AG1-411 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:47
Maddox Creek-RP Mone 345 kV
100.0 MW Capacity / 100.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-411 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the AEP zone — Van Wert County, Ohio. The installed facilities will have a total capability of 100.0 MW with 100.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-411 |
| Project Name | Maddox Creek-RP Mone 345 kV |
| Developer Name | Butterfly Meadows Solar Project, LLC |
| State | Ohio |
| County | Van Wert |
| Transmission Owner | AEP |
| MFO | 100.0 MW |
| MWE | 100.0 MW |
| MWC | 100.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-411 will interconnect on the AEP transmission system at RP Mone – Maddox Creek 345kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 100.0 MW (Capacity 100.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP |
AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line
965420 to 246929 ckt 1 |
Base Case | Single | AC | 105.46 % | 110.94 % | 897.0 | A | 995.15 | 48.21 | |
| AEP |
AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line
965420 to 246929 ckt 1 |
AEP_P1-2_#7441_100545-A
CONTINGENCY 'AEP_P1-2_#7441_100545-A' OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 END |
Single | AC | 97.82 % | 101.68 % | 1301.0 | B | 1322.83 | 49.79 | |
| AEP |
AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line
958430 to 242928 ckt 1 |
AEP_P1-2_#6457_16758-B
CONTINGENCY 'AEP_P1-2_#6457_16758-B' OPEN BRANCH FROM BUS 965420 TO BUS 246929 CKT 1 /*AG1-410 TAP 345.0 - 05MADDOX 345.0 END |
Single | AC | 99.79 % | 100.18 % | 4142.0 | B | 4149.46 | 24.94 | |
| AEP |
AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line
965420 to 246929 ckt 1 |
AEP_P4_#7445_05MARYSV 765_B
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B' OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 OPEN BRANCH FROM BUS 962760 TO BUS 242928 CKT 1 /*AG1-125 TAP 765.0 - 05MARYSV 765.0 END |
Breaker | AC | 104.91 % | 108.77 % | 1301.0 | B | 1415.11 | 49.46 | |
| AEP |
05SORENS-05ROB PK 345.0 kV Ckt 1 line
243232 to 243231 ckt 1 |
AEP_P4_#9391_05SORENS 345_F
CONTINGENCY 'AEP_P4_#9391_05SORENS 345_F' OPEN BRANCH FROM BUS 243211 TO BUS 243232 CKT 1 /*05ALLEN 345.0 - 05SORENS 345.0 OPEN BRANCH FROM BUS 243232 TO BUS 246999 CKT 3 /*05SORENS 345.0 - 05SORENS 765.0 END |
Breaker | AC | 103.81 % | 105.19 % | 1203.0 | B | 1265.38 | 17.16 | |
| AEP |
AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line
965420 to 246929 ckt 1 |
AEP_P4_#7446_05MARYSV 765_B2
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2' OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2 /*05MARYSV 765.0 - 05MARYSV 345.0 OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 END |
Breaker | AC | 100.1 % | 103.88 % | 1301.0 | B | 1351.49 | 48.98 | |
| AEP |
05SORENS-05ROB PK 345.0 kV Ckt 1 line
243232 to 243231 ckt 1 |
AEP_P4_#7445_05MARYSV 765_B
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B' OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 OPEN BRANCH FROM BUS 962760 TO BUS 242928 CKT 1 /*AG1-125 TAP 765.0 - 05MARYSV 765.0 END |
Breaker | AC | 100.8 % | 101.88 % | 1203.0 | B | 1225.57 | 12.75 | |
| AEP |
05SORENS-05ROB PK 345.0 kV Ckt 1 line
243232 to 243231 ckt 1 |
AEP_P4_#7446_05MARYSV 765_B2
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2' OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2 /*05MARYSV 765.0 - 05MARYSV 345.0 OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 END |
Breaker | AC | 99.44 % | 100.49 % | 1203.0 | B | 1208.85 | 12.91 | |
| Details for AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 961761 | AG1-017 C | 80/20 | 0.12 MW | 0.12 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 962031 | AG1-047 C | 80/20 | 3.1 MW | 3.1 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 962601 | AG1-109 | 80/20 | 1.36 MW | 1.36 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 963701 | AG1-222 C | 80/20 | 7.25 MW | 7.25 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 963731 | AG1-225 C | 80/20 | 17.41 MW | 17.41 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 963791 | AG1-232 C | 80/20 | 8.34 MW | 8.34 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 964611 | AG1-324 C O1 | 80/20 | 1.43 MW | 1.43 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965011 | AG1-365 C | 80/20 | 10.45 MW | 10.45 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965021 | AG1-366 C | 80/20 | 3.48 MW | 3.48 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965031 | AG1-367 C | 80/20 | 3.06 MW | 3.06 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965041 | AG1-368 C | 80/20 | 5.94 MW | 5.94 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965051 | AG1-369 C | 80/20 | 2.5 MW | 2.5 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965101 | AG1-375 C | 80/20 | 3.81 MW | 3.81 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965421 | AG1-410 C O1 | 80/20 | 86.78 MW | 86.78 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965431 | AG1-411 O1 | 80/20 | 48.21 MW | 48.21 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965491 | AG1-417 C O1 | 80/20 | 2.8 MW | 2.8 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965501 | AG1-418 C O1 | 80/20 | 2.8 MW | 2.8 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965561 | AG1-424 C | 80/20 | 4.76 MW | 4.76 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965651 | AG1-433 C | 80/20 | 1.15 MW | 1.15 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965681 | AG1-436 C | 80/20 | 3.77 MW | 3.77 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965791 | AG1-447 | 80/20 | 2.76 MW | 2.76 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965841 | AG1-453 C O1 | 80/20 | 7.1 MW | 7.1 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 965851 | AG1-454 O1 | 80/20 | 4.23 MW | 4.23 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 246397 | 05ELKHART HY | 80/20 | 0.03 MW | 0.03 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 246416 | 05TWIN BRCH1 | 80/20 | 0.04 MW | 0.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 246422 | 05MAYFLWER | 80/20 | 0.05 MW | 0.05 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 246431 | 05BUCHANAN | 80/20 | 0.03 MW | 0.03 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 246536 | 05MOTTVILL | 80/20 | 0.02 MW | 0.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 246953 | 05TIMB G C | 80/20 | 0.28 MW | 0.28 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247270 | 05RPMNG1 | 80/20 | 10.26 MW | 10.26 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247271 | 05RPMNG2 | 80/20 | 10.25 MW | 10.25 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247272 | 05RPMNG3 | 80/20 | 10.26 MW | 10.26 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247292 | 05KEY G1 | 80/20 | 0.7 MW | 0.7 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247293 | 05KEY G2 | 80/20 | 0.7 MW | 0.7 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247294 | 05KEY G3 | 80/20 | 0.72 MW | 0.72 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247295 | 05KEY G4 | 80/20 | 0.72 MW | 0.72 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247521 | T131 | 80/20 | 0.43 MW | 0.43 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247620 | Y3-023 | 80/20 | 0.05 MW | 0.05 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247621 | Y3-024 | 80/20 | 0.02 MW | 0.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 247643 | Z2-116 C | 80/20 | 0.01 MW | 0.01 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 926865 | AC1-173 C | 80/20 | 0.14 MW | 0.14 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 936141 | AD2-020 C O1 | 80/20 | 3.38 MW | 3.38 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 936631 | AD2-079 C O1 | 80/20 | 0.72 MW | 0.72 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 942221 | AE2-234 C O1 | 80/20 | 1.82 MW | 1.82 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 942241 | AE2-236 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 943001 | AE2-323 C | 80/20 | 5.41 MW | 5.41 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 943021 | AE2-325 C | 80/20 | 1.71 MW | 1.71 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944161 | AF1-084 C | 80/20 | 2.88 MW | 2.88 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944231 | AF1-091 C O1 | 80/20 | 12.94 MW | 12.94 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944241 | AF1-092 C O1 | 80/20 | 9.12 MW | 9.12 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944531 | AF1-118 C O1 | 80/20 | 19.68 MW | 19.68 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944541 | AF1-119 C O1 | 80/20 | 9.12 MW | 9.12 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944761 | AF1-141 C O1 | 80/20 | 6.65 MW | 6.65 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944831 | AF1-148 C O1 | 80/20 | 6.82 MW | 6.82 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944931 | AF1-158 C O1 | 80/20 | 4.78 MW | 4.78 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 944961 | AF1-161 C | 80/20 | 1.36 MW | 1.36 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 945111 | AF1-176 C O1 | 80/20 | 9.22 MW | 9.22 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 945371 | AF1-202 C O1 | 80/20 | 2.07 MW | 2.07 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 945581 | AF1-223 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 958711 | AF2-162 C | 80/20 | 1.95 MW | 1.95 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 958821 | AF2-173 C | 80/20 | 4.28 MW | 4.28 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 958861 | AF2-177 C O1 | 80/20 | 1.65 MW | 1.65 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 959001 | AF2-191 C O1 | 80/20 | 3.48 MW | 3.48 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 959131 | AF2-204 C | 80/20 | 5.22 MW | 5.22 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 959181 | AF2-209 C | 80/20 | 6.55 MW | 6.55 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 959331 | AF2-224 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 960441 | AF2-335 C | 80/20 | 3.03 MW | 3.03 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 960681 | AF2-359 C | 80/20 | 3.77 MW | 3.77 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 960791 | AF2-370 | 80/20 | 1.01 MW | 1.01 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 960851 | AF2-376 C | 80/20 | 1.42 MW | 1.42 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 960861 | AF2-377 C | 80/20 | 1.67 MW | 1.67 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 960971 | AF2-388 C | 80/20 | 2.29 MW | 2.29 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 960981 | AF2-389 C | 80/20 | 1.7 MW | 1.7 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 961051 | AF2-396 O1 | 80/20 | 11.27 MW | 11.27 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 243071 | 05BERRINSP G | 80/20 | 0.05 MW | 0.05 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 243440 | 05CKG1 | 80/20 | 8.67 MW | 8.67 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 244412 | 05WTRV SLR C | 80/20 | 0.02 MW | 0.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 244415 | 05OLIV SLR C | 80/20 | 0.13 MW | 0.13 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 270100 | X2-052 CT1 | 80/20 | 2.0 MW | 2.0 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 270101 | X2-052 CT2 | 80/20 | 2.0 MW | 2.0 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 270102 | X2-052 ST | 80/20 | 2.17 MW | 2.17 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 270142 | AA2-116_CT1 | 80/20 | 3.55 MW | 3.55 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 270143 | AA2-116_CT2 | 80/20 | 3.55 MW | 3.55 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 270144 | AA2-116_ST | 80/20 | 3.14 MW | 3.14 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 933594 | AC2-176 C | 80/20 | 0.15 MW | 0.15 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 939395 | AE1-170 C | 80/20 | 3.48 MW | 3.48 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 939771 | AE1-208 C | 80/20 | 3.15 MW | 3.15 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 939781 | AE1-209 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 939791 | AE1-210 C O1 | 80/20 | 0.66 MW | 0.66 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 940981 | AE2-089 C O1 | 80/20 | 6.64 MW | 6.64 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 941691 | AE2-169 | 80/20 | 1.89 MW | 1.89 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 957741 | AF2-068 C O1 | 80/20 | 4.65 MW | 4.65 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 957891 | AF2-083 C O1 | 80/20 | 5.68 MW | 5.68 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 958001 | AF2-094 C | 80/20 | 2.09 MW | 2.09 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | 958311 | AF2-125 C | 80/20 | 3.76 MW | 3.76 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.05 MW | 0.05 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.57 MW | 0.57 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.02 MW | 2.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 37.86 MW | 37.86 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 21.27 MW | 21.27 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.27 MW | 3.27 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.0 MW | 1.0 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.76 MW | 5.76 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.75 MW | 0.75 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.26 MW | 0.26 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.08 MW | 2.08 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.37 MW | 1.37 MW |
