1.59 MW | 1.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957331 | AF2-027 C | Adder | 1.66 MW | 1.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957332 | AF2-027 E | Adder | 2.49 MW | 2.11 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957371 | AF2-031 C O1 | Adder | 0.75 MW | 0.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957372 | AF2-031 E O1 | Adder | 1.13 MW | 0.96 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957401 | AF2-034 C | Adder | 0.95 MW | 0.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957402 | AF2-034 E | Adder | 0.81 MW | 0.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957471 | AF2-041 C | Adder | 14.21 MW | 12.08 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957472 | AF2-041 E | Adder | 7.11 MW | 6.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958011 | AF2-095 C O1 | Adder | 12.04 MW | 10.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958012 | AF2-095 E O1 | Adder | 5.66 MW | 4.82 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958021 | AF2-096 C | Adder | 23.51 MW | 19.98 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958022 | AF2-096 E | Adder | 11.06 MW | 9.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934101 | AD2-000 1 | Adder | 3.69 MW | 3.13 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934111 | AD2-000 2 | Adder | 4.02 MW | 3.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 290108 | LEEDK;1U E | Adder | 16.13 MW | 13.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 945351 | AF1-200 FTIR | Adder | 205.0 MW | 174.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965792 | AG1-447 BAT | Adder | 5.08 MW | 4.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.48 MW | 0.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.21 MW | 1.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.16 MW | 0.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 48.85 MW | 48.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.48 MW | 13.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.05 MW | 0.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.32 MW | 0.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.71 MW | 8.71 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.57 MW | 8.57 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.41 MW | 0.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.48 MW | 2.48 MW |
| Details for GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962691 | AG1-118 C O1 | Adder | 14.64 MW | 12.45 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962692 | AG1-118 E O1 | Adder | 9.76 MW | 8.3 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962701 | AG1-119 C | Adder | 14.44 MW | 12.27 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962702 | AG1-119 E | Adder | 9.62 MW | 8.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962711 | AG1-120 C O1 | Adder | 5.7 MW | 4.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962712 | AG1-120 E O1 | Adder | 3.8 MW | 3.23 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962781 | AG1-127 C | Adder | 4.62 MW | 3.93 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962782 | AG1-127 E | Adder | 3.08 MW | 2.62 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 964361 | AG1-298 O1 | Adder | 47.1 MW | 40.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965061 | AG1-371 | Adder | 2.36 MW | 2.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965081 | AG1-373 | Adder | 0.79 MW | 0.67 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965141 | AG1-379 C | Adder | 11.28 MW | 9.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965142 | AG1-379 E | Adder | 5.16 MW | 4.39 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965551 | AG1-423 C O1 | Adder | 9.63 MW | 8.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965552 | AG1-423 E O1 | Adder | 6.42 MW | 5.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965661 | AG1-434 C O1 | Adder | 2.73 MW | 2.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965662 | AG1-434 E O1 | Adder | 12.8 MW | 10.88 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966091 | AG1-478 C | Adder | 1.37 MW | 1.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966092 | AG1-478 E | Adder | 0.34 MW | 0.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966441 | AG1-513 C | Adder | 0.34 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966442 | AG1-513 E | Adder | 0.5 MW | 0.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966651 | AG1-535 O1 | Adder | 8.01 MW | 6.81 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 272364 | ESS H440N ;R | Adder | 1.74 MW | 1.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 13.16 MW | 11.19 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 6.93 MW | 5.89 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 3.71 MW | 3.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 910542 | X3-005 E | Adder | 0.52 MW | 0.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 10.71 MW | 9.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 1.61 MW | 1.37 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 2.81 MW | 2.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 2.81 MW | 2.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 1.22 MW | 1.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 1.95 MW | 1.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 0.61 MW | 0.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.0 MW | 0.85 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.37 MW | 0.31 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 12.85 MW | 10.92 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 59.95 MW | 50.96 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 2.14 MW | 1.82 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 10.04 MW | 8.53 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | Adder | 2.99 MW | 2.54 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | Adder | 14.6 MW | 12.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 1.76 MW | 1.5 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 5.56 MW | 4.73 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 3.71 MW | 3.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 1.68 MW | 1.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 6.7 MW | 5.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 5.18 MW | 4.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 5.19 MW | 4.41 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 2.06 MW | 1.75 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 6.17 MW | 5.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.57 MW | 0.48 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 3.49 MW | 2.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 5.4 MW | 4.59 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 2.66 MW | 2.26 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 8.41 MW | 7.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 4.13 MW | 3.51 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 5.6 MW | 4.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 2.77 MW | 2.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 2.53 MW | 2.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 1.68 MW | 1.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 7.39 MW | 6.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 4.92 MW | 4.19 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 7.31 MW | 6.21 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 4.87 MW | 4.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 4.72 MW | 4.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 2.36 MW | 2.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 9.44 MW | 8.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 6.3 MW | 5.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 8.62 MW | 7.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 1.79 MW | 1.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 2.68 MW | 2.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 1.79 MW | 1.52 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 2.68 MW | 2.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 3.53 MW | 3.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 14.37 MW | 12.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 9.58 MW | 8.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 5.28 MW | 4.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 3.52 MW | 2.99 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 0.7 MW | 0.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.06 MW | 0.9 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 3.91 MW | 3.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 2.61 MW | 2.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 4.61 MW | 3.92 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 3.07 MW | 2.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961501 | AF2-441 C O1 | Adder | 7.34 MW | 6.24 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961502 | AF2-441 E O1 | Adder | 11.01 MW | 9.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274751 | CRETE EC ;1U | 50/50 | 2.14 MW | 2.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274752 | CRETE EC ;2U | 50/50 | 2.14 MW | 2.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274753 | CRETE EC ;3U | 50/50 | 2.14 MW | 2.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274754 | CRETE EC ;4U | 50/50 | 2.14 MW | 2.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274788 | SE CHICAG;5U | Adder | 3.53 MW | 3.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274789 | SE CHICAG;6U | Adder | 3.54 MW | 3.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274790 | SE CHICAG;7U | Adder | 3.58 MW | 3.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274791 | SE CHICAG;8U | Adder | 3.58 MW | 3.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274792 | SE CHICAG;9U | Adder | 3.64 MW | 3.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274793 | SE CHICAG;0U | Adder | 3.64 MW | 3.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274794 | SE CHICAG;1U | Adder | 3.64 MW | 3.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274795 | SE CHICAG;2U | Adder | 3.64 MW | 3.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | Adder | 12.31 MW | 10.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 1.64 MW | 1.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276591 | L-013 2 | Adder | 2.42 MW | 2.06 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 10.19 MW | 8.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | Adder | 7.29 MW | 6.2 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | Adder | 14.15 MW | 12.03 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293799 | PILOT HIL;1E | Adder | 12.31 MW | 10.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 12.94 MW | 11.0 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 2.48 MW | 2.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 2.48 MW | 2.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 2.48 MW | 2.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 3.6 MW | 3.06 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930482 | AB1-089 CT | Adder | 24.18 MW | 20.55 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930483 | AB1-089 ST | Adder | 19.22 MW | 16.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930761 | AB1-122 CT1 | Adder | 45.46 MW | 38.64 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930771 | AB1-122 CT2 | Adder | 49.48 MW | 42.05 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933411 | AC2-154 C | Adder | 1.67 MW | 1.42 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933412 | AC2-154 E | Adder | 2.73 MW | 2.32 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 6.1 MW | 5.18 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 5.57 MW | 4.74 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C O1 | Adder | 5.43 MW | 4.61 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E O1 | Adder | 19.24 MW | 16.36 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 3.98 MW | 3.38 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 24.44 MW | 20.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 6.79 MW | 5.77 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 6.27 MW | 5.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.09 MW | 0.07 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 4.34 MW | 3.69 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 2.89 MW | 2.46 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 7.83 MW | 6.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 5.22 MW | 4.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 13.52 MW | 11.49 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 1.32 MW | 1.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.29 MW | 0.25 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 1.58 MW | 1.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 1.65 MW | 1.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 2.48 MW | 2.1 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957371 | AF2-031 C O1 | Adder | 0.74 MW | 0.63 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957372 | AF2-031 E O1 | Adder | 1.12 MW | 0.95 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 0.94 MW | 0.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 0.8 MW | 0.68 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 14.17 MW | 12.04 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 7.08 MW | 6.02 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 11.96 MW | 10.16 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 5.63 MW | 4.78 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | Adder | 23.37 MW | 19.87 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | Adder | 11.0 MW | 9.35 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 3.68 MW | 3.12 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 4.0 MW | 3.4 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 16.07 MW | 13.66 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 203.93 MW | 173.34 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965792 | AG1-447 BAT | Adder | 5.21 MW | 4.43 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.44 MW | 0.44 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.83 MW | 0.83 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.97 MW | 47.97 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.6 MW | 14.6 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.28 MW | 0.28 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.8 MW | 2.8 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.76 MW | 8.76 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.56 MW | 8.56 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.29 MW | 0.29 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.15 MW | 1.15 MW |
| GREENACRE; T-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.48 MW | 2.48 MW |
| Details for WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 962691 | AG1-118 C O1 | Adder | 58.87 MW | 50.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 962692 | AG1-118 E O1 | Adder | 39.25 MW | 33.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 962701 | AG1-119 C | Adder | 57.23 MW | 48.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 962702 | AG1-119 E | Adder | 38.15 MW | 32.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 962711 | AG1-120 C O1 | Adder | 22.77 MW | 19.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 962712 | AG1-120 E O1 | Adder | 15.18 MW | 12.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 962781 | AG1-127 C | Adder | 18.58 MW | 15.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 962782 | AG1-127 E | Adder | 12.36 MW | 10.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965061 | AG1-371 | Adder | 9.38 MW | 7.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965081 | AG1-373 | Adder | 3.13 MW | 2.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965141 | AG1-379 C | Adder | 42.64 MW | 36.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965142 | AG1-379 E | Adder | 19.52 MW | 16.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965551 | AG1-423 C O1 | Adder | 38.17 MW | 32.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965552 | AG1-423 E O1 | Adder | 25.44 MW | 21.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965661 | AG1-434 C O1 | Adder | 10.85 MW | 9.22 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965662 | AG1-434 E O1 | Adder | 50.8 MW | 43.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965681 | AG1-436 C | Adder | 23.78 MW | 20.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965682 | AG1-436 E | Adder | 15.85 MW | 13.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 965791 | AG1-447 | Adder | 17.44 MW | 14.82 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 966091 | AG1-478 C | Adder | 5.04 MW | 4.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 966092 | AG1-478 E | Adder | 1.27 MW | 1.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 966431 | AG1-512 C | Adder | 5.11 MW | 4.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 966432 | AG1-512 E | Adder | 7.67 MW | 6.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 966441 | AG1-513 C | Adder | 1.35 MW | 1.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 966442 | AG1-513 E | Adder | 2.02 MW | 1.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 272364 | ESS H440N ;R | Adder | 6.97 MW | 5.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 290021 | O50 E | Adder | 49.72 MW | 42.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 290051 | GSG-6; E | Adder | 27.72 MW | 23.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 295109 | WESTBROOK E | Adder | 14.84 MW | 12.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 918052 | AA1-018 E OP | Adder | 40.7 MW | 34.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 920272 | AA2-123 E | Adder | 6.36 MW | 5.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 926331 | AC1-110 1 | Adder | 5.01 MW | 4.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 926341 | AC1-110 2 | Adder | 5.01 MW | 4.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 927451 | AC1-142A 1 | Adder | 10.35 MW | 8.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 927461 | AC1-142A 2 | Adder | 10.34 MW | 8.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 933911 | AD1-013 C | Adder | 4.88 MW | 4.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 933912 | AD1-013 E | Adder | 7.8 MW | 6.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 933931 | AD1-016 C | Adder | 2.42 MW | 2.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 933932 | AD1-016 E | Adder | 3.94 MW | 3.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 934432 | AD1-067 E | Adder | 1.46 MW | 1.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 934721 | AD1-100 C | Adder | 50.03 MW | 42.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 934722 | AD1-100 E | Adder | 233.49 MW | 198.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 934971 | AD1-129 C | Adder | 2.35 MW | 2.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 934972 | AD1-129 E | Adder | 1.57 MW | 1.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 936291 | AD2-038 C O1 | Adder | 8.16 MW | 6.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 936292 | AD2-038 E O1 | Adder | 38.2 MW | 32.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 936371 | AD2-047 C O1 | Adder | 10.66 MW | 9.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 936372 | AD2-047 E O1 | Adder | 52.06 MW | 44.25 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 936461 | AD2-060 | Adder | 6.27 MW | 5.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 936511 | AD2-066 C O1 | Adder | 21.25 MW | 18.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 936512 | AD2-066 E O1 | Adder | 14.17 MW | 12.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 937001 | AD2-134 C | Adder | 6.71 MW | 5.7 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 937002 | AD2-134 E | Adder | 26.8 MW | 22.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 937311 | AD2-172 C | Adder | 6.42 MW | 5.45 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 937312 | AD2-172 E | Adder | 8.86 MW | 7.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 937401 | AD2-194 1 | Adder | 19.21 MW | 16.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 937411 | AD2-194 2 | Adder | 19.2 MW | 16.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 942421 | AE2-255 C O1 | Adder | 7.77 MW | 6.6 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 942422 | AE2-255 E O1 | Adder | 23.31 MW | 19.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 942651 | AE2-281 C O1 | Adder | 2.16 MW | 1.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 942652 | AE2-281 E O1 | Adder | 13.29 MW | 11.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 942991 | AE2-321 C | Adder | 21.31 MW | 18.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 942992 | AE2-321 E | Adder | 10.5 MW | 8.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 943121 | AE2-341 C | Adder | 34.66 MW | 29.46 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 943122 | AE2-341 E | Adder | 17.02 MW | 14.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 943591 | AF1-030 C O1 | Adder | 23.05 MW | 19.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 943592 | AF1-030 E O1 | Adder | 11.41 MW | 9.7 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 943801 | AF1-048 C | Adder | 9.96 MW | 8.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 943802 | AF1-048 E | Adder | 6.64 MW | 5.