AG1-412 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:56
Ladysmith CT-Mine Road 230 kV
80.0 MW Capacity / 200.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-412 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the Dominion zone — Caroline County, Virginia. The installed facilities will have a total capability of 200.0 MW with 80.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-412 |
| Project Name | Ladysmith CT-Mine Road 230 kV |
| Developer Name | Matta Grid, LLC |
| State | Virginia |
| County | Caroline |
| Transmission Owner | Dominion |
| MFO | 200.0 MW |
| MWE | 200.0 MW |
| MWC | 80.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-412 "Ladysmith CT-Mine Road 230 kV" will interconnect with the Dominion transmission system. The primary POI will be a newly constructed 230 kV three breaker ring bus located on the line between the Ladysmith CT substation and Summit substation.
Summer Peak Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 80.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
6CRANES-6STAFORD 230.0 kV Ckt 1 line
314134 to 314142 ckt 1 |
DVP_P1-2: LN 2089
CONTINGENCY 'DVP_P1-2: LN 2089' OPEN BRANCH FROM BUS 314196 TO BUS 314197 CKT 1 /*6LADYSMITH 230.0 - 6LDYSMITH CT 230.0 END |
Single | AC | 122.93 % | 126.36 % | 678.68 | B | 857.58 | 30.21 | |
| DVP |
6CRANES-6STAFORD 230.0 kV Ckt 1 line
314134 to 314142 ckt 1 |
DVP_P1-2: LN 568
CONTINGENCY 'DVP_P1-2: LN 568' OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET POSTCONTRATING 2078 BRANCH FROM BUS 314919 TO BUS 314922 CKT 1 /*8OX 500.0 - 8POSSUM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TAP 500.0 SET PRECONTRATING 1905 BRANCH FROM BUS 314919 TO BUS 314922 CKT 1 /*8OX 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TAP 500.0 END |
Single | AC | 116.95 % | 118.78 % | 678.68 | B | 806.16 | 16.09 | |
| DVP |
6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line
314142 to 314145 ckt 1 |
DVP_P1-2: LN 2089
CONTINGENCY 'DVP_P1-2: LN 2089' OPEN BRANCH FROM BUS 314196 TO BUS 314197 CKT 1 /*6LADYSMITH 230.0 - 6LDYSMITH CT 230.0 END |
Single | AC | 108.68 % | 112.08 % | 678.68 | B | 760.64 | 30.21 | |
| DVP |
6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line
314142 to 314145 ckt 1 |
DVP_P1-2: LN 568
CONTINGENCY 'DVP_P1-2: LN 568' OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH 500.0 - 8POSSUM 500.0 SET POSTCONTRATING 2078 BRANCH FROM BUS 314919 TO BUS 314922 CKT 1 /*8OX 500.0 - 8POSSUM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TAP 500.0 SET PRECONTRATING 1905 BRANCH FROM BUS 314919 TO BUS 314922 CKT 1 /*8OX 500.0 - 8POSSUM 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314911 TO BUS 962840 CKT 1 /*8LADYSMITH 500.0 - AG1-133 TAP 500.0 END |
Single | AC | 102.74 % | 104.56 % | 678.68 | B | 709.59 | 16.09 | |
| DVP |
6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line
314197 to 314196 ckt 1 |
DVP_P1-2: LN 2032
CONTINGENCY 'DVP_P1-2: LN 2032' OPEN BRANCH FROM BUS 314218 TO BUS 314222 CKT 1 /*6ELMONT 230.0 - 6HANOVER 230.0 OPEN BRANCH FROM BUS 314222 TO BUS 314212 CKT 1 /*6HANOVER 230.0 - 6FOUR RIVERS 230.0 OPEN BUS 314222 /*6HANOVER 230.0 END |
Single | AC | 102.06 % | 104.69 % | 1151.5 | B | 1205.47 | 53.27 | |
| DVP |
6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line
314144 to 314105 ckt 1 |
DVP_P1-2: LN 2089
CONTINGENCY 'DVP_P1-2: LN 2089' OPEN BRANCH FROM BUS 314196 TO BUS 314197 CKT 1 /*6LADYSMITH 230.0 - 6LDYSMITH CT 230.0 END |
Single | AC | 99.07 % | 102.49 % | 678.68 | B | 695.58 | 30.21 | |
| DVP |
6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line
314212 to 314222 ckt 1 |
DVP_P1-2: LN 2089
CONTINGENCY 'DVP_P1-2: LN 2089' OPEN BRANCH FROM BUS 314196 TO BUS 314197 CKT 1 /*6LADYSMITH 230.0 - 6LDYSMITH CT 230.0 END |
Single | AC | 98.64 % | 101.64 % | 1123.3 | B | 1141.68 | 34.05 | |
| Details for 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314131 | 6ARNOLDS | 80/20 | 0.58 MW | 0.58 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314134 | 6CRANES | 80/20 | 0.19 MW | 0.19 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314184 | 3SHACKLE | 80/20 | 0.33 MW | 0.33 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314190 | 6WESTMOR | 80/20 | 0.56 MW | 0.56 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314375 | 6CORRCTN | 80/20 | 0.21 MW | 0.21 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315033 | 1BIRCHWDA | 80/20 | 20.96 MW | 20.96 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315034 | 1NORNECKC1 | 80/20 | 0.81 MW | 0.81 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315035 | 1NORNECKC2 | 80/20 | 0.78 MW | 0.78 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315037 | 1LDYSMT1 | 80/20 | 9.88 MW | 9.88 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315038 | 1LDYSMT2 | 80/20 | 9.88 MW | 9.88 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315039 | 1LDYSMT3 | 80/20 | 9.51 MW | 9.51 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315040 | 1LDYSMT4 | 80/20 | 9.52 MW | 9.52 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315041 | 1LDYSMT5 | 80/20 | 9.55 MW | 9.55 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315050 | 1FOURRIVERG | 80/20 | 4.26 MW | 4.26 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315051 | 1AA1-145 CT1 | 80/20 | 4.23 MW | 4.23 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315052 | 1AA1-145 CT2 | 80/20 | 4.23 MW | 4.23 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 925863 | AC1-065 C | 80/20 | 3.37 MW | 3.37 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 927044 | AC1-191 C | 80/20 | 5.08 MW | 5.08 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934141 | AD1-041 C | 80/20 | 2.99 MW | 2.99 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934391 | AD1-063 C | 80/20 | 0.15 MW | 0.15 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934781 | AD1-105 C | 80/20 | 7.05 MW | 7.05 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 936581 | AD2-073 C | 80/20 | 2.96 MW | 2.96 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 936591 | AD2-074 C | 80/20 | 5.16 MW | 5.16 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 942191 | AE2-231 C O1 | 80/20 | 6.76 MW | 6.76 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943431 | AF1-014 C | 80/20 | 0.7 MW | 0.7 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943471 | AF1-018 | 80/20 | 3.81 MW | 3.81 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943741 | AF1-042 C | 80/20 | 2.7 MW | 2.7 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 944491 | AF1-114 C | 80/20 | 12.96 MW | 12.96 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 945831 | AF1-248 | 80/20 | 0.07 MW | 0.07 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 960091 | AF2-300 C | 80/20 | 3.07 MW | 3.07 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 961781 | AG1-019 | 80/20 | 37.07 MW | 37.07 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 961951 | AG1-038 C | 80/20 | 2.98 MW | 2.98 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966661 | AG1-536 C | 80/20 | 5.31 MW | 5.31 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966871 | AG1-558 C | 80/20 | 1.27 MW | 1.27 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966881 | AG1-559 C | 80/20 | 3.41 MW | 3.41 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 316077 | AC2-138 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 316156 | AD2-030 C | 80/20 | 0.23 MW | 0.23 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939245 | AE1-155 C | 80/20 | 12.64 MW | 12.64 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939261 | AE1-157 C O1 | 80/20 | 22.59 MW | 22.59 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939611 | AE1-191 C | 80/20 | 5.98 MW | 5.98 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 940231 | AE2-005 C | 80/20 | 0.74 MW | 0.74 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 940551 | AE2-041 | 80/20 | 3.81 MW | 3.81 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957191 | AF2-013 | 80/20 | 37.07 MW | 37.07 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957411 | AF2-035 C | 80/20 | 12.29 MW | 12.29 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957601 | AF2-054 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962851 | AG1-134 C | 80/20 | 9.53 MW | 9.53 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962861 | AG1-135 C | 80/20 | 5.85 MW | 5.85 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962971 | AG1-146 C | 80/20 | 2.56 MW | 2.56 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962981 | AG1-147 C | 80/20 | 5.98 MW | 5.98 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963051 | AG1-154 C | 80/20 | 6.99 MW | 6.99 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963611 | AG1-210 C | 80/20 | 0.77 MW | 0.77 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963621 | AG1-213 C | 80/20 | 1.02 MW | 1.02 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 964211 | AG1-282 C | 80/20 | 2.14 MW | 2.14 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 965441 | AG1-412 C | 80/20 | 30.21 MW | 30.21 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957971 | AF2-091 C | 80/20 | 4.41 MW | 4.41 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 958261 | AF2-120 C | 80/20 | 6.17 MW | 6.17 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315043 | 1FOUR RIVERA | 80/20 | 2.69 MW | 2.69 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315044 | 1FOUR RIVERB | 80/20 | 2.69 MW | 2.69 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315045 | 1FOUR RIVERC | 80/20 | 3.28 MW | 3.28 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315046 | 1FOUR RIVERD | 80/20 | 2.69 MW | 2.69 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315047 | 1FOUR RIVERE | 80/20 | 2.69 MW | 2.69 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315048 | 1FOUR RIVERF | 80/20 | 3.28 MW | 3.28 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.16 MW | 1.16 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.34 MW | 21.34 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.05 MW | 6.05 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.35 MW | 7.35 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.76 MW | 1.76 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.76 MW | 1.76 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.33 MW | 0.33 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.95 MW | 0.95 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.82 MW | 0.82 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.44 MW | 1.44 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314131 | 6ARNOLDS | 80/20 | 0.45 MW | 0.45 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314134 | 6CRANES | 80/20 | 0.15 MW | 0.15 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314184 | 3SHACKLE | 80/20 | 0.3 MW | 0.3 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314190 | 6WESTMOR | 80/20 | 0.44 MW | 0.44 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314375 | 6CORRCTN | 80/20 | 0.19 MW | 0.19 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315033 | 1BIRCHWDA | 80/20 | 16.15 MW | 16.15 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315034 | 1NORNECKC1 | 80/20 | 0.66 MW | 0.66 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315035 | 1NORNECKC2 | 80/20 | 0.64 MW | 0.64 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315037 | 1LDYSMT1 | 80/20 | 4.37 MW | 4.37 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315038 | 1LDYSMT2 | 80/20 | 4.37 MW | 4.37 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315039 | 1LDYSMT3 | 80/20 | 4.21 MW | 4.21 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315040 | 1LDYSMT4 | 80/20 | 4.21 MW | 4.21 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315041 | 1LDYSMT5 | 80/20 | 4.23 MW | 4.23 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315050 | 1FOURRIVERG | 80/20 | 3.37 MW | 3.37 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315051 | 1AA1-145 CT1 | 80/20 | 2.57 MW | 2.57 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315052 | 1AA1-145 CT2 | 80/20 | 2.57 MW | 2.57 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 925863 | AC1-065 C | 80/20 | 3.02 MW | 3.02 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 927044 | AC1-191 C | 80/20 | 4.24 MW | 4.24 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 934141 | AD1-041 C | 80/20 | 2.67 MW | 2.67 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 934391 | AD1-063 C | 80/20 | 0.13 