AG1-400 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:52
Blue Mound-Chestnut 345 kV
150.0 MW Capacity / 150.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-400 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the ComEd zone — McLean County, Illinois. The installed facilities will have a total capability of 150.0 MW with 150.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-400 |
| Project Name | Blue Mound-Chestnut 345 kV |
| Developer Name | Wapella Bluffs Wind Project, LLC |
| State | Illinois |
| County | McLean |
| Transmission Owner | ComEd |
| MFO | 150.0 MW |
| MWE | 150.0 MW |
| MWC | 150.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-400 will interconnect on the ComEd transmission system utilizing the physical interconnection facilities of the AG1-399 project which will tap the Blue Mound to Chestnut 345 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 150.0 MW (Capacity 150.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545
CONTINGENCY 'EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545' OPEN BRANCH FROM BUS 249521 TO BUS 347340 CKT 1 /*08SUGCRK 345.0 - 7KANSAS 345.0 END |
Single | AC | 120.34 % | 121.5 % | 1466.0 | B | 1781.18 | 18.94 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
Base Case | Single | AC | 110.95 % | 112.17 % | 1334.0 | A | 1496.37 | 15.65 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 152.52 % | 155.02 % | 2107.0 | STE | 3266.18 | 51.83 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P4_012-45-BT14-15
CONTINGENCY 'COMED_P4_012-45-BT14-15' TRIP BRANCH FROM BUS 270697 TO BUS 270717 CKT 1 /*COLLINS ; R 345.0 - DRESDEN ; R 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 148.09 % | 150.55 % | 2107.0 | STE | 3172.07 | 51.16 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 166.55 % | 169.4 % | 1846.0 | STE | 3127.14 | 51.83 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P4_012-45-BT14-15
CONTINGENCY 'COMED_P4_012-45-BT14-15' TRIP BRANCH FROM BUS 270697 TO BUS 270717 CKT 1 /*COLLINS ; R 345.0 - DRESDEN ; R 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 160.16 % | 162.96 % | 1846.0 | STE | 3008.16 | 51.16 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 157.03 % | 159.86 % | 1837.0 | STE | 2936.65 | 51.86 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P4_012-45-BT14-15
CONTINGENCY 'COMED_P4_012-45-BT14-15' TRIP BRANCH FROM BUS 270697 TO BUS 270717 CKT 1 /*COLLINS ; R 345.0 - DRESDEN ; R 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 150.63 % | 153.42 % | 1837.0 | STE | 2818.24 | 51.2 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3128_05EUGENE 345_A2
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2' OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1 /*05EUGENE 345.0 - 08CAYSUB 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 169.38 % | 169.83 % | 1466.0 | B | 2489.69 | 20.62 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3130_05EUGENE 345_B2
CONTINGENCY 'AEP_P4_#3130_05EUGENE 345_B2' OPEN BRANCH FROM BUS 243221 TO BUS 247712 CKT 1 /*05EUGENE 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 156.51 % | 156.84 % | 1466.0 | B | 2299.25 | 20.12 | |
| CE |
BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line
270668 to 270852 ckt 1 |
COMED_P4_BRO-45-BT2-3__
CONTINGENCY 'COMED_P4_BRO-45-BT2-3__' TRIP BRANCH FROM BUS 270853 TO BUS 270819 CKT 1 /*PONTIAC ; R 345.0 - MCLEAN ; R 345.0 TRIP BRANCH FROM BUS 348847 TO BUS 348848 CKT 2 /*7BROKAW 345.0 - 4BROKAW 138.0 END |
Breaker | AC | 122.64 % | 126.15 % | 1797.0 | STE | 2266.96 | 64.64 | |
| AMIL/CE |
AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line
924260 to 348847 ckt 1 |
COMED_P4_LAT-45-BT11___
CONTINGENCY 'COMED_P4_LAT-45-BT11___' TRIP BRANCH FROM BUS 270796 TO BUS 348856 CKT 1 /*KINCAID ; B 345.0 - 7LATHAM 345.0 TRIP BRANCH FROM BUS 348856 TO BUS 348849 CKT 1 /*7LATHAM 345.0 - 4LATHAM 2 138.0 END |
Breaker | AC | 115.42 % | 116.5 % | 1327.0 | B | 1545.98 | 14.72 | |
| AMIL/CE |
AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line
924260 to 348847 ckt 1 |
COMED_P4_LAT-45-BT15___
CONTINGENCY 'COMED_P4_LAT-45-BT15___' TRIP BRANCH FROM BUS 270796 TO BUS 348856 CKT 1 /*KINCAID ; B 345.0 - 7LATHAM 345.0 TRIP BRANCH FROM BUS 348856 TO BUS 270685 CKT 1 /*7LATHAM 345.0 - CHESTNUT ; B 345.0 END |
Breaker | AC | 113.68 % | 114.78 % | 1327.0 | B | 1523.08 | 14.89 | |
| CE |
AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line
925770 to 924260 ckt 1 |
COMED_P4_LAT-45-BT11___
CONTINGENCY 'COMED_P4_LAT-45-BT11___' TRIP BRANCH FROM BUS 270796 TO BUS 348856 CKT 1 /*KINCAID ; B 345.0 - 7LATHAM 345.0 TRIP BRANCH FROM BUS 348856 TO BUS 348849 CKT 1 /*7LATHAM 345.0 - 4LATHAM 2 138.0 END |
Breaker | AC | 104.23 % | 105.29 % | 1346.0 | STE | 1417.24 | 14.72 | |
| CE |
AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line
925770 to 924260 ckt 1 |
COMED_P4_LAT-45-BT15___
CONTINGENCY 'COMED_P4_LAT-45-BT15___' TRIP BRANCH FROM BUS 270796 TO BUS 348856 CKT 1 /*KINCAID ; B 345.0 - 7LATHAM 345.0 TRIP BRANCH FROM BUS 348856 TO BUS 270685 CKT 1 /*7LATHAM 345.0 - CHESTNUT ; B 345.0 END |
Breaker | AC | 102.5 % | 103.57 % | 1346.0 | STE | 1394.08 | 14.89 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P2-2_#286_05EUGENE 345_2
CONTINGENCY 'AEP_P2-2_#286_05EUGENE 345_2' OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Bus | AC | 157.51 % | 157.62 % | 1466.0 | B | 2310.75 | 20.42 | |
| CE |
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
934720 to 270926 ckt 1 |
COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A
CONTINGENCY 'COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A' TRIP BRANCH FROM BUS 270671 TO BUS 270729 CKT 1 /*BRAIDWOOD; R 345.0 - E FRANKFO; R 345.0 TRIP BRANCH FROM BUS 270728 TO BUS 270766 CKT 1 /*E FRANKFO; B 345.0 - GOODINGS ;3B 345.0 TRIP BRANCH FROM BUS 270728 TO BUS 274750 CKT 1 /*E FRANKFO; B 345.0 - CRETE EC ;BP 345.0 TRIP BRANCH FROM BUS 958020 TO BUS 270728 CKT 1 /*AF2-096 TAP 345.0 - E FRANKFO; B 345.0 END |
Tower | AC | 99.49 % | 100.26 % | 2554.0 | ALDR | 2560.68 | 18.98 | |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 961651 | AG1-005 C O1 | 80/20 | 11.76 MW | 11.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 962721 | AG1-121 C O1 | 80/20 | 4.07 MW | 4.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 963831 | AG1-236 C | 80/20 | 3.67 MW | 3.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 964581 | AG1-321 C O1 | 80/20 | 10.95 MW | 10.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 966821 | AG1-553 C O1 | 80/20 | 18.77 MW | 18.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965061 | AG1-371 | Adder | 1.93 MW | 1.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965081 | AG1-373 | Adder | 0.64 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965091 | AG1-374 C | 80/20 | 20.2 MW | 20.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965141 | AG1-379 C | Adder | 8.57 MW | 7.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965331 | AG1-398 | 80/20 | 1.01 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965341 | AG1-399 C | 80/20 | 6.67 MW | 6.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965351 | AG1-400 | 80/20 | 18.94 MW | 18.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965371 | AG1-402 | 80/20 | 18.94 MW | 18.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965391 | AG1-404 | 80/20 | 12.62 MW | 12.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965661 | AG1-434 C O1 | Adder | 2.33 MW | 1.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965671 | AG1-435 C O1 | 80/20 | 2.78 MW | 2.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965911 | AG1-460 C | 80/20 | 2.02 MW | 2.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 965931 | AG1-462 C O1 | 80/20 | 12.14 MW | 12.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 272364 | ESS H440N ;R | Adder | 1.39 MW | 1.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 295110 | SUBLETTE C | 80/20 | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 919221 | AA1-146 | 80/20 | 1.92 MW | 1.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 919581 | AA2-030 C | 80/20 | 11.24 MW | 11.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 925771 | AC1-053 C | 80/20 | 3.67 MW | 3.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 926821 | AC1-168 C O1 | 80/20 | 0.76 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 927201 | AC1-214 C O1 | 80/20 | 0.26 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 933911 | AD1-013 C | Adder | 0.98 MW | 0.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 934051 | AD1-031 C O1 | 80/20 | 2.12 MW | 2.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 934971 | AD1-129 C | Adder | 0.47 MW | 0.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 935141 | AD1-148 | 80/20 | 5.36 MW | 5.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 936511 | AD2-066 C O1 | Adder | 4.53 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 936771 | AD2-100 C | 80/20 | 21.97 MW | 21.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 936971 | AD2-131 C | 80/20 | 1.45 MW | 1.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 937001 | AD2-134 C | Adder | 1.35 MW | 1.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 937311 | AD2-172 C | Adder | 1.4 MW | 1.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 942111 | AE2-223 C | 80/20 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 942421 | AE2-255 C O1 | Adder | 1.56 MW | 1.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 942481 | AE2-261 C | 80/20 | 30.19 MW | 30.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 945871 | AF1-252 O1 | 80/20 | 11.99 MW | 11.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 945881 | AF1-253 | 80/20 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 958911 | AF2-182 C | 80/20 | 12.57 MW | 12.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 958921 | AF2-183 C | 80/20 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959081 | AF2-199 C | Adder | 3.86 MW | 3.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959091 | AF2-200 C O1 | Adder | 7.73 MW | 6.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959101 | AF2-201 C O1 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959341 | AF2-225 C | 80/20 | 6.45 MW | 6.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 959611 | AF2-252 C | 80/20 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 960141 | AF2-305 | 80/20 | 1.27 MW | 1.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 960261 | AF2-317 | 80/20 | 2.32 MW | 2.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 960611 | AF2-352 C | 80/20 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 961011 | AF2-392 C O1 | 80/20 | 2.5 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 961021 | AF2-393 O1 | 80/20 | 4.26 MW | 4.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 961031 | AF2-394 O1 | 80/20 | 2.84 MW | 2.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274650 | KINCAID ;1U | 80/20 | 15.72 MW | 15.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274651 | KINCAID ;2U | 80/20 | 15.71 MW | 15.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274662 | QUAD CITI;1U | 80/20 | 12.34 MW | 12.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274663 | QUAD CITI;2U | 80/20 | 12.34 MW | 12.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274699 | CORDOVA ;1C | 80/20 | 2.17 MW | 2.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274700 | CORDOVA ;2C | 80/20 | 2.17 MW | 2.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274701 | CORDOVA ;1S | 80/20 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274715 | NELSON EC;1C | 80/20 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274716 | NELSON EC;1S | 80/20 | 1.5 MW | 1.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274717 | NELSON EC;2C | 80/20 | 2.07 MW | 2.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274718 | NELSON EC;2S | 80/20 | 1.51 MW | 1.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274760 | LEE CO EC;1U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274761 | LEE CO EC;2U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274762 | LEE CO EC;3U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274764 | LEE CO EC;5U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274765 | LEE CO EC;6U | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274848 | CAMPGROVE;RU | 80/20 | 0.36 MW | 0.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274849 | CRESCENT ;1U | 80/20 | 0.14 MW | 0.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274851 | PROVIDENC;RU | 80/20 | 0.14 MW | 0.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274853 | TWINGROVE;U1 | 80/20 | 0.67 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274854 | TWINGROVE;U2 | 80/20 | 0.68 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274863 | CAYUGA RI;1U | 80/20 | 0.3 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274864 | CAYUGA RI;2U | 80/20 | 0.3 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274877 | BISHOP HL;1U | 80/20 | 0.27 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274878 | BISHOP HL;2U | 80/20 | 0.27 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274880 | RADFORD R;1U | 80/20 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 274889 | BRIGHTSTK;1U | 80/20 | 0.45 MW | 0.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 276156 | O-029 C | 80/20 | 0.14 MW | 0.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 276157 | O-029 C | 80/20 | 0.15 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 276158 | O-029 C | 80/20 | 0.27 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 293513 | O-009 C1 | 80/20 | 0.26 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 293514 | O-009 C2 | 80/20 | 0.13 MW | 0.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 293515 | O-009 C3 | 80/20 | 0.14 MW | 0.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 924041 | AB2-047 C O1 | 80/20 | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 924261 | AB2-070 C O1 | 80/20 | 3.59 MW | 3.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 925581 | AC1-033 C | 80/20 | 1.04 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 930482 | AB1-089 CT | Adder | 19.56 MW | 16.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 930483 | AB1-089 ST | Adder | 15.55 MW | 13.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 930761 | AB1-122 CT1 | Adder | 38.62 MW | 32.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 938851 | AE1-113 C O1 | Adder | 4.12 MW | 3.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 938861 | AE1-114 C O1 | Adder | 2.32 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 939051 | AE1-134 1 | 80/20 | 0.87 MW | 0.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 939061 | AE1-134 2 | 80/20 | 0.87 MW | 0.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 939401 | AE1-172 C O1 | 80/20 | 3.23 MW | 3.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 939741 | AE1-205 C O1 | 80/20 | 8.6 MW | 8.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 940501 | AE2-035 C | Adder | 1.4 MW | 1.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 941731 | AE2-173 O1 | 80/20 | 5.12 MW | 5.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 944221 | AF1-090 C O1 | 80/20 | 6.76 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946151 | AF1-280 C O1 | 80/20 | 9.57 MW | 9.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946161 | AF1-281 C O1 | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946321 | AF1-296 C O1 | 80/20 | 2.92 MW | 2.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946501 | AF1-314 C | Adder | 2.47 MW | 2.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946541 | AF1-318 C O1 | 80/20 | 4.14 MW | 4.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 946671 | AF1-331 | Adder | 1.27 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 957381 | AF2-032 C | 80/20 | 2.26 MW | 2.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 957471 | AF2-041 C | Adder | 11.59 MW | 9.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 957751 | AF2-069 C | 80/20 | 0.17 MW | 0.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 957761 | AF2-070 C | 80/20 | 0.24 MW | 0.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 958341 | AF2-128 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 934101 | AD2-000 1 | Adder | 3.12 MW | 2.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 944202 | AF1-088 FTWR | 80/20 | 245.28 MW | 245.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 952651 | J756 C | External Queue | 2.22 MW | 2.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 952871 | J757 C | External Queue | 4.04 MW | 4.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953371 | J808 | External Queue | 10.27 MW | 10.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953401 | J811 | External Queue | 19.51 MW | 19.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953431 | J853 | External Queue | 12.26 MW | 12.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953641 | J813 | External Queue | 43.35 MW | 43.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953651 | J815 | External Queue | 33.52 MW | 33.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953671 | J817 | External Queue | 11.46 MW | 11.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953741 | J826 C | External Queue | 1.11 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953881 | J848 C | External Queue | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 953951 | J859 | External Queue | 9.46 MW | 9.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 954411 | J912 | External Queue | 15.02 MW | 15.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 954681 | J949 C | External Queue | 38.76 MW | 38.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 954721 | J750 C | External Queue | 2.12 MW | 2.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 954821 | J955 | External Queue | 113.42 MW | 113.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 956151 | J1102 | External Queue | 5.29 MW | 5.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 956281 | J1115 C | External Queue | 2.59 MW | 2.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 956451 | J1139 | External Queue | 12.24 MW | 12.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990056 | J1201 | External Queue | 7.49 MW | 7.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990071 | J1204 | External Queue | 71.26 MW | 71.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990271 | J1263 | External Queue | 121.58 MW | 121.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990351 | J1289 C | External Queue | 2.11 MW | 2.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 990856 | J1408 | External Queue | 10.35 MW | 10.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991191 | J1610 | External Queue | 9.56 MW | 9.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991196 | J1626 | External Queue | 29.56 MW | 29.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991236 | J1676 C | External Queue | 3.32 MW | 3.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991266 | J1714 | External Queue | 19.71 MW | 19.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | 991261 | J1713 C | External Queue | 3.18 MW | 3.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 4.33 MW | 4.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.63 MW | 1.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.23 MW | 15.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 68.22 MW | 68.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.57 MW | 67.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.59 MW | 0.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 1.7 MW | 1.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.02 MW | 13.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.72 MW | 1.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.21 MW | 15.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.47 MW | 1.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.97 MW | 7.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o EXT_P12:345:DEI-AMIL:AMEREN KANSAS-SUGAR CREEK 34545 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.01 MW | 2.01 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961651 | AG1-005 C O1 | 80/20 | 9.86 MW | 9.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C O1 | 80/20 | 3.42 MW | 3.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 3.04 MW | 3.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 964581 | AG1-321 C O1 | 80/20 | 9.09 MW | 9.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 15.99 MW | 15.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965091 | AG1-374 C | 80/20 | 16.71 MW | 16.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 0.84 MW | 0.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C | 80/20 | 5.51 MW | 5.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 | 80/20 | 15.65 MW | 15.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 | 80/20 | 15.65 MW | 15.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 | 80/20 | 10.43 MW | 10.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C O1 | 80/20 | 2.34 MW | 2.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965931 | AG1-462 C O1 | 80/20 | 10.35 MW | 10.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.03 MW | 0.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 1.63 MW | 1.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 919581 | AA2-030 C | 80/20 | 9.55 MW | 9.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 3.04 MW | 3.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.64 MW | 0.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 934051 | AD1-031 C O1 | 80/20 | 1.78 MW | 1.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 4.45 MW | 4.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 936771 | AD2-100 C | 80/20 | 18.31 MW | 18.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 936971 | AD2-131 C | 80/20 | 1.21 MW | 1.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 937311 | AD2-172 C | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942481 | AE2-261 C | 80/20 | 25.14 MW | 25.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 10.01 MW | 10.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 6.93 MW | 6.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958911 | AF2-182 C | 80/20 | 10.68 MW | 10.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 1.9 MW | 1.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | Adder | 2.9 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959341 | AF2-225 C | 80/20 | 5.33 MW | 5.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 1.86 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 1.92 MW | 1.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 1.86 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 2.12 MW | 2.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 3.62 MW | 3.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.41 MW | 2.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274650 | KINCAID ;1U | 80/20 | 13.09 MW | 13.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274651 | KINCAID ;2U | 80/20 | 13.08 MW | 13.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274662 | QUAD CITI;1U | 80/20 | 10.51 MW | 10.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274663 | QUAD CITI;2U | 80/20 | 10.51 MW | 10.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274699 | CORDOVA ;1C | 80/20 | 1.84 MW | 1.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274700 | CORDOVA ;2C | 80/20 | 1.84 MW | 1.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274701 | CORDOVA ;1S | 80/20 | 2.07 MW | 2.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274715 | NELSON EC;1C | 80/20 | 1.74 MW | 1.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274716 | NELSON EC;1S | 80/20 | 1.27 MW | 1.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274717 | NELSON EC;2C | 80/20 | 1.76 MW | 1.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274718 | NELSON EC;2S | 80/20 | 1.28 MW | 1.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274760 | LEE CO EC;1U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274761 | LEE CO EC;2U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274762 | LEE CO EC;3U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274764 | LEE CO EC;5U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274765 | LEE CO EC;6U | 80/20 | 0.85 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.3 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.11 MW | 0.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 0.55 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 0.25 MW | 0.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 0.25 MW | 0.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.23 MW | 0.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.23 MW | 0.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 0.89 MW | 0.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 0.38 MW | 0.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.13 MW | 0.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.23 MW | 0.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.22 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.11 MW | 0.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 0.47 MW | 0.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 2.97 MW | 2.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.88 MW | 0.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 930761 | AB1-122 CT1 | Adder | 32.47 MW | 27.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | Adder | 1.97 MW | 1.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939051 | AE1-134 1 | 80/20 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939061 | AE1-134 2 | 80/20 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939741 | AE1-205 C O1 | 80/20 | 7.11 MW | 7.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 940501 | AE2-035 C | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 4.23 MW | 4.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 5.64 MW | 5.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946151 | AF1-280 C O1 | 80/20 | 8.13 MW | 8.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.18 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 2.48 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | Adder | 2.1 MW | 1.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 3.48 MW | 3.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957381 | AF2-032 C | 80/20 | 1.88 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 0.92 MW | 0.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 934101 | AD2-000 1 | Adder | 2.63 MW | 2.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 944202 | AF1-088 FTWR | 80/20 | 256.43 MW | 256.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 952871 | J757 C | External Queue | 3.17 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953371 | J808 | External Queue | 8.84 MW | 8.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953401 | J811 | External Queue | 16.63 MW | 16.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953431 | J853 | External Queue | 10.98 MW | 10.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953641 | J813 | External Queue | 38.0 MW | 38.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953651 | J815 | External Queue | 26.98 MW | 26.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953671 | J817 | External Queue | 9.65 MW | 9.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 953881 | J848 C | External Queue | 4.42 MW | 4.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 954411 | J912 | External Queue | 12.2 MW | 12.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 954681 | J949 C | External Queue | 27.62 MW | 27.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 954721 | J750 C | External Queue | 1.64 MW | 1.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 954821 | J955 | External Queue | 89.27 MW | 89.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 956151 | J1102 | External Queue | 4.0 MW | 4.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 956281 | J1115 C | External Queue | 1.95 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 956451 | J1139 | External Queue | 8.69 MW | 8.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990056 | J1201 | External Queue | 6.29 MW | 6.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990071 | J1204 | External Queue | 63.47 MW | 63.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990271 | J1263 | External Queue | 98.78 MW | 98.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990856 | J1408 | External Queue | 8.15 MW | 8.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991191 | J1610 | External Queue | 7.47 MW | 7.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991196 | J1626 | External Queue | 25.2 MW | 25.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991266 | J1714 | External Queue | 16.8 MW | 16.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991261 | J1713 C | External Queue | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.37 MW | 0.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.96 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.51 MW | 14.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 59.93 MW | 59.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 63.08 MW | 63.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.58 MW | 0.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 11.66 MW | 11.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.44 MW | 1.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 13.12 MW | 13.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.31 MW | 7.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.71 MW | 1.71 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 6.93 MW | 6.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 46.41 MW | 46.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964581 | AG1-321 C O1 | 50/50 | 63.38 MW | 63.38 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964582 | AG1-321 E O1 | 50/50 | 36.9 MW | 36.9 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965091 | AG1-374 C | 50/50 | 73.7 MW | 73.7 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 49.13 MW | 49.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 2.02 MW | 2.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C | 50/50 | 18.24 MW | 18.24 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E | 50/50 | 85.41 MW | 85.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 | 50/50 | 51.83 MW | 51.83 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 | 50/50 | 51.83 MW | 51.83 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 | 50/50 | 34.55 MW | 34.55 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.46 MW | 2.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.68 MW | 3.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 64.85 MW | 64.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 64.85 MW | 64.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 6.93 MW | 6.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 46.41 MW | 46.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.01 MW | 9.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936771 | AD2-100 C | 50/50 | 24.95 MW | 24.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936772 | AD2-100 E | 50/50 | 16.63 MW | 16.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936971 | AD2-131 C | 50/50 | 1.64 MW | 1.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936972 | AD2-131 E | 50/50 | 8.26 MW | 8.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 8.58 MW | 8.58 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 57.41 MW | 57.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942481 | AE2-261 C | 50/50 | 36.7 MW | 36.7 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942482 | AE2-261 E | 50/50 | 24.47 MW | 24.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 11.16 MW | 11.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.73 MW | 7.73 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959341 | AF2-225 C | 50/50 | 27.72 MW | 27.72 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959342 | AF2-225 E | 50/50 | 38.27 MW | 38.27 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.19 MW | 8.19 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.28 MW | 12.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.53 MW | 2.53 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.89 MW | 3.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.19 MW | 8.19 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.28 MW | 12.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274650 | KINCAID ;1U | 50/50 | 19.6 MW | 19.6 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274651 | KINCAID ;2U | 50/50 | 19.59 MW | 19.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 2.43 MW | 2.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 2.5 MW | 2.5 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274863 | CAYUGA RI;1U | 50/50 | 2.33 MW | 2.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274864 | CAYUGA RI;2U | 50/50 | 2.33 MW | 2.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 2.25 MW | 2.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 1.95 MW | 1.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 12.79 MW | 12.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 45.91 MW | 45.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293777 | CAYUG;1U E | 50/50 | 73.14 MW | 73.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293778 | CAYUG;2U E | 50/50 | 73.14 MW | 73.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 75.48 MW | 75.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 76.55 MW | 76.55 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 2.44 MW | 2.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 95.69 MW | 95.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 7.16 MW | 7.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 43.37 MW | 43.37 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939401 | AE1-172 C O1 | 50/50 | 30.02 MW | 30.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939402 | AE1-172 E O1 | 50/50 | 140.85 MW | 140.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939741 | AE1-205 C O1 | 50/50 | 36.95 MW | 36.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939742 | AE1-205 E O1 | 50/50 | 51.03 MW | 51.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 22.0 MW | 22.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 6.3 MW | 6.3 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 29.48 MW | 29.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957381 | AF2-032 C | 50/50 | 2.81 MW | 2.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 1.32 MW | 1.32 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.01 MW | 9.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.26 MW | 2.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.51 MW | 4.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952651 | J756 C | External Queue | 4.84 MW | 4.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952652 | J756 E | External Queue | 26.21 MW | 26.21 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952871 | J757 C | External Queue | 5.98 MW | 5.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952872 | J757 E | External Queue | 32.33 MW | 32.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953401 | J811 | External Queue | 11.09 MW | 11.09 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953651 | J815 | External Queue | 39.31 MW | 39.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953741 | J826 C | External Queue | 3.16 MW | 3.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953742 | J826 E | External Queue | 17.1 MW | 17.1 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953851 | J845 C | External Queue | 3.11 MW | 3.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953852 | J845 E | External Queue | 16.83 MW | 16.83 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953881 | J848 C | External Queue | 6.01 MW | 6.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953882 | J848 E | External Queue | 32.53 MW | 32.53 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954411 | J912 | External Queue | 14.81 MW | 14.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954721 | J750 C | External Queue | 3.98 MW | 3.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954722 | J750 E | External Queue | 21.54 MW | 21.54 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954821 | J955 | External Queue | 187.12 MW | 187.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 30.38 MW | 30.38 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.37 MW | 2.37 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 12.84 MW | 12.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956151 | J1102 | External Queue | 12.11 MW | 12.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.66 MW | 7.66 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 41.46 MW | 41.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956451 | J1139 | External Queue | 16.12 MW | 16.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 5.18 MW | 5.18 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990672 | J1360 E | External Queue | 58.47 MW | 58.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 16.3 MW | 16.3 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991191 | J1610 | External Queue | 16.68 MW | 16.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991196 | J1626 | External Queue | 16.81 MW | 16.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 C | External Queue | 12.89 MW | 12.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991237 | J1676 E | External Queue | 69.75 MW | 69.75 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991266 | J1714 | External Queue | 11.2 MW | 11.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 C | External Queue | 3.92 MW | 3.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991262 | J1713 E | External Queue | 21.21 MW | 21.21 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.84 MW | 0.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.95 MW | 0.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.41 MW | 1.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 22.42 MW | 22.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 50.04 MW | 50.04 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.02 MW | 2.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.4 MW | 7.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.65 MW | 1.65 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.35 MW | 3.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.45 MW | 0.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.54 MW | 5.54 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.42 MW | 5.42 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963831 | AG1-236 C | 50/50 | 6.78 MW | 6.78 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963832 | AG1-236 E | 50/50 | 45.39 MW | 45.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964581 | AG1-321 C O1 | 50/50 | 63.1 MW | 63.1 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964582 | AG1-321 E O1 | 50/50 | 36.74 MW | 36.74 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965091 | AG1-374 C | 50/50 | 73.06 MW | 73.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965092 | AG1-374 E | 50/50 | 48.71 MW | 48.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965331 | AG1-398 | 50/50 | 1.98 MW | 1.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965341 | AG1-399 C | 50/50 | 18.01 MW | 18.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965342 | AG1-399 E | 50/50 | 84.31 MW | 84.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965351 | AG1-400 | 50/50 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965371 | AG1-402 | 50/50 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965391 | AG1-404 | 50/50 | 34.11 MW | 34.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965911 | AG1-460 C | 50/50 | 2.38 MW | 2.38 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965912 | AG1-460 E | 50/50 | 3.56 MW | 3.56 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290261 | S-027 E | 50/50 | 64.29 MW | 64.29 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290265 | S-028 E | 50/50 | 64.29 MW | 64.29 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925771 | AC1-053 C | 50/50 | 6.78 MW | 6.78 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925772 | AC1-053 E | 50/50 | 45.39 MW | 45.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 935141 | AD1-148 | 50/50 | 8.78 MW | 8.78 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936771 | AD2-100 C | 50/50 | 24.14 MW | 24.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936772 | AD2-100 E | 50/50 | 16.1 MW | 16.1 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936971 | AD2-131 C | 50/50 | 1.59 MW | 1.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936972 | AD2-131 E | 50/50 | 7.99 MW | 7.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942111 | AE2-223 C | 50/50 | 8.52 MW | 8.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942112 | AE2-223 E | 50/50 | 57.01 MW | 57.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942481 | AE2-261 C | 50/50 | 35.52 MW | 35.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942482 | AE2-261 E | 50/50 | 23.68 MW | 23.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945871 | AF1-252 O1 | 50/50 | 10.79 MW | 10.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945881 | AF1-253 | 50/50 | 7.47 MW | 7.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959341 | AF2-225 C | 50/50 | 27.52 MW | 27.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959342 | AF2-225 E | 50/50 | 38.0 MW | 38.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959611 | AF2-252 C | 50/50 | 8.12 MW | 8.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959612 | AF2-252 E | 50/50 | 12.18 MW | 12.18 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960141 | AF2-305 | 50/50 | 2.48 MW | 2.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960261 | AF2-317 | 50/50 | 3.79 MW | 3.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960611 | AF2-352 C | 50/50 | 8.12 MW | 8.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960612 | AF2-352 E | 50/50 | 12.18 MW | 12.18 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274650 | KINCAID ;1U | 50/50 | 18.97 MW | 18.97 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274651 | KINCAID ;2U | 50/50 | 18.97 MW | 18.97 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274853 | TWINGROVE;U1 | 50/50 | 2.41 MW | 2.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274854 | TWINGROVE;U2 | 50/50 | 2.48 MW | 2.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274863 | CAYUGA RI;1U | 50/50 | 2.33 MW | 2.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274864 | CAYUGA RI;2U | 50/50 | 2.33 MW | 2.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274880 | RADFORD R;1U | 50/50 | 2.21 MW | 2.21 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274889 | BRIGHTSTK;1U | 50/50 | 1.93 MW | 1.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276615 | W2-048 GEN | 50/50 | 12.47 MW | 12.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276621 | X2-022 GEN | 50/50 | 44.76 MW | 44.76 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293777 | CAYUG;1U E | 50/50 | 73.06 MW | 73.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293778 | CAYUG;2U E | 50/50 | 73.06 MW | 73.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293798 | W4-005 E | 50/50 | 74.12 MW | 74.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 917502 | Z2-087 E | 50/50 | 76.01 MW | 76.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924041 | AB2-047 C O1 | 50/50 | 2.42 MW | 2.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924042 | AB2-047 E O1 | 50/50 | 95.01 MW | 95.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924261 | AB2-070 C O1 | 50/50 | 7.01 MW | 7.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924262 | AB2-070 E O1 | 50/50 | 42.48 MW | 42.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939401 | AE1-172 C O1 | 50/50 | 30.03 MW | 30.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939402 | AE1-172 E O1 | 50/50 | 140.9 MW | 140.9 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939741 | AE1-205 C O1 | 50/50 | 36.69 MW | 36.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939742 | AE1-205 E O1 | 50/50 | 50.67 MW | 50.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 941731 | AE2-173 O1 | 50/50 | 21.84 MW | 21.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944221 | AF1-090 C O1 | 50/50 | 6.09 MW | 6.09 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944222 | AF1-090 E O1 | 50/50 | 28.49 MW | 28.49 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957381 | AF2-032 C | 50/50 | 2.73 MW | 2.73 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957382 | AF2-032 E | 50/50 | 1.28 MW | 1.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958023 | AF2-096 BAT | 50/50 | 8.75 MW | 8.75 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960603 | AF2-351 BAT | 50/50 | 2.18 MW | 2.18 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958013 | AF2-095 BAT | 50/50 | 4.36 MW | 4.36 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952651 | J756 C | External Queue | 4.53 MW | 4.53 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952652 | J756 E | External Queue | 24.49 MW | 24.49 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952871 | J757 C | External Queue | 5.57 MW | 5.57 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952872 | J757 E | External Queue | 30.14 MW | 30.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953401 | J811 | External Queue | 10.84 MW | 10.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953651 | J815 | External Queue | 38.25 MW | 38.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953741 | J826 C | External Queue | 3.12 MW | 3.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953742 | J826 E | External Queue | 16.89 MW | 16.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953851 | J845 C | External Queue | 3.08 MW | 3.08 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953852 | J845 E | External Queue | 16.65 MW | 16.65 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953881 | J848 C | External Queue | 5.87 MW | 5.87 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953882 | J848 E | External Queue | 31.74 MW | 31.74 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954411 | J912 | External Queue | 14.46 MW | 14.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954721 | J750 C | External Queue | 3.82 MW | 3.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954722 | J750 E | External Queue | 20.65 MW | 20.65 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954821 | J955 | External Queue | 182.06 MW | 182.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 955402 | J1022 E | External Queue | 30.01 MW | 30.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956151 | J1102 | External Queue | 11.51 MW | 11.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956281 | J1115 C | External Queue | 7.56 MW | 7.56 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956282 | J1115 E | External Queue | 40.92 MW | 40.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956451 | J1139 | External Queue | 15.98 MW | 15.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990056 | J1201 | External Queue | 5.05 MW | 5.05 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990672 | J1360 E | External Queue | 57.81 MW | 57.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990856 | J1408 | External Queue | 15.71 MW | 15.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991191 | J1610 | External Queue | 16.01 MW | 16.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991196 | J1626 | External Queue | 16.42 MW | 16.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991236 | J1676 C | External Queue | 12.76 MW | 12.76 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991237 | J1676 E | External Queue | 69.03 MW | 69.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991266 | J1714 | External Queue | 10.95 MW | 10.95 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991261 | J1713 C | External Queue | 3.85 MW | 3.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991262 | J1713 E | External Queue | 20.81 MW | 20.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.8 MW | 0.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.92 MW | 0.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.33 MW | 1.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.2 MW | 21.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 46.96 MW | 46.96 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.2 MW | 1.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.94 MW | 1.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.85 MW | 6.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.59 MW | 1.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.44 MW | 2.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.43 MW | 0.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.2 MW | 5.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.22 MW | 5.22 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 6.93 MW | 6.93 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 46.41 MW | 46.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964581 | AG1-321 C O1 | 50/50 | 63.38 MW | 63.38 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964582 | AG1-321 E O1 | 50/50 | 36.9 MW | 36.9 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965091 | AG1-374 C | 50/50 | 73.7 MW | 73.7 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 49.13 MW | 49.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 2.02 MW | 2.02 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C | 50/50 | 18.24 MW | 18.24 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E | 50/50 | 85.41 MW | 85.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 | 50/50 | 51.83 MW | 51.83 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 | 50/50 | 51.83 MW | 51.83 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 | 50/50 | 34.55 MW | 34.55 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.46 MW | 2.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.68 MW | 3.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 64.85 MW | 64.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 64.85 MW | 64.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 6.93 MW | 6.93 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 46.41 MW | 46.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.01 MW | 9.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936771 | AD2-100 C | 50/50 | 24.95 MW | 24.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936772 | AD2-100 E | 50/50 | 16.63 MW | 16.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936971 | AD2-131 C | 50/50 | 1.64 MW | 1.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936972 | AD2-131 E | 50/50 | 8.26 MW | 8.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 8.58 MW | 8.58 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 57.41 MW | 57.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942481 | AE2-261 C | 50/50 | 36.7 MW | 36.7 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942482 | AE2-261 E | 50/50 | 24.47 MW | 24.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 11.16 MW | 11.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.73 MW | 7.73 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959341 | AF2-225 C | 50/50 | 27.72 MW | 27.72 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959342 | AF2-225 E | 50/50 | 38.27 MW | 38.27 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.19 MW | 8.19 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.28 MW | 12.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.53 MW | 2.53 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.89 MW | 3.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.19 MW | 8.19 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.28 MW | 12.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274650 | KINCAID ;1U | 50/50 | 19.6 MW | 19.6 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274651 | KINCAID ;2U | 50/50 | 19.59 MW | 19.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 2.43 MW | 2.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 2.5 MW | 2.5 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274863 | CAYUGA RI;1U | 50/50 | 2.33 MW | 2.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274864 | CAYUGA RI;2U | 50/50 | 2.33 MW | 2.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 2.25 MW | 2.25 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 1.95 MW | 1.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 12.79 MW | 12.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 45.91 MW | 45.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293777 | CAYUG;1U E | 50/50 | 73.14 MW | 73.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293778 | CAYUG;2U E | 50/50 | 73.14 MW | 73.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 75.48 MW | 75.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 76.55 MW | 76.55 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 2.44 MW | 2.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 95.69 MW | 95.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 7.16 MW | 7.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 43.37 MW | 43.37 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939741 | AE1-205 C O1 | 50/50 | 36.95 MW | 36.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939742 | AE1-205 E O1 | 50/50 | 51.03 MW | 51.03 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 22.0 MW | 22.