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 958481 | AF2-142 C | Adder | 28.07 MW | 23.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 958482 | AF2-142 E | Adder | 18.71 MW | 15.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 958491 | AF2-143 C | Adder | 27.82 MW | 23.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 958492 | AF2-143 E | Adder | 18.55 MW | 15.76 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 959081 | AF2-199 C | Adder | 18.77 MW | 15.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 959082 | AF2-199 E | Adder | 9.38 MW | 7.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 959091 | AF2-200 C O1 | Adder | 37.54 MW | 31.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 959092 | AF2-200 E O1 | Adder | 25.02 MW | 21.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 959101 | AF2-201 C O1 | Adder | 15.7 MW | 13.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 959102 | AF2-201 E O1 | Adder | 45.09 MW | 38.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 959351 | AF2-226 C | Adder | 6.14 MW | 5.22 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 959352 | AF2-226 E | Adder | 9.22 MW | 7.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960281 | AF2-319 C | Adder | 6.14 MW | 5.22 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960282 | AF2-319 E | Adder | 9.22 MW | 7.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960381 | AF2-329 | Adder | 14.54 MW | 12.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960581 | AF2-349 C | Adder | 56.67 MW | 48.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960582 | AF2-349 E | Adder | 37.78 MW | 32.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960591 | AF2-350 C O1 | Adder | 18.82 MW | 15.99 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960592 | AF2-350 E O1 | Adder | 12.54 MW | 10.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960601 | AF2-351 C O1 | Adder | 2.51 MW | 2.13 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960602 | AF2-351 E O1 | Adder | 3.76 MW | 3.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960681 | AF2-359 C | Adder | 23.78 MW | 20.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960682 | AF2-359 E | Adder | 15.85 MW | 13.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960721 | AF2-363 C O1 | Adder | 15.62 MW | 13.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960722 | AF2-363 E O1 | Adder | 10.41 MW | 8.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960751 | AF2-366 C | Adder | 18.53 MW | 15.75 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 960752 | AF2-366 E | Adder | 12.35 MW | 10.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 274770 | LINCOLN ;1U | 50/50 | 5.16 MW | 5.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 274772 | LINCOLN ;3U | 50/50 | 5.16 MW | 5.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 274773 | LINCOLN ;4U | 50/50 | 5.16 MW | 5.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 274774 | LINCOLN ;5U | 50/50 | 5.16 MW | 5.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 274775 | LINCOLN ;6U | 50/50 | 5.16 MW | 5.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 274776 | LINCOLN ;7U | 50/50 | 5.16 MW | 5.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 274777 | LINCOLN ;8U | 50/50 | 5.16 MW | 5.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 275149 | KELLYCK ;1E | Adder | 43.91 MW | 37.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 276170 | Z1-108 E | Adder | 6.47 MW | 5.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 276591 | L-013 2 | Adder | 9.66 MW | 8.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 293061 | N-015 E | Adder | 40.37 MW | 34.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 293644 | O22 E1 | Adder | 25.07 MW | 21.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 293645 | O22 E2 | Adder | 48.66 MW | 41.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 293799 | PILOT HIL;1E | Adder | 43.91 MW | 37.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 294392 | P-010 E | Adder | 51.26 MW | 43.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 294763 | P-046 E | Adder | 24.44 MW | 20.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 915011 | Y3-013 1 | Adder | 9.59 MW | 8.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 915021 | Y3-013 2 | Adder | 9.59 MW | 8.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 915031 | Y3-013 3 | Adder | 9.59 MW | 8.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 916221 | Z1-073 E | Adder | 14.4 MW | 12.24 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 930482 | AB1-089 CT | Adder | 95.65 MW | 81.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 930483 | AB1-089 ST | Adder | 76.05 MW | 64.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 930761 | AB1-122 CT1 | Adder | 179.68 MW | 152.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 930771 | AB1-122 CT2 | Adder | 184.52 MW | 156.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 933411 | AC2-154 C | Adder | 5.96 MW | 5.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 933412 | AC2-154 E | Adder | 9.72 MW | 8.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 938511 | AE1-070 1 | Adder | 22.57 MW | 19.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 938521 | AE1-070 2 | Adder | 20.65 MW | 17.55 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 938851 | AE1-113 C O1 | Adder | 20.51 MW | 17.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 938852 | AE1-113 E O1 | Adder | 72.72 MW | 61.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 938862 | AE1-114 E O1 | Adder | 24.78 MW | 21.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 939321 | AE1-163 C O1 | Adder | 15.15 MW | 12.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 939322 | AE1-163 E O1 | Adder | 93.04 MW | 79.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 939351 | AE1-166 C O1 | Adder | 25.71 MW | 21.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 939352 | AE1-166 E O1 | Adder | 23.73 MW | 20.17 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 939401 | AE1-172 C O1 | Adder | 13.8 MW | 11.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 939402 | AE1-172 E O1 | Adder | 64.75 MW | 55.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 940501 | AE2-035 C | Adder | 6.42 MW | 5.45 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 940502 | AE2-035 E | Adder | 8.86 MW | 7.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 940752 | AE2-062 E | Adder | 0.32 MW | 0.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 941131 | AE2-107 C | Adder | 17.43 MW | 14.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 941132 | AE2-107 E | Adder | 11.62 MW | 9.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 941551 | AE2-152 C O1 | Adder | 29.66 MW | 25.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 941552 | AE2-152 E O1 | Adder | 19.78 MW | 16.81 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 946501 | AF1-314 C | Adder | 11.36 MW | 9.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 946502 | AF1-314 E | Adder | 53.4 MW | 45.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 946661 | AF1-330 C | Adder | 5.22 MW | 4.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 946662 | AF1-330 E | Adder | 1.15 MW | 0.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 946671 | AF1-331 | Adder | 6.34 MW | 5.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 957331 | AF2-027 C | Adder | 6.39 MW | 5.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 957332 | AF2-027 E | Adder | 9.59 MW | 8.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 957401 | AF2-034 C | Adder | 3.46 MW | 2.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 957402 | AF2-034 E | Adder | 2.95 MW | 2.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 957471 | AF2-041 C | Adder | 56.3 MW | 47.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 957472 | AF2-041 E | Adder | 28.15 MW | 23.93 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 958011 | AF2-095 C O1 | Adder | 42.65 MW | 36.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 958012 | AF2-095 E O1 | Adder | 20.07 MW | 17.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 958021 | AF2-096 C | Adder | 82.7 MW | 70.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 958022 | AF2-096 E | Adder | 38.92 MW | 33.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 934101 | AD2-000 1 | Adder | 14.53 MW | 12.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 934111 | AD2-000 2 | Adder | 14.92 MW | 12.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 290108 | LEEDK;1U E | Adder | 64.54 MW | 54.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | 945351 | AF1-200 FTIR | Adder | 911.71 MW | 774.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.95 MW | 1.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 4.63 MW | 4.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.66 MW | 0.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.73 MW | 0.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 185.82 MW | 185.82 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 55.31 MW | 55.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 5.32 MW | 5.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.3 MW | 1.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 10.56 MW | 10.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.73 MW | 0.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 34.32 MW | 34.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.85 MW | 2.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 34.14 MW | 34.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.59 MW | 1.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.06 MW | 4.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o AEP_P5_#11277_05OLIV_05OLIV | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 9.63 MW | 9.63 MW |
| Details for NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962012 | AG1-044 E | 50/50 | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962701 | AG1-119 C | Adder | 26.65 MW | 22.65 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 962702 | AG1-119 E | Adder | 17.77 MW | 15.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966821 | AG1-553 C O1 | Adder | 45.28 MW | 38.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 966822 | AG1-553 E O1 | Adder | 9.12 MW | 7.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965551 | AG1-423 C O1 | Adder | 17.77 MW | 15.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965552 | AG1-423 E O1 | Adder | 11.84 MW | 10.07 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965931 | AG1-462 C O1 | Adder | 29.3 MW | 24.91 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965932 | AG1-462 E O1 | Adder | 19.54 MW | 16.61 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 272364 | ESS H440N ;R | Adder | 2.01 MW | 1.71 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 290051 | GSG-6; E | Adder | 8.22 MW | 6.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295109 | WESTBROOK E | Adder | 4.4 MW | 3.74 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 295111 | SUBLETTE E | Adder | 4.56 MW | 3.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919221 | AA1-146 | 50/50 | 7.02 MW | 7.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 919581 | AA2-030 C | 50/50 | 41.23 MW | 41.23 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933911 | AD1-013 C | Adder | 1.4 MW | 1.19 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 933912 | AD1-013 E | Adder | 2.23 MW | 1.9 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934051 | AD1-031 C O1 | Adder | 2.31 MW | 1.96 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934052 | AD1-031 E O1 | Adder | 3.76 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934432 | AD1-067 E | Adder | 0.43 MW | 0.37 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934971 | AD1-129 C | Adder | 0.67 MW | 0.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 934972 | AD1-129 E | Adder | 0.44 MW | 0.38 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937001 | AD2-134 C | Adder | 1.99 MW | 1.69 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937002 | AD2-134 E | Adder | 7.95 MW | 6.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937311 | AD2-172 C | Adder | 2.99 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 937312 | AD2-172 E | Adder | 4.13 MW | 3.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958911 | AF2-182 C | 50/50 | 41.62 MW | 41.62 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958912 | AF2-182 E | 50/50 | 27.75 MW | 27.75 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958921 | AF2-183 C | 50/50 | 7.4 MW | 7.4 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 958922 | AF2-183 E | 50/50 | 11.1 MW | 11.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959101 | AF2-201 C O1 | Adder | 7.32 MW | 6.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 959102 | AF2-201 E O1 | Adder | 21.01 MW | 17.86 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960581 | AF2-349 C | Adder | 15.01 MW | 12.76 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 960582 | AF2-349 E | Adder | 10.01 MW | 8.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961011 | AF2-392 C O1 | 50/50 | 7.79 MW | 7.79 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961012 | AF2-392 E O1 | 50/50 | 36.47 MW | 36.47 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961021 | AF2-393 O1 | 50/50 | 13.28 MW | 13.28 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 961031 | AF2-394 O1 | 50/50 | 8.85 MW | 8.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274715 | NELSON EC;1C | 50/50 | 7.53 MW | 7.53 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274716 | NELSON EC;1S | 50/50 | 5.49 MW | 5.49 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274717 | NELSON EC;2C | 50/50 | 7.59 MW | 7.59 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274718 | NELSON EC;2S | 50/50 | 5.54 MW | 5.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274761 | LEE CO EC;2U | 50/50 | 3.14 MW | 3.14 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274764 | LEE CO EC;5U | 50/50 | 3.15 MW | 3.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274765 | LEE CO EC;6U | 50/50 | 3.15 MW | 3.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274859 | EASYR;U1 E | Adder | 20.86 MW | 17.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 274860 | EASYR;U2 E | Adder | 20.86 MW | 17.73 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293516 | O-009 E1 | Adder | 16.04 MW | 13.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293517 | O-009 E2 | Adder | 8.15 MW | 6.92 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293518 | O-009 E3 | Adder | 8.97 MW | 7.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293715 | O-029 E | Adder | 17.15 MW | 14.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293716 | O-029 E | Adder | 9.4 MW | 7.99 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 293717 | O-029 E | Adder | 8.64 MW | 7.34 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294401 | BSHIL;1U E | Adder | 6.98 MW | 5.94 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294410 | BSHIL;2U E | Adder | 6.98 MW | 5.94 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 294763 | P-046 E | Adder | 11.39 MW | 9.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 916221 | Z1-073 E | Adder | 4.27 MW | 3.63 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925581 | AC1-033 C | Adder | 1.14 MW | 0.97 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 925582 | AC1-033 E | Adder | 7.66 MW | 6.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930482 | AB1-089 CT | Adder | 45.39 MW | 38.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 930483 | AB1-089 ST | Adder | 36.09 MW | 30.67 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938861 | AE1-114 C O1 | Adder | 5.75 MW | 4.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 938862 | AE1-114 E O1 | Adder | 19.61 MW | 16.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939051 | AE1-134 1 | 50/50 | 3.2 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 939061 | AE1-134 2 | 50/50 | 3.2 MW | 3.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940501 | AE2-035 C | Adder | 2.99 MW | 2.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 940502 | AE2-035 E | Adder | 4.13 MW | 3.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946151 | AF1-280 C O1 | 50/50 | 31.68 MW | 31.68 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946152 | AF1-280 E O1 | 50/50 | 14.57 MW | 14.57 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946161 | AF1-281 C O1 | 50/50 | 0.69 MW | 0.69 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946162 | AF1-281 E O1 | 50/50 | 3.93 MW | 3.93 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946321 | AF1-296 C O1 | Adder | 7.08 MW | 6.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946322 | AF1-296 E O1 | Adder | 33.16 MW | 28.19 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946501 | AF1-314 C | Adder | 5.3 MW | 4.5 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946502 | AF1-314 E | Adder | 24.88 MW | 21.15 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 946671 | AF1-331 | Adder | 1.82 MW | 1.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990901 | L-005 E | Adder | 9.46 MW | 8.04 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965082 | AG1-373 BAT | 50/50 | 11.42 MW | 11.42 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 965062 | AG1-371 BAT | 50/50 | 34.25 MW | 34.25 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951381 | J504 | External Queue | 4.22 MW | 4.22 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951421 | J514 | External Queue | 2.51 MW | 2.51 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951511 | J530 C | External Queue | 3.88 MW | 3.88 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 951512 | J530 E | External Queue | 15.5 MW | 15.5 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953921 | J855 C | External Queue | 1.26 MW | 1.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 953922 | J855 E | External Queue | 6.83 MW | 6.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 955971 | J1084 | External Queue | 22.66 MW | 22.66 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 956411 | J1131 | External Queue | 11.85 MW | 11.85 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990726 | J1377 | External Queue | 7.58 MW | 7.58 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 990947 | J1432 E | External Queue | 33.18 MW | 33.18 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | 991091 | J1477 | External Queue | 5.93 MW | 5.93 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.06 MW | 0.06 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.36 MW | 0.36 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.42 MW | 0.42 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.35 MW | 3.35 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 61.98 MW | 61.98 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.54 MW | 17.54 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.1 MW | 0.1 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.44 MW | 0.44 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.3 MW | 4.3 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.26 MW | 0.26 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.2 MW | 15.2 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.24 MW | 0.24 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.83 MW | 2.83 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.02 MW | 0.02 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.13 MW | 0.13 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.96 MW | 1.96 MW |
| NELSON ; B-AG1-434 TAP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT6-8__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.09 MW | 1.09 MW |
| Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 962691 | AG1-118 C O1 | Adder | 38.26 MW | 32.52 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 962692 | AG1-118 E O1 | Adder | 25.5 MW | 21.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 962701 | AG1-119 C | Adder | 37.71 MW | 32.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 962702 | AG1-119 E | Adder | 25.14 MW | 21.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 962711 | AG1-120 C O1 | Adder | 14.94 MW | 12.7 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 962712 | AG1-120 E O1 | Adder | 9.96 MW | 8.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 962781 | AG1-127 C | Adder | 12.1 MW | 10.28 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 962782 | AG1-127 E | Adder | 8.05 MW | 6.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 964361 | AG1-298 O1 | Adder | 108.65 MW | 92.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965141 | AG1-379 C | Adder | 28.92 MW | 24.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965142 | AG1-379 E | Adder | 13.24 MW | 11.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965551 | AG1-423 C O1 | Adder | 25.14 MW | 21.37 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965552 | AG1-423 E O1 | Adder | 16.76 MW | 14.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965681 | AG1-436 C | Adder | 16.19 MW | 13.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965682 | AG1-436 E | Adder | 10.79 MW | 9.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 965791 | AG1-447 | Adder | 11.87 MW | 10.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966091 | AG1-478 C | Adder | 3.44 MW | 2.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966092 | AG1-478 E | Adder | 0.86 MW | 0.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966431 | AG1-512 C | Adder | 3.49 MW | 2.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966432 | AG1-512 E | Adder | 5.23 MW | 4.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966441 | AG1-513 C | Adder | 0.87 MW | 0.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966442 | AG1-513 E | Adder | 1.3 MW | 1.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 966651 | AG1-535 O1 | Adder | 18.42 MW | 15.66 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 272364 | ESS H440N ;R | Adder | 4.59 MW | 3.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 290021 | O50 E | Adder | 33.72 MW | 28.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 290051 | GSG-6; E | Adder | 18.25 MW | 15.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 295109 | WESTBROOK E | Adder | 9.77 MW | 8.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 910542 | X3-005 E | Adder | 1.22 MW | 1.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 918052 | AA1-018 E OP | Adder | 27.83 MW | 23.65 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 920272 | AA2-123 E | Adder | 4.2 MW | 3.57 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 926331 | AC1-110 1 | Adder | 3.24 MW | 2.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 926341 | AC1-110 2 | Adder | 3.24 MW | 2.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 927451 | AC1-142A 1 | Adder | 6.96 MW | 5.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 927461 | AC1-142A 2 | Adder | 6.96 MW | 5.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933911 | AD1-013 C | Adder | 3.21 MW | 2.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933912 | AD1-013 E | Adder | 5.13 MW | 4.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933931 | AD1-016 C | Adder | 1.59 MW | 1.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933932 | AD1-016 E | Adder | 2.6 MW | 2.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 934432 | AD1-067 E | Adder | 0.96 MW | 0.82 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 934721 | AD1-100 C | Adder | 32.87 MW | 27.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 934722 | AD1-100 E | Adder | 153.41 MW | 130.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 934971 | AD1-129 C | Adder | 1.56 MW | 1.33 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 934972 | AD1-129 E | Adder | 1.04 MW | 0.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 936291 | AD2-038 C O1 | Adder | 5.58 MW | 4.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 936292 | AD2-038 E O1 | Adder | 26.13 MW | 22.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 936371 | AD2-047 C O1 | Adder | 7.42 MW | 6.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 936372 | AD2-047 E O1 | Adder | 36.24 MW | 30.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 936461 | AD2-060 | Adder | 4.37 MW | 3.71 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 936511 | AD2-066 C O1 | Adder | 14.54 MW | 12.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 936512 | AD2-066 E O1 | Adder | 9.7 MW | 8.24 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 937001 | AD2-134 C | Adder | 4.42 MW | 3.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 937002 | AD2-134 E | Adder | 17.64 MW | 15.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 937401 | AD2-194 1 | Adder | 12.95 MW | 11.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 937411 | AD2-194 2 | Adder | 12.96 MW | 11.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 942421 | AE2-255 C O1 | Adder | 5.27 MW | 4.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 942422 | AE2-255 E O1 | Adder | 15.81 MW | 13.44 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 942651 | AE2-281 C O1 | Adder | 1.48 MW | 1.26 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 942652 | AE2-281 E O1 | Adder | 9.09 MW | 7.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 942991 | AE2-321 C | Adder | 14.06 MW | 11.95 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 942992 | AE2-321 E | Adder | 6.93 MW | 5.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 943121 | AE2-341 C | Adder | 21.96 MW | 18.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 943122 | AE2-341 E | Adder | 10.78 MW | 9.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 943591 | AF1-030 C O1 | Adder | 14.6 MW | 12.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 943592 | AF1-030 E O1 | Adder | 7.23 MW | 6.14 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 943801 | AF1-048 C | Adder | 6.57 MW | 5.59 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 943802 | AF1-048 E | Adder | 4.38 MW | 3.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958481 | AF2-142 C | Adder | 19.19 MW | 16.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958482 | AF2-142 E | Adder | 12.79 MW | 10.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958491 | AF2-143 C | Adder | 19.02 MW | 16.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958492 | AF2-143 E | Adder | 12.68 MW | 10.78 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 959081 | AF2-199 C | Adder | 0.17 MW | 0.14 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 959091 | AF2-200 C O1 | Adder | 24.85 MW | 21.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 959092 | AF2-200 E O1 | Adder | 16.57 MW | 14.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 959351 | AF2-226 C | Adder | 4.26 MW | 3.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 959352 | AF2-226 E | Adder | 6.39 MW | 5.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960281 | AF2-319 C | Adder | 4.26 MW | 3.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960282 | AF2-319 E | Adder | 6.39 MW | 5.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960381 | AF2-329 | Adder | 9.21 MW | 7.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960581 | AF2-349 C | Adder | 37.53 MW | 31.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960582 | AF2-349 E | Adder | 25.02 MW | 21.27 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960591 | AF2-350 C O1 | Adder | 13.1 MW | 11.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960592 | AF2-350 E O1 | Adder | 8.73 MW | 7.42 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960601 | AF2-351 C O1 | Adder | 1.75 MW | 1.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960602 | AF2-351 E O1 | Adder | 2.62 MW | 2.23 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960681 | AF2-359 C | Adder | 16.19 MW | 13.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960682 | AF2-359 E | Adder | 10.79 MW | 9.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960721 | AF2-363 C O1 | Adder | 10.25 MW | 8.71 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960722 | AF2-363 E O1 | Adder | 6.83 MW | 5.81 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960751 | AF2-366 C | Adder | 12.06 MW | 10.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 960752 | AF2-366 E | Adder | 8.04 MW | 6.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 961501 | AF2-441 C O1 | Adder | 17.42 MW | 14.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 961502 | AF2-441 E O1 | Adder | 26.12 MW | 22.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 243441 | 05CKG2 | 50/50 | 56.04 MW | 56.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274770 | LINCOLN ;1U | 50/50 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274771 | LINCOLN ;2U | 50/50 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274772 | LINCOLN ;3U | 50/50 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274773 | LINCOLN ;4U | 50/50 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274774 | LINCOLN ;5U | 50/50 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274775 | LINCOLN ;6U | 50/50 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274776 | LINCOLN ;7U | 50/50 | 3.05 MW | 3.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274788 | SE CHICAG;5U | Adder | 8.21 MW | 6.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274789 | SE CHICAG;6U | Adder | 8.24 MW | 7.0 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274790 | SE CHICAG;7U | Adder | 8.34 MW | 7.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274791 | SE CHICAG;8U | Adder | 8.34 MW | 7.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274792 | SE CHICAG;9U | Adder | 8.33 MW | 7.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274793 | SE CHICAG;0U | Adder | 8.33 MW | 7.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274794 | SE CHICAG;1U | Adder | 8.33 MW | 7.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 274795 | SE CHICAG;2U | Adder | 8.33 MW | 7.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 275149 | KELLYCK ;1E | Adder | 30.56 MW | 25.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 276170 | Z1-108 E | Adder | 4.25 MW | 3.61 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 276591 | L-013 2 | Adder | 6.25 MW | 5.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 293061 | N-015 E | Adder | 26.19 MW | 22.26 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 293644 | O22 E1 | Adder | 17.38 MW | 14.77 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 293645 | O22 E2 | Adder | 33.73 MW | 28.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 293799 | PILOT HIL;1E | Adder | 30.56 MW | 25.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 294392 | P-010 E | Adder | 33.26 MW | 28.27 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 915011 | Y3-013 1 | Adder | 6.36 MW | 5.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 915021 | Y3-013 2 | Adder | 6.36 MW | 5.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 915031 | Y3-013 3 | Adder | 6.36 MW | 5.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 916221 | Z1-073 E | Adder | 9.48 MW | 8.06 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 930761 | AB1-122 CT1 | Adder | 120.33 MW | 102.28 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 930771 | AB1-122 CT2 | Adder | 123.88 MW | 105.3 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933281 | AC2-140 C | 50/50 | 1.85 MW | 1.85 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933282 | AC2-140 E | 50/50 | 0.57 MW | 0.57 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933411 | AC2-154 C | Adder | 4.15 MW | 3.52 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 933412 | AC2-154 E | Adder | 6.77 MW | 5.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 938511 | AE1-070 1 | Adder | 15.22 MW | 12.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 938521 | AE1-070 2 | Adder | 13.93 MW | 11.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 938851 | AE1-113 C O1 | Adder | 13.91 MW | 11.82 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 938852 | AE1-113 E O1 | Adder | 49.32 MW | 41.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 939321 | AE1-163 C O1 | Adder | 10.36 MW | 8.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 939322 | AE1-163 E O1 | Adder | 63.62 MW | 54.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 939351 | AE1-166 C O1 | Adder | 17.09 MW | 14.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 939352 | AE1-166 E O1 | Adder | 15.78 MW | 13.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 939401 | AE1-172 C O1 | Adder | 9.36 MW | 7.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 939402 | AE1-172 E O1 | Adder | 43.94 MW | 37.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 940752 | AE2-062 E | Adder | 0.22 MW | 0.18 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 941131 | AE2-107 C | Adder | 11.38 MW | 9.67 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 941132 | AE2-107 E | Adder | 7.59 MW | 6.45 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 941551 | AE2-152 C O1 | Adder | 19.72 MW | 16.77 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 941552 | AE2-152 E O1 | Adder | 13.15 MW | 11.18 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 946661 | AF1-330 C | Adder | 3.44 MW | 2.93 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 946662 | AF1-330 E | Adder | 0.76 MW | 0.64 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 946671 | AF1-331 | Adder | 4.17 MW | 3.54 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957331 | AF2-027 C | Adder | 4.24 MW | 3.6 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957332 | AF2-027 E | Adder | 6.36 MW | 5.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957371 | AF2-031 C O1 | Adder | 1.74 MW | 1.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957372 | AF2-031 E O1 | Adder | 2.6 MW | 2.21 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957401 | AF2-034 C | Adder | 2.33 MW | 1.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957402 | AF2-034 E | Adder | 1.99 MW | 1.69 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957471 | AF2-041 C | Adder | 37.27 MW | 31.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 957472 | AF2-041 E | Adder | 18.64 MW | 15.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958011 | AF2-095 C O1 | Adder | 29.69 MW | 25.23 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958012 | AF2-095 E O1 | Adder | 13.97 MW | 11.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958021 | AF2-096 C | Adder | 55.85 MW | 47.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 958022 | AF2-096 E | Adder | 26.28 MW | 22.34 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 934101 | AD2-000 1 | Adder | 9.73 MW | 8.27 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 934111 | AD2-000 2 | Adder | 10.02 MW | 8.52 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 290108 | LEEDK;1U E | Adder | 42.15 MW | 35.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | 945351 | AF1-200 FTIR | Adder | 543.03 MW | 461.57 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.77 MW | 1.77 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.51 MW | 0.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.77 MW | 1.77 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 205.9 MW | 205.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 75.26 MW | 75.26 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 5.5 MW | 5.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.11 MW | 1.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.53 MW | 11.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.29 MW | 3.29 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 25.74 MW | 25.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.89 MW | 2.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 35.26 MW | 35.26 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.79 MW | 0.79 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 6.33 MW | 6.33 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 6.46 MW | 6.46 MW |
| Details for 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 962691 | AG1-118 C O1 | Adder | 41.3 MW | 35.1 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 962692 | AG1-118 E O1 | Adder | 27.53 MW | 23.4 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 962701 | AG1-119 C | Adder | 40.66 MW | 34.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 962702 | AG1-119 E | Adder | 27.11 MW | 23.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 962711 | AG1-120 C O1 | Adder | 16.11 MW | 13.69 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 962712 | AG1-120 E O1 | Adder | 10.74 MW | 9.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 962781 | AG1-127 C | Adder | 13.05 MW | 11.1 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 962782 | AG1-127 E | Adder | 8.69 MW | 7.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 964361 | AG1-298 O1 | Adder | 118.44 MW | 100.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965141 | AG1-379 C | Adder | 31.21 MW | 26.53 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965142 | AG1-379 E | Adder | 14.29 MW | 12.14 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965551 | AG1-423 C O1 | Adder | 27.11 MW | 23.05 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965552 | AG1-423 E O1 | Adder | 18.08 MW | 15.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965681 | AG1-436 C | Adder | 17.94 MW | 15.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965682 | AG1-436 E | Adder | 11.96 MW | 10.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 965791 | AG1-447 | Adder | 13.16 MW | 11.18 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966091 | AG1-478 C | Adder | 3.73 MW | 3.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966092 | AG1-478 E | Adder | 0.94 MW | 0.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966431 | AG1-512 C | Adder | 3.8 MW | 3.23 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966432 | AG1-512 E | Adder | 5.7 MW | 4.84 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966441 | AG1-513 C | Adder | 0.94 MW | 0.8 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966442 | AG1-513 E | Adder | 1.41 MW | 1.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 966651 | AG1-535 O1 | Adder | 20.1 MW | 17.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 247967 | 05OLIV SLR E | Adder | 0.56 MW | 0.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 272364 | ESS H440N ;R | Adder | 4.94 MW | 4.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 290021 | O50 E | Adder | 36.4 MW | 30.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 290051 | GSG-6; E | Adder | 19.66 MW | 16.71 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 295109 | WESTBROOK E | Adder | 10.53 MW | 8.95 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 910542 | X3-005 E | Adder | 1.33 MW | 1.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 918052 | AA1-018 E OP | Adder | 30.1 MW | 25.59 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 920272 | AA2-123 E | Adder | 4.53 MW | 3.85 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 926331 | AC1-110 1 | Adder | 3.51 MW | 2.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 926341 | AC1-110 2 | Adder | 3.51 MW | 2.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 927451 | AC1-142A 1 | Adder | 7.54 MW | 6.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 927461 | AC1-142A 2 | Adder | 7.54 MW | 6.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933911 | AD1-013 C | Adder | 3.46 MW | 2.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933912 | AD1-013 E | Adder | 5.53 MW | 4.7 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933931 | AD1-016 C | Adder | 1.72 MW | 1.46 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933932 | AD1-016 E | Adder | 2.81 MW | 2.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 934432 | AD1-067 E | Adder | 1.04 MW | 0.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 934721 | AD1-100 C | Adder | 35.59 MW | 30.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 934722 | AD1-100 E | Adder | 166.11 MW | 141.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 934971 | AD1-129 C | Adder | 1.68 MW | 1.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 934972 | AD1-129 E | Adder | 1.12 MW | 0.95 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936291 | AD2-038 C O1 | Adder | 6.03 MW | 5.12 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936292 | AD2-038 E O1 | Adder | 28.22 MW | 23.99 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936371 | AD2-047 C O1 | Adder | 8.06 MW | 6.85 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936372 | AD2-047 E O1 | Adder | 39.34 MW | 33.44 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936461 | AD2-060 | Adder | 4.74 MW | 4.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936511 | AD2-066 C O1 | Adder | 15.68 MW | 13.33 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 936512 | AD2-066 E O1 | Adder | 10.45 MW | 8.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 937001 | AD2-134 C | Adder | 4.76 MW | 4.04 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 937002 | AD2-134 E | Adder | 19.01 MW | 16.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 937401 | AD2-194 1 | Adder | 14.03 MW | 11.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 937411 | AD2-194 2 | Adder | 14.03 MW | 11.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942421 | AE2-255 C O1 | Adder | 5.69 MW | 4.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942422 | AE2-255 E O1 | Adder | 17.06 MW | 14.5 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942651 | AE2-281 C O1 | Adder | 1.6 MW | 1.36 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942652 | AE2-281 E O1 | Adder | 9.82 MW | 8.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942991 | AE2-321 C | Adder | 15.17 MW | 12.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 942992 | AE2-321 E | Adder | 7.47 MW | 6.35 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 943121 | AE2-341 C | Adder | 23.75 MW | 20.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 943122 | AE2-341 E | Adder | 11.66 MW | 9.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 943591 | AF1-030 C O1 | Adder | 15.79 MW | 13.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 943592 | AF1-030 E O1 | Adder | 7.81 MW | 6.64 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 943801 | AF1-048 C | Adder | 7.09 MW | 6.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 943802 | AF1-048 E | Adder | 4.73 MW | 4.02 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 958481 | AF2-142 C | Adder | 20.76 MW | 17.64 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 958482 | AF2-142 E | Adder | 13.84 MW | 11.