AG1-284 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:45
Fork Union 115 kV
42.0 MW Capacity / 70.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-284 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar generating facility located in the Dominion zone — Fluvanna County, Virginia. The installed facilities will have a total capability of 70.0 MW with 42.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-284 |
| Project Name | Fork Union 115 kV |
| Developer Name | Weber Solar, LLC |
| State | Virginia |
| County | Fluvanna |
| Transmission Owner | Dominion |
| MFO | 70.0 MW |
| MWE | 70.0 MW |
| MWC | 42.0 MW |
| Fuel Type | Solar |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-284 will interconnect with the Dominion transmission system at the Fork Union 115 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 70.0 MW (Capacity 42.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 138.52 % | 141.5 % | 661.76 | B | 936.42 | 20.23 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 134.55 % | 137.53 % | 661.76 | B | 910.09 | 20.23 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 134.32 % | 137.3 % | 661.76 | B | 908.6 | 20.23 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
314333 6POWHATN 230 933500 AC2-165 TAP 230 1
CONTINGENCY '314333 6POWHATN 230 933500 AC2-165 TAP 230 1' /* Auto-generated /* 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 END |
Single | AC | 131.2 % | 134.17 % | 661.76 | B | 887.91 | 20.23 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 130.35 % | 133.32 % | 661.76 | B | 882.28 | 20.23 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 2027
CONTINGENCY 'DVP_P1-2: LN 2027' OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 933500 CKT 1 /*6CARTERV 230.0 - AC2-165 TAP 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314322 CKT 1 /*6JUDES F 230.0 - 6MDLTHAN 230.0 OPEN BRANCH FROM BUS 314310 TO BUS 314333 CKT 1 /*6JUDES F 230.0 - 6POWHATN 230.0 OPEN BRANCH FROM BUS 314333 TO BUS 933500 CKT 1 /*6POWHATN 230.0 - AC2-165 TAP 230.0 OPEN BUS 313868 /*6CARTERV 230.0 OPEN BUS 314310 /*6JUDES F 230.0 OPEN BUS 314333 /*6POWHATN 230.0 OPEN BUS 923862 /*AB2-026 E 230.0 OPEN BUS 933500 /*AC2-165 TAP 230.0 OPEN BUS 933501 /*AC2-165 C 230.0 OPEN BUS 933502 /*AC2-165 E 230.0 OPEN BUS 938561 /*AE1-075 C 230.0 OPEN BUS 938562 /*AE1-075 E 230.0 END |
Single | AC | 127.31 % | 130.29 % | 661.76 | B | 862.22 | 20.23 | |
| DVP |
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1 |
DVP_P1-2: LN 550
CONTINGENCY 'DVP_P1-2: LN 550' OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1 /*8MT STM 500.0 - 8VALLEY 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 END |
Single | AC | 107.55 % | 108.62 % | 550.84 | B | 598.34 | 5.62 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 105.41 % | 107.53 % | 800.88 | B | 861.19 | 17.0 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 105.4 % | 107.52 % | 800.88 | B | 861.12 | 17.0 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 105.37 % | 107.49 % | 800.88 | B | 860.87 | 17.0 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 105.36 % | 107.48 % | 800.88 | B | 860.79 | 17.0 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 104.75 % | 106.87 % | 800.88 | B | 855.92 | 17.0 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 104.74 % | 106.86 % | 800.88 | B | 855.84 | 17.0 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 100.73 % | 104.89 % | 169.2 | B | 177.47 | 7.04 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 100.39 % | 104.54 % | 169.2 | B | 176.89 | 7.04 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 99.42 % | 101.54 % | 800.88 | B | 813.22 | 17.0 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 99.41 % | 101.53 % | 800.88 | B | 813.15 | 17.0 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
DVP_P1-2: LN 2028
CONTINGENCY 'DVP_P1-2: LN 2028' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Single | AC | 98.16 % | 100.28 % | 800.88 | B | 803.09 | 17.0 | |
| DVP |
6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line
313868 to 933500 ckt 1 |
314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1
CONTINGENCY '314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1' /* Auto-generated /* 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 END |
Single | AC | 98.15 % | 100.27 % | 800.88 | B | 803.01 | 17.0 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P1-2: LN 2028-C
CONTINGENCY 'DVP_P1-2: LN 2028-C' OPEN BRANCH FROM BUS 313707 TO BUS 961060 CKT 1 /*6FORK UNION 230.0 - AF2-397 TAP 230.0 END |
Single | AC | 96.02 % | 100.17 % | 169.2 | B | 169.49 | 7.04 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P4-2: YT1030
CONTINGENCY 'DVP_P4-2: YT1030' OPEN BRANCH FROM BUS 313707 TO BUS 313708 CKT 1 /*6FORK UNION 230.0 - 3FORK UNION 115.0 OPEN BRANCH FROM BUS 313708 TO BUS 314744 CKT 1 /*3FORK UNION 115.0 - 3BREMO 115.0 OPEN BUS 313872 /*3FORK UNIO_1 115.0 END |
Breaker | AC | 111.98 % | 147.05 % | 208.0 | C | 305.86 | 70.0 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 556T591