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 6.3 MW | 6.3 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 29.48 MW | 29.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957381 | AF2-032 C | 50/50 | 2.81 MW | 2.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 1.32 MW | 1.32 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.01 MW | 9.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.26 MW | 2.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.51 MW | 4.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952651 | J756 C | External Queue | 4.84 MW | 4.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952652 | J756 E | External Queue | 26.21 MW | 26.21 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952871 | J757 C | External Queue | 5.98 MW | 5.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952872 | J757 E | External Queue | 32.33 MW | 32.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953401 | J811 | External Queue | 11.09 MW | 11.09 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953651 | J815 | External Queue | 39.31 MW | 39.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953741 | J826 C | External Queue | 3.16 MW | 3.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953742 | J826 E | External Queue | 17.1 MW | 17.1 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953851 | J845 C | External Queue | 3.11 MW | 3.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953852 | J845 E | External Queue | 16.83 MW | 16.83 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953881 | J848 C | External Queue | 6.01 MW | 6.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953882 | J848 E | External Queue | 32.53 MW | 32.53 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954411 | J912 | External Queue | 14.81 MW | 14.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954721 | J750 C | External Queue | 3.98 MW | 3.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954722 | J750 E | External Queue | 21.54 MW | 21.54 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954821 | J955 | External Queue | 187.12 MW | 187.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 30.38 MW | 30.38 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.37 MW | 2.37 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 12.84 MW | 12.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956151 | J1102 | External Queue | 12.11 MW | 12.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.66 MW | 7.66 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 41.46 MW | 41.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956451 | J1139 | External Queue | 16.12 MW | 16.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 5.18 MW | 5.18 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990672 | J1360 E | External Queue | 58.47 MW | 58.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 16.3 MW | 16.3 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991191 | J1610 | External Queue | 16.68 MW | 16.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991196 | J1626 | External Queue | 16.81 MW | 16.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991216 | J1653 | External Queue | 15.06 MW | 15.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 C | External Queue | 12.89 MW | 12.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991237 | J1676 E | External Queue | 69.75 MW | 69.75 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991266 | J1714 | External Queue | 11.2 MW | 11.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 C | External Queue | 1.57 MW | 1.57 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991277 | J1725 E | External Queue | 8.48 MW | 8.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 C | External Queue | 3.92 MW | 3.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991262 | J1713 E | External Queue | 21.21 MW | 21.21 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.84 MW | 0.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.95 MW | 0.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.41 MW | 1.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 22.42 MW | 22.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 50.04 MW | 50.04 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.26 MW | 1.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.02 MW | 2.02 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.4 MW | 7.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.65 MW | 1.65 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.35 MW | 3.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.45 MW | 0.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.54 MW | 5.54 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.42 MW | 5.42 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963831 | AG1-236 C | 50/50 | 6.78 MW | 6.78 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963832 | AG1-236 E | 50/50 | 45.39 MW | 45.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964581 | AG1-321 C O1 | 50/50 | 63.1 MW | 63.1 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964582 | AG1-321 E O1 | 50/50 | 36.74 MW | 36.74 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965091 | AG1-374 C | 50/50 | 73.06 MW | 73.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965092 | AG1-374 E | 50/50 | 48.71 MW | 48.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965331 | AG1-398 | 50/50 | 1.98 MW | 1.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965341 | AG1-399 C | 50/50 | 18.01 MW | 18.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965342 | AG1-399 E | 50/50 | 84.31 MW | 84.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965351 | AG1-400 | 50/50 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965371 | AG1-402 | 50/50 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965391 | AG1-404 | 50/50 | 34.11 MW | 34.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965911 | AG1-460 C | 50/50 | 2.38 MW | 2.38 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965912 | AG1-460 E | 50/50 | 3.56 MW | 3.56 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290261 | S-027 E | 50/50 | 64.29 MW | 64.29 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290265 | S-028 E | 50/50 | 64.29 MW | 64.29 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925771 | AC1-053 C | 50/50 | 6.78 MW | 6.78 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925772 | AC1-053 E | 50/50 | 45.39 MW | 45.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 935141 | AD1-148 | 50/50 | 8.78 MW | 8.78 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936771 | AD2-100 C | 50/50 | 24.14 MW | 24.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936772 | AD2-100 E | 50/50 | 16.1 MW | 16.1 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936971 | AD2-131 C | 50/50 | 1.59 MW | 1.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936972 | AD2-131 E | 50/50 | 7.99 MW | 7.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942111 | AE2-223 C | 50/50 | 8.52 MW | 8.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942112 | AE2-223 E | 50/50 | 57.01 MW | 57.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942481 | AE2-261 C | 50/50 | 35.52 MW | 35.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942482 | AE2-261 E | 50/50 | 23.68 MW | 23.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945871 | AF1-252 O1 | 50/50 | 10.79 MW | 10.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945881 | AF1-253 | 50/50 | 7.47 MW | 7.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959341 | AF2-225 C | 50/50 | 27.52 MW | 27.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959342 | AF2-225 E | 50/50 | 38.0 MW | 38.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959611 | AF2-252 C | 50/50 | 8.12 MW | 8.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959612 | AF2-252 E | 50/50 | 12.18 MW | 12.18 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960141 | AF2-305 | 50/50 | 2.48 MW | 2.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960261 | AF2-317 | 50/50 | 3.79 MW | 3.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960611 | AF2-352 C | 50/50 | 8.12 MW | 8.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960612 | AF2-352 E | 50/50 | 12.18 MW | 12.18 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274650 | KINCAID ;1U | 50/50 | 18.97 MW | 18.97 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274651 | KINCAID ;2U | 50/50 | 18.97 MW | 18.97 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274853 | TWINGROVE;U1 | 50/50 | 2.41 MW | 2.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274854 | TWINGROVE;U2 | 50/50 | 2.48 MW | 2.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274863 | CAYUGA RI;1U | 50/50 | 2.33 MW | 2.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274864 | CAYUGA RI;2U | 50/50 | 2.33 MW | 2.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274880 | RADFORD R;1U | 50/50 | 2.21 MW | 2.21 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274889 | BRIGHTSTK;1U | 50/50 | 1.93 MW | 1.93 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276615 | W2-048 GEN | 50/50 | 12.47 MW | 12.47 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276621 | X2-022 GEN | 50/50 | 44.76 MW | 44.76 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293777 | CAYUG;1U E | 50/50 | 73.06 MW | 73.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293778 | CAYUG;2U E | 50/50 | 73.06 MW | 73.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293798 | W4-005 E | 50/50 | 74.12 MW | 74.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 917502 | Z2-087 E | 50/50 | 76.01 MW | 76.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924041 | AB2-047 C O1 | 50/50 | 2.42 MW | 2.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924042 | AB2-047 E O1 | 50/50 | 95.01 MW | 95.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924261 | AB2-070 C O1 | 50/50 | 7.01 MW | 7.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924262 | AB2-070 E O1 | 50/50 | 42.48 MW | 42.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939741 | AE1-205 C O1 | 50/50 | 36.69 MW | 36.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939742 | AE1-205 E O1 | 50/50 | 50.67 MW | 50.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 941731 | AE2-173 O1 | 50/50 | 21.84 MW | 21.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944221 | AF1-090 C O1 | 50/50 | 6.09 MW | 6.09 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944222 | AF1-090 E O1 | 50/50 | 28.49 MW | 28.49 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957381 | AF2-032 C | 50/50 | 2.73 MW | 2.73 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957382 | AF2-032 E | 50/50 | 1.28 MW | 1.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958023 | AF2-096 BAT | 50/50 | 8.75 MW | 8.75 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960603 | AF2-351 BAT | 50/50 | 2.18 MW | 2.18 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958013 | AF2-095 BAT | 50/50 | 4.36 MW | 4.36 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952651 | J756 C | External Queue | 4.53 MW | 4.53 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952652 | J756 E | External Queue | 24.49 MW | 24.49 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952871 | J757 C | External Queue | 5.57 MW | 5.57 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952872 | J757 E | External Queue | 30.14 MW | 30.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953401 | J811 | External Queue | 10.84 MW | 10.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953651 | J815 | External Queue | 38.25 MW | 38.25 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953741 | J826 C | External Queue | 3.12 MW | 3.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953742 | J826 E | External Queue | 16.89 MW | 16.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953851 | J845 C | External Queue | 3.08 MW | 3.08 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953852 | J845 E | External Queue | 16.65 MW | 16.65 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953881 | J848 C | External Queue | 5.87 MW | 5.87 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953882 | J848 E | External Queue | 31.74 MW | 31.74 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954411 | J912 | External Queue | 14.46 MW | 14.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954721 | J750 C | External Queue | 3.82 MW | 3.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954722 | J750 E | External Queue | 20.65 MW | 20.65 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954821 | J955 | External Queue | 182.06 MW | 182.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 955402 | J1022 E | External Queue | 30.01 MW | 30.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956151 | J1102 | External Queue | 11.51 MW | 11.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956281 | J1115 C | External Queue | 7.56 MW | 7.56 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956282 | J1115 E | External Queue | 40.92 MW | 40.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956451 | J1139 | External Queue | 15.98 MW | 15.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990056 | J1201 | External Queue | 5.05 MW | 5.05 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990672 | J1360 E | External Queue | 57.81 MW | 57.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990856 | J1408 | External Queue | 15.71 MW | 15.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991191 | J1610 | External Queue | 16.01 MW | 16.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991196 | J1626 | External Queue | 16.42 MW | 16.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991236 | J1676 C | External Queue | 12.76 MW | 12.76 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991237 | J1676 E | External Queue | 69.03 MW | 69.03 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991266 | J1714 | External Queue | 10.95 MW | 10.95 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991261 | J1713 C | External Queue | 3.85 MW | 3.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991262 | J1713 E | External Queue | 20.81 MW | 20.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.8 MW | 0.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.92 MW | 0.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.33 MW | 1.33 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.2 MW | 21.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 46.96 MW | 46.96 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.2 MW | 1.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.94 MW | 1.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.85 MW | 6.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.59 MW | 1.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.44 MW | 2.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.43 MW | 0.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.2 MW | 5.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.22 MW | 5.22 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 6.94 MW | 6.94 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 46.45 MW | 46.45 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964581 | AG1-321 C O1 | 50/50 | 63.41 MW | 63.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 964582 | AG1-321 E O1 | 50/50 | 36.92 MW | 36.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965091 | AG1-374 C | 50/50 | 73.74 MW | 73.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 49.16 MW | 49.16 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 2.02 MW | 2.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C | 50/50 | 18.25 MW | 18.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E | 50/50 | 85.47 MW | 85.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 | 50/50 | 51.86 MW | 51.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 | 50/50 | 51.86 MW | 51.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 | 50/50 | 34.57 MW | 34.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.46 MW | 2.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.69 MW | 3.69 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 64.89 MW | 64.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 64.89 MW | 64.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 6.94 MW | 6.94 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 46.45 MW | 46.45 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.02 MW | 9.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936771 | AD2-100 C | 50/50 | 24.98 MW | 24.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936772 | AD2-100 E | 50/50 | 16.65 MW | 16.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936971 | AD2-131 C | 50/50 | 1.65 MW | 1.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 936972 | AD2-131 E | 50/50 | 8.27 MW | 8.27 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 8.58 MW | 8.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 57.44 MW | 57.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942481 | AE2-261 C | 50/50 | 36.74 MW | 36.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942482 | AE2-261 E | 50/50 | 24.49 MW | 24.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 11.18 MW | 11.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.74 MW | 7.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959341 | AF2-225 C | 50/50 | 27.73 MW | 27.73 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959342 | AF2-225 E | 50/50 | 38.3 MW | 38.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.19 MW | 8.19 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.29 MW | 12.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.54 MW | 2.54 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.89 MW | 3.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.19 MW | 8.19 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.29 MW | 12.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274650 | KINCAID ;1U | 50/50 | 19.62 MW | 19.62 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274651 | KINCAID ;2U | 50/50 | 19.61 MW | 19.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 2.43 MW | 2.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 2.5 MW | 2.5 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 2.25 MW | 2.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 1.95 MW | 1.95 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 12.8 MW | 12.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 45.95 MW | 45.95 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 75.54 MW | 75.54 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 76.59 MW | 76.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 2.44 MW | 2.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 95.74 MW | 95.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 7.17 MW | 7.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 43.41 MW | 43.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939741 | AE1-205 C O1 | 50/50 | 36.98 MW | 36.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939742 | AE1-205 E O1 | 50/50 | 51.06 MW | 51.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 22.01 MW | 22.01 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 6.3 MW | 6.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 29.52 MW | 29.52 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957381 | AF2-032 C | 50/50 | 2.82 MW | 2.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 1.33 MW | 1.33 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 8.99 MW | 8.99 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.25 MW | 2.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.5 MW | 4.5 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952651 | J756 C | External Queue | 4.84 MW | 4.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952652 | J756 E | External Queue | 26.21 MW | 26.21 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952871 | J757 C | External Queue | 5.98 MW | 5.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 952872 | J757 E | External Queue | 32.33 MW | 32.33 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953401 | J811 | External Queue | 11.09 MW | 11.09 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953651 | J815 | External Queue | 39.31 MW | 39.31 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953741 | J826 C | External Queue | 3.16 MW | 3.16 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953742 | J826 E | External Queue | 17.1 MW | 17.1 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953851 | J845 C | External Queue | 3.11 MW | 3.11 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953852 | J845 E | External Queue | 16.83 MW | 16.83 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953881 | J848 C | External Queue | 6.01 MW | 6.01 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 953882 | J848 E | External Queue | 32.53 MW | 32.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954411 | J912 | External Queue | 14.81 MW | 14.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954721 | J750 C | External Queue | 3.98 MW | 3.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954722 | J750 E | External Queue | 21.54 MW | 21.54 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 954821 | J955 | External Queue | 187.12 MW | 187.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 30.38 MW | 30.38 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.37 MW | 2.37 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 12.84 MW | 12.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956151 | J1102 | External Queue | 12.11 MW | 12.11 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.66 MW | 7.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 41.46 MW | 41.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956451 | J1139 | External Queue | 16.12 MW | 16.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 5.18 MW | 5.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990672 | J1360 E | External Queue | 58.47 MW | 58.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 16.3 MW | 16.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991191 | J1610 | External Queue | 16.68 MW | 16.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991196 | J1626 | External Queue | 16.81 MW | 16.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991216 | J1653 | External Queue | 15.06 MW | 15.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 C | External Queue | 12.89 MW | 12.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991237 | J1676 E | External Queue | 69.75 MW | 69.75 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991266 | J1714 | External Queue | 11.2 MW | 11.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 C | External Queue | 1.57 MW | 1.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991277 | J1725 E | External Queue | 8.48 MW | 8.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 C | External Queue | 3.92 MW | 3.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991262 | J1713 E | External Queue | 21.21 MW | 21.21 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.85 MW | 0.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.98 MW | 0.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.42 MW | 1.42 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 22.67 MW | 22.67 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 50.25 MW | 50.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.28 MW | 1.28 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.07 MW | 2.07 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 7.44 MW | 7.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.66 MW | 1.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.39 MW | 3.39 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.45 MW | 0.45 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.58 MW | 5.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.57 MW | 5.57 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963831 | AG1-236 C | 50/50 | 6.79 MW | 6.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 963832 | AG1-236 E | 50/50 | 45.43 MW | 45.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964581 | AG1-321 C O1 | 50/50 | 63.13 MW | 63.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 964582 | AG1-321 E O1 | 50/50 | 36.76 MW | 36.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965091 | AG1-374 C | 50/50 | 73.1 MW | 73.1 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965092 | AG1-374 E | 50/50 | 48.74 MW | 48.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965331 | AG1-398 | 50/50 | 1.98 MW | 1.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965341 | AG1-399 C | 50/50 | 18.02 MW | 18.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965342 | AG1-399 E | 50/50 | 84.37 MW | 84.37 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965351 | AG1-400 | 50/50 | 51.2 MW | 51.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965371 | AG1-402 | 50/50 | 51.2 MW | 51.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965391 | AG1-404 | 50/50 | 34.13 MW | 34.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965911 | AG1-460 C | 50/50 | 2.38 MW | 2.38 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 965912 | AG1-460 E | 50/50 | 3.57 MW | 3.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290261 | S-027 E | 50/50 | 64.33 MW | 64.33 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 290265 | S-028 E | 50/50 | 64.33 MW | 64.33 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925771 | AC1-053 C | 50/50 | 6.79 MW | 6.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 925772 | AC1-053 E | 50/50 | 45.43 MW | 45.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 935141 | AD1-148 | 50/50 | 8.79 MW | 8.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936771 | AD2-100 C | 50/50 | 24.17 MW | 24.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936772 | AD2-100 E | 50/50 | 16.12 MW | 16.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936971 | AD2-131 C | 50/50 | 1.59 MW | 1.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 936972 | AD2-131 E | 50/50 | 8.0 MW | 8.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942111 | AE2-223 C | 50/50 | 8.52 MW | 8.52 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942112 | AE2-223 E | 50/50 | 57.04 MW | 57.04 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942481 | AE2-261 C | 50/50 | 35.56 MW | 35.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 942482 | AE2-261 E | 50/50 | 23.71 MW | 23.71 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945871 | AF1-252 O1 | 50/50 | 10.8 MW | 10.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 945881 | AF1-253 | 50/50 | 7.48 MW | 7.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959341 | AF2-225 C | 50/50 | 27.54 MW | 27.54 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959342 | AF2-225 E | 50/50 | 38.02 MW | 38.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959611 | AF2-252 C | 50/50 | 8.12 MW | 8.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 959612 | AF2-252 E | 50/50 | 12.18 MW | 12.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960141 | AF2-305 | 50/50 | 2.48 MW | 2.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960261 | AF2-317 | 50/50 | 3.8 MW | 3.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960611 | AF2-352 C | 50/50 | 8.12 MW | 8.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960612 | AF2-352 E | 50/50 | 12.18 MW | 12.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274650 | KINCAID ;1U | 50/50 | 19.0 MW | 19.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274651 | KINCAID ;2U | 50/50 | 18.99 MW | 18.99 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274853 | TWINGROVE;U1 | 50/50 | 2.41 MW | 2.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274854 | TWINGROVE;U2 | 50/50 | 2.48 MW | 2.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274880 | RADFORD R;1U | 50/50 | 2.21 MW | 2.21 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 274889 | BRIGHTSTK;1U | 50/50 | 1.94 MW | 1.94 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276615 | W2-048 GEN | 50/50 | 12.48 MW | 12.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 276621 | X2-022 GEN | 50/50 | 44.8 MW | 44.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 293798 | W4-005 E | 50/50 | 74.18 MW | 74.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 917502 | Z2-087 E | 50/50 | 76.05 MW | 76.05 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924041 | AB2-047 C O1 | 50/50 | 2.42 MW | 2.42 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924042 | AB2-047 E O1 | 50/50 | 95.06 MW | 95.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924261 | AB2-070 C O1 | 50/50 | 7.02 MW | 7.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 924262 | AB2-070 E O1 | 50/50 | 42.51 MW | 42.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939741 | AE1-205 C O1 | 50/50 | 36.71 MW | 36.71 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 939742 | AE1-205 E O1 | 50/50 | 50.7 MW | 50.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 941731 | AE2-173 O1 | 50/50 | 21.85 MW | 21.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944221 | AF1-090 C O1 | 50/50 | 6.09 MW | 6.09 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 944222 | AF1-090 E O1 | 50/50 | 28.53 MW | 28.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957381 | AF2-032 C | 50/50 | 2.73 MW | 2.73 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 957382 | AF2-032 E | 50/50 | 1.28 MW | 1.28 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958023 | AF2-096 BAT | 50/50 | 8.73 MW | 8.73 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 960603 | AF2-351 BAT | 50/50 | 2.17 MW | 2.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 958013 | AF2-095 BAT | 50/50 | 4.35 MW | 4.35 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952651 | J756 C | External Queue | 4.53 MW | 4.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952652 | J756 E | External Queue | 24.49 MW | 24.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952871 | J757 C | External Queue | 5.57 MW | 5.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 952872 | J757 E | External Queue | 30.14 MW | 30.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953401 | J811 | External Queue | 10.84 MW | 10.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953651 | J815 | External Queue | 38.25 MW | 38.25 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953741 | J826 C | External Queue | 3.12 MW | 3.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953742 | J826 E | External Queue | 16.89 MW | 16.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953851 | J845 C | External Queue | 3.08 MW | 3.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953852 | J845 E | External Queue | 16.65 MW | 16.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953881 | J848 C | External Queue | 5.87 MW | 5.87 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 953882 | J848 E | External Queue | 31.74 MW | 31.74 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954411 | J912 | External Queue | 14.46 MW | 14.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954721 | J750 C | External Queue | 3.82 MW | 3.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954722 | J750 E | External Queue | 20.65 MW | 20.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 954821 | J955 | External Queue | 182.06 MW | 182.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 955402 | J1022 E | External Queue | 30.01 MW | 30.01 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956151 | J1102 | External Queue | 11.51 MW | 11.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956281 | J1115 C | External Queue | 7.56 MW | 7.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956282 | J1115 E | External Queue | 40.92 MW | 40.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 956451 | J1139 | External Queue | 15.98 MW | 15.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990056 | J1201 | External Queue | 5.05 MW | 5.05 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990672 | J1360 E | External Queue | 57.81 MW | 57.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 990856 | J1408 | External Queue | 15.71 MW | 15.71 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991191 | J1610 | External Queue | 16.01 MW | 16.01 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991196 | J1626 | External Queue | 16.42 MW | 16.42 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991236 | J1676 C | External Queue | 12.76 MW | 12.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991237 | J1676 E | External Queue | 69.03 MW | 69.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991266 | J1714 | External Queue | 10.95 MW | 10.95 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991261 | J1713 C | External Queue | 3.85 MW | 3.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | 991262 | J1713 E | External Queue | 20.81 MW | 20.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.81 MW | 0.81 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.95 MW | 0.95 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.34 MW | 1.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 21.44 MW | 21.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 47.17 MW | 47.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.21 MW | 1.21 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 2.0 MW | 2.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 6.89 MW | 6.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.05 MW | 0.05 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.6 MW | 1.6 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.48 MW | 2.48 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.43 MW | 0.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 5.24 MW | 5.24 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT14-15 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 5.37 MW | 5.37 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961651 | AG1-005 C O1 | Adder | 12.31 MW | 10.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961652 | AG1-005 E O1 | Adder | 8.21 MW | 6.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962721 | AG1-121 C O1 | Adder | 4.22 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962722 | AG1-121 E O1 | Adder | 19.72 MW | 16.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963831 | AG1-236 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963832 | AG1-236 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964581 | AG1-321 C O1 | Adder | 11.78 MW | 10.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 964582 | AG1-321 E O1 | Adder | 6.86 MW | 5.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966821 | AG1-553 C O1 | Adder | 18.91 MW | 16.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966822 | AG1-553 E O1 | Adder | 3.81 MW | 3.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965091 | AG1-374 C | 50/50 | 21.96 MW | 21.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965092 | AG1-374 E | 50/50 | 14.64 MW | 14.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965331 | AG1-398 | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965341 | AG1-399 C | 50/50 | 7.26 MW | 7.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965342 | AG1-399 E | 50/50 | 33.99 MW | 33.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965351 | AG1-400 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965371 | AG1-402 | 50/50 | 20.62 MW | 20.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965391 | AG1-404 | 50/50 | 13.75 MW | 13.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965671 | AG1-435 C O1 | Adder | 2.87 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965672 | AG1-435 E O1 | Adder | 13.45 MW | 11.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965911 | AG1-460 C | 50/50 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965912 | AG1-460 E | 50/50 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965931 | AG1-462 C O1 | Adder | 12.24 MW | 10.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965932 | AG1-462 E O1 | Adder | 8.16 MW | 6.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290261 | S-027 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290265 | S-028 E | 50/50 | 19.32 MW | 19.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 295111 | SUBLETTE E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919581 | AA2-030 C | Adder | 11.31 MW | 9.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925771 | AC1-053 C | 50/50 | 3.97 MW | 3.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925772 | AC1-053 E | 50/50 | 26.57 MW | 26.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926821 | AC1-168 C O1 | Adder | 0.79 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926822 | AC1-168 E O1 | Adder | 5.29 MW | 4.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 927202 | AC1-214 E O1 | Adder | 4.96 MW | 4.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934051 | AD1-031 C O1 | Adder | 2.19 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934052 | AD1-031 E O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 935141 | AD1-148 | 50/50 | 5.71 MW | 5.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936771 | AD2-100 C | 50/50 | 22.42 MW | 22.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936772 | AD2-100 E | 50/50 | 14.95 MW | 14.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936971 | AD2-131 C | 50/50 | 1.48 MW | 1.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 936972 | AD2-131 E | 50/50 | 7.42 MW | 7.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942111 | AE2-223 C | 50/50 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942112 | AE2-223 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942481 | AE2-261 C | 50/50 | 31.04 MW | 31.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942482 | AE2-261 E | 50/50 | 20.7 MW | 20.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945871 | AF1-252 O1 | 50/50 | 11.99 MW | 11.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945881 | AF1-253 | 50/50 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946542 | AF1-318 E O1 | Adder | 20.29 MW | 17.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958911 | AF2-182 C | Adder | 12.64 MW | 10.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958912 | AF2-182 E | Adder | 8.43 MW | 7.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958921 | AF2-183 C | Adder | 2.25 MW | 1.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958922 | AF2-183 E | Adder | 3.37 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959341 | AF2-225 C | 50/50 | 7.12 MW | 7.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959342 | AF2-225 E | 50/50 | 9.83 MW | 9.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959611 | AF2-252 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959612 | AF2-252 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960141 | AF2-305 | 50/50 | 1.38 MW | 1.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960261 | AF2-317 | 50/50 | 2.47 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960611 | AF2-352 C | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960612 | AF2-352 E | 50/50 | 3.66 MW | 3.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961011 | AF2-392 C O1 | Adder | 2.52 MW | 2.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961012 | AF2-392 E O1 | Adder | 11.79 MW | 10.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961021 | AF2-393 O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961031 | AF2-394 O1 | Adder | 2.86 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274650 | KINCAID ;1U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274651 | KINCAID ;2U | 50/50 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274859 | EASYR;U1 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274860 | EASYR;U2 E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274880 | RADFORD R;1U | 50/50 | 1.17 MW | 1.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276615 | W2-048 GEN | 50/50 | 8.12 MW | 8.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276621 | X2-022 GEN | 50/50 | 29.13 MW | 29.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293516 | O-009 E1 | Adder | 6.11 MW | 5.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293517 | O-009 E2 | Adder | 3.11 MW | 2.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293518 | O-009 E3 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293715 | O-029 E | Adder | 6.54 MW | 5.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293716 | O-029 E | Adder | 3.58 MW | 3.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293717 | O-029 E | Adder | 3.29 MW | 2.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293771 | O-035 E | Adder | 4.86 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293777 | CAYUG;1U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293778 | CAYUG;2U E | Adder | 10.16 MW | 8.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293798 | W4-005 E | 50/50 | 39.32 MW | 39.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294401 | BSHIL;1U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 294410 | BSHIL;2U E | Adder | 6.58 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916211 | Z1-072 E | Adder | 3.68 MW | 3.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 917502 | Z2-087 E | 50/50 | 19.65 MW | 19.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924042 | AB2-047 E O1 | 50/50 | 24.56 MW | 24.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924261 | AB2-070 C O1 | 50/50 | 3.91 MW | 3.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924262 | AB2-070 E O1 | 50/50 | 23.69 MW | 23.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925581 | AC1-033 C | Adder | 1.08 MW | 0.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925582 | AC1-033 E | Adder | 7.21 MW | 6.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 930761 | AB1-122 CT1 | Adder | 39.4 MW | 33.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938861 | AE1-114 C O1 | Adder | 2.33 MW | 1.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938862 | AE1-114 E O1 | Adder | 7.94 MW | 6.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939051 | AE1-134 1 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939061 | AE1-134 2 | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939401 | AE1-172 C O1 | Adder | 3.42 MW | 2.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939402 | AE1-172 E O1 | Adder | 16.04 MW | 13.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939741 | AE1-205 C O1 | 50/50 | 9.49 MW | 9.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939742 | AE1-205 E O1 | 50/50 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941731 | AE2-173 O1 | 50/50 | 5.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944221 | AF1-090 C O1 | 50/50 | 6.77 MW | 6.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944222 | AF1-090 E O1 | 50/50 | 31.68 MW | 31.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946151 | AF1-280 C O1 | Adder | 9.62 MW | 8.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946152 | AF1-280 E O1 | Adder | 4.42 MW | 3.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946161 | AF1-281 C O1 | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946162 | AF1-281 E O1 | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946321 | AF1-296 C O1 | Adder | 2.94 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946322 | AF1-296 E O1 | Adder | 13.76 MW | 11.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946541 | AF1-318 C O1 | Adder | 4.33 MW | 3.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957381 | AF2-032 C | 50/50 | 2.33 MW | 2.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957382 | AF2-032 E | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957752 | AF2-069 E | Adder | 0.58 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957761 | AF2-070 C | Adder | 0.25 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957762 | AF2-070 E | Adder | 1.24 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958341 | AF2-128 C O1 | Adder | 1.15 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958342 | AF2-128 E O1 | Adder | 5.38 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990901 | L-005 E | Adder | 10.49 MW | 8.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934101 | AD2-000 1 | Adder | 3.19 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944202 | AF1-088 FTWR | 50/50 | 279.8 MW | 279.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942602 | AE2-276 BAT | 50/50 | 13.99 MW | 13.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941343 | AE2-130 BAT | 50/50 | 31.84 MW | 31.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953371 | J808 | External Queue | 2.59 MW | 2.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953401 | J811 | External Queue | 18.15 MW | 18.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953641 | J813 | External Queue | 40.39 MW | 40.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953651 | J815 | External Queue | 32.21 MW | 32.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953741 | J826 C | External Queue | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953742 | J826 E | External Queue | 9.11 MW | 9.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953881 | J848 C | External Queue | 5.26 MW | 5.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 953882 | J848 E | External Queue | 28.46 MW | 28.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954411 | J912 | External Queue | 14.27 MW | 14.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954681 | J949 C | External Queue | 33.84 MW | 33.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 954821 | J955 | External Queue | 112.27 MW | 112.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955402 | J1022 E | External Queue | 16.19 MW | 16.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956451 | J1139 | External Queue | 20.56 MW | 20.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990056 | J1201 | External Queue | 6.99 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990071 | J1204 | External Queue | 65.14 MW | 65.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990271 | J1263 | External Queue | 107.73 MW | 107.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990672 | J1360 E | External Queue | 35.45 MW | 35.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990856 | J1408 | External Queue | 10.19 MW | 10.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991196 | J1626 | External Queue | 27.49 MW | 27.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991266 | J1714 | External Queue | 18.33 MW | 18.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991261 | J1713 C | External Queue | 3.06 MW | 3.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991262 | J1713 E | External Queue | 16.55 MW | 16.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.68 MW | 2.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.77 MW | 1.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 16.49 MW | 16.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 68.32 MW | 68.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 74.8 MW | 74.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 13.26 MW | 13.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.26 MW | 15.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.41 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.79 MW | 4.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.99 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 8.32 MW | 8.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.01 MW | 2.01 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961651 | AG1-005 C O1 | Adder | 12.53 MW | 10.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961652 | AG1-005 E O1 | Adder | 8.35 MW | 7.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962721 | AG1-121 C O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 962722 | AG1-121 E O1 | Adder | 20.08 MW | 17.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963831 | AG1-236 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 963832 | AG1-236 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964581 | AG1-321 C O1 | Adder | 11.86 MW | 10.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 964582 | AG1-321 E O1 | Adder | 6.91 MW | 5.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966821 | AG1-553 C O1 | Adder | 19.16 MW | 16.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965091 | AG1-374 C | 50/50 | 21.61 MW | 21.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965092 | AG1-374 E | 50/50 | 14.4 MW | 14.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965331 | AG1-398 | 50/50 | 1.07 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965341 | AG1-399 C | 50/50 | 7.08 MW | 7.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965342 | AG1-399 E | 50/50 | 33.15 MW | 33.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965351 | AG1-400 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965371 | AG1-402 | 50/50 | 20.12 MW | 20.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965391 | AG1-404 | 50/50 | 13.41 MW | 13.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965671 | AG1-435 C O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965672 | AG1-435 E O1 | Adder | 13.68 MW | 11.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965911 | AG1-460 C | 50/50 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965912 | AG1-460 E | 50/50 | 3.0 MW | 3.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965931 | AG1-462 C O1 | Adder | 12.4 MW | 10.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 965932 | AG1-462 E O1 | Adder | 8.27 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290261 | S-027 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 290265 | S-028 E | 50/50 | 19.01 MW | 19.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 295111 | SUBLETTE E | Adder | 1.66 MW | 1.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 919581 | AA2-030 C | Adder | 11.63 MW | 9.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925771 | AC1-053 C | 50/50 | 3.85 MW | 3.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925772 | AC1-053 E | 50/50 | 25.74 MW | 25.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926821 | AC1-168 C O1 | Adder | 0.81 MW | 0.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 926822 | AC1-168 E O1 | Adder | 5.42 MW | 4.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 927202 | AC1-214 E O1 | Adder | 5.04 MW | 4.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934051 | AD1-031 C O1 | Adder | 2.22 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934052 | AD1-031 E O1 | Adder | 3.62 MW | 3.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 935141 | AD1-148 | 50/50 | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936511 | AD2-066 C O1 | Adder | 4.85 MW | 4.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936512 | AD2-066 E O1 | Adder | 3.24 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936771 | AD2-100 C | 50/50 | 21.54 MW | 21.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936772 | AD2-100 E | 50/50 | 14.36 MW | 14.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936971 | AD2-131 C | 50/50 | 1.42 MW | 1.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 936972 | AD2-131 E | 50/50 | 7.13 MW | 7.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937311 | AD2-172 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 937312 | AD2-172 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942111 | AE2-223 C | 50/50 | 2.18 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942112 | AE2-223 E | 50/50 | 14.59 MW | 14.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942481 | AE2-261 C | 50/50 | 29.87 MW | 29.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942482 | AE2-261 E | 50/50 | 19.91 MW | 19.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945871 | AF1-252 O1 | 50/50 | 11.48 MW | 11.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 945881 | AF1-253 | 50/50 | 7.95 MW | 7.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946542 | AF1-318 E O1 | Adder | 20.64 MW | 17.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958911 | AF2-182 C | Adder | 13.04 MW | 11.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958912 | AF2-182 E | Adder | 8.69 MW | 7.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958921 | AF2-183 C | Adder | 2.32 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958922 | AF2-183 E | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959101 | AF2-201 C O1 | Adder | 3.57 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959102 | AF2-201 E O1 | Adder | 10.24 MW | 8.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959341 | AF2-225 C | 50/50 | 7.04 MW | 7.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959342 | AF2-225 E | 50/50 | 9.73 MW | 9.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959611 | AF2-252 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 959612 | AF2-252 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960141 | AF2-305 | 50/50 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960261 | AF2-317 | 50/50 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960611 | AF2-352 C | 50/50 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 960612 | AF2-352 E | 50/50 | 3.6 MW | 3.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961011 | AF2-392 C O1 | Adder | 2.59 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961012 | AF2-392 E O1 | Adder | 12.14 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961021 | AF2-393 O1 | Adder | 4.42 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 961031 | AF2-394 O1 | Adder | 2.95 MW | 2.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274650 | KINCAID ;1U | 50/50 | 15.61 MW | 15.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274651 | KINCAID ;2U | 50/50 | 15.6 MW | 15.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274853 | TWINGROVE;U1 | 50/50 | 0.71 MW | 0.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274854 | TWINGROVE;U2 | 50/50 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274859 | EASYR;U1 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274860 | EASYR;U2 E | Adder | 6.88 MW | 5.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274880 | RADFORD R;1U | 50/50 | 1.14 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276615 | W2-048 GEN | 50/50 | 7.85 MW | 7.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 276621 | X2-022 GEN | 50/50 | 28.17 MW | 28.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293516 | O-009 E1 | Adder | 6.27 MW | 5.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293517 | O-009 E2 | Adder | 3.18 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293518 | O-009 E3 | Adder | 3.51 MW | 2.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293715 | O-029 E | Adder | 6.7 MW | 5.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293716 | O-029 E | Adder | 3.67 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293717 | O-029 E | Adder | 3.38 MW | 2.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293771 | O-035 E | Adder | 4.94 MW | 4.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293777 | CAYUG;1U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293778 | CAYUG;2U E | Adder | 10.34 MW | 8.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 293798 | W4-005 E | 50/50 | 38.12 MW | 38.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294401 | BSHIL;1U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294410 | BSHIL;2U E | Adder | 6.68 MW | 5.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 294763 | P-046 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 916211 | Z1-072 E | Adder | 3.74 MW | 3.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 917502 | Z2-087 E | 50/50 | 19.45 MW | 19.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924042 | AB2-047 E O1 | 50/50 | 24.32 MW | 24.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924261 | AB2-070 C O1 | 50/50 | 3.79 MW | 3.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 924262 | AB2-070 E O1 | 50/50 | 22.98 MW | 22.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 925582 | AC1-033 E | Adder | 7.32 MW | 6.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 930761 | AB1-122 CT1 | Adder | 41.0 MW | 34.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938861 | AE1-114 C O1 | Adder | 2.41 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 938862 | AE1-114 E O1 | Adder | 8.22 MW | 6.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939401 | AE1-172 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939402 | AE1-172 E O1 | Adder | 16.51 MW | 14.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939741 | AE1-205 C O1 | 50/50 | 9.39 MW | 9.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 939742 | AE1-205 E O1 | 50/50 | 12.97 MW | 12.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940501 | AE2-035 C | Adder | 1.46 MW | 1.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 940502 | AE2-035 E | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941731 | AE2-173 O1 | 50/50 | 5.59 MW | 5.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944221 | AF1-090 C O1 | 50/50 | 6.48 MW | 6.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944222 | AF1-090 E O1 | 50/50 | 30.33 MW | 30.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946151 | AF1-280 C O1 | Adder | 9.92 MW | 8.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946152 | AF1-280 E O1 | Adder | 4.56 MW | 3.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946162 | AF1-281 E O1 | Adder | 1.23 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946322 | AF1-296 E O1 | Adder | 13.97 MW | 11.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946501 | AF1-314 C | Adder | 2.58 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946502 | AF1-314 E | Adder | 12.12 MW | 10.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 946541 | AF1-318 C O1 | Adder | 4.41 MW | 3.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957381 | AF2-032 C | 50/50 | 2.24 MW | 2.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957382 | AF2-032 E | 50/50 | 1.05 MW | 1.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 957762 | AF2-070 E | Adder | 1.26 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958341 | AF2-128 C O1 | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 958342 | AF2-128 E O1 | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990901 | L-005 E | Adder | 10.63 MW | 9.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 934101 | AD2-000 1 | Adder | 3.32 MW | 2.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 944202 | AF1-088 FTWR | 50/50 | 309.06 MW | 309.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 942602 | AE2-276 BAT | 50/50 | 15.45 MW | 15.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 941343 | AE2-130 BAT | 50/50 | 34.8 MW | 34.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953401 | J811 | External Queue | 17.16 MW | 17.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953641 | J813 | External Queue | 37.62 MW | 37.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953651 | J815 | External Queue | 30.66 MW | 30.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953881 | J848 C | External Queue | 4.99 MW | 4.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 953882 | J848 E | External Queue | 27.02 MW | 27.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954411 | J912 | External Queue | 13.54 MW | 13.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954681 | J949 C | External Queue | 31.51 MW | 31.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 954821 | J955 | External Queue | 84.37 MW | 84.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 956451 | J1139 | External Queue | 19.36 MW | 19.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990056 | J1201 | External Queue | 6.62 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990071 | J1204 | External Queue | 61.78 MW | 61.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990271 | J1263 | External Queue | 101.39 MW | 101.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 990672 | J1360 E | External Queue | 33.75 MW | 33.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991196 | J1626 | External Queue | 26.01 MW | 26.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991266 | J1714 | External Queue | 17.34 MW | 17.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991261 | J1713 C | External Queue | 2.9 MW | 2.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | 991262 | J1713 E | External Queue | 15.68 MW | 15.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.31 MW | 0.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.8 MW | 3.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.57 MW | 13.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 71.43 MW | 71.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 67.74 MW | 67.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.49 MW | 0.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.36 MW | 12.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.6 MW | 1.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.01 MW | 15.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.43 MW | 0.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.1 MW | 5.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.33 MW | 1.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.55 MW | 7.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3130_05EUGENE 345_B2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.1 MW | 2.1 MW |
