AG1-297 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:53
Hanna-Tanners Creek 345 kV
200.0 MW Capacity / 500.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-297 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Storage generating facility located in the AEP zone — Shelby County, Indiana. The installed facilities will have a total capability of 500.0 MW with 200.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-297 |
| Project Name | Hanna-Tanners Creek 345 kV |
| Developer Name | Hecate Energy Blue River LLC |
| State | Indiana |
| County | Shelby |
| Transmission Owner | AEP |
| MFO | 500.0 MW |
| MWE | 500.0 MW |
| MWC | 200.0 MW |
| Fuel Type | Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-297 will interconnect on the AEP transmission system tapping the Hanna to Tanners Creek 345 kV line.
Summer Peak Analysis
The Queue Project was evaluated as a 500.0 MW (Capacity 200.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| AEP/DEI |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line
243221 to 249504 ckt 1 |
AEP_P4_#4697_05DEQUIN 345_B
CONTINGENCY 'AEP_P4_#4697_05DEQUIN 345_B' OPEN BRANCH FROM BUS 243217 TO BUS 243878 CKT 1 /*05DEQUIN 345.0 - 05MEADOW 345.0 OPEN BRANCH FROM BUS 243217 TO BUS 963840 CKT 1 /*05DEQUIN 345.0 - AG1-237 TAP 345.0 END |
Breaker | AC | 112.07 % | 113.69 % | 1374.0 | B | 1562.07 | 31.61 | |
| OVEC |
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
248001 to 248013 ckt 1 |
DEOK_P2-3_1403_MIAMIFORT
CONTINGENCY 'DEOK_P2-3_1403_MIAMIFORT' OPEN BRANCH FROM BUS 249567 TO BUS 243233 CKT 1 /*08M.FORT 345.0 - 05TANNER 345.0 OPEN BRANCH FROM BUS 249567 TO BUS 251950 CKT 7 /*08M.FORT 345.0 - 08M.FRT7 22.0 END |
Breaker | AC | 108.81 % | 115.49 % | 971.0 | B | 1121.37 | 63.14 | |
| OVEC |
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
248001 to 248013 ckt 1 |
DEOK_P2-3_1401_MIAMIFORT
CONTINGENCY 'DEOK_P2-3_1401_MIAMIFORT' OPEN BRANCH FROM BUS 249567 TO BUS 243233 CKT 1 /*08M.FORT 345.0 - 05TANNER 345.0 OPEN BRANCH FROM BUS 249567 TO BUS 250057 CKT 9 /*08M.FORT 345.0 - 08M.FORT 138.0 END |
Breaker | AC | 108.33 % | 115.01 % | 971.0 | B | 1116.79 | 63.15 | |
| AEP/DEO&K |
05TANNER-08M.FORT 345.0 kV Ckt 1 line
243233 to 249567 ckt 1 |
AEP_P4_#9456_06DEARB1 345_DC
CONTINGENCY 'AEP_P4_#9456_06DEARB1 345_DC' OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1 /*05TANNER 345.0 - 06DEARB1 345.0 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1 /*05TANNER 345.0 - 08EBEND 345.0 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1 /*06CLIFTY 345.0 - 06DEARB1 345.0 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1 /*06DEARB1 345.0 - 06PIERCE 345.0 END |
Breaker | AC | 106.45 % | 113.79 % | 2151.0 | B | 2447.54 | 155.81 | |
| AEP/OVEC |
05TANNER-06DEARB1 345.0 kV Ckt Z1 line
243233 to 248001 ckt Z1 |
DEOK_P2-3_1401_MIAMIFORT
CONTINGENCY 'DEOK_P2-3_1401_MIAMIFORT' OPEN BRANCH FROM BUS 249567 TO BUS 243233 CKT 1 /*08M.FORT 345.0 - 05TANNER 345.0 OPEN BRANCH FROM BUS 249567 TO BUS 250057 CKT 9 /*08M.FORT 345.0 - 08M.FORT 138.0 END |
Breaker | AC | 103.63 % | 112.75 % | 1204.0 | B | 1357.49 | 107.16 | |
| AEP/DEO&K |
05TANNER-08M.FORT 345.0 kV Ckt 1 line
243233 to 249567 ckt 1 |
AEP_P2-2_#9456_06DEARB1 345_1
CONTINGENCY 'AEP_P2-2_#9456_06DEARB1 345_1' OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1 /*05TANNER 345.0 - 06DEARB1 345.0 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1 /*05TANNER 345.0 - 08EBEND 345.0 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1 /*06CLIFTY 345.0 - 06DEARB1 345.0 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1 /*06DEARB1 345.0 - 06PIERCE 345.0 END |
Bus | AC | 106.47 % | 113.8 % | 2151.0 | B | 2447.75 | 155.81 | |
| AEP/OVEC |
05TANNER-06DEARB1 345.0 kV Ckt Z1 line
243233 to 248001 ckt Z1 |
DEOK_P7_4504MFTANNERS4512EBTANNERS
CONTINGENCY 'DEOK_P7_4504MFTANNERS4512EBTANNERS' OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1 /*05TANNER 345.0 - 08EBEND 345.0 OPEN BRANCH FROM BUS 243233 TO BUS 249567 CKT 1 /*05TANNER 345.0 - 08M.FORT 345.0 END |
Tower | AC | 143.26 % | 154.99 % | 1204.0 | B | 1866.04 | 138.95 | |
| OVEC |
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
248001 to 248013 ckt 1 |
DEOK_P7_4504MFTANNERS4512EBTANNERS
CONTINGENCY 'DEOK_P7_4504MFTANNERS4512EBTANNERS' OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1 /*05TANNER 345.0 - 08EBEND 345.0 OPEN BRANCH FROM BUS 243233 TO BUS 249567 CKT 1 /*05TANNER 345.0 - 08M.FORT 345.0 END |
Tower | AC | 140.5 % | 149.22 % | 971.0 | B | 1448.94 | 82.57 | |
| AEP/DEI |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line
243221 to 249504 ckt 1 |
AEP_P7-1_#11014-A
CONTINGENCY 'AEP_P7-1_#11014-A' OPEN BRANCH FROM BUS 243217 TO BUS 247712 CKT 1 /*05DEQUIN 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 243217 TO BUS 963840 CKT 1 /*05DEQUIN 345.0 - AG1-237 TAP 345.0 END |
Tower | AC | 123.85 % | 125.42 % | 1374.0 | B | 1723.28 | 30.25 | |
| AEP/DEI |
05EUGENE-08CAYSUB 345.0 kV Ckt 1 line
243221 to 249504 ckt 1 |
AEP_P7-1_#11014-B
CONTINGENCY 'AEP_P7-1_#11014-B' OPEN BRANCH FROM BUS 243217 TO BUS 247712 CKT 1 /*05DEQUIN 345.0 - 05SULLIVAN 345.0 OPEN BRANCH FROM BUS 963840 TO BUS 963740 CKT 1 /*AG1-237 TAP 345.0 - AG1-226 TAP 345.0 END |
Tower | AC | 117.79 % | 119.31 % | 1374.0 | B | 1639.36 | 30.25 | |
| Details for 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963741 | AG1-226 C O1 | 50/50 | 175.72 MW | 175.72 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963742 | AG1-226 E O1 | 50/50 | 62.81 MW | 62.81 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963831 | AG1-236 C | Adder | 2.34 MW | 1.99 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963832 | AG1-236 E | Adder | 15.67 MW | 13.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963841 | AG1-237 C O1 | 50/50 | 13.78 MW | 13.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 963842 | AG1-237 E O1 | 50/50 | 92.23 MW | 92.23 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 964581 | AG1-321 C O1 | Adder | 7.38 MW | 6.28 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 964582 | AG1-321 E O1 | Adder | 4.3 MW | 3.65 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965091 | AG1-374 C | Adder | 13.61 MW | 11.57 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965092 | AG1-374 E | Adder | 9.08 MW | 7.71 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965331 | AG1-398 | Adder | 0.67 MW | 0.57 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965341 | AG1-399 C | Adder | 4.45 MW | 3.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965342 | AG1-399 E | Adder | 20.83 MW | 17.7 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965351 | AG1-400 | Adder | 12.64 MW | 10.74 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965371 | AG1-402 | Adder | 12.64 MW | 10.74 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965391 | AG1-404 | Adder | 8.43 MW | 7.16 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965911 | AG1-460 C | Adder | 0.99 MW | 0.84 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 965912 | AG1-460 E | Adder | 1.48 MW | 1.26 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966531 | AG1-522 C | Adder | 15.09 MW | 12.83 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966532 | AG1-522 E | Adder | 10.06 MW | 8.55 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966541 | AG1-523 C | Adder | 15.09 MW | 12.83 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966542 | AG1-523 E | Adder | 10.06 MW | 8.55 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966551 | AG1-524 C | Adder | 15.09 MW | 12.83 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966552 | AG1-524 E | Adder | 10.06 MW | 8.55 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966561 | AG1-525 C | Adder | 15.09 MW | 12.83 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 966562 | AG1-525 E | Adder | 10.06 MW | 8.55 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 290261 | S-027 E | Adder | 11.98 MW | 10.18 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 290265 | S-028 E | Adder | 11.98 MW | 10.18 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 925771 | AC1-053 C | Adder | 2.34 MW | 1.99 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 925772 | AC1-053 E | Adder | 15.67 MW | 13.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 935141 | AD1-148 | Adder | 3.19 MW | 2.71 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 936771 | AD2-100 C | Adder | 10.29 MW | 8.75 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 936772 | AD2-100 E | Adder | 6.86 MW | 5.83 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 936971 | AD2-131 C | Adder | 0.68 MW | 0.58 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 936972 | AD2-131 E | Adder | 3.41 MW | 2.9 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942111 | AE2-223 C | Adder | 1.44 MW | 1.23 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942112 | AE2-223 E | Adder | 9.65 MW | 8.21 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942481 | AE2-261 C | Adder | 14.79 MW | 12.57 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942482 | AE2-261 E | Adder | 9.86 MW | 8.38 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942601 | AE2-276 | 50/50 | 5.41 MW | 5.41 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 942791 | AE2-297 C O1 | Adder | -4.6 MW | -3.91 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 945391 | AF1-204 C O1 | 50/50 | 33.79 MW | 33.79 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 945392 | AF1-204 E O1 | 50/50 | 101.38 MW | 101.38 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 945871 | AF1-252 O1 | Adder | 4.96 MW | 4.21 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 945881 | AF1-253 | Adder | 3.43 MW | 2.92 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 959341 | AF2-225 C | Adder | 4.66 MW | 3.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 959342 | AF2-225 E | Adder | 6.44 MW | 5.47 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 959611 | AF2-252 C | Adder | 1.51 MW | 1.29 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 959612 | AF2-252 E | Adder | 2.27 MW | 1.93 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 960141 | AF2-305 | Adder | 0.84 MW | 0.71 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 960261 | AF2-317 | Adder | 1.38 MW | 1.17 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 960611 | AF2-352 C | Adder | 1.51 MW | 1.29 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 960612 | AF2-352 E | Adder | 2.27 MW | 1.93 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 276615 | W2-048 GEN | Adder | 4.53 MW | 3.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 276621 | X2-022 GEN | Adder | 16.25 MW | 13.81 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 293777 | CAYUG;1U E | Adder | 6.36 MW | 5.41 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 293778 | CAYUG;2U E | Adder | 6.36 MW | 5.41 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 293798 | W4-005 E | Adder | 23.9 MW | 20.31 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 917502 | Z2-087 E | Adder | 12.87 MW | 10.94 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 924042 | AB2-047 E O1 | Adder | 16.09 MW | 13.67 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 924261 | AB2-070 C O1 | Adder | 2.37 MW | 2.01 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 924262 | AB2-070 E O1 | Adder | 14.35 MW | 12.2 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 930461 | AB1-087 CT1 | 50/50 | 33.16 MW | 33.16 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 930462 | AB1-087 ST1 | 50/50 | 26.37 MW | 26.37 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 930471 | AB1-088 CT1 | 50/50 | 33.16 MW | 33.16 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 930472 | AB1-088 ST1 | 50/50 | 26.37 MW | 26.37 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 933446 | AC2-157 1C | 50/50 | 4.11 MW | 4.11 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 933447 | AC2-157 2C | 50/50 | 4.11 MW | 4.11 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 933448 | AC2-157 1E | 50/50 | 6.71 MW | 6.71 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 933449 | AC2-157 2E | 50/50 | 6.71 MW | 6.71 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 939741 | AE1-205 C O1 | Adder | 6.21 MW | 5.28 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 939742 | AE1-205 E O1 | Adder | 8.58 MW | 7.29 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 941341 | AE2-130 C | Adder | 25.05 MW | 21.29 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 941342 | AE2-130 E | Adder | 16.7 MW | 14.19 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 941731 | AE2-173 O1 | Adder | 3.7 MW | 3.14 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 944221 | AF1-090 C O1 | Adder | 2.8 MW | 2.38 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 944222 | AF1-090 E O1 | Adder | 13.09 MW | 11.13 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 957381 | AF2-032 C | Adder | 1.13 MW | 0.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 957382 | AF2-032 E | Adder | 0.53 MW | 0.45 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 961162 | AF2-407 BAT | Adder | 25.03 MW | 21.27 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 964353 | AG1-297 BAT | Adder | 37.19 MW | 31.61 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 957141 | AF2-008 FTIR | 50/50 | 54.12 MW | 54.12 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 944201 | AF1-088 FTIR | 50/50 | 108.24 MW | 108.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 957142 | AF2-008 NFTI | 50/50 | 54.12 MW | 54.12 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 961172 | AF2-408 BAT | Adder | 5.88 MW | 5.0 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 953741 | J826 C | External Queue | 2.37 MW | 2.37 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 953742 | J826 E | External Queue | 12.85 MW | 12.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 953851 | J845 C | External Queue | 2.98 MW | 2.98 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 953852 | J845 E | External Queue | 16.1 MW | 16.1 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 954681 | J949 C | External Queue | 12.72 MW | 12.72 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 954821 | J955 | External Queue | 73.5 MW | 73.5 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 955402 | J1022 E | External Queue | 22.84 MW | 22.84 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 956151 | J1102 | External Queue | 4.93 MW | 4.93 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 956281 | J1115 C | External Queue | 3.01 MW | 3.01 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 956282 | J1115 E | External Queue | 16.26 MW | 16.26 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 956451 | J1139 | External Queue | 29.98 MW | 29.98 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 990071 | J1204 | External Queue | 14.34 MW | 14.34 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 990271 | J1263 | External Queue | 9.29 MW | 9.29 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 990672 | J1360 E | External Queue | 47.19 MW | 47.19 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 991236 | J1676 C | External Queue | 4.53 MW | 4.53 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 991237 | J1676 E | External Queue | 24.5 MW | 24.5 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 991261 | J1713 C | External Queue | 1.8 MW | 1.8 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | 991262 | J1713 E | External Queue | 9.76 MW | 9.76 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.08 MW | 0.08 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 3.38 MW | 3.38 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.18 MW | 0.18 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.38 MW | 0.38 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 26.14 MW | 26.14 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.81 MW | 4.81 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.59 MW | 0.59 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 2.47 MW | 2.47 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.03 MW | 0.03 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.18 MW | 3.18 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.64 MW | 0.64 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.97 MW | 5.97 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.81 MW | 3.81 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 1.03 MW | 1.03 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.44 MW | 1.44 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P4_#4697_05DEQUIN 345_B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.0 MW | 1.0 MW |