| Details for AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 961631 | AG1-003 C | 80/20 | 23.08 MW | 23.08 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 961641 | AG1-004 | 80/20 | 20.43 MW | 20.43 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 962601 | AG1-109 | 80/20 | 2.12 MW | 2.12 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 963701 | AG1-222 C | 80/20 | 9.98 MW | 9.98 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 963731 | AG1-225 C | 80/20 | 22.21 MW | 22.21 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 963791 | AG1-232 C | 80/20 | 10.36 MW | 10.36 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965011 | AG1-365 C | 80/20 | 12.13 MW | 12.13 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965021 | AG1-366 C | 80/20 | 4.04 MW | 4.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965041 | AG1-368 C | 80/20 | 7.39 MW | 7.39 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965051 | AG1-369 C | 80/20 | 3.16 MW | 3.16 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965101 | AG1-375 C | 80/20 | 5.4 MW | 5.4 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965421 | AG1-410 C O1 | 80/20 | 89.62 MW | 89.62 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965431 | AG1-411 O1 | 80/20 | 49.79 MW | 49.79 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965491 | AG1-417 C O1 | 80/20 | 3.75 MW | 3.75 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965501 | AG1-418 C O1 | 80/20 | 3.75 MW | 3.75 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965561 | AG1-424 C | 80/20 | 6.26 MW | 6.26 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965651 | AG1-433 C | 80/20 | 1.62 MW | 1.62 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965681 | AG1-436 C | 80/20 | 6.08 MW | 6.08 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965791 | AG1-447 | 80/20 | 4.46 MW | 4.46 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965841 | AG1-453 C O1 | 80/20 | 9.63 MW | 9.63 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965851 | AG1-454 O1 | 80/20 | 5.73 MW | 5.73 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 246397 | 05ELKHART HY | 80/20 | 0.04 MW | 0.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 246416 | 05TWIN BRCH1 | 80/20 | 0.06 MW | 0.06 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 246422 | 05MAYFLWER | 80/20 | 0.08 MW | 0.08 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 246431 | 05BUCHANAN | 80/20 | 0.04 MW | 0.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 246536 | 05MOTTVILL | 80/20 | 0.02 MW | 0.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 246953 | 05TIMB G C | 80/20 | 0.36 MW | 0.36 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247270 | 05RPMNG1 | 80/20 | 10.74 MW | 10.74 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247271 | 05RPMNG2 | 80/20 | 10.73 MW | 10.73 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247272 | 05RPMNG3 | 80/20 | 10.74 MW | 10.74 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247292 | 05KEY G1 | 80/20 | 0.98 MW | 0.98 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247293 | 05KEY G2 | 80/20 | 0.98 MW | 0.98 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247294 | 05KEY G3 | 80/20 | 1.01 MW | 1.01 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247295 | 05KEY G4 | 80/20 | 1.01 MW | 1.01 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247521 | T131 | 80/20 | 0.54 MW | 0.54 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247604 | X1-042 | 80/20 | 0.04 MW | 0.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247620 | Y3-023 | 80/20 | 0.07 MW | 0.07 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247643 | Z2-116 C | 80/20 | 0.02 MW | 0.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 926865 | AC1-173 C | 80/20 | 0.18 MW | 0.18 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 936141 | AD2-020 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 936631 | AD2-079 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 938261 | AE1-039 | 80/20 | 0.01 MW | 0.01 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 942221 | AE2-234 C O1 | 80/20 | 2.42 MW | 2.42 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 942241 | AE2-236 C O1 | 80/20 | 4.57 MW | 4.57 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 943001 | AE2-323 C | 80/20 | 7.44 MW | 7.44 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 943021 | AE2-325 C | 80/20 | 2.66 MW | 2.66 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944161 | AF1-084 C | 80/20 | 4.52 MW | 4.52 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944231 | AF1-091 C O1 | 80/20 | 16.7 MW | 16.7 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944241 | AF1-092 C O1 | 80/20 | 12.66 MW | 12.66 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944531 | AF1-118 C O1 | 80/20 | 27.67 MW | 27.67 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944541 | AF1-119 C O1 | 80/20 | 12.9 MW | 12.9 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944761 | AF1-141 C O1 | 80/20 | 8.47 MW | 8.47 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944831 | AF1-148 C O1 | 80/20 | 9.6 MW | 9.6 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944931 | AF1-158 C O1 | 80/20 | 7.56 MW | 7.56 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944961 | AF1-161 C | 80/20 | 2.12 MW | 2.12 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 945111 | AF1-176 C O1 | 80/20 | 13.96 MW | 13.96 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 945371 | AF1-202 C O1 | 80/20 | 2.93 MW | 2.93 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 945581 | AF1-223 C O1 | 80/20 | 7.76 MW | 7.76 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958711 | AF2-162 C | 80/20 | 2.76 MW | 2.76 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958861 | AF2-177 C O1 | 80/20 | 2.34 MW | 2.34 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959001 | AF2-191 C O1 | 80/20 | 5.51 MW | 5.51 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959131 | AF2-204 C | 80/20 | 7.18 MW | 7.18 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959181 | AF2-209 C | 80/20 | 8.8 MW | 8.8 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959331 | AF2-224 C O1 | 80/20 | 8.49 MW | 8.49 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960681 | AF2-359 C | 80/20 | 6.08 MW | 6.08 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960851 | AF2-376 C | 80/20 | 1.85 MW | 1.85 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960861 | AF2-377 C | 80/20 | 2.11 MW | 2.11 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960971 | AF2-388 C | 80/20 | 3.24 MW | 3.24 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960981 | AF2-389 C | 80/20 | 2.62 MW | 2.62 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 961051 | AF2-396 O1 | 80/20 | 17.35 MW | 17.35 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 243071 | 05BERRINSP G | 80/20 | 0.09 MW | 0.09 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 243440 | 05CKG1 | 80/20 | 14.05 MW | 14.05 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 243441 | 05CKG2 | 80/20 | 16.27 MW | 16.27 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 244412 | 05WTRV SLR C | 80/20 | 0.03 MW | 0.03 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 244415 | 05OLIV SLR C | 80/20 | 0.21 MW | 0.21 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 270100 | X2-052 CT1 | 80/20 | 3.23 MW | 3.23 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 270101 | X2-052 CT2 | 80/20 | 3.23 MW | 3.23 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 270102 | X2-052 ST | 80/20 | 3.5 MW | 3.5 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 270142 | AA2-116_CT1 | 80/20 | 5.54 MW | 5.54 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 270143 | AA2-116_CT2 | 80/20 | 5.54 MW | 5.54 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 270144 | AA2-116_ST | 80/20 | 4.91 MW | 4.91 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274751 | CRETE EC ;1U | 80/20 | 1.0 MW | 1.0 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274753 | CRETE EC ;3U | 80/20 | 1.0 MW | 1.0 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274754 | CRETE EC ;4U | 80/20 | 1.0 MW | 1.0 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 933281 | AC2-140 C | 80/20 | 0.54 MW | 0.54 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 939395 | AE1-170 C | 80/20 | 5.42 MW | 5.42 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 939771 | AE1-208 C | 80/20 | 4.43 MW | 4.43 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 940981 | AE2-089 C O1 | 80/20 | 8.67 MW | 8.67 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 941691 | AE2-169 | 80/20 | 2.66 MW | 2.66 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 957891 | AF2-083 C O1 | 80/20 | 8.75 MW | 8.75 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958001 | AF2-094 C | 80/20 | 2.91 MW | 2.91 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958311 | AF2-125 C | 80/20 | 4.79 MW | 4.79 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958431 | AF2-137 C | 80/20 | 21.45 MW | 21.45 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.25 MW | 0.25 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.87 MW | 0.87 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.87 MW | 0.87 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 68.34 MW | 68.34 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 33.13 MW | 33.13 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.09 MW | 0.09 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.04 MW | 5.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.6 MW | 1.6 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.29 MW | 9.29 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.17 MW | 1.17 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.4 MW | 0.4 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.13 MW | 3.13 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.23 MW | 2.23 MW |
| Details for AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 961631 | AG1-003 C | 80/20 | 157.28 MW | 157.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 961641 | AG1-004 | 80/20 | 139.19 MW | 139.19 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 962601 | AG1-109 | 80/20 | 5.79 MW | 5.79 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 962691 | AG1-118 C O1 | Adder | 38.35 MW | 32.59 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 962701 | AG1-119 C | Adder | 37.92 MW | 32.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 962711 | AG1-120 C O1 | Adder | 15.01 MW | 12.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 962781 | AG1-127 C | Adder | 12.13 MW | 10.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 963701 | AG1-222 C | 80/20 | 21.47 MW | 21.47 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 964361 | AG1-298 O1 | Adder | 112.02 MW | 95.22 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 964401 | AG1-302 C O1 | Adder | 38.28 MW | 32.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 964861 | AG1-349 C O1 | Adder | 33.07 MW | 28.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965011 | AG1-365 C | 80/20 | 14.98 MW | 14.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965021 | AG1-366 C | 80/20 | 4.99 MW | 4.99 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965141 | AG1-379 C | Adder | 29.23 MW | 24.85 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965421 | AG1-410 C O1 | 80/20 | 44.89 MW | 44.89 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965431 | AG1-411 O1 | 80/20 | 24.94 MW | 24.94 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965491 | AG1-417 C O1 | 80/20 | 7.56 MW | 7.56 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965501 | AG1-418 C O1 | 80/20 | 7.56 MW | 7.56 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965551 | AG1-423 C O1 | Adder | 25.28 MW | 21.49 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965651 | AG1-433 C | Adder | 3.71 MW | 3.15 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965681 | AG1-436 C | 80/20 | 17.54 MW | 17.54 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965791 | AG1-447 | 80/20 | 12.86 MW | 12.86 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965841 | AG1-453 C O1 | 80/20 | 20.05 MW | 20.05 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 965851 | AG1-454 O1 | 80/20 | 11.93 MW | 11.93 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 966091 | AG1-478 C | Adder | 3.48 MW | 2.95 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 966431 | AG1-512 C | Adder | 3.56 MW | 3.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 966441 | AG1-513 C | Adder | 0.87 MW | 0.74 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 966651 | AG1-535 O1 | Adder | 19.1 MW | 16.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 246397 | 05ELKHART HY | 80/20 | 0.1 MW | 0.1 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 246416 | 05TWIN BRCH1 | 80/20 | 0.16 MW | 0.16 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 246422 | 05MAYFLWER | 80/20 | 0.23 MW | 0.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 246431 | 05BUCHANAN | 80/20 | 0.11 MW | 0.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 246536 | 05MOTTVILL | 80/20 | 0.06 MW | 0.06 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 247270 | 05RPMNG1 | 80/20 | 6.37 MW | 6.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 247271 | 05RPMNG2 | 80/20 | 6.36 MW | 6.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 247272 | 05RPMNG3 | 80/20 | 6.37 MW | 6.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 247295 | 05KEY G4 | 80/20 | 2.3 MW | 2.3 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 247604 | X1-042 | 80/20 | 0.12 MW | 0.12 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 247620 | Y3-023 | 80/20 | 0.18 MW | 0.18 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 247643 | Z2-116 C | 80/20 | 0.05 MW | 0.05 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 272364 | ESS H440N ;R | Adder | 4.61 MW | 3.92 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 926331 | AC1-110 1 | Adder | 3.25 MW | 2.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 926341 | AC1-110 2 | Adder | 3.25 MW | 2.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 927451 | AC1-142A 1 | Adder | 7.01 MW | 5.96 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 927461 | AC1-142A 2 | Adder | 7.01 MW | 5.96 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 933911 | AD1-013 C | Adder | 3.23 MW | 2.74 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 933931 | AD1-016 C | Adder | 1.6 MW | 1.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 934721 | AD1-100 C | Adder | 32.98 MW | 28.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 934971 | AD1-129 C | Adder | 1.57 MW | 1.33 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 936141 | AD2-020 C O1 | 80/20 | 14.34 MW | 14.34 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 936291 | AD2-038 C O1 | Adder | 5.65 MW | 4.