CONTINGENCY 'DVP_P4-2: 556T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 122.46 % | 125.5 % | 809.0 | C | 1015.3 | 25.15 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T556
CONTINGENCY 'DVP_P4-2: 511T556' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 966360 TO BUS 314936 CKT 1 /*AG1-505 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 122.46 % | 125.5 % | 809.0 | C | 1015.29 | 25.15 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P4-2: 511T591
CONTINGENCY 'DVP_P4-2: 511T591' OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 END |
Breaker | DC | 122.44 % | 125.48 % | 809.0 | C | 1015.14 | 25.15 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 104.62 % | 107.48 % | 980.0 | C | 1053.33 | 28.36 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 104.58 % | 107.45 % | 980.0 | C | 1052.99 | 28.36 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 104.26 % | 107.12 % | 980.0 | C | 1049.77 | 28.33 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 104.22 % | 107.08 % | 980.0 | C | 1049.42 | 28.33 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P4-2: 2028T2054-A
CONTINGENCY 'DVP_P4-2: 2028T2054-A' OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1 /*6CHARLVL 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1 /*6HOLLYMD 230.0 - 6PROFFIT 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 OPEN BUS 314772 /*6PROFFIT 230.0 END |
Breaker | AC | 103.27 % | 106.22 % | 980.0 | C | 1040.91 | 28.37 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P4-2: 233T2028-A
CONTINGENCY 'DVP_P4-2: 233T2028-A' OPEN BRANCH FROM BUS 313826 TO BUS 314742 CKT 1 /*6HYDRAULIC 230.0 - 6BARRCK2 230.0 OPEN BRANCH FROM BUS 313826 TO BUS 314749 CKT 1 /*6HYDRAULIC 230.0 - 6CHARLVL 230.0 OPEN BRANCH FROM BUS 314742 TO BUS 314751 CKT 1 /*6BARRCK2 230.0 - 6CROZET1 230.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 314751 TO BUS 314794 CKT 1 /*6CROZET1 230.0 - 6DOOMS 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 313826 /*6HYDRAULIC 230.0 OPEN BUS 314742 /*6BARRCK2 230.0 OPEN BUS 314751 /*6CROZET1 230.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Breaker | AC | 102.91 % | 105.84 % | 980.0 | C | 1037.23 | 28.34 | |
| DVP |
3SHERWOD-3RED HIL 115.0 kV Ckt 1 line
314774 to 314773 ckt 1 |
DVP_P4-2: YT1030
CONTINGENCY 'DVP_P4-2: YT1030' OPEN BRANCH FROM BUS 313707 TO BUS 313708 CKT 1 /*6FORK UNION 230.0 - 3FORK UNION 115.0 OPEN BRANCH FROM BUS 313708 TO BUS 314744 CKT 1 /*3FORK UNION 115.0 - 3BREMO 115.0 OPEN BUS 313872 /*3FORK UNIO_1 115.0 END |
Breaker | AC | 66.02 % | 100.3 % | 208.0 | C | 208.62 | 70.0 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 105.0 % | 107.86 % | 980.0 | C | 1057.03 | 28.33 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 104.99 % | 107.85 % | 980.0 | C | 1056.96 | 28.33 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 104.96 % | 107.83 % | 980.0 | C | 1056.69 | 28.33 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 104.95 % | 107.82 % | 980.0 | C | 1056.63 | 28.33 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 103.64 % | 106.58 % | 980.0 | C | 1044.45 | 28.34 | |
| DVP |
AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line
933500 to 314333 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 103.63 % | 106.57 % | 980.0 | C | 1044.39 | 28.34 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 100.36 % | 105.96 % | 208.0 | C | 220.39 | 11.73 | |
| DVP |
AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line
941010 to 314774 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 100.08 % | 105.68 % | 208.0 | C | 219.81 | 11.73 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P7-1: LN 5-2028-C
CONTINGENCY 'DVP_P7-1: LN 5-2028-C' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 314749 TO BUS 314765 CKT 1 /*6CHARLVL 230.0 - 6MTEAGLE 230.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 OPEN BUS 314765 /*6MTEAGLE 230.0 END |
Tower | AC | 97.34 % | 100.2 % | 980.0 | C | 982.0 | 28.34 | |
| DVP |
6BREMO-6CARTERV 230.0 kV Ckt 1 line
314747 to 313868 ckt 1 |
DVP_P7-1: LN 5-2028-B
CONTINGENCY 'DVP_P7-1: LN 5-2028-B' OPEN BRANCH FROM BUS 314744 TO BUS 314754 CKT 1 /*3BREMO 115.0 - 3CUNNING 115.0 OPEN BRANCH FROM BUS 961060 TO BUS 314765 CKT 1 /*AF2-397 TAP 230.0 - 6MTEAGLE 230.0 OPEN BUS 314754 /*3CUNNING 115.0 END |
Tower | AC | 97.33 % | 100.2 % | 980.0 | C | 981.93 | 28.34 | |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 31.79 MW | 31.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o 314333 6POWHATN 230 933500 AC2-165 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961061 | AF2-397 C | 80/20 | 49.39 MW | 49.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961791 | AG1-021 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961801 | AG1-022 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 961891 | AG1-030 C | 80/20 | 20.11 MW | 20.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962491 | AG1-098 C O1 | 80/20 | 11.98 MW | 11.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962741 | AG1-123 C O1 | 80/20 | 3.02 MW | 3.