| Details for 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 961761 | AG1-017 C | Adder | 0.15 MW | 0.13 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 961762 | AG1-017 E | Adder | 0.68 MW | 0.58 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 962031 | AG1-047 C | Adder | 3.95 MW | 3.35 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 962032 | AG1-047 E | Adder | 2.63 MW | 2.24 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 963721 | AG1-224 C O1 | 50/50 | 17.29 MW | 17.29 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 963722 | AG1-224 E O1 | 50/50 | 11.52 MW | 11.52 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 963731 | AG1-225 C | Adder | 10.82 MW | 9.2 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 963732 | AG1-225 E | Adder | 7.27 MW | 6.18 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 964351 | AG1-297 C | 50/50 | 25.26 MW | 25.26 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 964352 | AG1-297 E | 50/50 | 37.88 MW | 37.88 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 964611 | AG1-324 C O1 | Adder | 1.93 MW | 1.64 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 964612 | AG1-324 E O1 | Adder | 0.77 MW | 0.65 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 965031 | AG1-367 C | Adder | 5.73 MW | 4.87 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 965032 | AG1-367 E | Adder | 3.82 MW | 3.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 965101 | AG1-375 C | Adder | 4.65 MW | 3.95 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 965102 | AG1-375 E | Adder | 3.1 MW | 2.63 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 965461 | AG1-414 C O1 | Adder | 2.86 MW | 2.43 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 965462 | AG1-414 E O1 | Adder | 1.91 MW | 1.62 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 965651 | AG1-433 C | Adder | 1.32 MW | 1.12 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 965652 | AG1-433 E | Adder | 6.19 MW | 5.26 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247264 | 05LAWG1A | 50/50 | 7.1 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247265 | 05LAWG1B | 50/50 | 7.1 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247266 | 05LAWG1S | 50/50 | 11.34 MW | 11.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247267 | 05LAWG2A | 50/50 | 7.1 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247268 | 05LAWG2B | 50/50 | 7.1 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247269 | 05LAWG2S | 50/50 | 11.34 MW | 11.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247543 | V3-007 C | 50/50 | 0.53 MW | 0.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247929 | S-071 E | Adder | 6.52 MW | 5.54 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247935 | V3-007 E | 50/50 | 20.7 MW | 20.7 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247958 | 05WLD G2 E | Adder | 12.98 MW | 11.03 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247963 | 05HDWTR1G E | 50/50 | 20.7 MW | 20.7 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 247968 | Z2-115 E | Adder | 0.07 MW | 0.06 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 926881 | AC1-175 C | 50/50 | 9.04 MW | 9.04 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 926882 | AC1-175 E | 50/50 | 14.75 MW | 14.75 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 934161 | AD1-043 C O1 | Adder | 3.52 MW | 2.99 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 934162 | AD1-043 E O1 | Adder | 5.74 MW | 4.88 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 934961 | AD1-128 C | Adder | 4.79 MW | 4.07 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 934962 | AD1-128 E | Adder | 7.82 MW | 6.65 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 936561 | AD2-071 C | Adder | 4.76 MW | 4.04 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 936562 | AD2-071 E | Adder | 2.34 MW | 1.99 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 942081 | AE2-220 C | 50/50 | 6.25 MW | 6.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 942082 | AE2-220 E | 50/50 | 8.62 MW | 8.62 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 942221 | AE2-234 C O1 | Adder | 1.37 MW | 1.17 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 942222 | AE2-234 E O1 | Adder | 0.62 MW | 0.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 942791 | AE2-297 C O1 | 50/50 | 10.21 MW | 10.21 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 942792 | AE2-297 E O1 | 50/50 | 6.81 MW | 6.81 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 944031 | AF1-071 C | Adder | 0.54 MW | 0.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 944032 | AF1-071 E | Adder | 0.88 MW | 0.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 944531 | AF1-118 C O1 | Adder | 17.1 MW | 14.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 944532 | AF1-118 E O1 | Adder | 5.16 MW | 4.38 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 944541 | AF1-119 C O1 | Adder | 10.52 MW | 8.94 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 944542 | AF1-119 E O1 | Adder | 4.51 MW | 3.83 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 944831 | AF1-148 C O1 | Adder | 6.3 MW | 5.35 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 944832 | AF1-148 E O1 | Adder | 4.2 MW | 3.57 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 945371 | AF1-202 C O1 | Adder | 2.77 MW | 2.35 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 945372 | AF1-202 E O1 | Adder | 13.52 MW | 11.49 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 945561 | AF1-221 C O1 | 50/50 | 14.8 MW | 14.8 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 945562 | AF1-221 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 945581 | AF1-223 C O1 | Adder | 7.33 MW | 6.23 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 945582 | AF1-223 E O1 | Adder | 4.89 MW | 4.15 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 958711 | AF2-162 C | Adder | 2.25 MW | 1.92 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 958712 | AF2-162 E | Adder | 1.13 MW | 0.96 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 958821 | AF2-173 C | Adder | 8.03 MW | 6.82 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 958822 | AF2-173 E | Adder | 11.08 MW | 9.42 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 958861 | AF2-177 C O1 | Adder | 2.01 MW | 1.71 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 958862 | AF2-177 E O1 | Adder | 13.48 MW | 11.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 959131 | AF2-204 C | Adder | 4.26 MW | 3.62 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 959132 | AF2-204 E | Adder | 2.25 MW | 1.91 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 960441 | AF2-335 C | Adder | 5.01 MW | 4.26 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 960442 | AF2-335 E | Adder | 3.34 MW | 2.84 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 960791 | AF2-370 | Adder | 1.67 MW | 1.42 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 960971 | AF2-388 C | Adder | 2.64 MW | 2.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 960972 | AF2-388 E | Adder | 12.38 MW | 10.52 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 961161 | AF2-407 | Adder | 24.92 MW | 21.18 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 961171 | AF2-408 | Adder | 6.74 MW | 5.73 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 243795 | 05HDWTR1G C | 50/50 | 0.53 MW | 0.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 251947 | 08EBND2 | 50/50 | 12.74 MW | 12.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 932681 | AC2-090 C | 50/50 | 4.52 MW | 4.52 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 932682 | AC2-090 E | 50/50 | 7.38 MW | 7.38 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 932841 | AC2-111 C O1 | Adder | 2.39 MW | 2.03 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 932842 | AC2-111 E O1 | Adder | 3.9 MW | 3.31 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 933596 | AC2-176 E | Adder | 7.44 MW | 6.33 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 939761 | AE1-207 C | Adder | 4.63 MW | 3.94 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 939762 | AE1-207 E | Adder | 6.4 MW | 5.44 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 939771 | AE1-208 C | Adder | 4.14 MW | 3.52 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 939772 | AE1-208 E | Adder | 5.64 MW | 4.8 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 939781 | AE1-209 C O1 | Adder | 1.24 MW | 1.06 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 939782 | AE1-209 E O1 | Adder | 8.31 MW | 7.07 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 939791 | AE1-210 C O1 | Adder | 1.24 MW | 1.06 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 939792 | AE1-210 E O1 | Adder | 8.31 MW | 7.07 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 940981 | AE2-089 C O1 | Adder | 5.36 MW | 4.55 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 940982 | AE2-089 E O1 | Adder | 3.57 MW | 3.04 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 941691 | AE2-169 | Adder | 2.48 MW | 2.11 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 941721 | AE2-172 | Adder | 2.76 MW | 2.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 942071 | AE2-219 C | Adder | 2.94 MW | 2.5 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 942072 | AE2-219 E | Adder | 4.05 MW | 3.45 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 946031 | AF1-268 C O1 | Adder | 4.73 MW | 4.02 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 946032 | AF1-268 E O1 | Adder | 2.14 MW | 1.82 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 957741 | AF2-068 C O1 | Adder | 5.92 MW | 5.03 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 957742 | AF2-068 E O1 | Adder | 3.95 MW | 3.35 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | 250163 | Y3-099 BAT | Adder | 0.14 MW | 0.12 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.37 MW | 0.37 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.12 MW | 0.12 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 30.28 MW | 30.28 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 19.69 MW | 19.69 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.9 MW | 0.9 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.24 MW | 0.24 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.2 MW | 2.2 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.74 MW | 0.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.88 MW | 3.88 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.46 MW | 0.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.74 MW | 5.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.35 MW | 0.35 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.34 MW | 1.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1403_MIAMIFORT | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.84 MW | 0.84 MW |
| Details for 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 961761 | AG1-017 C | Adder | 0.15 MW | 0.13 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 961762 | AG1-017 E | Adder | 0.68 MW | 0.58 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 962031 | AG1-047 C | Adder | 3.95 MW | 3.36 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 962032 | AG1-047 E | Adder | 2.63 MW | 2.24 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963721 | AG1-224 C O1 | 50/50 | 17.29 MW | 17.29 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963722 | AG1-224 E O1 | 50/50 | 11.53 MW | 11.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963731 | AG1-225 C | Adder | 10.83 MW | 9.21 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963732 | AG1-225 E | Adder | 7.27 MW | 6.18 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 964351 | AG1-297 C | 50/50 | 25.26 MW | 25.26 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 964352 | AG1-297 E | 50/50 | 37.89 MW | 37.89 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 964611 | AG1-324 C O1 | Adder | 1.93 MW | 1.64 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 964612 | AG1-324 E O1 | Adder | 0.77 MW | 0.65 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965031 | AG1-367 C | Adder | 5.74 MW | 4.88 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965032 | AG1-367 E | Adder | 3.82 MW | 3.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965101 | AG1-375 C | Adder | 4.65 MW | 3.95 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965102 | AG1-375 E | Adder | 3.1 MW | 2.63 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965461 | AG1-414 C O1 | Adder | 2.86 MW | 2.44 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965462 | AG1-414 E O1 | Adder | 1.91 MW | 1.62 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965651 | AG1-433 C | Adder | 1.32 MW | 1.12 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965652 | AG1-433 E | Adder | 6.19 MW | 5.26 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247264 | 05LAWG1A | 50/50 | 7.1 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247265 | 05LAWG1B | 50/50 | 7.1 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247266 | 05LAWG1S | 50/50 | 11.34 MW | 11.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247267 | 05LAWG2A | 50/50 | 7.1 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247268 | 05LAWG2B | 50/50 | 7.1 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247269 | 05LAWG2S | 50/50 | 11.34 MW | 11.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247543 | V3-007 C | 50/50 | 0.53 MW | 0.