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 936371 | AD2-047 C O1 | Adder | 7.52 MW | 6.39 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 936461 | AD2-060 | Adder | 4.42 MW | 3.76 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 936511 | AD2-066 C O1 | Adder | 14.73 MW | 12.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 936631 | AD2-079 C O1 | 80/20 | 2.85 MW | 2.85 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 937001 | AD2-134 C | Adder | 4.44 MW | 3.77 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 937401 | AD2-194 1 | Adder | 13.07 MW | 11.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 937411 | AD2-194 2 | Adder | 13.07 MW | 11.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 938261 | AE1-039 | 80/20 | 0.03 MW | 0.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 942241 | AE2-236 C O1 | 80/20 | 9.71 MW | 9.71 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 942421 | AE2-255 C O1 | Adder | 5.33 MW | 4.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 942651 | AE2-281 C O1 | Adder | 1.5 MW | 1.27 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 942991 | AE2-321 C | Adder | 14.14 MW | 12.02 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 943001 | AE2-323 C | 80/20 | 16.01 MW | 16.01 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 943021 | AE2-325 C | 80/20 | 7.26 MW | 7.26 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 943121 | AE2-341 C | Adder | 21.88 MW | 18.6 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 943591 | AF1-030 C O1 | Adder | 14.55 MW | 12.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 943801 | AF1-048 C | Adder | 6.61 MW | 5.62 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944161 | AF1-084 C | 80/20 | 12.45 MW | 12.45 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944231 | AF1-091 C O1 | Adder | 30.43 MW | 25.86 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944241 | AF1-092 C O1 | 80/20 | 27.82 MW | 27.82 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944531 | AF1-118 C O1 | 80/20 | 62.47 MW | 62.47 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944541 | AF1-119 C O1 | Adder | 29.5 MW | 25.08 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944761 | AF1-141 C O1 | 80/20 | 14.84 MW | 14.84 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944831 | AF1-148 C O1 | 80/20 | 21.73 MW | 21.73 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944931 | AF1-158 C O1 | 80/20 | 21.13 MW | 21.13 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 944961 | AF1-161 C | 80/20 | 5.79 MW | 5.79 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 945111 | AF1-176 C O1 | 80/20 | 36.37 MW | 36.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 945501 | AF1-215 C O1 | Adder | 39.1 MW | 33.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958481 | AF2-142 C | Adder | 19.43 MW | 16.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958491 | AF2-143 C | Adder | 19.26 MW | 16.38 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958711 | AF2-162 C | Adder | 6.32 MW | 5.37 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 959001 | AF2-191 C O1 | 80/20 | 15.45 MW | 15.45 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 959131 | AF2-204 C | Adder | 15.44 MW | 13.12 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 959331 | AF2-224 C O1 | 80/20 | 10.49 MW | 10.49 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 959351 | AF2-226 C | Adder | 4.32 MW | 3.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960281 | AF2-319 C | Adder | 4.32 MW | 3.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960381 | AF2-329 | Adder | 9.18 MW | 7.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960581 | AF2-349 C | Adder | 37.78 MW | 32.11 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960591 | AF2-350 C O1 | Adder | 13.27 MW | 11.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960601 | AF2-351 C O1 | Adder | 1.77 MW | 1.5 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960681 | AF2-359 C | 80/20 | 17.54 MW | 17.54 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960721 | AF2-363 C O1 | Adder | 10.3 MW | 8.75 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960751 | AF2-366 C | Adder | 12.1 MW | 10.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960971 | AF2-388 C | Adder | 7.42 MW | 6.3 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 960981 | AF2-389 C | 80/20 | 7.03 MW | 7.03 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 961051 | AF2-396 O1 | 80/20 | 46.48 MW | 46.48 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 961501 | AF2-441 C O1 | Adder | 17.91 MW | 15.22 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 243071 | 05BERRINSP G | 80/20 | 0.24 MW | 0.24 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 243440 | 05CKG1 | 80/20 | 40.77 MW | 40.77 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 243441 | 05CKG2 | 80/20 | 50.67 MW | 50.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 244412 | 05WTRV SLR C | 80/20 | 0.09 MW | 0.09 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 244415 | 05OLIV SLR C | 80/20 | 0.59 MW | 0.59 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 270100 | X2-052 CT1 | 80/20 | 9.31 MW | 9.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 270101 | X2-052 CT2 | 80/20 | 9.31 MW | 9.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 270102 | X2-052 ST | 80/20 | 10.07 MW | 10.07 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 270142 | AA2-116_CT1 | 80/20 | 15.2 MW | 15.2 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 270143 | AA2-116_CT2 | 80/20 | 15.2 MW | 15.2 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 270144 | AA2-116_ST | 80/20 | 13.46 MW | 13.46 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274770 | LINCOLN ;1U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274771 | LINCOLN ;2U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274772 | LINCOLN ;3U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274773 | LINCOLN ;4U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274774 | LINCOLN ;5U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274775 | LINCOLN ;6U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274776 | LINCOLN ;7U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274777 | LINCOLN ;8U | 80/20 | 2.98 MW | 2.98 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274788 | SE CHICAG;5U | Adder | 8.52 MW | 7.24 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274789 | SE CHICAG;6U | Adder | 8.54 MW | 7.26 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274790 | SE CHICAG;7U | Adder | 8.65 MW | 7.35 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274791 | SE CHICAG;8U | Adder | 8.65 MW | 7.35 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274792 | SE CHICAG;9U | Adder | 8.66 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274793 | SE CHICAG;0U | Adder | 8.66 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274794 | SE CHICAG;1U | Adder | 8.66 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 274795 | SE CHICAG;2U | Adder | 8.66 MW | 7.36 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 915011 | Y3-013 1 | Adder | 6.4 MW | 5.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 915021 | Y3-013 2 | Adder | 6.4 MW | 5.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 915031 | Y3-013 3 | Adder | 6.4 MW | 5.44 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 930482 | AB1-089 CT | Adder | 7.85 MW | 6.67 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 930761 | AB1-122 CT1 | Adder | 121.35 MW | 103.15 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 930771 | AB1-122 CT2 | Adder | 124.9 MW | 106.17 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 933281 | AC2-140 C | 80/20 | 1.68 MW | 1.68 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 933411 | AC2-154 C | Adder | 4.2 MW | 3.57 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 938511 | AE1-070 1 | Adder | 15.36 MW | 13.06 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 938521 | AE1-070 2 | Adder | 14.05 MW | 11.95 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 938851 | AE1-113 C O1 | Adder | 14.06 MW | 11.95 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 939321 | AE1-163 C O1 | Adder | 10.49 MW | 8.91 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 939351 | AE1-166 C O1 | Adder | 17.19 MW | 14.61 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 939395 | AE1-170 C | 80/20 | 14.78 MW | 14.78 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 939401 | AE1-172 C O1 | Adder | 9.46 MW | 8.04 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 941131 | AE2-107 C | Adder | 11.42 MW | 9.71 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 941551 | AE2-152 C O1 | Adder | 19.84 MW | 16.86 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 946661 | AF1-330 C | Adder | 3.46 MW | 2.94 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 946671 | AF1-331 | Adder | 4.19 MW | 3.56 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 957331 | AF2-027 C | Adder | 4.26 MW | 3.62 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 957371 | AF2-031 C O1 | Adder | 1.8 MW | 1.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 957401 | AF2-034 C | Adder | 2.35 MW | 2.0 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 957891 | AF2-083 C O1 | 80/20 | 23.41 MW | 23.41 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958001 | AF2-094 C | 80/20 | 6.39 MW | 6.39 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958011 | AF2-095 C O1 | Adder | 30.08 MW | 25.57 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958021 | AF2-096 C | Adder | 56.38 MW | 47.92 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958311 | AF2-125 C | 80/20 | 8.39 MW | 8.39 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958381 | AF2-132 C O1 | Adder | 38.28 MW | 32.53 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958391 | AF2-133 C O1 | Adder | 37.85 MW | 32.17 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958401 | AF2-134 C O1 | Adder | 13.03 MW | 11.08 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 958431 | AF2-137 C | 80/20 | 146.15 MW | 146.15 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 934101 | AD2-000 1 | Adder | 9.81 MW | 8.34 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 934111 | AD2-000 2 | Adder | 10.1 MW | 8.59 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | 945351 | AF1-200 FTIR | Adder | 533.31 MW | 453.31 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.43 MW | 1.43 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.28 MW | 0.28 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.29 MW | 2.29 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 227.74 MW | 227.74 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 90.46 MW | 90.46 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.8 MW | 0.8 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.52 MW | 13.52 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 4.5 MW | 4.5 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 26.78 MW | 26.78 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.23 MW | 3.23 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 1.09 MW | 1.09 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.09 MW | 8.09 MW |
| AF2-137 TAP-05MARYSV 765.0 kV Ckt 1 line l/o AEP_P1-2_#6457_16758-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 6.52 MW | 6.52 MW |
| Details for AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961631 | AG1-003 C | 50/50 | 22.86 MW | 22.86 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961632 | AG1-003 E | 50/50 | 17.6 MW | 17.6 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961641 | AG1-004 | 50/50 | 20.23 MW | 20.23 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963701 | AG1-222 C | 50/50 | 9.86 MW | 9.86 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963702 | AG1-222 E | 50/50 | 6.57 MW | 6.57 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963731 | AG1-225 C | 50/50 | 21.89 MW | 21.89 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963732 | AG1-225 E | 50/50 | 14.7 MW | 14.7 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963791 | AG1-232 C | 50/50 | 10.22 MW | 10.22 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963792 | AG1-232 E | 50/50 | 6.82 MW | 6.82 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965011 | AG1-365 C | 50/50 | 12.02 MW | 12.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965012 | AG1-365 E | 50/50 | 8.02 MW | 8.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965021 | AG1-366 C | 50/50 | 4.01 MW | 4.01 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965022 | AG1-366 E | 50/50 | 6.01 MW | 6.01 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965041 | AG1-368 C | 50/50 | 7.26 MW | 7.26 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965042 | AG1-368 E | 50/50 | 4.84 MW | 4.84 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965051 | AG1-369 C | 50/50 | 3.09 MW | 3.09 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965052 | AG1-369 E | 50/50 | 2.06 MW | 2.06 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965421 | AG1-410 C O1 | 50/50 | 89.04 MW | 89.