MW | 0.13 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 934781 | AD1-105 C | 80/20 | 5.54 MW | 5.54 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 936581 | AD2-073 C | 80/20 | 2.38 MW | 2.38 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 936591 | AD2-074 C | 80/20 | 4.3 MW | 4.3 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 942191 | AE2-231 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 943431 | AF1-014 C | 80/20 | 0.62 MW | 0.62 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 943471 | AF1-018 | 80/20 | 3.43 MW | 3.43 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 943741 | AF1-042 C | 80/20 | 2.25 MW | 2.25 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 944491 | AF1-114 C | 80/20 | 10.17 MW | 10.17 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 945361 | AF1-201 C O1 | Adder | 6.42 MW | 5.46 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 945831 | AF1-248 | 80/20 | 0.06 MW | 0.06 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 960091 | AF2-300 C | 80/20 | 1.49 MW | 1.49 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 961781 | AG1-019 | 80/20 | 28.76 MW | 28.76 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 961951 | AG1-038 C | 80/20 | 2.49 MW | 2.49 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 966661 | AG1-536 C | 80/20 | 4.4 MW | 4.4 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 966871 | AG1-558 C | 80/20 | 1.06 MW | 1.06 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 966881 | AG1-559 C | 80/20 | 1.65 MW | 1.65 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 316077 | AC2-138 C | 80/20 | 0.17 MW | 0.17 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 316156 | AD2-030 C | 80/20 | 0.2 MW | 0.2 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 939245 | AE1-155 C | 80/20 | 10.48 MW | 10.48 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 939261 | AE1-157 C O1 | 80/20 | 10.54 MW | 10.54 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 939611 | AE1-191 C | 80/20 | 5.33 MW | 5.33 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 940231 | AE2-005 C | 80/20 | 0.66 MW | 0.66 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 940551 | AE2-041 | 80/20 | 3.43 MW | 3.43 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957191 | AF2-013 | 80/20 | 28.76 MW | 28.76 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957411 | AF2-035 C | 80/20 | 5.97 MW | 5.97 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957601 | AF2-054 C | 80/20 | 1.09 MW | 1.09 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962531 | AG1-102 C | Adder | 0.47 MW | 0.4 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962851 | AG1-134 C | 80/20 | 7.48 MW | 7.48 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962861 | AG1-135 C | 80/20 | 4.86 MW | 4.86 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962971 | AG1-146 C | 80/20 | 2.17 MW | 2.17 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962981 | AG1-147 C | 80/20 | 5.05 MW | 5.05 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 963051 | AG1-154 C | 80/20 | 3.09 MW | 3.09 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 963611 | AG1-210 C | 80/20 | 0.63 MW | 0.63 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 963621 | AG1-213 C | 80/20 | 0.5 MW | 0.5 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 964211 | AG1-282 C | 80/20 | 1.76 MW | 1.76 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 965441 | AG1-412 C | 80/20 | 16.09 MW | 16.09 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957831 | AF2-077 C | Adder | 0.91 MW | 0.78 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957971 | AF2-091 C | 80/20 | 3.46 MW | 3.46 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 958261 | AF2-120 C | 80/20 | 5.12 MW | 5.12 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315043 | 1FOUR RIVERA | 80/20 | 1.63 MW | 1.63 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315044 | 1FOUR RIVERB | 80/20 | 1.63 MW | 1.63 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315045 | 1FOUR RIVERC | 80/20 | 2.0 MW | 2.0 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315046 | 1FOUR RIVERD | 80/20 | 1.63 MW | 1.63 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315047 | 1FOUR RIVERE | 80/20 | 1.63 MW | 1.63 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315048 | 1FOUR RIVERF | 80/20 | 2.0 MW | 2.0 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.4 MW | 1.4 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.45 MW | 26.45 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.96 MW | 10.96 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.87 MW | 10.87 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.11 MW | 2.11 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.48 MW | 2.48 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.54 MW | 1.54 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.02 MW | 2.02 MW |
| 6CRANES-6STAFORD 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| Details for 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314131 | 6ARNOLDS | 80/20 | 0.58 MW | 0.58 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314134 | 6CRANES | 80/20 | 0.19 MW | 0.19 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314184 | 3SHACKLE | 80/20 | 0.33 MW | 0.33 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314190 | 6WESTMOR | 80/20 | 0.56 MW | 0.56 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314375 | 6CORRCTN | 80/20 | 0.21 MW | 0.21 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315033 | 1BIRCHWDA | 80/20 | 20.96 MW | 20.96 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315034 | 1NORNECKC1 | 80/20 | 0.81 MW | 0.81 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315035 | 1NORNECKC2 | 80/20 | 0.78 MW | 0.78 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315037 | 1LDYSMT1 | 80/20 | 9.88 MW | 9.88 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315038 | 1LDYSMT2 | 80/20 | 9.88 MW | 9.88 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315039 | 1LDYSMT3 | 80/20 | 9.51 MW | 9.51 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315040 | 1LDYSMT4 | 80/20 | 9.52 MW | 9.52 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315041 | 1LDYSMT5 | 80/20 | 9.55 MW | 9.55 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315050 | 1FOURRIVERG | 80/20 | 4.26 MW | 4.26 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315051 | 1AA1-145 CT1 | 80/20 | 4.23 MW | 4.23 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315052 | 1AA1-145 CT2 | 80/20 | 4.23 MW | 4.23 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 925863 | AC1-065 C | 80/20 | 3.37 MW | 3.37 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 927044 | AC1-191 C | 80/20 | 5.08 MW | 5.08 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934141 | AD1-041 C | 80/20 | 2.99 MW | 2.99 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934391 | AD1-063 C | 80/20 | 0.15 MW | 0.15 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934781 | AD1-105 C | 80/20 | 7.05 MW | 7.05 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 936581 | AD2-073 C | 80/20 | 2.96 MW | 2.96 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 936591 | AD2-074 C | 80/20 | 5.16 MW | 5.16 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 942191 | AE2-231 C O1 | 80/20 | 6.76 MW | 6.76 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943431 | AF1-014 C | 80/20 | 0.7 MW | 0.7 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943471 | AF1-018 | 80/20 | 3.81 MW | 3.81 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943741 | AF1-042 C | 80/20 | 2.7 MW | 2.7 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 944491 | AF1-114 C | 80/20 | 12.96 MW | 12.96 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 945831 | AF1-248 | 80/20 | 0.07 MW | 0.07 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 960091 | AF2-300 C | 80/20 | 3.07 MW | 3.07 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 961781 | AG1-019 | 80/20 | 37.07 MW | 37.07 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 961951 | AG1-038 C | 80/20 | 2.98 MW | 2.98 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966661 | AG1-536 C | 80/20 | 5.31 MW | 5.31 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966871 | AG1-558 C | 80/20 | 1.27 MW | 1.27 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966881 | AG1-559 C | 80/20 | 3.41 MW | 3.41 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 316077 | AC2-138 C | 80/20 | 0.21 MW | 0.21 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 316156 | AD2-030 C | 80/20 | 0.23 MW | 0.23 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939245 | AE1-155 C | 80/20 | 12.64 MW | 12.64 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939261 | AE1-157 C O1 | 80/20 | 22.59 MW | 22.59 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939611 | AE1-191 C | 80/20 | 5.98 MW | 5.98 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 940231 | AE2-005 C | 80/20 | 0.74 MW | 0.74 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 940551 | AE2-041 | 80/20 | 3.81 MW | 3.81 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957191 | AF2-013 | 80/20 | 37.07 MW | 37.07 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957411 | AF2-035 C | 80/20 | 12.29 MW | 12.29 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957601 | AF2-054 C | 80/20 | 1.23 MW | 1.23 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962851 | AG1-134 C | 80/20 | 9.53 MW | 9.53 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962861 | AG1-135 C | 80/20 | 5.85 MW | 5.85 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962971 | AG1-146 C | 80/20 | 2.56 MW | 2.56 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962981 | AG1-147 C | 80/20 | 5.98 MW | 5.98 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963051 | AG1-154 C | 80/20 | 6.99 MW | 6.99 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963611 | AG1-210 C | 80/20 | 0.77 MW | 0.77 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963621 | AG1-213 C | 80/20 | 1.02 MW | 1.02 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 964211 | AG1-282 C | 80/20 | 2.14 MW | 2.14 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 965441 | AG1-412 C | 80/20 | 30.21 MW | 30.21 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957971 | AF2-091 C | 80/20 | 4.41 MW | 4.41 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 958261 | AF2-120 C | 80/20 | 6.17 MW | 6.17 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315043 | 1FOUR RIVERA | 80/20 | 2.69 MW | 2.69 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315044 | 1FOUR RIVERB | 80/20 | 2.69 MW | 2.69 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315045 | 1FOUR RIVERC | 80/20 | 3.28 MW | 3.28 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315046 | 1FOUR RIVERD | 80/20 | 2.69 MW | 2.69 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315047 | 1FOUR RIVERE | 80/20 | 2.69 MW | 2.69 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315048 | 1FOUR RIVERF | 80/20 | 3.28 MW | 3.28 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.16 MW | 1.16 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.34 MW | 21.34 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.05 MW | 6.05 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.35 MW | 7.35 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.76 MW | 1.76 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.76 MW | 1.76 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.33 MW | 0.33 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.95 MW | 0.95 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.82 MW | 0.82 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.44 MW | 1.44 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314131 | 6ARNOLDS | 80/20 | 0.45 MW | 0.45 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314134 | 6CRANES | 80/20 | 0.15 MW | 0.15 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314184 | 3SHACKLE | 80/20 | 0.3 MW | 0.3 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314190 | 6WESTMOR | 80/20 | 0.44 MW | 0.44 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 314375 | 6CORRCTN | 80/20 | 0.19 MW | 0.19 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315033 | 1BIRCHWDA | 80/20 | 16.15 MW | 16.15 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315034 | 1NORNECKC1 | 80/20 | 0.66 MW | 0.66 