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247929 | S-071 E | Adder | 6.53 MW | 5.55 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247935 | V3-007 E | 50/50 | 20.7 MW | 20.7 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247958 | 05WLD G2 E | Adder | 12.98 MW | 11.03 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247963 | 05HDWTR1G E | 50/50 | 20.7 MW | 20.7 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247968 | Z2-115 E | Adder | 0.07 MW | 0.06 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 926881 | AC1-175 C | 50/50 | 9.04 MW | 9.04 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 926882 | AC1-175 E | 50/50 | 14.76 MW | 14.76 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 934161 | AD1-043 C O1 | Adder | 3.52 MW | 2.99 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 934162 | AD1-043 E O1 | Adder | 5.74 MW | 4.88 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 934961 | AD1-128 C | Adder | 4.8 MW | 4.08 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 934962 | AD1-128 E | Adder | 7.82 MW | 6.65 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 936561 | AD2-071 C | Adder | 4.76 MW | 4.04 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 936562 | AD2-071 E | Adder | 2.34 MW | 1.99 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942081 | AE2-220 C | 50/50 | 6.25 MW | 6.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942082 | AE2-220 E | 50/50 | 8.63 MW | 8.63 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942221 | AE2-234 C O1 | Adder | 1.37 MW | 1.17 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942222 | AE2-234 E O1 | Adder | 0.62 MW | 0.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942791 | AE2-297 C O1 | 50/50 | 10.21 MW | 10.21 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942792 | AE2-297 E O1 | 50/50 | 6.81 MW | 6.81 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944031 | AF1-071 C | Adder | 0.54 MW | 0.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944032 | AF1-071 E | Adder | 0.88 MW | 0.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944531 | AF1-118 C O1 | Adder | 17.11 MW | 14.54 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944532 | AF1-118 E O1 | Adder | 5.16 MW | 4.38 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944541 | AF1-119 C O1 | Adder | 10.52 MW | 8.94 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944542 | AF1-119 E O1 | Adder | 4.51 MW | 3.83 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944831 | AF1-148 C O1 | Adder | 6.3 MW | 5.35 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944832 | AF1-148 E O1 | Adder | 4.2 MW | 3.57 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945371 | AF1-202 C O1 | Adder | 2.77 MW | 2.35 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945372 | AF1-202 E O1 | Adder | 13.52 MW | 11.49 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945561 | AF1-221 C O1 | 50/50 | 14.8 MW | 14.8 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945562 | AF1-221 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945581 | AF1-223 C O1 | Adder | 7.33 MW | 6.23 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945582 | AF1-223 E O1 | Adder | 4.89 MW | 4.16 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958711 | AF2-162 C | Adder | 2.25 MW | 1.92 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958712 | AF2-162 E | Adder | 1.13 MW | 0.96 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958821 | AF2-173 C | Adder | 8.03 MW | 6.83 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958822 | AF2-173 E | Adder | 11.09 MW | 9.42 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958861 | AF2-177 C O1 | Adder | 2.02 MW | 1.71 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958862 | AF2-177 E O1 | Adder | 13.48 MW | 11.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 959131 | AF2-204 C | Adder | 4.26 MW | 3.62 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 959132 | AF2-204 E | Adder | 2.25 MW | 1.91 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960441 | AF2-335 C | Adder | 5.01 MW | 4.26 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960442 | AF2-335 E | Adder | 3.34 MW | 2.84 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960791 | AF2-370 | Adder | 1.67 MW | 1.42 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960971 | AF2-388 C | Adder | 2.65 MW | 2.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960972 | AF2-388 E | Adder | 12.38 MW | 10.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 961161 | AF2-407 | Adder | 24.93 MW | 21.19 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 961171 | AF2-408 | Adder | 6.74 MW | 5.73 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 243795 | 05HDWTR1G C | 50/50 | 0.53 MW | 0.53 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 251947 | 08EBND2 | 50/50 | 12.75 MW | 12.75 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 932681 | AC2-090 C | 50/50 | 4.52 MW | 4.52 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 932682 | AC2-090 E | 50/50 | 7.38 MW | 7.38 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 932841 | AC2-111 C O1 | Adder | 2.39 MW | 2.03 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 932842 | AC2-111 E O1 | Adder | 3.9 MW | 3.31 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 933596 | AC2-176 E | Adder | 7.44 MW | 6.33 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939761 | AE1-207 C | Adder | 4.63 MW | 3.94 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939762 | AE1-207 E | Adder | 6.4 MW | 5.44 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939771 | AE1-208 C | Adder | 4.14 MW | 3.52 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939772 | AE1-208 E | Adder | 5.65 MW | 4.8 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939781 | AE1-209 C O1 | Adder | 1.24 MW | 1.06 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939782 | AE1-209 E O1 | Adder | 8.32 MW | 7.07 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939791 | AE1-210 C O1 | Adder | 1.24 MW | 1.06 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939792 | AE1-210 E O1 | Adder | 8.32 MW | 7.07 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 940981 | AE2-089 C O1 | Adder | 5.36 MW | 4.55 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 940982 | AE2-089 E O1 | Adder | 3.57 MW | 3.04 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 941691 | AE2-169 | Adder | 2.48 MW | 2.11 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 941721 | AE2-172 | Adder | 2.76 MW | 2.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942071 | AE2-219 C | Adder | 2.94 MW | 2.5 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942072 | AE2-219 E | Adder | 4.06 MW | 3.45 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 946031 | AF1-268 C O1 | Adder | 4.73 MW | 4.02 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 946032 | AF1-268 E O1 | Adder | 2.15 MW | 1.82 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 957741 | AF2-068 C O1 | Adder | 5.92 MW | 5.04 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 957742 | AF2-068 E O1 | Adder | 3.95 MW | 3.36 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | 250163 | Y3-099 BAT | Adder | 0.14 MW | 0.12 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.37 MW | 0.37 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.12 MW | 0.12 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.38 MW | 0.38 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 30.31 MW | 30.31 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 19.71 MW | 19.71 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.89 MW | 0.89 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.24 MW | 0.24 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.21 MW | 2.21 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.74 MW | 0.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.88 MW | 3.88 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.46 MW | 0.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.72 MW | 5.72 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.35 MW | 0.35 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.34 MW | 1.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.84 MW | 0.84 MW |
| Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 961761 | AG1-017 C | Adder | 0.34 MW | 0.29 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 961762 | AG1-017 E | Adder | 1.56 MW | 1.32 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 962031 | AG1-047 C | Adder | 9.01 MW | 7.66 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 962032 | AG1-047 E | Adder | 6.0 MW | 5.1 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 963721 | AG1-224 C O1 | 50/50 | 42.9 MW | 42.9 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 963722 | AG1-224 E O1 | 50/50 | 28.6 MW | 28.6 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 963731 | AG1-225 C | Adder | 24.59 MW | 20.9 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 963732 | AG1-225 E | Adder | 16.51 MW | 14.03 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 964351 | AG1-297 C | 50/50 | 62.33 MW | 62.33 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 964352 | AG1-297 E | 50/50 | 93.49 MW | 93.49 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 964611 | AG1-324 C O1 | Adder | 4.46 MW | 3.79 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 964612 | AG1-324 E O1 | Adder | 1.77 MW | 1.51 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 965031 | AG1-367 C | 50/50 | 14.01 MW | 14.01 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 965032 | AG1-367 E | 50/50 | 9.34 MW | 9.34 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 965101 | AG1-375 C | 50/50 | 11.26 MW | 11.26 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 965102 | AG1-375 E | 50/50 | 7.51 MW | 7.51 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 965461 | AG1-414 C O1 | Adder | 6.71 MW | 5.7 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 965462 | AG1-414 E O1 | Adder | 4.47 MW | 3.8 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 965651 | AG1-433 C | 50/50 | 3.2 MW | 3.2 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 965652 | AG1-433 E | 50/50 | 14.98 MW | 14.98 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 246991 | 05WLD G1 C | 50/50 | 0.4 MW | 0.4 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247255 | 05WLD G2 C | 50/50 | 0.39 MW | 0.39 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247264 | 05LAWG1A | 50/50 | 18.25 MW | 18.25 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247265 | 05LAWG1B | 50/50 | 18.25 MW | 18.25 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247266 | 05LAWG1S | 50/50 | 29.15 MW | 29.15 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247267 | 05LAWG2A | 50/50 | 18.25 MW | 18.25 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247268 | 05LAWG2B | 50/50 | 18.25 MW | 18.25 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247269 | 05LAWG2S | 50/50 | 29.15 MW | 29.15 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247285 | 05AND G1 | 50/50 | 0.97 MW | 0.97 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247286 | 05AND G2 | 50/50 | 0.97 MW | 0.97 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247287 | 05AND G3 | 50/50 | 2.03 MW | 2.03 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247543 | V3-007 C | 50/50 | 1.31 MW | 1.31 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247929 | S-071 E | Adder | 14.77 MW | 12.55 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247935 | V3-007 E | 50/50 | 51.44 MW | 51.44 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247958 | 05WLD G2 E | 50/50 | 30.73 MW | 30.73 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247963 | 05HDWTR1G E | 50/50 | 51.44 MW | 51.44 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 247968 | Z2-115 E | Adder | 0.17 MW | 0.14 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 926881 | AC1-175 C | 50/50 | 22.47 MW | 22.47 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 926882 | AC1-175 E | 50/50 | 36.66 MW | 36.66 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 934161 | AD1-043 C O1 | 50/50 | 8.35 MW | 8.35 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 934162 | AD1-043 E O1 | 50/50 | 13.63 MW | 13.63 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 934961 | AD1-128 C | 50/50 | 11.2 MW | 11.2 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 934962 | AD1-128 E | 50/50 | 18.28 MW | 18.28 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 935031 | AD1-136 C | Adder | -0.67 MW | -0.57 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 936561 | AD2-071 C | 50/50 | 11.22 MW | 11.22 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 936562 | AD2-071 E | 50/50 | 5.53 MW | 5.53 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 942081 | AE2-220 C | 50/50 | 15.52 MW | 15.52 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 942082 | AE2-220 E | 50/50 | 21.43 MW | 21.43 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 942221 | AE2-234 C O1 | Adder | 3.18 MW | 2.71 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 942222 | AE2-234 E O1 | Adder | 1.44 MW | 1.22 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 942791 | AE2-297 C O1 | 50/50 | 24.96 MW | 24.96 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 942792 | AE2-297 E O1 | 50/50 | 16.64 MW | 16.64 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 944031 | AF1-071 C | 50/50 | 1.16 MW | 1.16 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 944032 | AF1-071 E | 50/50 | 1.9 MW | 1.9 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 944531 | AF1-118 C O1 | Adder | 41.02 MW | 34.87 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 944532 | AF1-118 E O1 | Adder | 12.37 MW | 10.52 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 944541 | AF1-119 C O1 | 50/50 | 25.45 MW | 25.45 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 944542 | AF1-119 E O1 | 50/50 | 10.91 MW | 10.91 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 944831 | AF1-148 C O1 | Adder | 15.14 MW | 12.87 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 944832 | AF1-148 E O1 | Adder | 10.09 MW | 8.58 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 945371 | AF1-202 C O1 | 50/50 | 6.72 MW | 6.72 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 945372 | AF1-202 E O1 | 50/50 | 32.83 MW | 32.83 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 945561 | AF1-221 C O1 | 50/50 | 34.43 MW | 34.43 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 945562 | AF1-221 E O1 | 50/50 | 10.35 MW | 10.35 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 945581 | AF1-223 C O1 | 50/50 | 17.8 MW | 17.8 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 945582 | AF1-223 E O1 | 50/50 | 11.87 MW | 11.87 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 945841 | AF1-249 C | Adder | -2.05 MW | -1.75 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 958711 | AF2-162 C | 50/50 | 5.45 MW | 5.45 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 958712 | AF2-162 E | 50/50 | 2.73 MW | 2.73 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 958821 | AF2-173 C | 50/50 | 19.62 MW | 19.62 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 958822 | AF2-173 E | 50/50 | 27.09 MW | 27.09 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 958861 | AF2-177 C O1 | 50/50 | 4.88 MW | 4.88 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 958862 | AF2-177 E O1 | 50/50 | 32.66 MW | 32.66 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 959131 | AF2-204 C | Adder | 10.04 MW | 8.53 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 