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965422 | AG1-410 E O1 | 50/50 | 59.36 MW | 59.36 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965431 | AG1-411 O1 | 50/50 | 49.46 MW | 49.46 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965491 | AG1-417 C O1 | 50/50 | 3.71 MW | 3.71 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965492 | AG1-417 E O1 | 50/50 | 2.47 MW | 2.47 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965501 | AG1-418 C O1 | 50/50 | 3.71 MW | 3.71 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965502 | AG1-418 E O1 | 50/50 | 2.47 MW | 2.47 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965561 | AG1-424 C | 50/50 | 6.15 MW | 6.15 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965562 | AG1-424 E | 50/50 | 4.1 MW | 4.1 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965841 | AG1-453 C O1 | 50/50 | 9.52 MW | 9.52 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965842 | AG1-453 E O1 | 50/50 | 6.35 MW | 6.35 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965851 | AG1-454 O1 | 50/50 | 5.67 MW | 5.67 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247270 | 05RPMNG1 | 50/50 | 10.67 MW | 10.67 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247271 | 05RPMNG2 | 50/50 | 10.66 MW | 10.66 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247272 | 05RPMNG3 | 50/50 | 10.67 MW | 10.67 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247521 | T131 | 50/50 | 0.53 MW | 0.53 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926865 | AC1-173 C | 50/50 | 0.17 MW | 0.17 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926866 | AC1-173 E | 50/50 | 6.81 MW | 6.81 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942221 | AE2-234 C O1 | Adder | 2.39 MW | 2.03 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942222 | AE2-234 E O1 | Adder | 1.08 MW | 0.92 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942241 | AE2-236 C O1 | 50/50 | 4.52 MW | 4.52 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942242 | AE2-236 E O1 | 50/50 | 1.94 MW | 1.94 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 943001 | AE2-323 C | 50/50 | 7.35 MW | 7.35 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 943002 | AE2-323 E | 50/50 | 3.6 MW | 3.6 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944231 | AF1-091 C O1 | 50/50 | 16.46 MW | 16.46 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944232 | AF1-091 E O1 | 50/50 | 4.95 MW | 4.95 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944241 | AF1-092 C O1 | 50/50 | 12.53 MW | 12.53 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944242 | AF1-092 E O1 | 50/50 | 3.81 MW | 3.81 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944531 | AF1-118 C O1 | 50/50 | 27.36 MW | 27.36 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944532 | AF1-118 E O1 | 50/50 | 8.25 MW | 8.25 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944761 | AF1-141 C O1 | 50/50 | 8.37 MW | 8.37 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944762 | AF1-141 E O1 | 50/50 | 4.42 MW | 4.42 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944831 | AF1-148 C O1 | Adder | 9.5 MW | 8.07 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944832 | AF1-148 E O1 | Adder | 6.33 MW | 5.38 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959131 | AF2-204 C | Adder | 7.1 MW | 6.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959132 | AF2-204 E | Adder | 3.75 MW | 3.19 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959331 | AF2-224 C O1 | 50/50 | 8.42 MW | 8.42 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959332 | AF2-224 E O1 | 50/50 | 11.62 MW | 11.62 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960861 | AF2-377 C | 50/50 | 2.06 MW | 2.06 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960862 | AF2-377 E | 50/50 | 3.09 MW | 3.09 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 270164 | T-131 E | 50/50 | 12.37 MW | 12.37 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958001 | AF2-094 C | 50/50 | 2.88 MW | 2.88 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958002 | AF2-094 E | 50/50 | 1.48 MW | 1.48 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958311 | AF2-125 C | 50/50 | 4.73 MW | 4.73 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958312 | AF2-125 E | 50/50 | 2.46 MW | 2.46 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958431 | AF2-137 C | 50/50 | 21.24 MW | 21.24 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958432 | AF2-137 E | 50/50 | 29.33 MW | 29.33 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946203 | AF1-285 BAT | 50/50 | 2.6 MW | 2.6 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936722 | AD2-091 BAT | 50/50 | 7.02 MW | 7.02 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942042 | AE2-216 BAT | 50/50 | 7.72 MW | 7.72 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.13 MW | 0.13 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.9 MW | 0.9 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.66 MW | 2.66 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 67.17 MW | 67.17 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 33.51 MW | 33.51 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.14 MW | 2.14 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.17 MW | 5.17 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.6 MW | 1.6 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 9.26 MW | 9.26 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.19 MW | 1.19 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 13.76 MW | 13.76 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.4 MW | 0.4 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.28 MW | 3.28 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.21 MW | 2.21 MW |
| Details for 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 963721 | AG1-224 C O1 | Adder | 10.08 MW | 8.57 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 963722 | AG1-224 E O1 | Adder | 6.72 MW | 5.71 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 964611 | AG1-324 C O1 | Adder | 1.92 MW | 1.63 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 964612 | AG1-324 E O1 | Adder | 0.76 MW | 0.65 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965031 | AG1-367 C | 50/50 | 9.69 MW | 9.69 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965032 | AG1-367 E | 50/50 | 6.46 MW | 6.46 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965101 | AG1-375 C | 50/50 | 13.39 MW | 13.39 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965102 | AG1-375 E | 50/50 | 8.93 MW | 8.93 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965461 | AG1-414 C O1 | Adder | 4.14 MW | 3.52 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965462 | AG1-414 E O1 | Adder | 2.76 MW | 2.35 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965491 | AG1-417 C O1 | Adder | 2.87 MW | 2.44 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965492 | AG1-417 E O1 | Adder | 1.91 MW | 1.63 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965501 | AG1-418 C O1 | Adder | 2.87 MW | 2.44 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965502 | AG1-418 E O1 | Adder | 1.91 MW | 1.63 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965651 | AG1-433 C | 50/50 | 4.07 MW | 4.07 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965652 | AG1-433 E | 50/50 | 19.05 MW | 19.05 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247292 | 05KEY G1 | 50/50 | 2.54 MW | 2.54 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247293 | 05KEY G2 | 50/50 | 2.56 MW | 2.56 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247294 | 05KEY G3 | 50/50 | 2.63 MW | 2.63 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247295 | 05KEY G4 | 50/50 | 2.63 MW | 2.63 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247543 | V3-007 C | 50/50 | 0.64 MW | 0.64 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247935 | V3-007 E | 50/50 | 24.97 MW | 24.97 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247958 | 05WLD G2 E | Adder | 16.96 MW | 14.42 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247963 | 05HDWTR1G E | 50/50 | 24.97 MW | 24.97 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 247968 | Z2-115 E | Adder | 0.1 MW | 0.09 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 926881 | AC1-175 C | 50/50 | 10.9 MW | 10.9 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 926882 | AC1-175 E | 50/50 | 17.79 MW | 17.79 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 934161 | AD1-043 C O1 | Adder | 4.46 MW | 3.79 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 934162 | AD1-043 E O1 | Adder | 7.28 MW | 6.19 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 934741 | AD1-101 C O1 | Adder | -2.09 MW | -1.78 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 934901 | AD1-119 C O1 | Adder | -2.86 MW | -2.43 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 934961 | AD1-128 C | 50/50 | 6.47 MW | 6.47 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 934962 | AD1-128 E | 50/50 | 10.56 MW | 10.56 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 936561 | AD2-071 C | Adder | 6.31 MW | 5.37 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 936562 | AD2-071 E | Adder | 3.11 MW | 2.64 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 942081 | AE2-220 C | 50/50 | 7.53 MW | 7.53 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 942082 | AE2-220 E | 50/50 | 10.4 MW | 10.4 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 942241 | AE2-236 C O1 | 50/50 | 4.8 MW | 4.8 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 942242 | AE2-236 E O1 | 50/50 | 2.06 MW | 2.06 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 942791 | AE2-297 C O1 | Adder | 8.54 MW | 7.26 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 942792 | AE2-297 E O1 | Adder | 5.69 MW | 4.84 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 944241 | AF1-092 C O1 | 50/50 | 18.5 MW | 18.5 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 944242 | AF1-092 E O1 | 50/50 | 5.63 MW | 5.63 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 944531 | AF1-118 C O1 | 50/50 | 72.76 MW | 72.76 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 944532 | AF1-118 E O1 | 50/50 | 21.94 MW | 21.94 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 944541 | AF1-119 C O1 | 50/50 | 32.37 MW | 32.37 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 944542 | AF1-119 E O1 | 50/50 | 13.87 MW | 13.87 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 944831 | AF1-148 C O1 | 50/50 | 25.03 MW | 25.03 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 944832 | AF1-148 E O1 | 50/50 | 16.68 MW | 16.68 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 945371 | AF1-202 C O1 | 50/50 | 7.13 MW | 7.13 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 945372 | AF1-202 E O1 | 50/50 | 34.8 MW | 34.8 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 945581 | AF1-223 C O1 | 50/50 | 18.87 MW | 18.87 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 945582 | AF1-223 E O1 | 50/50 | 12.58 MW | 12.58 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 958711 | AF2-162 C | 50/50 | 6.94 MW | 6.94 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 958712 | AF2-162 E | 50/50 | 3.47 MW | 3.47 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 958821 | AF2-173 C | 50/50 | 13.56 MW | 13.56 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 958822 | AF2-173 E | 50/50 | 18.73 MW | 18.73 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 958861 | AF2-177 C O1 | 50/50 | 5.8 MW | 5.8 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 958862 | AF2-177 E O1 | 50/50 | 38.84 MW | 38.84 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 959131 | AF2-204 C | 50/50 | 11.13 MW | 11.13 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 959132 | AF2-204 E | 50/50 | 5.87 MW | 5.87 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 960441 | AF2-335 C | 50/50 | 7.68 MW | 7.68 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 960442 | AF2-335 E | 50/50 | 5.12 MW | 5.12 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 960791 | AF2-370 | 50/50 | 2.56 MW | 2.56 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 960971 | AF2-388 C | 50/50 | 8.14 MW | 8.14 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 960972 | AF2-388 E | 50/50 | 38.1 MW | 38.1 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 961161 | AF2-407 | 50/50 | 31.54 MW | 31.54 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 961171 | AF2-408 | 50/50 | 8.11 MW | 8.11 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 243795 | 05HDWTR1G C | 50/50 | 0.64 MW | 0.64 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 932681 | AC2-090 C | 50/50 | 5.45 MW | 5.45 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 932682 | AC2-090 E | 50/50 | 8.9 MW | 8.9 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 939761 | AE1-207 C | 50/50 | 6.83 MW | 6.83 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 939762 | AE1-207 E | 50/50 | 9.43 MW | 9.43 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 939771 | AE1-208 C | 50/50 | 7.4 MW | 7.4 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 939772 | AE1-208 E | 50/50 | 10.09 MW | 10.09 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 939781 | AE1-209 C O1 | 50/50 | 2.1 MW | 2.1 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 939782 | AE1-209 E O1 | 50/50 | 14.05 MW | 14.05 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 939791 | AE1-210 C O1 | 50/50 | 2.1 MW | 2.1 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 939792 | AE1-210 E O1 | 50/50 | 14.05 MW | 14.05 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 941691 | AE2-169 | 50/50 | 4.44 MW | 4.44 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 941721 | AE2-172 | 50/50 | 4.06 MW | 4.06 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 946031 | AF1-268 C O1 | 50/50 | 6.72 MW | 6.72 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 946032 | AF1-268 E O1 | 50/50 | 3.05 MW | 3.05 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 958001 | AF2-094 C | 50/50 | 4.25 MW | 4.25 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 958002 | AF2-094 E | 50/50 | 2.19 MW | 2.19 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965432 | AG1-411 BAT | 50/50 | 17.16 MW | 17.16 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 963703 | AG1-222 BAT | Adder | 15.04 MW | 12.78 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965852 | AG1-454 BAT | Adder | 5.76 MW | 4.89 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 965023 | AG1-366 BAT | 50/50 | 13.0 MW | 13.0 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 960853 | AF2-376 BAT | 50/50 | 8.0 MW | 8.0 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | 960863 | AF2-377 BAT | 50/50 | 8.07 MW | 8.07 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.29 MW | 0.29 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.72 MW | 0.72 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 8.53 MW | 8.53 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 18.67 MW | 18.67 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.43 MW | 0.43 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.38 MW | 0.38 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.66 MW | 2.66 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.97 MW | 1.97 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.84 MW | 1.84 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.25 MW | 0.25 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 2.45 MW | 2.45 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.37 MW | 0.37 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.26 MW | 2.26 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#9391_05SORENS 345_F | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.23 MW | 0.23 MW |