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 958491 | AF2-143 C | Adder | 20.55 MW | 17.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 958492 | AF2-143 E | Adder | 13.7 MW | 11.64 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 959001 | AF2-191 C O1 | Adder | 14.8 MW | 12.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 959002 | AF2-191 E O1 | Adder | 9.87 MW | 8.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 959351 | AF2-226 C | Adder | 4.61 MW | 3.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 959352 | AF2-226 E | Adder | 6.91 MW | 5.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960281 | AF2-319 C | Adder | 4.61 MW | 3.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960282 | AF2-319 E | Adder | 6.91 MW | 5.88 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960381 | AF2-329 | Adder | 9.96 MW | 8.47 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960581 | AF2-349 C | Adder | 40.45 MW | 34.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960582 | AF2-349 E | Adder | 26.97 MW | 22.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960591 | AF2-350 C O1 | Adder | 14.22 MW | 12.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960592 | AF2-350 E O1 | Adder | 9.48 MW | 8.06 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960601 | AF2-351 C O1 | Adder | 1.9 MW | 1.61 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960602 | AF2-351 E O1 | Adder | 2.84 MW | 2.42 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960681 | AF2-359 C | Adder | 17.94 MW | 15.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960682 | AF2-359 E | Adder | 11.96 MW | 10.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960721 | AF2-363 C O1 | Adder | 11.05 MW | 9.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960722 | AF2-363 E O1 | Adder | 7.37 MW | 6.26 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960751 | AF2-366 C | Adder | 13.02 MW | 11.06 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 960752 | AF2-366 E | Adder | 8.68 MW | 7.38 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 961501 | AF2-441 C O1 | Adder | 18.97 MW | 16.13 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 961502 | AF2-441 E O1 | Adder | 28.46 MW | 24.19 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 243441 | 05CKG2 | 50/50 | 61.25 MW | 61.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 244415 | 05OLIV SLR C | Adder | 0.56 MW | 0.48 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274771 | LINCOLN ;2U | 50/50 | 3.31 MW | 3.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274772 | LINCOLN ;3U | 50/50 | 3.31 MW | 3.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274773 | LINCOLN ;4U | 50/50 | 3.31 MW | 3.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274774 | LINCOLN ;5U | 50/50 | 3.31 MW | 3.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274775 | LINCOLN ;6U | 50/50 | 3.31 MW | 3.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274776 | LINCOLN ;7U | 50/50 | 3.31 MW | 3.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274777 | LINCOLN ;8U | 50/50 | 3.31 MW | 3.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274788 | SE CHICAG;5U | Adder | 8.96 MW | 7.62 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274789 | SE CHICAG;6U | Adder | 8.99 MW | 7.64 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274790 | SE CHICAG;7U | Adder | 9.11 MW | 7.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274791 | SE CHICAG;8U | Adder | 9.11 MW | 7.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274792 | SE CHICAG;9U | Adder | 9.1 MW | 7.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274793 | SE CHICAG;0U | Adder | 9.1 MW | 7.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274794 | SE CHICAG;1U | Adder | 9.1 MW | 7.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 274795 | SE CHICAG;2U | Adder | 9.1 MW | 7.73 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 275149 | KELLYCK ;1E | Adder | 33.18 MW | 28.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 276170 | Z1-108 E | Adder | 4.59 MW | 3.9 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 276591 | L-013 2 | Adder | 6.76 MW | 5.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 293061 | N-015 E | Adder | 28.34 MW | 24.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 293644 | O22 E1 | Adder | 18.8 MW | 15.98 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 293645 | O22 E2 | Adder | 36.5 MW | 31.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 293799 | PILOT HIL;1E | Adder | 33.18 MW | 28.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 294392 | P-010 E | Adder | 35.99 MW | 30.59 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 915011 | Y3-013 1 | Adder | 6.86 MW | 5.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 915021 | Y3-013 2 | Adder | 6.86 MW | 5.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 915031 | Y3-013 3 | Adder | 6.86 MW | 5.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 916221 | Z1-073 E | Adder | 10.21 MW | 8.68 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930482 | AB1-089 CT | Adder | 68.35 MW | 58.09 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930483 | AB1-089 ST | Adder | 34.05 MW | 28.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930761 | AB1-122 CT1 | Adder | 129.6 MW | 110.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 930771 | AB1-122 CT2 | Adder | 134.08 MW | 113.97 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933281 | AC2-140 C | 50/50 | 2.03 MW | 2.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933282 | AC2-140 E | 50/50 | 0.63 MW | 0.63 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933411 | AC2-154 C | Adder | 4.5 MW | 3.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 933412 | AC2-154 E | Adder | 7.35 MW | 6.24 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 938511 | AE1-070 1 | Adder | 16.48 MW | 14.01 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 938521 | AE1-070 2 | Adder | 15.08 MW | 12.82 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 938851 | AE1-113 C O1 | Adder | 15.01 MW | 12.76 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 938852 | AE1-113 E O1 | Adder | 53.23 MW | 45.25 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 939321 | AE1-163 C O1 | Adder | 11.19 MW | 9.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 939322 | AE1-163 E O1 | Adder | 68.73 MW | 58.42 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 939351 | AE1-166 C O1 | Adder | 18.52 MW | 15.75 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 939352 | AE1-166 E O1 | Adder | 17.1 MW | 14.54 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 939401 | AE1-172 C O1 | Adder | 10.07 MW | 8.56 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 939402 | AE1-172 E O1 | Adder | 47.25 MW | 40.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 940752 | AE2-062 E | Adder | 0.24 MW | 0.2 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941131 | AE2-107 C | Adder | 12.27 MW | 10.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941132 | AE2-107 E | Adder | 8.18 MW | 6.96 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941551 | AE2-152 C O1 | Adder | 21.37 MW | 18.17 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 941552 | AE2-152 E O1 | Adder | 14.25 MW | 12.11 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 946661 | AF1-330 C | Adder | 3.71 MW | 3.16 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 946662 | AF1-330 E | Adder | 0.82 MW | 0.69 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 946671 | AF1-331 | Adder | 4.49 MW | 3.82 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957331 | AF2-027 C | Adder | 4.58 MW | 3.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957332 | AF2-027 E | Adder | 6.86 MW | 5.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957371 | AF2-031 C O1 | Adder | 1.89 MW | 1.61 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957372 | AF2-031 E O1 | Adder | 2.84 MW | 2.41 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957401 | AF2-034 C | Adder | 2.53 MW | 2.15 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 957402 | AF2-034 E | Adder | 2.15 MW | 1.83 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 958011 | AF2-095 C O1 | Adder | 32.23 MW | 27.39 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 958012 | AF2-095 E O1 | Adder | 15.17 MW | 12.89 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 958021 | AF2-096 C | Adder | 60.6 MW | 51.51 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 958022 | AF2-096 E | Adder | 28.52 MW | 24.24 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 934101 | AD2-000 1 | Adder | 10.48 MW | 8.91 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 934111 | AD2-000 2 | Adder | 10.84 MW | 9.22 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 290108 | LEEDK;1U E | Adder | 45.46 MW | 38.64 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | 945351 | AF1-200 FTIR | Adder | 588.14 MW | 499.92 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.03 MW | 2.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.65 MW | 0.65 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.43 MW | 1.43 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 222.34 MW | 222.34 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 72.31 MW | 72.31 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 5.61 MW | 5.61 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.32 MW | 1.32 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.03 MW | 11.03 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.74 MW | 1.74 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 27.08 MW | 27.08 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.94 MW | 2.94 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 35.95 MW | 35.95 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.65 MW | 0.65 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.58 MW | 5.58 MW |
| 05DUMONT-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 6.95 MW | 6.95 MW |
| Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 962691 | AG1-118 C O1 | Adder | 17.76 MW | 15.1 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 962692 | AG1-118 E O1 | Adder | 11.84 MW | 10.06 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 962701 | AG1-119 C | Adder | 17.48 MW | 14.86 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 962702 | AG1-119 E | Adder | 11.66 MW | 9.91 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 962711 | AG1-120 C O1 | Adder | 6.92 MW | 5.88 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 962712 | AG1-120 E O1 | Adder | 4.61 MW | 3.92 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 962781 | AG1-127 C | Adder | 5.61 MW | 4.77 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 962782 | AG1-127 E | Adder | 3.73 MW | 3.17 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 964361 | AG1-298 O1 | Adder | 49.51 MW | 42.09 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 964581 | AG1-321 C O1 | Adder | 12.28 MW | 10.43 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 964582 | AG1-321 E O1 | Adder | 7.15 MW | 6.08 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 965061 | AG1-371 | Adder | 2.86 MW | 2.43 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 965081 | AG1-373 | Adder | 0.95 MW | 0.81 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 965141 | AG1-379 C | Adder | 13.61 MW | 11.57 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 965142 | AG1-379 E | Adder | 6.23 MW | 5.3 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 965551 | AG1-423 C O1 | Adder | 11.66 MW | 9.91 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 965552 | AG1-423 E O1 | Adder | 7.77 MW | 6.61 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 965662 | AG1-434 E O1 | Adder | 6.82 MW | 5.79 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 966091 | AG1-478 C | Adder | 1.68 MW | 1.42 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 966092 | AG1-478 E | Adder | 0.42 MW | 0.36 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 966441 | AG1-513 C | Adder | 0.41 MW | 0.35 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 966442 | AG1-513 E | Adder | 0.61 MW | 0.52 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 272364 | ESS H440N ;R | Adder | 2.12 MW | 1.8 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 290021 | O50 E | Adder | 15.87 MW | 13.49 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 290051 | GSG-6; E | Adder | 8.41 MW | 7.15 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.5 MW | 3.83 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 910542 | X3-005 E | Adder | 0.59 MW | 0.5 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 13.38 MW | 11.38 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 920272 | AA2-123 E | Adder | 1.95 MW | 1.66 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.52 MW | 1.29 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.52 MW | 1.29 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.34 MW | 2.84 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.34 MW | 2.84 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.48 MW | 1.26 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.37 MW | 2.01 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.74 MW | 0.63 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.21 MW | 1.03 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.44 MW | 0.38 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 934721 | AD1-100 C | Adder | 19.21 MW | 16.33 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 934722 | AD1-100 E | Adder | 89.63 MW | 76.19 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.72 MW | 0.61 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.48 MW | 0.41 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 2.66 MW | 2.26 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 12.44 MW | 10.58 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.75 MW | 3.19 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 18.29 MW | 15.55 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.2 MW | 1.87 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.82 MW | 5.8 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.55 MW | 3.86 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.04 MW | 1.73 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 937002 | AD2-134 E | Adder | 8.13 MW | 6.91 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 6.22 MW | 5.29 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 6.22 MW | 5.29 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.48 MW | 2.11 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 7.44 MW | 6.33 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.7 MW | 0.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 4.33 MW | 3.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.54 MW | 5.55 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 942992 | AE2-321 E | Adder | 3.22 MW | 2.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 943121 | AE2-341 C | Adder | 10.23 MW | 8.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 943122 | AE2-341 E | Adder | 5.02 MW | 4.27 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.8 MW | 5.78 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.36 MW | 2.86 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.06 MW | 2.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.04 MW | 1.73 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 958481 | AF2-142 C | Adder | 9.23 MW | 7.84 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 958482 | AF2-142 E | Adder | 6.15 MW | 5.23 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 958491 | AF2-143 C | Adder | 9.06 MW | 7.7 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 958492 | AF2-143 E | Adder | 6.04 MW | 5.13 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.73 MW | 4.87 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 959082 | AF2-199 E | Adder | 2.86 MW | 2.43 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 11.45 MW | 9.73 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.63 MW | 6.49 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 959351 | AF2-226 C | Adder | 2.04 MW | 1.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 959352 | AF2-226 E | Adder | 3.06 MW | 2.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960281 | AF2-319 C | Adder | 2.04 MW | 1.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960282 | AF2-319 E | Adder | 3.06 MW | 2.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960381 | AF2-329 | Adder | 4.29 MW | 3.65 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960581 | AF2-349 C | Adder | 17.4 MW | 14.79 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960582 | AF2-349 E | Adder | 11.6 MW | 9.86 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 6.61 MW | 5.62 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 4.41 MW | 3.75 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.88 MW | 0.75 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.32 MW | 1.12 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.74 MW | 4.03 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 3.16 MW | 2.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.59 MW | 4.75 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.73 MW | 3.17 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 961501 | AF2-441 C O1 | Adder | 8.01 MW | 6.81 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 961502 | AF2-441 E O1 | Adder | 12.02 MW | 10.21 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 274770 | LINCOLN ;1U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 274771 | LINCOLN ;2U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 274773 | LINCOLN ;4U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 274774 | LINCOLN ;5U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 274775 | LINCOLN ;6U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 274776 | LINCOLN ;7U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 274777 | LINCOLN ;8U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 15.43 MW | 13.12 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 276170 | Z1-108 E | Adder | 1.99 MW | 1.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 276591 | L-013 2 | Adder | 2.93 MW | 2.49 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 293061 | N-015 E | Adder | 12.74 MW | 10.83 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 293644 | O22 E1 | Adder | 8.34 MW | 7.09 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 293645 | O22 E2 | Adder | 16.18 MW | 13.75 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 293777 | CAYUG;1U E | Adder | 13.19 MW | 11.21 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 293778 | CAYUG;2U E | Adder | 13.19 MW | 11.21 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 293799 | PILOT HIL;1E | Adder | 15.43 MW | 13.12 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 294392 | P-010 E | Adder | 16.18 MW | 13.75 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 2.98 MW | 2.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 2.98 MW | 2.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 2.98 MW | 2.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.37 MW | 3.71 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 930482 | AB1-089 CT | Adder | 29.3 MW | 24.9 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 930483 | AB1-089 ST | Adder | 23.29 MW | 19.8 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 930761 | AB1-122 CT1 | Adder | 55.84 MW | 47.46 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 930771 | AB1-122 CT2 | Adder | 59.11 MW | 50.24 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.09 MW | 1.78 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.42 MW | 2.9 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 7.31 MW | 6.21 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.68 MW | 5.68 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 938851 | AE1-113 C O1 | Adder | 6.55 MW | 5.57 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 938852 | AE1-113 E O1 | Adder | 23.22 MW | 19.73 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 4.93 MW | 4.19 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 30.31 MW | 25.76 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 9.48 MW | 8.06 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 8.75 MW | 7.44 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 939401 | AE1-172 C O1 | Adder | 5.26 MW | 4.47 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 939402 | AE1-172 E O1 | Adder | 24.7 MW | 20.99 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.1 MW | 0.09 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 941131 | AE2-107 C | Adder | 5.27 MW | 4.48 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.51 MW | 2.98 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 10.94 MW | 9.3 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 7.29 MW | 6.2 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.6 MW | 1.36 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.35 MW | 0.3 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.92 MW | 1.64 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 957331 | AF2-027 C | Adder | 1.99 MW | 1.69 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 957332 | AF2-027 E | Adder | 2.98 MW | 2.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.12 MW | 0.95 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.95 MW | 0.81 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 957471 | AF2-041 C | Adder | 17.18 MW | 14.6 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 957472 | AF2-041 E | Adder | 8.59 MW | 7.3 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 14.99 MW | 12.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 7.05 MW | 6.0 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 958021 | AF2-096 C | Adder | 28.52 MW | 24.24 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 958022 | AF2-096 E | Adder | 13.42 MW | 11.41 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.52 MW | 3.84 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.78 MW | 4.06 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 19.51 MW | 16.58 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 250.03 MW | 212.53 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.56 MW | 1.56 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 59.04 MW | 59.04 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.7 MW | 17.7 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.74 MW | 1.74 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.32 MW | 3.32 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.24 MW | 0.24 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.73 MW | 10.73 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.93 MW | 0.93 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 11.15 MW | 11.15 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.54 MW | 0.54 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.99 MW | 2.99 MW |
| Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 962691 | AG1-118 C O1 | Adder | 17.76 MW | 15.1 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 962692 | AG1-118 E O1 | Adder | 11.84 MW | 10.06 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 962701 | AG1-119 C | Adder | 17.48 MW | 14.86 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 962702 | AG1-119 E | Adder | 11.66 MW | 9.91 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 962711 | AG1-120 C O1 | Adder | 6.92 MW | 5.88 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 962712 | AG1-120 E O1 | Adder | 4.61 MW | 3.92 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 962781 | AG1-127 C | Adder | 5.61 MW | 4.77 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 962782 | AG1-127 E | Adder | 3.73 MW | 3.17 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 964361 | AG1-298 O1 | Adder | 49.51 MW | 42.09 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 964581 | AG1-321 C O1 | Adder | 12.28 MW | 10.43 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 964582 | AG1-321 E O1 | Adder | 7.15 MW | 6.08 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 965061 | AG1-371 | Adder | 2.86 MW | 2.43 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 965081 | AG1-373 | Adder | 0.95 MW | 0.81 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 965141 | AG1-379 C | Adder | 13.61 MW | 11.57 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 965142 | AG1-379 E | Adder | 6.23 MW | 5.3 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 965551 | AG1-423 C O1 | Adder | 11.66 MW | 9.91 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 965552 | AG1-423 E O1 | Adder | 7.77 MW | 6.61 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 965662 | AG1-434 E O1 | Adder | 6.82 MW | 5.79 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 966091 | AG1-478 C | Adder | 1.68 MW | 1.42 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 966092 | AG1-478 E | Adder | 0.42 MW | 0.36 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 966441 | AG1-513 C | Adder | 0.41 MW | 0.35 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 966442 | AG1-513 E | Adder | 0.61 MW | 0.52 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 272364 | ESS H440N ;R | Adder | 2.12 MW | 1.8 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 290021 | O50 E | Adder | 15.87 MW | 13.49 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 290051 | GSG-6; E | Adder | 8.41 MW | 7.15 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 295109 | WESTBROOK E | Adder | 4.5 MW | 3.83 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 910542 | X3-005 E | Adder | 0.59 MW | 0.5 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 918052 | AA1-018 E OP | Adder | 13.38 MW | 11.38 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 920272 | AA2-123 E | Adder | 1.95 MW | 1.66 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 926331 | AC1-110 1 | Adder | 1.52 MW | 1.29 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 926341 | AC1-110 2 | Adder | 1.52 MW | 1.29 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 927451 | AC1-142A 1 | Adder | 3.34 MW | 2.84 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 927461 | AC1-142A 2 | Adder | 3.34 MW | 2.84 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 933911 | AD1-013 C | Adder | 1.48 MW | 1.26 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 933912 | AD1-013 E | Adder | 2.37 MW | 2.01 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 933931 | AD1-016 C | Adder | 0.74 MW | 0.63 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 933932 | AD1-016 E | Adder | 1.21 MW | 1.03 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 934432 | AD1-067 E | Adder | 0.44 MW | 0.38 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 934721 | AD1-100 C | Adder | 19.21 MW | 16.33 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 934722 | AD1-100 E | Adder | 89.63 MW | 76.19 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 934971 | AD1-129 C | Adder | 0.72 MW | 0.61 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 934972 | AD1-129 E | Adder | 0.48 MW | 0.41 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 936291 | AD2-038 C O1 | Adder | 2.66 MW | 2.26 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 936292 | AD2-038 E O1 | Adder | 12.44 MW | 10.58 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 936371 | AD2-047 C O1 | Adder | 3.75 MW | 3.19 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 936372 | AD2-047 E O1 | Adder | 18.29 MW | 15.55 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 936461 | AD2-060 | Adder | 2.2 MW | 1.87 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 936511 | AD2-066 C O1 | Adder | 6.82 MW | 5.8 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 936512 | AD2-066 E O1 | Adder | 4.55 MW | 3.86 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 937001 | AD2-134 C | Adder | 2.04 MW | 1.73 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 937002 | AD2-134 E | Adder | 8.13 MW | 6.91 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 937401 | AD2-194 1 | Adder | 6.22 MW | 5.29 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 937411 | AD2-194 2 | Adder | 6.22 MW | 5.29 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 942421 | AE2-255 C O1 | Adder | 2.48 MW | 2.11 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 942422 | AE2-255 E O1 | Adder | 7.44 MW | 6.33 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 942651 | AE2-281 C O1 | Adder | 0.7 MW | 0.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 942652 | AE2-281 E O1 | Adder | 4.33 MW | 3.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 942991 | AE2-321 C | Adder | 6.54 MW | 5.55 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 942992 | AE2-321 E | Adder | 3.22 MW | 2.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 943121 | AE2-341 C | Adder | 10.23 MW | 8.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 943122 | AE2-341 E | Adder | 5.02 MW | 4.27 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 943591 | AF1-030 C O1 | Adder | 6.8 MW | 5.78 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 943592 | AF1-030 E O1 | Adder | 3.36 MW | 2.86 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 943801 | AF1-048 C | Adder | 3.06 MW | 2.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 943802 | AF1-048 E | Adder | 2.04 MW | 1.73 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 958481 | AF2-142 C | Adder | 9.23 MW | 7.84 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 958482 | AF2-142 E | Adder | 6.15 MW | 5.23 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 958491 | AF2-143 C | Adder | 9.06 MW | 7.7 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 958492 | AF2-143 E | Adder | 6.04 MW | 5.13 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 959081 | AF2-199 C | Adder | 5.73 MW | 4.87 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 959082 | AF2-199 E | Adder | 2.86 MW | 2.43 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 959091 | AF2-200 C O1 | Adder | 11.45 MW | 9.73 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 959092 | AF2-200 E O1 | Adder | 7.63 MW | 6.49 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 959351 | AF2-226 C | Adder | 2.04 MW | 1.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 959352 | AF2-226 E | Adder | 3.06 MW | 2.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960281 | AF2-319 C | Adder | 2.04 MW | 1.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960282 | AF2-319 E | Adder | 3.06 MW | 2.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960381 | AF2-329 | Adder | 4.29 MW | 3.65 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960581 | AF2-349 C | Adder | 17.4 MW | 14.79 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960582 | AF2-349 E | Adder | 11.6 MW | 9.86 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960591 | AF2-350 C O1 | Adder | 6.61 MW | 5.62 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960592 | AF2-350 E O1 | Adder | 4.41 MW | 3.75 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960601 | AF2-351 C O1 | Adder | 0.88 MW | 0.75 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960602 | AF2-351 E O1 | Adder | 1.32 MW | 1.12 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960721 | AF2-363 C O1 | Adder | 4.74 MW | 4.03 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960722 | AF2-363 E O1 | Adder | 3.16 MW | 2.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960751 | AF2-366 C | Adder | 5.59 MW | 4.75 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 960752 | AF2-366 E | Adder | 3.73 MW | 3.17 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 961501 | AF2-441 C O1 | Adder | 8.01 MW | 6.81 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 961502 | AF2-441 E O1 | Adder | 12.02 MW | 10.21 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 274770 | LINCOLN ;1U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 274771 | LINCOLN ;2U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 274773 | LINCOLN ;4U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 274774 | LINCOLN ;5U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 274775 | LINCOLN ;6U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 274776 | LINCOLN ;7U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 274777 | LINCOLN ;8U | 50/50 | 2.48 MW | 2.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 275149 | KELLYCK ;1E | Adder | 15.43 MW | 13.12 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 276170 | Z1-108 E | Adder | 1.99 MW | 1.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 276591 | L-013 2 | Adder | 2.93 MW | 2.49 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 293061 | N-015 E | Adder | 12.74 MW | 10.83 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 293644 | O22 E1 | Adder | 8.34 MW | 7.09 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 293645 | O22 E2 | Adder | 16.18 MW | 13.75 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 293777 | CAYUG;1U E | Adder | 13.19 MW | 11.21 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 293778 | CAYUG;2U E | Adder | 13.19 MW | 11.21 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 293799 | PILOT HIL;1E | Adder | 15.43 MW | 13.12 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 294392 | P-010 E | Adder | 16.18 MW | 13.75 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 915011 | Y3-013 1 | Adder | 2.98 MW | 2.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 915021 | Y3-013 2 | Adder | 2.98 MW | 2.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 915031 | Y3-013 3 | Adder | 2.98 MW | 2.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 916221 | Z1-073 E | Adder | 4.37 MW | 3.71 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 930482 | AB1-089 CT | Adder | 29.3 MW | 24.9 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 930483 | AB1-089 ST | Adder | 23.29 MW | 19.8 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 930761 | AB1-122 CT1 | Adder | 55.84 MW | 47.46 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 930771 | AB1-122 CT2 | Adder | 59.11 MW | 50.24 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 933411 | AC2-154 C | Adder | 2.09 MW | 1.78 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 933412 | AC2-154 E | Adder | 3.42 MW | 2.9 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 938511 | AE1-070 1 | Adder | 7.31 MW | 6.21 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 938521 | AE1-070 2 | Adder | 6.68 MW | 5.68 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 938851 | AE1-113 C O1 | Adder | 6.55 MW | 5.57 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 938852 | AE1-113 E O1 | Adder | 23.22 MW | 19.73 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 939321 | AE1-163 C O1 | Adder | 4.93 MW | 4.19 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 939322 | AE1-163 E O1 | Adder | 30.31 MW | 25.76 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 939351 | AE1-166 C O1 | Adder | 9.48 MW | 8.06 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 939352 | AE1-166 E O1 | Adder | 8.75 MW | 7.44 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 939401 | AE1-172 C O1 | Adder | 5.26 MW | 4.47 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 939402 | AE1-172 E O1 | Adder | 24.7 MW | 20.99 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 940752 | AE2-062 E | Adder | 0.1 MW | 0.09 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 941131 | AE2-107 C | Adder | 5.27 MW | 4.48 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 941132 | AE2-107 E | Adder | 3.51 MW | 2.98 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 941551 | AE2-152 C O1 | Adder | 10.94 MW | 9.3 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 941552 | AE2-152 E O1 | Adder | 7.29 MW | 6.2 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 946661 | AF1-330 C | Adder | 1.6 MW | 1.36 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 946662 | AF1-330 E | Adder | 0.35 MW | 0.3 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 946671 | AF1-331 | Adder | 1.92 MW | 1.64 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 957331 | AF2-027 C | Adder | 1.99 MW | 1.69 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 957332 | AF2-027 E | Adder | 2.98 MW | 2.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 957401 | AF2-034 C | Adder | 1.12 MW | 0.95 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 957402 | AF2-034 E | Adder | 0.95 MW | 0.81 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 957471 | AF2-041 C | Adder | 17.18 MW | 14.6 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 957472 | AF2-041 E | Adder | 8.59 MW | 7.3 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 958011 | AF2-095 C O1 | Adder | 14.99 MW | 12.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 958012 | AF2-095 E O1 | Adder | 7.05 MW | 6.0 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 958021 | AF2-096 C | Adder | 28.52 MW | 24.24 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 958022 | AF2-096 E | Adder | 13.42 MW | 11.41 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 934101 | AD2-000 1 | Adder | 4.52 MW | 3.84 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 934111 | AD2-000 2 | Adder | 4.78 MW | 4.06 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 290108 | LEEDK;1U E | Adder | 19.51 MW | 16.58 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | 945351 | AF1-200 FTIR | Adder | 250.03 MW | 212.53 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.65 MW | 0.65 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.56 MW | 1.56 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.23 MW | 0.23 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 59.04 MW | 59.04 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.7 MW | 17.7 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.02 MW | 0.02 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.74 MW | 1.74 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.44 MW | 0.44 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.32 MW | 3.32 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.24 MW | 0.24 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 10.73 MW | 10.73 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.93 MW | 0.93 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 11.15 MW | 11.15 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.54 MW | 0.54 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.27 MW | 1.27 MW |
| WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4__ | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.99 MW | 2.99 MW |
| Details for 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962691 | AG1-118 C O1 | Adder | 14.7 MW | 12.5 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962692 | AG1-118 E O1 | Adder | 9.8 MW | 8.33 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962701 | AG1-119 C | Adder | 14.49 MW | 12.32 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962702 | AG1-119 E | Adder | 9.66 MW | 8.21 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962711 | AG1-120 C O1 | Adder | 5.72 MW | 4.87 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962712 | AG1-120 E O1 | Adder | 3.82 MW | 3.24 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962781 | AG1-127 C | Adder | 4.64 MW | 3.95 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 962782 | AG1-127 E | Adder | 3.09 MW | 2.63 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 964361 | AG1-298 O1 | Adder | 47.49 MW | 40.37 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965061 | AG1-371 | Adder | 2.37 MW | 2.01 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965081 | AG1-373 | Adder | 0.79 MW | 0.67 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965141 | AG1-379 C | Adder | 11.33 MW | 9.63 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965142 | AG1-379 E | Adder | 5.19 MW | 4.41 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965551 | AG1-423 C O1 | Adder | 9.66 MW | 8.21 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965552 | AG1-423 E O1 | Adder | 6.44 MW | 5.48 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965661 | AG1-434 C O1 | Adder | 2.74 MW | 2.33 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965662 | AG1-434 E O1 | Adder | 12.84 MW | 10.91 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966091 | AG1-478 C | Adder | 1.38 MW | 1.17 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966092 | AG1-478 E | Adder | 0.35 MW | 0.29 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966441 | AG1-513 C | Adder | 0.34 MW | 0.29 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966442 | AG1-513 E | Adder | 0.51 MW | 0.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 966651 | AG1-535 O1 | Adder | 8.08 MW | 6.87 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 272364 | ESS H440N ;R | Adder | 1.75 MW | 1.49 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 290021 | O50 E | Adder | 13.21 MW | 11.23 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 290051 | GSG-6; E | Adder | 6.95 MW | 5.91 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 295109 | WESTBROOK E | Adder | 3.72 MW | 3.16 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 910542 | X3-005 E | Adder | 0.52 MW | 0.44 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 918052 | AA1-018 E OP | Adder | 10.77 MW | 9.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 920272 | AA2-123 E | Adder | 1.62 MW | 1.38 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 927451 | AC1-142A 1 | Adder | 2.82 MW | 2.4 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 927461 | AC1-142A 2 | Adder | 2.82 MW | 2.4 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933911 | AD1-013 C | Adder | 1.22 MW | 1.04 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933912 | AD1-013 E | Adder | 1.95 MW | 1.66 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933931 | AD1-016 C | Adder | 0.62 MW | 0.52 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933932 | AD1-016 E | Adder | 1.0 MW | 0.85 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934432 | AD1-067 E | Adder | 0.37 MW | 0.31 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934721 | AD1-100 C | Adder | 12.91 MW | 10.98 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934722 | AD1-100 E | Adder | 60.26 MW | 51.22 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936291 | AD2-038 C O1 | Adder | 2.15 MW | 1.83 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936292 | AD2-038 E O1 | Adder | 10.08 MW | 8.57 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936371 | AD2-047 C O1 | Adder | 3.01 MW | 2.56 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936372 | AD2-047 E O1 | Adder | 14.69 MW | 12.49 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936461 | AD2-060 | Adder | 1.77 MW | 1.5 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936511 | AD2-066 C O1 | Adder | 5.58 MW | 4.75 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 936512 | AD2-066 E O1 | Adder | 3.72 MW | 3.17 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 937001 | AD2-134 C | Adder | 1.68 MW | 1.