959132 | AF2-204 E | Adder | 5.3 MW | 4.5 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 960441 | AF2-335 C | 50/50 | 12.0 MW | 12.0 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 960442 | AF2-335 E | 50/50 | 8.0 MW | 8.0 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 960791 | AF2-370 | 50/50 | 4.0 MW | 4.0 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 960971 | AF2-388 C | 50/50 | 6.4 MW | 6.4 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 960972 | AF2-388 E | 50/50 | 29.96 MW | 29.96 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 961161 | AF2-407 | 50/50 | 59.29 MW | 59.29 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 961171 | AF2-408 | 50/50 | 15.99 MW | 15.99 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 243795 | 05HDWTR1G C | 50/50 | 1.31 MW | 1.31 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 913222 | Y1-054 E | Adder | -3.17 MW | -2.7 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 932661 | AC2-088 C O1 | Adder | -4.75 MW | -4.04 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 932681 | AC2-090 C | 50/50 | 11.23 MW | 11.23 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 932682 | AC2-090 E | 50/50 | 18.33 MW | 18.33 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 932841 | AC2-111 C O1 | 50/50 | 5.16 MW | 5.16 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 932842 | AC2-111 E O1 | 50/50 | 8.42 MW | 8.42 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 933596 | AC2-176 E | Adder | 16.98 MW | 14.43 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 939761 | AE1-207 C | 50/50 | 10.94 MW | 10.94 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 939762 | AE1-207 E | 50/50 | 15.1 MW | 15.1 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 939771 | AE1-208 C | 50/50 | 9.87 MW | 9.87 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 939772 | AE1-208 E | 50/50 | 13.45 MW | 13.45 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 939781 | AE1-209 C O1 | 50/50 | 3.04 MW | 3.04 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 939782 | AE1-209 E O1 | 50/50 | 20.32 MW | 20.32 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 939791 | AE1-210 C O1 | 50/50 | 3.04 MW | 3.04 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 939792 | AE1-210 E O1 | 50/50 | 20.32 MW | 20.32 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 940981 | AE2-089 C O1 | Adder | 12.19 MW | 10.36 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 940982 | AE2-089 E O1 | Adder | 8.13 MW | 6.91 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 941691 | AE2-169 | 50/50 | 5.92 MW | 5.92 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 941721 | AE2-172 | 50/50 | 6.51 MW | 6.51 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 942071 | AE2-219 C | Adder | 6.61 MW | 5.62 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 942072 | AE2-219 E | Adder | 9.13 MW | 7.76 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 946031 | AF1-268 C O1 | 50/50 | 11.27 MW | 11.27 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 946032 | AF1-268 E O1 | 50/50 | 5.11 MW | 5.11 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 957741 | AF2-068 C O1 | Adder | 13.51 MW | 11.48 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 957742 | AF2-068 E O1 | Adder | 9.01 MW | 7.66 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 251823 | Z1-065 BAT | 50/50 | 1.03 MW | 1.03 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 250163 | Y3-099 BAT | Adder | 0.29 MW | 0.24 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | 943773 | AF1-045 BAT | Adder | 8.0 MW | 6.8 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.42 MW | 0.42 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.12 MW | 0.12 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.14 MW | 64.14 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 40.39 MW | 40.39 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.18 MW | 1.18 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.26 MW | 0.26 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.37 MW | 4.37 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.13 MW | 8.13 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.61 MW | 0.61 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.57 MW | 7.57 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.65 MW | 0.65 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.17 MW | 0.17 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.46 MW | 2.46 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.8 MW | 1.8 MW |
| Details for 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 961761 | AG1-017 C | 50/50 | 0.26 MW | 0.26 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 961762 | AG1-017 E | 50/50 | 1.2 MW | 1.2 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 962031 | AG1-047 C | 50/50 | 6.92 MW | 6.92 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 962032 | AG1-047 E | 50/50 | 4.61 MW | 4.61 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963721 | AG1-224 C O1 | 50/50 | 30.69 MW | 30.69 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963722 | AG1-224 E O1 | 50/50 | 20.46 MW | 20.46 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963731 | AG1-225 C | Adder | 18.2 MW | 15.47 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963732 | AG1-225 E | Adder | 12.22 MW | 10.39 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963791 | AG1-232 C | Adder | 5.87 MW | 4.99 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 963792 | AG1-232 E | Adder | 3.91 MW | 3.32 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 964351 | AG1-297 C | 50/50 | 42.87 MW | 42.87 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 964352 | AG1-297 E | 50/50 | 64.3 MW | 64.3 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 964611 | AG1-324 C O1 | 50/50 | 3.37 MW | 3.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 964612 | AG1-324 E O1 | 50/50 | 1.34 MW | 1.34 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965031 | AG1-367 C | 50/50 | 9.78 MW | 9.78 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965032 | AG1-367 E | 50/50 | 6.52 MW | 6.52 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965101 | AG1-375 C | 50/50 | 7.77 MW | 7.77 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965102 | AG1-375 E | 50/50 | 5.18 MW | 5.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965461 | AG1-414 C O1 | Adder | 4.36 MW | 3.71 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965462 | AG1-414 E O1 | Adder | 2.91 MW | 2.47 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965651 | AG1-433 C | 50/50 | 2.2 MW | 2.2 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 965652 | AG1-433 E | 50/50 | 10.31 MW | 10.31 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 246991 | 05WLD G1 C | 50/50 | 0.27 MW | 0.27 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247255 | 05WLD G2 C | 50/50 | 0.26 MW | 0.26 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247264 | 05LAWG1A | 50/50 | 13.03 MW | 13.03 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247265 | 05LAWG1B | 50/50 | 13.03 MW | 13.03 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247266 | 05LAWG1S | 50/50 | 20.8 MW | 20.8 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247267 | 05LAWG2A | 50/50 | 13.03 MW | 13.03 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247268 | 05LAWG2B | 50/50 | 13.03 MW | 13.03 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247269 | 05LAWG2S | 50/50 | 20.8 MW | 20.8 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247288 | 05RICHG1 | 50/50 | 0.79 MW | 0.79 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247289 | 05RICHG2 | 50/50 | 0.79 MW | 0.79 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247536 | 05BLUFF P WF | 50/50 | 0.5 MW | 0.5 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247543 | V3-007 C | 50/50 | 0.92 MW | 0.92 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247621 | Y3-024 | 50/50 | 0.04 MW | 0.04 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247929 | S-071 E | 50/50 | 11.65 MW | 11.65 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247935 | V3-007 E | 50/50 | 36.18 MW | 36.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247958 | 05WLD G2 E | 50/50 | 20.71 MW | 20.71 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247963 | 05HDWTR1G E | 50/50 | 36.18 MW | 36.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 247968 | Z2-115 E | Adder | 0.11 MW | 0.09 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 926881 | AC1-175 C | 50/50 | 15.8 MW | 15.8 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 926882 | AC1-175 E | 50/50 | 25.78 MW | 25.78 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 934161 | AD1-043 C O1 | 50/50 | 5.66 MW | 5.66 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 934162 | AD1-043 E O1 | 50/50 | 9.23 MW | 9.23 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 934961 | AD1-128 C | 50/50 | 8.5 MW | 8.5 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 934962 | AD1-128 E | 50/50 | 13.88 MW | 13.88 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 936561 | AD2-071 C | 50/50 | 7.48 MW | 7.48 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 936562 | AD2-071 E | 50/50 | 3.68 MW | 3.68 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942081 | AE2-220 C | 50/50 | 10.92 MW | 10.92 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942082 | AE2-220 E | 50/50 | 15.07 MW | 15.07 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942221 | AE2-234 C O1 | Adder | 2.25 MW | 1.91 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942222 | AE2-234 E O1 | Adder | 1.02 MW | 0.86 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942791 | AE2-297 C O1 | 50/50 | 17.63 MW | 17.63 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942792 | AE2-297 E O1 | 50/50 | 11.75 MW | 11.75 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944031 | AF1-071 C | 50/50 | 1.07 MW | 1.07 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944032 | AF1-071 E | 50/50 | 1.74 MW | 1.74 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944531 | AF1-118 C O1 | Adder | 27.89 MW | 23.7 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944532 | AF1-118 E O1 | Adder | 8.41 MW | 7.15 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944541 | AF1-119 C O1 | 50/50 | 17.52 MW | 17.52 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944542 | AF1-119 E O1 | 50/50 | 7.51 MW | 7.51 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944831 | AF1-148 C O1 | Adder | 10.32 MW | 8.77 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 944832 | AF1-148 E O1 | Adder | 6.88 MW | 5.85 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945371 | AF1-202 C O1 | 50/50 | 4.65 MW | 4.65 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945372 | AF1-202 E O1 | 50/50 | 22.71 MW | 22.71 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945561 | AF1-221 C O1 | 50/50 | 28.46 MW | 28.46 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945562 | AF1-221 E O1 | 50/50 | 8.55 MW | 8.55 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945581 | AF1-223 C O1 | 50/50 | 12.31 MW | 12.31 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 945582 | AF1-223 E O1 | 50/50 | 8.21 MW | 8.21 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958711 | AF2-162 C | 50/50 | 3.75 MW | 3.75 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958712 | AF2-162 E | 50/50 | 1.88 MW | 1.88 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958821 | AF2-173 C | 50/50 | 13.69 MW | 13.69 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958822 | AF2-173 E | 50/50 | 18.91 MW | 18.91 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958861 | AF2-177 C O1 | 50/50 | 3.37 MW | 3.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 958862 | AF2-177 E O1 | 50/50 | 22.52 MW | 22.52 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 959131 | AF2-204 C | Adder | 6.86 MW | 5.83 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 959132 | AF2-204 E | Adder | 3.62 MW | 3.08 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960441 | AF2-335 C | 50/50 | 8.45 MW | 8.45 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960442 | AF2-335 E | 50/50 | 5.63 MW | 5.63 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960791 | AF2-370 | 50/50 | 2.82 MW | 2.82 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960971 | AF2-388 C | 50/50 | 4.4 MW | 4.4 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 960972 | AF2-388 E | 50/50 | 20.62 MW | 20.62 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 961161 | AF2-407 | 50/50 | 40.06 MW | 40.06 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 961171 | AF2-408 | 50/50 | 10.97 MW | 10.97 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 243415 | 05WWVSTA | 50/50 | 2.28 MW | 2.28 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 243795 | 05HDWTR1G C | 50/50 | 0.92 MW | 0.92 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 251947 | 08EBND2 | 50/50 | 24.56 MW | 24.56 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 932681 | AC2-090 C | 50/50 | 7.9 MW | 7.9 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 932682 | AC2-090 E | 50/50 | 12.89 MW | 12.89 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 932841 | AC2-111 C O1 | 50/50 | 4.75 MW | 4.75 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 932842 | AC2-111 E O1 | 50/50 | 7.75 MW | 7.75 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 933594 | AC2-176 C | 50/50 | 0.33 MW | 0.33 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 933596 | AC2-176 E | 50/50 | 13.04 MW | 13.04 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939761 | AE1-207 C | Adder | 7.3 MW | 6.2 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939762 | AE1-207 E | Adder | 10.08 MW | 8.57 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939771 | AE1-208 C | 50/50 | 6.87 MW | 6.87 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939772 | AE1-208 E | 50/50 | 9.37 MW | 9.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939781 | AE1-209 C O1 | 50/50 | 2.12 MW | 2.12 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939782 | AE1-209 E O1 | 50/50 | 14.18 MW | 14.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939791 | AE1-210 C O1 | 50/50 | 2.12 MW | 2.12 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 939792 | AE1-210 E O1 | 50/50 | 14.18 MW | 14.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 940981 | AE2-089 C O1 | Adder | 9.17 MW | 7.8 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 940982 | AE2-089 E O1 | Adder | 6.12 MW | 5.2 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 941691 | AE2-169 | 50/50 | 4.12 MW | 4.12 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 941721 | AE2-172 | Adder | 4.34 MW | 3.69 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942071 | AE2-219 C | 50/50 | 5.32 MW | 5.32 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 942072 | AE2-219 E | 50/50 | 7.35 MW | 7.35 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 946031 | AF1-268 C O1 | 50/50 | 8.1 MW | 8.1 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 946032 | AF1-268 E O1 | 50/50 | 3.68 MW | 3.68 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 957741 | AF2-068 C O1 | 50/50 | 10.37 MW | 10.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 957742 | AF2-068 E O1 | 50/50 | 6.92 MW | 6.92 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 953351 | J805 | External Queue | 15.08 MW | 15.08 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 954351 | J903 | External Queue | 7.83 MW | 7.83 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 955151 | J993 | External Queue | 15.13 MW | 15.13 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | 991186 | J1593 | External Queue | 15.23 MW | 15.23 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.84 MW | 0.84 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 8.78 MW | 8.78 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.36 MW | 0.36 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.37 MW | 0.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 27.02 MW | 27.02 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 14.69 MW | 14.69 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.37 MW | 0.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.06 MW | 1.06 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.62 MW | 0.62 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.72 MW | 0.72 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 2.21 MW | 2.21 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 3.21 MW | 3.21 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.53 MW | 0.53 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.76 MW | 6.76 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.23 MW | 0.23 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 3.21 MW | 3.21 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P2-3_1401_MIAMIFORT | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.78 MW | 0.78 MW |
| Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 961761 | AG1-017 C | Adder | 0.34 MW | 0.29 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 961762 | AG1-017 E | Adder | 1.56 MW | 1.32 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 962031 | AG1-047 C | Adder | 9.01 MW | 7.66 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 962032 | AG1-047 E | Adder | 6.0 MW | 5.1 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 963721 | AG1-224 C O1 | 50/50 | 42.9 MW | 42.9 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 963722 | AG1-224 E O1 | 50/50 | 28.6 MW | 28.6 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 963731 | AG1-225 C | Adder | 24.59 MW | 20.9 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 963732 | AG1-225 E | Adder | 16.51 MW | 14.03 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 964351 | AG1-297 C | 50/50 | 62.33 MW | 62.33 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 964352 | AG1-297 E | 50/50 | 93.49 MW | 93.49 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 964611 | AG1-324 C O1 | Adder | 4.46 MW | 3.79 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 964612 | AG1-324 E O1 | Adder | 1.77 MW | 1.51 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 965031 | AG1-367 C | 50/50 | 14.01 MW | 14.01 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 965032 | AG1-367 E | 50/50 | 9.34 MW | 9.34 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 965101 | AG1-375 C | 50/50 | 11.26 MW | 11.26 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 965102 | AG1-375 E | 50/50 | 7.51 MW | 7.51 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 965461 | AG1-414 C O1 | Adder | 6.71 MW | 5.7 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 965462 | AG1-414 E O1 | Adder | 4.47 MW | 3.8 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 965651 | AG1-433 C | 50/50 | 3.2 MW | 3.2 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 965652 | AG1-433 E | 50/50 | 14.98 MW | 14.98 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 246991 | 05WLD G1 C | 50/50 | 0.4 MW | 0.4 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247255 | 05WLD G2 C | 50/50 | 0.39 MW | 0.39 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247264 | 05LAWG1A | 50/50 | 18.25 MW | 18.25 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247265 | 05LAWG1B | 50/50 | 18.25 MW | 18.25 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247266 | 05LAWG1S | 50/50 | 29.15 MW | 29.15 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247267 | 05LAWG2A | 50/50 | 18.25 MW | 18.25 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247268 | 05LAWG2B | 50/50 | 18.25 MW | 18.25 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247269 | 05LAWG2S | 50/50 | 29.15 MW | 29.15 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247285 | 05AND G1 | 50/50 | 0.97 MW | 0.97 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247286 | 05AND G2 | 50/50 | 0.97 MW | 0.97 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247287 | 05AND G3 | 50/50 | 2.03 MW | 2.03 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247543 | V3-007 C | 50/50 | 1.31 MW | 1.31 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247929 | S-071 E | Adder | 14.77 MW | 12.55 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247935 | V3-007 E | 50/50 | 51.44 MW | 51.44 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247958 | 05WLD G2 E | 50/50 | 30.73 MW | 30.73 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247963 | 05HDWTR1G E | 50/50 | 51.44 MW | 51.44 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 247968 | Z2-115 E | Adder | 0.17 MW | 0.14 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 926881 | AC1-175 C | 50/50 | 22.47 MW | 22.47 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 926882 | AC1-175 E | 50/50 | 36.66 MW | 36.66 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 934161 | AD1-043 C O1 | 50/50 | 8.35 MW | 8.35 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 934162 | AD1-043 E O1 | 50/50 | 13.63 MW | 13.63 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 934961 | AD1-128 C | 50/50 | 11.2 MW | 11.2 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 934962 | AD1-128 E | 50/50 | 18.28 MW | 18.28 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 935031 | AD1-136 C | Adder | -0.67 MW | -0.57 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 936561 | AD2-071 C | 50/50 | 11.22 MW | 11.22 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 936562 | AD2-071 E | 50/50 | 5.53 MW | 5.53 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 942081 | AE2-220 C | 50/50 | 15.52 MW | 15.52 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 942082 | AE2-220 E | 50/50 | 21.43 MW | 21.43 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 942221 | AE2-234 C O1 | Adder | 3.18 MW | 2.71 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 942222 | AE2-234 E O1 | Adder | 1.44 MW | 1.22 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 942791 | AE2-297 C O1 | 50/50 | 24.96 MW | 24.96 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 942792 | AE2-297 E O1 | 50/50 | 16.64 MW | 16.64 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 944031 | AF1-071 C | 50/50 | 1.16 MW | 1.16 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 944032 | AF1-071 E | 50/50 | 1.9 MW | 1.9 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 944531 | AF1-118 C O1 | Adder | 41.02 MW | 34.87 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 944532 | AF1-118 E O1 | Adder | 12.37 MW | 10.52 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 944541 | AF1-119 C O1 | 50/50 | 25.45 MW | 25.45 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 944542 | AF1-119 E O1 | 50/50 | 10.91 MW | 10.91 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 944831 | AF1-148 C O1 | Adder | 15.14 MW | 12.87 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 944832 | AF1-148 E O1 | Adder | 10.09 MW | 8.58 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 945371 | AF1-202 C O1 | 50/50 | 6.72 MW | 6.72 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 945372 | AF1-202 E O1 | 50/50 | 32.83 MW | 32.83 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 945561 | AF1-221 C O1 | 50/50 | 34.43 MW | 34.43 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 945562 | AF1-221 E O1 | 50/50 | 10.35 MW | 10.35 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 945581 | AF1-223 C O1 | 50/50 | 17.8 MW | 17.8 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 945582 | AF1-223 E O1 | 50/50 | 11.87 MW | 11.87 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 945841 | AF1-249 C | Adder | -2.05 MW | -1.75 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 958711 | AF2-162 C | 50/50 | 5.45 MW | 5.45 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 958712 | AF2-162 E | 50/50 | 2.73 MW | 2.73 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 958821 | AF2-173 C | 50/50 | 19.62 MW | 19.62 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 958822 | AF2-173 E | 50/50 | 27.09 MW | 27.09 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 958861 | AF2-177 C O1 | 50/50 | 4.88 MW | 4.88 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 958862 | AF2-177 E O1 | 50/50 | 32.66 MW | 32.66 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 959131 | AF2-204 C | Adder | 10.04 MW | 8.53 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 959132 | AF2-204 E | Adder | 5.3 MW | 4.5 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 960441 | AF2-335 C | 50/50 | 12.0 MW | 12.0 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 960442 | AF2-335 E | 50/50 | 8.0 MW | 8.0 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 960791 | AF2-370 | 50/50 | 4.0 MW | 4.0 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 960971 | AF2-388 C | 50/50 | 6.4 MW | 6.4 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 960972 | AF2-388 E | 50/50 | 29.96 MW | 29.96 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 961161 | AF2-407 | 50/50 | 59.29 MW | 59.29 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 961171 | AF2-408 | 50/50 | 15.99 MW | 15.99 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 243795 | 05HDWTR1G C | 50/50 | 1.31 MW | 1.31 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 913222 | Y1-054 E | Adder | -3.17 MW | -2.7 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 932661 | AC2-088 C O1 | Adder | -4.75 MW | -4.04 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 932681 | AC2-090 C | 50/50 | 11.23 MW | 11.23 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 932682 | AC2-090 E | 50/50 | 18.33 MW | 18.33 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 932841 | AC2-111 C O1 | 50/50 | 5.16 MW | 5.16 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 932842 | AC2-111 E O1 | 50/50 | 8.42 MW | 8.42 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 933596 | AC2-176 E | Adder | 16.98 MW | 14.43 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 939761 | AE1-207 C | 50/50 | 10.94 MW | 10.94 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 939762 | AE1-207 E | 50/50 | 15.1 MW | 15.1 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 939771 | AE1-208 C | 50/50 | 9.87 MW | 9.87 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 939772 | AE1-208 E | 50/50 | 13.45 MW | 13.45 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 939781 | AE1-209 C O1 | 50/50 | 3.04 MW | 3.04 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 939782 | AE1-209 E O1 | 50/50 | 20.32 MW | 20.32 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 939791 | AE1-210 C O1 | 50/50 | 3.04 MW | 3.04 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 939792 | AE1-210 E O1 | 50/50 | 20.32 MW | 20.32 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 940981 | AE2-089 C O1 | Adder | 12.19 MW | 10.36 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 940982 | AE2-089 E O1 | Adder | 8.13 MW | 6.91 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 941691 | AE2-169 | 50/50 | 5.92 MW | 5.92 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 941721 | AE2-172 | 50/50 | 6.51 MW | 6.51 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 942071 | AE2-219 C | Adder | 6.61 MW | 5.62 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 942072 | AE2-219 E | Adder | 9.13 MW | 7.76 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 946031 | AF1-268 C O1 | 50/50 | 11.27 MW | 11.27 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 946032 | AF1-268 E O1 | 50/50 | 5.11 MW | 5.11 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 957741 | AF2-068 C O1 | Adder | 13.51 MW | 11.48 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 957742 | AF2-068 E O1 | Adder | 9.01 MW | 7.66 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 251823 | Z1-065 BAT | 50/50 | 1.03 MW | 1.03 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 250163 | Y3-099 BAT | Adder | 0.29 MW | 0.24 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | 943773 | AF1-045 BAT | Adder | 8.0 MW | 6.8 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.42 MW | 0.42 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.12 MW | 0.12 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.51 MW | 0.51 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 64.14 MW | 64.14 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 40.39 MW | 40.39 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.18 MW | 1.18 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.26 MW | 0.26 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 4.37 MW | 4.37 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.13 MW | 8.13 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.61 MW | 0.61 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.57 MW | 7.57 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.65 MW | 0.65 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.17 MW | 0.17 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.46 MW | 2.46 MW |
| 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.8 MW | 1.8 MW |