| Details for BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 963831 | AG1-236 C | 50/50 | 4.24 MW | 4.24 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 963832 | AG1-236 E | 50/50 | 28.39 MW | 28.39 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965091 | AG1-374 C | 50/50 | 102.44 MW | 102.44 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965092 | AG1-374 E | 50/50 | 68.29 MW | 68.29 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965331 | AG1-398 | 50/50 | 1.19 MW | 1.19 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965341 | AG1-399 C | 50/50 | 22.75 MW | 22.75 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965342 | AG1-399 E | 50/50 | 106.53 MW | 106.53 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965351 | AG1-400 | 50/50 | 64.64 MW | 64.64 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965371 | AG1-402 | 50/50 | 64.64 MW | 64.64 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965391 | AG1-404 | 50/50 | 43.1 MW | 43.1 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965911 | AG1-460 C | 50/50 | 1.97 MW | 1.97 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 965912 | AG1-460 E | 50/50 | 2.96 MW | 2.96 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 290261 | S-027 E | 50/50 | 90.15 MW | 90.15 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 290265 | S-028 E | 50/50 | 90.15 MW | 90.15 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 925771 | AC1-053 C | 50/50 | 4.24 MW | 4.24 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 925772 | AC1-053 E | 50/50 | 28.39 MW | 28.39 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 935141 | AD1-148 | 50/50 | 5.95 MW | 5.95 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936771 | AD2-100 C | 50/50 | 19.97 MW | 19.97 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936772 | AD2-100 E | 50/50 | 13.31 MW | 13.31 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936971 | AD2-131 C | 50/50 | 1.31 MW | 1.31 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 936972 | AD2-131 E | 50/50 | 6.61 MW | 6.61 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942111 | AE2-223 C | 50/50 | 3.15 MW | 3.15 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942112 | AE2-223 E | 50/50 | 21.05 MW | 21.05 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942481 | AE2-261 C | 50/50 | 29.45 MW | 29.45 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 942482 | AE2-261 E | 50/50 | 19.63 MW | 19.63 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 945871 | AF1-252 O1 | 50/50 | 8.85 MW | 8.85 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 945881 | AF1-253 | 50/50 | 6.13 MW | 6.13 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959341 | AF2-225 C | 50/50 | 10.16 MW | 10.16 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959342 | AF2-225 E | 50/50 | 14.03 MW | 14.03 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959611 | AF2-252 C | 50/50 | 11.38 MW | 11.38 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 959612 | AF2-252 E | 50/50 | 17.07 MW | 17.07 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960141 | AF2-305 | 50/50 | 1.5 MW | 1.5 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960261 | AF2-317 | 50/50 | 2.57 MW | 2.57 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960611 | AF2-352 C | 50/50 | 11.38 MW | 11.38 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 960612 | AF2-352 E | 50/50 | 17.07 MW | 17.07 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274650 | KINCAID ;1U | 50/50 | 15.74 MW | 15.74 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274651 | KINCAID ;2U | 50/50 | 15.76 MW | 15.76 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274853 | TWINGROVE;U1 | 50/50 | 3.37 MW | 3.37 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274854 | TWINGROVE;U2 | 50/50 | 3.47 MW | 3.47 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274880 | RADFORD R;1U | 50/50 | 2.41 MW | 2.41 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 274889 | BRIGHTSTK;1U | 50/50 | 0.71 MW | 0.71 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 276615 | W2-048 GEN | 50/50 | 8.45 MW | 8.45 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 276621 | X2-022 GEN | 50/50 | 30.31 MW | 30.31 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 293798 | W4-005 E | 50/50 | 80.89 MW | 80.89 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 917502 | Z2-087 E | 50/50 | 28.07 MW | 28.07 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924041 | AB2-047 C O1 | 50/50 | 0.89 MW | 0.89 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924042 | AB2-047 E O1 | 50/50 | 35.08 MW | 35.08 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924261 | AB2-070 C O1 | 50/50 | 4.23 MW | 4.23 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 924262 | AB2-070 E O1 | 50/50 | 25.64 MW | 25.64 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 939741 | AE1-205 C O1 | 50/50 | 13.55 MW | 13.55 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 939742 | AE1-205 E O1 | 50/50 | 18.71 MW | 18.71 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 941731 | AE2-173 O1 | 50/50 | 8.06 MW | 8.06 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 944221 | AF1-090 C O1 | 50/50 | 4.99 MW | 4.99 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 944222 | AF1-090 E O1 | 50/50 | 23.38 MW | 23.38 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 957381 | AF2-032 C | 50/50 | 2.26 MW | 2.26 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 957382 | AF2-032 E | 50/50 | 1.06 MW | 1.06 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952651 | J756 C | External Queue | 3.89 MW | 3.89 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952652 | J756 E | External Queue | 21.04 MW | 21.04 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952871 | J757 C | External Queue | 4.56 MW | 4.56 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 952872 | J757 E | External Queue | 24.69 MW | 24.69 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953401 | J811 | External Queue | 9.02 MW | 9.02 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953651 | J815 | External Queue | 32.09 MW | 32.09 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953741 | J826 C | External Queue | 1.83 MW | 1.83 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953742 | J826 E | External Queue | 9.9 MW | 9.9 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953851 | J845 C | External Queue | 1.82 MW | 1.82 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953852 | J845 E | External Queue | 9.84 MW | 9.84 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953881 | J848 C | External Queue | 4.93 MW | 4.93 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 953882 | J848 E | External Queue | 26.67 MW | 26.67 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954411 | J912 | External Queue | 12.12 MW | 12.12 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954721 | J750 C | External Queue | 3.11 MW | 3.11 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954722 | J750 E | External Queue | 16.82 MW | 16.82 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 954821 | J955 | External Queue | 154.2 MW | 154.2 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 955402 | J1022 E | External Queue | 17.6 MW | 17.6 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956151 | J1102 | External Queue | 10.09 MW | 10.09 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956281 | J1115 C | External Queue | 6.94 MW | 6.94 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956282 | J1115 E | External Queue | 37.57 MW | 37.57 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 956451 | J1139 | External Queue | 11.74 MW | 11.74 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990056 | J1201 | External Queue | 4.21 MW | 4.21 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990672 | J1360 E | External Queue | 43.09 MW | 43.09 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 990856 | J1408 | External Queue | 13.14 MW | 13.14 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991191 | J1610 | External Queue | 13.18 MW | 13.18 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991196 | J1626 | External Queue | 13.66 MW | 13.66 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991236 | J1676 C | External Queue | 7.61 MW | 7.61 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991237 | J1676 E | External Queue | 41.17 MW | 41.17 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991266 | J1714 | External Queue | 9.11 MW | 9.11 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991261 | J1713 C | External Queue | 3.18 MW | 3.18 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | 991262 | J1713 E | External Queue | 17.23 MW | 17.23 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.64 MW | 0.64 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.82 MW | 0.82 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.03 MW | 1.03 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 16.92 MW | 16.92 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 35.3 MW | 35.3 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.97 MW | 0.97 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 1.72 MW | 1.72 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 5.17 MW | 5.17 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.04 MW | 0.04 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.26 MW | 1.26 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.94 MW | 0.94 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.33 MW | 0.33 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 4.02 MW | 4.02 MW |
| BLUEMOUND; B-PONTIAC ; B 345.0 kV Ckt 1 line l/o COMED_P4_BRO-45-BT2-3__ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 4.63 MW | 4.63 MW |
| Details for AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 963831 | AG1-236 C | 50/50 | 14.06 MW | 14.06 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 963832 | AG1-236 E | 50/50 | 94.09 MW | 94.09 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965331 | AG1-398 | 50/50 | 4.3 MW | 4.3 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965911 | AG1-460 C | 50/50 | 2.82 MW | 2.82 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965912 | AG1-460 E | 50/50 | 4.22 MW | 4.22 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 925771 | AC1-053 C | 50/50 | 14.06 MW | 14.06 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 925772 | AC1-053 E | 50/50 | 94.09 MW | 94.09 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 935141 | AD1-148 | 50/50 | 16.11 MW | 16.11 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 936771 | AD2-100 C | 50/50 | 27.67 MW | 27.67 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 936772 | AD2-100 E | 50/50 | 18.45 MW | 18.45 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 936971 | AD2-131 C | 50/50 | 1.82 MW | 1.82 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 936972 | AD2-131 E | 50/50 | 9.16 MW | 9.16 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 942481 | AE2-261 C | 50/50 | 42.09 MW | 42.09 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 942482 | AE2-261 E | 50/50 | 28.06 MW | 28.06 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 945871 | AF1-252 O1 | 50/50 | 10.96 MW | 10.96 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 945881 | AF1-253 | 50/50 | 7.59 MW | 7.59 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 960141 | AF2-305 | 50/50 | 5.39 MW | 5.39 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 960261 | AF2-317 | 50/50 | 6.96 MW | 6.96 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 274650 | KINCAID ;1U | 50/50 | 22.74 MW | 22.74 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 274651 | KINCAID ;2U | 50/50 | 22.66 MW | 22.66 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 276615 | W2-048 GEN | 50/50 | 22.88 MW | 22.88 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 276621 | X2-022 GEN | 50/50 | 82.1 MW | 82.1 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 924261 | AB2-070 C O1 | 50/50 | 15.25 MW | 15.25 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 924262 | AB2-070 E O1 | 50/50 | 92.34 MW | 92.34 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 944221 | AF1-090 C O1 | 50/50 | 6.18 MW | 6.18 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 944222 | AF1-090 E O1 | 50/50 | 28.95 MW | 28.95 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 957381 | AF2-032 C | 50/50 | 3.27 MW | 3.27 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 957382 | AF2-032 E | 50/50 | 1.54 MW | 1.54 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965392 | AG1-404 BAT | Adder | 11.55 MW | 9.82 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965352 | AG1-400 BAT | Adder | 17.32 MW | 14.72 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965372 | AG1-402 BAT | Adder | 17.32 MW | 14.72 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 960613 | AF2-352 BAT | Adder | 5.83 MW | 4.96 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 959613 | AF2-252 BAT | Adder | 5.83 MW | 4.96 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 941732 | AE2-173 BAT | 50/50 | 6.78 MW | 6.78 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 952651 | J756 C | External Queue | 2.13 MW | 2.13 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 952652 | J756 E | External Queue | 11.51 MW | 11.51 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 952871 | J757 C | External Queue | 6.59 MW | 6.59 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 952872 | J757 E | External Queue | 35.67 MW | 35.67 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953401 | J811 | External Queue | 8.33 MW | 8.33 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953651 | J815 | External Queue | 37.91 MW | 37.91 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953881 | J848 C | External Queue | 5.64 MW | 5.64 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953882 | J848 E | External Queue | 30.53 MW | 30.53 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953951 | J859 | External Queue | 11.43 MW | 11.43 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 954411 | J912 | External Queue | 12.68 MW | 12.68 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 954721 | J750 C | External Queue | 4.14 MW | 4.14 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 954722 | J750 E | External Queue | 22.39 MW | 22.39 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 954821 | J955 | External Queue | 217.13 MW | 217.13 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 956151 | J1102 | External Queue | 5.09 MW | 5.09 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 990056 | J1201 | External Queue | 4.3 MW | 4.3 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 990351 | J1289 C | External Queue | 2.71 MW | 2.71 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 990352 | J1289 E | External Queue | 14.64 MW | 14.64 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 990856 | J1408 | External Queue | 18.09 MW | 18.09 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 991191 | J1610 | External Queue | 17.8 MW | 17.8 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 991196 | J1626 | External Queue | 12.62 MW | 12.62 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 991266 | J1714 | External Queue | 8.42 MW | 8.42 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.39 MW | 0.39 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.23 MW | 0.23 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.78 MW | 0.78 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.04 MW | 11.04 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.52 MW | 2.52 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 24.64 MW | 24.64 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.58 MW | 0.58 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.53 MW | 0.53 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.91 MW | 4.91 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.27 MW | 0.27 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.62 MW | 3.62 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.28 MW | 3.28 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.41 MW | 1.41 MW |
| Details for AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 963831 | AG1-236 C | 50/50 | 14.03 MW | 14.03 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 963832 | AG1-236 E | 50/50 | 93.88 MW | 93.88 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965331 | AG1-398 | 50/50 | 4.3 MW | 4.3 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965911 | AG1-460 C | 50/50 | 2.75 MW | 2.75 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965912 | AG1-460 E | 50/50 | 4.13 MW | 4.13 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 925771 | AC1-053 C | 50/50 | 14.03 MW | 14.03 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 925772 | AC1-053 E | 50/50 | 93.88 MW | 93.88 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 935141 | AD1-148 | 50/50 | 15.97 MW | 15.97 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 936771 | AD2-100 C | 50/50 | 27.02 MW | 27.02 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 936772 | AD2-100 E | 50/50 | 18.02 MW | 18.02 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 936971 | AD2-131 C | 50/50 | 1.78 MW | 1.78 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 936972 | AD2-131 E | 50/50 | 8.94 MW | 8.94 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 942481 | AE2-261 C | 50/50 | 41.13 MW | 41.13 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 942482 | AE2-261 E | 50/50 | 27.42 MW | 27.42 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 945871 | AF1-252 O1 | 50/50 | 10.68 MW | 10.68 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 945881 | AF1-253 | 50/50 | 7.39 MW | 7.39 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 960141 | AF2-305 | 50/50 | 5.39 MW | 5.39 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 960261 | AF2-317 | 50/50 | 6.9 MW | 6.9 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 274650 | KINCAID ;1U | 50/50 | 22.23 MW | 22.23 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 274651 | KINCAID ;2U | 50/50 | 22.15 MW | 22.15 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 276615 | W2-048 GEN | 50/50 | 22.68 MW | 22.68 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 276621 | X2-022 GEN | 50/50 | 81.38 MW | 81.38 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 924261 | AB2-070 C O1 | 50/50 | 15.25 MW | 15.25 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 924262 | AB2-070 E O1 | 50/50 | 92.35 MW | 92.35 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 944221 | AF1-090 C O1 | 50/50 | 6.02 MW | 6.02 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 944222 | AF1-090 E O1 | 50/50 | 28.2 MW | 28.2 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 957381 | AF2-032 C | 50/50 | 3.19 MW | 3.19 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 957382 | AF2-032 E | 50/50 | 1.5 MW | 1.5 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965392 | AG1-404 BAT | Adder | 11.68 MW | 9.93 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965352 | AG1-400 BAT | Adder | 17.52 MW | 14.89 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965372 | AG1-402 BAT | Adder | 17.52 MW | 14.89 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 960613 | AF2-352 BAT | Adder | 5.84 MW | 4.96 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 959613 | AF2-252 BAT | Adder | 5.84 MW | 4.96 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 941732 | AE2-173 BAT | 50/50 | 6.64 MW | 6.64 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 952871 | J757 C | External Queue | 6.38 MW | 6.38 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 952872 | J757 E | External Queue | 34.54 MW | 34.54 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953401 | J811 | External Queue | 8.17 MW | 8.17 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953651 | J815 | External Queue | 36.76 MW | 36.76 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953881 | J848 C | External Queue | 5.51 MW | 5.51 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953882 | J848 E | External Queue | 29.79 MW | 29.79 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953951 | J859 | External Queue | 10.65 MW | 10.65 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 954411 | J912 | External Queue | 12.32 MW | 12.32 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 954721 | J750 C | External Queue | 3.79 MW | 3.79 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 954722 | J750 E | External Queue | 20.52 MW | 20.52 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 954821 | J955 | External Queue | 212.2 MW | 212.2 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 990056 | J1201 | External Queue | 4.21 MW | 4.21 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 990351 | J1289 C | External Queue | 2.58 MW | 2.58 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 990352 | J1289 E | External Queue | 13.94 MW | 13.94 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 990856 | J1408 | External Queue | 17.47 MW | 17.47 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 991191 | J1610 | External Queue | 16.68 MW | 16.68 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 991196 | J1626 | External Queue | 12.39 MW | 12.39 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 991266 | J1714 | External Queue | 8.26 MW | 8.26 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.39 MW | 0.39 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.25 MW | 0.25 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.76 MW | 0.76 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.94 MW | 10.94 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.12 MW | 1.12 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 24.12 MW | 24.12 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.58 MW | 0.58 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.57 MW | 0.57 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.75 MW | 4.75 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.27 MW | 3.27 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.2 MW | 3.2 MW |
| AB2-070 TAP-7BROKAW 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.52 MW | 1.52 MW |
| Details for AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 963831 | AG1-236 C | 50/50 | 14.06 MW | 14.06 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 963832 | AG1-236 E | 50/50 | 94.09 MW | 94.09 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965331 | AG1-398 | Adder | -3.03 MW | -2.58 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965911 | AG1-460 C | 50/50 | 2.82 MW | 2.82 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965912 | AG1-460 E | 50/50 | 4.22 MW | 4.22 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 925771 | AC1-053 C | 50/50 | 14.06 MW | 14.06 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 925772 | AC1-053 E | 50/50 | 94.09 MW | 94.09 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 935141 | AD1-148 | 50/50 | 16.11 MW | 16.11 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 936771 | AD2-100 C | 50/50 | 27.67 MW | 27.67 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 936772 | AD2-100 E | 50/50 | 18.45 MW | 18.45 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 936971 | AD2-131 C | 50/50 | 1.82 MW | 1.82 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 936972 | AD2-131 E | 50/50 | 9.16 MW | 9.16 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 942481 | AE2-261 C | 50/50 | 42.09 MW | 42.09 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 942482 | AE2-261 E | 50/50 | 28.06 MW | 28.06 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 945871 | AF1-252 O1 | 50/50 | 10.96 MW | 10.96 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 945881 | AF1-253 | 50/50 | 7.59 MW | 7.59 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 960141 | AF2-305 | Adder | -3.8 MW | -3.23 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 960261 | AF2-317 | 50/50 | 6.96 MW | 6.96 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 274650 | KINCAID ;1U | 50/50 | 22.74 MW | 22.74 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 274651 | KINCAID ;2U | 50/50 | 22.66 MW | 22.66 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 276615 | W2-048 GEN | 50/50 | 22.88 MW | 22.88 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 276621 | X2-022 GEN | 50/50 | 82.1 MW | 82.1 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 924261 | AB2-070 C O1 | Adder | -10.75 MW | -9.14 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 944221 | AF1-090 C O1 | 50/50 | 6.18 MW | 6.18 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 944222 | AF1-090 E O1 | 50/50 | 28.95 MW | 28.95 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 957381 | AF2-032 C | 50/50 | 3.27 MW | 3.27 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 957382 | AF2-032 E | 50/50 | 1.54 MW | 1.54 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965392 | AG1-404 BAT | Adder | 11.55 MW | 9.82 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965352 | AG1-400 BAT | Adder | 17.32 MW | 14.72 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 965372 | AG1-402 BAT | Adder | 17.32 MW | 14.72 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 960613 | AF2-352 BAT | Adder | 5.83 MW | 4.96 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 959613 | AF2-252 BAT | Adder | 5.83 MW | 4.96 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 941732 | AE2-173 BAT | 50/50 | 6.78 MW | 6.78 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 952651 | J756 C | External Queue | 2.13 MW | 2.13 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 952652 | J756 E | External Queue | 11.51 MW | 11.51 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 952871 | J757 C | External Queue | 6.59 MW | 6.59 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 952872 | J757 E | External Queue | 35.67 MW | 35.67 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953401 | J811 | External Queue | 8.33 MW | 8.33 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953651 | J815 | External Queue | 37.91 MW | 37.91 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953881 | J848 C | External Queue | 5.64 MW | 5.64 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953882 | J848 E | External Queue | 30.53 MW | 30.53 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 953951 | J859 | External Queue | 11.43 MW | 11.43 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 954411 | J912 | External Queue | 12.68 MW | 12.68 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 954721 | J750 C | External Queue | 4.14 MW | 4.14 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 954722 | J750 E | External Queue | 22.39 MW | 22.39 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 954821 | J955 | External Queue | 217.13 MW | 217.13 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 956151 | J1102 | External Queue | 5.09 MW | 5.09 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 990056 | J1201 | External Queue | 4.3 MW | 4.3 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 990351 | J1289 C | External Queue | 2.71 MW | 2.71 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 990352 | J1289 E | External Queue | 14.64 MW | 14.64 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 990856 | J1408 | External Queue | 18.09 MW | 18.09 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 991191 | J1610 | External Queue | 17.8 MW | 17.8 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 991196 | J1626 | External Queue | 12.62 MW | 12.62 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | 991266 | J1714 | External Queue | 8.42 MW | 8.42 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.39 MW | 0.39 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.23 MW | 0.23 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.78 MW | 0.78 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 11.04 MW | 11.04 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 2.52 MW | 2.52 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 24.64 MW | 24.64 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.58 MW | 0.58 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.53 MW | 0.53 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.91 MW | 4.91 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.27 MW | 0.27 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.62 MW | 3.62 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.12 MW | 0.12 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.28 MW | 3.28 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT11___ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.41 MW | 1.41 MW |
| Details for AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 963831 | AG1-236 C | 50/50 | 14.03 MW | 14.03 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 963832 | AG1-236 E | 50/50 | 93.88 MW | 93.88 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965331 | AG1-398 | Adder | -3.03 MW | -2.58 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965911 | AG1-460 C | 50/50 | 2.75 MW | 2.75 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965912 | AG1-460 E | 50/50 | 4.13 MW | 4.13 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 925771 | AC1-053 C | 50/50 | 14.03 MW | 14.03 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 925772 | AC1-053 E | 50/50 | 93.88 MW | 93.88 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 935141 | AD1-148 | 50/50 | 15.97 MW | 15.97 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 936771 | AD2-100 C | 50/50 | 27.02 MW | 27.02 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 936772 | AD2-100 E | 50/50 | 18.02 MW | 18.02 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 936971 | AD2-131 C | 50/50 | 1.78 MW | 1.78 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 936972 | AD2-131 E | 50/50 | 8.94 MW | 8.94 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 942481 | AE2-261 C | 50/50 | 41.13 MW | 41.13 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 942482 | AE2-261 E | 50/50 | 27.42 MW | 27.42 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 945871 | AF1-252 O1 | 50/50 | 10.68 MW | 10.68 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 945881 | AF1-253 | 50/50 | 7.39 MW | 7.39 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 960141 | AF2-305 | Adder | -3.8 MW | -3.23 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 960261 | AF2-317 | 50/50 | 6.9 MW | 6.9 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 274650 | KINCAID ;1U | 50/50 | 22.23 MW | 22.23 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 274651 | KINCAID ;2U | 50/50 | 22.15 MW | 22.15 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 276615 | W2-048 GEN | 50/50 | 22.68 MW | 22.68 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 276621 | X2-022 GEN | 50/50 | 81.38 MW | 81.38 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 924261 | AB2-070 C O1 | Adder | -10.75 MW | -9.14 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 944221 | AF1-090 C O1 | 50/50 | 6.02 MW | 6.02 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 944222 | AF1-090 E O1 | 50/50 | 28.2 MW | 28.2 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 957381 | AF2-032 C | 50/50 | 3.19 MW | 3.19 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 957382 | AF2-032 E | 50/50 | 1.5 MW | 1.5 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965392 | AG1-404 BAT | Adder | 11.68 MW | 9.93 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965352 | AG1-400 BAT | Adder | 17.52 MW | 14.89 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 965372 | AG1-402 BAT | Adder | 17.52 MW | 14.89 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 960613 | AF2-352 BAT | Adder | 5.84 MW | 4.96 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 959613 | AF2-252 BAT | Adder | 5.84 MW | 4.96 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 941732 | AE2-173 BAT | 50/50 | 6.64 MW | 6.64 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 952871 | J757 C | External Queue | 6.38 MW | 6.38 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 952872 | J757 E | External Queue | 34.54 MW | 34.54 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953401 | J811 | External Queue | 8.17 MW | 8.17 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953651 | J815 | External Queue | 36.76 MW | 36.76 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953881 | J848 C | External Queue | 5.51 MW | 5.51 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953882 | J848 E | External Queue | 29.79 MW | 29.79 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 953951 | J859 | External Queue | 10.65 MW | 10.65 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 954411 | J912 | External Queue | 12.32 MW | 12.32 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 954721 | J750 C | External Queue | 3.79 MW | 3.79 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 954722 | J750 E | External Queue | 20.52 MW | 20.52 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 954821 | J955 | External Queue | 212.2 MW | 212.2 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 990056 | J1201 | External Queue | 4.21 MW | 4.21 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 990351 | J1289 C | External Queue | 2.58 MW | 2.58 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 990352 | J1289 E | External Queue | 13.94 MW | 13.94 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 990856 | J1408 | External Queue | 17.47 MW | 17.47 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 991191 | J1610 | External Queue | 16.68 MW | 16.68 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 991196 | J1626 | External Queue | 12.39 MW | 12.39 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | 991266 | J1714 | External Queue | 8.26 MW | 8.26 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.39 MW | 0.39 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.25 MW | 0.25 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.76 MW | 0.76 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 10.94 MW | 10.94 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.12 MW | 1.12 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 24.12 MW | 24.12 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.58 MW | 0.58 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.57 MW | 0.57 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.75 MW | 4.75 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.25 MW | 0.25 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.27 MW | 3.27 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.13 MW | 0.13 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.2 MW | 3.2 MW |
| AC1-053 TAP-AB2-070 TAP 345.0 kV Ckt 1 line l/o COMED_P4_LAT-45-BT15___ | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 1.52 MW | 1.52 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961651 | AG1-005 C O1 | Adder | 12.46 MW | 10.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961652 | AG1-005 E O1 | Adder | 8.31 MW | 7.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962721 | AG1-121 C O1 | Adder | 4.27 MW | 3.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 962722 | AG1-121 E O1 | Adder | 19.98 MW | 16.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963831 | AG1-236 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 963832 | AG1-236 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964581 | AG1-321 C O1 | Adder | 11.85 MW | 10.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 964582 | AG1-321 E O1 | Adder | 6.9 MW | 5.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966821 | AG1-553 C O1 | Adder | 19.15 MW | 16.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 966822 | AG1-553 E O1 | Adder | 3.86 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965061 | AG1-371 | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965081 | AG1-373 | Adder | 0.66 MW | 0.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965091 | AG1-374 C | 50/50 | 21.84 MW | 21.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965092 | AG1-374 E | 50/50 | 14.56 MW | 14.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965331 | AG1-398 | 50/50 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965341 | AG1-399 C | 50/50 | 7.19 MW | 7.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965342 | AG1-399 E | 50/50 | 33.66 MW | 33.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965351 | AG1-400 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965371 | AG1-402 | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965391 | AG1-404 | 50/50 | 13.62 MW | 13.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965661 | AG1-434 C O1 | Adder | 2.4 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965662 | AG1-434 E O1 | Adder | 11.22 MW | 9.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965671 | AG1-435 C O1 | Adder | 2.91 MW | 2.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965672 | AG1-435 E O1 | Adder | 13.62 MW | 11.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965911 | AG1-460 C | 50/50 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965912 | AG1-460 E | 50/50 | 3.07 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965931 | AG1-462 C O1 | Adder | 12.39 MW | 10.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 965932 | AG1-462 E O1 | Adder | 8.26 MW | 7.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 272364 | ESS H440N ;R | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290051 | GSG-6; E | Adder | 5.74 MW | 4.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290261 | S-027 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 290265 | S-028 E | 50/50 | 19.21 MW | 19.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295109 | WESTBROOK E | Adder | 3.07 MW | 2.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 295111 | SUBLETTE E | Adder | 1.64 MW | 1.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 919581 | AA2-030 C | Adder | 11.53 MW | 9.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925771 | AC1-053 C | 50/50 | 3.92 MW | 3.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925772 | AC1-053 E | 50/50 | 26.24 MW | 26.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926821 | AC1-168 C O1 | Adder | 0.8 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 926822 | AC1-168 E O1 | Adder | 5.37 MW | 4.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 927202 | AC1-214 E O1 | Adder | 5.02 MW | 4.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933911 | AD1-013 C | Adder | 1.01 MW | 0.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 933912 | AD1-013 E | Adder | 1.61 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934051 | AD1-031 C O1 | Adder | 2.21 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934052 | AD1-031 E O1 | Adder | 3.61 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934432 | AD1-067 E | Adder | 0.3 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 935141 | AD1-148 | 50/50 | 5.64 MW | 5.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936511 | AD2-066 C O1 | Adder | 4.77 MW | 4.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936512 | AD2-066 E O1 | Adder | 3.18 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936771 | AD2-100 C | 50/50 | 22.11 MW | 22.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936772 | AD2-100 E | 50/50 | 14.74 MW | 14.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936971 | AD2-131 C | 50/50 | 1.46 MW | 1.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 936972 | AD2-131 E | 50/50 | 7.32 MW | 7.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937001 | AD2-134 C | Adder | 1.39 MW | 1.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937002 | AD2-134 E | Adder | 5.55 MW | 4.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937311 | AD2-172 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 937312 | AD2-172 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942111 | AE2-223 C | 50/50 | 2.19 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942112 | AE2-223 E | 50/50 | 14.69 MW | 14.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942481 | AE2-261 C | 50/50 | 30.63 MW | 30.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942482 | AE2-261 E | 50/50 | 20.42 MW | 20.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945871 | AF1-252 O1 | 50/50 | 11.82 MW | 11.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 945881 | AF1-253 | 50/50 | 8.19 MW | 8.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946542 | AF1-318 E O1 | Adder | 20.54 MW | 17.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958911 | AF2-182 C | Adder | 12.9 MW | 10.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958912 | AF2-182 E | Adder | 8.6 MW | 7.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958921 | AF2-183 C | Adder | 2.29 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958922 | AF2-183 E | Adder | 3.44 MW | 2.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959081 | AF2-199 C | Adder | 3.98 MW | 3.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959082 | AF2-199 E | Adder | 1.99 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959091 | AF2-200 C O1 | Adder | 7.96 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959092 | AF2-200 E O1 | Adder | 5.31 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959101 | AF2-201 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959102 | AF2-201 E O1 | Adder | 10.09 MW | 8.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959341 | AF2-225 C | 50/50 | 7.09 MW | 7.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959342 | AF2-225 E | 50/50 | 9.79 MW | 9.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959611 | AF2-252 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 959612 | AF2-252 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960141 | AF2-305 | 50/50 | 1.37 MW | 1.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960261 | AF2-317 | 50/50 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960611 | AF2-352 C | 50/50 | 2.43 MW | 2.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 960612 | AF2-352 E | 50/50 | 3.64 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961011 | AF2-392 C O1 | Adder | 2.57 MW | 2.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961012 | AF2-392 E O1 | Adder | 12.02 MW | 10.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961021 | AF2-393 O1 | Adder | 4.38 MW | 3.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 961031 | AF2-394 O1 | Adder | 2.92 MW | 2.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274650 | KINCAID ;1U | 50/50 | 16.0 MW | 16.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274651 | KINCAID ;2U | 50/50 | 15.99 MW | 15.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274853 | TWINGROVE;U1 | 50/50 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274854 | TWINGROVE;U2 | 50/50 | 0.74 MW | 0.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274859 | EASYR;U1 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274860 | EASYR;U2 E | Adder | 6.81 MW | 5.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274880 | RADFORD R;1U | 50/50 | 1.16 MW | 1.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 274889 | BRIGHTSTK;1U | 50/50 | 0.5 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276615 | W2-048 GEN | 50/50 | 8.02 MW | 8.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 276621 | X2-022 GEN | 50/50 | 28.76 MW | 28.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293516 | O-009 E1 | Adder | 6.22 MW | 5.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293517 | O-009 E2 | Adder | 3.16 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293518 | O-009 E3 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293715 | O-029 E | Adder | 6.65 MW | 5.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293716 | O-029 E | Adder | 3.65 MW | 3.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293717 | O-029 E | Adder | 3.35 MW | 2.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293771 | O-035 E | Adder | 4.92 MW | 4.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293777 | CAYUG;1U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293778 | CAYUG;2U E | Adder | 10.27 MW | 8.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 293798 | W4-005 E | 50/50 | 38.82 MW | 38.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294401 | BSHIL;1U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294410 | BSHIL;2U E | Adder | 6.66 MW | 5.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 294763 | P-046 E | Adder | 5.47 MW | 4.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916211 | Z1-072 E | Adder | 3.73 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 916221 | Z1-073 E | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 917502 | Z2-087 E | 50/50 | 19.59 MW | 19.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924041 | AB2-047 C O1 | 50/50 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924042 | AB2-047 E O1 | 50/50 | 24.48 MW | 24.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924261 | AB2-070 C O1 | 50/50 | 3.86 MW | 3.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 924262 | AB2-070 E O1 | 50/50 | 23.4 MW | 23.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925581 | AC1-033 C | Adder | 1.09 MW | 0.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 925582 | AC1-033 E | Adder | 7.3 MW | 6.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930482 | AB1-089 CT | Adder | 20.14 MW | 17.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930483 | AB1-089 ST | Adder | 16.01 MW | 13.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 930761 | AB1-122 CT1 | Adder | 40.35 MW | 34.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938861 | AE1-114 C O1 | Adder | 2.38 MW | 2.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 938862 | AE1-114 E O1 | Adder | 8.12 MW | 6.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939051 | AE1-134 1 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939061 | AE1-134 2 | Adder | 0.9 MW | 0.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939401 | AE1-172 C O1 | Adder | 3.48 MW | 2.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939402 | AE1-172 E O1 | Adder | 16.31 MW | 13.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939741 | AE1-205 C O1 | 50/50 | 9.46 MW | 9.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 939742 | AE1-205 E O1 | 50/50 | 13.06 MW | 13.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940501 | AE2-035 C | Adder | 1.44 MW | 1.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 940502 | AE2-035 E | Adder | 1.98 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941731 | AE2-173 O1 | 50/50 | 5.63 MW | 5.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944221 | AF1-090 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944222 | AF1-090 E O1 | 50/50 | 31.22 MW | 31.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946151 | AF1-280 C O1 | Adder | 9.82 MW | 8.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946152 | AF1-280 E O1 | Adder | 4.52 MW | 3.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946161 | AF1-281 C O1 | Adder | 0.22 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946162 | AF1-281 E O1 | Adder | 1.22 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946321 | AF1-296 C O1 | Adder | 2.98 MW | 2.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946322 | AF1-296 E O1 | Adder | 13.95 MW | 11.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946501 | AF1-314 C | Adder | 2.54 MW | 2.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946502 | AF1-314 E | Adder | 11.95 MW | 10.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946541 | AF1-318 C O1 | Adder | 4.39 MW | 3.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 946671 | AF1-331 | Adder | 1.31 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957381 | AF2-032 C | 50/50 | 2.3 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957382 | AF2-032 E | 50/50 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957471 | AF2-041 C | Adder | 11.94 MW | 10.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957472 | AF2-041 E | Adder | 5.97 MW | 5.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957751 | AF2-069 C | Adder | 0.18 MW | 0.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957752 | AF2-069 E | Adder | 0.59 MW | 0.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957761 | AF2-070 C | Adder | 0.26 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 957762 | AF2-070 E | Adder | 1.25 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958341 | AF2-128 C O1 | Adder | 1.16 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 958342 | AF2-128 E O1 | Adder | 5.44 MW | 4.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990901 | L-005 E | Adder | 10.6 MW | 9.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 934101 | AD2-000 1 | Adder | 3.26 MW | 2.77 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 944202 | AF1-088 FTWR | 50/50 | 260.6 MW | 260.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 942602 | AE2-276 BAT | 50/50 | 13.03 MW | 13.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 941343 | AE2-130 BAT | 50/50 | 29.76 MW | 29.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953401 | J811 | External Queue | 18.24 MW | 18.24 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953641 | J813 | External Queue | 40.35 MW | 40.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953881 | J848 C | External Queue | 5.27 MW | 5.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 953882 | J848 E | External Queue | 28.49 MW | 28.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954411 | J912 | External Queue | 14.3 MW | 14.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 954681 | J949 C | External Queue | 32.68 MW | 32.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 956451 | J1139 | External Queue | 20.06 MW | 20.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990056 | J1201 | External Queue | 7.03 MW | 7.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990071 | J1204 | External Queue | 65.85 MW | 65.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 990271 | J1263 | External Queue | 106.84 MW | 106.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991196 | J1626 | External Queue | 27.64 MW | 27.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991266 | J1714 | External Queue | 18.43 MW | 18.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991261 | J1713 C | External Queue | 3.03 MW | 3.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | 991262 | J1713 E | External Queue | 3.46 MW | 3.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.36 MW | 0.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.61 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 1.65 MW | 1.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.0 MW | 15.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 69.74 MW | 69.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 68.94 MW | 68.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.78 MW | 0.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.87 MW | 12.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.61 MW | 1.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 15.25 MW | 15.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.26 MW | 1.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 7.93 MW | 7.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 2.06 MW | 2.06 MW |