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962751 | AG1-124 C O1 | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963171 | AG1-166 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963181 | AG1-167 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963191 | AG1-168 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963201 | AG1-169 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963211 | AG1-170 C | 80/20 | 2.89 MW | 2.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963301 | AG1-179 C | 80/20 | 2.73 MW | 2.73 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963311 | AG1-180 | 80/20 | 1.33 MW | 1.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963321 | AG1-181 C O1 | 80/20 | 18.37 MW | 18.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 963361 | AG1-185 O1 | 80/20 | 8.89 MW | 8.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964111 | AG1-272 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964121 | AG1-273 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964131 | AG1-274 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964231 | AG1-284 C O1 | 80/20 | 20.23 MW | 20.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964241 | AG1-285 C O1 | 80/20 | 11.04 MW | 11.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 964791 | AG1-342 C | 80/20 | 2.6 MW | 2.6 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966691 | AG1-539 C | 80/20 | 1.94 MW | 1.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965191 | AG1-384 C | 80/20 | 2.94 MW | 2.94 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965581 | AG1-426 | 80/20 | 6.43 MW | 6.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965591 | AG1-427 C | 80/20 | 10.55 MW | 10.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965601 | AG1-428 C O2 | 80/20 | 2.28 MW | 2.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965641 | AG1-432 C O1 | 80/20 | 36.99 MW | 36.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965721 | AG1-440 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965731 | AG1-441 C | 80/20 | 3.8 MW | 3.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965771 | AG1-445 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965781 | AG1-446 | 80/20 | 2.2 MW | 2.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 965831 | AG1-451 | 80/20 | 6.17 MW | 6.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966251 | AG1-494 C | 80/20 | 1.82 MW | 1.82 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 966621 | AG1-532 C | 80/20 | 0.41 MW | 0.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314429 | 3JTRSVLE | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314572 | 3EMPORIA | 80/20 | 0.13 MW | 0.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314704 | 3LAWRENC | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315153 | 1CLOVER1 | 80/20 | 7.42 MW | 7.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315154 | 1CLOVER2 | 80/20 | 7.35 MW | 7.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315158 | 1KERR 1 | 80/20 | 0.23 MW | 0.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315159 | 1KERR 2 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315160 | 1KERR 3 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315161 | 1KERR 4 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315162 | 1KERR 5 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 926023 | AC1-080 C | 80/20 | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927251 | AC1-221 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 927261 | AC1-222 C | 80/20 | 1.83 MW | 1.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934311 | AD1-055 C | 80/20 | 1.27 MW | 1.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934341 | AD1-058 C | 80/20 | 1.91 MW | 1.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934615 | AD1-087 C | 80/20 | 4.3 MW | 4.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934625 | AD1-088 C | 80/20 | 13.51 MW | 13.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 934991 | AD1-131 C | 80/20 | 0.63 MW | 0.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 935171 | AD1-152 C O1 | 80/20 | 4.27 MW | 4.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 936265 | AD2-033 C | 80/20 | 13.96 MW | 13.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 937481 | AD2-202 C O1 | 80/20 | 1.26 MW | 1.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942461 | AE2-259 C O1 | 80/20 | 18.5 MW | 18.5 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942751 | AE2-291 C | 80/20 | 3.71 MW | 3.71 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 942761 | AE2-292 C O1 | 80/20 | 4.62 MW | 4.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 943901 | AF1-058 C | 80/20 | 1.0 MW | 1.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 945811 | AF1-246 C O1 | 80/20 | 3.34 MW | 3.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958801 | AF2-171 C | 80/20 | 21.61 MW | 21.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 959311 | AF2-222 C | 80/20 | 19.76 MW | 19.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960061 | AF2-297 C | 80/20 | 4.01 MW | 4.