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315035 | 1NORNECKC2 | 80/20 | 0.64 MW | 0.64 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315037 | 1LDYSMT1 | 80/20 | 4.37 MW | 4.37 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315038 | 1LDYSMT2 | 80/20 | 4.37 MW | 4.37 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315039 | 1LDYSMT3 | 80/20 | 4.21 MW | 4.21 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315040 | 1LDYSMT4 | 80/20 | 4.21 MW | 4.21 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315041 | 1LDYSMT5 | 80/20 | 4.23 MW | 4.23 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315050 | 1FOURRIVERG | 80/20 | 3.37 MW | 3.37 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315051 | 1AA1-145 CT1 | 80/20 | 2.57 MW | 2.57 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315052 | 1AA1-145 CT2 | 80/20 | 2.57 MW | 2.57 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 925863 | AC1-065 C | 80/20 | 3.02 MW | 3.02 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 927044 | AC1-191 C | 80/20 | 4.24 MW | 4.24 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 934141 | AD1-041 C | 80/20 | 2.67 MW | 2.67 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 934391 | AD1-063 C | 80/20 | 0.13 MW | 0.13 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 934781 | AD1-105 C | 80/20 | 5.54 MW | 5.54 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 936581 | AD2-073 C | 80/20 | 2.38 MW | 2.38 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 936591 | AD2-074 C | 80/20 | 4.3 MW | 4.3 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 942191 | AE2-231 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 943431 | AF1-014 C | 80/20 | 0.62 MW | 0.62 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 943471 | AF1-018 | 80/20 | 3.43 MW | 3.43 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 943741 | AF1-042 C | 80/20 | 2.25 MW | 2.25 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 944491 | AF1-114 C | 80/20 | 10.17 MW | 10.17 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 945361 | AF1-201 C O1 | Adder | 6.42 MW | 5.46 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 945831 | AF1-248 | 80/20 | 0.06 MW | 0.06 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 960091 | AF2-300 C | 80/20 | 1.49 MW | 1.49 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 961781 | AG1-019 | 80/20 | 28.76 MW | 28.76 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 961951 | AG1-038 C | 80/20 | 2.49 MW | 2.49 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 966661 | AG1-536 C | 80/20 | 4.4 MW | 4.4 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 966871 | AG1-558 C | 80/20 | 1.06 MW | 1.06 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 966881 | AG1-559 C | 80/20 | 1.65 MW | 1.65 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 316077 | AC2-138 C | 80/20 | 0.17 MW | 0.17 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 316156 | AD2-030 C | 80/20 | 0.2 MW | 0.2 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 939245 | AE1-155 C | 80/20 | 10.48 MW | 10.48 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 939261 | AE1-157 C O1 | 80/20 | 10.54 MW | 10.54 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 939611 | AE1-191 C | 80/20 | 5.33 MW | 5.33 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 940231 | AE2-005 C | 80/20 | 0.66 MW | 0.66 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 940551 | AE2-041 | 80/20 | 3.43 MW | 3.43 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957191 | AF2-013 | 80/20 | 28.76 MW | 28.76 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957411 | AF2-035 C | 80/20 | 5.97 MW | 5.97 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957601 | AF2-054 C | 80/20 | 1.09 MW | 1.09 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962531 | AG1-102 C | Adder | 0.47 MW | 0.4 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962851 | AG1-134 C | 80/20 | 7.48 MW | 7.48 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962861 | AG1-135 C | 80/20 | 4.86 MW | 4.86 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962971 | AG1-146 C | 80/20 | 2.17 MW | 2.17 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 962981 | AG1-147 C | 80/20 | 5.05 MW | 5.05 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 963051 | AG1-154 C | 80/20 | 3.09 MW | 3.09 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 963611 | AG1-210 C | 80/20 | 0.63 MW | 0.63 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 963621 | AG1-213 C | 80/20 | 0.5 MW | 0.5 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 964211 | AG1-282 C | 80/20 | 1.76 MW | 1.76 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 965441 | AG1-412 C | 80/20 | 16.09 MW | 16.09 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957831 | AF2-077 C | Adder | 0.91 MW | 0.78 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 957971 | AF2-091 C | 80/20 | 3.46 MW | 3.46 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 958261 | AF2-120 C | 80/20 | 5.12 MW | 5.12 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315043 | 1FOUR RIVERA | 80/20 | 1.63 MW | 1.63 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315044 | 1FOUR RIVERB | 80/20 | 1.63 MW | 1.63 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315045 | 1FOUR RIVERC | 80/20 | 2.0 MW | 2.0 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315046 | 1FOUR RIVERD | 80/20 | 1.63 MW | 1.63 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315047 | 1FOUR RIVERE | 80/20 | 1.63 MW | 1.63 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | 315048 | 1FOUR RIVERF | 80/20 | 2.0 MW | 2.0 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.4 MW | 1.4 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.45 MW | 26.45 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.96 MW | 10.96 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 10.87 MW | 10.87 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.11 MW | 2.11 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.48 MW | 2.48 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.13 MW | 0.13 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.56 MW | 0.56 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.54 MW | 1.54 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.91 MW | 0.91 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.1 MW | 0.1 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.02 MW | 2.02 MW |