| Details for AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 961651 | AG1-005 C O1 | Adder | 8.65 MW | 7.35 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 961652 | AG1-005 E O1 | Adder | 5.77 MW | 4.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 963831 | AG1-236 C | Adder | 2.59 MW | 2.2 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 963832 | AG1-236 E | Adder | 17.32 MW | 14.73 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 964581 | AG1-321 C O1 | 50/50 | 19.5 MW | 19.5 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 964582 | AG1-321 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965091 | AG1-374 C | 50/50 | 26.8 MW | 26.8 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965092 | AG1-374 E | 50/50 | 17.87 MW | 17.87 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965331 | AG1-398 | 50/50 | 0.75 MW | 0.75 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965341 | AG1-399 C | 50/50 | 6.68 MW | 6.68 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965342 | AG1-399 E | 50/50 | 31.28 MW | 31.28 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965351 | AG1-400 | 50/50 | 18.98 MW | 18.98 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965371 | AG1-402 | 50/50 | 18.98 MW | 18.98 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965391 | AG1-404 | 50/50 | 12.65 MW | 12.65 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965911 | AG1-460 C | Adder | 0.93 MW | 0.79 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 965912 | AG1-460 E | Adder | 1.4 MW | 1.19 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 966091 | AG1-478 C | Adder | 1.09 MW | 0.93 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 966092 | AG1-478 E | Adder | 0.27 MW | 0.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 290261 | S-027 E | 50/50 | 23.58 MW | 23.58 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 290265 | S-028 E | 50/50 | 23.58 MW | 23.58 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 925771 | AC1-053 C | Adder | 2.59 MW | 2.2 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 925772 | AC1-053 E | Adder | 17.32 MW | 14.73 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 926821 | AC1-168 C O1 | Adder | 0.68 MW | 0.57 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 926822 | AC1-168 E O1 | Adder | 4.54 MW | 3.86 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 934721 | AD1-100 C | 50/50 | 51.75 MW | 51.75 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 934722 | AD1-100 E | 50/50 | 241.48 MW | 241.48 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 935141 | AD1-148 | Adder | 3.38 MW | 2.87 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 936371 | AD2-047 C O1 | 50/50 | 4.96 MW | 4.96 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 936372 | AD2-047 E O1 | 50/50 | 24.23 MW | 24.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 936461 | AD2-060 | 50/50 | 2.92 MW | 2.92 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 936771 | AD2-100 C | Adder | 9.45 MW | 8.03 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 936772 | AD2-100 E | Adder | 6.3 MW | 5.36 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 936971 | AD2-131 C | Adder | 0.62 MW | 0.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 936972 | AD2-131 E | Adder | 3.13 MW | 2.66 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 942111 | AE2-223 C | 50/50 | 3.1 MW | 3.1 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 942112 | AE2-223 E | 50/50 | 20.78 MW | 20.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 942481 | AE2-261 C | Adder | 13.92 MW | 11.83 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 942482 | AE2-261 E | Adder | 9.28 MW | 7.89 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 945871 | AF1-252 O1 | Adder | 4.21 MW | 3.58 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 945881 | AF1-253 | Adder | 2.91 MW | 2.48 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 946542 | AF1-318 E O1 | Adder | 13.89 MW | 11.81 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 959341 | AF2-225 C | 50/50 | 10.03 MW | 10.03 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 959342 | AF2-225 E | 50/50 | 13.85 MW | 13.85 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 959611 | AF2-252 C | 50/50 | 2.98 MW | 2.98 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 959612 | AF2-252 E | 50/50 | 4.47 MW | 4.47 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 960141 | AF2-305 | 50/50 | 0.94 MW | 0.94 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 960261 | AF2-317 | Adder | 1.46 MW | 1.24 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 960591 | AF2-350 C O1 | 50/50 | 8.76 MW | 8.76 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 960592 | AF2-350 E O1 | 50/50 | 5.84 MW | 5.84 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 960601 | AF2-351 C O1 | 50/50 | 1.17 MW | 1.17 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 960602 | AF2-351 E O1 | 50/50 | 1.75 MW | 1.75 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 960611 | AF2-352 C | 50/50 | 2.98 MW | 2.98 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 960612 | AF2-352 E | 50/50 | 4.47 MW | 4.47 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274654 | BRAIDWOOD;1U | 50/50 | 46.81 MW | 46.81 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274655 | BRAIDWOOD;2U | 50/50 | 45.45 MW | 45.45 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274660 | LASCO STA;1U | 50/50 | 29.59 MW | 29.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274661 | LASCO STA;2U | 50/50 | 29.72 MW | 29.72 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274847 | GR RIDGE ;BU | 50/50 | 0.59 MW | 0.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274853 | TWINGROVE;U1 | 50/50 | 0.88 MW | 0.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274854 | TWINGROVE;U2 | 50/50 | 0.91 MW | 0.91 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274863 | CAYUGA RI;1U | 50/50 | 0.99 MW | 0.99 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274864 | CAYUGA RI;2U | 50/50 | 0.99 MW | 0.99 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274871 | GR RIDGE ;2U | 50/50 | 0.22 MW | 0.22 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274880 | RADFORD R;1U | 50/50 | 0.83 MW | 0.83 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274887 | PILOT HIL;1U | 50/50 | 0.87 MW | 0.87 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274888 | KELLY CRK;1U | 50/50 | 0.87 MW | 0.87 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 274889 | BRIGHTSTK;1U | 50/50 | 0.7 MW | 0.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 275149 | KELLYCK ;1E | 50/50 | 20.44 MW | 20.44 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 276615 | W2-048 GEN | Adder | 4.8 MW | 4.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 276621 | X2-022 GEN | Adder | 17.23 MW | 14.65 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 293061 | N-015 E | 50/50 | 15.24 MW | 15.24 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 293777 | CAYUG;1U E | 50/50 | 30.97 MW | 30.97 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 293778 | CAYUG;2U E | 50/50 | 30.97 MW | 30.97 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 293798 | W4-005 E | 50/50 | 27.88 MW | 27.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 293799 | PILOT HIL;1E | 50/50 | 20.44 MW | 20.44 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 294392 | P-010 E | 50/50 | 19.35 MW | 19.35 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 917502 | Z2-087 E | 50/50 | 27.71 MW | 27.71 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 924041 | AB2-047 C O1 | 50/50 | 0.88 MW | 0.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 924042 | AB2-047 E O1 | 50/50 | 34.63 MW | 34.63 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 924261 | AB2-070 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 924262 | AB2-070 E O1 | 50/50 | 16.16 MW | 16.16 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 933411 | AC2-154 C | 50/50 | 2.77 MW | 2.77 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 933412 | AC2-154 E | 50/50 | 4.53 MW | 4.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 939351 | AE1-166 C O1 | 50/50 | 22.64 MW | 22.64 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 939352 | AE1-166 E O1 | 50/50 | 20.89 MW | 20.89 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 939401 | AE1-172 C O1 | 50/50 | 13.51 MW | 13.51 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 939402 | AE1-172 E O1 | 50/50 | 63.38 MW | 63.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 939741 | AE1-205 C O1 | 50/50 | 13.38 MW | 13.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 939742 | AE1-205 E O1 | 50/50 | 18.47 MW | 18.47 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 941551 | AE2-152 C O1 | 50/50 | 26.12 MW | 26.12 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 941552 | AE2-152 E O1 | 50/50 | 17.41 MW | 17.41 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 941731 | AE2-173 O1 | 50/50 | 7.96 MW | 7.96 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 944221 | AF1-090 C O1 | Adder | 2.37 MW | 2.02 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 944222 | AF1-090 E O1 | Adder | 11.11 MW | 9.45 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 946541 | AF1-318 C O1 | Adder | 2.97 MW | 2.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 957381 | AF2-032 C | Adder | 1.07 MW | 0.91 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 957382 | AF2-032 E | Adder | 0.5 MW | 0.43 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 958011 | AF2-095 C O1 | 50/50 | 19.85 MW | 19.85 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 958012 | AF2-095 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 958021 | AF2-096 C | 50/50 | 59.23 MW | 59.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 958022 | AF2-096 E | 50/50 | 27.88 MW | 27.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 958341 | AF2-128 C O1 | Adder | 0.81 MW | 0.69 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 958342 | AF2-128 E O1 | Adder | 3.78 MW | 3.21 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 952651 | J756 C | External Queue | 1.81 MW | 1.81 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 952652 | J756 E | External Queue | 9.79 MW | 9.79 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 953741 | J826 C | External Queue | 1.04 MW | 1.04 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 953742 | J826 E | External Queue | 5.6 MW | 5.6 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 954721 | J750 C | External Queue | 1.41 MW | 1.41 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 954722 | J750 E | External Queue | 7.62 MW | 7.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 954821 | J955 | External Queue | 63.7 MW | 63.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 955402 | J1022 E | External Queue | 9.95 MW | 9.95 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 956151 | J1102 | External Queue | 4.39 MW | 4.39 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 956281 | J1115 C | External Queue | 2.59 MW | 2.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 956282 | J1115 E | External Queue | 14.02 MW | 14.02 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 990672 | J1360 E | External Queue | 18.78 MW | 18.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 990856 | J1408 | External Queue | 5.65 MW | 5.65 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 991191 | J1610 | External Queue | 5.85 MW | 5.85 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 991236 | J1676 C | External Queue | 4.39 MW | 4.39 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 991237 | J1676 E | External Queue | 23.74 MW | 23.74 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 991261 | J1713 C | External Queue | 1.27 MW | 1.27 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | 991262 | J1713 E | External Queue | 6.88 MW | 6.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.09 MW | 0.09 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.36 MW | 0.36 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.63 MW | 0.63 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 10.6 MW | 10.6 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.88 MW | 17.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.73 MW | 0.73 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.02 MW | 0.02 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.75 MW | 2.75 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.11 MW | 0.11 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 4.31 MW | 4.31 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.4 MW | 0.4 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.7 MW | 4.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.09 MW | 0.09 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.59 MW | 1.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L2001__B-S_+_345-L2003__R-S-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.45 MW | 0.45 MW |
Light Load Analysis
The Queue Project was evaluated as a 150.0 MW (Capacity 150.0 MW) injection in the ComEd area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P1-2_345-L8014__R-S-A
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-A' TRIP BRANCH FROM BUS 270853 TO BUS 964580 CKT 1 /*PONTIAC ; R 345.0 - AG1-321 TAP 345.0 END |
Single | AC | 109.22 % | 111.49 % | 2107.0 | STE | 2348.99 | 51.16 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P1-2_345-L8014__R-S-B
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-B' TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Single | AC | 109.22 % | 111.48 % | 2107.0 | STE | 2348.84 | 51.16 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 107.09 % | 109.34 % | 2107.0 | STE | 2303.77 | 51.41 | |
| CE |
AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line
939400 to 934720 ckt 1 |
Base Case | Single | AC | 105.34 % | 107.93 % | 1364.0 | A | 1472.17 | 35.45 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
COMED_P1-2_765-L11215__-S
CONTINGENCY 'COMED_P1-2_765-L11215__-S' REMOVE SHUNT 1 FROM BUS 270644 /*WILTON ; 765.0 TRIP BRANCH FROM BUS 270644 TO BUS 243206 CKT 1 /*WILTON ; 765.0 - 05DUMONT 765.0 END |
Single | DC | 146.88 % | 147.83 % | 1409.0 | B | 2082.92 | 14.23 | |
| AEP/NIPS |
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
255113 to 243219 ckt 1 |
AEP_P1-2_#695_1681
CONTINGENCY 'AEP_P1-2_#695_1681' OPEN BRANCH FROM BUS 243206 TO BUS 270644 CKT 1 /*05DUMONT 765.0 - WILTON ; 765.0 END |
Single | DC | 146.88 % | 147.83 % | 1409.0 | B | 2082.92 | 14.23 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P1-2_345-L8014__R-S-A
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-A' TRIP BRANCH FROM BUS 270853 TO BUS 964580 CKT 1 /*PONTIAC ; R 345.0 - AG1-321 TAP 345.0 END |
Single | AC | 117.56 % | 120.15 % | 1846.0 | STE | 2217.89 | 51.16 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P1-2_345-L8014__R-S-B
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-B' TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Single | AC | 117.55 % | 120.14 % | 1846.0 | STE | 2217.74 | 51.16 | |
| CE |
LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line
270704 to 939400 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 115.02 % | 117.6 % | 1846.0 | STE | 2170.98 | 51.41 | |
| CE |
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
934720 to 270926 ckt 1 |
COMED_P1-2_765-L11216__-S
CONTINGENCY 'COMED_P1-2_765-L11216__-S' TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1 /*WILTON ; 765.0 - COLLINS ; 765.0 END |
Single | DC | 114.24 % | 115.28 % | 1846.0 | STE | 2128.05 | 19.36 | |
| CE |
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
934720 to 270926 ckt 1 |
COMED_P1-2_345-L8014__R-S-B
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-B' TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Single | AC | 99.07 % | 100.16 % | 1846.0 | STE | 1848.88 | 23.08 | |
| CE |
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
934720 to 270926 ckt 1 |
COMED_P1-2_345-L8014__R-S-A
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-A' TRIP BRANCH FROM BUS 270853 TO BUS 964580 CKT 1 /*PONTIAC ; R 345.0 - AG1-321 TAP 345.0 END |
Single | AC | 99.06 % | 100.14 % | 1846.0 | STE | 1848.57 | 23.08 | |
| CE |
AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line
934720 to 270926 ckt 1 |
Base Case | Single | AC | 112.21 % | 113.29 % | 1364.0 | A | 1545.28 | 16.38 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P1-2_345-L8014__R-S-A
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-A' TRIP BRANCH FROM BUS 270853 TO BUS 964580 CKT 1 /*PONTIAC ; R 345.0 - AG1-321 TAP 345.0 END |
Single | AC | 108.34 % | 110.95 % | 1837.0 | STE | 2038.2 | 51.34 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P1-2_345-L8014__R-S-B
CONTINGENCY 'COMED_P1-2_345-L8014__R-S-B' TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Single | AC | 108.33 % | 110.94 % | 1837.0 | STE | 2038.05 | 51.34 | |
| CE |
PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line
270852 to 270704 ckt 1 |
COMED_P4_012-45-BT12-14
CONTINGENCY 'COMED_P4_012-45-BT12-14' TRIP BRANCH FROM BUS 270717 TO BUS 930760 CKT 1 /*DRESDEN ; R 345.0 - AB1-122 TAP1 345.0 TRIP BRANCH FROM BUS 964580 TO BUS 270717 CKT 1 /*AG1-321 TAP 345.0 - DRESDEN ; R 345.0 END |
Breaker | AC | 106.01 % | 108.62 % | 1837.0 | STE | 1995.26 | 51.59 | |
| CE |
PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line
270853 to 964580 ckt 1 |
COMED_P1-2_345-L11212_B-S-B
CONTINGENCY 'COMED_P1-2_345-L11212_B-S-B' TRIP BRANCH FROM BUS 934720 TO BUS 939400 CKT 1 /*AD1-100 TAP 345.0 - AE1-172 TAP 345.0 END |
Single | DC | 116.83 % | 119.42 % | 1797.0 | STE | 2146.01 | 46.55 | |
| CE |
PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line
270853 to 964580 ckt 1 |
COMED_P1-2_345-L11212_B-S-C
CONTINGENCY 'COMED_P1-2_345-L11212_B-S-C' TRIP BRANCH FROM BUS 939400 TO BUS 270704 CKT 1 /*AE1-172 TAP 345.0 - LORETTO ; B 345.0 END |
Single | DC | 111.66 % | 114.25 % | 1797.0 | STE | 2053.11 | 46.55 | |
| CE |
AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line
964580 to 270717 ckt 1 |
COMED_P1-2_345-L11212_B-S-B
CONTINGENCY 'COMED_P1-2_345-L11212_B-S-B' TRIP BRANCH FROM BUS 934720 TO BUS 939400 CKT 1 /*AD1-100 TAP 345.0 - AE1-172 TAP 345.0 END |
Single | DC | 126.43 % | 129.24 % | 1656.0 | B | 2140.21 | 46.55 | |
| CE |
AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line
964580 to 270717 ckt 1 |
COMED_P1-2_345-L11212_B-S-C
CONTINGENCY 'COMED_P1-2_345-L11212_B-S-C' TRIP BRANCH FROM BUS 939400 TO BUS 270704 CKT 1 /*AE1-172 TAP 345.0 - LORETTO ; B 345.0 END |
Single | DC | 120.82 % | 123.63 % | 1656.0 | B | 2047.31 | 46.55 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P4_#3128_05EUGENE 345_A2
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2' OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1 /*05EUGENE 345.0 - 08CAYSUB 345.0 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Breaker | AC | 113.09 % | 114.66 % | 1466.0 | B | 1680.92 | 20.47 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
AEP_P1-2_#286_1687
CONTINGENCY 'AEP_P1-2_#286_1687' OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1 /*05EUGENE 345.0 - 7BUNSONVILLE 345.0 END |
Single | DC | 105.47 % | 106.85 % | 1466.0 | B | 1566.42 | 20.22 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
PJM_PLANT RKG1
CONTINGENCY 'PJM_PLANT RKG1' REMOVE MACHINE 1H FROM BUS 243442 /*05RKG1 26.0 REMOVE MACHINE 1L FROM BUS 243442 /*05RKG1 26.0 END |
Single | DC | 102.71 % | 104.1 % | 1466.0 | B | 1526.11 | 15.52 | |
| AEP/ARE_2 |
J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line
956820 to 247712 ckt 1 |
Base Case | Single | AC | 100.16 % | 101.26 % | 1334.0 | A | 1350.81 | 15.52 | |
| CE |
MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line
270819 to 270853 ckt 1 |
COMED_P1-2_345-L8002___-S
CONTINGENCY 'COMED_P1-2_345-L8002___-S' TRIP BRANCH FROM BUS 270852 TO BUS 270668 CKT 1 /*PONTIAC ; B 345.0 - BLUEMOUND; B 345.0 END |
Single | AC | 113.6 % | 115.27 % | 1837.0 | STE | 2117.5 | 33.15 | |
| CE |
MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line
270819 to 270853 ckt 1 |
COMED_P1-2_345-L9515___-S-B
CONTINGENCY 'COMED_P1-2_345-L9515___-S-B' TRIP BRANCH FROM BUS 965340 TO BUS 270668 CKT 1 /*AG1-399 TAP 345.0 - BLUEMOUND; B 345.0 END |
Single | AC | 106.79 % | 108.48 % | 1837.0 | STE | 1992.71 | 33.29 | |
| CE |
MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line
270819 to 270853 ckt 1 |
COMED_P1-2_345-L9503___-S
CONTINGENCY 'COMED_P1-2_345-L9503___-S' TRIP BRANCH FROM BUS 348856 TO BUS 270685 CKT 1 /*7LATHAM 345.0 - CHESTNUT ; B 345.0 END |
Single | AC | 98.19 % | 100.54 % | 1837.0 | STE | 1846.83 | 46.91 | |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274853 | TWINGROVE;U1 | 80/20 | 5.64 MW | 5.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274854 | TWINGROVE;U2 | 80/20 | 5.8 MW | 5.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274863 | CAYUGA RI;1U | 80/20 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274864 | CAYUGA RI;2U | 80/20 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274880 | RADFORD R;1U | 80/20 | 5.2 MW | 5.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274889 | BRIGHTSTK;1U | 80/20 | 5.11 MW | 5.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276615 | W2-048 GEN | 80/20 | 7.12 MW | 7.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276621 | X2-022 GEN | 80/20 | 20.26 MW | 20.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290261 | S-027 E | 80/20 | 25.68 MW | 25.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290265 | S-028 E | 80/20 | 25.68 MW | 25.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293777 | CAYUG;1U E | 80/20 | 32.81 MW | 32.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293778 | CAYUG;2U E | 80/20 | 32.81 MW | 32.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293798 | W4-005 E | 80/20 | 34.79 MW | 34.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 917502 | Z2-087 E | 80/20 | 30.35 MW | 30.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924041 | AB2-047 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924042 | AB2-047 E O1 | 80/20 | 37.94 MW | 37.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924261 | AB2-070 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924262 | AB2-070 E O1 | 80/20 | 34.07 MW | 34.07 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925771 | AC1-053 C | 80/20 | 5.44 MW | 5.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925772 | AC1-053 E | 80/20 | 36.42 MW | 36.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 935141 | AD1-148 | 80/20 | 9.52 MW | 9.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 939401 | AE1-172 C O1 | 80/20 | 23.93 MW | 23.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 939402 | AE1-172 E O1 | 80/20 | 112.25 MW | 112.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 941731 | AE2-173 O1 | 80/20 | 21.8 MW | 21.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942111 | AE2-223 C | 80/20 | 6.8 MW | 6.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942112 | AE2-223 E | 80/20 | 45.52 MW | 45.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942601 | AE2-276 | 80/20 | 2.69 MW | 2.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944221 | AF1-090 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944222 | AF1-090 E O1 | 80/20 | 22.91 MW | 22.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945391 | AF1-204 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945392 | AF1-204 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945871 | AF1-252 O1 | 80/20 | 10.85 MW | 10.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945881 | AF1-253 | 80/20 | 7.51 MW | 7.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959611 | AF2-252 C | 80/20 | 8.11 MW | 8.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959612 | AF2-252 E | 80/20 | 12.16 MW | 12.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960141 | AF2-305 | 80/20 | 1.99 MW | 1.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960261 | AF2-317 | 80/20 | 3.05 MW | 3.05 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960611 | AF2-352 C | 80/20 | 8.11 MW | 8.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960612 | AF2-352 E | 80/20 | 12.16 MW | 12.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963831 | AG1-236 C | 80/20 | 5.44 MW | 5.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963832 | AG1-236 E | 80/20 | 36.42 MW | 36.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965092 | AG1-374 E | 80/20 | 30.4 MW | 30.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965341 | AG1-399 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965342 | AG1-399 E O1 | 80/20 | 67.45 MW | 67.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965351 | AG1-400 O1 | 80/20 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965371 | AG1-402 O1 | 80/20 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965391 | AG1-404 O1 | 80/20 | 34.11 MW | 34.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965911 | AG1-460 C | 80/20 | 2.39 MW | 2.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965912 | AG1-460 E | 80/20 | 3.59 MW | 3.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957382 | AF2-032 E | 80/20 | 0.4 MW | 0.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276172 | Z1-108 BAT | 80/20 | 1.22 MW | 1.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 920273 | AA2-123 BAT | 80/20 | 1.11 MW | 1.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 943803 | AF1-048 BAT | 80/20 | 2.88 MW | 2.88 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944201 | AF1-088 FTIR | 80/20 | 53.82 MW | 53.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957141 | AF2-008 FTIR | 80/20 | 26.91 MW | 26.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957333 | AF2-027 BAT | 80/20 | 3.09 MW | 3.09 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957373 | AF2-031 BAT | 80/20 | 1.64 MW | 1.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957403 | AF2-034 BAT | 80/20 | 0.71 MW | 0.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958013 | AF2-095 BAT | 80/20 | 4.56 MW | 4.56 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958023 | AF2-096 BAT | 80/20 | 9.11 MW | 9.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959353 | AF2-226 BAT | 80/20 | 2.64 MW | 2.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960283 | AF2-319 BAT | 80/20 | 2.64 MW | 2.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960382 | AF2-329 BAT | 80/20 | 2.94 MW | 2.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960603 | AF2-351 BAT | 80/20 | 2.28 MW | 2.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 961503 | AF2-441 BAT | 80/20 | 17.02 MW | 17.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 964362 | AG1-298 BAT | 80/20 | 42.2 MW | 42.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966093 | AG1-478 BAT | 80/20 | 0.85 MW | 0.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966433 | AG1-512 BAT | 80/20 | 3.35 MW | 3.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966443 | AG1-513 BAT | 80/20 | 0.7 MW | 0.7 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966652 | AG1-535 BAT | 80/20 | 6.98 MW | 6.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.64 MW | 5.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.8 MW | 5.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274863 | CAYUGA RI;1U | 80/20 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274864 | CAYUGA RI;2U | 80/20 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274880 | RADFORD R;1U | 80/20 | 5.2 MW | 5.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 5.11 MW | 5.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276615 | W2-048 GEN | 80/20 | 7.12 MW | 7.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276621 | X2-022 GEN | 80/20 | 20.26 MW | 20.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290261 | S-027 E | 80/20 | 25.68 MW | 25.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290265 | S-028 E | 80/20 | 25.68 MW | 25.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293777 | CAYUG;1U E | 80/20 | 32.81 MW | 32.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293778 | CAYUG;2U E | 80/20 | 32.81 MW | 32.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293798 | W4-005 E | 80/20 | 34.79 MW | 34.79 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 917502 | Z2-087 E | 80/20 | 30.35 MW | 30.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924042 | AB2-047 E O1 | 80/20 | 37.94 MW | 37.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924262 | AB2-070 E O1 | 80/20 | 34.07 MW | 34.07 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925771 | AC1-053 C | 80/20 | 5.44 MW | 5.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925772 | AC1-053 E | 80/20 | 36.42 MW | 36.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 935141 | AD1-148 | 80/20 | 9.52 MW | 9.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 939401 | AE1-172 C O1 | 80/20 | 23.93 MW | 23.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 939402 | AE1-172 E O1 | 80/20 | 112.25 MW | 112.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 941731 | AE2-173 O1 | 80/20 | 21.8 MW | 21.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942111 | AE2-223 C | 80/20 | 6.8 MW | 6.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942112 | AE2-223 E | 80/20 | 45.52 MW | 45.52 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942601 | AE2-276 | 80/20 | 2.69 MW | 2.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944222 | AF1-090 E O1 | 80/20 | 22.91 MW | 22.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945391 | AF1-204 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945392 | AF1-204 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945871 | AF1-252 O1 | 80/20 | 10.85 MW | 10.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945881 | AF1-253 | 80/20 | 7.51 MW | 7.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959611 | AF2-252 C | 80/20 | 8.11 MW | 8.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959612 | AF2-252 E | 80/20 | 12.16 MW | 12.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960141 | AF2-305 | 80/20 | 1.99 MW | 1.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960261 | AF2-317 | 80/20 | 3.05 MW | 3.05 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960611 | AF2-352 C | 80/20 | 8.11 MW | 8.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960612 | AF2-352 E | 80/20 | 12.16 MW | 12.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963831 | AG1-236 C | 80/20 | 5.44 MW | 5.44 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963832 | AG1-236 E | 80/20 | 36.42 MW | 36.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965092 | AG1-374 E | 80/20 | 30.4 MW | 30.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965341 | AG1-399 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965342 | AG1-399 E O1 | 80/20 | 67.45 MW | 67.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965351 | AG1-400 O1 | 80/20 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965371 | AG1-402 O1 | 80/20 | 51.16 MW | 51.16 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965391 | AG1-404 O1 | 80/20 | 34.11 MW | 34.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965911 | AG1-460 C | 80/20 | 2.39 MW | 2.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965912 | AG1-460 E | 80/20 | 3.59 MW | 3.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957382 | AF2-032 E | 80/20 | 0.4 MW | 0.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276172 | Z1-108 BAT | 80/20 | 1.22 MW | 1.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 920273 | AA2-123 BAT | 80/20 | 1.11 MW | 1.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 943803 | AF1-048 BAT | 80/20 | 2.88 MW | 2.88 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944201 | AF1-088 FTIR | 80/20 | 53.82 MW | 53.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957141 | AF2-008 FTIR | 80/20 | 26.91 MW | 26.91 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957333 | AF2-027 BAT | 80/20 | 3.09 MW | 3.09 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957373 | AF2-031 BAT | 80/20 | 1.64 MW | 1.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957403 | AF2-034 BAT | 80/20 | 0.71 MW | 0.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958013 | AF2-095 BAT | 80/20 | 4.56 MW | 4.56 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958023 | AF2-096 BAT | 80/20 | 9.11 MW | 9.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959353 | AF2-226 BAT | 80/20 | 2.64 MW | 2.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960283 | AF2-319 BAT | 80/20 | 2.64 MW | 2.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960382 | AF2-329 BAT | 80/20 | 2.94 MW | 2.94 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960603 | AF2-351 BAT | 80/20 | 2.28 MW | 2.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 961503 | AF2-441 BAT | 80/20 | 17.02 MW | 17.02 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 964362 | AG1-298 BAT | 80/20 | 42.2 MW | 42.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966093 | AG1-478 BAT | 80/20 | 0.85 MW | 0.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966433 | AG1-512 BAT | 80/20 | 3.35 MW | 3.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966443 | AG1-513 BAT | 80/20 | 0.7 MW | 0.7 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966652 | AG1-535 BAT | 80/20 | 6.98 MW | 6.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 5.66 MW | 5.66 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 5.82 MW | 5.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274863 | CAYUGA RI;1U | 50/50 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274864 | CAYUGA RI;2U | 50/50 | 5.46 MW | 5.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 5.24 MW | 5.24 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 5.12 MW | 5.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 7.19 MW | 7.19 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 20.46 MW | 20.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 25.77 MW | 25.77 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 25.77 MW | 25.77 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293777 | CAYUG;1U E | 50/50 | 32.82 MW | 32.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293778 | CAYUG;2U E | 50/50 | 32.82 MW | 32.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 35.04 MW | 35.04 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 30.43 MW | 30.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 5.68 MW | 5.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 38.03 MW | 38.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 5.67 MW | 5.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 34.35 MW | 34.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 5.49 MW | 5.49 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 36.74 MW | 36.74 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.62 MW | 9.62 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939401 | AE1-172 C O1 | 50/50 | 23.92 MW | 23.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 939402 | AE1-172 E O1 | 50/50 | 112.22 MW | 112.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 21.86 MW | 21.86 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 6.82 MW | 6.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 45.64 MW | 45.64 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942601 | AE2-276 | Adder | 2.71 MW | 2.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 4.96 MW | 4.96 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 23.22 MW | 23.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945391 | AF1-204 C O1 | Adder | 3.3 MW | 2.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945392 | AF1-204 E O1 | Adder | 9.91 MW | 8.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 10.99 MW | 10.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.61 MW | 7.61 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.13 MW | 8.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.2 MW | 12.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.01 MW | 2.01 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.08 MW | 3.08 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.13 MW | 8.13 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.2 MW | 12.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 5.49 MW | 5.49 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 36.74 MW | 36.74 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 30.5 MW | 30.5 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 1.6 MW | 1.6 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C O1 | 50/50 | 14.48 MW | 14.48 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E O1 | 50/50 | 67.78 MW | 67.78 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 O1 | 50/50 | 51.41 MW | 51.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 O1 | 50/50 | 51.41 MW | 51.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 O1 | 50/50 | 34.28 MW | 34.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.42 MW | 2.42 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.63 MW | 3.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 0.41 MW | 0.41 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944201 | AF1-088 FTIR | Adder | 63.82 MW | 54.25 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957141 | AF2-008 FTIR | Adder | 31.91 MW | 27.12 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.62 MW | 4.62 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.22 MW | 9.22 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.31 MW | 2.31 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 4.84 MW | 4.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990271 | J1263 | External Queue | 30.69 MW | 30.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990351 | J1289 C | External Queue | 2.43 MW | 2.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 15.53 MW | 15.53 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 29.24 MW | 29.24 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.2 MW | 2.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 11.92 MW | 11.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.43 MW | 7.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 40.17 MW | 40.17 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 | External Queue | 80.35 MW | 80.35 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 | External Queue | 24.0 MW | 24.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 | External Queue | 9.28 MW | 9.28 MW |
| Details for AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 3.89 MW | 3.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 4.0 MW | 4.0 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 4.47 MW | 4.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 4.47 MW | 4.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 3.62 MW | 3.62 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 3.51 MW | 3.51 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 276615 | W2-048 GEN | 80/20 | 4.99 MW | 4.99 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 276621 | X2-022 GEN | 80/20 | 14.21 MW | 14.21 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 17.72 MW | 17.72 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 17.72 MW | 17.72 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 26.87 MW | 26.87 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 26.87 MW | 26.87 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 293798 | W4-005 E | 80/20 | 24.23 MW | 24.23 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 20.82 MW | 20.82 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 3.89 MW | 3.89 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 26.03 MW | 26.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 3.92 MW | 3.92 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 924262 | AB2-070 E O1 | 80/20 | 23.77 MW | 23.77 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 3.8 MW | 3.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 925772 | AC1-053 E | 80/20 | 25.45 MW | 25.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 6.68 MW | 6.68 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 20.93 MW | 20.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 98.19 MW | 98.19 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 14.96 MW | 14.96 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 4.67 MW | 4.67 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 31.24 MW | 31.24 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 3.47 MW | 3.47 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 944222 | AF1-090 E O1 | 80/20 | 16.26 MW | 16.26 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 7.69 MW | 7.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 5.33 MW | 5.33 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 5.59 MW | 5.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 8.39 MW | 8.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 1.39 MW | 1.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 2.14 MW | 2.14 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 5.59 MW | 5.59 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 8.39 MW | 8.39 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 3.8 MW | 3.8 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 963832 | AG1-236 E | 80/20 | 25.45 MW | 25.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 20.97 MW | 20.97 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 1.11 MW | 1.11 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C O1 | 80/20 | 9.98 MW | 9.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965342 | AG1-399 E O1 | 80/20 | 46.73 MW | 46.73 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 O1 | 80/20 | 35.45 MW | 35.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 O1 | 80/20 | 35.45 MW | 35.45 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 O1 | 80/20 | 23.63 MW | 23.63 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 1.69 MW | 1.69 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 965912 | AG1-460 E | 80/20 | 2.54 MW | 2.54 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 957382 | AF2-032 E | 80/20 | 0.28 MW | 0.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 957373 | AF2-031 BAT | 80/20 | 1.23 MW | 1.23 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 958013 | AF2-095 BAT | 80/20 | 4.06 MW | 4.06 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 958023 | AF2-096 BAT | 80/20 | 8.46 MW | 8.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 960603 | AF2-351 BAT | 80/20 | 2.03 MW | 2.03 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 961503 | AF2-441 BAT | 80/20 | 12.76 MW | 12.76 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 964362 | AG1-298 BAT | 80/20 | 31.81 MW | 31.81 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 966093 | AG1-478 BAT | 80/20 | 0.55 MW | 0.55 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 966433 | AG1-512 BAT | 80/20 | 2.4 MW | 2.4 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 966652 | AG1-535 BAT | 80/20 | 5.28 MW | 5.28 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 990056 | J1201 | External Queue | 3.2 MW | 3.2 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 990351 | J1289 C | External Queue | 1.71 MW | 1.71 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 990856 | J1408 | External Queue | 10.46 MW | 10.46 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 955402 | J1022 E | External Queue | 19.43 MW | 19.43 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 955711 | J1055 C | External Queue | 1.55 MW | 1.55 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 955712 | J1055 E | External Queue | 8.36 MW | 8.36 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 956281 | J1115 C | External Queue | 4.98 MW | 4.98 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 956282 | J1115 E | External Queue | 26.93 MW | 26.93 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 991236 | J1676 | External Queue | 53.84 MW | 53.84 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 991261 | J1713 | External Queue | 15.96 MW | 15.96 MW |