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960081 | AF2-299 C | 80/20 | 0.76 MW | 0.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 960111 | AF2-302 C | 80/20 | 4.04 MW | 4.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315163 | 1KERR 6 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315164 | 1KERR 7 | 80/20 | 0.66 MW | 0.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315266 | 1PLYWOOD A | 80/20 | 0.69 MW | 0.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316118 | AC1-105 C | 80/20 | 3.22 MW | 3.22 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316129 | AC1-054 C | 80/20 | 3.2 MW | 3.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316131 | AB2-060 C | 80/20 | 1.25 MW | 1.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924301 | AB2-077 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924311 | AB2-078 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 924321 | AB2-079 C O1 | 80/20 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 925611 | AC1-036 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 932761 | AC2-100 C | 80/20 | 1.75 MW | 1.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938371 | AE1-056 C | 80/20 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 938821 | AE1-108 C O1 | 80/20 | 33.92 MW | 33.92 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 939181 | AE1-148 C | 80/20 | 5.38 MW | 5.38 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 940661 | AE2-053 O1 | 80/20 | 1.99 MW | 1.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941011 | AE2-092 C | 80/20 | 28.72 MW | 28.72 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 941791 | AE2-182 C | 80/20 | 2.19 MW | 2.19 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946281 | AF1-292 C | 80/20 | 0.45 MW | 0.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946291 | AF1-293 C O1 | 80/20 | 46.34 MW | 46.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946301 | AF1-294 C | 80/20 | 5.93 MW | 5.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 946591 | AF1-323 C | 80/20 | 11.11 MW | 11.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 957481 | AF2-042 C | 80/20 | 23.85 MW | 23.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958131 | AF2-107 C | 80/20 | 5.01 MW | 5.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 958211 | AF2-115 C | 80/20 | 3.62 MW | 3.62 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 314677 | 6BUCKING | 80/20 | 1.04 MW | 1.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315191 | 1BEARGRDN G1 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315192 | 1BEARGRDN G2 | 80/20 | 18.14 MW | 18.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 315193 | 1BEARGRDN S1 | 80/20 | 23.46 MW | 23.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 962561 | AG1-105 C O1 | 80/20 | 5.81 MW | 5.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | 316123 | AC1-075 C | 80/20 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.51 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.37 MW | 0.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 5.3 MW | 5.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.55 MW | 7.55 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.29 MW | 2.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.89 MW | 1.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.29 MW | 0.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.91 MW | 0.91 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.44 MW | 0.44 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.05 MW | 0.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2027 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.13 MW | 0.13 MW |
| Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961791 | AG1-021 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961801 | AG1-022 C | 80/20 | 1.26 MW | 1.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961891 | AG1-030 C | 80/20 | 5.49 MW | 5.49 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962491 | AG1-098 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962741 | AG1-123 C O1 | 80/20 | 2.24 MW | 2.24 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962751 | AG1-124 C O1 | 80/20 | 3.29 MW | 3.29 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963021 | AG1-151 O1 | 80/20 | 9.03 MW | 9.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963171 | AG1-166 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963181 | AG1-167 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963191 | AG1-168 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963201 | AG1-169 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963211 | AG1-170 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963321 | AG1-181 C O1 | 80/20 | 5.27 MW | 5.27 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963361 | AG1-185 O1 | 80/20 | 2.55 MW | 2.55 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963471 | AG1-196 O1 | 80/20 | 17.34 MW | 17.34 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964111 | AG1-272 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964121 | AG1-273 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964131 | AG1-274 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964231 | AG1-284 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964831 | AG1-346 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965191 | AG1-384 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965581 | AG1-426 | 80/20 | 1.92 MW | 1.