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 937002 | AD2-134 E | Adder | 6.72 MW | 5.71 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 937401 | AD2-194 1 | Adder | 5.21 MW | 4.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 937411 | AD2-194 2 | Adder | 5.22 MW | 4.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942421 | AE2-255 C O1 | Adder | 2.06 MW | 1.75 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942422 | AE2-255 E O1 | Adder | 6.19 MW | 5.26 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942651 | AE2-281 C O1 | Adder | 0.57 MW | 0.48 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942652 | AE2-281 E O1 | Adder | 3.51 MW | 2.98 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942991 | AE2-321 C | Adder | 5.42 MW | 4.61 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 942992 | AE2-321 E | Adder | 2.67 MW | 2.27 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943121 | AE2-341 C | Adder | 8.46 MW | 7.19 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943122 | AE2-341 E | Adder | 4.15 MW | 3.53 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943591 | AF1-030 C O1 | Adder | 5.62 MW | 4.78 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943592 | AF1-030 E O1 | Adder | 2.78 MW | 2.37 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943801 | AF1-048 C | Adder | 2.54 MW | 2.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 943802 | AF1-048 E | Adder | 1.69 MW | 1.44 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958481 | AF2-142 C | Adder | 7.43 MW | 6.31 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958482 | AF2-142 E | Adder | 4.95 MW | 4.21 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958491 | AF2-143 C | Adder | 7.34 MW | 6.24 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958492 | AF2-143 E | Adder | 4.89 MW | 4.16 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959081 | AF2-199 C | Adder | 4.74 MW | 4.03 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959082 | AF2-199 E | Adder | 2.37 MW | 2.01 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959091 | AF2-200 C O1 | Adder | 9.48 MW | 8.05 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959092 | AF2-200 E O1 | Adder | 6.32 MW | 5.37 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959102 | AF2-201 E O1 | Adder | 8.64 MW | 7.35 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959351 | AF2-226 C | Adder | 1.8 MW | 1.53 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 959352 | AF2-226 E | Adder | 2.69 MW | 2.29 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960281 | AF2-319 C | Adder | 1.8 MW | 1.53 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960282 | AF2-319 E | Adder | 2.69 MW | 2.29 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960381 | AF2-329 | Adder | 3.55 MW | 3.02 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960581 | AF2-349 C | Adder | 14.43 MW | 12.26 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960582 | AF2-349 E | Adder | 9.62 MW | 8.18 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960591 | AF2-350 C O1 | Adder | 5.31 MW | 4.51 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960592 | AF2-350 E O1 | Adder | 3.54 MW | 3.01 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960601 | AF2-351 C O1 | Adder | 0.71 MW | 0.6 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960602 | AF2-351 E O1 | Adder | 1.06 MW | 0.9 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960721 | AF2-363 C O1 | Adder | 3.93 MW | 3.34 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960722 | AF2-363 E O1 | Adder | 2.62 MW | 2.23 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960751 | AF2-366 C | Adder | 4.63 MW | 3.94 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 960752 | AF2-366 E | Adder | 3.09 MW | 2.62 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 961501 | AF2-441 C O1 | Adder | 7.4 MW | 6.29 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 961502 | AF2-441 E O1 | Adder | 11.11 MW | 9.44 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274751 | CRETE EC ;1U | 50/50 | 2.15 MW | 2.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274752 | CRETE EC ;2U | 50/50 | 2.15 MW | 2.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274753 | CRETE EC ;3U | 50/50 | 2.15 MW | 2.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274754 | CRETE EC ;4U | 50/50 | 2.15 MW | 2.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274788 | SE CHICAG;5U | Adder | 3.56 MW | 3.03 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274789 | SE CHICAG;6U | Adder | 3.57 MW | 3.04 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274790 | SE CHICAG;7U | Adder | 3.62 MW | 3.08 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274791 | SE CHICAG;8U | Adder | 3.62 MW | 3.08 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274792 | SE CHICAG;9U | Adder | 3.68 MW | 3.12 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274793 | SE CHICAG;0U | Adder | 3.68 MW | 3.12 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274794 | SE CHICAG;1U | Adder | 3.68 MW | 3.12 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 274795 | SE CHICAG;2U | Adder | 3.68 MW | 3.12 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 275149 | KELLYCK ;1E | Adder | 12.39 MW | 10.53 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 276170 | Z1-108 E | Adder | 1.65 MW | 1.4 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 276591 | L-013 2 | Adder | 2.43 MW | 2.07 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 293061 | N-015 E | Adder | 10.24 MW | 8.7 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 293644 | O22 E1 | Adder | 7.32 MW | 6.22 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 293645 | O22 E2 | Adder | 14.22 MW | 12.08 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 293799 | PILOT HIL;1E | Adder | 12.39 MW | 10.53 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 294392 | P-010 E | Adder | 13.0 MW | 11.05 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 915011 | Y3-013 1 | Adder | 2.49 MW | 2.11 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 915021 | Y3-013 2 | Adder | 2.49 MW | 2.11 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 915031 | Y3-013 3 | Adder | 2.49 MW | 2.11 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 916221 | Z1-073 E | Adder | 3.61 MW | 3.07 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 930482 | AB1-089 CT | Adder | 24.26 MW | 20.62 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 930483 | AB1-089 ST | Adder | 19.29 MW | 16.39 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 930761 | AB1-122 CT1 | Adder | 45.6 MW | 38.76 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 930771 | AB1-122 CT2 | Adder | 49.73 MW | 42.27 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933411 | AC2-154 C | Adder | 1.68 MW | 1.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 933412 | AC2-154 E | Adder | 2.74 MW | 2.33 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 938511 | AE1-070 1 | Adder | 6.13 MW | 5.21 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 938521 | AE1-070 2 | Adder | 5.6 MW | 4.76 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 938851 | AE1-113 C O1 | Adder | 5.45 MW | 4.63 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 938852 | AE1-113 E O1 | Adder | 19.32 MW | 16.42 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 939321 | AE1-163 C O1 | Adder | 4.0 MW | 3.4 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 939322 | AE1-163 E O1 | Adder | 24.55 MW | 20.87 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 939351 | AE1-166 C O1 | Adder | 6.83 MW | 5.8 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 939352 | AE1-166 E O1 | Adder | 6.3 MW | 5.36 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 940752 | AE2-062 E | Adder | 0.09 MW | 0.07 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 941131 | AE2-107 C | Adder | 4.36 MW | 3.7 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 941132 | AE2-107 E | Adder | 2.9 MW | 2.47 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 941551 | AE2-152 C O1 | Adder | 7.88 MW | 6.7 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 941552 | AE2-152 E O1 | Adder | 5.25 MW | 4.46 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 946502 | AF1-314 E | Adder | 13.56 MW | 11.53 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 946661 | AF1-330 C | Adder | 1.33 MW | 1.13 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 946662 | AF1-330 E | Adder | 0.29 MW | 0.25 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 946671 | AF1-331 | Adder | 1.59 MW | 1.35 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957331 | AF2-027 C | Adder | 1.66 MW | 1.41 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957332 | AF2-027 E | Adder | 2.49 MW | 2.11 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957371 | AF2-031 C O1 | Adder | 0.75 MW | 0.64 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957372 | AF2-031 E O1 | Adder | 1.13 MW | 0.96 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957401 | AF2-034 C | Adder | 0.95 MW | 0.81 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957402 | AF2-034 E | Adder | 0.81 MW | 0.69 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957471 | AF2-041 C | Adder | 14.21 MW | 12.08 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 957472 | AF2-041 E | Adder | 7.11 MW | 6.04 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958011 | AF2-095 C O1 | Adder | 12.04 MW | 10.23 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958012 | AF2-095 E O1 | Adder | 5.66 MW | 4.82 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958021 | AF2-096 C | Adder | 23.51 MW | 19.98 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 958022 | AF2-096 E | Adder | 11.06 MW | 9.4 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934101 | AD2-000 1 | Adder | 3.69 MW | 3.13 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 934111 | AD2-000 2 | Adder | 4.02 MW | 3.42 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 290108 | LEEDK;1U E | Adder | 16.13 MW | 13.71 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 945351 | AF1-200 FTIR | Adder | 205.0 MW | 174.25 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | 965792 | AG1-447 BAT | Adder | 5.08 MW | 4.31 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.48 MW | 0.48 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.21 MW | 1.21 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.16 MW | 0.16 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 48.85 MW | 48.85 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 13.48 MW | 13.48 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.05 MW | 0.05 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.32 MW | 0.32 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.63 MW | 2.63 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.19 MW | 0.19 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.71 MW | 8.71 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.57 MW | 8.57 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.41 MW | 0.41 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.0 MW | 1.0 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.48 MW | 2.48 MW |
| Details for 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962691 | AG1-118 C O1 | Adder | 14.64 MW | 12.45 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962692 | AG1-118 E O1 | Adder | 9.76 MW | 8.3 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962701 | AG1-119 C | Adder | 14.44 MW | 12.27 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962702 | AG1-119 E | Adder | 9.62 MW | 8.18 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962711 | AG1-120 C O1 | Adder | 5.7 MW | 4.85 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962712 | AG1-120 E O1 | Adder | 3.8 MW | 3.23 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962781 | AG1-127 C | Adder | 4.62 MW | 3.93 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 962782 | AG1-127 E | Adder | 3.08 MW | 2.62 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 964361 | AG1-298 O1 | Adder | 47.1 MW | 40.04 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965061 | AG1-371 | Adder | 2.36 MW | 2.01 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965081 | AG1-373 | Adder | 0.79 MW | 0.67 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965141 | AG1-379 C | Adder | 11.28 MW | 9.59 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965142 | AG1-379 E | Adder | 5.16 MW | 4.39 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965551 | AG1-423 C O1 | Adder | 9.63 MW | 8.18 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965552 | AG1-423 E O1 | Adder | 6.42 MW | 5.46 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965661 | AG1-434 C O1 | Adder | 2.73 MW | 2.32 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965662 | AG1-434 E O1 | Adder | 12.8 MW | 10.88 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966091 | AG1-478 C | Adder | 1.37 MW | 1.16 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966092 | AG1-478 E | Adder | 0.34 MW | 0.29 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966441 | AG1-513 C | Adder | 0.34 MW | 0.28 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966442 | AG1-513 E | Adder | 0.5 MW | 0.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 966651 | AG1-535 O1 | Adder | 8.01 MW | 6.81 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 272364 | ESS H440N ;R | Adder | 1.74 MW | 1.48 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290021 | O50 E | Adder | 13.16 MW | 11.19 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290051 | GSG-6; E | Adder | 6.93 MW | 5.89 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 295109 | WESTBROOK E | Adder | 3.71 MW | 3.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 910542 | X3-005 E | Adder | 0.52 MW | 0.44 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 918052 | AA1-018 E OP | Adder | 10.71 MW | 9.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 920272 | AA2-123 E | Adder | 1.61 MW | 1.37 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926331 | AC1-110 1 | Adder | 1.26 MW | 1.07 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 926341 | AC1-110 2 | Adder | 1.26 MW | 1.07 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927451 | AC1-142A 1 | Adder | 2.81 MW | 2.38 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 927461 | AC1-142A 2 | Adder | 2.81 MW | 2.38 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933911 | AD1-013 C | Adder | 1.22 MW | 1.04 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933912 | AD1-013 E | Adder | 1.95 MW | 1.66 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933931 | AD1-016 C | Adder | 0.61 MW | 0.52 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933932 | AD1-016 E | Adder | 1.0 MW | 0.85 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934432 | AD1-067 E | Adder | 0.37 MW | 0.31 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934721 | AD1-100 C | Adder | 12.85 MW | 10.92 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934722 | AD1-100 E | Adder | 59.95 MW | 50.96 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934971 | AD1-129 C | Adder | 0.6 MW | 0.51 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934972 | AD1-129 E | Adder | 0.4 MW | 0.34 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936291 | AD2-038 C O1 | Adder | 2.14 MW | 1.82 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936292 | AD2-038 E O1 | Adder | 10.04 MW | 8.53 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936371 | AD2-047 C O1 | Adder | 2.99 MW | 2.54 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936372 | AD2-047 E O1 | Adder | 14.6 MW | 12.41 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936461 | AD2-060 | Adder | 1.76 MW | 1.5 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936511 | AD2-066 C O1 | Adder | 5.56 MW | 4.73 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 936512 | AD2-066 E O1 | Adder | 3.71 MW | 3.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937001 | AD2-134 C | Adder | 1.68 MW | 1.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937002 | AD2-134 E | Adder | 6.7 MW | 5.69 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937401 | AD2-194 1 | Adder | 5.18 MW | 4.41 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 937411 | AD2-194 2 | Adder | 5.19 MW | 4.41 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942421 | AE2-255 C O1 | Adder | 2.06 MW | 1.75 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942422 | AE2-255 E O1 | Adder | 6.17 MW | 5.24 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942651 | AE2-281 C O1 | Adder | 0.57 MW | 0.48 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942652 | AE2-281 E O1 | Adder | 3.49 MW | 2.97 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942991 | AE2-321 C | Adder | 5.4 MW | 4.59 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 942992 | AE2-321 E | Adder | 2.66 MW | 2.26 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943121 | AE2-341 C | Adder | 8.41 MW | 7.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943122 | AE2-341 E | Adder | 4.13 MW | 3.51 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943591 | AF1-030 C O1 | Adder | 5.6 MW | 4.76 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943592 | AF1-030 E O1 | Adder | 2.77 MW | 2.35 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943801 | AF1-048 C | Adder | 2.53 MW | 2.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 943802 | AF1-048 E | Adder | 1.68 MW | 1.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958481 | AF2-142 C | Adder | 7.39 MW | 6.28 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958482 | AF2-142 E | Adder | 4.92 MW | 4.19 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958491 | AF2-143 C | Adder | 7.31 MW | 6.21 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958492 | AF2-143 E | Adder | 4.87 MW | 4.14 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959081 | AF2-199 C | Adder | 4.72 MW | 4.01 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959082 | AF2-199 E | Adder | 2.36 MW | 2.01 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959091 | AF2-200 C O1 | Adder | 9.44 MW | 8.03 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959092 | AF2-200 E O1 | Adder | 6.3 MW | 5.35 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959102 | AF2-201 E O1 | Adder | 8.62 MW | 7.33 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959351 | AF2-226 C | Adder | 1.79 MW | 1.52 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 959352 | AF2-226 E | Adder | 2.68 MW | 2.28 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960281 | AF2-319 C | Adder | 1.79 MW | 1.52 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960282 | AF2-319 E | Adder | 2.68 MW | 2.28 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960381 | AF2-329 | Adder | 3.53 MW | 3.0 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960581 | AF2-349 C | Adder | 14.37 MW | 12.22 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960582 | AF2-349 E | Adder | 9.58 MW | 8.14 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960591 | AF2-350 C O1 | Adder | 5.28 MW | 4.49 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960592 | AF2-350 E O1 | Adder | 3.52 MW | 2.99 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960601 | AF2-351 C O1 | Adder | 0.7 MW | 0.6 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960602 | AF2-351 E O1 | Adder | 1.06 MW | 0.9 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960721 | AF2-363 C O1 | Adder | 3.91 MW | 3.33 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960722 | AF2-363 E O1 | Adder | 2.61 MW | 2.22 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960751 | AF2-366 C | Adder | 4.61 MW | 3.92 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 960752 | AF2-366 E | Adder | 3.07 MW | 2.61 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961501 | AF2-441 C O1 | Adder | 7.34 MW | 6.24 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 961502 | AF2-441 E O1 | Adder | 11.01 MW | 9.36 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274751 | CRETE EC ;1U | 50/50 | 2.14 MW | 2.14 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274752 | CRETE EC ;2U | 50/50 | 2.14 MW | 2.14 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274753 | CRETE EC ;3U | 50/50 | 2.14 MW | 2.14 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274754 | CRETE EC ;4U | 50/50 | 2.14 MW | 2.14 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274788 | SE CHICAG;5U | Adder | 3.53 MW | 3.0 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274789 | SE CHICAG;6U | Adder | 3.54 MW | 3.01 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274790 | SE CHICAG;7U | Adder | 3.58 MW | 3.05 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274791 | SE CHICAG;8U | Adder | 3.58 MW | 3.05 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274792 | SE CHICAG;9U | Adder | 3.64 MW | 3.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274793 | SE CHICAG;0U | Adder | 3.64 MW | 3.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274794 | SE CHICAG;1U | Adder | 3.64 MW | 3.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 274795 | SE CHICAG;2U | Adder | 3.64 MW | 3.