| Details for AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 961631 | AG1-003 C | Adder | 22.22 MW | 18.89 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 961632 | AG1-003 E | Adder | 17.11 MW | 14.54 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 961641 | AG1-004 | Adder | 19.66 MW | 16.71 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 963701 | AG1-222 C | 50/50 | 9.59 MW | 9.59 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 963702 | AG1-222 E | 50/50 | 6.39 MW | 6.39 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 963731 | AG1-225 C | 50/50 | 21.23 MW | 21.23 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 963732 | AG1-225 E | 50/50 | 14.26 MW | 14.26 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 963791 | AG1-232 C | 50/50 | 9.96 MW | 9.96 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 963792 | AG1-232 E | 50/50 | 6.64 MW | 6.64 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965011 | AG1-365 C | 50/50 | 11.81 MW | 11.81 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965012 | AG1-365 E | 50/50 | 7.87 MW | 7.87 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965021 | AG1-366 C | 50/50 | 3.94 MW | 3.94 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965022 | AG1-366 E | 50/50 | 5.91 MW | 5.91 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965041 | AG1-368 C | 50/50 | 7.03 MW | 7.03 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965042 | AG1-368 E | 50/50 | 4.69 MW | 4.69 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965051 | AG1-369 C | Adder | 2.97 MW | 2.52 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965052 | AG1-369 E | Adder | 1.98 MW | 1.68 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965421 | AG1-410 C O1 | 50/50 | 88.16 MW | 88.16 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965422 | AG1-410 E O1 | 50/50 | 58.77 MW | 58.77 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965431 | AG1-411 O1 | 50/50 | 48.98 MW | 48.98 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965491 | AG1-417 C O1 | 50/50 | 3.62 MW | 3.62 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965492 | AG1-417 E O1 | 50/50 | 2.41 MW | 2.41 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965501 | AG1-418 C O1 | 50/50 | 3.62 MW | 3.62 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965502 | AG1-418 E O1 | 50/50 | 2.41 MW | 2.41 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965561 | AG1-424 C | Adder | 5.95 MW | 5.06 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965562 | AG1-424 E | Adder | 3.97 MW | 3.37 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965841 | AG1-453 C O1 | 50/50 | 9.27 MW | 9.27 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965842 | AG1-453 E O1 | 50/50 | 6.18 MW | 6.18 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965851 | AG1-454 O1 | 50/50 | 5.51 MW | 5.51 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247270 | 05RPMNG1 | 50/50 | 10.55 MW | 10.55 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247271 | 05RPMNG2 | 50/50 | 10.54 MW | 10.54 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247272 | 05RPMNG3 | 50/50 | 10.55 MW | 10.55 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 926866 | AC1-173 E | Adder | 6.54 MW | 5.56 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942221 | AE2-234 C O1 | Adder | 2.32 MW | 1.97 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942222 | AE2-234 E O1 | Adder | 1.05 MW | 0.89 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942241 | AE2-236 C O1 | 50/50 | 4.4 MW | 4.4 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942242 | AE2-236 E O1 | 50/50 | 1.89 MW | 1.89 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 943001 | AE2-323 C | 50/50 | 7.15 MW | 7.15 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 943002 | AE2-323 E | 50/50 | 3.5 MW | 3.5 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944231 | AF1-091 C O1 | 50/50 | 16.0 MW | 16.0 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944232 | AF1-091 E O1 | 50/50 | 4.81 MW | 4.81 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944241 | AF1-092 C O1 | 50/50 | 12.19 MW | 12.19 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944242 | AF1-092 E O1 | 50/50 | 3.71 MW | 3.71 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944531 | AF1-118 C O1 | Adder | 26.58 MW | 22.6 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944532 | AF1-118 E O1 | Adder | 8.02 MW | 6.82 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944761 | AF1-141 C O1 | 50/50 | 8.16 MW | 8.16 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944762 | AF1-141 E O1 | 50/50 | 4.32 MW | 4.32 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944831 | AF1-148 C O1 | Adder | 9.22 MW | 7.84 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944832 | AF1-148 E O1 | Adder | 6.15 MW | 5.22 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 959131 | AF2-204 C | Adder | 6.89 MW | 5.86 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 959132 | AF2-204 E | Adder | 3.64 MW | 3.09 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 959331 | AF2-224 C O1 | 50/50 | 8.27 MW | 8.27 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 959332 | AF2-224 E O1 | 50/50 | 11.42 MW | 11.42 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960861 | AF2-377 C | Adder | 1.98 MW | 1.68 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960862 | AF2-377 E | Adder | 2.97 MW | 2.53 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 270164 | T-131 E | Adder | 11.89 MW | 10.11 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958001 | AF2-094 C | 50/50 | 2.8 MW | 2.8 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958002 | AF2-094 E | 50/50 | 1.44 MW | 1.44 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958311 | AF2-125 C | 50/50 | 4.62 MW | 4.62 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958312 | AF2-125 E | 50/50 | 2.4 MW | 2.4 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958431 | AF2-137 C | Adder | 20.64 MW | 17.55 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958432 | AF2-137 E | Adder | 28.51 MW | 24.23 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 946203 | AF1-285 BAT | 50/50 | 2.8 MW | 2.8 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 936722 | AD2-091 BAT | 50/50 | 7.48 MW | 7.48 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942042 | AE2-216 BAT | 50/50 | 8.23 MW | 8.23 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.19 MW | 0.19 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.83 MW | 0.83 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.46 MW | 1.46 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 63.65 MW | 63.65 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 31.59 MW | 31.59 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 2.0 MW | 2.0 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.04 MW | 0.04 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.83 MW | 4.83 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.46 MW | 1.46 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.88 MW | 8.88 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 1.11 MW | 1.11 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 12.87 MW | 12.87 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.38 MW | 0.38 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.01 MW | 3.01 MW |
| AG1-410 TAP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.13 MW | 2.13 MW |
| Details for 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 238979 | 02NAPMUN | Adder | -2.03 MW | -1.72 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961631 | AG1-003 C | 50/50 | 27.75 MW | 27.75 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961632 | AG1-003 E | 50/50 | 21.36 MW | 21.36 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961641 | AG1-004 | 50/50 | 24.56 MW | 24.56 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965031 | AG1-367 C | Adder | 5.91 MW | 5.02 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965032 | AG1-367 E | Adder | 3.94 MW | 3.35 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965101 | AG1-375 C | 50/50 | 8.15 MW | 8.15 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965102 | AG1-375 E | 50/50 | 5.43 MW | 5.43 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965461 | AG1-414 C O1 | Adder | 2.67 MW | 2.27 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965462 | AG1-414 E O1 | Adder | 1.78 MW | 1.51 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965651 | AG1-433 C | 50/50 | 2.48 MW | 2.48 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965652 | AG1-433 E | 50/50 | 11.59 MW | 11.59 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247292 | 05KEY G1 | 50/50 | 1.55 MW | 1.55 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247293 | 05KEY G2 | 50/50 | 1.55 MW | 1.55 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247294 | 05KEY G3 | 50/50 | 1.6 MW | 1.6 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247295 | 05KEY G4 | 50/50 | 1.6 MW | 1.6 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247935 | V3-007 E | Adder | 15.23 MW | 12.94 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247958 | 05WLD G2 E | Adder | 10.66 MW | 9.06 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247963 | 05HDWTR1G E | Adder | 15.23 MW | 12.94 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247968 | Z2-115 E | Adder | 0.07 MW | 0.06 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926881 | AC1-175 C | Adder | 6.65 MW | 5.65 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926882 | AC1-175 E | Adder | 10.85 MW | 9.22 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934161 | AD1-043 C O1 | Adder | 2.8 MW | 2.38 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934162 | AD1-043 E O1 | Adder | 4.57 MW | 3.89 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934741 | AD1-101 C O1 | Adder | -1.93 MW | -1.64 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934901 | AD1-119 C O1 | Adder | -2.72 MW | -2.31 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934961 | AD1-128 C | Adder | 3.87 MW | 3.29 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934962 | AD1-128 E | Adder | 6.31 MW | 5.37 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936561 | AD2-071 C | Adder | 4.01 MW | 3.41 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936562 | AD2-071 E | Adder | 1.97 MW | 1.68 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942081 | AE2-220 C | Adder | 4.6 MW | 3.91 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942082 | AE2-220 E | Adder | 6.34 MW | 5.39 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942241 | AE2-236 C O1 | Adder | 2.18 MW | 1.85 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942242 | AE2-236 E O1 | Adder | 0.93 MW | 0.79 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942661 | AE2-282 C | Adder | -2.58 MW | -2.19 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942791 | AE2-297 C O1 | Adder | 5.28 MW | 4.49 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942792 | AE2-297 E O1 | Adder | 3.52 MW | 2.99 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944241 | AF1-092 C O1 | Adder | 10.34 MW | 8.79 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944242 | AF1-092 E O1 | Adder | 3.15 MW | 2.68 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944531 | AF1-118 C O1 | 50/50 | 44.24 MW | 44.24 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944532 | AF1-118 E O1 | 50/50 | 13.34 MW | 13.34 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944541 | AF1-119 C O1 | 50/50 | 19.7 MW | 19.7 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944542 | AF1-119 E O1 | 50/50 | 8.44 MW | 8.44 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944551 | AF1-120 C | Adder | -1.56 MW | -1.33 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944831 | AF1-148 C O1 | 50/50 | 15.22 MW | 15.22 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944832 | AF1-148 E O1 | 50/50 | 10.15 MW | 10.15 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945371 | AF1-202 C O1 | 50/50 | 4.34 MW | 4.34 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945372 | AF1-202 E O1 | 50/50 | 21.19 MW | 21.19 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945581 | AF1-223 C O1 | 50/50 | 11.49 MW | 11.49 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945582 | AF1-223 E O1 | 50/50 | 7.66 MW | 7.66 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958711 | AF2-162 C | 50/50 | 4.22 MW | 4.22 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958712 | AF2-162 E | 50/50 | 2.11 MW | 2.11 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958821 | AF2-173 C | Adder | 8.27 MW | 7.03 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958822 | AF2-173 E | Adder | 11.42 MW | 9.71 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958861 | AF2-177 C O1 | 50/50 | 3.53 MW | 3.53 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958862 | AF2-177 E O1 | 50/50 | 23.64 MW | 23.64 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959131 | AF2-204 C | Adder | 6.12 MW | 5.21 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959132 | AF2-204 E | Adder | 3.23 MW | 2.75 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960441 | AF2-335 C | Adder | 4.59 MW | 3.9 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960442 | AF2-335 E | Adder | 3.06 MW | 2.6 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960791 | AF2-370 | Adder | 1.53 MW | 1.3 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960971 | AF2-388 C | 50/50 | 4.95 MW | 4.95 