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965641 | AG1-432 C O1 | 80/20 | 9.5 MW | 9.5 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965831 | AG1-451 | 80/20 | 1.58 MW | 1.58 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966251 | AG1-494 C | 80/20 | 1.21 MW | 1.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314429 | 3JTRSVLE | 80/20 | 0.18 MW | 0.18 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934625 | AD1-088 C | 80/20 | 3.65 MW | 3.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 936265 | AD2-033 C | 80/20 | 4.02 MW | 4.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942461 | AE2-259 C O1 | 80/20 | 4.75 MW | 4.75 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958801 | AF2-171 C | 80/20 | 5.81 MW | 5.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 959311 | AF2-222 C | 80/20 | 5.55 MW | 5.55 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 960111 | AF2-302 C | 80/20 | 1.26 MW | 1.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 242889 | 05REUSENS | 80/20 | 0.04 MW | 0.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 925611 | AC1-036 C | 80/20 | 0.08 MW | 0.08 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938371 | AE1-056 C | 80/20 | 2.67 MW | 2.67 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938821 | AE1-108 C O1 | 80/20 | 10.13 MW | 10.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941011 | AE2-092 C | 80/20 | 11.2 MW | 11.2 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941791 | AE2-182 C | 80/20 | 0.59 MW | 0.59 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946291 | AF1-293 C O1 | 80/20 | 14.58 MW | 14.58 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946301 | AF1-294 C | 80/20 | 1.59 MW | 1.59 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946591 | AF1-323 C | 80/20 | 3.48 MW | 3.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958131 | AF2-107 C | 80/20 | 2.33 MW | 2.33 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958211 | AF2-115 C | 80/20 | 0.97 MW | 0.97 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 235034 | 01SHY_Z2-039 | 80/20 | 0.01 MW | 0.01 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 235035 | 01NHY_Z2-039 | 80/20 | 0.02 MW | 0.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 237092 | AD1-085_C | 80/20 | 0.16 MW | 0.16 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940451 | AE2-029 C | 80/20 | 3.28 MW | 3.28 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943571 | AF1-028 O1 | 80/20 | 18.07 MW | 18.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 933501 | AC2-165 C | 80/20 | 4.35 MW | 4.35 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944071 | AF1-075 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961061 | AF2-397 C | 80/20 | 12.98 MW | 12.98 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 313738 | 3CUSHAW | 80/20 | 0.1 MW | 0.1 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314333 | 6POWHATN | 80/20 | 0.15 MW | 0.15 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314677 | 6BUCKING | 80/20 | 0.26 MW | 0.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314859 | 4WSTVACO | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 926001 | AC1-076 C | Adder | -2.55 MW | -2.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958501 | AF2-144 C | 80/20 | 0.65 MW | 0.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966671 | AG1-537 C | 80/20 | 4.45 MW | 4.45 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315186 | 1LOWMORA | 80/20 | 0.44 MW | 0.44 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315188 | 1LOWMORC | 80/20 | 0.44 MW | 0.44 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315191 | 1BEARGRDN G1 | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315192 | 1BEARGRDN G2 | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315193 | 1BEARGRDN S1 | 80/20 | 5.67 MW | 5.67 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315201 | 1BATH 1A | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315202 | 1BATH 2B | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315203 | 1BATH 3C | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315204 | 1BATH 4D | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315205 | 1BATH 5E | 80/20 | 7.9 MW | 7.9 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315206 | 1BATH 6F | 80/20 | 7.92 MW | 7.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315216 | 1CUNINGA | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315217 | 1CUNINGB | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315218 | 1CUNINGC | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315219 | 1CUNINGD | 80/20 | 4.22 MW | 4.22 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315616 | AA1-038 C | 80/20 | 1.04 MW | 1.