| AE1-172 TAP-AD1-100 TAP 345.0 kV Ckt 1 line l/o Base Case | 991276 | J1725 | External Queue | 6.54 MW | 6.54 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274658 | DRESDEN ;2U | 80/20 | 133.62 MW | 133.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274659 | DRESDEN ;3U | 80/20 | 128.3 MW | 128.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.6 MW | 1.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274848 | CAMPGROVE;RU | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274849 | CRESCENT ;1U | 80/20 | 0.49 MW | 0.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274850 | MENDOTA H;RU | 80/20 | 0.73 MW | 0.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274851 | PROVIDENC;RU | 80/20 | 0.51 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274853 | TWINGROVE;U1 | 80/20 | 1.46 MW | 1.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274854 | TWINGROVE;U2 | 80/20 | 1.5 MW | 1.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274855 | GSG-6 ;RU | 80/20 | 1.2 MW | 1.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274856 | ECOGROVE ;U1 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274859 | EASYR;U1 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274860 | EASYR;U2 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274863 | CAYUGA RI;1U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274864 | CAYUGA RI;2U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274872 | LEE DEKAL;1U | 80/20 | 2.22 MW | 2.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274877 | BISHOP HL;1U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274878 | BISHOP HL;2U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274879 | MINONK ;1U | 80/20 | 2.21 MW | 2.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274880 | RADFORD R;1U | 80/20 | 1.57 MW | 1.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274887 | PILOT HIL;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274888 | KELLY CRK;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.29 MW | 1.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 274891 | OTTER CRK;1U | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 275149 | KELLYCK ;1E | 80/20 | 8.95 MW | 8.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276156 | O-029 C | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276157 | O-029 C | 80/20 | 0.69 MW | 0.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276158 | O-029 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276615 | W2-048 GEN | 80/20 | 2.41 MW | 2.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 276621 | X2-022 GEN | 80/20 | 6.85 MW | 6.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290021 | O50 E | 80/20 | 8.86 MW | 8.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290051 | GSG-6; E | 80/20 | 4.78 MW | 4.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290108 | LEEDK;1U E | 80/20 | 11.11 MW | 11.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290261 | S-027 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 290265 | S-028 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293061 | N-015 E | 80/20 | 7.02 MW | 7.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293513 | O-009 C1 | 80/20 | 1.17 MW | 1.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293514 | O-009 C2 | 80/20 | 0.59 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293515 | O-009 C3 | 80/20 | 0.66 MW | 0.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293516 | O-009 E1 | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293517 | O-009 E2 | 80/20 | 2.11 MW | 2.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293518 | O-009 E3 | 80/20 | 2.32 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293644 | O22 E1 | 80/20 | 4.77 MW | 4.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293645 | O22 E2 | 80/20 | 9.25 MW | 9.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293715 | O-029 E | 80/20 | 4.44 MW | 4.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293716 | O-029 E | 80/20 | 2.44 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293717 | O-029 E | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293771 | O-035 E | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293777 | CAYUG;1U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293778 | CAYUG;2U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293798 | W4-005 E | 80/20 | 10.52 MW | 10.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 293799 | PILOT HIL;1E | 80/20 | 10.09 MW | 10.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294392 | P-010 E | 80/20 | 8.91 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294401 | BSHIL;1U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294410 | BSHIL;2U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 294763 | P-046 E | 80/20 | 4.26 MW | 4.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295108 | WESTBROOK C | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295109 | WESTBROOK E | 80/20 | 2.88 MW | 2.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295110 | SUBLETTE C | 80/20 | 0.17 MW | 0.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 295111 | SUBLETTE E | 80/20 | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916211 | Z1-072 E | 80/20 | 4.42 MW | 4.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 916221 | Z1-073 E | 80/20 | 2.8 MW | 2.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 917502 | Z2-087 E | 80/20 | 7.66 MW | 7.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 918052 | AA1-018 E OP | 80/20 | 8.42 MW | 8.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924041 | AB2-047 C O1 | 80/20 | 1.43 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924042 | AB2-047 E O1 | 80/20 | 9.58 MW | 9.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924261 | AB2-070 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 924262 | AB2-070 E O1 | 80/20 | 10.82 MW | 10.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925581 | AC1-033 C | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925582 | AC1-033 E | 80/20 | 8.58 MW | 8.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925771 | AC1-053 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 925772 | AC1-053 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926821 | AC1-168 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 926822 | AC1-168 E O1 | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927201 | AC1-214 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 927202 | AC1-214 E O1 | 80/20 | 2.98 MW | 2.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934432 | AD1-067 E | 80/20 | 0.25 MW | 0.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934721 | AD1-100 C | 80/20 | 17.95 MW | 17.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 934722 | AD1-100 E | 80/20 | 83.78 MW | 83.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 935141 | AD1-148 | 80/20 | 3.22 MW | 3.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936371 | AD2-047 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 936372 | AD2-047 E O1 | 80/20 | 21.23 MW | 21.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937001 | AD2-134 C | 80/20 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 937002 | AD2-134 E | 80/20 | 9.24 MW | 9.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938851 | AE1-113 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938852 | AE1-113 E O1 | 80/20 | 25.92 MW | 25.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938861 | AE1-114 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 938862 | AE1-114 E O1 | 80/20 | 12.21 MW | 12.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939321 | AE1-163 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939322 | AE1-163 E O1 | 80/20 | 33.59 MW | 33.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939401 | AE1-172 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 939402 | AE1-172 E O1 | 80/20 | 22.71 MW | 22.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 941731 | AE2-173 O1 | 80/20 | 5.5 MW | 5.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942111 | AE2-223 C | 80/20 | 1.72 MW | 1.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942112 | AE2-223 E | 80/20 | 11.49 MW | 11.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942421 | AE2-255 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942422 | AE2-255 E O1 | 80/20 | 8.31 MW | 8.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942651 | AE2-281 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 942652 | AE2-281 E O1 | 80/20 | 4.8 MW | 4.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943801 | AF1-048 C | 80/20 | 4.36 MW | 4.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 943802 | AF1-048 E | 80/20 | 2.91 MW | 2.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946161 | AF1-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946162 | AF1-281 E O1 | 80/20 | 2.2 MW | 2.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946321 | AF1-296 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946322 | AF1-296 E O1 | 80/20 | 16.86 MW | 16.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946501 | AF1-314 C | 80/20 | 3.96 MW | 3.96 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946502 | AF1-314 E | 80/20 | 18.62 MW | 18.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946541 | AF1-318 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 946542 | AF1-318 E O1 | 80/20 | 24.61 MW | 24.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957331 | AF2-027 C | 80/20 | 2.85 MW | 2.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957332 | AF2-027 E | 80/20 | 4.28 MW | 4.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957371 | AF2-031 C O1 | 80/20 | 1.56 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957372 | AF2-031 E O1 | 80/20 | 2.33 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957401 | AF2-034 C | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957402 | AF2-034 E | 80/20 | 0.9 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957751 | AF2-069 C | 80/20 | 0.22 MW | 0.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957752 | AF2-069 E | 80/20 | 0.7 MW | 0.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957761 | AF2-070 C | 80/20 | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 957762 | AF2-070 E | 80/20 | 1.48 MW | 1.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958011 | AF2-095 C O1 | 80/20 | 6.39 MW | 6.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958021 | AF2-096 C | 80/20 | 11.4 MW | 11.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958341 | AF2-128 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958342 | AF2-128 E O1 | 80/20 | 6.54 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958921 | AF2-183 C | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 958922 | AF2-183 E | 80/20 | 6.22 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959101 | AF2-201 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959102 | AF2-201 E O1 | 80/20 | 15.72 MW | 15.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959611 | AF2-252 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 959612 | AF2-252 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960141 | AF2-305 | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960261 | AF2-317 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960381 | AF2-329 | 80/20 | 6.13 MW | 6.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960601 | AF2-351 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960602 | AF2-351 E O1 | 80/20 | 1.92 MW | 1.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960611 | AF2-352 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 960612 | AF2-352 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961011 | AF2-392 C O1 | 80/20 | 3.62 MW | 3.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961012 | AF2-392 E O1 | 80/20 | 16.95 MW | 16.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961021 | AF2-393 O1 | 80/20 | 7.71 MW | 7.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961031 | AF2-394 O1 | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961501 | AF2-441 C O1 | 80/20 | 14.82 MW | 14.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 961502 | AF2-441 E O1 | 80/20 | 22.23 MW | 22.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962012 | AG1-044 E | 80/20 | 0.07 MW | 0.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962721 | AG1-121 C | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 962722 | AG1-121 E | 80/20 | 24.05 MW | 24.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963831 | AG1-236 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 963832 | AG1-236 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 964361 | AG1-298 O1 | 80/20 | 93.36 MW | 93.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965092 | AG1-374 E | 80/20 | 7.86 MW | 7.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965331 | AG1-398 | 80/20 | 0.5 MW | 0.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965341 | AG1-399 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965342 | AG1-399 E O1 | 80/20 | 18.76 MW | 18.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965351 | AG1-400 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965371 | AG1-402 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965391 | AG1-404 O1 | 80/20 | 9.49 MW | 9.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965661 | AG1-434 C | 80/20 | 3.76 MW | 3.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965662 | AG1-434 E | 80/20 | 17.61 MW | 17.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965671 | AG1-435 C | 80/20 | 3.47 MW | 3.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965672 | AG1-435 E | 80/20 | 16.25 MW | 16.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966091 | AG1-478 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966092 | AG1-478 E | 80/20 | 0.91 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966431 | AG1-512 C | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966432 | AG1-512 E | 80/20 | 3.07 MW | 3.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966441 | AG1-513 C | 80/20 | 0.58 MW | 0.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966442 | AG1-513 E | 80/20 | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966651 | AG1-535 O1 | 80/20 | 16.35 MW | 16.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966821 | AG1-553 C O1 | 80/20 | 7.87 MW | 7.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 966822 | AG1-553 E O1 | 80/20 | 11.81 MW | 11.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 919221 | AA1-146 | 80/20 | 20.06 MW | 20.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965061 | AG1-371 C | 80/20 | 4.07 MW | 4.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965062 | AG1-371 E | 80/20 | 6.1 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965081 | AG1-373 C | 80/20 | 1.35 MW | 1.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 965082 | AG1-373 E | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11215__-S | 945351 | AF1-200 FTIR | 80/20 | 301.12 MW | 301.12 MW |
| Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274658 | DRESDEN ;2U | 80/20 | 133.62 MW | 133.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274659 | DRESDEN ;3U | 80/20 | 128.3 MW | 128.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274847 | GR RIDGE ;BU | 80/20 | 1.6 MW | 1.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274848 | CAMPGROVE;RU | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274849 | CRESCENT ;1U | 80/20 | 0.49 MW | 0.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274850 | MENDOTA H;RU | 80/20 | 0.73 MW | 0.73 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274851 | PROVIDENC;RU | 80/20 | 0.51 MW | 0.51 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274853 | TWINGROVE;U1 | 80/20 | 1.46 MW | 1.46 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274854 | TWINGROVE;U2 | 80/20 | 1.5 MW | 1.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274855 | GSG-6 ;RU | 80/20 | 1.2 MW | 1.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274856 | ECOGROVE ;U1 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274857 | BIG SKY ;U1 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274858 | BIG SKY ;U2 | 80/20 | 0.79 MW | 0.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274859 | EASYR;U1 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274860 | EASYR;U2 E | 80/20 | 5.01 MW | 5.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274861 | TOP CROP ;1U | 80/20 | 1.07 MW | 1.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274862 | TOP CROP ;2U | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274863 | CAYUGA RI;1U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274864 | CAYUGA RI;2U | 80/20 | 1.16 MW | 1.16 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274871 | GR RIDGE ;2U | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274872 | LEE DEKAL;1U | 80/20 | 2.22 MW | 2.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274877 | BISHOP HL;1U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274878 | BISHOP HL;2U | 80/20 | 0.98 MW | 0.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274879 | MINONK ;1U | 80/20 | 2.21 MW | 2.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274880 | RADFORD R;1U | 80/20 | 1.57 MW | 1.57 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274887 | PILOT HIL;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274888 | KELLY CRK;1U | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274889 | BRIGHTSTK;1U | 80/20 | 1.29 MW | 1.29 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 274891 | OTTER CRK;1U | 80/20 | 1.26 MW | 1.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 275149 | KELLYCK ;1E | 80/20 | 8.95 MW | 8.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276156 | O-029 C | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276157 | O-029 C | 80/20 | 0.69 MW | 0.69 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276158 | O-029 C | 80/20 | 1.25 MW | 1.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276615 | W2-048 GEN | 80/20 | 2.41 MW | 2.41 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 276621 | X2-022 GEN | 80/20 | 6.85 MW | 6.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290021 | O50 E | 80/20 | 8.86 MW | 8.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290051 | GSG-6; E | 80/20 | 4.78 MW | 4.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290108 | LEEDK;1U E | 80/20 | 11.11 MW | 11.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290261 | S-027 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 290265 | S-028 E | 80/20 | 6.64 MW | 6.64 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293061 | N-015 E | 80/20 | 7.02 MW | 7.02 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293513 | O-009 C1 | 80/20 | 1.17 MW | 1.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293514 | O-009 C2 | 80/20 | 0.59 MW | 0.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293515 | O-009 C3 | 80/20 | 0.66 MW | 0.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293516 | O-009 E1 | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293517 | O-009 E2 | 80/20 | 2.11 MW | 2.11 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293518 | O-009 E3 | 80/20 | 2.32 MW | 2.32 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293644 | O22 E1 | 80/20 | 4.77 MW | 4.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293645 | O22 E2 | 80/20 | 9.25 MW | 9.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293715 | O-029 E | 80/20 | 4.44 MW | 4.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293716 | O-029 E | 80/20 | 2.44 MW | 2.44 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293717 | O-029 E | 80/20 | 2.24 MW | 2.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293771 | O-035 E | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293777 | CAYUG;1U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293778 | CAYUG;2U E | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293798 | W4-005 E | 80/20 | 10.52 MW | 10.52 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 293799 | PILOT HIL;1E | 80/20 | 10.09 MW | 10.09 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294392 | P-010 E | 80/20 | 8.91 MW | 8.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294401 | BSHIL;1U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294410 | BSHIL;2U E | 80/20 | 3.91 MW | 3.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 294763 | P-046 E | 80/20 | 4.26 MW | 4.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295108 | WESTBROOK C | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295109 | WESTBROOK E | 80/20 | 2.88 MW | 2.88 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295110 | SUBLETTE C | 80/20 | 0.17 MW | 0.17 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 295111 | SUBLETTE E | 80/20 | 1.33 MW | 1.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916211 | Z1-072 E | 80/20 | 4.42 MW | 4.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 916221 | Z1-073 E | 80/20 | 2.8 MW | 2.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 917502 | Z2-087 E | 80/20 | 7.66 MW | 7.66 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 918052 | AA1-018 E OP | 80/20 | 8.42 MW | 8.42 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924041 | AB2-047 C O1 | 80/20 | 1.43 MW | 1.43 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924042 | AB2-047 E O1 | 80/20 | 9.58 MW | 9.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924261 | AB2-070 C O1 | 80/20 | 1.79 MW | 1.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 924262 | AB2-070 E O1 | 80/20 | 10.82 MW | 10.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925581 | AC1-033 C | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925582 | AC1-033 E | 80/20 | 8.58 MW | 8.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925771 | AC1-053 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 925772 | AC1-053 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926821 | AC1-168 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 926822 | AC1-168 E O1 | 80/20 | 7.0 MW | 7.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927201 | AC1-214 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 927202 | AC1-214 E O1 | 80/20 | 2.98 MW | 2.98 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934431 | AD1-067 C | 80/20 | 0.06 MW | 0.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934432 | AD1-067 E | 80/20 | 0.25 MW | 0.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934721 | AD1-100 C | 80/20 | 17.95 MW | 17.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 934722 | AD1-100 E | 80/20 | 83.78 MW | 83.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 935141 | AD1-148 | 80/20 | 3.22 MW | 3.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936371 | AD2-047 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 936372 | AD2-047 E O1 | 80/20 | 21.23 MW | 21.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937001 | AD2-134 C | 80/20 | 2.31 MW | 2.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 937002 | AD2-134 E | 80/20 | 9.24 MW | 9.24 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938851 | AE1-113 C O1 | 80/20 | 7.31 MW | 7.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938852 | AE1-113 E O1 | 80/20 | 25.92 MW | 25.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938861 | AE1-114 C O1 | 80/20 | 3.58 MW | 3.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 938862 | AE1-114 E O1 | 80/20 | 12.21 MW | 12.21 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939321 | AE1-163 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939322 | AE1-163 E O1 | 80/20 | 33.59 MW | 33.59 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939401 | AE1-172 C O1 | 80/20 | 4.84 MW | 4.84 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 939402 | AE1-172 E O1 | 80/20 | 22.71 MW | 22.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 941731 | AE2-173 O1 | 80/20 | 5.5 MW | 5.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942111 | AE2-223 C | 80/20 | 1.72 MW | 1.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942112 | AE2-223 E | 80/20 | 11.49 MW | 11.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942421 | AE2-255 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942422 | AE2-255 E O1 | 80/20 | 8.31 MW | 8.31 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942651 | AE2-281 C O1 | 80/20 | 0.78 MW | 0.78 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 942652 | AE2-281 E O1 | 80/20 | 4.8 MW | 4.8 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943801 | AF1-048 C | 80/20 | 4.36 MW | 4.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 943802 | AF1-048 E | 80/20 | 2.91 MW | 2.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946161 | AF1-281 C O1 | 80/20 | 0.39 MW | 0.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946162 | AF1-281 E O1 | 80/20 | 2.2 MW | 2.2 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946321 | AF1-296 C O1 | 80/20 | 3.6 MW | 3.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946322 | AF1-296 E O1 | 80/20 | 16.86 MW | 16.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946501 | AF1-314 C | 80/20 | 3.96 MW | 3.96 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946502 | AF1-314 E | 80/20 | 18.62 MW | 18.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946541 | AF1-318 C O1 | 80/20 | 5.26 MW | 5.26 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 946542 | AF1-318 E O1 | 80/20 | 24.61 MW | 24.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957331 | AF2-027 C | 80/20 | 2.85 MW | 2.85 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957332 | AF2-027 E | 80/20 | 4.28 MW | 4.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957371 | AF2-031 C O1 | 80/20 | 1.56 MW | 1.56 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957372 | AF2-031 E O1 | 80/20 | 2.33 MW | 2.33 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957401 | AF2-034 C | 80/20 | 0.6 MW | 0.6 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957402 | AF2-034 E | 80/20 | 0.9 MW | 0.9 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957751 | AF2-069 C | 80/20 | 0.22 MW | 0.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957752 | AF2-069 E | 80/20 | 0.7 MW | 0.7 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957761 | AF2-070 C | 80/20 | 0.3 MW | 0.3 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 957762 | AF2-070 E | 80/20 | 1.48 MW | 1.48 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958011 | AF2-095 C O1 | 80/20 | 6.39 MW | 6.39 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958021 | AF2-096 C | 80/20 | 11.4 MW | 11.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958341 | AF2-128 C O1 | 80/20 | 1.4 MW | 1.4 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958342 | AF2-128 E O1 | 80/20 | 6.54 MW | 6.54 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958921 | AF2-183 C | 80/20 | 4.15 MW | 4.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 958922 | AF2-183 E | 80/20 | 6.22 MW | 6.22 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959101 | AF2-201 C O1 | 80/20 | 5.47 MW | 5.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959102 | AF2-201 E O1 | 80/20 | 15.72 MW | 15.72 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959351 | AF2-226 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959352 | AF2-226 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959611 | AF2-252 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 959612 | AF2-252 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960141 | AF2-305 | 80/20 | 0.63 MW | 0.63 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960261 | AF2-317 | 80/20 | 1.03 MW | 1.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960281 | AF2-319 C | 80/20 | 2.92 MW | 2.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960282 | AF2-319 E | 80/20 | 4.38 MW | 4.38 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960381 | AF2-329 | 80/20 | 6.13 MW | 6.13 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960601 | AF2-351 C O1 | 80/20 | 1.28 MW | 1.28 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960602 | AF2-351 E O1 | 80/20 | 1.92 MW | 1.92 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960611 | AF2-352 C | 80/20 | 2.1 MW | 2.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 960612 | AF2-352 E | 80/20 | 3.15 MW | 3.15 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961011 | AF2-392 C O1 | 80/20 | 3.62 MW | 3.62 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961012 | AF2-392 E O1 | 80/20 | 16.95 MW | 16.95 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961021 | AF2-393 O1 | 80/20 | 7.71 MW | 7.71 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961031 | AF2-394 O1 | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961501 | AF2-441 C O1 | 80/20 | 14.82 MW | 14.82 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 961502 | AF2-441 E O1 | 80/20 | 22.23 MW | 22.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962012 | AG1-044 E | 80/20 | 0.07 MW | 0.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962721 | AG1-121 C | 80/20 | 5.14 MW | 5.14 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 962722 | AG1-121 E | 80/20 | 24.05 MW | 24.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963831 | AG1-236 C | 80/20 | 1.76 MW | 1.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 963832 | AG1-236 E | 80/20 | 11.79 MW | 11.79 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 964361 | AG1-298 O1 | 80/20 | 93.36 MW | 93.36 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965092 | AG1-374 E | 80/20 | 7.86 MW | 7.86 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965331 | AG1-398 | 80/20 | 0.5 MW | 0.5 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965341 | AG1-399 C O1 | 80/20 | 4.01 MW | 4.01 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965342 | AG1-399 E O1 | 80/20 | 18.76 MW | 18.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965351 | AG1-400 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965371 | AG1-402 O1 | 80/20 | 14.23 MW | 14.23 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965391 | AG1-404 O1 | 80/20 | 9.49 MW | 9.49 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965661 | AG1-434 C | 80/20 | 3.76 MW | 3.76 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965662 | AG1-434 E | 80/20 | 17.61 MW | 17.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965671 | AG1-435 C | 80/20 | 3.47 MW | 3.47 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965672 | AG1-435 E | 80/20 | 16.25 MW | 16.25 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966091 | AG1-478 C | 80/20 | 0.61 MW | 0.61 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966092 | AG1-478 E | 80/20 | 0.91 MW | 0.91 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966431 | AG1-512 C | 80/20 | 2.05 MW | 2.05 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966432 | AG1-512 E | 80/20 | 3.07 MW | 3.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966441 | AG1-513 C | 80/20 | 0.58 MW | 0.58 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966442 | AG1-513 E | 80/20 | 0.87 MW | 0.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966651 | AG1-535 O1 | 80/20 | 16.35 MW | 16.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966821 | AG1-553 C O1 | 80/20 | 7.87 MW | 7.87 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 966822 | AG1-553 E O1 | 80/20 | 11.81 MW | 11.81 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 919221 | AA1-146 | 80/20 | 20.06 MW | 20.06 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965061 | AG1-371 C | 80/20 | 4.07 MW | 4.07 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965062 | AG1-371 E | 80/20 | 6.1 MW | 6.1 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965081 | AG1-373 C | 80/20 | 1.35 MW | 1.35 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 965082 | AG1-373 E | 80/20 | 2.03 MW | 2.03 MW |
| 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681 | 945351 | AF1-200 FTIR | 80/20 | 301.12 MW | 301.12 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274853 | TWINGROVE;U1 | 80/20 | 5.64 MW | 5.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274854 | TWINGROVE;U2 | 80/20 | 5.8 MW | 5.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274863 | CAYUGA RI;1U | 80/20 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274864 | CAYUGA RI;2U | 80/20 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274880 | RADFORD R;1U | 80/20 | 5.2 MW | 5.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274889 | BRIGHTSTK;1U | 80/20 | 5.11 MW | 5.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276615 | W2-048 GEN | 80/20 | 7.12 MW | 7.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276621 | X2-022 GEN | 80/20 | 20.26 MW | 20.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290261 | S-027 E | 80/20 | 25.68 MW | 25.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290265 | S-028 E | 80/20 | 25.68 MW | 25.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293777 | CAYUG;1U E | 80/20 | 32.81 MW | 32.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293778 | CAYUG;2U E | 80/20 | 32.81 MW | 32.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293798 | W4-005 E | 80/20 | 34.79 MW | 34.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 917502 | Z2-087 E | 80/20 | 30.35 MW | 30.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924041 | AB2-047 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924042 | AB2-047 E O1 | 80/20 | 37.94 MW | 37.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924261 | AB2-070 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924262 | AB2-070 E O1 | 80/20 | 34.07 MW | 34.07 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925771 | AC1-053 C | 80/20 | 5.44 MW | 5.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925772 | AC1-053 E | 80/20 | 36.42 MW | 36.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 935141 | AD1-148 | 80/20 | 9.52 MW | 9.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 941731 | AE2-173 O1 | 80/20 | 21.8 MW | 21.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942111 | AE2-223 C | 80/20 | 6.8 MW | 6.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942112 | AE2-223 E | 80/20 | 45.52 MW | 45.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942601 | AE2-276 | 80/20 | 2.69 MW | 2.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944221 | AF1-090 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944222 | AF1-090 E O1 | 80/20 | 22.91 MW | 22.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945391 | AF1-204 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945392 | AF1-204 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945871 | AF1-252 O1 | 80/20 | 10.85 MW | 10.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945881 | AF1-253 | 80/20 | 7.51 MW | 7.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959611 | AF2-252 C | 80/20 | 8.11 MW | 8.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959612 | AF2-252 E | 80/20 | 12.16 MW | 12.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960141 | AF2-305 | 80/20 | 1.99 MW | 1.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960261 | AF2-317 | 80/20 | 3.05 MW | 3.05 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960611 | AF2-352 C | 80/20 | 8.11 MW | 8.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960612 | AF2-352 E | 80/20 | 12.16 MW | 12.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963831 | AG1-236 C | 80/20 | 5.44 MW | 5.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963832 | AG1-236 E | 80/20 | 36.42 MW | 36.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965092 | AG1-374 E | 80/20 | 30.4 MW | 30.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965341 | AG1-399 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965342 | AG1-399 E O1 | 80/20 | 67.45 MW | 67.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965351 | AG1-400 O1 | 80/20 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965371 | AG1-402 O1 | 80/20 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965391 | AG1-404 O1 | 80/20 | 34.11 MW | 34.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965911 | AG1-460 C | 80/20 | 2.39 MW | 2.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965912 | AG1-460 E | 80/20 | 3.59 MW | 3.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957382 | AF2-032 E | 80/20 | 0.4 MW | 0.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276172 | Z1-108 BAT | 80/20 | 1.22 MW | 1.22 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 920273 | AA2-123 BAT | 80/20 | 1.11 MW | 1.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 943803 | AF1-048 BAT | 80/20 | 2.88 MW | 2.88 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944201 | AF1-088 FTIR | 80/20 | 53.82 MW | 53.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957141 | AF2-008 FTIR | 80/20 | 26.91 MW | 26.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957333 | AF2-027 BAT | 80/20 | 3.09 MW | 3.09 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957373 | AF2-031 BAT | 80/20 | 1.64 MW | 1.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957403 | AF2-034 BAT | 80/20 | 0.71 MW | 0.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958013 | AF2-095 BAT | 80/20 | 4.56 MW | 4.56 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958023 | AF2-096 BAT | 80/20 | 9.11 MW | 9.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959353 | AF2-226 BAT | 80/20 | 2.64 MW | 2.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960283 | AF2-319 BAT | 80/20 | 2.64 MW | 2.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960382 | AF2-329 BAT | 80/20 | 2.94 MW | 2.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960603 | AF2-351 BAT | 80/20 | 2.28 MW | 2.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 961503 | AF2-441 BAT | 80/20 | 17.02 MW | 17.02 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 964362 | AG1-298 BAT | 80/20 | 42.2 MW | 42.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966093 | AG1-478 BAT | 80/20 | 0.85 MW | 0.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966433 | AG1-512 BAT | 80/20 | 3.35 MW | 3.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966443 | AG1-513 BAT | 80/20 | 0.7 MW | 0.7 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966652 | AG1-535 BAT | 80/20 | 6.98 MW | 6.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.64 MW | 5.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.8 MW | 5.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274863 | CAYUGA RI;1U | 80/20 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274864 | CAYUGA RI;2U | 80/20 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274880 | RADFORD R;1U | 80/20 | 5.2 MW | 5.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 5.11 MW | 5.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276615 | W2-048 GEN | 80/20 | 7.12 MW | 7.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276621 | X2-022 GEN | 80/20 | 20.26 MW | 20.26 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290261 | S-027 E | 80/20 | 25.68 MW | 25.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290265 | S-028 E | 80/20 | 25.68 MW | 25.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293777 | CAYUG;1U E | 80/20 | 32.81 MW | 32.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293778 | CAYUG;2U E | 80/20 | 32.81 MW | 32.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293798 | W4-005 E | 80/20 | 34.79 MW | 34.79 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 917502 | Z2-087 E | 80/20 | 30.35 MW | 30.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.67 MW | 5.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924042 | AB2-047 E O1 | 80/20 | 37.94 MW | 37.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924262 | AB2-070 E O1 | 80/20 | 34.07 MW | 34.07 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925771 | AC1-053 C | 80/20 | 5.44 MW | 5.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925772 | AC1-053 E | 80/20 | 36.42 MW | 36.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 935141 | AD1-148 | 80/20 | 9.52 MW | 9.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 941731 | AE2-173 O1 | 80/20 | 21.8 MW | 21.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942111 | AE2-223 C | 80/20 | 6.8 MW | 6.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942112 | AE2-223 E | 80/20 | 45.52 MW | 45.52 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942601 | AE2-276 | 80/20 | 2.69 MW | 2.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.89 MW | 4.89 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944222 | AF1-090 E O1 | 80/20 | 22.91 MW | 22.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945391 | AF1-204 C O1 | 80/20 | 3.28 MW | 3.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945392 | AF1-204 E O1 | 80/20 | 9.85 MW | 9.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945871 | AF1-252 O1 | 80/20 | 10.85 MW | 10.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945881 | AF1-253 | 80/20 | 7.51 MW | 7.51 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959611 | AF2-252 C | 80/20 | 8.11 MW | 8.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959612 | AF2-252 E | 80/20 | 12.16 MW | 12.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960141 | AF2-305 | 80/20 | 1.99 MW | 1.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960261 | AF2-317 | 80/20 | 3.05 MW | 3.05 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960611 | AF2-352 C | 80/20 | 8.11 MW | 8.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960612 | AF2-352 E | 80/20 | 12.16 MW | 12.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963831 | AG1-236 C | 80/20 | 5.44 MW | 5.44 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963832 | AG1-236 E | 80/20 | 36.42 MW | 36.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965092 | AG1-374 E | 80/20 | 30.4 MW | 30.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965341 | AG1-399 C O1 | 80/20 | 14.41 MW | 14.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965342 | AG1-399 E O1 | 80/20 | 67.45 MW | 67.45 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965351 | AG1-400 O1 | 80/20 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965371 | AG1-402 O1 | 80/20 | 51.16 MW | 51.16 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965391 | AG1-404 O1 | 80/20 | 34.11 MW | 34.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965911 | AG1-460 C | 80/20 | 2.39 MW | 2.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965912 | AG1-460 E | 80/20 | 3.59 MW | 3.59 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957382 | AF2-032 E | 80/20 | 0.4 MW | 0.4 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276172 | Z1-108 BAT | 80/20 | 1.22 MW | 1.22 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 920273 | AA2-123 BAT | 80/20 | 1.11 MW | 1.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 943803 | AF1-048 BAT | 80/20 | 2.88 MW | 2.88 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944201 | AF1-088 FTIR | 80/20 | 53.82 MW | 53.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957141 | AF2-008 FTIR | 80/20 | 26.91 MW | 26.91 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957333 | AF2-027 BAT | 80/20 | 3.09 MW | 3.09 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957373 | AF2-031 BAT | 80/20 | 1.64 MW | 1.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957403 | AF2-034 BAT | 80/20 | 0.71 MW | 0.71 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958013 | AF2-095 BAT | 80/20 | 4.56 MW | 4.56 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958023 | AF2-096 BAT | 80/20 | 9.11 MW | 9.11 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959353 | AF2-226 BAT | 80/20 | 2.64 MW | 2.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960283 | AF2-319 BAT | 80/20 | 2.64 MW | 2.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960382 | AF2-329 BAT | 80/20 | 2.94 MW | 2.94 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960603 | AF2-351 BAT | 80/20 | 2.28 MW | 2.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 961503 | AF2-441 BAT | 80/20 | 17.02 MW | 17.02 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 964362 | AG1-298 BAT | 80/20 | 42.2 MW | 42.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966093 | AG1-478 BAT | 80/20 | 0.85 MW | 0.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966433 | AG1-512 BAT | 80/20 | 3.35 MW | 3.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966443 | AG1-513 BAT | 80/20 | 0.7 MW | 0.7 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966652 | AG1-535 BAT | 80/20 | 6.98 MW | 6.98 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 5.66 MW | 5.66 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 5.82 MW | 5.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274863 | CAYUGA RI;1U | 50/50 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274864 | CAYUGA RI;2U | 50/50 | 5.46 MW | 5.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 5.24 MW | 5.24 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 5.12 MW | 5.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 7.19 MW | 7.19 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 20.46 MW | 20.46 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 25.77 MW | 25.77 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 25.77 MW | 25.77 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293777 | CAYUG;1U E | 50/50 | 32.82 MW | 32.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293778 | CAYUG;2U E | 50/50 | 32.82 MW | 32.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 35.04 MW | 35.04 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 30.43 MW | 30.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 5.68 MW | 5.68 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 38.03 MW | 38.03 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 5.67 MW | 5.67 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 34.35 MW | 34.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 5.49 MW | 5.49 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 36.74 MW | 36.74 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.62 MW | 9.62 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 21.86 MW | 21.86 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 6.82 MW | 6.82 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 45.64 MW | 45.64 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942601 | AE2-276 | Adder | 2.71 MW | 2.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 4.96 MW | 4.96 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 23.22 MW | 23.22 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945391 | AF1-204 C O1 | Adder | 3.3 MW | 2.81 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945392 | AF1-204 E O1 | Adder | 9.91 MW | 8.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 10.99 MW | 10.99 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.61 MW | 7.61 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.13 MW | 8.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.2 MW | 12.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.01 MW | 2.01 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.08 MW | 3.08 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.13 MW | 8.13 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.2 MW | 12.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 5.49 MW | 5.49 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 36.74 MW | 36.74 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 30.5 MW | 30.5 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 1.6 MW | 1.6 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C O1 | 50/50 | 14.48 MW | 14.48 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E O1 | 50/50 | 67.78 MW | 67.78 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 O1 | 50/50 | 51.41 MW | 51.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 O1 | 50/50 | 51.41 MW | 51.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 O1 | 50/50 | 34.28 MW | 34.28 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.42 MW | 2.42 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.63 MW | 3.63 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 0.41 MW | 0.41 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944201 | AF1-088 FTIR | Adder | 63.82 MW | 54.25 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957141 | AF2-008 FTIR | Adder | 31.91 MW | 27.12 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.62 MW | 4.62 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.22 MW | 9.22 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.31 MW | 2.31 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 4.84 MW | 4.84 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990271 | J1263 | External Queue | 30.69 MW | 30.69 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990351 | J1289 C | External Queue | 2.43 MW | 2.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 15.53 MW | 15.53 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 29.24 MW | 29.24 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.2 MW | 2.2 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 11.92 MW | 11.92 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.43 MW | 7.43 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 40.17 MW | 40.17 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 | External Queue | 80.35 MW | 80.35 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 | External Queue | 24.0 MW | 24.0 MW |
| LORETTO ; B-AE1-172 TAP 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 | External Queue | 9.28 MW | 9.28 MW |
| Details for AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274659 | DRESDEN ;3U | 80/20 | 64.48 MW | 64.48 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274847 | GR RIDGE ;BU | 80/20 | 1.32 MW | 1.32 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274848 | CAMPGROVE;RU | 80/20 | 0.7 MW | 0.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274849 | CRESCENT ;1U | 80/20 | 0.28 MW | 0.28 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274850 | MENDOTA H;RU | 80/20 | 0.32 MW | 0.32 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274851 | PROVIDENC;RU | 80/20 | 0.29 MW | 0.29 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274853 | TWINGROVE;U1 | 80/20 | 2.1 MW | 2.1 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274854 | TWINGROVE;U2 | 80/20 | 2.16 MW | 2.16 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274855 | GSG-6 ;RU | 80/20 | 0.52 MW | 0.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274856 | ECOGROVE ;U1 | 80/20 | 0.43 MW | 0.43 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274857 | BIG SKY ;U1 | 80/20 | 0.34 MW | 0.34 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274858 | BIG SKY ;U2 | 80/20 | 0.34 MW | 0.34 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274859 | EASYR;U1 E | 80/20 | 2.15 MW | 2.15 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274860 | EASYR;U2 E | 80/20 | 2.15 MW | 2.15 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274863 | CAYUGA RI;1U | 80/20 | 2.23 MW | 2.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274864 | CAYUGA RI;2U | 80/20 | 2.23 MW | 2.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274871 | GR RIDGE ;2U | 80/20 | 0.49 MW | 0.49 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274872 | LEE DEKAL;1U | 80/20 | 0.96 MW | 0.96 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274877 | BISHOP HL;1U | 80/20 | 0.54 MW | 0.54 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274878 | BISHOP HL;2U | 80/20 | 0.54 MW | 0.54 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274880 | RADFORD R;1U | 80/20 | 2.01 MW | 2.01 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274887 | PILOT HIL;1U | 80/20 | 1.81 MW | 1.81 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274888 | KELLY CRK;1U | 80/20 | 1.81 MW | 1.81 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 274889 | BRIGHTSTK;1U | 80/20 | 1.89 MW | 1.89 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 275149 | KELLYCK ;1E | 80/20 | 7.25 MW | 7.25 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276156 | O-029 C | 80/20 | 0.3 MW | 0.3 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276157 | O-029 C | 80/20 | 0.32 MW | 0.32 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276158 | O-029 C | 80/20 | 0.58 MW | 0.58 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276615 | W2-048 GEN | 80/20 | 2.85 MW | 2.85 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 276621 | X2-022 GEN | 80/20 | 8.1 MW | 8.1 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290051 | GSG-6; E | 80/20 | 2.08 MW | 2.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290108 | LEEDK;1U E | 80/20 | 4.81 MW | 4.81 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290261 | S-027 E | 80/20 | 9.56 MW | 9.56 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 290265 | S-028 E | 80/20 | 9.56 MW | 9.56 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293061 | N-015 E | 80/20 | 5.77 MW | 5.77 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293513 | O-009 C1 | 80/20 | 0.55 MW | 0.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293514 | O-009 C2 | 80/20 | 0.28 MW | 0.28 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293515 | O-009 C3 | 80/20 | 0.31 MW | 0.31 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293516 | O-009 E1 | 80/20 | 1.95 MW | 1.95 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293517 | O-009 E2 | 80/20 | 0.99 MW | 0.99 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293518 | O-009 E3 | 80/20 | 1.09 MW | 1.09 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293715 | O-029 E | 80/20 | 2.08 MW | 2.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293716 | O-029 E | 80/20 | 1.14 MW | 1.14 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293717 | O-029 E | 80/20 | 1.05 MW | 1.05 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293771 | O-035 E | 80/20 | 1.67 MW | 1.67 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293777 | CAYUG;1U E | 80/20 | 13.41 MW | 13.41 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293778 | CAYUG;2U E | 80/20 | 13.41 MW | 13.41 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293798 | W4-005 E | 80/20 | 13.43 MW | 13.43 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 293799 | PILOT HIL;1E | 80/20 | 8.17 MW | 8.17 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294392 | P-010 E | 80/20 | 7.33 MW | 7.33 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294401 | BSHIL;1U E | 80/20 | 2.14 MW | 2.14 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294410 | BSHIL;2U E | 80/20 | 2.14 MW | 2.14 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 294763 | P-046 E | 80/20 | 1.78 MW | 1.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295108 | WESTBROOK C | 80/20 | 0.17 MW | 0.17 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295109 | WESTBROOK E | 80/20 | 1.25 MW | 1.25 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295110 | SUBLETTE C | 80/20 | 0.07 MW | 0.07 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 295111 | SUBLETTE E | 80/20 | 0.59 MW | 0.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 916211 | Z1-072 E | 80/20 | 2.52 MW | 2.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 916221 | Z1-073 E | 80/20 | 1.22 MW | 1.22 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 917502 | Z2-087 E | 80/20 | 11.22 MW | 11.22 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924041 | AB2-047 C O1 | 80/20 | 2.1 MW | 2.1 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924042 | AB2-047 E O1 | 80/20 | 14.03 MW | 14.03 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924261 | AB2-070 C O1 | 80/20 | 2.21 MW | 2.21 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 924262 | AB2-070 E O1 | 80/20 | 13.37 MW | 13.37 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925581 | AC1-033 C | 80/20 | 0.7 MW | 0.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925582 | AC1-033 E | 80/20 | 4.7 MW | 4.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925771 | AC1-053 C | 80/20 | 2.15 MW | 2.15 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 925772 | AC1-053 E | 80/20 | 14.37 MW | 14.37 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 926821 | AC1-168 C O1 | 80/20 | 0.67 MW | 0.67 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 926822 | AC1-168 E O1 | 80/20 | 4.46 MW | 4.46 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 927201 | AC1-214 C O1 | 80/20 | 0.54 MW | 0.54 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 927202 | AC1-214 E O1 | 80/20 | 1.7 MW | 1.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934432 | AD1-067 E | 80/20 | 0.11 MW | 0.11 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934721 | AD1-100 C | 80/20 | 36.88 MW | 36.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 934722 | AD1-100 E | 80/20 | 172.09 MW | 172.09 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 935141 | AD1-148 | 80/20 | 3.81 MW | 3.81 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936371 | AD2-047 C O1 | 80/20 | 3.52 MW | 3.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 936372 | AD2-047 E O1 | 80/20 | 17.19 MW | 17.19 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 937001 | AD2-134 C | 80/20 | 1.01 MW | 1.01 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 937002 | AD2-134 E | 80/20 | 4.02 MW | 4.02 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938861 | AE1-114 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 938862 | AE1-114 E O1 | 80/20 | 5.22 MW | 5.22 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939401 | AE1-172 C O1 | 80/20 | 10.21 MW | 10.21 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 939402 | AE1-172 E O1 | 80/20 | 47.9 MW | 47.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 941731 | AE2-173 O1 | 80/20 | 8.06 MW | 8.06 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942111 | AE2-223 C | 80/20 | 2.52 MW | 2.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 942112 | AE2-223 E | 80/20 | 16.83 MW | 16.83 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 943801 | AF1-048 C | 80/20 | 1.72 MW | 1.72 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 943802 | AF1-048 E | 80/20 | 1.15 MW | 1.15 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 944221 | AF1-090 C O1 | 80/20 | 1.98 MW | 1.98 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 944222 | AF1-090 E O1 | 80/20 | 9.29 MW | 9.29 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 945871 | AF1-252 O1 | 80/20 | 4.4 MW | 4.4 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 945881 | AF1-253 | 80/20 | 3.04 MW | 3.04 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946161 | AF1-281 C O1 | 80/20 | 0.17 MW | 0.17 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946162 | AF1-281 E O1 | 80/20 | 0.95 MW | 0.95 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946321 | AF1-296 C O1 | 80/20 | 1.65 MW | 1.65 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946322 | AF1-296 E O1 | 80/20 | 7.73 MW | 7.73 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946501 | AF1-314 C | 80/20 | 1.66 MW | 1.66 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946502 | AF1-314 E | 80/20 | 7.78 MW | 7.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946541 | AF1-318 C O1 | 80/20 | 3.18 MW | 3.18 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 946542 | AF1-318 E O1 | 80/20 | 14.88 MW | 14.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957752 | AF2-069 E | 80/20 | 0.4 MW | 0.4 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957762 | AF2-070 E | 80/20 | 0.85 MW | 0.85 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958011 | AF2-095 C O1 | 80/20 | 5.18 MW | 5.18 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958021 | AF2-096 C | 80/20 | 12.05 MW | 12.05 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958341 | AF2-128 C O1 | 80/20 | 0.85 MW | 0.85 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958342 | AF2-128 E O1 | 80/20 | 4.0 MW | 4.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958921 | AF2-183 C | 80/20 | 1.79 MW | 1.79 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 958922 | AF2-183 E | 80/20 | 2.69 MW | 2.69 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959101 | AF2-201 C O1 | 80/20 | 2.29 MW | 2.29 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959102 | AF2-201 E O1 | 80/20 | 6.57 MW | 6.57 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959611 | AF2-252 C | 80/20 | 3.02 MW | 3.02 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 959612 | AF2-252 E | 80/20 | 4.53 MW | 4.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960141 | AF2-305 | 80/20 | 0.78 MW | 0.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960261 | AF2-317 | 80/20 | 1.22 MW | 1.22 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960381 | AF2-329 | 80/20 | 2.8 MW | 2.8 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960601 | AF2-351 C O1 | 80/20 | 1.04 MW | 1.04 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960602 | AF2-351 E O1 | 80/20 | 1.55 MW | 1.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960611 | AF2-352 C | 80/20 | 3.02 MW | 3.02 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 960612 | AF2-352 E | 80/20 | 4.53 MW | 4.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961011 | AF2-392 C O1 | 80/20 | 1.6 MW | 1.6 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961012 | AF2-392 E O1 | 80/20 | 7.51 MW | 7.51 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961021 | AF2-393 O1 | 80/20 | 3.42 MW | 3.42 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 961031 | AF2-394 O1 | 80/20 | 2.28 MW | 2.28 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 962012 | AG1-044 E | 80/20 | 0.03 MW | 0.03 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 962721 | AG1-121 C | 80/20 | 2.97 MW | 2.97 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 962722 | AG1-121 E | 80/20 | 13.9 MW | 13.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 963831 | AG1-236 C | 80/20 | 2.15 MW | 2.15 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 963832 | AG1-236 E | 80/20 | 14.37 MW | 14.37 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965092 | AG1-374 E | 80/20 | 11.32 MW | 11.32 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965331 | AG1-398 | 80/20 | 0.62 MW | 0.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965341 | AG1-399 C O1 | 80/20 | 5.45 MW | 5.45 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965342 | AG1-399 E O1 | 80/20 | 25.52 MW | 25.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965351 | AG1-400 O1 | 80/20 | 19.36 MW | 19.36 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965371 | AG1-402 O1 | 80/20 | 19.36 MW | 19.36 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965391 | AG1-404 O1 | 80/20 | 12.9 MW | 12.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965661 | AG1-434 C | 80/20 | 1.61 MW | 1.61 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965662 | AG1-434 E | 80/20 | 7.53 MW | 7.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965671 | AG1-435 C | 80/20 | 1.97 MW | 1.97 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965672 | AG1-435 E | 80/20 | 9.21 MW | 9.21 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965911 | AG1-460 C | 80/20 | 0.98 MW | 0.98 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965912 | AG1-460 E | 80/20 | 1.47 MW | 1.47 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966091 | AG1-478 C | 80/20 | 0.33 MW | 0.33 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966092 | AG1-478 E | 80/20 | 0.5 MW | 0.5 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966441 | AG1-513 C | 80/20 | 0.24 MW | 0.24 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966442 | AG1-513 E | 80/20 | 0.36 MW | 0.36 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966821 | AG1-553 C O1 | 80/20 | 3.62 MW | 3.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 966822 | AG1-553 E O1 | 80/20 | 5.44 MW | 5.44 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 919221 | AA1-146 | 80/20 | 8.83 MW | 8.83 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 957382 | AF2-032 E | 80/20 | 0.17 MW | 0.17 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965061 | AG1-371 C | 80/20 | 1.72 MW | 1.72 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965062 | AG1-371 E | 80/20 | 2.58 MW | 2.58 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965081 | AG1-373 C | 80/20 | 0.57 MW | 0.57 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 965082 | AG1-373 E | 80/20 | 0.86 MW | 0.86 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_765-L11216__-S | 945351 | AF1-200 FTIR | 80/20 | 174.89 MW | 174.89 MW |