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960972 | AF2-388 E | 50/50 | 23.18 MW | 23.18 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961161 | AF2-407 | Adder | 19.87 MW | 16.89 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961171 | AF2-408 | Adder | 5.08 MW | 4.32 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 932681 | AC2-090 C | Adder | 3.33 MW | 2.83 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 932682 | AC2-090 E | Adder | 5.43 MW | 4.61 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939761 | AE1-207 C | Adder | 4.31 MW | 3.66 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939762 | AE1-207 E | Adder | 5.95 MW | 5.06 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939771 | AE1-208 C | Adder | 4.3 MW | 3.66 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939772 | AE1-208 E | Adder | 5.86 MW | 4.99 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939781 | AE1-209 C O1 | Adder | 1.28 MW | 1.09 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939782 | AE1-209 E O1 | Adder | 8.56 MW | 7.28 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939791 | AE1-210 C O1 | Adder | 1.28 MW | 1.09 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939792 | AE1-210 E O1 | Adder | 8.56 MW | 7.28 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 941691 | AE2-169 | Adder | 2.58 MW | 2.19 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 941721 | AE2-172 | Adder | 2.57 MW | 2.18 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946031 | AF1-268 C O1 | Adder | 3.94 MW | 3.35 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946032 | AF1-268 E O1 | Adder | 1.79 MW | 1.52 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958001 | AF2-094 C | Adder | 2.37 MW | 2.02 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958002 | AF2-094 E | Adder | 1.22 MW | 1.04 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958431 | AF2-137 C | 50/50 | 25.78 MW | 25.78 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958432 | AF2-137 E | 50/50 | 35.61 MW | 35.61 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965432 | AG1-411 BAT | 50/50 | 12.75 MW | 12.75 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963703 | AG1-222 BAT | Adder | 15.21 MW | 12.93 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965852 | AG1-454 BAT | Adder | 5.88 MW | 5.0 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965023 | AG1-366 BAT | 50/50 | 9.37 MW | 9.37 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960853 | AF2-376 BAT | 50/50 | 6.79 MW | 6.79 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960863 | AF2-377 BAT | 50/50 | 6.74 MW | 6.74 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.18 MW | 0.18 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.61 MW | 0.61 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.04 MW | 6.04 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.72 MW | 5.72 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.82 MW | 17.82 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.26 MW | 0.26 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.67 MW | 0.67 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.75 MW | 2.75 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.42 MW | 1.42 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.42 MW | 3.42 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.35 MW | 4.35 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.28 MW | 0.28 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.04 MW | 2.04 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.72 MW | 0.72 MW |
| Details for 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 238979 | 02NAPMUN | Adder | -2.06 MW | -1.75 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 961631 | AG1-003 C | 50/50 | 27.53 MW | 27.53 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 961632 | AG1-003 E | 50/50 | 21.2 MW | 21.2 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 961641 | AG1-004 | 50/50 | 24.36 MW | 24.36 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965031 | AG1-367 C | Adder | 5.85 MW | 4.97 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965032 | AG1-367 E | Adder | 3.9 MW | 3.31 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965101 | AG1-375 C | 50/50 | 8.09 MW | 8.09 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965102 | AG1-375 E | 50/50 | 5.39 MW | 5.39 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965461 | AG1-414 C O1 | Adder | 2.63 MW | 2.23 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965462 | AG1-414 E O1 | Adder | 1.75 MW | 1.49 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965651 | AG1-433 C | 50/50 | 2.46 MW | 2.46 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965652 | AG1-433 E | 50/50 | 11.51 MW | 11.51 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247292 | 05KEY G1 | 50/50 | 1.54 MW | 1.54 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247293 | 05KEY G2 | 50/50 | 1.54 MW | 1.54 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247294 | 05KEY G3 | 50/50 | 1.59 MW | 1.59 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247295 | 05KEY G4 | 50/50 | 1.59 MW | 1.59 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247935 | V3-007 E | Adder | 15.07 MW | 12.81 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247958 | 05WLD G2 E | Adder | 10.5 MW | 8.93 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247963 | 05HDWTR1G E | Adder | 15.07 MW | 12.81 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 247968 | Z2-115 E | Adder | 0.07 MW | 0.06 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 926881 | AC1-175 C | Adder | 6.58 MW | 5.59 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 926882 | AC1-175 E | Adder | 10.74 MW | 9.13 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 934161 | AD1-043 C O1 | Adder | 2.76 MW | 2.35 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 934162 | AD1-043 E O1 | Adder | 4.5 MW | 3.83 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 934741 | AD1-101 C O1 | Adder | -1.96 MW | -1.66 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 934901 | AD1-119 C O1 | Adder | -2.74 MW | -2.33 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 934961 | AD1-128 C | Adder | 3.82 MW | 3.24 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 934962 | AD1-128 E | Adder | 6.23 MW | 5.29 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 936561 | AD2-071 C | Adder | 3.94 MW | 3.35 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 936562 | AD2-071 E | Adder | 1.94 MW | 1.65 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942081 | AE2-220 C | Adder | 4.55 MW | 3.87 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942082 | AE2-220 E | Adder | 6.28 MW | 5.34 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942241 | AE2-236 C O1 | Adder | 2.14 MW | 1.82 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942242 | AE2-236 E O1 | Adder | 0.92 MW | 0.78 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942661 | AE2-282 C | Adder | -2.61 MW | -2.22 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942791 | AE2-297 C O1 | Adder | 5.2 MW | 4.42 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 942792 | AE2-297 E O1 | Adder | 3.47 MW | 2.95 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944241 | AF1-092 C O1 | Adder | 10.22 MW | 8.69 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944242 | AF1-092 E O1 | Adder | 3.11 MW | 2.65 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944531 | AF1-118 C O1 | 50/50 | 43.98 MW | 43.98 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944532 | AF1-118 E O1 | 50/50 | 13.26 MW | 13.26 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944541 | AF1-119 C O1 | 50/50 | 19.56 MW | 19.56 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944542 | AF1-119 E O1 | 50/50 | 8.38 MW | 8.38 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944551 | AF1-120 C | Adder | -1.58 MW | -1.34 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944831 | AF1-148 C O1 | 50/50 | 15.13 MW | 15.13 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 944832 | AF1-148 E O1 | 50/50 | 10.08 MW | 10.08 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 945371 | AF1-202 C O1 | 50/50 | 4.31 MW | 4.31 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 945372 | AF1-202 E O1 | 50/50 | 21.03 MW | 21.03 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 945581 | AF1-223 C O1 | 50/50 | 11.4 MW | 11.4 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 945582 | AF1-223 E O1 | 50/50 | 7.6 MW | 7.6 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958711 | AF2-162 C | 50/50 | 4.19 MW | 4.19 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958712 | AF2-162 E | 50/50 | 2.1 MW | 2.1 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958821 | AF2-173 C | Adder | 8.19 MW | 6.96 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958822 | AF2-173 E | Adder | 11.31 MW | 9.62 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958861 | AF2-177 C O1 | 50/50 | 3.51 MW | 3.51 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958862 | AF2-177 E O1 | 50/50 | 23.47 MW | 23.47 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 959131 | AF2-204 C | Adder | 6.05 MW | 5.14 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 959132 | AF2-204 E | Adder | 3.19 MW | 2.71 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960441 | AF2-335 C | Adder | 4.54 MW | 3.86 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960442 | AF2-335 E | Adder | 3.02 MW | 2.57 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960791 | AF2-370 | Adder | 1.51 MW | 1.29 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960971 | AF2-388 C | 50/50 | 4.92 MW | 4.92 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960972 | AF2-388 E | 50/50 | 23.02 MW | 23.02 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 961161 | AF2-407 | Adder | 19.6 MW | 16.66 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 961171 | AF2-408 | Adder | 5.0 MW | 4.25 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 932681 | AC2-090 C | Adder | 3.29 MW | 2.8 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 932682 | AC2-090 E | Adder | 5.37 MW | 4.56 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 939761 | AE1-207 C | Adder | 4.25 MW | 3.61 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 939762 | AE1-207 E | Adder | 5.86 MW | 4.99 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 939771 | AE1-208 C | Adder | 4.25 MW | 3.61 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 939772 | AE1-208 E | Adder | 5.79 MW | 4.92 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 939781 | AE1-209 C O1 | Adder | 1.27 MW | 1.08 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 939782 | AE1-209 E O1 | Adder | 8.48 MW | 7.21 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 939791 | AE1-210 C O1 | Adder | 1.27 MW | 1.08 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 939792 | AE1-210 E O1 | Adder | 8.48 MW | 7.21 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 941691 | AE2-169 | Adder | 2.55 MW | 2.17 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 941721 | AE2-172 | Adder | 2.53 MW | 2.15 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 946031 | AF1-268 C O1 | Adder | 3.88 MW | 3.3 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 946032 | AF1-268 E O1 | Adder | 1.76 MW | 1.5 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958001 | AF2-094 C | Adder | 2.35 MW | 2.0 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958002 | AF2-094 E | Adder | 1.21 MW | 1.03 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958431 | AF2-137 C | 50/50 | 25.58 MW | 25.58 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 958432 | AF2-137 E | 50/50 | 35.32 MW | 35.32 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965432 | AG1-411 BAT | 50/50 | 12.91 MW | 12.91 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 963703 | AG1-222 BAT | Adder | 15.39 MW | 13.08 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965852 | AG1-454 BAT | 50/50 | 5.05 MW | 5.05 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 965023 | AG1-366 BAT | 50/50 | 9.43 MW | 9.43 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960853 | AF2-376 BAT | 50/50 | 6.86 MW | 6.86 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | 960863 | AF2-377 BAT | 50/50 | 6.8 MW | 6.8 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.58 MW | 0.58 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.53 MW | 5.53 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 4.51 MW | 4.51 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.11 MW | 17.11 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.23 MW | 0.23 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.62 MW | 0.62 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.61 MW | 2.61 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.37 MW | 1.37 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.29 MW | 3.29 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.38 MW | 0.38 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.02 MW | 4.02 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.27 MW | 0.27 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.94 MW | 1.94 MW |
| 05SORENS-05ROB PK 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.69 MW | 0.69 MW |
Light Load Analysis
The Queue Project was evaluated as a 100.0 MW (Capacity 100.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P1-2_#7441_100545-A
CONTINGENCY 'AEP_P1-2_#7441_100545-A' OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 END |
Single | DC | 130.79 % | 128.71 % | 897.0 | B | 1154.53 | 50.38 | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P1-2_#7441_100545-B
CONTINGENCY 'AEP_P1-2_#7441_100545-B' OPEN BRANCH FROM BUS 958430 TO BUS 246999 CKT 1 /*AF2-137 TAP 765.0 - 05SORENS 765.0 END |
Single | DC | 130.37 % | 126.98 % | 897.0 | B | 1139.01 | 50.38 | |
| AEP |
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
243211 to 242933 ckt 1 |
AEP_P4_#7445_05MARYSV 765_B
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B' OPEN BRANCH FROM BUS 242928 TO BUS 958430 CKT 1 /*05MARYSV 765.0 - AF2-137 TAP 765.0 OPEN BRANCH FROM BUS 962760 TO BUS 242928 CKT 1 /*AG1-125 TAP 765.0 - 05MARYSV 765.0 END |