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 932854 | AC2-112 C | 80/20 | 14.33 MW | 14.33 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938561 | AE1-075 C | 80/20 | 0.13 MW | 0.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938625 | AE1-084 C | 80/20 | 6.92 MW | 6.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941381 | AE2-134 | Adder | -1.76 MW | -1.49 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963461 | AG1-195 | 80/20 | 16.21 MW | 16.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965531 | AG1-421 C | 80/20 | 13.88 MW | 13.88 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965541 | AG1-422 | 80/20 | 5.78 MW | 5.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966851 | AG1-556 C | 80/20 | 10.31 MW | 10.31 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.09 MW | 1.09 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.81 MW | 0.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.07 MW | 26.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 21.87 MW | 21.87 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.65 MW | 17.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.7 MW | 3.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.12 MW | 1.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.81 MW | 2.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.07 MW | 3.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.52 MW | 0.52 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 6.79 MW | 6.79 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314333 | 6POWHATN | 80/20 | 0.12 MW | 0.12 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.18 MW | 0.18 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | 80/20 | 0.52 MW | 0.52 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 4.14 MW | 4.14 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938561 | AE1-075 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 6.79 MW | 6.79 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314333 | 6POWHATN | 80/20 | 0.12 MW | 0.12 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.18 MW | 0.18 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | 80/20 | 0.52 MW | 0.52 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 4.14 MW | 4.14 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938561 | AE1-075 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961891 | AG1-030 C | 80/20 | 15.84 MW | 15.84 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962491 | AG1-098 C O1 | 80/20 | 9.06 MW | 9.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963321 | AG1-181 C O1 | 80/20 | 14.07 MW | 14.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964241 | AG1-285 C O1 | 80/20 | 8.15 MW | 8.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965591 | AG1-427 C | 80/20 | 7.8 MW | 7.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965641 | AG1-432 C O1 | 80/20 | 30.11 MW | 30.11 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965721 | AG1-440 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965731 | AG1-441 C | 80/20 | 2.37 MW | 2.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965771 | AG1-445 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965781 | AG1-446 | 80/20 | 1.37 MW | 1.37 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315153 | 1CLOVER1 | 80/20 | 4.68 MW | 4.68 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315154 | 1CLOVER2 | 80/20 | 4.63 MW | 4.63 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934311 | AD1-055 C | 80/20 | 0.86 MW | 0.86 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 934625 | AD1-088 C | 80/20 | 10.24 MW | 10.24 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 936265 | AD2-033 C | 80/20 | 10.66 MW | 10.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 937481 | AD2-202 C O1 | 80/20 | 0.8 MW | 0.8 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 942461 | AE2-259 C O1 | 80/20 | 15.06 MW | 15.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 943901 | AF1-058 C | 80/20 | 0.67 MW | 0.67 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958801 | AF2-171 C | 80/20 | 17.17 MW | 17.17 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 959311 | AF2-222 C | 80/20 | 15.32 MW | 15.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 938821 | AE1-108 C O1 | 80/20 | 28.71 MW | 28.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 939181 | AE1-148 C | 80/20 | 3.6 MW | 3.6 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941011 | AE2-092 C | 80/20 | 25.29 MW | 25.29 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946291 | AF1-293 C O1 | 80/20 | 39.55 MW | 39.