| Details for AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274847 | GR RIDGE ;BU | 80/20 | 0.74 MW | 0.74 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274853 | TWINGROVE;U1 | 80/20 | 2.54 MW | 2.54 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274854 | TWINGROVE;U2 | 80/20 | 2.62 MW | 2.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274863 | CAYUGA RI;1U | 80/20 | 2.46 MW | 2.46 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274864 | CAYUGA RI;2U | 80/20 | 2.46 MW | 2.46 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274871 | GR RIDGE ;2U | 80/20 | 0.28 MW | 0.28 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274880 | RADFORD R;1U | 80/20 | 2.35 MW | 2.35 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274887 | PILOT HIL;1U | 80/20 | 1.38 MW | 1.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274888 | KELLY CRK;1U | 80/20 | 1.38 MW | 1.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 2.31 MW | 2.31 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 275149 | KELLYCK ;1E | 80/20 | 5.53 MW | 5.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276615 | W2-048 GEN | 80/20 | 3.23 MW | 3.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276621 | X2-022 GEN | 80/20 | 9.2 MW | 9.2 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290261 | S-027 E | 80/20 | 11.59 MW | 11.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290265 | S-028 E | 80/20 | 11.59 MW | 11.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293061 | N-015 E | 80/20 | 3.24 MW | 3.24 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293777 | CAYUG;1U E | 80/20 | 14.78 MW | 14.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293778 | CAYUG;2U E | 80/20 | 14.78 MW | 14.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293798 | W4-005 E | 80/20 | 15.7 MW | 15.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293799 | PILOT HIL;1E | 80/20 | 6.23 MW | 6.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 294392 | P-010 E | 80/20 | 4.11 MW | 4.11 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 917502 | Z2-087 E | 80/20 | 13.7 MW | 13.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924041 | AB2-047 C O1 | 80/20 | 2.56 MW | 2.56 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924042 | AB2-047 E O1 | 80/20 | 17.12 MW | 17.12 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924261 | AB2-070 C O1 | 80/20 | 2.55 MW | 2.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924262 | AB2-070 E O1 | 80/20 | 15.45 MW | 15.45 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925771 | AC1-053 C | 80/20 | 2.47 MW | 2.47 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925772 | AC1-053 E | 80/20 | 16.52 MW | 16.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 934721 | AD1-100 C | 80/20 | 35.26 MW | 35.26 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 934722 | AD1-100 E | 80/20 | 164.54 MW | 164.54 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 935141 | AD1-148 | 80/20 | 4.32 MW | 4.32 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 936371 | AD2-047 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 936372 | AD2-047 E O1 | 80/20 | 13.11 MW | 13.11 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 939401 | AE1-172 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 939402 | AE1-172 E O1 | 80/20 | 50.55 MW | 50.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 941731 | AE2-173 O1 | 80/20 | 9.84 MW | 9.84 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942111 | AE2-223 C | 80/20 | 3.07 MW | 3.07 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942112 | AE2-223 E | 80/20 | 20.55 MW | 20.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944221 | AF1-090 C O1 | 80/20 | 2.19 MW | 2.19 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944222 | AF1-090 E O1 | 80/20 | 10.26 MW | 10.26 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945871 | AF1-252 O1 | 80/20 | 4.86 MW | 4.86 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945881 | AF1-253 | 80/20 | 3.36 MW | 3.36 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958011 | AF2-095 C O1 | 80/20 | 3.95 MW | 3.95 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958021 | AF2-096 C | 80/20 | 9.62 MW | 9.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959611 | AF2-252 C | 80/20 | 3.66 MW | 3.66 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959612 | AF2-252 E | 80/20 | 5.49 MW | 5.49 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960141 | AF2-305 | 80/20 | 0.9 MW | 0.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960261 | AF2-317 | 80/20 | 1.38 MW | 1.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960601 | AF2-351 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960602 | AF2-351 E O1 | 80/20 | 1.19 MW | 1.19 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960611 | AF2-352 C | 80/20 | 3.66 MW | 3.66 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960612 | AF2-352 E | 80/20 | 5.49 MW | 5.49 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963831 | AG1-236 C | 80/20 | 2.47 MW | 2.47 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963832 | AG1-236 E | 80/20 | 16.52 MW | 16.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965092 | AG1-374 E | 80/20 | 13.71 MW | 13.71 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965331 | AG1-398 | 80/20 | 0.72 MW | 0.72 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965341 | AG1-399 C O1 | 80/20 | 6.5 MW | 6.5 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965342 | AG1-399 E O1 | 80/20 | 30.43 MW | 30.43 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965351 | AG1-400 O1 | 80/20 | 23.08 MW | 23.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965371 | AG1-402 O1 | 80/20 | 23.08 MW | 23.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965391 | AG1-404 O1 | 80/20 | 15.39 MW | 15.39 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965911 | AG1-460 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965912 | AG1-460 E | 80/20 | 1.62 MW | 1.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957382 | AF2-032 E | 80/20 | 0.18 MW | 0.18 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990856 | J1408 | External Queue | 6.9 MW | 6.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955402 | J1022 E | External Queue | 12.66 MW | 12.66 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956281 | J1115 C | External Queue | 3.27 MW | 3.27 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956282 | J1115 E | External Queue | 17.72 MW | 17.72 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991236 | J1676 | External Queue | 35.63 MW | 35.63 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991261 | J1713 | External Queue | 10.29 MW | 10.29 MW |
| Details for AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274847 | GR RIDGE ;BU | 80/20 | 0.74 MW | 0.74 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274853 | TWINGROVE;U1 | 80/20 | 2.54 MW | 2.54 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274854 | TWINGROVE;U2 | 80/20 | 2.62 MW | 2.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274863 | CAYUGA RI;1U | 80/20 | 2.46 MW | 2.46 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274864 | CAYUGA RI;2U | 80/20 | 2.46 MW | 2.46 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274871 | GR RIDGE ;2U | 80/20 | 0.28 MW | 0.28 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274880 | RADFORD R;1U | 80/20 | 2.35 MW | 2.35 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274887 | PILOT HIL;1U | 80/20 | 1.38 MW | 1.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274888 | KELLY CRK;1U | 80/20 | 1.38 MW | 1.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274889 | BRIGHTSTK;1U | 80/20 | 2.31 MW | 2.31 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 275149 | KELLYCK ;1E | 80/20 | 5.53 MW | 5.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276615 | W2-048 GEN | 80/20 | 3.23 MW | 3.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276621 | X2-022 GEN | 80/20 | 9.2 MW | 9.2 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290261 | S-027 E | 80/20 | 11.59 MW | 11.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290265 | S-028 E | 80/20 | 11.59 MW | 11.59 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293061 | N-015 E | 80/20 | 3.24 MW | 3.24 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293777 | CAYUG;1U E | 80/20 | 14.78 MW | 14.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293778 | CAYUG;2U E | 80/20 | 14.78 MW | 14.78 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293798 | W4-005 E | 80/20 | 15.7 MW | 15.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293799 | PILOT HIL;1E | 80/20 | 6.23 MW | 6.23 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 294392 | P-010 E | 80/20 | 4.11 MW | 4.11 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 917502 | Z2-087 E | 80/20 | 13.7 MW | 13.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924041 | AB2-047 C O1 | 80/20 | 2.56 MW | 2.56 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924042 | AB2-047 E O1 | 80/20 | 17.12 MW | 17.12 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924261 | AB2-070 C O1 | 80/20 | 2.55 MW | 2.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924262 | AB2-070 E O1 | 80/20 | 15.45 MW | 15.45 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925771 | AC1-053 C | 80/20 | 2.47 MW | 2.47 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925772 | AC1-053 E | 80/20 | 16.52 MW | 16.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 934721 | AD1-100 C | 80/20 | 35.26 MW | 35.26 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 934722 | AD1-100 E | 80/20 | 164.54 MW | 164.54 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 935141 | AD1-148 | 80/20 | 4.32 MW | 4.32 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 936371 | AD2-047 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 936372 | AD2-047 E O1 | 80/20 | 13.11 MW | 13.11 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 939401 | AE1-172 C O1 | 80/20 | 10.77 MW | 10.77 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 939402 | AE1-172 E O1 | 80/20 | 50.55 MW | 50.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 941731 | AE2-173 O1 | 80/20 | 9.84 MW | 9.84 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942111 | AE2-223 C | 80/20 | 3.07 MW | 3.07 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942112 | AE2-223 E | 80/20 | 20.55 MW | 20.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944221 | AF1-090 C O1 | 80/20 | 2.19 MW | 2.19 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944222 | AF1-090 E O1 | 80/20 | 10.26 MW | 10.26 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945871 | AF1-252 O1 | 80/20 | 4.86 MW | 4.86 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945881 | AF1-253 | 80/20 | 3.36 MW | 3.36 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958011 | AF2-095 C O1 | 80/20 | 3.95 MW | 3.95 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958021 | AF2-096 C | 80/20 | 9.62 MW | 9.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959611 | AF2-252 C | 80/20 | 3.66 MW | 3.66 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959612 | AF2-252 E | 80/20 | 5.49 MW | 5.49 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960141 | AF2-305 | 80/20 | 0.9 MW | 0.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960261 | AF2-317 | 80/20 | 1.38 MW | 1.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960601 | AF2-351 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960602 | AF2-351 E O1 | 80/20 | 1.19 MW | 1.19 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960611 | AF2-352 C | 80/20 | 3.66 MW | 3.66 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960612 | AF2-352 E | 80/20 | 5.49 MW | 5.49 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963831 | AG1-236 C | 80/20 | 2.47 MW | 2.47 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963832 | AG1-236 E | 80/20 | 16.52 MW | 16.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965092 | AG1-374 E | 80/20 | 13.71 MW | 13.71 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965331 | AG1-398 | 80/20 | 0.72 MW | 0.72 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965341 | AG1-399 C O1 | 80/20 | 6.5 MW | 6.5 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965342 | AG1-399 E O1 | 80/20 | 30.43 MW | 30.43 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965351 | AG1-400 O1 | 80/20 | 23.08 MW | 23.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965371 | AG1-402 O1 | 80/20 | 23.08 MW | 23.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965391 | AG1-404 O1 | 80/20 | 15.39 MW | 15.39 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965911 | AG1-460 C | 80/20 | 1.08 MW | 1.08 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965912 | AG1-460 E | 80/20 | 1.62 MW | 1.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957382 | AF2-032 E | 80/20 | 0.18 MW | 0.18 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990856 | J1408 | External Queue | 6.9 MW | 6.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955402 | J1022 E | External Queue | 12.66 MW | 12.66 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956281 | J1115 C | External Queue | 3.27 MW | 3.27 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956282 | J1115 E | External Queue | 17.72 MW | 17.72 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991236 | J1676 | External Queue | 35.63 MW | 35.63 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991261 | J1713 | External Queue | 10.29 MW | 10.29 MW |
| Details for AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274847 | GR RIDGE ;BU | 80/20 | 0.84 MW | 0.84 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 1.8 MW | 1.8 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 1.85 MW | 1.85 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 2.04 MW | 2.04 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 2.04 MW | 2.04 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274871 | GR RIDGE ;2U | 80/20 | 0.31 MW | 0.31 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 1.67 MW | 1.67 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274887 | PILOT HIL;1U | 80/20 | 1.46 MW | 1.46 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274888 | KELLY CRK;1U | 80/20 | 1.46 MW | 1.46 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 1.62 MW | 1.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 275149 | KELLYCK ;1E | 80/20 | 5.83 MW | 5.83 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 276615 | W2-048 GEN | 80/20 | 2.33 MW | 2.33 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 276621 | X2-022 GEN | 80/20 | 6.62 MW | 6.62 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 8.19 MW | 8.19 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 8.19 MW | 8.19 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 293061 | N-015 E | 80/20 | 3.7 MW | 3.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 12.25 MW | 12.25 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 12.25 MW | 12.25 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 293798 | W4-005 E | 80/20 | 11.2 MW | 11.2 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 293799 | PILOT HIL;1E | 80/20 | 6.57 MW | 6.57 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 294392 | P-010 E | 80/20 | 4.7 MW | 4.7 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 9.64 MW | 9.64 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 1.8 MW | 1.8 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 12.05 MW | 12.05 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 1.83 MW | 1.83 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 924262 | AB2-070 E O1 | 80/20 | 11.06 MW | 11.06 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 1.77 MW | 1.77 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 925772 | AC1-053 E | 80/20 | 11.84 MW | 11.84 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 934721 | AD1-100 C | 80/20 | 34.51 MW | 34.51 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 934722 | AD1-100 E | 80/20 | 161.04 MW | 161.04 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 3.11 MW | 3.11 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 936371 | AD2-047 C O1 | 80/20 | 2.83 MW | 2.83 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 936372 | AD2-047 E O1 | 80/20 | 13.82 MW | 13.82 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 9.5 MW | 9.5 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 44.55 MW | 44.55 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 6.92 MW | 6.92 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 2.16 MW | 2.16 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 14.46 MW | 14.46 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 1.58 MW | 1.58 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 944222 | AF1-090 E O1 | 80/20 | 7.42 MW | 7.42 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 3.51 MW | 3.51 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 2.43 MW | 2.43 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 958011 | AF2-095 C O1 | 80/20 | 4.16 MW | 4.16 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 958012 | AF2-095 E O1 | 80/20 | 0.0 MW | 0.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 958021 | AF2-096 C | 80/20 | 9.9 MW | 9.9 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 958022 | AF2-096 E | 80/20 | 0.0 MW | 0.0 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 2.58 MW | 2.58 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 3.88 MW | 3.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 0.65 MW | 0.65 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 0.99 MW | 0.99 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 960601 | AF2-351 C O1 | 80/20 | 0.83 MW | 0.83 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 960602 | AF2-351 E O1 | 80/20 | 1.25 MW | 1.25 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 2.58 MW | 2.58 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 3.88 MW | 3.88 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 1.77 MW | 1.77 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 963832 | AG1-236 E | 80/20 | 11.84 MW | 11.84 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 9.69 MW | 9.69 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 0.52 MW | 0.52 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C O1 | 80/20 | 4.61 MW | 4.61 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965342 | AG1-399 E O1 | 80/20 | 21.6 MW | 21.6 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 O1 | 80/20 | 16.38 MW | 16.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 O1 | 80/20 | 16.38 MW | 16.38 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 O1 | 80/20 | 10.92 MW | 10.92 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 0.79 MW | 0.79 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 965912 | AG1-460 E | 80/20 | 1.18 MW | 1.18 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 966091 | AG1-478 C | 80/20 | 0.2 MW | 0.2 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 966092 | AG1-478 E | 80/20 | 0.31 MW | 0.31 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 957382 | AF2-032 E | 80/20 | 0.13 MW | 0.13 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 955402 | J1022 E | External Queue | 8.53 MW | 8.53 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 956281 | J1115 C | External Queue | 2.24 MW | 2.24 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 956282 | J1115 E | External Queue | 12.14 MW | 12.14 MW |
| AD1-100 TAP-WILTON ; B 345.0 kV Ckt 1 line l/o Base Case | 991236 | J1676 | External Queue | 24.45 MW | 24.45 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274853 | TWINGROVE;U1 | 80/20 | 5.66 MW | 5.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274854 | TWINGROVE;U2 | 80/20 | 5.82 MW | 5.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274880 | RADFORD R;1U | 80/20 | 5.22 MW | 5.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 274889 | BRIGHTSTK;1U | 80/20 | 5.12 MW | 5.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276615 | W2-048 GEN | 80/20 | 7.15 MW | 7.15 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276621 | X2-022 GEN | 80/20 | 20.36 MW | 20.36 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290261 | S-027 E | 80/20 | 25.76 MW | 25.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 290265 | S-028 E | 80/20 | 25.76 MW | 25.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 293798 | W4-005 E | 80/20 | 34.93 MW | 34.93 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 917502 | Z2-087 E | 80/20 | 30.43 MW | 30.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924041 | AB2-047 C O1 | 80/20 | 5.68 MW | 5.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924042 | AB2-047 E O1 | 80/20 | 38.04 MW | 38.04 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924261 | AB2-070 C O1 | 80/20 | 5.65 MW | 5.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 924262 | AB2-070 E O1 | 80/20 | 34.22 MW | 34.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925771 | AC1-053 C | 80/20 | 5.47 MW | 5.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 925772 | AC1-053 E | 80/20 | 36.59 MW | 36.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 935141 | AD1-148 | 80/20 | 9.57 MW | 9.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 941731 | AE2-173 O1 | 80/20 | 21.86 MW | 21.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942111 | AE2-223 C | 80/20 | 6.82 MW | 6.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942112 | AE2-223 E | 80/20 | 45.64 MW | 45.64 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 942601 | AE2-276 | 80/20 | 2.75 MW | 2.75 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944221 | AF1-090 C O1 | 80/20 | 4.93 MW | 4.93 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944222 | AF1-090 E O1 | 80/20 | 23.07 MW | 23.07 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945391 | AF1-204 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945392 | AF1-204 E O1 | 80/20 | 10.03 MW | 10.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945871 | AF1-252 O1 | 80/20 | 10.92 MW | 10.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 945881 | AF1-253 | 80/20 | 7.56 MW | 7.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959611 | AF2-252 C | 80/20 | 8.13 MW | 8.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959612 | AF2-252 E | 80/20 | 12.2 MW | 12.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960141 | AF2-305 | 80/20 | 2.0 MW | 2.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960261 | AF2-317 | 80/20 | 3.06 MW | 3.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960611 | AF2-352 C | 80/20 | 8.13 MW | 8.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960612 | AF2-352 E | 80/20 | 12.2 MW | 12.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963831 | AG1-236 C | 80/20 | 5.47 MW | 5.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 963832 | AG1-236 E | 80/20 | 36.59 MW | 36.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965092 | AG1-374 E | 80/20 | 30.49 MW | 30.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965341 | AG1-399 C O1 | 80/20 | 14.46 MW | 14.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965342 | AG1-399 E O1 | 80/20 | 67.68 MW | 67.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965351 | AG1-400 O1 | 80/20 | 51.34 MW | 51.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965371 | AG1-402 O1 | 80/20 | 51.34 MW | 51.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965391 | AG1-404 O1 | 80/20 | 34.22 MW | 34.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965911 | AG1-460 C | 80/20 | 2.4 MW | 2.4 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 965912 | AG1-460 E | 80/20 | 3.61 MW | 3.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957382 | AF2-032 E | 80/20 | 0.41 MW | 0.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 276172 | Z1-108 BAT | 80/20 | 1.2 MW | 1.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 920273 | AA2-123 BAT | 80/20 | 1.08 MW | 1.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 943803 | AF1-048 BAT | 80/20 | 2.82 MW | 2.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 944201 | AF1-088 FTIR | 80/20 | 54.98 MW | 54.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957141 | AF2-008 FTIR | 80/20 | 27.49 MW | 27.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957333 | AF2-027 BAT | 80/20 | 3.03 MW | 3.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957373 | AF2-031 BAT | 80/20 | 1.61 MW | 1.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 957403 | AF2-034 BAT | 80/20 | 0.7 MW | 0.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958013 | AF2-095 BAT | 80/20 | 4.52 MW | 4.52 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 958023 | AF2-096 BAT | 80/20 | 9.02 MW | 9.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 959353 | AF2-226 BAT | 80/20 | 2.58 MW | 2.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960283 | AF2-319 BAT | 80/20 | 2.58 MW | 2.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960382 | AF2-329 BAT | 80/20 | 2.89 MW | 2.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 960603 | AF2-351 BAT | 80/20 | 2.26 MW | 2.26 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 961503 | AF2-441 BAT | 80/20 | 16.79 MW | 16.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 964362 | AG1-298 BAT | 80/20 | 41.62 MW | 41.62 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966093 | AG1-478 BAT | 80/20 | 0.84 MW | 0.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966433 | AG1-512 BAT | 80/20 | 3.3 MW | 3.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966443 | AG1-513 BAT | 80/20 | 0.68 MW | 0.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 966652 | AG1-535 BAT | 80/20 | 6.88 MW | 6.88 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-A | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.66 MW | 5.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.82 MW | 5.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274880 | RADFORD R;1U | 80/20 | 5.22 MW | 5.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 5.12 MW | 5.12 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276615 | W2-048 GEN | 80/20 | 7.15 MW | 7.15 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276621 | X2-022 GEN | 80/20 | 20.36 MW | 20.36 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290261 | S-027 E | 80/20 | 25.76 MW | 25.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 290265 | S-028 E | 80/20 | 25.76 MW | 25.76 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 293798 | W4-005 E | 80/20 | 34.93 MW | 34.93 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 917502 | Z2-087 E | 80/20 | 30.43 MW | 30.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.68 MW | 5.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924042 | AB2-047 E O1 | 80/20 | 38.04 MW | 38.04 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.65 MW | 5.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 924262 | AB2-070 E O1 | 80/20 | 34.22 MW | 34.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925771 | AC1-053 C | 80/20 | 5.47 MW | 5.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 925772 | AC1-053 E | 80/20 | 36.59 MW | 36.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 935141 | AD1-148 | 80/20 | 9.57 MW | 9.57 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 941731 | AE2-173 O1 | 80/20 | 21.86 MW | 21.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942111 | AE2-223 C | 80/20 | 6.82 MW | 6.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942112 | AE2-223 E | 80/20 | 45.64 MW | 45.64 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 942601 | AE2-276 | 80/20 | 2.75 MW | 2.75 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.93 MW | 4.93 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944222 | AF1-090 E O1 | 80/20 | 23.07 MW | 23.07 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945391 | AF1-204 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945392 | AF1-204 E O1 | 80/20 | 10.03 MW | 10.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945871 | AF1-252 O1 | 80/20 | 10.92 MW | 10.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 945881 | AF1-253 | 80/20 | 7.56 MW | 7.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959611 | AF2-252 C | 80/20 | 8.13 MW | 8.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959612 | AF2-252 E | 80/20 | 12.2 MW | 12.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960141 | AF2-305 | 80/20 | 2.0 MW | 2.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960261 | AF2-317 | 80/20 | 3.06 MW | 3.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960611 | AF2-352 C | 80/20 | 8.13 MW | 8.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960612 | AF2-352 E | 80/20 | 12.2 MW | 12.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963831 | AG1-236 C | 80/20 | 5.47 MW | 5.47 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 963832 | AG1-236 E | 80/20 | 36.59 MW | 36.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965092 | AG1-374 E | 80/20 | 30.49 MW | 30.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965331 | AG1-398 | 80/20 | 1.59 MW | 1.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965341 | AG1-399 C O1 | 80/20 | 14.46 MW | 14.46 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965342 | AG1-399 E O1 | 80/20 | 67.68 MW | 67.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965351 | AG1-400 O1 | 80/20 | 51.34 MW | 51.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965371 | AG1-402 O1 | 80/20 | 51.34 MW | 51.34 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965391 | AG1-404 O1 | 80/20 | 34.22 MW | 34.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965911 | AG1-460 C | 80/20 | 2.4 MW | 2.4 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 965912 | AG1-460 E | 80/20 | 3.61 MW | 3.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957382 | AF2-032 E | 80/20 | 0.41 MW | 0.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 964362 | AG1-298 BAT | 80/20 | 41.62 MW | 41.62 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966093 | AG1-478 BAT | 80/20 | 0.84 MW | 0.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966433 | AG1-512 BAT | 80/20 | 3.3 MW | 3.3 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966443 | AG1-513 BAT | 80/20 | 0.68 MW | 0.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 966652 | AG1-535 BAT | 80/20 | 6.88 MW | 6.88 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 276172 | Z1-108 BAT | 80/20 | 1.2 MW | 1.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 920273 | AA2-123 BAT | 80/20 | 1.08 MW | 1.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 943803 | AF1-048 BAT | 80/20 | 2.82 MW | 2.82 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 944201 | AF1-088 FTIR | 80/20 | 54.98 MW | 54.98 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957141 | AF2-008 FTIR | 80/20 | 27.49 MW | 27.49 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957333 | AF2-027 BAT | 80/20 | 3.03 MW | 3.03 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957373 | AF2-031 BAT | 80/20 | 1.61 MW | 1.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 957403 | AF2-034 BAT | 80/20 | 0.7 MW | 0.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958013 | AF2-095 BAT | 80/20 | 4.52 MW | 4.52 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 958023 | AF2-096 BAT | 80/20 | 9.02 MW | 9.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 959353 | AF2-226 BAT | 80/20 | 2.58 MW | 2.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960283 | AF2-319 BAT | 80/20 | 2.58 MW | 2.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960382 | AF2-329 BAT | 80/20 | 2.89 MW | 2.89 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 960603 | AF2-351 BAT | 80/20 | 2.26 MW | 2.26 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 961503 | AF2-441 BAT | 80/20 | 16.79 MW | 16.79 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990056 | J1201 | External Queue | 4.8 MW | 4.8 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990271 | J1263 | External Queue | 30.68 MW | 30.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990351 | J1289 C | External Queue | 2.29 MW | 2.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 990856 | J1408 | External Queue | 15.31 MW | 15.31 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955402 | J1022 E | External Queue | 29.13 MW | 29.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955711 | J1055 C | External Queue | 2.06 MW | 2.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 955712 | J1055 E | External Queue | 11.14 MW | 11.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956281 | J1115 C | External Queue | 7.39 MW | 7.39 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 956282 | J1115 E | External Queue | 40.0 MW | 40.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991236 | J1676 | External Queue | 80.08 MW | 80.08 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991261 | J1713 | External Queue | 23.85 MW | 23.85 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8014__R-S-B | 991276 | J1725 | External Queue | 8.62 MW | 8.62 MW |
| Details for PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274853 | TWINGROVE;U1 | 50/50 | 5.68 MW | 5.68 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274854 | TWINGROVE;U2 | 50/50 | 5.84 MW | 5.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274880 | RADFORD R;1U | 50/50 | 5.26 MW | 5.26 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 274889 | BRIGHTSTK;1U | 50/50 | 5.14 MW | 5.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276615 | W2-048 GEN | 50/50 | 7.22 MW | 7.22 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 276621 | X2-022 GEN | 50/50 | 20.56 MW | 20.56 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290261 | S-027 E | 50/50 | 25.84 MW | 25.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 290265 | S-028 E | 50/50 | 25.84 MW | 25.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 293798 | W4-005 E | 50/50 | 35.18 MW | 35.18 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 917502 | Z2-087 E | 50/50 | 30.51 MW | 30.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924041 | AB2-047 C O1 | 50/50 | 5.7 MW | 5.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924042 | AB2-047 E O1 | 50/50 | 38.14 MW | 38.14 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924261 | AB2-070 C O1 | 50/50 | 5.7 MW | 5.7 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 924262 | AB2-070 E O1 | 50/50 | 34.5 MW | 34.5 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925771 | AC1-053 C | 50/50 | 5.51 MW | 5.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 925772 | AC1-053 E | 50/50 | 36.91 MW | 36.91 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 935141 | AD1-148 | 50/50 | 9.66 MW | 9.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 941731 | AE2-173 O1 | 50/50 | 21.92 MW | 21.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942111 | AE2-223 C | 50/50 | 6.84 MW | 6.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942112 | AE2-223 E | 50/50 | 45.77 MW | 45.77 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 942601 | AE2-276 | Adder | 2.77 MW | 2.35 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944221 | AF1-090 C O1 | 50/50 | 4.99 MW | 4.99 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944222 | AF1-090 E O1 | 50/50 | 23.37 MW | 23.37 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945391 | AF1-204 C O1 | Adder | 3.36 MW | 2.86 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945392 | AF1-204 E O1 | Adder | 10.09 MW | 8.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945871 | AF1-252 O1 | 50/50 | 11.06 MW | 11.06 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 945881 | AF1-253 | 50/50 | 7.66 MW | 7.66 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959611 | AF2-252 C | 50/50 | 8.16 MW | 8.16 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 959612 | AF2-252 E | 50/50 | 12.23 MW | 12.23 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960141 | AF2-305 | 50/50 | 2.02 MW | 2.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960261 | AF2-317 | 50/50 | 3.09 MW | 3.09 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960611 | AF2-352 C | 50/50 | 8.16 MW | 8.16 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960612 | AF2-352 E | 50/50 | 12.23 MW | 12.23 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963831 | AG1-236 C | 50/50 | 5.51 MW | 5.51 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 963832 | AG1-236 E | 50/50 | 36.91 MW | 36.91 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965092 | AG1-374 E | 50/50 | 30.59 MW | 30.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965331 | AG1-398 | 50/50 | 1.61 MW | 1.61 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965341 | AG1-399 C O1 | 50/50 | 14.53 MW | 14.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965342 | AG1-399 E O1 | 50/50 | 68.02 MW | 68.02 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965351 | AG1-400 O1 | 50/50 | 51.59 MW | 51.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965371 | AG1-402 O1 | 50/50 | 51.59 MW | 51.59 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965391 | AG1-404 O1 | 50/50 | 34.39 MW | 34.39 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965911 | AG1-460 C | 50/50 | 2.44 MW | 2.44 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 965912 | AG1-460 E | 50/50 | 3.65 MW | 3.65 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957382 | AF2-032 E | 50/50 | 0.41 MW | 0.41 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 944201 | AF1-088 FTIR | Adder | 65.2 MW | 55.42 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 957141 | AF2-008 FTIR | Adder | 32.6 MW | 27.71 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958013 | AF2-095 BAT | 50/50 | 4.58 MW | 4.58 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 958023 | AF2-096 BAT | 50/50 | 9.13 MW | 9.13 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 960603 | AF2-351 BAT | 50/50 | 2.29 MW | 2.29 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990056 | J1201 | External Queue | 4.84 MW | 4.84 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990271 | J1263 | External Queue | 30.69 MW | 30.69 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990351 | J1289 C | External Queue | 2.43 MW | 2.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 990856 | J1408 | External Queue | 15.53 MW | 15.53 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955402 | J1022 E | External Queue | 29.24 MW | 29.24 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955711 | J1055 C | External Queue | 2.2 MW | 2.2 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 955712 | J1055 E | External Queue | 11.92 MW | 11.92 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956281 | J1115 C | External Queue | 7.43 MW | 7.43 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 956282 | J1115 E | External Queue | 40.17 MW | 40.17 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991236 | J1676 | External Queue | 80.35 MW | 80.35 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991261 | J1713 | External Queue | 24.0 MW | 24.0 MW |
| PONTIAC ; B-LORETTO ; B 345.0 kV Ckt 1 line l/o COMED_P4_012-45-BT12-14 | 991276 | J1725 | External Queue | 9.28 MW | 9.28 MW |
| Details for PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.16 MW | 5.16 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.3 MW | 5.3 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274863 | CAYUGA RI;1U | 80/20 | 4.12 MW | 4.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274864 | CAYUGA RI;2U | 80/20 | 4.12 MW | 4.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274880 | RADFORD R;1U | 80/20 | 4.71 MW | 4.71 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 4.69 MW | 4.69 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276615 | W2-048 GEN | 80/20 | 6.4 MW | 6.4 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276621 | X2-022 GEN | 80/20 | 18.23 MW | 18.23 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 290261 | S-027 E | 80/20 | 23.46 MW | 23.46 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 290265 | S-028 E | 80/20 | 23.46 MW | 23.46 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293777 | CAYUG;1U E | 80/20 | 24.77 MW | 24.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293778 | CAYUG;2U E | 80/20 | 24.77 MW | 24.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293798 | W4-005 E | 80/20 | 31.5 MW | 31.5 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 917502 | Z2-087 E | 80/20 | 27.86 MW | 27.86 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924042 | AB2-047 E O1 | 80/20 | 34.83 MW | 34.83 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924262 | AB2-070 E O1 | 80/20 | 30.81 MW | 30.81 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 925771 | AC1-053 C | 80/20 | 4.91 MW | 4.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 925772 | AC1-053 E | 80/20 | 32.88 MW | 32.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 935141 | AD1-148 | 80/20 | 8.57 MW | 8.57 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 937001 | AD2-134 C | Adder | -1.05 MW | -0.89 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 939401 | AE1-172 C O1 | 80/20 | 16.41 MW | 16.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 939402 | AE1-172 E O1 | 80/20 | 76.98 MW | 76.98 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 941731 | AE2-173 O1 | 80/20 | 20.02 MW | 20.02 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 942111 | AE2-223 C | 80/20 | 6.25 MW | 6.25 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 942112 | AE2-223 E | 80/20 | 41.8 MW | 41.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 944222 | AF1-090 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945391 | AF1-204 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945392 | AF1-204 E O1 | 80/20 | 8.96 MW | 8.96 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945871 | AF1-252 O1 | 80/20 | 9.65 MW | 9.65 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945881 | AF1-253 | 80/20 | 6.68 MW | 6.68 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959611 | AF2-252 C | 80/20 | 7.41 MW | 7.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959612 | AF2-252 E | 80/20 | 11.11 MW | 11.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960141 | AF2-305 | 80/20 | 1.8 MW | 1.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960261 | AF2-317 | 80/20 | 2.74 MW | 2.74 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960611 | AF2-352 C | 80/20 | 7.41 MW | 7.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960612 | AF2-352 E | 80/20 | 11.11 MW | 11.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 963831 | AG1-236 C | 80/20 | 4.91 MW | 4.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 963832 | AG1-236 E | 80/20 | 32.88 MW | 32.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965092 | AG1-374 E | 80/20 | 27.77 MW | 27.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965331 | AG1-398 | 80/20 | 1.43 MW | 1.43 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965341 | AG1-399 C O1 | 80/20 | 13.11 MW | 13.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965342 | AG1-399 E O1 | 80/20 | 61.37 MW | 61.37 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965351 | AG1-400 O1 | 80/20 | 46.55 MW | 46.55 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965371 | AG1-402 O1 | 80/20 | 46.55 MW | 46.55 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965391 | AG1-404 O1 | 80/20 | 31.03 MW | 31.03 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965911 | AG1-460 C | 80/20 | 2.13 MW | 2.13 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965912 | AG1-460 E | 80/20 | 3.2 MW | 3.2 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957382 | AF2-032 E | 80/20 | 0.36 MW | 0.36 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276172 | Z1-108 BAT | 80/20 | 1.53 MW | 1.53 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 920273 | AA2-123 BAT | 80/20 | 1.42 MW | 1.42 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 943803 | AF1-048 BAT | 80/20 | 3.68 MW | 3.68 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957333 | AF2-027 BAT | 80/20 | 3.8 MW | 3.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957373 | AF2-031 BAT | 80/20 | 1.37 MW | 1.37 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957403 | AF2-034 BAT | 80/20 | 0.88 MW | 0.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 958013 | AF2-095 BAT | 80/20 | 3.04 MW | 3.04 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 958023 | AF2-096 BAT | 80/20 | 5.64 MW | 5.64 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959353 | AF2-226 BAT | 80/20 | 3.15 MW | 3.15 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960283 | AF2-319 BAT | 80/20 | 3.15 MW | 3.15 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960382 | AF2-329 BAT | 80/20 | 3.35 MW | 3.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960603 | AF2-351 BAT | 80/20 | 1.52 MW | 1.52 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 961503 | AF2-441 BAT | 80/20 | 14.3 MW | 14.3 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 964362 | AG1-298 BAT | 80/20 | 35.23 MW | 35.23 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965063 | AG1-371 BAT | 80/20 | 4.54 MW | 4.54 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965083 | AG1-373 BAT | 80/20 | 1.51 MW | 1.51 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966093 | AG1-478 BAT | 80/20 | 0.82 MW | 0.82 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966433 | AG1-512 BAT | 80/20 | 2.94 MW | 2.94 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966443 | AG1-513 BAT | 80/20 | 0.88 MW | 0.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966652 | AG1-535 BAT | 80/20 | 5.8 MW | 5.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990056 | J1201 | External Queue | 4.53 MW | 4.53 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990271 | J1263 | External Queue | 30.31 MW | 30.31 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990351 | J1289 C | External Queue | 1.94 MW | 1.94 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990856 | J1408 | External Queue | 14.12 MW | 14.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955402 | J1022 E | External Queue | 27.43 MW | 27.43 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955711 | J1055 C | External Queue | 1.73 MW | 1.73 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955712 | J1055 E | External Queue | 9.35 MW | 9.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 956281 | J1115 C | External Queue | 6.91 MW | 6.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 956282 | J1115 E | External Queue | 37.36 MW | 37.36 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991236 | J1676 | External Queue | 74.89 MW | 74.89 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991261 | J1713 | External Queue | 22.4 MW | 22.4 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991276 | J1725 | External Queue | 7.14 MW | 7.14 MW |