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 275149 | KELLYCK ;1E | Adder | 12.31 MW | 10.46 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276170 | Z1-108 E | Adder | 1.64 MW | 1.4 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 276591 | L-013 2 | Adder | 2.42 MW | 2.06 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293061 | N-015 E | Adder | 10.19 MW | 8.66 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293644 | O22 E1 | Adder | 7.29 MW | 6.2 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293645 | O22 E2 | Adder | 14.15 MW | 12.03 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 293799 | PILOT HIL;1E | Adder | 12.31 MW | 10.46 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 294392 | P-010 E | Adder | 12.94 MW | 11.0 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915011 | Y3-013 1 | Adder | 2.48 MW | 2.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915021 | Y3-013 2 | Adder | 2.48 MW | 2.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 915031 | Y3-013 3 | Adder | 2.48 MW | 2.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 916221 | Z1-073 E | Adder | 3.6 MW | 3.06 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930482 | AB1-089 CT | Adder | 24.18 MW | 20.55 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930483 | AB1-089 ST | Adder | 19.22 MW | 16.34 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930761 | AB1-122 CT1 | Adder | 45.46 MW | 38.64 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 930771 | AB1-122 CT2 | Adder | 49.48 MW | 42.05 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933411 | AC2-154 C | Adder | 1.67 MW | 1.42 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 933412 | AC2-154 E | Adder | 2.73 MW | 2.32 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938511 | AE1-070 1 | Adder | 6.1 MW | 5.18 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938521 | AE1-070 2 | Adder | 5.57 MW | 4.74 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938851 | AE1-113 C O1 | Adder | 5.43 MW | 4.61 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 938852 | AE1-113 E O1 | Adder | 19.24 MW | 16.36 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939321 | AE1-163 C O1 | Adder | 3.98 MW | 3.38 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939322 | AE1-163 E O1 | Adder | 24.44 MW | 20.77 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939351 | AE1-166 C O1 | Adder | 6.79 MW | 5.77 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 939352 | AE1-166 E O1 | Adder | 6.27 MW | 5.33 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 940752 | AE2-062 E | Adder | 0.09 MW | 0.07 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941131 | AE2-107 C | Adder | 4.34 MW | 3.69 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941132 | AE2-107 E | Adder | 2.89 MW | 2.46 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941551 | AE2-152 C O1 | Adder | 7.83 MW | 6.66 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 941552 | AE2-152 E O1 | Adder | 5.22 MW | 4.44 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946502 | AF1-314 E | Adder | 13.52 MW | 11.49 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946661 | AF1-330 C | Adder | 1.32 MW | 1.12 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946662 | AF1-330 E | Adder | 0.29 MW | 0.25 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 946671 | AF1-331 | Adder | 1.58 MW | 1.35 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957331 | AF2-027 C | Adder | 1.65 MW | 1.4 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957332 | AF2-027 E | Adder | 2.48 MW | 2.1 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957371 | AF2-031 C O1 | Adder | 0.74 MW | 0.63 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957372 | AF2-031 E O1 | Adder | 1.12 MW | 0.95 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957401 | AF2-034 C | Adder | 0.94 MW | 0.8 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957402 | AF2-034 E | Adder | 0.8 MW | 0.68 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957471 | AF2-041 C | Adder | 14.17 MW | 12.04 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 957472 | AF2-041 E | Adder | 7.08 MW | 6.02 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958011 | AF2-095 C O1 | Adder | 11.96 MW | 10.16 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958012 | AF2-095 E O1 | Adder | 5.63 MW | 4.78 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958021 | AF2-096 C | Adder | 23.37 MW | 19.87 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 958022 | AF2-096 E | Adder | 11.0 MW | 9.35 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934101 | AD2-000 1 | Adder | 3.68 MW | 3.12 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 934111 | AD2-000 2 | Adder | 4.0 MW | 3.4 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 290108 | LEEDK;1U E | Adder | 16.07 MW | 13.66 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 945351 | AF1-200 FTIR | Adder | 203.93 MW | 173.34 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | 965792 | AG1-447 BAT | Adder | 5.21 MW | 4.43 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.44 MW | 0.44 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.83 MW | 0.83 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.14 MW | 0.14 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.22 MW | 0.22 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 47.97 MW | 47.97 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.6 MW | 14.6 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.33 MW | 1.33 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.28 MW | 0.28 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.8 MW | 2.8 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.76 MW | 8.76 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.72 MW | 0.72 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 8.56 MW | 8.56 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.29 MW | 0.29 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.15 MW | 1.15 MW |
| 17GREEN_ACRE-GREENACRE; T 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.48 MW | 2.48 MW |
| Details for WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 962691 | AG1-118 C O1 | Adder | 59.65 MW | 50.7 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 962692 | AG1-118 E O1 | Adder | 39.76 MW | 33.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 962701 | AG1-119 C | Adder | 58.0 MW | 49.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 962702 | AG1-119 E | Adder | 38.67 MW | 32.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 962711 | AG1-120 C O1 | Adder | 23.07 MW | 19.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 962712 | AG1-120 E O1 | Adder | 15.38 MW | 13.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 962781 | AG1-127 C | Adder | 18.82 MW | 16.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 962782 | AG1-127 E | Adder | 12.53 MW | 10.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 965061 | AG1-371 | Adder | 9.51 MW | 8.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 965081 | AG1-373 | Adder | 3.17 MW | 2.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 965141 | AG1-379 C | Adder | 43.3 MW | 36.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 965142 | AG1-379 E | Adder | 19.82 MW | 16.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 965551 | AG1-423 C O1 | Adder | 38.68 MW | 32.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 965552 | AG1-423 E O1 | Adder | 25.79 MW | 21.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 965661 | AG1-434 C O1 | Adder | 10.99 MW | 9.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 965662 | AG1-434 E O1 | Adder | 51.47 MW | 43.75 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 966091 | AG1-478 C | Adder | 5.08 MW | 4.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 966092 | AG1-478 E | Adder | 1.28 MW | 1.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 966431 | AG1-512 C | Adder | 5.15 MW | 4.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 966432 | AG1-512 E | Adder | 7.73 MW | 6.57 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 966441 | AG1-513 C | Adder | 1.36 MW | 1.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 966442 | AG1-513 E | Adder | 2.05 MW | 1.74 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 272364 | ESS H440N ;R | Adder | 7.06 MW | 6.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 290021 | O50 E | Adder | 50.5 MW | 42.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 290051 | GSG-6; E | Adder | 28.08 MW | 23.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 295109 | WESTBROOK E | Adder | 15.03 MW | 12.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 295111 | SUBLETTE E | Adder | 6.9 MW | 5.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 918052 | AA1-018 E OP | Adder | 41.1 MW | 34.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 920272 | AA2-123 E | Adder | 6.45 MW | 5.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 926331 | AC1-110 1 | Adder | 5.08 MW | 4.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 926341 | AC1-110 2 | Adder | 5.08 MW | 4.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 927451 | AC1-142A 1 | Adder | 10.52 MW | 8.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 927461 | AC1-142A 2 | Adder | 10.52 MW | 8.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 933911 | AD1-013 C | Adder | 4.94 MW | 4.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 933912 | AD1-013 E | Adder | 7.9 MW | 6.71 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 933931 | AD1-016 C | Adder | 2.45 MW | 2.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 933932 | AD1-016 E | Adder | 3.99 MW | 3.4 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 934432 | AD1-067 E | Adder | 1.48 MW | 1.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 934721 | AD1-100 C | Adder | 50.62 MW | 43.03 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 934722 | AD1-100 E | Adder | 236.23 MW | 200.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 934971 | AD1-129 C | Adder | 2.39 MW | 2.03 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 934972 | AD1-129 E | Adder | 1.59 MW | 1.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 936291 | AD2-038 C O1 | Adder | 8.25 MW | 7.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 936292 | AD2-038 E O1 | Adder | 38.63 MW | 32.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 936371 | AD2-047 C O1 | Adder | 10.67 MW | 9.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 936372 | AD2-047 E O1 | Adder | 52.09 MW | 44.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 936461 | AD2-060 | Adder | 6.28 MW | 5.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 936511 | AD2-066 C O1 | Adder | 21.52 MW | 18.3 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 936512 | AD2-066 E O1 | Adder | 14.35 MW | 12.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 937001 | AD2-134 C | Adder | 6.8 MW | 5.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 937002 | AD2-134 E | Adder | 27.15 MW | 23.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 937311 | AD2-172 C | Adder | 6.5 MW | 5.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 937312 | AD2-172 E | Adder | 8.98 MW | 7.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 937401 | AD2-194 1 | Adder | 19.54 MW | 16.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 937411 | AD2-194 2 | Adder | 19.53 MW | 16.6 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 942421 | AE2-255 C O1 | Adder | 7.89 MW | 6.71 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 942422 | AE2-255 E O1 | Adder | 23.67 MW | 20.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 942651 | AE2-281 C O1 | Adder | 2.19 MW | 1.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 942652 | AE2-281 E O1 | Adder | 13.44 MW | 11.42 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 942991 | AE2-321 C | Adder | 21.61 MW | 18.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 942992 | AE2-321 E | Adder | 10.64 MW | 9.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 943121 | AE2-341 C | Adder | 35.11 MW | 29.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 943122 | AE2-341 E | Adder | 17.24 MW | 14.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 943591 | AF1-030 C O1 | Adder | 23.35 MW | 19.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 943592 | AF1-030 E O1 | Adder | 11.55 MW | 9.82 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 943801 | AF1-048 C | Adder | 10.1 MW | 8.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 943802 | AF1-048 E | Adder | 6.73 MW | 5.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958481 | AF2-142 C | Adder | 28.35 MW | 24.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958482 | AF2-142 E | Adder | 18.9 MW | 16.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958491 | AF2-143 C | Adder | 28.13 MW | 23.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958492 | AF2-143 E | Adder | 18.75 MW | 15.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958911 | AF2-182 C | Adder | 6.69 MW | 5.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 959081 | AF2-199 C | Adder | 19.02 MW | 16.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 959082 | AF2-199 E | Adder | 9.51 MW | 8.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 959091 | AF2-200 C O1 | Adder | 38.04 MW | 32.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 959092 | AF2-200 E O1 | Adder | 25.36 MW | 21.55 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 959101 | AF2-201 C O1 | Adder | 15.91 MW | 13.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 959102 | AF2-201 E O1 | Adder | 45.68 MW | 38.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 959351 | AF2-226 C | Adder | 6.31 MW | 5.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 959352 | AF2-226 E | Adder | 9.46 MW | 8.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960281 | AF2-319 C | Adder | 6.31 MW | 5.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960282 | AF2-319 E | Adder | 9.46 MW | 8.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960381 | AF2-329 | Adder | 14.73 MW | 12.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960581 | AF2-349 C | Adder | 57.44 MW | 48.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960582 | AF2-349 E | Adder | 38.3 MW | 32.55 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960591 | AF2-350 C O1 | Adder | 18.83 MW | 16.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960592 | AF2-350 E O1 | Adder | 12.55 MW | 10.67 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960601 | AF2-351 C O1 | Adder | 2.51 MW | 2.13 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960602 | AF2-351 E O1 | Adder | 3.77 MW | 3.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960721 | AF2-363 C O1 | Adder | 15.83 MW | 13.45 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960722 | AF2-363 E O1 | Adder | 10.55 MW | 8.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960751 | AF2-366 C | Adder | 18.77 MW | 15.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 960752 | AF2-366 E | Adder | 12.51 MW | 10.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274770 | LINCOLN ;1U | 50/50 | 5.18 MW | 5.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274771 | LINCOLN ;2U | 50/50 | 5.18 MW | 5.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274772 | LINCOLN ;3U | 50/50 | 5.18 MW | 5.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274773 | LINCOLN ;4U | 50/50 | 5.18 MW | 5.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274774 | LINCOLN ;5U | 50/50 | 5.18 MW | 5.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274775 | LINCOLN ;6U | 50/50 | 5.18 MW | 5.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274776 | LINCOLN ;7U | 50/50 | 5.18 MW | 5.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274859 | EASYR;U1 E | Adder | 29.18 MW | 24.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 274860 | EASYR;U2 E | Adder | 29.18 MW | 24.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 275149 | KELLYCK ;1E | Adder | 43.93 MW | 37.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 276170 | Z1-108 E | Adder | 6.56 MW | 5.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 276591 | L-013 2 | Adder | 9.79 MW | 8.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 293061 | N-015 E | Adder | 41.0 MW | 34.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 293644 | O22 E1 | Adder | 25.74 MW | 21.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 293645 | O22 E2 | Adder | 49.96 MW | 42.46 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 293799 | PILOT HIL;1E | Adder | 43.93 MW | 37.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 294392 | P-010 E | Adder | 52.08 MW | 44.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 294763 | P-046 E | Adder | 24.76 MW | 21.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 915011 | Y3-013 1 | Adder | 9.73 MW | 8.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 915021 | Y3-013 2 | Adder | 9.73 MW | 8.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 915031 | Y3-013 3 | Adder | 9.73 MW | 8.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 916221 | Z1-073 E | Adder | 14.58 MW | 12.4 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 930482 | AB1-089 CT | Adder | 96.94 MW | 82.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 930483 | AB1-089 ST | Adder | 77.07 MW | 65.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 930761 | AB1-122 CT1 | Adder | 182.02 MW | 154.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 930771 | AB1-122 CT2 | Adder | 187.63 MW | 159.48 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 933411 | AC2-154 C | Adder | 5.96 MW | 5.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 933412 | AC2-154 E | Adder | 9.73 MW | 8.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 938511 | AE1-070 1 | Adder | 22.95 MW | 19.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 938521 | AE1-070 2 | Adder | 21.0 MW | 17.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 938851 | AE1-113 C O1 | Adder | 20.83 MW | 17.7 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 938852 | AE1-113 E O1 | Adder | 73.85 MW | 62.77 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 938861 | AE1-114 C O1 | Adder | 10.42 MW | 8.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 938862 | AE1-114 E O1 | Adder | 35.53 MW | 30.2 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 939321 | AE1-163 C O1 | Adder | 15.32 MW | 13.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 939322 | AE1-163 E O1 | Adder | 94.08 MW | 79.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 939351 | AE1-166 C O1 | Adder | 26.06 MW | 22.15 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 939352 | AE1-166 E O1 | Adder | 24.05 MW | 20.45 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 939401 | AE1-172 C O1 | Adder | 13.93 MW | 11.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 939402 | AE1-172 E O1 | Adder | 65.34 MW | 55.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 940501 | AE2-035 C | Adder | 6.5 MW | 5.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 940502 | AE2-035 E | Adder | 8.98 MW | 7.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 940752 | AE2-062 E | Adder | 0.33 MW | 0.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 941131 | AE2-107 C | Adder | 17.65 MW | 15.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 941132 | AE2-107 E | Adder | 11.77 MW | 10.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 941551 | AE2-152 C O1 | Adder | 30.07 MW | 25.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 941552 | AE2-152 E O1 | Adder | 20.04 MW | 17.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 946501 | AF1-314 C | Adder | 11.51 MW | 9.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 946502 | AF1-314 E | Adder | 54.1 MW | 45.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 946661 | AF1-330 C | Adder | 5.29 MW | 4.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 946662 | AF1-330 E | Adder | 1.16 MW | 0.99 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 946671 | AF1-331 | Adder | 6.42 MW | 5.46 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 957331 | AF2-027 C | Adder | 6.49 MW | 5.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 957332 | AF2-027 E | Adder | 9.73 MW | 8.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 957401 | AF2-034 C | Adder | 3.53 MW | 3.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 957402 | AF2-034 E | Adder | 3.0 MW | 2.55 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 957471 | AF2-041 C | Adder | 57.05 MW | 48.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 957472 | AF2-041 E | Adder | 28.53 MW | 24.25 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958011 | AF2-095 C O1 | Adder | 42.68 MW | 36.27 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958012 | AF2-095 E O1 | Adder | 20.08 MW | 17.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958021 | AF2-096 C | Adder | 85.05 MW | 72.29 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 958022 | AF2-096 E | Adder | 40.02 MW | 34.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 934101 | AD2-000 1 | Adder | 14.72 MW | 12.51 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 934111 | AD2-000 2 | Adder | 15.17 MW | 12.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 290108 | LEEDK;1U E | Adder | 65.39 MW | 55.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | 945351 | AF1-200 FTIR | Adder | 922.93 MW | 784.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.04 MW | 2.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 5.11 MW | 5.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.71 MW | 0.71 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.67 MW | 0.67 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 185.73 MW | 185.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 53.88 MW | 53.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.09 MW | 0.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 5.43 MW | 5.43 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.14 MW | 0.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.38 MW | 1.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 10.39 MW | 10.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.78 MW | 0.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 34.62 MW | 34.62 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.91 MW | 2.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 34.83 MW | 34.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.75 MW | 1.75 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.86 MW | 3.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 9.76 MW | 9.76 MW |