| 6STAFORD-6AQUI_HARB_B 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 568 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.27 MW | 0.27 MW |
| Details for 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 314131 | 6ARNOLDS | 80/20 | 0.48 MW | 0.48 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 314134 | 6CRANES | 80/20 | 0.12 MW | 0.12 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 314190 | 6WESTMOR | 80/20 | 0.39 MW | 0.39 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315008 | 1POSSM6A | 80/20 | 1.74 MW | 1.74 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315009 | 1POSSM6B | 80/20 | 1.74 MW | 1.74 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315010 | 1POSSM6S | 80/20 | 2.71 MW | 2.71 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315015 | 1POSSMC1 | 80/20 | 0.39 MW | 0.39 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315018 | 1POSSMC2 | 80/20 | 0.39 MW | 0.39 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315033 | 1BIRCHWDA | 80/20 | 17.45 MW | 17.45 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315034 | 1NORNECKC1 | 80/20 | 0.5 MW | 0.5 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315035 | 1NORNECKC2 | 80/20 | 0.49 MW | 0.49 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315037 | 1LDYSMT1 | 80/20 | 20.87 MW | 20.87 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315038 | 1LDYSMT2 | 80/20 | 20.87 MW | 20.87 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315039 | 1LDYSMT3 | 80/20 | 20.1 MW | 20.1 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315040 | 1LDYSMT4 | 80/20 | 20.13 MW | 20.13 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315041 | 1LDYSMT5 | 80/20 | 20.2 MW | 20.2 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315050 | 1FOURRIVERG | 80/20 | 2.02 MW | 2.02 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315051 | 1AA1-145 CT1 | 80/20 | 21.38 MW | 21.38 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315052 | 1AA1-145 CT2 | 80/20 | 21.38 MW | 21.38 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 934781 | AD1-105 C | 80/20 | 3.72 MW | 3.72 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 936581 | AD2-073 C | 80/20 | 1.99 MW | 1.99 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 936591 | AD2-074 C | 80/20 | 2.78 MW | 2.78 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 942191 | AE2-231 C O1 | 80/20 | 19.49 MW | 19.49 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 943741 | AF1-042 C | 80/20 | 1.45 MW | 1.45 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 944491 | AF1-114 C | 80/20 | 9.94 MW | 9.94 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 945831 | AF1-248 | 80/20 | 0.04 MW | 0.04 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 960091 | AF2-300 C | 80/20 | 8.86 MW | 8.86 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 961781 | AG1-019 | 80/20 | 29.94 MW | 29.94 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 961951 | AG1-038 C | 80/20 | 1.6 MW | 1.6 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 966661 | AG1-536 C | 80/20 | 2.97 MW | 2.97 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 966881 | AG1-559 C | 80/20 | 9.82 MW | 9.82 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 316077 | AC2-138 C | 80/20 | 0.13 MW | 0.13 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 939245 | AE1-155 C | 80/20 | 7.08 MW | 7.08 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 939261 | AE1-157 C O1 | 80/20 | 57.44 MW | 57.44 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 957191 | AF2-013 | 80/20 | 29.94 MW | 29.94 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 957411 | AF2-035 C | 80/20 | 35.44 MW | 35.44 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 962851 | AG1-134 C | 80/20 | 5.03 MW | 5.03 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 962861 | AG1-135 C | 80/20 | 3.22 MW | 3.22 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 962971 | AG1-146 C | 80/20 | 1.25 MW | 1.25 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 962981 | AG1-147 C | 80/20 | 2.91 MW | 2.91 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 963051 | AG1-154 C | 80/20 | 14.77 MW | 14.77 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 963611 | AG1-210 C | 80/20 | 0.48 MW | 0.48 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 963621 | AG1-213 C | 80/20 | 2.95 MW | 2.95 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 964211 | AG1-282 C | 80/20 | 1.26 MW | 1.26 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 965441 | AG1-412 C | 80/20 | 53.27 MW | 53.27 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 957971 | AF2-091 C | 80/20 | 3.38 MW | 3.38 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 958261 | AF2-120 C | 80/20 | 3.46 MW | 3.46 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315043 | 1FOUR RIVERA | 80/20 | 13.58 MW | 13.58 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315044 | 1FOUR RIVERB | 80/20 | 13.58 MW | 13.58 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315045 | 1FOUR RIVERC | 80/20 | 16.6 MW | 16.6 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315046 | 1FOUR RIVERD | 80/20 | 13.58 MW | 13.58 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315047 | 1FOUR RIVERE | 80/20 | 13.58 MW | 13.58 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | 315048 | 1FOUR RIVERF | 80/20 | 16.6 MW | 16.6 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.12 MW | 1.12 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.09 MW | 1.09 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 1.92 MW | 1.92 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.62 MW | 0.62 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.48 MW | 0.48 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.63 MW | 0.63 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 2.52 MW | 2.52 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.6 MW | 0.6 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.82 MW | 0.82 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.2 MW | 0.2 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 2.94 MW | 2.94 MW |