| Details for PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274853 | TWINGROVE;U1 | 80/20 | 5.16 MW | 5.16 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274854 | TWINGROVE;U2 | 80/20 | 5.3 MW | 5.3 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274863 | CAYUGA RI;1U | 80/20 | 4.12 MW | 4.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274864 | CAYUGA RI;2U | 80/20 | 4.12 MW | 4.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274880 | RADFORD R;1U | 80/20 | 4.71 MW | 4.71 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274889 | BRIGHTSTK;1U | 80/20 | 4.69 MW | 4.69 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276615 | W2-048 GEN | 80/20 | 6.4 MW | 6.4 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276621 | X2-022 GEN | 80/20 | 18.23 MW | 18.23 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 290261 | S-027 E | 80/20 | 23.46 MW | 23.46 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 290265 | S-028 E | 80/20 | 23.46 MW | 23.46 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293777 | CAYUG;1U E | 80/20 | 24.77 MW | 24.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293778 | CAYUG;2U E | 80/20 | 24.77 MW | 24.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293798 | W4-005 E | 80/20 | 31.5 MW | 31.5 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 917502 | Z2-087 E | 80/20 | 27.86 MW | 27.86 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924041 | AB2-047 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924042 | AB2-047 E O1 | 80/20 | 34.83 MW | 34.83 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924261 | AB2-070 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924262 | AB2-070 E O1 | 80/20 | 30.81 MW | 30.81 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 925771 | AC1-053 C | 80/20 | 4.91 MW | 4.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 925772 | AC1-053 E | 80/20 | 32.88 MW | 32.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 935141 | AD1-148 | 80/20 | 8.57 MW | 8.57 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 937001 | AD2-134 C | Adder | -1.05 MW | -0.89 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 941731 | AE2-173 O1 | 80/20 | 20.02 MW | 20.02 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 942111 | AE2-223 C | 80/20 | 6.25 MW | 6.25 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 942112 | AE2-223 E | 80/20 | 41.8 MW | 41.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 944221 | AF1-090 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 944222 | AF1-090 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945391 | AF1-204 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945392 | AF1-204 E O1 | 80/20 | 8.96 MW | 8.96 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945871 | AF1-252 O1 | 80/20 | 9.65 MW | 9.65 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945881 | AF1-253 | 80/20 | 6.68 MW | 6.68 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959611 | AF2-252 C | 80/20 | 7.41 MW | 7.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959612 | AF2-252 E | 80/20 | 11.11 MW | 11.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960141 | AF2-305 | 80/20 | 1.8 MW | 1.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960261 | AF2-317 | 80/20 | 2.74 MW | 2.74 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960611 | AF2-352 C | 80/20 | 7.41 MW | 7.41 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960612 | AF2-352 E | 80/20 | 11.11 MW | 11.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 963831 | AG1-236 C | 80/20 | 4.91 MW | 4.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 963832 | AG1-236 E | 80/20 | 32.88 MW | 32.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965092 | AG1-374 E | 80/20 | 27.77 MW | 27.77 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965331 | AG1-398 | 80/20 | 1.43 MW | 1.43 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965341 | AG1-399 C O1 | 80/20 | 13.11 MW | 13.11 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965342 | AG1-399 E O1 | 80/20 | 61.37 MW | 61.37 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965351 | AG1-400 O1 | 80/20 | 46.55 MW | 46.55 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965371 | AG1-402 O1 | 80/20 | 46.55 MW | 46.55 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965391 | AG1-404 O1 | 80/20 | 31.03 MW | 31.03 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965911 | AG1-460 C | 80/20 | 2.13 MW | 2.13 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965912 | AG1-460 E | 80/20 | 3.2 MW | 3.2 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957382 | AF2-032 E | 80/20 | 0.36 MW | 0.36 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276172 | Z1-108 BAT | 80/20 | 1.53 MW | 1.53 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 920273 | AA2-123 BAT | 80/20 | 1.42 MW | 1.42 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 943803 | AF1-048 BAT | 80/20 | 3.68 MW | 3.68 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957333 | AF2-027 BAT | 80/20 | 3.8 MW | 3.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957373 | AF2-031 BAT | 80/20 | 1.37 MW | 1.37 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957403 | AF2-034 BAT | 80/20 | 0.88 MW | 0.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 958013 | AF2-095 BAT | 80/20 | 3.04 MW | 3.04 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 958023 | AF2-096 BAT | 80/20 | 5.64 MW | 5.64 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959353 | AF2-226 BAT | 80/20 | 3.15 MW | 3.15 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960283 | AF2-319 BAT | 80/20 | 3.15 MW | 3.15 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960382 | AF2-329 BAT | 80/20 | 3.35 MW | 3.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960603 | AF2-351 BAT | 80/20 | 1.52 MW | 1.52 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 961503 | AF2-441 BAT | 80/20 | 14.3 MW | 14.3 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 964362 | AG1-298 BAT | 80/20 | 35.23 MW | 35.23 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965063 | AG1-371 BAT | 80/20 | 4.54 MW | 4.54 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965083 | AG1-373 BAT | 80/20 | 1.51 MW | 1.51 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966093 | AG1-478 BAT | 80/20 | 0.82 MW | 0.82 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966433 | AG1-512 BAT | 80/20 | 2.94 MW | 2.94 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966443 | AG1-513 BAT | 80/20 | 0.88 MW | 0.88 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966652 | AG1-535 BAT | 80/20 | 5.8 MW | 5.8 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990056 | J1201 | External Queue | 4.53 MW | 4.53 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990271 | J1263 | External Queue | 30.31 MW | 30.31 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990351 | J1289 C | External Queue | 1.94 MW | 1.94 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990856 | J1408 | External Queue | 14.12 MW | 14.12 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955402 | J1022 E | External Queue | 27.43 MW | 27.43 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955711 | J1055 C | External Queue | 1.73 MW | 1.73 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955712 | J1055 E | External Queue | 9.35 MW | 9.35 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 956281 | J1115 C | External Queue | 6.91 MW | 6.91 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 956282 | J1115 E | External Queue | 37.36 MW | 37.36 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991236 | J1676 | External Queue | 74.89 MW | 74.89 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991261 | J1713 | External Queue | 22.4 MW | 22.4 MW |
| PONTIAC ; R-AG1-321 TAP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991276 | J1725 | External Queue | 7.14 MW | 7.14 MW |
| Details for AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274853 | TWINGROVE;U1 | 80/20 | 5.16 MW | 5.16 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274854 | TWINGROVE;U2 | 80/20 | 5.3 MW | 5.3 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274863 | CAYUGA RI;1U | 80/20 | 4.12 MW | 4.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274864 | CAYUGA RI;2U | 80/20 | 4.12 MW | 4.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274880 | RADFORD R;1U | 80/20 | 4.71 MW | 4.71 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 4.69 MW | 4.69 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276615 | W2-048 GEN | 80/20 | 6.4 MW | 6.4 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276621 | X2-022 GEN | 80/20 | 18.23 MW | 18.23 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 290261 | S-027 E | 80/20 | 23.46 MW | 23.46 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 290265 | S-028 E | 80/20 | 23.46 MW | 23.46 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293777 | CAYUG;1U E | 80/20 | 24.77 MW | 24.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293778 | CAYUG;2U E | 80/20 | 24.77 MW | 24.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 293798 | W4-005 E | 80/20 | 31.5 MW | 31.5 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 917502 | Z2-087 E | 80/20 | 27.86 MW | 27.86 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924041 | AB2-047 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924042 | AB2-047 E O1 | 80/20 | 34.83 MW | 34.83 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924261 | AB2-070 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 924262 | AB2-070 E O1 | 80/20 | 30.81 MW | 30.81 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 925771 | AC1-053 C | 80/20 | 4.91 MW | 4.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 925772 | AC1-053 E | 80/20 | 32.88 MW | 32.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 935141 | AD1-148 | 80/20 | 8.57 MW | 8.57 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 937001 | AD2-134 C | Adder | -1.05 MW | -0.89 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 939401 | AE1-172 C O1 | 80/20 | 16.41 MW | 16.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 939402 | AE1-172 E O1 | 80/20 | 76.98 MW | 76.98 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 941731 | AE2-173 O1 | 80/20 | 20.02 MW | 20.02 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 942111 | AE2-223 C | 80/20 | 6.25 MW | 6.25 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 942112 | AE2-223 E | 80/20 | 41.8 MW | 41.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 944222 | AF1-090 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945391 | AF1-204 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945392 | AF1-204 E O1 | 80/20 | 8.96 MW | 8.96 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945871 | AF1-252 O1 | 80/20 | 9.65 MW | 9.65 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 945881 | AF1-253 | 80/20 | 6.68 MW | 6.68 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959611 | AF2-252 C | 80/20 | 7.41 MW | 7.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959612 | AF2-252 E | 80/20 | 11.11 MW | 11.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960141 | AF2-305 | 80/20 | 1.8 MW | 1.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960261 | AF2-317 | 80/20 | 2.74 MW | 2.74 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960611 | AF2-352 C | 80/20 | 7.41 MW | 7.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960612 | AF2-352 E | 80/20 | 11.11 MW | 11.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 963831 | AG1-236 C | 80/20 | 4.91 MW | 4.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 963832 | AG1-236 E | 80/20 | 32.88 MW | 32.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965092 | AG1-374 E | 80/20 | 27.77 MW | 27.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965331 | AG1-398 | 80/20 | 1.43 MW | 1.43 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965341 | AG1-399 C O1 | 80/20 | 13.11 MW | 13.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965342 | AG1-399 E O1 | 80/20 | 61.37 MW | 61.37 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965351 | AG1-400 O1 | 80/20 | 46.55 MW | 46.55 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965371 | AG1-402 O1 | 80/20 | 46.55 MW | 46.55 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965391 | AG1-404 O1 | 80/20 | 31.03 MW | 31.03 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965911 | AG1-460 C | 80/20 | 2.13 MW | 2.13 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965912 | AG1-460 E | 80/20 | 3.2 MW | 3.2 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957382 | AF2-032 E | 80/20 | 0.36 MW | 0.36 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 276172 | Z1-108 BAT | 80/20 | 1.53 MW | 1.53 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 920273 | AA2-123 BAT | 80/20 | 1.42 MW | 1.42 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 943803 | AF1-048 BAT | 80/20 | 3.68 MW | 3.68 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957333 | AF2-027 BAT | 80/20 | 3.8 MW | 3.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957373 | AF2-031 BAT | 80/20 | 1.37 MW | 1.37 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 957403 | AF2-034 BAT | 80/20 | 0.88 MW | 0.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 958013 | AF2-095 BAT | 80/20 | 3.04 MW | 3.04 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 958023 | AF2-096 BAT | 80/20 | 5.64 MW | 5.64 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 959353 | AF2-226 BAT | 80/20 | 3.15 MW | 3.15 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960283 | AF2-319 BAT | 80/20 | 3.15 MW | 3.15 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960382 | AF2-329 BAT | 80/20 | 3.35 MW | 3.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 960603 | AF2-351 BAT | 80/20 | 1.52 MW | 1.52 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 961503 | AF2-441 BAT | 80/20 | 14.3 MW | 14.3 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 964362 | AG1-298 BAT | 80/20 | 35.23 MW | 35.23 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965063 | AG1-371 BAT | 80/20 | 4.54 MW | 4.54 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 965083 | AG1-373 BAT | 80/20 | 1.51 MW | 1.51 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966093 | AG1-478 BAT | 80/20 | 0.82 MW | 0.82 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966433 | AG1-512 BAT | 80/20 | 2.94 MW | 2.94 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966443 | AG1-513 BAT | 80/20 | 0.88 MW | 0.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 966652 | AG1-535 BAT | 80/20 | 5.8 MW | 5.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990056 | J1201 | External Queue | 4.53 MW | 4.53 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990271 | J1263 | External Queue | 30.31 MW | 30.31 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990351 | J1289 C | External Queue | 1.94 MW | 1.94 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 990856 | J1408 | External Queue | 14.12 MW | 14.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955402 | J1022 E | External Queue | 27.43 MW | 27.43 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955711 | J1055 C | External Queue | 1.73 MW | 1.73 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 955712 | J1055 E | External Queue | 9.35 MW | 9.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 956281 | J1115 C | External Queue | 6.91 MW | 6.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 956282 | J1115 E | External Queue | 37.36 MW | 37.36 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991236 | J1676 | External Queue | 74.89 MW | 74.89 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991261 | J1713 | External Queue | 22.4 MW | 22.4 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-B | 991276 | J1725 | External Queue | 7.14 MW | 7.14 MW |
| Details for AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274853 | TWINGROVE;U1 | 80/20 | 5.16 MW | 5.16 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274854 | TWINGROVE;U2 | 80/20 | 5.3 MW | 5.3 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274863 | CAYUGA RI;1U | 80/20 | 4.12 MW | 4.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274864 | CAYUGA RI;2U | 80/20 | 4.12 MW | 4.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274880 | RADFORD R;1U | 80/20 | 4.71 MW | 4.71 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 274889 | BRIGHTSTK;1U | 80/20 | 4.69 MW | 4.69 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276615 | W2-048 GEN | 80/20 | 6.4 MW | 6.4 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276621 | X2-022 GEN | 80/20 | 18.23 MW | 18.23 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 290261 | S-027 E | 80/20 | 23.46 MW | 23.46 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 290265 | S-028 E | 80/20 | 23.46 MW | 23.46 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293777 | CAYUG;1U E | 80/20 | 24.77 MW | 24.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293778 | CAYUG;2U E | 80/20 | 24.77 MW | 24.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 293798 | W4-005 E | 80/20 | 31.5 MW | 31.5 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 917502 | Z2-087 E | 80/20 | 27.86 MW | 27.86 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924041 | AB2-047 C O1 | 80/20 | 5.2 MW | 5.2 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924042 | AB2-047 E O1 | 80/20 | 34.83 MW | 34.83 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924261 | AB2-070 C O1 | 80/20 | 5.09 MW | 5.09 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 924262 | AB2-070 E O1 | 80/20 | 30.81 MW | 30.81 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 925771 | AC1-053 C | 80/20 | 4.91 MW | 4.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 925772 | AC1-053 E | 80/20 | 32.88 MW | 32.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 935141 | AD1-148 | 80/20 | 8.57 MW | 8.57 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 937001 | AD2-134 C | Adder | -1.05 MW | -0.89 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 941731 | AE2-173 O1 | 80/20 | 20.02 MW | 20.02 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 942111 | AE2-223 C | 80/20 | 6.25 MW | 6.25 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 942112 | AE2-223 E | 80/20 | 41.8 MW | 41.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 944221 | AF1-090 C O1 | 80/20 | 4.35 MW | 4.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 944222 | AF1-090 E O1 | 80/20 | 20.38 MW | 20.38 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945391 | AF1-204 C O1 | 80/20 | 2.99 MW | 2.99 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945392 | AF1-204 E O1 | 80/20 | 8.96 MW | 8.96 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945871 | AF1-252 O1 | 80/20 | 9.65 MW | 9.65 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 945881 | AF1-253 | 80/20 | 6.68 MW | 6.68 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959611 | AF2-252 C | 80/20 | 7.41 MW | 7.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959612 | AF2-252 E | 80/20 | 11.11 MW | 11.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960141 | AF2-305 | 80/20 | 1.8 MW | 1.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960261 | AF2-317 | 80/20 | 2.74 MW | 2.74 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960611 | AF2-352 C | 80/20 | 7.41 MW | 7.41 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960612 | AF2-352 E | 80/20 | 11.11 MW | 11.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 963831 | AG1-236 C | 80/20 | 4.91 MW | 4.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 963832 | AG1-236 E | 80/20 | 32.88 MW | 32.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965092 | AG1-374 E | 80/20 | 27.77 MW | 27.77 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965331 | AG1-398 | 80/20 | 1.43 MW | 1.43 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965341 | AG1-399 C O1 | 80/20 | 13.11 MW | 13.11 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965342 | AG1-399 E O1 | 80/20 | 61.37 MW | 61.37 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965351 | AG1-400 O1 | 80/20 | 46.55 MW | 46.55 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965371 | AG1-402 O1 | 80/20 | 46.55 MW | 46.55 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965391 | AG1-404 O1 | 80/20 | 31.03 MW | 31.03 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965911 | AG1-460 C | 80/20 | 2.13 MW | 2.13 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965912 | AG1-460 E | 80/20 | 3.2 MW | 3.2 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957382 | AF2-032 E | 80/20 | 0.36 MW | 0.36 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 276172 | Z1-108 BAT | 80/20 | 1.53 MW | 1.53 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 920273 | AA2-123 BAT | 80/20 | 1.42 MW | 1.42 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 943803 | AF1-048 BAT | 80/20 | 3.68 MW | 3.68 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957333 | AF2-027 BAT | 80/20 | 3.8 MW | 3.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957373 | AF2-031 BAT | 80/20 | 1.37 MW | 1.37 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 957403 | AF2-034 BAT | 80/20 | 0.88 MW | 0.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 958013 | AF2-095 BAT | 80/20 | 3.04 MW | 3.04 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 958023 | AF2-096 BAT | 80/20 | 5.64 MW | 5.64 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 959353 | AF2-226 BAT | 80/20 | 3.15 MW | 3.15 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960283 | AF2-319 BAT | 80/20 | 3.15 MW | 3.15 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960382 | AF2-329 BAT | 80/20 | 3.35 MW | 3.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 960603 | AF2-351 BAT | 80/20 | 1.52 MW | 1.52 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 961503 | AF2-441 BAT | 80/20 | 14.3 MW | 14.3 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 964362 | AG1-298 BAT | 80/20 | 35.23 MW | 35.23 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965063 | AG1-371 BAT | 80/20 | 4.54 MW | 4.54 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 965083 | AG1-373 BAT | 80/20 | 1.51 MW | 1.51 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966093 | AG1-478 BAT | 80/20 | 0.82 MW | 0.82 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966433 | AG1-512 BAT | 80/20 | 2.94 MW | 2.94 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966443 | AG1-513 BAT | 80/20 | 0.88 MW | 0.88 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 966652 | AG1-535 BAT | 80/20 | 5.8 MW | 5.8 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990056 | J1201 | External Queue | 4.53 MW | 4.53 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990271 | J1263 | External Queue | 30.31 MW | 30.31 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990351 | J1289 C | External Queue | 1.94 MW | 1.94 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 990856 | J1408 | External Queue | 14.12 MW | 14.12 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955402 | J1022 E | External Queue | 27.43 MW | 27.43 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955711 | J1055 C | External Queue | 1.73 MW | 1.73 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 955712 | J1055 E | External Queue | 9.35 MW | 9.35 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 956281 | J1115 C | External Queue | 6.91 MW | 6.91 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 956282 | J1115 E | External Queue | 37.36 MW | 37.36 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991236 | J1676 | External Queue | 74.89 MW | 74.89 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991261 | J1713 | External Queue | 22.4 MW | 22.4 MW |
| AG1-321 TAP-DRESDEN ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L11212_B-S-C | 991276 | J1725 | External Queue | 7.14 MW | 7.14 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274658 | DRESDEN ;2U | Adder | 48.02 MW | 40.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274659 | DRESDEN ;3U | Adder | 52.33 MW | 44.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274853 | TWINGROVE;U1 | 50/50 | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274854 | TWINGROVE;U2 | 50/50 | 1.73 MW | 1.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274880 | RADFORD R;1U | 50/50 | 2.74 MW | 2.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 274889 | BRIGHTSTK;1U | 50/50 | 1.3 MW | 1.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276170 | Z1-108 E | Adder | 1.34 MW | 1.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276615 | W2-048 GEN | 50/50 | 4.6 MW | 4.6 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 276621 | X2-022 GEN | 50/50 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290261 | S-027 E | 50/50 | 7.64 MW | 7.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 290265 | S-028 E | 50/50 | 7.64 MW | 7.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 293798 | W4-005 E | 50/50 | 18.35 MW | 18.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 916211 | Z1-072 E | Adder | 3.0 MW | 2.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 917502 | Z2-087 E | 50/50 | 7.75 MW | 7.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 920272 | AA2-123 E | Adder | 1.4 MW | 1.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924041 | AB2-047 C O1 | 50/50 | 1.45 MW | 1.45 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924042 | AB2-047 E O1 | 50/50 | 9.69 MW | 9.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924261 | AB2-070 C O1 | 50/50 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 924262 | AB2-070 E O1 | 50/50 | 18.89 MW | 18.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925581 | AC1-033 C | Adder | 0.88 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925582 | AC1-033 E | Adder | 5.91 MW | 5.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925771 | AC1-053 C | 50/50 | 3.17 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 925772 | AC1-053 E | 50/50 | 21.19 MW | 21.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926821 | AC1-168 C O1 | Adder | 0.64 MW | 0.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 926822 | AC1-168 E O1 | Adder | 4.29 MW | 3.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934721 | AD1-100 C | Adder | 6.39 MW | 5.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 934722 | AD1-100 E | Adder | 29.8 MW | 25.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 935141 | AD1-148 | 50/50 | 6.16 MW | 6.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 937001 | AD2-134 C | Adder | 1.06 MW | 0.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 937002 | AD2-134 E | Adder | 4.25 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938851 | AE1-113 C O1 | Adder | 3.47 MW | 2.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938852 | AE1-113 E O1 | Adder | 12.29 MW | 10.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938861 | AE1-114 C O1 | Adder | 1.85 MW | 1.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 938862 | AE1-114 E O1 | Adder | 6.3 MW | 5.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939321 | AE1-163 C O1 | Adder | 2.51 MW | 2.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939322 | AE1-163 E O1 | Adder | 15.4 MW | 13.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939401 | AE1-172 C O1 | Adder | 2.67 MW | 2.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 939402 | AE1-172 E O1 | Adder | 12.51 MW | 10.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941731 | AE2-173 O1 | 50/50 | 5.57 MW | 5.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942111 | AE2-223 C | 50/50 | 1.74 MW | 1.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942112 | AE2-223 E | 50/50 | 11.62 MW | 11.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942421 | AE2-255 C O1 | Adder | 1.31 MW | 1.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942422 | AE2-255 E O1 | Adder | 3.94 MW | 3.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942651 | AE2-281 C O1 | Adder | 0.36 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942652 | AE2-281 E O1 | Adder | 2.2 MW | 1.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 943801 | AF1-048 C | Adder | 1.87 MW | 1.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 943802 | AF1-048 E | Adder | 1.24 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944221 | AF1-090 C O1 | 50/50 | 5.41 MW | 5.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944222 | AF1-090 E O1 | 50/50 | 25.32 MW | 25.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945871 | AF1-252 O1 | 50/50 | 11.98 MW | 11.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945881 | AF1-253 | 50/50 | 8.3 MW | 8.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946161 | AF1-281 C O1 | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946162 | AF1-281 E O1 | Adder | 1.19 MW | 1.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946321 | AF1-296 C O1 | Adder | 2.36 MW | 2.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946322 | AF1-296 E O1 | Adder | 11.05 MW | 9.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946501 | AF1-314 C | Adder | 1.96 MW | 1.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946502 | AF1-314 E | Adder | 9.22 MW | 7.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946541 | AF1-318 C O1 | Adder | 3.52 MW | 2.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 946542 | AF1-318 E O1 | Adder | 16.48 MW | 14.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957331 | AF2-027 C | Adder | 1.13 MW | 0.96 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957332 | AF2-027 E | Adder | 1.69 MW | 1.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957401 | AF2-034 C | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957402 | AF2-034 E | Adder | 0.31 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957751 | AF2-069 C | Adder | 0.15 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957752 | AF2-069 E | Adder | 0.48 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957761 | AF2-070 C | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957762 | AF2-070 E | Adder | 1.01 MW | 0.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958341 | AF2-128 C O1 | Adder | 0.93 MW | 0.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958342 | AF2-128 E O1 | Adder | 4.36 MW | 3.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958921 | AF2-183 C | Adder | 2.23 MW | 1.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 958922 | AF2-183 E | Adder | 3.35 MW | 2.85 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959101 | AF2-201 C O1 | Adder | 2.71 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959102 | AF2-201 E O1 | Adder | 7.78 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959351 | AF2-226 C | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959352 | AF2-226 E | Adder | 1.75 MW | 1.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959611 | AF2-252 C | 50/50 | 2.41 MW | 2.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 959612 | AF2-252 E | 50/50 | 3.62 MW | 3.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960141 | AF2-305 | 50/50 | 1.1 MW | 1.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960261 | AF2-317 | 50/50 | 1.97 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960281 | AF2-319 C | Adder | 1.17 MW | 0.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960282 | AF2-319 E | Adder | 1.75 MW | 1.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960381 | AF2-329 | Adder | 2.22 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960611 | AF2-352 C | 50/50 | 2.41 MW | 2.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 960612 | AF2-352 E | 50/50 | 3.62 MW | 3.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961011 | AF2-392 C O1 | Adder | 2.01 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961012 | AF2-392 E O1 | Adder | 9.4 MW | 7.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961021 | AF2-393 O1 | Adder | 4.28 MW | 3.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 961031 | AF2-394 O1 | Adder | 2.85 MW | 2.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962012 | AG1-044 E | Adder | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962721 | AG1-121 C | Adder | 3.45 MW | 2.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 962722 | AG1-121 E | Adder | 16.12 MW | 13.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963831 | AG1-236 C | 50/50 | 3.17 MW | 3.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 963832 | AG1-236 E | 50/50 | 21.19 MW | 21.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965092 | AG1-374 E | 50/50 | 9.04 MW | 9.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965331 | AG1-398 | 50/50 | 0.88 MW | 0.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965341 | AG1-399 C O1 | 50/50 | 5.76 MW | 5.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965342 | AG1-399 E O1 | 50/50 | 26.99 MW | 26.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965351 | AG1-400 O1 | 50/50 | 20.47 MW | 20.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965371 | AG1-402 O1 | 50/50 | 20.47 MW | 20.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965391 | AG1-404 O1 | 50/50 | 13.65 MW | 13.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965661 | AG1-434 C | Adder | 1.85 MW | 1.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965662 | AG1-434 E | Adder | 8.66 MW | 7.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965671 | AG1-435 C | Adder | 2.35 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965672 | AG1-435 E | Adder | 11.0 MW | 9.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965911 | AG1-460 C | 50/50 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965912 | AG1-460 E | 50/50 | 3.11 MW | 3.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966091 | AG1-478 C | Adder | 0.2 MW | 0.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966092 | AG1-478 E | Adder | 0.31 MW | 0.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966441 | AG1-513 C | Adder | 0.21 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966442 | AG1-513 E | Adder | 0.32 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966821 | AG1-553 C O1 | Adder | 5.31 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 966822 | AG1-553 E O1 | Adder | 7.96 MW | 6.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 919221 | AA1-146 | Adder | 11.27 MW | 9.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 957382 | AF2-032 E | 50/50 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965061 | AG1-371 C | Adder | 1.91 MW | 1.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965062 | AG1-371 E | Adder | 2.86 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965081 | AG1-373 C | Adder | 0.64 MW | 0.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 965082 | AG1-373 E | Adder | 0.95 MW | 0.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 941343 | AE2-130 BAT | 50/50 | 32.07 MW | 32.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 942602 | AE2-276 BAT | 50/50 | 14.04 MW | 14.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 944202 | AF1-088 FTWR | 50/50 | 280.83 MW | 280.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 945351 | AF1-200 FTIR | Adder | 112.21 MW | 95.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990056 | J1201 | External Queue | 6.89 MW | 6.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990271 | J1263 | External Queue | 106.62 MW | 106.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990351 | J1289 C | External Queue | 2.01 MW | 2.01 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 990856 | J1408 | External Queue | 10.02 MW | 10.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955402 | J1022 E | External Queue | 15.8 MW | 15.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955711 | J1055 C | External Queue | 1.2 MW | 1.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 955712 | J1055 E | External Queue | 6.51 MW | 6.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956281 | J1115 C | External Queue | 2.9 MW | 2.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 956282 | J1115 E | External Queue | 15.71 MW | 15.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991236 | J1676 | External Queue | 24.78 MW | 24.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991261 | J1713 | External Queue | 19.26 MW | 19.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2 | 991276 | J1725 | External Queue | 5.14 MW | 5.14 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274658 | DRESDEN ;2U | 80/20 | 49.8 MW | 49.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274659 | DRESDEN ;3U | 80/20 | 53.84 MW | 53.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274847 | GR RIDGE ;BU | 80/20 | 0.61 MW | 0.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274848 | CAMPGROVE;RU | 80/20 | 0.91 MW | 0.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274849 | CRESCENT ;1U | 80/20 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274850 | MENDOTA H;RU | 80/20 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274851 | PROVIDENC;RU | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274853 | TWINGROVE;U1 | 80/20 | 1.66 MW | 1.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274854 | TWINGROVE;U2 | 80/20 | 1.71 MW | 1.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274855 | GSG-6 ;RU | 80/20 | 0.56 MW | 0.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274856 | ECOGROVE ;U1 | 80/20 | 0.52 MW | 0.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274857 | BIG SKY ;U1 | 80/20 | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274858 | BIG SKY ;U2 | 80/20 | 0.42 MW | 0.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274859 | EASYR;U1 E | 80/20 | 2.69 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274860 | EASYR;U2 E | 80/20 | 2.69 MW | 2.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274861 | TOP CROP ;1U | 80/20 | 0.44 MW | 0.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274862 | TOP CROP ;2U | 80/20 | 0.84 MW | 0.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274863 | CAYUGA RI;1U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274864 | CAYUGA RI;2U | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274871 | GR RIDGE ;2U | 80/20 | 0.23 MW | 0.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274872 | LEE DEKAL;1U | 80/20 | 0.98 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274877 | BISHOP HL;1U | 80/20 | 0.68 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274878 | BISHOP HL;2U | 80/20 | 0.68 MW | 0.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274879 | MINONK ;1U | 80/20 | 1.07 MW | 1.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274880 | RADFORD R;1U | 80/20 | 2.7 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274889 | BRIGHTSTK;1U | 80/20 | 1.3 MW | 1.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 274891 | OTTER CRK;1U | 80/20 | 0.54 MW | 0.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276156 | O-029 C | 80/20 | 0.38 MW | 0.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276157 | O-029 C | 80/20 | 0.41 MW | 0.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276158 | O-029 C | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276615 | W2-048 GEN | 80/20 | 4.54 MW | 4.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 276621 | X2-022 GEN | 80/20 | 12.91 MW | 12.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290021 | O50 E | 80/20 | 4.29 MW | 4.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290051 | GSG-6; E | 80/20 | 2.25 MW | 2.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290108 | LEEDK;1U E | 80/20 | 4.93 MW | 4.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290261 | S-027 E | 80/20 | 7.58 MW | 7.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 290265 | S-028 E | 80/20 | 7.58 MW | 7.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293061 | N-015 E | 80/20 | 2.66 MW | 2.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293513 | O-009 C1 | 80/20 | 0.7 MW | 0.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293514 | O-009 C2 | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293515 | O-009 C3 | 80/20 | 0.39 MW | 0.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293516 | O-009 E1 | 80/20 | 2.49 MW | 2.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293517 | O-009 E2 | 80/20 | 1.26 MW | 1.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293518 | O-009 E3 | 80/20 | 1.39 MW | 1.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293644 | O22 E1 | 80/20 | 1.97 MW | 1.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293645 | O22 E2 | 80/20 | 3.81 MW | 3.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293715 | O-029 E | 80/20 | 2.66 MW | 2.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293716 | O-029 E | 80/20 | 1.46 MW | 1.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293717 | O-029 E | 80/20 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293771 | O-035 E | 80/20 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293777 | CAYUG;1U E | 80/20 | 4.51 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293778 | CAYUG;2U E | 80/20 | 4.51 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 293798 | W4-005 E | 80/20 | 18.07 MW | 18.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 294392 | P-010 E | 80/20 | 3.38 MW | 3.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 294401 | BSHIL;1U E | 80/20 | 2.71 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 294410 | BSHIL;2U E | 80/20 | 2.71 MW | 2.71 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 294763 | P-046 E | 80/20 | 2.15 MW | 2.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 295108 | WESTBROOK C | 80/20 | 0.18 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 295109 | WESTBROOK E | 80/20 | 1.36 MW | 1.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 295110 | SUBLETTE C | 80/20 | 0.09 MW | 0.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 295111 | SUBLETTE E | 80/20 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 916211 | Z1-072 E | 80/20 | 3.02 MW | 3.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 916221 | Z1-073 E | 80/20 | 1.32 MW | 1.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 917502 | Z2-087 E | 80/20 | 7.7 MW | 7.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 918052 | AA1-018 E OP | 80/20 | 3.58 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 924041 | AB2-047 C O1 | 80/20 | 1.44 MW | 1.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 924042 | AB2-047 E O1 | 80/20 | 9.63 MW | 9.63 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 924261 | AB2-070 C O1 | 80/20 | 3.07 MW | 3.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 924262 | AB2-070 E O1 | 80/20 | 18.61 MW | 18.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 925581 | AC1-033 C | 80/20 | 0.89 MW | 0.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 925582 | AC1-033 E | 80/20 | 5.95 MW | 5.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 925771 | AC1-053 C | 80/20 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 925772 | AC1-053 E | 80/20 | 20.88 MW | 20.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 926821 | AC1-168 C O1 | 80/20 | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 926822 | AC1-168 E O1 | 80/20 | 4.34 MW | 4.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 927201 | AC1-214 C O1 | 80/20 | 0.64 MW | 0.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 927202 | AC1-214 E O1 | 80/20 | 2.04 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 934431 | AD1-067 C | 80/20 | 0.03 MW | 0.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 934432 | AD1-067 E | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 934721 | AD1-100 C | 80/20 | 6.62 MW | 6.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 934722 | AD1-100 E | 80/20 | 30.89 MW | 30.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 935141 | AD1-148 | 80/20 | 6.07 MW | 6.07 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 937001 | AD2-134 C | 80/20 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 937002 | AD2-134 E | 80/20 | 4.35 MW | 4.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 938851 | AE1-113 C O1 | 80/20 | 3.54 MW | 3.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 938852 | AE1-113 E O1 | 80/20 | 12.55 MW | 12.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 938861 | AE1-114 C O1 | 80/20 | 1.88 MW | 1.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 938862 | AE1-114 E O1 | 80/20 | 6.41 MW | 6.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 939321 | AE1-163 C O1 | 80/20 | 2.57 MW | 2.57 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 939322 | AE1-163 E O1 | 80/20 | 15.76 MW | 15.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 939401 | AE1-172 C O1 | 80/20 | 2.7 MW | 2.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 939402 | AE1-172 E O1 | 80/20 | 12.67 MW | 12.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 941731 | AE2-173 O1 | 80/20 | 5.53 MW | 5.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942111 | AE2-223 C | 80/20 | 1.73 MW | 1.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942112 | AE2-223 E | 80/20 | 11.55 MW | 11.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942421 | AE2-255 C O1 | 80/20 | 1.34 MW | 1.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942422 | AE2-255 E O1 | 80/20 | 4.02 MW | 4.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942651 | AE2-281 C O1 | 80/20 | 0.37 MW | 0.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942652 | AE2-281 E O1 | 80/20 | 2.25 MW | 2.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 943801 | AF1-048 C | 80/20 | 1.92 MW | 1.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 943802 | AF1-048 E | 80/20 | 1.28 MW | 1.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 944221 | AF1-090 C O1 | 80/20 | 5.32 MW | 5.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 944222 | AF1-090 E O1 | 80/20 | 24.9 MW | 24.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 945871 | AF1-252 O1 | 80/20 | 11.79 MW | 11.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 945881 | AF1-253 | 80/20 | 8.16 MW | 8.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946161 | AF1-281 C O1 | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946162 | AF1-281 E O1 | 80/20 | 1.21 MW | 1.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946321 | AF1-296 C O1 | 80/20 | 2.38 MW | 2.38 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946322 | AF1-296 E O1 | 80/20 | 11.14 MW | 11.14 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946501 | AF1-314 C | 80/20 | 2.0 MW | 2.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946502 | AF1-314 E | 80/20 | 9.4 MW | 9.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946541 | AF1-318 C O1 | 80/20 | 3.54 MW | 3.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 946542 | AF1-318 E O1 | 80/20 | 16.59 MW | 16.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957331 | AF2-027 C | 80/20 | 1.16 MW | 1.16 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957332 | AF2-027 E | 80/20 | 1.74 MW | 1.74 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957401 | AF2-034 C | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957402 | AF2-034 E | 80/20 | 0.32 MW | 0.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957751 | AF2-069 C | 80/20 | 0.15 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957752 | AF2-069 E | 80/20 | 0.48 MW | 0.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957761 | AF2-070 C | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957762 | AF2-070 E | 80/20 | 1.02 MW | 1.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 958341 | AF2-128 C O1 | 80/20 | 0.94 MW | 0.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 958342 | AF2-128 E O1 | 80/20 | 4.39 MW | 4.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 958921 | AF2-183 C | 80/20 | 2.27 MW | 2.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 958922 | AF2-183 E | 80/20 | 3.4 MW | 3.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959101 | AF2-201 C O1 | 80/20 | 2.76 MW | 2.76 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959102 | AF2-201 E O1 | 80/20 | 7.93 MW | 7.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959351 | AF2-226 C | 80/20 | 1.2 MW | 1.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959352 | AF2-226 E | 80/20 | 1.81 MW | 1.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959611 | AF2-252 C | 80/20 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 959612 | AF2-252 E | 80/20 | 3.59 MW | 3.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960141 | AF2-305 | 80/20 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960261 | AF2-317 | 80/20 | 1.94 MW | 1.94 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960281 | AF2-319 C | 80/20 | 1.2 MW | 1.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960282 | AF2-319 E | 80/20 | 1.81 MW | 1.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960381 | AF2-329 | 80/20 | 2.3 MW | 2.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960611 | AF2-352 C | 80/20 | 2.39 MW | 2.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 960612 | AF2-352 E | 80/20 | 3.59 MW | 3.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 961011 | AF2-392 C O1 | 80/20 | 2.04 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 961012 | AF2-392 E O1 | 80/20 | 9.54 MW | 9.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 961021 | AF2-393 O1 | 80/20 | 4.34 MW | 4.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 961031 | AF2-394 O1 | 80/20 | 2.89 MW | 2.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 962012 | AG1-044 E | 80/20 | 0.04 MW | 0.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 962721 | AG1-121 C | 80/20 | 3.47 MW | 3.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 962722 | AG1-121 E | 80/20 | 16.23 MW | 16.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 963831 | AG1-236 C | 80/20 | 3.12 MW | 3.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 963832 | AG1-236 E | 80/20 | 20.88 MW | 20.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965092 | AG1-374 E | 80/20 | 8.97 MW | 8.97 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965331 | AG1-398 | 80/20 | 0.87 MW | 0.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965341 | AG1-399 C O1 | 80/20 | 5.69 MW | 5.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965342 | AG1-399 E O1 | 80/20 | 26.65 MW | 26.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965351 | AG1-400 O1 | 80/20 | 20.22 MW | 20.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965371 | AG1-402 O1 | 80/20 | 20.22 MW | 20.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965391 | AG1-404 O1 | 80/20 | 13.48 MW | 13.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965661 | AG1-434 C | 80/20 | 1.89 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965662 | AG1-434 E | 80/20 | 8.83 MW | 8.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965671 | AG1-435 C | 80/20 | 2.37 MW | 2.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965672 | AG1-435 E | 80/20 | 11.08 MW | 11.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965911 | AG1-460 C | 80/20 | 2.04 MW | 2.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965912 | AG1-460 E | 80/20 | 3.06 MW | 3.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966091 | AG1-478 C | 80/20 | 0.21 MW | 0.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966092 | AG1-478 E | 80/20 | 0.32 MW | 0.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966441 | AG1-513 C | 80/20 | 0.22 MW | 0.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966442 | AG1-513 E | 80/20 | 0.33 MW | 0.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966821 | AG1-553 C O1 | 80/20 | 5.34 MW | 5.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 966822 | AG1-553 E O1 | 80/20 | 8.02 MW | 8.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 919221 | AA1-146 | 80/20 | 11.43 MW | 11.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 957382 | AF2-032 E | 80/20 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965061 | AG1-371 C | 80/20 | 1.95 MW | 1.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965062 | AG1-371 E | 80/20 | 2.93 MW | 2.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965081 | AG1-373 C | 80/20 | 0.65 MW | 0.65 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 965082 | AG1-373 E | 80/20 | 0.98 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 941343 | AE2-130 BAT | 80/20 | 30.06 MW | 30.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 942602 | AE2-276 BAT | 80/20 | 13.1 MW | 13.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P1-2_#286_1687 | 944202 | AF1-088 FTWR | 80/20 | 261.98 MW | 261.98 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274848 | CAMPGROVE;RU | 80/20 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274849 | CRESCENT ;1U | 80/20 | 0.27 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274850 | MENDOTA H;RU | 80/20 | 0.28 MW | 0.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274853 | TWINGROVE;U1 | 80/20 | 1.28 MW | 1.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274854 | TWINGROVE;U2 | 80/20 | 1.31 MW | 1.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274855 | GSG-6 ;RU | 80/20 | 0.47 MW | 0.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274856 | ECOGROVE ;U1 | 80/20 | 0.43 MW | 0.