| Details for WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 962691 | AG1-118 C O1 | Adder | 59.72 MW | 50.76 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 962692 | AG1-118 E O1 | Adder | 39.81 MW | 33.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 962701 | AG1-119 C | Adder | 58.07 MW | 49.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 962702 | AG1-119 E | Adder | 38.72 MW | 32.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 962711 | AG1-120 C O1 | Adder | 23.1 MW | 19.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 962712 | AG1-120 E O1 | Adder | 15.4 MW | 13.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 962781 | AG1-127 C | Adder | 18.85 MW | 16.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 962782 | AG1-127 E | Adder | 12.54 MW | 10.66 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 965061 | AG1-371 | Adder | 9.52 MW | 8.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 965081 | AG1-373 | Adder | 3.17 MW | 2.7 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 965141 | AG1-379 C | Adder | 43.36 MW | 36.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 965142 | AG1-379 E | Adder | 19.84 MW | 16.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 965551 | AG1-423 C O1 | Adder | 38.73 MW | 32.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 965552 | AG1-423 E O1 | Adder | 25.82 MW | 21.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 965661 | AG1-434 C O1 | Adder | 11.01 MW | 9.36 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 965662 | AG1-434 E O1 | Adder | 51.54 MW | 43.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 966091 | AG1-478 C | Adder | 5.09 MW | 4.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 966092 | AG1-478 E | Adder | 1.28 MW | 1.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 966431 | AG1-512 C | Adder | 5.16 MW | 4.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 966432 | AG1-512 E | Adder | 7.74 MW | 6.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 966441 | AG1-513 C | Adder | 1.37 MW | 1.16 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 966442 | AG1-513 E | Adder | 2.05 MW | 1.74 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 272364 | ESS H440N ;R | Adder | 7.07 MW | 6.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 290021 | O50 E | Adder | 50.56 MW | 42.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 290051 | GSG-6; E | Adder | 28.11 MW | 23.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 295109 | WESTBROOK E | Adder | 15.05 MW | 12.79 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 295111 | SUBLETTE E | Adder | 6.91 MW | 5.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 918052 | AA1-018 E OP | Adder | 41.15 MW | 34.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 920272 | AA2-123 E | Adder | 6.46 MW | 5.49 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 926331 | AC1-110 1 | Adder | 5.09 MW | 4.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 926341 | AC1-110 2 | Adder | 5.09 MW | 4.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 927451 | AC1-142A 1 | Adder | 10.53 MW | 8.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 927461 | AC1-142A 2 | Adder | 10.53 MW | 8.95 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 933911 | AD1-013 C | Adder | 4.95 MW | 4.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 933912 | AD1-013 E | Adder | 7.91 MW | 6.72 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 933931 | AD1-016 C | Adder | 2.45 MW | 2.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 933932 | AD1-016 E | Adder | 4.0 MW | 3.4 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 934432 | AD1-067 E | Adder | 1.48 MW | 1.26 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 934721 | AD1-100 C | Adder | 50.68 MW | 43.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 934722 | AD1-100 E | Adder | 236.52 MW | 201.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 934971 | AD1-129 C | Adder | 2.39 MW | 2.03 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 934972 | AD1-129 E | Adder | 1.59 MW | 1.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 936291 | AD2-038 C O1 | Adder | 8.26 MW | 7.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 936292 | AD2-038 E O1 | Adder | 38.68 MW | 32.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 936371 | AD2-047 C O1 | Adder | 10.68 MW | 9.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 936372 | AD2-047 E O1 | Adder | 52.16 MW | 44.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 936461 | AD2-060 | Adder | 6.28 MW | 5.34 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 936511 | AD2-066 C O1 | Adder | 21.55 MW | 18.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 936512 | AD2-066 E O1 | Adder | 14.37 MW | 12.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 937001 | AD2-134 C | Adder | 6.8 MW | 5.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 937002 | AD2-134 E | Adder | 27.18 MW | 23.11 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 937311 | AD2-172 C | Adder | 6.51 MW | 5.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 937312 | AD2-172 E | Adder | 8.99 MW | 7.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 937401 | AD2-194 1 | Adder | 19.56 MW | 16.63 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 937411 | AD2-194 2 | Adder | 19.56 MW | 16.62 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 942421 | AE2-255 C O1 | Adder | 7.9 MW | 6.71 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 942422 | AE2-255 E O1 | Adder | 23.7 MW | 20.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 942651 | AE2-281 C O1 | Adder | 2.19 MW | 1.86 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 942652 | AE2-281 E O1 | Adder | 13.46 MW | 11.44 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 942991 | AE2-321 C | Adder | 21.63 MW | 18.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 942992 | AE2-321 E | Adder | 10.66 MW | 9.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 943121 | AE2-341 C | Adder | 35.15 MW | 29.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 943122 | AE2-341 E | Adder | 17.26 MW | 14.67 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 943591 | AF1-030 C O1 | Adder | 23.38 MW | 19.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 943592 | AF1-030 E O1 | Adder | 11.57 MW | 9.83 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 943801 | AF1-048 C | Adder | 10.11 MW | 8.6 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 943802 | AF1-048 E | Adder | 6.74 MW | 5.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958481 | AF2-142 C | Adder | 28.38 MW | 24.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958482 | AF2-142 E | Adder | 18.92 MW | 16.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958491 | AF2-143 C | Adder | 28.17 MW | 23.94 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958492 | AF2-143 E | Adder | 18.78 MW | 15.96 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958911 | AF2-182 C | Adder | 6.7 MW | 5.69 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 959081 | AF2-199 C | Adder | 19.04 MW | 16.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 959082 | AF2-199 E | Adder | 9.52 MW | 8.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 959091 | AF2-200 C O1 | Adder | 38.08 MW | 32.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 959092 | AF2-200 E O1 | Adder | 25.39 MW | 21.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 959101 | AF2-201 C O1 | Adder | 15.93 MW | 13.54 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 959102 | AF2-201 E O1 | Adder | 45.74 MW | 38.88 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 959351 | AF2-226 C | Adder | 6.32 MW | 5.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 959352 | AF2-226 E | Adder | 9.47 MW | 8.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960281 | AF2-319 C | Adder | 6.32 MW | 5.37 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960282 | AF2-319 E | Adder | 9.47 MW | 8.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960381 | AF2-329 | Adder | 14.75 MW | 12.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960581 | AF2-349 C | Adder | 57.52 MW | 48.89 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960582 | AF2-349 E | Adder | 38.34 MW | 32.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960591 | AF2-350 C O1 | Adder | 18.85 MW | 16.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960592 | AF2-350 E O1 | Adder | 12.57 MW | 10.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960601 | AF2-351 C O1 | Adder | 2.51 MW | 2.14 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960602 | AF2-351 E O1 | Adder | 3.77 MW | 3.21 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960721 | AF2-363 C O1 | Adder | 15.85 MW | 13.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960722 | AF2-363 E O1 | Adder | 10.56 MW | 8.98 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960751 | AF2-366 C | Adder | 18.79 MW | 15.97 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 960752 | AF2-366 E | Adder | 12.53 MW | 10.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274770 | LINCOLN ;1U | 50/50 | 5.19 MW | 5.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274771 | LINCOLN ;2U | 50/50 | 5.19 MW | 5.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274772 | LINCOLN ;3U | 50/50 | 5.19 MW | 5.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274773 | LINCOLN ;4U | 50/50 | 5.19 MW | 5.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274774 | LINCOLN ;5U | 50/50 | 5.19 MW | 5.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274775 | LINCOLN ;6U | 50/50 | 5.19 MW | 5.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274776 | LINCOLN ;7U | 50/50 | 5.19 MW | 5.19 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274859 | EASYR;U1 E | Adder | 29.22 MW | 24.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 274860 | EASYR;U2 E | Adder | 29.22 MW | 24.84 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 275149 | KELLYCK ;1E | Adder | 43.99 MW | 37.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 276170 | Z1-108 E | Adder | 6.57 MW | 5.58 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 276591 | L-013 2 | Adder | 9.8 MW | 8.33 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 293061 | N-015 E | Adder | 41.05 MW | 34.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 293644 | O22 E1 | Adder | 25.77 MW | 21.9 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 293645 | O22 E2 | Adder | 50.02 MW | 42.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 293799 | PILOT HIL;1E | Adder | 43.99 MW | 37.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 294392 | P-010 E | Adder | 52.14 MW | 44.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 294763 | P-046 E | Adder | 24.79 MW | 21.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 915011 | Y3-013 1 | Adder | 9.74 MW | 8.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 915021 | Y3-013 2 | Adder | 9.74 MW | 8.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 915031 | Y3-013 3 | Adder | 9.74 MW | 8.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 916221 | Z1-073 E | Adder | 14.6 MW | 12.41 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 930482 | AB1-089 CT | Adder | 97.06 MW | 82.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 930483 | AB1-089 ST | Adder | 77.17 MW | 65.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 930761 | AB1-122 CT1 | Adder | 182.26 MW | 154.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 930771 | AB1-122 CT2 | Adder | 187.86 MW | 159.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 933411 | AC2-154 C | Adder | 5.97 MW | 5.08 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 933412 | AC2-154 E | Adder | 9.74 MW | 8.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 938511 | AE1-070 1 | Adder | 22.98 MW | 19.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 938521 | AE1-070 2 | Adder | 21.03 MW | 17.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 938851 | AE1-113 C O1 | Adder | 20.86 MW | 17.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 938852 | AE1-113 E O1 | Adder | 73.95 MW | 62.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 938861 | AE1-114 C O1 | Adder | 10.43 MW | 8.87 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 938862 | AE1-114 E O1 | Adder | 35.58 MW | 30.25 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 939321 | AE1-163 C O1 | Adder | 15.34 MW | 13.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 939322 | AE1-163 E O1 | Adder | 94.2 MW | 80.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 939351 | AE1-166 C O1 | Adder | 26.09 MW | 22.18 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 939352 | AE1-166 E O1 | Adder | 24.08 MW | 20.47 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 939401 | AE1-172 C O1 | Adder | 13.94 MW | 11.85 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 939402 | AE1-172 E O1 | Adder | 65.42 MW | 55.61 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 940501 | AE2-035 C | Adder | 6.51 MW | 5.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 940502 | AE2-035 E | Adder | 8.99 MW | 7.64 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 940752 | AE2-062 E | Adder | 0.33 MW | 0.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 941131 | AE2-107 C | Adder | 17.68 MW | 15.03 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 941132 | AE2-107 E | Adder | 11.78 MW | 10.02 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 941551 | AE2-152 C O1 | Adder | 30.1 MW | 25.59 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 941552 | AE2-152 E O1 | Adder | 20.07 MW | 17.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 946501 | AF1-314 C | Adder | 11.53 MW | 9.8 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 946502 | AF1-314 E | Adder | 54.17 MW | 46.05 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 946661 | AF1-330 C | Adder | 5.3 MW | 4.5 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 946662 | AF1-330 E | Adder | 1.16 MW | 0.99 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 946671 | AF1-331 | Adder | 6.43 MW | 5.46 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 957331 | AF2-027 C | Adder | 6.49 MW | 5.52 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 957332 | AF2-027 E | Adder | 9.74 MW | 8.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 957401 | AF2-034 C | Adder | 3.53 MW | 3.0 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 957402 | AF2-034 E | Adder | 3.01 MW | 2.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 957471 | AF2-041 C | Adder | 57.13 MW | 48.56 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 957472 | AF2-041 E | Adder | 28.56 MW | 24.28 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958011 | AF2-095 C O1 | Adder | 42.73 MW | 36.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958012 | AF2-095 E O1 | Adder | 20.11 MW | 17.09 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958021 | AF2-096 C | Adder | 85.15 MW | 72.38 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 958022 | AF2-096 E | Adder | 40.07 MW | 34.06 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 934101 | AD2-000 1 | Adder | 14.74 MW | 12.53 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 934111 | AD2-000 2 | Adder | 15.19 MW | 12.91 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 290108 | LEEDK;1U E | Adder | 65.47 MW | 55.65 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | 945351 | AF1-200 FTIR | Adder | 923.91 MW | 785.32 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 2.01 MW | 2.01 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 5.04 MW | 5.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.7 MW | 0.7 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.68 MW | 0.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 186.31 MW | 186.31 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 54.25 MW | 54.25 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.07 MW | 0.07 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 5.39 MW | 5.39 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.12 MW | 0.12 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.35 MW | 1.35 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 10.46 MW | 10.46 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.78 MW | 0.78 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 34.68 MW | 34.68 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.89 MW | 2.89 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 34.55 MW | 34.55 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.73 MW | 1.73 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.92 MW | 3.92 MW |
| WILTON ;-05DUMONT 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 9.77 MW | 9.77 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n4056.1 | Replace the 2 3000A 765kV CB's at Dumont station | $6,000,000 | |
| b3775.11 | Upgrade the limiting element at Stillwell substation to increase the rating of the Stillwell-Dumont. | $0 | |
| b3775.7 | Upgrade limiting element at Dumont substation on the Stillwell-Dumont 345 kV line. | $0 | |
| b3775.6 | Perform sag study mitigation work on the Dumont-Stillwell 345 kV line | $0 | |
| n5769.2 | Replace two Dumont 3000A Non-Oil breakers. | $2,000,000 | |
| (TBD) | Rebuild NIPS portion of line and upgrade substation conductor (MISO - Upgrade #2) | $8,000,000 | |
| n5769.4 | Rebuild/Recondutor 8.6 miles of ACSR ~ 954 ~ 45/7 ~ RAIL conductor to mitigate the overload | $17,200,000 | |
| n5769.3 | Replace 11 jumpers/risers at Dumont substation | $275,000 | |
| n5769.5 | Replace 4 Dumont switches (3000 A). | $2,400,000 | |
| (TBD) | Upgrade circuit breakers and MODs at Stillwell. (MISO Upgrade #4) | $1,500,000 | |
| n5769.6 | An engineering study will need to be conducted to determine if the Dumont Relay Compliance Trip limit settings can be adjusted | $600,000 | |
| (TBD) | Upgrade transmission conductor and conductor drop.. (MISO - Upgrade #3) | $6,500,000 | |
| n5252 | Mitigate the sag on L11215 | $9,000,000 | |
| n6860 | Wilton Upgrade exisiting Current Transformers | $1,000,000 | |
| n6600 | Replace Dumont Circuit Breaker B1 | $3,000,000 | |
| n7467 | Replace one Marysville 765kV CB | $3,000,000 | |
| b3775.1 | Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line | $0 | |
| s2631 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| b3775.10 | Sag study on the Olive – University Park | $0 | |
| s2509 | NextEra review required: Acquired from ComEd. NextEra section SE rating is 1091 MVA | $0 | |
| b3775.9 | Upgrade existing terminal equipment (substation conductor) at Green Acres on the St. John to Green Acres 345 kV lin | $0 | |
| b3775.8 | Upgrade existing terminal equipment at St. John on the existing Crete to St. John 345 kV line | $0 | |
| b3775.3 | Rebuild ComEd’s section of 345 kV double circuit in IL from St. John to Crete | $0 | |
| b3775.2 | Reconductor NEET’s section of Crete(IN/IL border)-St. John 345 kV line (6.95 miles). | $0 | |
| b3775.5 | Replace E. Frankfort 345 kV circuit breaker “9-14” with 3150A SF6 circuit breaker. | $0 | |
| n3515.1 | Cherry Valley - Garden Prarie 345 kV line - reconductoring and sag mitigation. | $19,400,000 | |
| n3515.2 | Cherry Valley - Garden Prarie 345 kV Line Circuit Breaker Replacement | $3,000,000 | |
| b3775.4 | Rebuild 345 kV double circuit extending from Crete to E. Frankfort. | $0 | |
| n5318.1 | Garden Prarie - Silver Lake R 345 kV Line - Reconductor and Station Bus Work | $45,700,000 | |
| n5318.2 | Reconductor 26.7 miles of 2338 kcmil. Mitigate sag limits. Upgrade relay package. Replace station conductor at both line terminals. Replace 2-345 kV breakers and CT's at TSS 138 Silver Lake. | $170,000,000 | |
| n6279 | TSS 116 Replace 345 kV Circuit Breaker | $3,200,000 | |
| n8373 | Plano - Install 3rd Auto Transformer at TSS 167 Plano. | $20,000,000 | |
| (TBD) | Upgrade the 345kV line conductor from AB1-089 Interconnect Substation to AG1-119 Interconnection Substation (POI) | $45,000,000 | |
| n5145 | Reconfigure Wilton 765kV bus | $55,229,373 | |
| s2929 | Move 345 kV line 11126 (Electric Junction-Wayne) to Bus 6 and install 345 kV Bus Tie 5-6 CB. | $0 | |
| n8379 | Wilton Center - Install 3rd Transformer | $38,000,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-423 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.