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 946591 | AF1-323 C | 80/20 | 9.43 MW | 9.43 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958131 | AF2-107 C | 80/20 | 4.38 MW | 4.38 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 961061 | AF2-397 C | 80/20 | 36.66 MW | 36.66 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315191 | 1BEARGRDN G1 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315192 | 1BEARGRDN G2 | 80/20 | 15.4 MW | 15.4 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 962561 | AG1-105 C O1 | 80/20 | 4.06 MW | 4.06 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6CARTERV-AC2-165 TAP 230.0 kV Ckt 1 line l/o 314765 6MTEAGLE 230 961060 AF2-397 TAP 230 1 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961801 | AG1-022 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964231 | AG1-284 C O1 | 80/20 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965581 | AG1-426 | 80/20 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965641 | AG1-432 C O1 | 80/20 | 6.79 MW | 6.79 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965831 | AG1-451 | 80/20 | 1.13 MW | 1.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 942461 | AE2-259 C O1 | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960111 | AF2-302 C | 80/20 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938821 | AE1-108 C O1 | 80/20 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941011 | AE2-092 C | 80/20 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946291 | AF1-293 C O1 | 80/20 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946591 | AF1-323 C | 80/20 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 933501 | AC2-165 C | 80/20 | 3.4 MW | 3.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314333 | 6POWHATN | 80/20 | 0.12 MW | 0.12 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314677 | 6BUCKING | 80/20 | 0.18 MW | 0.18 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958501 | AF2-144 C | 80/20 | 0.52 MW | 0.52 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315191 | 1BEARGRDN G1 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315192 | 1BEARGRDN G2 | 80/20 | 3.21 MW | 3.21 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315193 | 1BEARGRDN S1 | 80/20 | 4.14 MW | 4.14 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938561 | AE1-075 C | 80/20 | 0.1 MW | 0.1 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 964231 | AG1-284 C O1 | 50/50 | 42.0 MW | 42.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 964232 | AG1-284 E O1 | 50/50 | 28.0 MW | 28.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 941011 | AE2-092 C | 50/50 | 82.8 MW | 82.8 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 941012 | AE2-092 E | 50/50 | 55.2 MW | 55.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 946291 | AF1-293 C O1 | 50/50 | 108.4 MW | 108.4 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 946292 | AF1-293 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 556T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T556 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961791 | AG1-021 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961792 | AG1-021 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961801 | AG1-022 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961802 | AG1-022 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961891 | AG1-030 C | 50/50 | 17.76 MW | 17.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961892 | AG1-030 E | 50/50 | 11.84 MW | 11.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962491 | AG1-098 C O1 | 50/50 | 13.31 MW | 13.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962492 | AG1-098 E O1 | 50/50 | 8.87 MW | 8.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963171 | AG1-166 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963172 | AG1-166 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963181 | AG1-167 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963182 | AG1-167 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963191 | AG1-168 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963192 | AG1-168 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963201 | AG1-169 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963202 | AG1-169 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963211 | AG1-170 C | 50/50 | 2.52 MW | 2.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963212 | AG1-170 E | 50/50 | 1.68 MW | 1.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963301 | AG1-179 C | Adder | 2.85 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963311 | AG1-180 | Adder | 1.39 MW | 1.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963321 | AG1-181 C O1 | 50/50 | 16.84 MW | 16.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 963361 | AG1-185 O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964111 | AG1-272 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964112 | AG1-272 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964121 | AG1-273 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964122 | AG1-273 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964131 | AG1-274 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964132 | AG1-274 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964231 | AG1-284 C O1 | 50/50 | 15.09 MW | 15.