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274857 | BIG SKY ;U1 | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274858 | BIG SKY ;U2 | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274859 | EASYR;U1 E | 80/20 | 2.23 MW | 2.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274860 | EASYR;U2 E | 80/20 | 2.23 MW | 2.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274863 | CAYUGA RI;1U | 80/20 | 0.58 MW | 0.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274864 | CAYUGA RI;2U | 80/20 | 0.58 MW | 0.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274872 | LEE DEKAL;1U | 80/20 | 0.81 MW | 0.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274879 | MINONK ;1U | 80/20 | 0.88 MW | 0.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274880 | RADFORD R;1U | 80/20 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 274889 | BRIGHTSTK;1U | 80/20 | 0.98 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 276156 | O-029 C | 80/20 | 0.31 MW | 0.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 276157 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 276158 | O-029 C | 80/20 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 276615 | W2-048 GEN | 80/20 | 3.58 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 276621 | X2-022 GEN | 80/20 | 10.19 MW | 10.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 290021 | O50 E | 80/20 | 3.5 MW | 3.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 290051 | GSG-6; E | 80/20 | 1.86 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 290108 | LEEDK;1U E | 80/20 | 4.06 MW | 4.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 290261 | S-027 E | 80/20 | 5.81 MW | 5.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 290265 | S-028 E | 80/20 | 5.81 MW | 5.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293513 | O-009 C1 | 80/20 | 0.58 MW | 0.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293514 | O-009 C2 | 80/20 | 0.29 MW | 0.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293515 | O-009 C3 | 80/20 | 0.32 MW | 0.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293516 | O-009 E1 | 80/20 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293517 | O-009 E2 | 80/20 | 1.04 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293518 | O-009 E3 | 80/20 | 1.15 MW | 1.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293715 | O-029 E | 80/20 | 2.19 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293716 | O-029 E | 80/20 | 1.2 MW | 1.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293717 | O-029 E | 80/20 | 1.11 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293771 | O-035 E | 80/20 | 1.61 MW | 1.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293777 | CAYUG;1U E | 80/20 | 3.48 MW | 3.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293778 | CAYUG;2U E | 80/20 | 3.48 MW | 3.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 293798 | W4-005 E | 80/20 | 13.88 MW | 13.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 294401 | BSHIL;1U E | 80/20 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 294410 | BSHIL;2U E | 80/20 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 294763 | P-046 E | 80/20 | 1.78 MW | 1.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 295108 | WESTBROOK C | 80/20 | 0.15 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 295109 | WESTBROOK E | 80/20 | 1.12 MW | 1.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 295110 | SUBLETTE C | 80/20 | 0.08 MW | 0.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 295111 | SUBLETTE E | 80/20 | 0.61 MW | 0.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 916211 | Z1-072 E | 80/20 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 916221 | Z1-073 E | 80/20 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 917502 | Z2-087 E | 80/20 | 5.8 MW | 5.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 924041 | AB2-047 C O1 | 80/20 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 924042 | AB2-047 E O1 | 80/20 | 7.25 MW | 7.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 924261 | AB2-070 C O1 | 80/20 | 2.37 MW | 2.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 924262 | AB2-070 E O1 | 80/20 | 14.33 MW | 14.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 925582 | AC1-033 E | 80/20 | 4.82 MW | 4.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 925771 | AC1-053 C | 80/20 | 2.42 MW | 2.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 925772 | AC1-053 E | 80/20 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 926821 | AC1-168 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 926822 | AC1-168 E O1 | 80/20 | 3.48 MW | 3.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 927201 | AC1-214 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 927202 | AC1-214 E O1 | 80/20 | 1.64 MW | 1.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 934432 | AD1-067 E | 80/20 | 0.1 MW | 0.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 935141 | AD1-148 | 80/20 | 4.79 MW | 4.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 937001 | AD2-134 C | 80/20 | 0.9 MW | 0.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 937002 | AD2-134 E | 80/20 | 3.59 MW | 3.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 938851 | AE1-113 C O1 | 80/20 | 2.89 MW | 2.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 938852 | AE1-113 E O1 | 80/20 | 10.23 MW | 10.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 938861 | AE1-114 C O1 | 80/20 | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 938862 | AE1-114 E O1 | 80/20 | 5.32 MW | 5.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 939321 | AE1-163 C O1 | 80/20 | 2.09 MW | 2.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 939322 | AE1-163 E O1 | 80/20 | 12.86 MW | 12.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 939401 | AE1-172 C O1 | 80/20 | 2.1 MW | 2.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 939402 | AE1-172 E O1 | 80/20 | 9.84 MW | 9.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 941731 | AE2-173 O1 | 80/20 | 4.17 MW | 4.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 942111 | AE2-223 C | 80/20 | 1.3 MW | 1.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 942112 | AE2-223 E | 80/20 | 8.7 MW | 8.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 942421 | AE2-255 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 942422 | AE2-255 E O1 | 80/20 | 3.28 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 942651 | AE2-281 C O1 | 80/20 | 0.3 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 942652 | AE2-281 E O1 | 80/20 | 1.84 MW | 1.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 943801 | AF1-048 C | 80/20 | 1.58 MW | 1.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 943802 | AF1-048 E | 80/20 | 1.06 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 944221 | AF1-090 C O1 | 80/20 | 4.51 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 944222 | AF1-090 E O1 | 80/20 | 21.12 MW | 21.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 945871 | AF1-252 O1 | 80/20 | 10.0 MW | 10.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 945881 | AF1-253 | 80/20 | 6.92 MW | 6.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 946161 | AF1-281 C O1 | 80/20 | 0.18 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 946162 | AF1-281 E O1 | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 946321 | AF1-296 C O1 | 80/20 | 1.99 MW | 1.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 946322 | AF1-296 E O1 | 80/20 | 9.33 MW | 9.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 946501 | AF1-314 C | 80/20 | 1.66 MW | 1.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 946502 | AF1-314 E | 80/20 | 7.8 MW | 7.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 946541 | AF1-318 C O1 | 80/20 | 2.83 MW | 2.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 946542 | AF1-318 E O1 | 80/20 | 13.22 MW | 13.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 957752 | AF2-069 E | 80/20 | 0.39 MW | 0.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 957762 | AF2-070 E | 80/20 | 0.82 MW | 0.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 958341 | AF2-128 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 958342 | AF2-128 E O1 | 80/20 | 3.49 MW | 3.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 958921 | AF2-183 C | 80/20 | 1.89 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 958922 | AF2-183 E | 80/20 | 2.83 MW | 2.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 959101 | AF2-201 C O1 | 80/20 | 2.29 MW | 2.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 959102 | AF2-201 E O1 | 80/20 | 6.59 MW | 6.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 959611 | AF2-252 C | 80/20 | 1.83 MW | 1.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 959612 | AF2-252 E | 80/20 | 2.75 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 960141 | AF2-305 | 80/20 | 0.84 MW | 0.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 960261 | AF2-317 | 80/20 | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 960611 | AF2-352 C | 80/20 | 1.83 MW | 1.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 960612 | AF2-352 E | 80/20 | 2.75 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 961011 | AF2-392 C O1 | 80/20 | 1.69 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 961012 | AF2-392 E O1 | 80/20 | 7.92 MW | 7.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 961021 | AF2-393 O1 | 80/20 | 3.61 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 961031 | AF2-394 O1 | 80/20 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 962012 | AG1-044 E | 80/20 | 0.03 MW | 0.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 962721 | AG1-121 C | 80/20 | 2.8 MW | 2.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 962722 | AG1-121 E | 80/20 | 13.09 MW | 13.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 963831 | AG1-236 C | 80/20 | 2.42 MW | 2.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 963832 | AG1-236 E | 80/20 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965092 | AG1-374 E | 80/20 | 6.87 MW | 6.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965331 | AG1-398 | 80/20 | 0.67 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965341 | AG1-399 C O1 | 80/20 | 4.37 MW | 4.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965342 | AG1-399 E O1 | 80/20 | 20.46 MW | 20.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965351 | AG1-400 O1 | 80/20 | 15.52 MW | 15.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965371 | AG1-402 O1 | 80/20 | 15.52 MW | 15.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965391 | AG1-404 O1 | 80/20 | 10.35 MW | 10.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965661 | AG1-434 C | 80/20 | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965662 | AG1-434 E | 80/20 | 7.32 MW | 7.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965671 | AG1-435 C | 80/20 | 1.91 MW | 1.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965672 | AG1-435 E | 80/20 | 8.95 MW | 8.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965911 | AG1-460 C | 80/20 | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965912 | AG1-460 E | 80/20 | 2.52 MW | 2.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 966821 | AG1-553 C O1 | 80/20 | 4.49 MW | 4.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 966822 | AG1-553 E O1 | 80/20 | 6.73 MW | 6.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 919221 | AA1-146 | 80/20 | 9.52 MW | 9.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 957382 | AF2-032 E | 80/20 | 0.28 MW | 0.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965061 | AG1-371 C | 80/20 | 1.62 MW | 1.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965062 | AG1-371 E | 80/20 | 2.42 MW | 2.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965081 | AG1-373 C | 80/20 | 0.54 MW | 0.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 965082 | AG1-373 E | 80/20 | 0.81 MW | 0.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 941343 | AE2-130 BAT | 80/20 | 29.13 MW | 29.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 942602 | AE2-276 BAT | 80/20 | 12.86 MW | 12.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 944202 | AF1-088 FTWR | 80/20 | 257.25 MW | 257.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 945351 | AF1-200 FTIR | Adder | 95.72 MW | 81.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 990056 | J1201 | External Queue | 6.26 MW | 6.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 990271 | J1263 | External Queue | 98.41 MW | 98.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 990351 | J1289 C | External Queue | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 990856 | J1408 | External Queue | 8.15 MW | 8.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 955402 | J1022 E | External Queue | 7.55 MW | 7.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 956281 | J1115 C | External Queue | 1.93 MW | 1.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 956282 | J1115 E | External Queue | 10.42 MW | 10.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 991236 | J1676 | External Queue | 15.42 MW | 15.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o PJM_PLANT RKG1 | 991261 | J1713 | External Queue | 15.3 MW | 15.3 MW |
| Details for J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274848 | CAMPGROVE;RU | 80/20 | 0.73 MW | 0.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274849 | CRESCENT ;1U | 80/20 | 0.27 MW | 0.27 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274850 | MENDOTA H;RU | 80/20 | 0.28 MW | 0.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274851 | PROVIDENC;RU | 80/20 | 0.28 MW | 0.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274853 | TWINGROVE;U1 | 80/20 | 1.28 MW | 1.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274854 | TWINGROVE;U2 | 80/20 | 1.31 MW | 1.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274855 | GSG-6 ;RU | 80/20 | 0.47 MW | 0.47 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274856 | ECOGROVE ;U1 | 80/20 | 0.43 MW | 0.43 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274857 | BIG SKY ;U1 | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274858 | BIG SKY ;U2 | 80/20 | 0.35 MW | 0.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274859 | EASYR;U1 E | 80/20 | 2.23 MW | 2.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274860 | EASYR;U2 E | 80/20 | 2.23 MW | 2.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274863 | CAYUGA RI;1U | 80/20 | 0.58 MW | 0.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274864 | CAYUGA RI;2U | 80/20 | 0.58 MW | 0.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274872 | LEE DEKAL;1U | 80/20 | 0.81 MW | 0.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274877 | BISHOP HL;1U | 80/20 | 0.55 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274878 | BISHOP HL;2U | 80/20 | 0.55 MW | 0.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274879 | MINONK ;1U | 80/20 | 0.88 MW | 0.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274880 | RADFORD R;1U | 80/20 | 2.08 MW | 2.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 274889 | BRIGHTSTK;1U | 80/20 | 0.98 MW | 0.98 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276156 | O-029 C | 80/20 | 0.31 MW | 0.31 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276157 | O-029 C | 80/20 | 0.34 MW | 0.34 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276158 | O-029 C | 80/20 | 0.62 MW | 0.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276615 | W2-048 GEN | 80/20 | 3.58 MW | 3.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 276621 | X2-022 GEN | 80/20 | 10.19 MW | 10.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 290021 | O50 E | 80/20 | 3.5 MW | 3.5 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 290051 | GSG-6; E | 80/20 | 1.86 MW | 1.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 290108 | LEEDK;1U E | 80/20 | 4.06 MW | 4.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 290261 | S-027 E | 80/20 | 5.81 MW | 5.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 290265 | S-028 E | 80/20 | 5.81 MW | 5.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293513 | O-009 C1 | 80/20 | 0.58 MW | 0.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293514 | O-009 C2 | 80/20 | 0.29 MW | 0.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293515 | O-009 C3 | 80/20 | 0.32 MW | 0.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293516 | O-009 E1 | 80/20 | 2.05 MW | 2.05 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293517 | O-009 E2 | 80/20 | 1.04 MW | 1.04 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293518 | O-009 E3 | 80/20 | 1.15 MW | 1.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293715 | O-029 E | 80/20 | 2.19 MW | 2.19 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293716 | O-029 E | 80/20 | 1.2 MW | 1.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293717 | O-029 E | 80/20 | 1.11 MW | 1.11 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293771 | O-035 E | 80/20 | 1.61 MW | 1.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293777 | CAYUG;1U E | 80/20 | 3.48 MW | 3.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293778 | CAYUG;2U E | 80/20 | 3.48 MW | 3.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 293798 | W4-005 E | 80/20 | 13.88 MW | 13.88 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 294401 | BSHIL;1U E | 80/20 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 294410 | BSHIL;2U E | 80/20 | 2.2 MW | 2.2 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 294763 | P-046 E | 80/20 | 1.78 MW | 1.78 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 295108 | WESTBROOK C | 80/20 | 0.15 MW | 0.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 295109 | WESTBROOK E | 80/20 | 1.12 MW | 1.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 295110 | SUBLETTE C | 80/20 | 0.08 MW | 0.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 295111 | SUBLETTE E | 80/20 | 0.61 MW | 0.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 916211 | Z1-072 E | 80/20 | 2.44 MW | 2.44 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 916221 | Z1-073 E | 80/20 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 917502 | Z2-087 E | 80/20 | 5.8 MW | 5.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 924041 | AB2-047 C O1 | 80/20 | 1.08 MW | 1.08 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 924042 | AB2-047 E O1 | 80/20 | 7.25 MW | 7.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 924261 | AB2-070 C O1 | 80/20 | 2.37 MW | 2.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 924262 | AB2-070 E O1 | 80/20 | 14.33 MW | 14.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 925581 | AC1-033 C | 80/20 | 0.72 MW | 0.72 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 925582 | AC1-033 E | 80/20 | 4.82 MW | 4.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 925771 | AC1-053 C | 80/20 | 2.42 MW | 2.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 925772 | AC1-053 E | 80/20 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 926821 | AC1-168 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 926822 | AC1-168 E O1 | 80/20 | 3.48 MW | 3.48 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 927201 | AC1-214 C O1 | 80/20 | 0.52 MW | 0.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 927202 | AC1-214 E O1 | 80/20 | 1.64 MW | 1.64 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 934431 | AD1-067 C | 80/20 | 0.02 MW | 0.02 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 934432 | AD1-067 E | 80/20 | 0.1 MW | 0.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 935141 | AD1-148 | 80/20 | 4.79 MW | 4.79 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 937001 | AD2-134 C | 80/20 | 0.9 MW | 0.9 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 937002 | AD2-134 E | 80/20 | 3.59 MW | 3.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 938851 | AE1-113 C O1 | 80/20 | 2.89 MW | 2.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 938852 | AE1-113 E O1 | 80/20 | 10.23 MW | 10.23 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 938861 | AE1-114 C O1 | 80/20 | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 938862 | AE1-114 E O1 | 80/20 | 5.32 MW | 5.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939321 | AE1-163 C O1 | 80/20 | 2.09 MW | 2.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939322 | AE1-163 E O1 | 80/20 | 12.86 MW | 12.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939401 | AE1-172 C O1 | 80/20 | 2.1 MW | 2.1 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 939402 | AE1-172 E O1 | 80/20 | 9.84 MW | 9.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 941731 | AE2-173 O1 | 80/20 | 4.17 MW | 4.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942111 | AE2-223 C | 80/20 | 1.3 MW | 1.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942112 | AE2-223 E | 80/20 | 8.7 MW | 8.7 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942421 | AE2-255 C O1 | 80/20 | 1.09 MW | 1.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942422 | AE2-255 E O1 | 80/20 | 3.28 MW | 3.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942651 | AE2-281 C O1 | 80/20 | 0.3 MW | 0.3 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942652 | AE2-281 E O1 | 80/20 | 1.84 MW | 1.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 943801 | AF1-048 C | 80/20 | 1.58 MW | 1.58 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 943802 | AF1-048 E | 80/20 | 1.06 MW | 1.06 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 944221 | AF1-090 C O1 | 80/20 | 4.51 MW | 4.51 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 944222 | AF1-090 E O1 | 80/20 | 21.12 MW | 21.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 945871 | AF1-252 O1 | 80/20 | 10.0 MW | 10.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 945881 | AF1-253 | 80/20 | 6.92 MW | 6.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946161 | AF1-281 C O1 | 80/20 | 0.18 MW | 0.18 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946162 | AF1-281 E O1 | 80/20 | 1.0 MW | 1.0 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946321 | AF1-296 C O1 | 80/20 | 1.99 MW | 1.99 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946322 | AF1-296 E O1 | 80/20 | 9.33 MW | 9.33 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946501 | AF1-314 C | 80/20 | 1.66 MW | 1.66 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946502 | AF1-314 E | 80/20 | 7.8 MW | 7.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946541 | AF1-318 C O1 | 80/20 | 2.83 MW | 2.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 946542 | AF1-318 E O1 | 80/20 | 13.22 MW | 13.22 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957751 | AF2-069 C | 80/20 | 0.12 MW | 0.12 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957752 | AF2-069 E | 80/20 | 0.39 MW | 0.39 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957761 | AF2-070 C | 80/20 | 0.17 MW | 0.17 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957762 | AF2-070 E | 80/20 | 0.82 MW | 0.82 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958341 | AF2-128 C O1 | 80/20 | 0.75 MW | 0.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958342 | AF2-128 E O1 | 80/20 | 3.49 MW | 3.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958921 | AF2-183 C | 80/20 | 1.89 MW | 1.89 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 958922 | AF2-183 E | 80/20 | 2.83 MW | 2.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959101 | AF2-201 C O1 | 80/20 | 2.29 MW | 2.29 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959102 | AF2-201 E O1 | 80/20 | 6.59 MW | 6.59 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959611 | AF2-252 C | 80/20 | 1.83 MW | 1.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 959612 | AF2-252 E | 80/20 | 2.75 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960141 | AF2-305 | 80/20 | 0.84 MW | 0.84 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960261 | AF2-317 | 80/20 | 1.53 MW | 1.53 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960611 | AF2-352 C | 80/20 | 1.83 MW | 1.83 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 960612 | AF2-352 E | 80/20 | 2.75 MW | 2.75 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961011 | AF2-392 C O1 | 80/20 | 1.69 MW | 1.69 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961012 | AF2-392 E O1 | 80/20 | 7.92 MW | 7.92 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961021 | AF2-393 O1 | 80/20 | 3.61 MW | 3.61 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 961031 | AF2-394 O1 | 80/20 | 2.4 MW | 2.4 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 962012 | AG1-044 E | 80/20 | 0.03 MW | 0.03 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 962721 | AG1-121 C | 80/20 | 2.8 MW | 2.8 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 962722 | AG1-121 E | 80/20 | 13.09 MW | 13.09 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 963831 | AG1-236 C | 80/20 | 2.42 MW | 2.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 963832 | AG1-236 E | 80/20 | 16.21 MW | 16.21 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965092 | AG1-374 E | 80/20 | 6.87 MW | 6.87 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965331 | AG1-398 | 80/20 | 0.67 MW | 0.67 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965341 | AG1-399 C O1 | 80/20 | 4.37 MW | 4.37 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965342 | AG1-399 E O1 | 80/20 | 20.46 MW | 20.46 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965351 | AG1-400 O1 | 80/20 | 15.52 MW | 15.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965371 | AG1-402 O1 | 80/20 | 15.52 MW | 15.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965391 | AG1-404 O1 | 80/20 | 10.35 MW | 10.35 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965661 | AG1-434 C | 80/20 | 1.56 MW | 1.56 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965662 | AG1-434 E | 80/20 | 7.32 MW | 7.32 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965671 | AG1-435 C | 80/20 | 1.91 MW | 1.91 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965672 | AG1-435 E | 80/20 | 8.95 MW | 8.95 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965911 | AG1-460 C | 80/20 | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965912 | AG1-460 E | 80/20 | 2.52 MW | 2.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 966821 | AG1-553 C O1 | 80/20 | 4.49 MW | 4.49 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 966822 | AG1-553 E O1 | 80/20 | 6.73 MW | 6.73 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 919221 | AA1-146 | 80/20 | 9.52 MW | 9.52 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 957382 | AF2-032 E | 80/20 | 0.28 MW | 0.28 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965061 | AG1-371 C | 80/20 | 1.62 MW | 1.62 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965062 | AG1-371 E | 80/20 | 2.42 MW | 2.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965081 | AG1-373 C | 80/20 | 0.54 MW | 0.54 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 965082 | AG1-373 E | 80/20 | 0.81 MW | 0.81 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 941343 | AE2-130 BAT | 80/20 | 29.13 MW | 29.13 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 942602 | AE2-276 BAT | 80/20 | 12.86 MW | 12.86 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 944202 | AF1-088 FTWR | 80/20 | 257.25 MW | 257.25 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 945351 | AF1-200 FTIR | Adder | 95.72 MW | 81.36 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990056 | J1201 | External Queue | 6.26 MW | 6.26 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990271 | J1263 | External Queue | 98.41 MW | 98.41 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990351 | J1289 C | External Queue | 1.68 MW | 1.68 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 990856 | J1408 | External Queue | 8.15 MW | 8.15 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 955402 | J1022 E | External Queue | 7.55 MW | 7.55 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 956281 | J1115 C | External Queue | 1.93 MW | 1.93 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 956282 | J1115 E | External Queue | 10.42 MW | 10.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991236 | J1676 | External Queue | 15.42 MW | 15.42 MW |
| J1180 TAP-05SULLIVAN 345.0 kV Ckt 1 line l/o Base Case | 991261 | J1713 | External Queue | 15.3 MW | 15.3 MW |
| Details for MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274853 | TWINGROVE;U1 | 80/20 | 3.08 MW | 3.08 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274854 | TWINGROVE;U2 | 80/20 | 3.16 MW | 3.16 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274880 | RADFORD R;1U | 80/20 | 4.03 MW | 4.03 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 274889 | BRIGHTSTK;1U | 80/20 | 6.83 MW | 6.83 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276615 | W2-048 GEN | 80/20 | 7.73 MW | 7.73 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276621 | X2-022 GEN | 80/20 | 22.0 MW | 22.0 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 290261 | S-027 E | 80/20 | 14.0 MW | 14.0 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 290265 | S-028 E | 80/20 | 14.0 MW | 14.0 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 293798 | W4-005 E | 80/20 | 26.98 MW | 26.98 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 917502 | Z2-087 E | 80/20 | 40.58 MW | 40.58 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924041 | AB2-047 C O1 | 80/20 | 7.58 MW | 7.58 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924042 | AB2-047 E O1 | 80/20 | 50.72 MW | 50.72 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924261 | AB2-070 C O1 | 80/20 | 6.45 MW | 6.45 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 924262 | AB2-070 E O1 | 80/20 | 39.05 MW | 39.05 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 925771 | AC1-053 C | 80/20 | 6.14 MW | 6.14 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 925772 | AC1-053 E | 80/20 | 41.09 MW | 41.09 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 935141 | AD1-148 | 80/20 | 10.34 MW | 10.34 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 937001 | AD2-134 C | Adder | -0.96 MW | -0.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 941731 | AE2-173 O1 | 80/20 | 29.15 MW | 29.15 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 942111 | AE2-223 C | 80/20 | 9.1 MW | 9.1 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 942112 | AE2-223 E | 80/20 | 60.86 MW | 60.86 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 942601 | AE2-276 | 80/20 | 2.79 MW | 2.79 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944221 | AF1-090 C O1 | 80/20 | 4.74 MW | 4.74 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944222 | AF1-090 E O1 | 80/20 | 22.18 MW | 22.18 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945391 | AF1-204 C O1 | 80/20 | 3.48 MW | 3.48 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945392 | AF1-204 E O1 | 80/20 | 10.44 MW | 10.44 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945871 | AF1-252 O1 | 80/20 | 10.5 MW | 10.5 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 945881 | AF1-253 | 80/20 | 7.27 MW | 7.27 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959611 | AF2-252 C | 80/20 | 4.42 MW | 4.42 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959612 | AF2-252 E | 80/20 | 6.63 MW | 6.63 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960141 | AF2-305 | 80/20 | 2.28 MW | 2.28 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960261 | AF2-317 | 80/20 | 3.31 MW | 3.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960611 | AF2-352 C | 80/20 | 4.42 MW | 4.42 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960612 | AF2-352 E | 80/20 | 6.63 MW | 6.63 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 963831 | AG1-236 C | 80/20 | 6.14 MW | 6.14 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 963832 | AG1-236 E | 80/20 | 41.09 MW | 41.09 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965092 | AG1-374 E | 80/20 | 16.57 MW | 16.57 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965331 | AG1-398 | 80/20 | 1.82 MW | 1.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965341 | AG1-399 C O1 | 80/20 | 9.34 MW | 9.34 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965342 | AG1-399 E O1 | 80/20 | 43.71 MW | 43.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965351 | AG1-400 O1 | 80/20 | 33.15 MW | 33.15 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965371 | AG1-402 O1 | 80/20 | 33.15 MW | 33.15 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965391 | AG1-404 O1 | 80/20 | 22.1 MW | 22.1 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965911 | AG1-460 C | 80/20 | 2.3 MW | 2.3 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965912 | AG1-460 E | 80/20 | 3.45 MW | 3.45 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957382 | AF2-032 E | 80/20 | 0.39 MW | 0.39 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 276172 | Z1-108 BAT | 80/20 | 1.43 MW | 1.43 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 920273 | AA2-123 BAT | 80/20 | 1.31 MW | 1.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 943803 | AF1-048 BAT | 80/20 | 3.41 MW | 3.41 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 944201 | AF1-088 FTIR | 80/20 | 55.8 MW | 55.8 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957141 | AF2-008 FTIR | 80/20 | 27.9 MW | 27.9 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957333 | AF2-027 BAT | 80/20 | 3.59 MW | 3.59 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957373 | AF2-031 BAT | 80/20 | 1.58 MW | 1.58 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 957403 | AF2-034 BAT | 80/20 | 0.83 MW | 0.83 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 958013 | AF2-095 BAT | 80/20 | 4.03 MW | 4.03 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 958023 | AF2-096 BAT | 80/20 | 7.82 MW | 7.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 959353 | AF2-226 BAT | 80/20 | 2.99 MW | 2.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960283 | AF2-319 BAT | 80/20 | 2.99 MW | 2.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960382 | AF2-329 BAT | 80/20 | 3.28 MW | 3.28 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 960603 | AF2-351 BAT | 80/20 | 2.01 MW | 2.01 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 961503 | AF2-441 BAT | 80/20 | 16.45 MW | 16.45 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 964362 | AG1-298 BAT | 80/20 | 40.67 MW | 40.67 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965063 | AG1-371 BAT | 80/20 | 4.14 MW | 4.14 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 965083 | AG1-373 BAT | 80/20 | 1.38 MW | 1.38 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966093 | AG1-478 BAT | 80/20 | 0.88 MW | 0.88 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966433 | AG1-512 BAT | 80/20 | 3.3 MW | 3.3 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966443 | AG1-513 BAT | 80/20 | 0.82 MW | 0.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 966652 | AG1-535 BAT | 80/20 | 6.71 MW | 6.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990056 | J1201 | External Queue | 4.75 MW | 4.75 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990271 | J1263 | External Queue | 32.23 MW | 32.23 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990351 | J1289 C | External Queue | 2.13 MW | 2.13 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 990856 | J1408 | External Queue | 14.85 MW | 14.85 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955402 | J1022 E | External Queue | 34.21 MW | 34.21 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955711 | J1055 C | External Queue | 1.99 MW | 1.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 955712 | J1055 E | External Queue | 10.78 MW | 10.78 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 956281 | J1115 C | External Queue | 6.82 MW | 6.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 956282 | J1115 E | External Queue | 36.91 MW | 36.91 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991236 | J1676 | External Queue | 94.19 MW | 94.19 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991261 | J1713 | External Queue | 23.71 MW | 23.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L8002___-S | 991276 | J1725 | External Queue | 8.35 MW | 8.35 MW |
| Details for MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 274880 | RADFORD R;1U | 80/20 | 4.05 MW | 4.05 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 274889 | BRIGHTSTK;1U | 80/20 | 6.84 MW | 6.84 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 276615 | W2-048 GEN | 80/20 | 7.76 MW | 7.76 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 276621 | X2-022 GEN | 80/20 | 22.07 MW | 22.07 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 293798 | W4-005 E | 80/20 | 27.09 MW | 27.09 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 917502 | Z2-087 E | 80/20 | 40.64 MW | 40.64 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 924041 | AB2-047 C O1 | 80/20 | 7.59 MW | 7.59 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 924042 | AB2-047 E O1 | 80/20 | 50.8 MW | 50.8 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 924261 | AB2-070 C O1 | 80/20 | 6.47 MW | 6.47 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 924262 | AB2-070 E O1 | 80/20 | 39.17 MW | 39.17 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 925771 | AC1-053 C | 80/20 | 6.16 MW | 6.16 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 925772 | AC1-053 E | 80/20 | 41.22 MW | 41.22 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 935141 | AD1-148 | 80/20 | 10.38 MW | 10.38 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 937001 | AD2-134 C | Adder | -0.94 MW | -0.8 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 941731 | AE2-173 O1 | 80/20 | 29.2 MW | 29.2 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 942111 | AE2-223 C | 80/20 | 9.11 MW | 9.11 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 942112 | AE2-223 E | 80/20 | 60.96 MW | 60.96 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 942601 | AE2-276 | 80/20 | 2.84 MW | 2.84 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 944221 | AF1-090 C O1 | 80/20 | 4.76 MW | 4.76 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 944222 | AF1-090 E O1 | 80/20 | 22.3 MW | 22.3 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 945391 | AF1-204 C O1 | 80/20 | 3.53 MW | 3.53 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 945392 | AF1-204 E O1 | 80/20 | 10.58 MW | 10.58 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 945871 | AF1-252 O1 | 80/20 | 10.56 MW | 10.56 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 945881 | AF1-253 | 80/20 | 7.31 MW | 7.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960141 | AF2-305 | 80/20 | 2.29 MW | 2.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960261 | AF2-317 | 80/20 | 3.32 MW | 3.32 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 963831 | AG1-236 C | 80/20 | 6.16 MW | 6.16 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 963832 | AG1-236 E | 80/20 | 41.22 MW | 41.22 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965331 | AG1-398 | 80/20 | 1.82 MW | 1.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965341 | AG1-399 C O1 | 80/20 | 9.38 MW | 9.38 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965342 | AG1-399 E O1 | 80/20 | 43.9 MW | 43.9 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965351 | AG1-400 O1 | 80/20 | 33.29 MW | 33.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965371 | AG1-402 O1 | 80/20 | 33.29 MW | 33.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965391 | AG1-404 O1 | 80/20 | 22.2 MW | 22.2 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965911 | AG1-460 C | 80/20 | 2.31 MW | 2.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965912 | AG1-460 E | 80/20 | 3.47 MW | 3.47 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957382 | AF2-032 E | 80/20 | 0.39 MW | 0.39 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 276172 | Z1-108 BAT | 80/20 | 1.41 MW | 1.41 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 920273 | AA2-123 BAT | 80/20 | 1.29 MW | 1.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 943803 | AF1-048 BAT | 80/20 | 3.36 MW | 3.36 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 944201 | AF1-088 FTIR | 80/20 | 56.76 MW | 56.76 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957141 | AF2-008 FTIR | 80/20 | 28.38 MW | 28.38 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957333 | AF2-027 BAT | 80/20 | 3.54 MW | 3.54 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957373 | AF2-031 BAT | 80/20 | 1.56 MW | 1.56 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 957403 | AF2-034 BAT | 80/20 | 0.82 MW | 0.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 958013 | AF2-095 BAT | 80/20 | 3.99 MW | 3.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 958023 | AF2-096 BAT | 80/20 | 7.75 MW | 7.75 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 959353 | AF2-226 BAT | 80/20 | 2.94 MW | 2.94 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 959613 | AF2-252 BAT | 80/20 | 15.68 MW | 15.68 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960283 | AF2-319 BAT | 80/20 | 2.94 MW | 2.94 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960382 | AF2-329 BAT | 80/20 | 3.24 MW | 3.24 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960603 | AF2-351 BAT | 80/20 | 1.99 MW | 1.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 960613 | AF2-352 BAT | 80/20 | 15.68 MW | 15.68 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 961503 | AF2-441 BAT | 80/20 | 16.26 MW | 16.26 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 964362 | AG1-298 BAT | 80/20 | 40.2 MW | 40.2 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965063 | AG1-371 BAT | 80/20 | 4.07 MW | 4.07 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 965083 | AG1-373 BAT | 80/20 | 1.36 MW | 1.36 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 966093 | AG1-478 BAT | 80/20 | 0.87 MW | 0.87 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 966433 | AG1-512 BAT | 80/20 | 3.26 MW | 3.26 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 966443 | AG1-513 BAT | 80/20 | 0.81 MW | 0.81 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 966652 | AG1-535 BAT | 80/20 | 6.63 MW | 6.63 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 990056 | J1201 | External Queue | 4.75 MW | 4.75 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 990271 | J1263 | External Queue | 32.23 MW | 32.23 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 990351 | J1289 C | External Queue | 2.13 MW | 2.13 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 990856 | J1408 | External Queue | 14.85 MW | 14.85 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 955402 | J1022 E | External Queue | 34.21 MW | 34.21 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 955711 | J1055 C | External Queue | 1.99 MW | 1.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 955712 | J1055 E | External Queue | 10.78 MW | 10.78 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 956281 | J1115 C | External Queue | 6.82 MW | 6.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 956282 | J1115 E | External Queue | 36.91 MW | 36.91 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 991236 | J1676 | External Queue | 94.19 MW | 94.19 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 991261 | J1713 | External Queue | 23.71 MW | 23.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9515___-S-B | 991276 | J1725 | External Queue | 8.35 MW | 8.35 MW |
| Details for MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 274889 | BRIGHTSTK;1U | 80/20 | 6.85 MW | 6.85 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 276615 | W2-048 GEN | 80/20 | 7.78 MW | 7.78 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 276621 | X2-022 GEN | 80/20 | 22.15 MW | 22.15 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 917502 | Z2-087 E | 80/20 | 40.7 MW | 40.7 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 924041 | AB2-047 C O1 | 80/20 | 7.6 MW | 7.6 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 924042 | AB2-047 E O1 | 80/20 | 50.88 MW | 50.88 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 924261 | AB2-070 C O1 | 80/20 | 6.49 MW | 6.49 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 924262 | AB2-070 E O1 | 80/20 | 39.28 MW | 39.28 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 925771 | AC1-053 C | 80/20 | 6.18 MW | 6.18 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 925772 | AC1-053 E | 80/20 | 41.34 MW | 41.34 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 935141 | AD1-148 | 80/20 | 10.41 MW | 10.41 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 937001 | AD2-134 C | Adder | -0.93 MW | -0.79 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 941731 | AE2-173 O1 | 80/20 | 29.24 MW | 29.24 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 942111 | AE2-223 C | 80/20 | 9.12 MW | 9.12 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 942112 | AE2-223 E | 80/20 | 61.05 MW | 61.05 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 942601 | AE2-276 | 80/20 | 2.88 MW | 2.88 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 944221 | AF1-090 C O1 | 80/20 | 4.79 MW | 4.79 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 944222 | AF1-090 E O1 | 80/20 | 22.42 MW | 22.42 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 945391 | AF1-204 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 945392 | AF1-204 E O1 | 80/20 | 10.71 MW | 10.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 945871 | AF1-252 O1 | 80/20 | 10.61 MW | 10.61 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 945881 | AF1-253 | 80/20 | 7.35 MW | 7.35 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 960141 | AF2-305 | 80/20 | 2.29 MW | 2.29 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 960261 | AF2-317 | 80/20 | 3.33 MW | 3.33 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 963831 | AG1-236 C | 80/20 | 6.18 MW | 6.18 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 963832 | AG1-236 E | 80/20 | 41.34 MW | 41.34 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 965331 | AG1-398 | 80/20 | 1.83 MW | 1.83 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 965911 | AG1-460 C | 80/20 | 2.32 MW | 2.32 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 965912 | AG1-460 E | 80/20 | 3.48 MW | 3.48 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 957382 | AF2-032 E | 80/20 | 0.39 MW | 0.39 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 276172 | Z1-108 BAT | 80/20 | 1.4 MW | 1.4 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 920273 | AA2-123 BAT | 80/20 | 1.27 MW | 1.27 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 943803 | AF1-048 BAT | 80/20 | 3.31 MW | 3.31 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 944201 | AF1-088 FTIR | 80/20 | 57.62 MW | 57.62 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 957141 | AF2-008 FTIR | 80/20 | 28.81 MW | 28.81 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 957333 | AF2-027 BAT | 80/20 | 3.5 MW | 3.5 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 957373 | AF2-031 BAT | 80/20 | 1.54 MW | 1.54 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 957403 | AF2-034 BAT | 80/20 | 0.81 MW | 0.81 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 958013 | AF2-095 BAT | 80/20 | 3.95 MW | 3.95 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 958023 | AF2-096 BAT | 80/20 | 7.69 MW | 7.69 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 959353 | AF2-226 BAT | 80/20 | 2.9 MW | 2.9 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 959613 | AF2-252 BAT | 80/20 | 15.64 MW | 15.64 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 960283 | AF2-319 BAT | 80/20 | 2.9 MW | 2.9 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 960382 | AF2-329 BAT | 80/20 | 3.2 MW | 3.2 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 960603 | AF2-351 BAT | 80/20 | 1.98 MW | 1.98 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 960613 | AF2-352 BAT | 80/20 | 15.64 MW | 15.64 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 961503 | AF2-441 BAT | 80/20 | 16.09 MW | 16.09 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 964362 | AG1-298 BAT | 80/20 | 39.77 MW | 39.77 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 965063 | AG1-371 BAT | 80/20 | 4.01 MW | 4.01 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 965083 | AG1-373 BAT | 80/20 | 1.33 MW | 1.33 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 965352 | AG1-400 BAT | 80/20 | 46.91 MW | 46.91 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 965372 | AG1-402 BAT | 80/20 | 46.91 MW | 46.91 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 965392 | AG1-404 BAT | 80/20 | 31.27 MW | 31.27 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 966093 | AG1-478 BAT | 80/20 | 0.86 MW | 0.86 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 966433 | AG1-512 BAT | 80/20 | 3.23 MW | 3.23 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 966443 | AG1-513 BAT | 80/20 | 0.8 MW | 0.8 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 966652 | AG1-535 BAT | 80/20 | 6.56 MW | 6.56 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 990056 | J1201 | External Queue | 4.75 MW | 4.75 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 990271 | J1263 | External Queue | 32.23 MW | 32.23 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 990351 | J1289 C | External Queue | 2.13 MW | 2.13 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 990856 | J1408 | External Queue | 14.85 MW | 14.85 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 955402 | J1022 E | External Queue | 34.21 MW | 34.21 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 955711 | J1055 C | External Queue | 1.99 MW | 1.99 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 955712 | J1055 E | External Queue | 10.78 MW | 10.78 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 956281 | J1115 C | External Queue | 6.82 MW | 6.82 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 956282 | J1115 E | External Queue | 36.91 MW | 36.91 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 991236 | J1676 | External Queue | 94.19 MW | 94.19 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 991261 | J1713 | External Queue | 23.71 MW | 23.71 MW |
| MCLEAN ; R-PONTIAC ; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L9503___-S | 991276 | J1725 | External Queue | 8.35 MW | 8.35 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| b3775.11 | Upgrade the limiting element at Stillwell substation to increase the rating of the Stillwell-Dumont. | $0 | |
| b3775.7 | Upgrade limiting element at Dumont substation on the Stillwell-Dumont 345 kV line. | $0 | |
| b3775.6 | Perform sag study mitigation work on the Dumont-Stillwell 345 kV line | $0 | |
| n5769.2 | Replace two Dumont 3000A Non-Oil breakers. | $2,000,000 | |
| (TBD) | Rebuild NIPS portion of line and upgrade substation conductor (MISO - Upgrade #2) | $8,000,000 | |
| n5769.4 | Rebuild/Recondutor 8.6 miles of ACSR ~ 954 ~ 45/7 ~ RAIL conductor to mitigate the overload | $17,200,000 | |
| n5769.3 | Replace 11 jumpers/risers at Dumont substation | $275,000 | |
| (TBD) | Upgrade transmission conductor and conductor drop.. (MISO - Upgrade #3) | $6,500,000 | |
| n7925.1 | Reconductor/rebuild 0.82 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 5 | $1,640,000 | |
| n7925.2 | Reconductor/rebuild 1 miles of ACAR ~ 1024.5 ~ 30/7 ~ RAIL1 conductor section 6 | $2,000,000 | |
| n7925.3 | Replace two sullivan 3000A Wavetrap | $400,000 | |
| n7925.4 | Replace three 2-2000 AAC 91 Str | $300,000 | |
| (TBD) | Brokaw - AB2-070 - AC1-053 345 kV Line - Mitigate Sag on the Line. | $17,300,000 | |
| (TBD) | MISO (AMIL) Review required | $0 | |
| n7207 | AD1-100 - AE1-172 - Loretto - replace-4-345kV circuit breakers, upgrade a line relay scheme, station conductor upgrades at both terminals | $47,000,000 | |
| n8403 | Construct a new 345kV line from TSS 93 Loretto to TSS 905 Essex (AD1-100 Interconnection Substation) | $127,000,000 | |
| n8091 | The upgrade will be to mitigate sag on the line, upgrade station conductor at both terminals and upgrade two 345 kV CBs at Pontiac. | $21,800,000 | |
| (TBD) | Additional ComEd Reinforcement Needed | $0 | |
| n6260.1 | Upgrade of TSS 80 Pontiac 345kV circuit breaker BT 4-5 and 345kV station and bus conductor | $4,000,000 | |
| n6260.2 | Replace a line disconnect switch to upgrade the Pontiac - Loretto 345 kV line. | $500,000 | |
| n6260.3 | ComEd 345kV L8012 SSTE rating is 1846 MVA. Station upgrade and line re-conductoring, ratings will be 1754/2246/2297/2488 MVA (SN/SLTE/SSTE/SLD). | $61,500,000 | |
| n7938 | Construct a new 345kV line from TSS 80 Pontiac to TSS 196 Katydid. New 345kV circuit breakers, relay upgrades and 345kV bus expansion | $127,000,000 | |
| n6261.1 | Mitigate Sag on the Pontiac - AD1-133 Tap 345 kV Line | $12,300,000 | |
| n7941 | Pontiac - Z2-087 (McLean) Sag Mitigation | $10,500,000 | |
| n7941.1 | Pontiac - Z2-087 (McLean) 345 kV line - upgarde station conductor at both stations and upgrade 2-138kV line traps. | $2,200,000 | |
| n6563 | Reconductor and terminal upgrades at Wilton Center. | $43,200,000 | |
| n5808 | AEP: eliminate the Eugene stuck breaker contingency. (AMIL upgrade will not be required) | $3,424,014 | |
| n8379 | Wilton Center - Install 3rd Transformer | $38,000,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-400 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.