Breaker | AC | 119.59 % | 123.12 % | 897.0 | B | 1104.39 | 50.72 | |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247521 | T131 | 80/20 | 1.25 MW | 1.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 270164 | T-131 E | 80/20 | 4.98 MW | 4.98 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274658 | DRESDEN ;2U | 80/20 | 65.53 MW | 65.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274659 | DRESDEN ;3U | 80/20 | 64.61 MW | 64.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274847 | GR RIDGE ;BU | 80/20 | 0.8 MW | 0.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274861 | TOP CROP ;1U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274862 | TOP CROP ;2U | 80/20 | 1.01 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274871 | GR RIDGE ;2U | 80/20 | 0.3 MW | 0.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274887 | PILOT HIL;1U | 80/20 | 1.04 MW | 1.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 274888 | KELLY CRK;1U | 80/20 | 1.04 MW | 1.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 275149 | KELLYCK ;1E | 80/20 | 4.15 MW | 4.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 293061 | N-015 E | 80/20 | 3.49 MW | 3.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 293644 | O22 E1 | 80/20 | 2.34 MW | 2.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 293645 | O22 E2 | 80/20 | 4.55 MW | 4.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 293799 | PILOT HIL;1E | 80/20 | 4.68 MW | 4.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 294392 | P-010 E | 80/20 | 4.44 MW | 4.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 926865 | AC1-173 C | 80/20 | 0.41 MW | 0.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 926866 | AC1-173 E | 80/20 | 2.74 MW | 2.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 933281 | AC2-140 C | 80/20 | 3.1 MW | 3.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 933282 | AC2-140 E | 80/20 | 0.16 MW | 0.16 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 934721 | AD1-100 C | 80/20 | 8.8 MW | 8.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 934722 | AD1-100 E | 80/20 | 41.06 MW | 41.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 936371 | AD2-047 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 936372 | AD2-047 E O1 | 80/20 | 9.84 MW | 9.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 943021 | AE2-325 C | 80/20 | 2.61 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 943022 | AE2-325 E | 80/20 | 1.74 MW | 1.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944241 | AF1-092 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944242 | AF1-092 E O1 | 80/20 | 12.48 MW | 12.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944531 | AF1-118 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944532 | AF1-118 E O1 | 80/20 | 35.47 MW | 35.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944541 | AF1-119 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944542 | AF1-119 E O1 | 80/20 | 17.66 MW | 17.66 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944831 | AF1-148 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944832 | AF1-148 E O1 | 80/20 | 15.76 MW | 15.76 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944931 | AF1-158 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944932 | AF1-158 E O1 | 80/20 | 12.37 MW | 12.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944961 | AF1-161 C | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 944962 | AF1-161 E | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 945111 | AF1-176 C O1 | 80/20 | 4.28 MW | 4.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 945112 | AF1-176 E O1 | 80/20 | 6.42 MW | 6.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 945371 | AF1-202 C O1 | 80/20 | 2.3 MW | 2.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 945372 | AF1-202 E O1 | 80/20 | 11.25 MW | 11.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 957371 | AF2-031 C O1 | 80/20 | 0.61 MW | 0.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 957372 | AF2-031 E O1 | 80/20 | 0.91 MW | 0.91 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 957401 | AF2-034 C | 80/20 | 0.29 MW | 0.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 957402 | AF2-034 E | 80/20 | 0.44 MW | 0.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958011 | AF2-095 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958021 | AF2-096 C | 80/20 | 5.55 MW | 5.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958861 | AF2-177 C O1 | 80/20 | 1.84 MW | 1.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 958862 | AF2-177 E O1 | 80/20 | 12.31 MW | 12.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959131 | AF2-204 C | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959132 | AF2-204 E | 80/20 | 8.18 MW | 8.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959181 | AF2-209 C | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959182 | AF2-209 E | 80/20 | 8.64 MW | 8.64 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 959352 | AF2-226 E | 80/20 | 2.15 MW | 2.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960282 | AF2-319 E | 80/20 | 2.15 MW | 2.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960381 | AF2-329 | 80/20 | 3.05 MW | 3.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960601 | AF2-351 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960602 | AF2-351 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960851 | AF2-376 C | 80/20 | 1.82 MW | 1.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960852 | AF2-376 E | 80/20 | 2.73 MW | 2.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960861 | AF2-377 C | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960862 | AF2-377 E | 80/20 | 3.12 MW | 3.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960971 | AF2-388 C | 80/20 | 2.55 MW | 2.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 960972 | AF2-388 E | 80/20 | 11.94 MW | 11.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 961051 | AF2-396 O1 | 80/20 | 6.81 MW | 6.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 961501 | AF2-441 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 961502 | AF2-441 E O1 | 80/20 | 9.06 MW | 9.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 961631 | AG1-003 | 80/20 | 10.05 MW | 10.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 961641 | AG1-004 | 80/20 | 20.11 MW | 20.11 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 962601 | AG1-109 | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 964361 | AG1-298 O1 | 80/20 | 37.83 MW | 37.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965021 | AG1-366 C | 80/20 | 4.01 MW | 4.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965022 | AG1-366 E | 80/20 | 6.02 MW | 6.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965651 | AG1-433 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965652 | AG1-433 E | 80/20 | 5.97 MW | 5.97 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965791 | AG1-447 | 80/20 | 4.38 MW | 4.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965851 | AG1-454 O1 | 80/20 | 5.65 MW | 5.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 966091 | AG1-478 C | 80/20 | 0.29 MW | 0.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 966092 | AG1-478 E | 80/20 | 0.44 MW | 0.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 966431 | AG1-512 C | 80/20 | 1.2 MW | 1.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 966432 | AG1-512 E | 80/20 | 1.79 MW | 1.79 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 966441 | AG1-513 C | 80/20 | 0.29 MW | 0.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 966442 | AG1-513 E | 80/20 | 0.43 MW | 0.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 966651 | AG1-535 O1 | 80/20 | 6.46 MW | 6.46 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 246953 | 05TIMB G C | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247911 | 05TIMB G E | 80/20 | 4.39 MW | 4.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 247968 | Z2-115 E | 80/20 | 0.07 MW | 0.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 963701 | AG1-222 C | 80/20 | 9.83 MW | 9.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 963702 | AG1-222 E | 80/20 | 6.56 MW | 6.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 936722 | AD2-091 BAT | 80/20 | 6.78 MW | 6.78 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 942042 | AE2-216 BAT | 80/20 | 7.46 MW | 7.46 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 945351 | AF1-200 FTIR | 80/20 | 149.84 MW | 149.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 946203 | AF1-285 BAT | 80/20 | 2.49 MW | 2.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-A | 965432 | AG1-411 BAT | 80/20 | 50.38 MW | 50.38 MW |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 247521 | T131 | 80/20 | 1.25 MW | 1.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 270164 | T-131 E | 80/20 | 4.98 MW | 4.98 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274658 | DRESDEN ;2U | 80/20 | 65.53 MW | 65.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274659 | DRESDEN ;3U | 80/20 | 64.61 MW | 64.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274847 | GR RIDGE ;BU | 80/20 | 0.8 MW | 0.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274861 | TOP CROP ;1U | 80/20 | 0.53 MW | 0.53 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274862 | TOP CROP ;2U | 80/20 | 1.01 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274871 | GR RIDGE ;2U | 80/20 | 0.3 MW | 0.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274887 | PILOT HIL;1U | 80/20 | 1.04 MW | 1.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274888 | KELLY CRK;1U | 80/20 | 1.04 MW | 1.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 274891 | OTTER CRK;1U | 80/20 | 0.63 MW | 0.63 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 275149 | KELLYCK ;1E | 80/20 | 4.15 MW | 4.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 293061 | N-015 E | 80/20 | 3.49 MW | 3.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 293644 | O22 E1 | 80/20 | 2.34 MW | 2.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 293645 | O22 E2 | 80/20 | 4.55 MW | 4.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 293799 | PILOT HIL;1E | 80/20 | 4.68 MW | 4.68 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 294392 | P-010 E | 80/20 | 4.44 MW | 4.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 918052 | AA1-018 E OP | 80/20 | 4.21 MW | 4.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 926865 | AC1-173 C | 80/20 | 0.41 MW | 0.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 926866 | AC1-173 E | 80/20 | 2.74 MW | 2.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 933281 | AC2-140 C | 80/20 | 3.1 MW | 3.1 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 933282 | AC2-140 E | 80/20 | 0.16 MW | 0.16 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 934721 | AD1-100 C | 80/20 | 8.8 MW | 8.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 934722 | AD1-100 E | 80/20 | 41.06 MW | 41.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 936371 | AD2-047 C O1 | 80/20 | 2.02 MW | 2.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 936372 | AD2-047 E O1 | 80/20 | 9.84 MW | 9.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 943021 | AE2-325 C | 80/20 | 2.61 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 943022 | AE2-325 E | 80/20 | 1.74 MW | 1.74 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944241 | AF1-092 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944242 | AF1-092 E O1 | 80/20 | 12.48 MW | 12.48 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944531 | AF1-118 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944532 | AF1-118 E O1 | 80/20 | 35.47 MW | 35.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944541 | AF1-119 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944542 | AF1-119 E O1 | 80/20 | 17.66 MW | 17.66 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944831 | AF1-148 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944832 | AF1-148 E O1 | 80/20 | 15.76 MW | 15.76 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944931 | AF1-158 C O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944932 | AF1-158 E O1 | 80/20 | 12.37 MW | 12.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944961 | AF1-161 C | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 944962 | AF1-161 E | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 945111 | AF1-176 C O1 | 80/20 | 4.28 MW | 4.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 945112 | AF1-176 E O1 | 80/20 | 6.42 MW | 6.42 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 945371 | AF1-202 C O1 | 80/20 | 2.3 MW | 2.3 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 945372 | AF1-202 E O1 | 80/20 | 11.25 MW | 11.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 957371 | AF2-031 C O1 | 80/20 | 0.61 MW | 0.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 957372 | AF2-031 E O1 | 80/20 | 0.91 MW | 0.91 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 957401 | AF2-034 C | 80/20 | 0.29 MW | 0.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 957402 | AF2-034 E | 80/20 | 0.44 MW | 0.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 958011 | AF2-095 C O1 | 80/20 | 2.96 MW | 2.96 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 958021 | AF2-096 C | 80/20 | 5.55 MW | 5.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 958861 | AF2-177 C O1 | 80/20 | 1.84 MW | 1.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 958862 | AF2-177 E O1 | 80/20 | 12.31 MW | 12.31 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 959131 | AF2-204 C | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 959132 | AF2-204 E | 80/20 | 8.18 MW | 8.18 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 959181 | AF2-209 C | 80/20 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 959182 | AF2-209 E | 80/20 | 8.64 MW | 8.64 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 959351 | AF2-226 C | 80/20 | 1.44 MW | 1.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 959352 | AF2-226 E | 80/20 | 2.15 MW | 2.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960281 | AF2-319 C | 80/20 | 1.44 MW | 1.