| Details for 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 961761 | AG1-017 C | Adder | 0.33 MW | 0.28 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 961762 | AG1-017 E | Adder | 1.5 MW | 1.27 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 962031 | AG1-047 C | Adder | 8.64 MW | 7.35 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 962032 | AG1-047 E | Adder | 5.76 MW | 4.9 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963721 | AG1-224 C O1 | 50/50 | 39.14 MW | 39.14 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963722 | AG1-224 E O1 | 50/50 | 26.09 MW | 26.09 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963731 | AG1-225 C | Adder | 23.12 MW | 19.65 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963732 | AG1-225 E | Adder | 15.52 MW | 13.2 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963791 | AG1-232 C | Adder | 7.54 MW | 6.41 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963792 | AG1-232 E | Adder | 5.03 MW | 4.27 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 964351 | AG1-297 C | 50/50 | 55.58 MW | 55.58 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 964352 | AG1-297 E | 50/50 | 83.37 MW | 83.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 964611 | AG1-324 C O1 | 50/50 | 4.23 MW | 4.23 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 964612 | AG1-324 E O1 | 50/50 | 1.68 MW | 1.68 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965031 | AG1-367 C | 50/50 | 12.62 MW | 12.62 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965032 | AG1-367 E | 50/50 | 8.41 MW | 8.41 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965101 | AG1-375 C | 50/50 | 10.09 MW | 10.09 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965102 | AG1-375 E | 50/50 | 6.72 MW | 6.72 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965461 | AG1-414 C O1 | Adder | 5.82 MW | 4.95 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965462 | AG1-414 E O1 | Adder | 3.88 MW | 3.3 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965651 | AG1-433 C | 50/50 | 2.86 MW | 2.86 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965652 | AG1-433 E | 50/50 | 13.4 MW | 13.4 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 246991 | 05WLD G1 C | 50/50 | 0.35 MW | 0.35 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247255 | 05WLD G2 C | 50/50 | 0.34 MW | 0.34 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247264 | 05LAWG1A | 50/50 | 16.6 MW | 16.6 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247265 | 05LAWG1B | 50/50 | 16.6 MW | 16.6 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247266 | 05LAWG1S | 50/50 | 26.5 MW | 26.5 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247267 | 05LAWG2A | 50/50 | 16.6 MW | 16.6 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247268 | 05LAWG2B | 50/50 | 16.6 MW | 16.6 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247269 | 05LAWG2S | 50/50 | 26.5 MW | 26.5 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247288 | 05RICHG1 | 50/50 | 0.94 MW | 0.94 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247289 | 05RICHG2 | 50/50 | 0.94 MW | 0.94 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247295 | 05KEY G4 | 50/50 | 1.47 MW | 1.47 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247536 | 05BLUFF P WF | 50/50 | 0.61 MW | 0.61 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247543 | V3-007 C | 50/50 | 1.18 MW | 1.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247621 | Y3-024 | 50/50 | 0.06 MW | 0.06 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247929 | S-071 E | 50/50 | 14.4 MW | 14.4 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247935 | V3-007 E | 50/50 | 46.49 MW | 46.49 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247958 | 05WLD G2 E | 50/50 | 27.18 MW | 27.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247963 | 05HDWTR1G E | 50/50 | 46.49 MW | 46.49 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247968 | Z2-115 E | Adder | 0.15 MW | 0.12 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 926881 | AC1-175 C | 50/50 | 20.3 MW | 20.3 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 926882 | AC1-175 E | 50/50 | 33.13 MW | 33.13 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 934161 | AD1-043 C O1 | 50/50 | 7.41 MW | 7.41 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 934162 | AD1-043 E O1 | 50/50 | 12.09 MW | 12.09 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 934961 | AD1-128 C | 50/50 | 10.63 MW | 10.63 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 934962 | AD1-128 E | 50/50 | 17.34 MW | 17.34 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 936561 | AD2-071 C | 50/50 | 9.86 MW | 9.86 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 936562 | AD2-071 E | 50/50 | 4.86 MW | 4.86 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942081 | AE2-220 C | 50/50 | 14.03 MW | 14.03 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942082 | AE2-220 E | 50/50 | 19.37 MW | 19.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942221 | AE2-234 C O1 | Adder | 2.91 MW | 2.47 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942222 | AE2-234 E O1 | Adder | 1.31 MW | 1.12 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942791 | AE2-297 C O1 | 50/50 | 22.63 MW | 22.63 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942792 | AE2-297 E O1 | 50/50 | 15.09 MW | 15.09 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944031 | AF1-071 C | 50/50 | 1.25 MW | 1.25 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944032 | AF1-071 E | 50/50 | 2.03 MW | 2.03 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944531 | AF1-118 C O1 | Adder | 36.49 MW | 31.02 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944532 | AF1-118 E O1 | Adder | 11.0 MW | 9.35 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944541 | AF1-119 C O1 | 50/50 | 22.77 MW | 22.77 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944542 | AF1-119 E O1 | 50/50 | 9.76 MW | 9.76 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944831 | AF1-148 C O1 | Adder | 13.48 MW | 11.46 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944832 | AF1-148 E O1 | Adder | 8.99 MW | 7.64 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945371 | AF1-202 C O1 | 50/50 | 6.03 MW | 6.03 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945372 | AF1-202 E O1 | 50/50 | 29.45 MW | 29.45 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945561 | AF1-221 C O1 | 50/50 | 34.37 MW | 34.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945562 | AF1-221 E O1 | 50/50 | 10.33 MW | 10.33 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945581 | AF1-223 C O1 | 50/50 | 15.96 MW | 15.96 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945582 | AF1-223 E O1 | 50/50 | 10.64 MW | 10.64 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958711 | AF2-162 C | 50/50 | 4.88 MW | 4.88 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958712 | AF2-162 E | 50/50 | 2.44 MW | 2.44 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958821 | AF2-173 C | 50/50 | 17.67 MW | 17.67 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958822 | AF2-173 E | 50/50 | 24.4 MW | 24.4 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958861 | AF2-177 C O1 | 50/50 | 4.37 MW | 4.37 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958862 | AF2-177 E O1 | 50/50 | 29.25 MW | 29.25 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 959131 | AF2-204 C | Adder | 8.97 MW | 7.62 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 959132 | AF2-204 E | Adder | 4.73 MW | 4.02 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960441 | AF2-335 C | 50/50 | 10.88 MW | 10.88 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960442 | AF2-335 E | 50/50 | 7.25 MW | 7.25 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960791 | AF2-370 | 50/50 | 3.63 MW | 3.63 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960971 | AF2-388 C | 50/50 | 5.72 MW | 5.72 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960972 | AF2-388 E | 50/50 | 26.8 MW | 26.8 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 961161 | AF2-407 | 50/50 | 52.48 MW | 52.48 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 961171 | AF2-408 | 50/50 | 14.28 MW | 14.28 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 243415 | 05WWVSTA | 50/50 | 2.73 MW | 2.73 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 243795 | 05HDWTR1G C | 50/50 | 1.18 MW | 1.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932681 | AC2-090 C | 50/50 | 10.15 MW | 10.15 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932682 | AC2-090 E | 50/50 | 16.57 MW | 16.57 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932841 | AC2-111 C O1 | 50/50 | 5.54 MW | 5.54 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932842 | AC2-111 E O1 | 50/50 | 9.03 MW | 9.03 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 933596 | AC2-176 E | Adder | 16.29 MW | 13.85 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939761 | AE1-207 C | Adder | 9.62 MW | 8.18 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939762 | AE1-207 E | Adder | 13.28 MW | 11.29 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939771 | AE1-208 C | 50/50 | 8.89 MW | 8.89 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939772 | AE1-208 E | 50/50 | 12.13 MW | 12.13 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939781 | AE1-209 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939782 | AE1-209 E O1 | 50/50 | 18.3 MW | 18.3 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939791 | AE1-210 C O1 | 50/50 | 2.73 MW | 2.73 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939792 | AE1-210 E O1 | 50/50 | 18.3 MW | 18.3 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 940981 | AE2-089 C O1 | Adder | 11.57 MW | 9.83 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 940982 | AE2-089 E O1 | Adder | 7.71 MW | 6.55 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 941691 | AE2-169 | 50/50 | 5.34 MW | 5.34 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 941721 | AE2-172 | Adder | 5.73 MW | 4.87 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942071 | AE2-219 C | 50/50 | 6.53 MW | 6.53 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942072 | AE2-219 E | 50/50 | 9.01 MW | 9.01 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 946031 | AF1-268 C O1 | 50/50 | 10.35 MW | 10.35 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 946032 | AF1-268 E O1 | 50/50 | 4.7 MW | 4.7 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 957741 | AF2-068 C O1 | Adder | 12.97 MW | 11.02 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 957742 | AF2-068 E O1 | Adder | 8.64 MW | 7.35 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 953351 | J805 | External Queue | 18.86 MW | 18.86 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 954351 | J903 | External Queue | 9.63 MW | 9.63 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 955151 | J993 | External Queue | 19.16 MW | 19.16 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 991186 | J1593 | External Queue | 19.0 MW | 19.0 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.76 MW | 0.76 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 6.51 MW | 6.51 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.2 MW | 0.2 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.01 MW | 0.01 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 45.26 MW | 45.26 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.55 MW | 26.55 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.2 MW | 0.2 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 1.17 MW | 1.17 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.55 MW | 0.55 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 2.24 MW | 2.24 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 1.2 MW | 1.2 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.54 MW | 5.54 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.59 MW | 0.59 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 7.51 MW | 7.51 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.42 MW | 0.42 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 2.46 MW | 2.46 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.93 MW | 0.93 MW |
| 05TANNER-06DEARB1 345.0 kV Ckt Z1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.28 MW | 1.28 MW |
| Details for 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 961761 | AG1-017 C | Adder | 0.19 MW | 0.16 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 961762 | AG1-017 E | Adder | 0.87 MW | 0.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 962031 | AG1-047 C | Adder | 5.01 MW | 4.26 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 962032 | AG1-047 E | Adder | 3.34 MW | 2.84 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963721 | AG1-224 C O1 | 50/50 | 22.46 MW | 22.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963722 | AG1-224 E O1 | 50/50 | 14.97 MW | 14.97 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963731 | AG1-225 C | Adder | 13.84 MW | 11.77 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 963732 | AG1-225 E | Adder | 9.3 MW | 7.9 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 964351 | AG1-297 C | 50/50 | 33.03 MW | 33.03 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 964352 | AG1-297 E | 50/50 | 49.54 MW | 49.54 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 964611 | AG1-324 C O1 | Adder | 2.46 MW | 2.09 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 964612 | AG1-324 E O1 | Adder | 0.98 MW | 0.83 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965031 | AG1-367 C | 50/50 | 7.47 MW | 7.47 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965032 | AG1-367 E | 50/50 | 4.98 MW | 4.98 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965101 | AG1-375 C | 50/50 | 6.07 MW | 6.07 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965102 | AG1-375 E | 50/50 | 4.04 MW | 4.04 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965461 | AG1-414 C O1 | Adder | 3.75 MW | 3.19 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965462 | AG1-414 E O1 | Adder | 2.5 MW | 2.13 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965651 | AG1-433 C | Adder | 1.73 MW | 1.47 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 965652 | AG1-433 E | Adder | 8.08 MW | 6.87 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247264 | 05LAWG1A | 50/50 | 9.29 MW | 9.29 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247265 | 05LAWG1B | 50/50 | 9.29 MW | 9.29 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247266 | 05LAWG1S | 50/50 | 14.83 MW | 14.83 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247267 | 05LAWG2A | 50/50 | 9.29 MW | 9.29 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247268 | 05LAWG2B | 50/50 | 9.29 MW | 9.29 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247269 | 05LAWG2S | 50/50 | 14.83 MW | 14.83 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247543 | V3-007 C | 50/50 | 0.69 MW | 0.69 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247929 | S-071 E | Adder | 8.21 MW | 6.98 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247935 | V3-007 E | 50/50 | 27.01 MW | 27.01 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247958 | 05WLD G2 E | Adder | 16.93 MW | 14.39 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247963 | 05HDWTR1G E | 50/50 | 27.01 MW | 27.01 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 247968 | Z2-115 E | Adder | 0.1 MW | 0.08 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 926881 | AC1-175 C | 50/50 | 11.8 MW | 11.8 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 926882 | AC1-175 E | 50/50 | 19.25 MW | 19.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 934161 | AD1-043 C O1 | 50/50 | 4.59 MW | 4.59 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 934162 | AD1-043 E O1 | 50/50 | 7.49 MW | 7.49 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 934961 | AD1-128 C | 50/50 | 6.09 MW | 6.09 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 934962 | AD1-128 E | 50/50 | 9.94 MW | 9.94 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 935031 | AD1-136 C | Adder | -0.4 MW | -0.34 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 936561 | AD2-071 C | Adder | 6.21 MW | 5.28 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 936562 | AD2-071 E | Adder | 3.06 MW | 2.6 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942081 | AE2-220 C | 50/50 | 8.15 MW | 8.15 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942082 | AE2-220 E | 50/50 | 11.25 MW | 11.