| 6LDYSMITH CT-6LADYSMITH 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2032 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.61 MW | 0.61 MW |
| Details for 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314131 | 6ARNOLDS | 80/20 | 0.58 MW | 0.58 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314134 | 6CRANES | 80/20 | 0.19 MW | 0.19 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314184 | 3SHACKLE | 80/20 | 0.33 MW | 0.33 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314190 | 6WESTMOR | 80/20 | 0.56 MW | 0.56 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314375 | 6CORRCTN | 80/20 | 0.21 MW | 0.21 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315033 | 1BIRCHWDA | 80/20 | 20.96 MW | 20.96 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315034 | 1NORNECKC1 | 80/20 | 0.81 MW | 0.81 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315035 | 1NORNECKC2 | 80/20 | 0.78 MW | 0.78 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315037 | 1LDYSMT1 | 80/20 | 9.88 MW | 9.88 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315038 | 1LDYSMT2 | 80/20 | 9.88 MW | 9.88 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315039 | 1LDYSMT3 | 80/20 | 9.51 MW | 9.51 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315040 | 1LDYSMT4 | 80/20 | 9.52 MW | 9.52 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315041 | 1LDYSMT5 | 80/20 | 9.55 MW | 9.55 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315050 | 1FOURRIVERG | 80/20 | 4.26 MW | 4.26 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315051 | 1AA1-145 CT1 | 80/20 | 4.23 MW | 4.23 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315052 | 1AA1-145 CT2 | 80/20 | 4.23 MW | 4.23 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 925863 | AC1-065 C | 80/20 | 3.37 MW | 3.37 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 927044 | AC1-191 C | 80/20 | 5.08 MW | 5.08 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934141 | AD1-041 C | 80/20 | 2.99 MW | 2.99 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934391 | AD1-063 C | 80/20 | 0.15 MW | 0.15 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 934781 | AD1-105 C | 80/20 | 7.05 MW | 7.05 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 936581 | AD2-073 C | 80/20 | 2.96 MW | 2.96 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 936591 | AD2-074 C | 80/20 | 5.16 MW | 5.16 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 942191 | AE2-231 C O1 | 80/20 | 6.76 MW | 6.76 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943431 | AF1-014 C | 80/20 | 0.7 MW | 0.7 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943471 | AF1-018 | 80/20 | 3.81 MW | 3.81 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 943741 | AF1-042 C | 80/20 | 2.7 MW | 2.7 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 944491 | AF1-114 C | 80/20 | 12.96 MW | 12.96 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 945831 | AF1-248 | 80/20 | 0.07 MW | 0.07 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 960091 | AF2-300 C | 80/20 | 3.07 MW | 3.07 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 961781 | AG1-019 | 80/20 | 37.07 MW | 37.07 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 961951 | AG1-038 C | 80/20 | 2.98 MW | 2.98 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966661 | AG1-536 C | 80/20 | 5.31 MW | 5.31 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966871 | AG1-558 C | 80/20 | 1.27 MW | 1.27 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966881 | AG1-559 C | 80/20 | 3.41 MW | 3.41 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 316077 | AC2-138 C | 80/20 | 0.21 MW | 0.21 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 316156 | AD2-030 C | 80/20 | 0.23 MW | 0.23 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939245 | AE1-155 C | 80/20 | 12.64 MW | 12.64 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939261 | AE1-157 C O1 | 80/20 | 22.59 MW | 22.59 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939611 | AE1-191 C | 80/20 | 5.98 MW | 5.98 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 940231 | AE2-005 C | 80/20 | 0.74 MW | 0.74 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 940551 | AE2-041 | 80/20 | 3.81 MW | 3.81 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957191 | AF2-013 | 80/20 | 37.07 MW | 37.07 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957411 | AF2-035 C | 80/20 | 12.29 MW | 12.29 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957601 | AF2-054 C | 80/20 | 1.23 MW | 1.23 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962851 | AG1-134 C | 80/20 | 9.53 MW | 9.53 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962861 | AG1-135 C | 80/20 | 5.85 MW | 5.85 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962971 | AG1-146 C | 80/20 | 2.56 MW | 2.56 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 962981 | AG1-147 C | 80/20 | 5.98 MW | 5.98 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963051 | AG1-154 C | 80/20 | 6.99 MW | 6.99 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963611 | AG1-210 C | 80/20 | 0.77 MW | 0.77 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963621 | AG1-213 C | 80/20 | 1.02 MW | 1.02 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 964211 | AG1-282 C | 80/20 | 2.14 MW | 2.14 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 965441 | AG1-412 C | 80/20 | 30.21 MW | 30.21 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957971 | AF2-091 C | 80/20 | 4.41 MW | 4.41 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 958261 | AF2-120 C | 80/20 | 6.17 MW | 6.17 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315043 | 1FOUR RIVERA | 80/20 | 2.69 MW | 2.69 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315044 | 1FOUR RIVERB | 80/20 | 2.69 MW | 2.69 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315045 | 1FOUR RIVERC | 80/20 | 3.28 MW | 3.28 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315046 | 1FOUR RIVERD | 80/20 | 2.69 MW | 2.69 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315047 | 1FOUR