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960282 | AF2-319 E | 80/20 | 2.15 MW | 2.15 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960381 | AF2-329 | 80/20 | 3.05 MW | 3.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960601 | AF2-351 C O1 | 80/20 | 0.59 MW | 0.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960602 | AF2-351 E O1 | 80/20 | 0.89 MW | 0.89 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960851 | AF2-376 C | 80/20 | 1.82 MW | 1.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960852 | AF2-376 E | 80/20 | 2.73 MW | 2.73 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960861 | AF2-377 C | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960862 | AF2-377 E | 80/20 | 3.12 MW | 3.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960971 | AF2-388 C | 80/20 | 2.55 MW | 2.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 960972 | AF2-388 E | 80/20 | 11.94 MW | 11.94 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 961051 | AF2-396 O1 | 80/20 | 6.81 MW | 6.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 961501 | AF2-441 C O1 | 80/20 | 6.04 MW | 6.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 961502 | AF2-441 E O1 | 80/20 | 9.06 MW | 9.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 962601 | AG1-109 | 80/20 | 2.08 MW | 2.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 964361 | AG1-298 O1 | 80/20 | 37.83 MW | 37.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 965021 | AG1-366 C | 80/20 | 4.01 MW | 4.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 965022 | AG1-366 E | 80/20 | 6.02 MW | 6.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 965651 | AG1-433 C | 80/20 | 1.28 MW | 1.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 965652 | AG1-433 E | 80/20 | 5.97 MW | 5.97 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 965791 | AG1-447 | 80/20 | 4.38 MW | 4.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 965851 | AG1-454 O1 | 80/20 | 5.65 MW | 5.65 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 966091 | AG1-478 C | 80/20 | 0.29 MW | 0.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 966092 | AG1-478 E | 80/20 | 0.44 MW | 0.44 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 966431 | AG1-512 C | 80/20 | 1.2 MW | 1.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 966432 | AG1-512 E | 80/20 | 1.79 MW | 1.79 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 966441 | AG1-513 C | 80/20 | 0.29 MW | 0.29 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 966442 | AG1-513 E | 80/20 | 0.43 MW | 0.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 966651 | AG1-535 O1 | 80/20 | 6.46 MW | 6.46 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 246953 | 05TIMB G C | 80/20 | 0.83 MW | 0.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 247911 | 05TIMB G E | 80/20 | 4.39 MW | 4.39 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 247968 | Z2-115 E | 80/20 | 0.07 MW | 0.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 963701 | AG1-222 C | 80/20 | 9.83 MW | 9.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 963702 | AG1-222 E | 80/20 | 6.56 MW | 6.56 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 936722 | AD2-091 BAT | 80/20 | 6.78 MW | 6.78 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 942042 | AE2-216 BAT | 80/20 | 7.46 MW | 7.46 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 945351 | AF1-200 FTIR | 80/20 | 149.84 MW | 149.84 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 946203 | AF1-285 BAT | 80/20 | 2.49 MW | 2.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545-B | 965432 | AG1-411 BAT | 80/20 | 50.38 MW | 50.38 MW |
| Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247521 | T131 | 50/50 | 1.22 MW | 1.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 270164 | T-131 E | 50/50 | 4.86 MW | 4.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 274658 | DRESDEN ;2U | Adder | 64.87 MW | 55.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 274659 | DRESDEN ;3U | Adder | 63.97 MW | 54.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 276170 | Z1-108 E | Adder | 1.66 MW | 1.41 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926865 | AC1-173 C | 50/50 | 0.4 MW | 0.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 926866 | AC1-173 E | 50/50 | 2.67 MW | 2.67 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 933281 | AC2-140 C | Adder | 3.07 MW | 2.61 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 933282 | AC2-140 E | Adder | 0.16 MW | 0.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934721 | AD1-100 C | Adder | 8.71 MW | 7.4 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 934722 | AD1-100 E | Adder | 40.64 MW | 34.55 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936371 | AD2-047 C O1 | Adder | 2.0 MW | 1.7 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936372 | AD2-047 E O1 | Adder | 9.74 MW | 8.28 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939321 | AE1-163 C O1 | Adder | 2.75 MW | 2.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939322 | AE1-163 E O1 | Adder | 16.87 MW | 14.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939401 | AE1-172 C O1 | Adder | 1.22 MW | 1.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939402 | AE1-172 E O1 | Adder | 5.72 MW | 4.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942651 | AE2-281 C O1 | Adder | 0.39 MW | 0.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942652 | AE2-281 E O1 | Adder | 2.41 MW | 2.05 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 943021 | AE2-325 C | Adder | 2.57 MW | 2.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 943022 | AE2-325 E | Adder | 1.72 MW | 1.46 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944241 | AF1-092 C O1 | 50/50 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944242 | AF1-092 E O1 | 50/50 | 12.34 MW | 12.34 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944531 | AF1-118 C O1 | 50/50 | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944532 | AF1-118 E O1 | 50/50 | 35.02 MW | 35.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944541 | AF1-119 C O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944542 | AF1-119 E O1 | Adder | 17.43 MW | 14.82 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944831 | AF1-148 C O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944832 | AF1-148 E O1 | Adder | 15.56 MW | 13.22 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944931 | AF1-158 C O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944932 | AF1-158 E O1 | Adder | 12.21 MW | 10.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944961 | AF1-161 C | Adder | 2.05 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 944962 | AF1-161 E | Adder | 2.05 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945111 | AF1-176 C O1 | Adder | 4.22 MW | 3.59 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945112 | AF1-176 E O1 | Adder | 6.33 MW | 5.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945371 | AF1-202 C O1 | Adder | 2.27 MW | 1.93 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945372 | AF1-202 E O1 | Adder | 11.1 MW | 9.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 957331 | AF2-027 C | Adder | 1.41 MW | 1.2 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 957332 | AF2-027 E | Adder | 2.11 MW | 1.8 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 957371 | AF2-031 C O1 | Adder | 0.6 MW | 0.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 957372 | AF2-031 E O1 | Adder | 0.9 MW | 0.77 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 957401 | AF2-034 C | Adder | 0.29 MW | 0.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 957402 | AF2-034 E | Adder | 0.43 MW | 0.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 957841 | AF2-078 C O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 957842 | AF2-078 E O1 | Adder | 1.4 MW | 1.19 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958011 | AF2-095 C O1 | Adder | 2.93 MW | 2.49 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958012 | AF2-095 E O1 | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958021 | AF2-096 C | Adder | 5.49 MW | 4.67 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958022 | AF2-096 E | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958861 | AF2-177 C O1 | Adder | 1.81 MW | 1.54 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 958862 | AF2-177 E O1 | Adder | 12.14 MW | 10.32 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959131 | AF2-204 C | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959132 | AF2-204 E | Adder | 8.07 MW | 6.86 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959181 | AF2-209 C | Adder | 0.0 MW | 0.0 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959182 | AF2-209 E | Adder | 8.44 MW | 7.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959351 | AF2-226 C | Adder | 1.42 MW | 1.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 959352 | AF2-226 E | Adder | 2.13 MW | 1.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960281 | AF2-319 C | Adder | 1.42 MW | 1.21 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960282 | AF2-319 E | Adder | 2.13 MW | 1.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960381 | AF2-329 | Adder | 3.02 MW | 2.57 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960601 | AF2-351 C O1 | Adder | 0.59 MW | 0.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960602 | AF2-351 E O1 | Adder | 0.88 MW | 0.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960851 | AF2-376 C | Adder | 1.77 MW | 1.5 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960852 | AF2-376 E | Adder | 2.65 MW | 2.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960861 | AF2-377 C | 50/50 | 2.03 MW | 2.03 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960862 | AF2-377 E | 50/50 | 3.04 MW | 3.04 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960971 | AF2-388 C | Adder | 2.52 MW | 2.14 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 960972 | AF2-388 E | Adder | 11.79 MW | 10.02 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961051 | AF2-396 O1 | Adder | 6.72 MW | 5.71 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961501 | AF2-441 C O1 | Adder | 5.97 MW | 5.08 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961502 | AF2-441 E O1 | Adder | 8.96 MW | 7.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961631 | AG1-003 | Adder | 9.94 MW | 8.45 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 961641 | AG1-004 | Adder | 19.89 MW | 16.9 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 962601 | AG1-109 | Adder | 2.05 MW | 1.75 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 964361 | AG1-298 O1 | Adder | 37.42 MW | 31.81 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965021 | AG1-366 C | 50/50 | 3.97 MW | 3.97 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965022 | AG1-366 E | 50/50 | 5.96 MW | 5.96 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965651 | AG1-433 C | Adder | 1.26 MW | 1.07 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965652 | AG1-433 E | Adder | 5.89 MW | 5.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965791 | AG1-447 | Adder | 4.32 MW | 3.67 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965851 | AG1-454 O1 | 50/50 | 5.58 MW | 5.58 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 966091 | AG1-478 C | Adder | 0.29 MW | 0.25 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 966092 | AG1-478 E | Adder | 0.43 MW | 0.37 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 966431 | AG1-512 C | Adder | 1.18 MW | 1.01 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 966432 | AG1-512 E | Adder | 1.78 MW | 1.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 966441 | AG1-513 C | Adder | 0.29 MW | 0.24 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 966442 | AG1-513 E | Adder | 0.43 MW | 0.36 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 966651 | AG1-535 O1 | Adder | 6.39 MW | 5.43 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 247968 | Z2-115 E | Adder | 0.07 MW | 0.06 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939781 | AE1-209 C O1 | Adder | 0.73 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939782 | AE1-209 E O1 | Adder | 4.91 MW | 4.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939791 | AE1-210 C O1 | Adder | 0.73 MW | 0.62 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 939792 | AE1-210 E O1 | Adder | 4.91 MW | 4.17 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 941721 | AE2-172 | Adder | 2.8 MW | 2.38 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965462 | AG1-414 E O1 | Adder | 1.78 MW | 1.51 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963701 | AG1-222 C | 50/50 | 9.71 MW | 9.71 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 963702 | AG1-222 E | 50/50 | 6.47 MW | 6.47 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 936722 | AD2-091 BAT | 50/50 | 7.12 MW | 7.12 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 942042 | AE2-216 BAT | 50/50 | 7.83 MW | 7.83 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 945351 | AF1-200 FTIR | Adder | 174.51 MW | 148.33 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 946203 | AF1-285 BAT | 50/50 | 2.63 MW | 2.63 MW |
| 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B | 965432 | AG1-411 BAT | 50/50 | 50.72 MW | 50.72 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n7683 | Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA. | $14,200,000 | |
| n7467 | Replace one Marysville 765kV CB | $3,000,000 | |
| n7751 | Replace 1600A Switches at Sorenson 345kV | $100,000 | |
| n8196.2 | In addition to N8196.1, replace an additional existing double circuit towers with steel double circuit single pole structures on the Allen - RPMone 345kV line. | $458,600 | |
| n8196.1 | AEP will replace two (2) existing double circuit towers with steel double circuit single pole structures on the Allen - RPMone 345kV line. | $916,437 | |
| n6740 | Sag Study - Allen and Rpmone 345 kV line (12.25 miles). Completed, Rate B should be 1057MVA. | $49,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-411 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.