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942221 | AE2-234 C O1 | Adder | 1.78 MW | 1.51 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942222 | AE2-234 E O1 | Adder | 0.8 MW | 0.68 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942791 | AE2-297 C O1 | 50/50 | 13.27 MW | 13.27 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942792 | AE2-297 E O1 | 50/50 | 8.85 MW | 8.85 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944031 | AF1-071 C | Adder | 0.65 MW | 0.55 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944032 | AF1-071 E | Adder | 1.05 MW | 0.9 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944531 | AF1-118 C O1 | Adder | 22.37 MW | 19.01 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944532 | AF1-118 E O1 | Adder | 6.75 MW | 5.73 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944541 | AF1-119 C O1 | Adder | 13.73 MW | 11.67 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944542 | AF1-119 E O1 | Adder | 5.89 MW | 5.0 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944831 | AF1-148 C O1 | Adder | 8.23 MW | 7.0 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 944832 | AF1-148 E O1 | Adder | 5.49 MW | 4.67 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945371 | AF1-202 C O1 | 50/50 | 3.61 MW | 3.61 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945372 | AF1-202 E O1 | 50/50 | 17.64 MW | 17.64 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945561 | AF1-221 C O1 | 50/50 | 18.43 MW | 18.43 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945562 | AF1-221 E O1 | 50/50 | 5.54 MW | 5.54 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945581 | AF1-223 C O1 | 50/50 | 9.56 MW | 9.56 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 945582 | AF1-223 E O1 | 50/50 | 6.38 MW | 6.38 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958711 | AF2-162 C | Adder | 2.94 MW | 2.5 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958712 | AF2-162 E | Adder | 1.47 MW | 1.25 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958821 | AF2-173 C | 50/50 | 10.46 MW | 10.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958822 | AF2-173 E | 50/50 | 14.45 MW | 14.45 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958861 | AF2-177 C O1 | 50/50 | 2.63 MW | 2.63 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 958862 | AF2-177 E O1 | 50/50 | 17.6 MW | 17.6 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 959131 | AF2-204 C | Adder | 5.55 MW | 4.72 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 959132 | AF2-204 E | Adder | 2.93 MW | 2.49 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960441 | AF2-335 C | 50/50 | 6.5 MW | 6.5 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960442 | AF2-335 E | 50/50 | 4.33 MW | 4.33 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960791 | AF2-370 | 50/50 | 2.17 MW | 2.17 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960971 | AF2-388 C | Adder | 3.45 MW | 2.94 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 960972 | AF2-388 E | Adder | 16.17 MW | 13.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 961161 | AF2-407 | 50/50 | 32.51 MW | 32.51 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 961171 | AF2-408 | 50/50 | 8.76 MW | 8.76 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 243795 | 05HDWTR1G C | 50/50 | 0.69 MW | 0.69 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 913222 | Y1-054 E | Adder | -1.41 MW | -1.2 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932661 | AC2-088 C O1 | Adder | -2.88 MW | -2.45 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932681 | AC2-090 C | 50/50 | 5.9 MW | 5.9 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932682 | AC2-090 E | 50/50 | 9.62 MW | 9.62 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932841 | AC2-111 C O1 | Adder | 2.87 MW | 2.44 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 932842 | AC2-111 E O1 | Adder | 4.68 MW | 3.98 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 933596 | AC2-176 E | Adder | 9.44 MW | 8.02 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939761 | AE1-207 C | Adder | 6.05 MW | 5.14 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939762 | AE1-207 E | Adder | 8.36 MW | 7.1 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939771 | AE1-208 C | Adder | 5.38 MW | 4.57 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939772 | AE1-208 E | Adder | 7.33 MW | 6.23 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939781 | AE1-209 C O1 | 50/50 | 1.62 MW | 1.62 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939782 | AE1-209 E O1 | 50/50 | 10.84 MW | 10.84 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939791 | AE1-210 C O1 | 50/50 | 1.62 MW | 1.62 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 939792 | AE1-210 E O1 | 50/50 | 10.84 MW | 10.84 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 940981 | AE2-089 C O1 | Adder | 6.82 MW | 5.8 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 940982 | AE2-089 E O1 | Adder | 4.55 MW | 3.87 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 941691 | AE2-169 | Adder | 3.23 MW | 2.74 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 941721 | AE2-172 | Adder | 3.6 MW | 3.06 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942071 | AE2-219 C | Adder | 3.67 MW | 3.12 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 942072 | AE2-219 E | Adder | 5.07 MW | 4.31 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 946031 | AF1-268 C O1 | 50/50 | 6.11 MW | 6.11 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 946032 | AF1-268 E O1 | 50/50 | 2.77 MW | 2.77 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 957741 | AF2-068 C O1 | Adder | 7.51 MW | 6.38 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 957742 | AF2-068 E O1 | Adder | 5.01 MW | 4.26 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 250163 | Y3-099 BAT | Adder | 0.2 MW | 0.17 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | 943773 | AF1-045 BAT | Adder | 4.23 MW | 3.6 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.32 MW | 0.32 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.08 MW | 0.08 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.54 MW | 0.54 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 41.43 MW | 41.43 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 26.91 MW | 26.91 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.96 MW | 0.96 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.19 MW | 0.19 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.13 MW | 3.13 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.02 MW | 1.02 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 5.3 MW | 5.3 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.5 MW | 0.5 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 6.18 MW | 6.18 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.46 MW | 0.46 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.93 MW | 1.93 MW |
| 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P7_4504MFTANNERS4512EBTANNERS | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.15 MW | 1.15 MW |
| Details for 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963741 | AG1-226 C O1 | 50/50 | 177.68 MW | 177.68 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963742 | AG1-226 E O1 | 50/50 | 63.52 MW | 63.52 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963831 | AG1-236 C | Adder | 2.4 MW | 2.04 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963832 | AG1-236 E | Adder | 16.08 MW | 13.66 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963841 | AG1-237 C O1 | 50/50 | 13.94 MW | 13.94 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 963842 | AG1-237 E O1 | 50/50 | 93.26 MW | 93.26 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 964581 | AG1-321 C O1 | Adder | 7.37 MW | 6.26 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 964582 | AG1-321 E O1 | Adder | 4.29 MW | 3.65 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965091 | AG1-374 C | Adder | 13.81 MW | 11.74 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965092 | AG1-374 E | Adder | 9.2 MW | 7.82 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965331 | AG1-398 | Adder | 0.68 MW | 0.58 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965341 | AG1-399 C | Adder | 4.54 MW | 3.86 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965342 | AG1-399 E | Adder | 21.25 MW | 18.06 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965351 | AG1-400 | Adder | 12.9 MW | 10.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965371 | AG1-402 | Adder | 12.9 MW | 10.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965391 | AG1-404 | Adder | 8.6 MW | 7.31 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965911 | AG1-460 C | Adder | 1.03 MW | 0.87 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 965912 | AG1-460 E | Adder | 1.54 MW | 1.31 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966531 | AG1-522 C | Adder | 17.39 MW | 14.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966532 | AG1-522 E | Adder | 11.59 MW | 9.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966541 | AG1-523 C | Adder | 17.39 MW | 14.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966542 | AG1-523 E | Adder | 11.59 MW | 9.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966551 | AG1-524 C | Adder | 17.39 MW | 14.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966552 | AG1-524 E | Adder | 11.59 MW | 9.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966561 | AG1-525 C | Adder | 17.39 MW | 14.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 966562 | AG1-525 E | Adder | 11.59 MW | 9.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 290261 | S-027 E | Adder | 12.15 MW | 10.33 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 290265 | S-028 E | Adder | 12.15 MW | 10.33 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 925771 | AC1-053 C | Adder | 2.4 MW | 2.04 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 925772 | AC1-053 E | Adder | 16.08 MW | 13.66 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 935141 | AD1-148 | Adder | 3.28 MW | 2.79 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936771 | AD2-100 C | Adder | 10.71 MW | 9.11 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936772 | AD2-100 E | Adder | 7.14 MW | 6.07 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936971 | AD2-131 C | Adder | 0.71 MW | 0.6 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 936972 | AD2-131 E | Adder | 3.54 MW | 3.01 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942111 | AE2-223 C | Adder | 1.46 MW | 1.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942112 | AE2-223 E | Adder | 9.74 MW | 8.28 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942481 | AE2-261 C | Adder | 15.36 MW | 13.05 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942482 | AE2-261 E | Adder | 10.24 MW | 8.7 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 942601 | AE2-276 | 50/50 | 6.22 MW | 6.22 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945391 | AF1-204 C O1 | 50/50 | 34.17 MW | 34.17 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945392 | AF1-204 E O1 | 50/50 | 102.52 MW | 102.52 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945871 | AF1-252 O1 | Adder | 5.2 MW | 4.42 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 945881 | AF1-253 | Adder | 3.6 MW | 3.06 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 959341 | AF2-225 C | Adder | 4.7 MW | 4.0 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 959342 | AF2-225 E | Adder | 6.5 MW | 5.52 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 959611 | AF2-252 C | Adder | 1.53 MW | 1.3 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 959612 | AF2-252 E | Adder | 2.3 MW | 1.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960141 | AF2-305 | Adder | 0.86 MW | 0.73 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960261 | AF2-317 | Adder | 1.42 MW | 1.2 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960611 | AF2-352 C | Adder | 1.53 MW | 1.3 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 960612 | AF2-352 E | Adder | 2.3 MW | 1.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 276615 | W2-048 GEN | Adder | 4.66 MW | 3.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 276621 | X2-022 GEN | Adder | 16.71 MW | 14.21 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 293777 | CAYUG;1U E | Adder | 6.31 MW | 5.36 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 293778 | CAYUG;2U E | Adder | 6.31 MW | 5.36 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 293798 | W4-005 E | Adder | 24.49 MW | 20.81 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 917502 | Z2-087 E | Adder | 12.99 MW | 11.04 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 924042 | AB2-047 E O1 | Adder | 16.24 MW | 13.8 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 924261 | AB2-070 C O1 | Adder | 2.43 MW | 2.06 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 924262 | AB2-070 E O1 | Adder | 14.7 MW | 12.49 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930461 | AB1-087 CT1 | 50/50 | 38.14 MW | 38.14 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930462 | AB1-087 ST1 | 50/50 | 30.32 MW | 30.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930471 | AB1-088 CT1 | 50/50 | 38.14 MW | 38.14 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 930472 | AB1-088 ST1 | 50/50 | 30.32 MW | 30.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933446 | AC2-157 1C | 50/50 | 4.73 MW | 4.73 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933447 | AC2-157 2C | 50/50 | 4.73 MW | 4.73 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933448 | AC2-157 1E | 50/50 | 7.72 MW | 7.72 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 933449 | AC2-157 2E | 50/50 | 7.72 MW | 7.72 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 939741 | AE1-205 C O1 | Adder | 6.27 MW | 5.33 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 939742 | AE1-205 E O1 | Adder | 8.66 MW | 7.36 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 941341 | AE2-130 C | Adder | 29.02 MW | 24.67 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 941342 | AE2-130 E | Adder | 19.35 MW | 16.44 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 941731 | AE2-173 O1 | Adder | 3.73 MW | 3.17 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944221 | AF1-090 C O1 | Adder | 2.93 MW | 2.49 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944222 | AF1-090 E O1 | Adder | 13.73 MW | 11.67 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957381 | AF2-032 C | Adder | 1.17 MW | 0.99 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957382 | AF2-032 E | Adder | 0.55 MW | 0.47 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 961162 | AF2-407 BAT | Adder | 24.49 MW | 20.82 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 964353 | AG1-297 BAT | Adder | 35.59 MW | 30.25 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957141 | AF2-008 FTIR | 50/50 | 62.24 MW | 62.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 944201 | AF1-088 FTIR | 50/50 | 124.48 MW | 124.48 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 957142 | AF2-008 NFTI | 50/50 | 62.24 MW | 62.