RIVERE | 80/20 | 2.69 MW | 2.69 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315048 | 1FOUR RIVERF | 80/20 | 3.28 MW | 3.28 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.16 MW | 1.16 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.34 MW | 21.34 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 6.05 MW | 6.05 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.35 MW | 7.35 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.76 MW | 1.76 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.76 MW | 1.76 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.12 MW | 0.12 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.33 MW | 0.33 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.95 MW | 0.95 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.82 MW | 0.82 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.06 MW | 0.06 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.44 MW | 1.44 MW |
| 6AQUI_HARB_A-6AQUIA 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.15 MW | 0.15 MW |
| Details for 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314131 | 6ARNOLDS | 80/20 | 0.29 MW | 0.29 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314134 | 6CRANES | 80/20 | 0.08 MW | 0.08 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 314190 | 6WESTMOR | 80/20 | 0.2 MW | 0.2 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315033 | 1BIRCHWDA | 80/20 | 10.83 MW | 10.83 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315037 | 1LDYSMT1 | 80/20 | 13.35 MW | 13.35 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315038 | 1LDYSMT2 | 80/20 | 13.35 MW | 13.35 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315039 | 1LDYSMT3 | 80/20 | 12.86 MW | 12.86 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315040 | 1LDYSMT4 | 80/20 | 12.88 MW | 12.88 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315041 | 1LDYSMT5 | 80/20 | 12.92 MW | 12.92 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315051 | 1AA1-145 CT1 | 80/20 | 23.38 MW | 23.38 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315052 | 1AA1-145 CT2 | 80/20 | 23.38 MW | 23.38 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 936581 | AD2-073 C | 80/20 | 0.92 MW | 0.92 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 942191 | AE2-231 C O1 | 80/20 | 16.52 MW | 16.52 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 944491 | AF1-114 C | 80/20 | 5.6 MW | 5.6 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 960091 | AF2-300 C | 80/20 | 7.51 MW | 7.51 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 961781 | AG1-019 | 80/20 | 17.96 MW | 17.96 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 966881 | AG1-559 C | 80/20 | 8.32 MW | 8.32 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 939261 | AE1-157 C O1 | 80/20 | 44.31 MW | 44.31 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957191 | AF2-013 | 80/20 | 17.96 MW | 17.96 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957411 | AF2-035 C | 80/20 | 30.05 MW | 30.05 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963051 | AG1-154 C | 80/20 | 9.45 MW | 9.45 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 963621 | AG1-213 C | 80/20 | 2.5 MW | 2.5 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 965441 | AG1-412 C | 80/20 | 34.05 MW | 34.05 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 957971 | AF2-091 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315043 | 1FOUR RIVERA | 80/20 | 14.85 MW | 14.85 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315044 | 1FOUR RIVERB | 80/20 | 14.85 MW | 14.85 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315045 | 1FOUR RIVERC | 80/20 | 18.15 MW | 18.15 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315046 | 1FOUR RIVERD | 80/20 | 14.85 MW | 14.85 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315047 | 1FOUR RIVERE | 80/20 | 14.85 MW | 14.85 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | 315048 | 1FOUR RIVERF | 80/20 | 18.15 MW | 18.15 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 1.31 MW | 1.31 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.93 MW | 1.93 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.18 MW | 2.18 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.85 MW | 0.85 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.76 MW | 0.76 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.17 MW | 0.17 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.87 MW | 0.87 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 3.31 MW | 3.31 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.68 MW | 0.68 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.69 MW | 0.69 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 1.4 MW | 1.4 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 3.54 MW | 3.54 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.7 MW | 0.7 MW |
| 6FOUR RIVERS-6HANOVER 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2089 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.8 MW | 1.8 MW |
Light Load Analysis
The Queue Project was evaluated as a 200.0 MW (Capacity 80.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7588 | Rebuild 3.745 miles of 230 kV Line 252 from Aquia to Aquia Harbor with 2-636 ACSR (24/7) 150 C. Replace Line lead at Aquia terminal and wave trap at Aquia Harbor terminal. | $9,562,500 | |
| b3321 | Rebuild 7.62 miles of 230 kV Line 2104 from Cranes Corner to Stafford with 2-636 | $0 | |
| n6162 | Replace Wave traps at the Four Rivers and Hanover 230 kV substations. | $300,000 | |
| b3027.2 | PJM Baseline Upgrade b3027.2. Re-conductor Line #2089 between Ladysmith and [...] 5 MVA. The baseline project has an projected in-service date of 06/01/2021. | $0 | |
| n6175 | Add a Second 230 kV Circuit between Ladysmith and Ladysmith CT. | $1,600,000 | |
| n6826 | Install a second 230 kV circuit of 3.94 miles from Ladysmith to Ladysmith CT (Line 2089) with a 2000/2000/2300 MVA conductor. Add Breakers at both stations. | $8,310,000 | |
| n6382 | Rebuild 0.32 miles of 230 kV Line2104 from Stafford to Aquia Harbor with 2-636 ACSR. | $500,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-412 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.