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 961172 | AF2-408 BAT | Adder | 5.77 MW | 4.9 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 953741 | J826 C | External Queue | 2.41 MW | 2.41 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 953742 | J826 E | External Queue | 13.06 MW | 13.06 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 953851 | J845 C | External Queue | 3.0 MW | 3.0 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 953852 | J845 E | External Queue | 16.24 MW | 16.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 954681 | J949 C | External Queue | 13.76 MW | 13.76 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 954821 | J955 | External Queue | 66.87 MW | 66.87 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 955402 | J1022 E | External Queue | 23.21 MW | 23.21 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 956281 | J1115 C | External Queue | 3.07 MW | 3.07 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 956282 | J1115 E | External Queue | 16.59 MW | 16.59 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 956451 | J1139 | External Queue | 30.58 MW | 30.58 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 990071 | J1204 | External Queue | 16.07 MW | 16.07 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 990271 | J1263 | External Queue | 31.12 MW | 31.12 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 990672 | J1360 E | External Queue | 48.09 MW | 48.09 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 991236 | J1676 C | External Queue | 4.6 MW | 4.6 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 991237 | J1676 E | External Queue | 24.9 MW | 24.9 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 991261 | J1713 C | External Queue | 1.88 MW | 1.88 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | 991262 | J1713 E | External Queue | 10.19 MW | 10.19 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.95 MW | 2.95 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.27 MW | 0.27 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.63 MW | 1.63 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 24.86 MW | 24.86 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.64 MW | 7.64 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 2.19 MW | 2.19 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.59 MW | 3.59 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.61 MW | 0.61 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.1 MW | 6.1 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.7 MW | 3.7 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.89 MW | 0.89 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.77 MW | 1.77 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.96 MW | 0.96 MW |
| Details for 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 963741 | AG1-226 C O1 | 50/50 | 177.68 MW | 177.68 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 963742 | AG1-226 E O1 | 50/50 | 63.52 MW | 63.52 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 963831 | AG1-236 C | Adder | 2.4 MW | 2.04 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 963832 | AG1-236 E | Adder | 16.08 MW | 13.66 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 964581 | AG1-321 C O1 | Adder | 7.37 MW | 6.26 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 964582 | AG1-321 E O1 | Adder | 4.29 MW | 3.65 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965091 | AG1-374 C | Adder | 13.81 MW | 11.74 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965092 | AG1-374 E | Adder | 9.2 MW | 7.82 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965331 | AG1-398 | Adder | 0.68 MW | 0.58 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965341 | AG1-399 C | Adder | 4.54 MW | 3.86 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965342 | AG1-399 E | Adder | 21.25 MW | 18.06 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965351 | AG1-400 | Adder | 12.9 MW | 10.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965371 | AG1-402 | Adder | 12.9 MW | 10.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965391 | AG1-404 | Adder | 8.6 MW | 7.31 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965911 | AG1-460 C | Adder | 1.03 MW | 0.87 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 965912 | AG1-460 E | Adder | 1.54 MW | 1.31 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966531 | AG1-522 C | Adder | 17.39 MW | 14.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966532 | AG1-522 E | Adder | 11.59 MW | 9.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966541 | AG1-523 C | Adder | 17.39 MW | 14.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966542 | AG1-523 E | Adder | 11.59 MW | 9.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966551 | AG1-524 C | Adder | 17.39 MW | 14.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966552 | AG1-524 E | Adder | 11.59 MW | 9.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966561 | AG1-525 C | Adder | 17.39 MW | 14.78 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 966562 | AG1-525 E | Adder | 11.59 MW | 9.85 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 290261 | S-027 E | Adder | 12.15 MW | 10.33 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 290265 | S-028 E | Adder | 12.15 MW | 10.33 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 925771 | AC1-053 C | Adder | 2.4 MW | 2.04 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 925772 | AC1-053 E | Adder | 16.08 MW | 13.66 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 935141 | AD1-148 | Adder | 3.28 MW | 2.79 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 936771 | AD2-100 C | Adder | 10.71 MW | 9.11 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 936772 | AD2-100 E | Adder | 7.14 MW | 6.07 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 936971 | AD2-131 C | Adder | 0.71 MW | 0.6 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 936972 | AD2-131 E | Adder | 3.54 MW | 3.01 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942111 | AE2-223 C | Adder | 1.46 MW | 1.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942112 | AE2-223 E | Adder | 9.74 MW | 8.28 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942481 | AE2-261 C | Adder | 15.36 MW | 13.05 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942482 | AE2-261 E | Adder | 10.24 MW | 8.7 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 942601 | AE2-276 | 50/50 | 6.22 MW | 6.22 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 945391 | AF1-204 C O1 | 50/50 | 34.17 MW | 34.17 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 945392 | AF1-204 E O1 | 50/50 | 102.52 MW | 102.52 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 945871 | AF1-252 O1 | Adder | 5.2 MW | 4.42 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 945881 | AF1-253 | Adder | 3.6 MW | 3.06 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 959341 | AF2-225 C | Adder | 4.7 MW | 4.0 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 959342 | AF2-225 E | Adder | 6.5 MW | 5.52 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 959611 | AF2-252 C | Adder | 1.53 MW | 1.3 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 959612 | AF2-252 E | Adder | 2.3 MW | 1.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 960141 | AF2-305 | Adder | 0.86 MW | 0.73 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 960261 | AF2-317 | Adder | 1.42 MW | 1.2 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 960611 | AF2-352 C | Adder | 1.53 MW | 1.3 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 960612 | AF2-352 E | Adder | 2.3 MW | 1.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 276615 | W2-048 GEN | Adder | 4.66 MW | 3.96 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 276621 | X2-022 GEN | Adder | 16.71 MW | 14.21 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 293777 | CAYUG;1U E | Adder | 6.31 MW | 5.36 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 293778 | CAYUG;2U E | Adder | 6.31 MW | 5.36 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 293798 | W4-005 E | Adder | 24.49 MW | 20.81 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 917502 | Z2-087 E | Adder | 12.99 MW | 11.04 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 924042 | AB2-047 E O1 | Adder | 16.24 MW | 13.8 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 924261 | AB2-070 C O1 | Adder | 2.43 MW | 2.06 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 924262 | AB2-070 E O1 | Adder | 14.7 MW | 12.49 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 930461 | AB1-087 CT1 | 50/50 | 38.14 MW | 38.14 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 930462 | AB1-087 ST1 | 50/50 | 30.32 MW | 30.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 930471 | AB1-088 CT1 | 50/50 | 38.14 MW | 38.14 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 930472 | AB1-088 ST1 | 50/50 | 30.32 MW | 30.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 933446 | AC2-157 1C | 50/50 | 4.73 MW | 4.73 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 933447 | AC2-157 2C | 50/50 | 4.73 MW | 4.73 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 933448 | AC2-157 1E | 50/50 | 7.72 MW | 7.72 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 933449 | AC2-157 2E | 50/50 | 7.72 MW | 7.72 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 939741 | AE1-205 C O1 | Adder | 6.27 MW | 5.33 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 939742 | AE1-205 E O1 | Adder | 8.66 MW | 7.36 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 941341 | AE2-130 C | Adder | 29.02 MW | 24.67 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 941342 | AE2-130 E | Adder | 19.35 MW | 16.44 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 941731 | AE2-173 O1 | Adder | 3.73 MW | 3.17 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 944221 | AF1-090 C O1 | Adder | 2.93 MW | 2.49 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 944222 | AF1-090 E O1 | Adder | 13.73 MW | 11.67 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 957381 | AF2-032 C | Adder | 1.17 MW | 0.99 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 957382 | AF2-032 E | Adder | 0.55 MW | 0.47 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 961162 | AF2-407 BAT | Adder | 24.49 MW | 20.82 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 964353 | AG1-297 BAT | Adder | 35.59 MW | 30.25 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 957141 | AF2-008 FTIR | 50/50 | 62.24 MW | 62.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 944201 | AF1-088 FTIR | 50/50 | 124.48 MW | 124.48 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 957142 | AF2-008 NFTI | 50/50 | 62.24 MW | 62.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 961172 | AF2-408 BAT | Adder | 5.77 MW | 4.9 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 953741 | J826 C | External Queue | 2.41 MW | 2.41 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 953742 | J826 E | External Queue | 13.06 MW | 13.06 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 953851 | J845 C | External Queue | 3.0 MW | 3.0 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 953852 | J845 E | External Queue | 16.24 MW | 16.24 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 954411 | J912 | External Queue | 5.35 MW | 5.35 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 954681 | J949 C | External Queue | 13.76 MW | 13.76 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 954821 | J955 | External Queue | 76.05 MW | 76.05 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 955402 | J1022 E | External Queue | 23.21 MW | 23.21 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 956281 | J1115 C | External Queue | 3.07 MW | 3.07 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 956282 | J1115 E | External Queue | 16.59 MW | 16.59 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 956451 | J1139 | External Queue | 30.58 MW | 30.58 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 990071 | J1204 | External Queue | 16.07 MW | 16.07 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 990271 | J1263 | External Queue | 31.12 MW | 31.12 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 990672 | J1360 E | External Queue | 48.09 MW | 48.09 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 991236 | J1676 C | External Queue | 4.6 MW | 4.6 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 991237 | J1676 E | External Queue | 24.9 MW | 24.9 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 991261 | J1713 C | External Queue | 1.88 MW | 1.88 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | 991262 | J1713 E | External Queue | 10.19 MW | 10.19 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 2.95 MW | 2.95 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.27 MW | 0.27 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.63 MW | 1.63 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 24.86 MW | 24.86 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.64 MW | 7.64 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.58 MW | 0.58 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 2.19 MW | 2.19 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.59 MW | 3.59 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.61 MW | 0.61 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 6.1 MW | 6.1 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.32 MW | 0.32 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 3.7 MW | 3.7 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.89 MW | 0.89 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.77 MW | 1.77 MW |
| 05EUGENE-08CAYSUB 345.0 kV Ckt 1 line l/o AEP_P7-1_#11014-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.96 MW | 0.96 MW |
Light Load Analysis
The Queue Project was evaluated as a 500.0 MW (Capacity 200.0 MW) injection in the AEP area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| (TBD) | AEP SE rating is 1868 MVA | $0 | |
| n8358.2 | Replace Dearborn 345 kV Bus (Sub Cond 2870 MCM ACSR) | $1,000,000 | |
| n8358.1 | Replace 4 1600 A switches at Dearborn 345 kV | $400,000 | |
| n8358.3 | Replace Dearborn 2500 Amp Wave Traps | $200,000 | |
| (TBD) | An engineering study will need to be conducted to determine if the Tanner CT thermal limit 399A settings can be adjusted to mitigate the overload. | $25,000 | |
| s2019 | AEP Project s2019 Resolves DEOK Overload | $0 | |
| b2831.2 | Rebuild the Tanner Creek – Miami Fort 345kV line (DEOK portion), Actual In-service date 5/14/2021 | $0 | |
| (TBD) | Replace 2 Tanner 345 kV 3000 A switches. | $1,000,000 | |
| (TBD) | Replace Tanner 345 kV 3000 A wavetrap. | $100,000 | |
| (TBD) | Replace 7 Tanner 345 kV 2-1700 AAC 61 Str risers. | $700,000 | |
| (TBD) | Rebuild 0.28 miles line conductor 954 ACSR 45/7 two bundle line conductor. | $560,000 | |
| (TBD) | Replace the Tanner's Creek 345 kV 3000 A Non oil circuit breaker. | $1,000,000 | |
| n7881 | Replace 16 tangent structures, 3 dead end structures, and conductor over one Ohio river crossing | $11,383,000 | |
| n6759.2 | Replace 2 1600 A switches at Dearborn 345 kV and 4 1600 A switches at Pierce 345kV | $9,000,000 | |
| n6759.3 | Replace 2156 KCM ACSR risers at Dearborn 345 kV | $175,000 | |
| n6759.4 | Replace/issue new settings for Dearborn line relays. | $100,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-297 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.