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964232 | AG1-284 E O1 | 50/50 | 10.06 MW | 10.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964241 | AG1-285 C O1 | 50/50 | 10.59 MW | 10.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964242 | AG1-285 E O1 | 50/50 | 7.06 MW | 7.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964791 | AG1-342 C | 50/50 | 2.97 MW | 2.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 964792 | AG1-342 E | 50/50 | 2.33 MW | 2.33 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965191 | AG1-384 C | 50/50 | 2.67 MW | 2.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965192 | AG1-384 E | 50/50 | 0.79 MW | 0.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965581 | AG1-426 | 50/50 | 4.79 MW | 4.79 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965591 | AG1-427 C | 50/50 | 10.1 MW | 10.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965592 | AG1-427 E | 50/50 | 6.75 MW | 6.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965601 | AG1-428 C O2 | Adder | 2.38 MW | 2.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965602 | AG1-428 E O2 | Adder | 1.58 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965641 | AG1-432 C O1 | 50/50 | 31.18 MW | 31.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965642 | AG1-432 E O1 | 50/50 | 20.78 MW | 20.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965721 | AG1-440 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965722 | AG1-440 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965731 | AG1-441 C | Adder | 4.0 MW | 3.4 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965732 | AG1-441 E | Adder | 2.67 MW | 2.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965771 | AG1-445 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965781 | AG1-446 | Adder | 2.31 MW | 1.97 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 965831 | AG1-451 | 50/50 | 5.2 MW | 5.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966361 | AG1-505 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966362 | AG1-505 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966371 | AG1-506 C | 50/50 | 14.49 MW | 14.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 966372 | AG1-506 E | 50/50 | 9.66 MW | 9.66 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313853 | 3PONTONDP | 50/50 | 0.84 MW | 0.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314429 | 3JTRSVLE | 50/50 | 0.57 MW | 0.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314713 | 3PAMPLIN | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315153 | 1CLOVER1 | 50/50 | 12.11 MW | 12.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315154 | 1CLOVER2 | 50/50 | 11.99 MW | 11.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 926274 | AC1-105 E | 50/50 | 1.88 MW | 1.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927261 | AC1-222 C | 50/50 | 2.37 MW | 2.37 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 927262 | AC1-222 E | 50/50 | 2.25 MW | 2.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934311 | AD1-055 C | 50/50 | 1.64 MW | 1.64 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934312 | AD1-055 E | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934615 | AD1-087 C | 50/50 | 7.02 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934616 | AD1-087 E | 50/50 | 3.29 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934625 | AD1-088 C | 50/50 | 14.9 MW | 14.9 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 934626 | AD1-088 E | 50/50 | 7.01 MW | 7.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935171 | AD1-152 C O1 | 50/50 | 6.67 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 935172 | AD1-152 E O1 | 50/50 | 4.45 MW | 4.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936265 | AD2-033 C | 50/50 | 12.83 MW | 12.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 936266 | AD2-033 E | 50/50 | 8.56 MW | 8.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937481 | AD2-202 C O1 | 50/50 | 2.06 MW | 2.06 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 937482 | AD2-202 E O1 | 50/50 | 0.96 MW | 0.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942461 | AE2-259 C O1 | 50/50 | 15.59 MW | 15.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 942462 | AE2-259 E O1 | 50/50 | 10.39 MW | 10.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943901 | AF1-058 C | 50/50 | 1.32 MW | 1.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 943902 | AF1-058 E | 50/50 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945811 | AF1-246 C O1 | 50/50 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 945812 | AF1-246 E O1 | 50/50 | 9.34 MW | 9.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946592 | AF1-323 E | 50/50 | 5.52 MW | 5.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958801 | AF2-171 C | 50/50 | 18.87 MW | 18.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958802 | AF2-171 E | 50/50 | 12.58 MW | 12.58 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959311 | AF2-222 C | 50/50 | 17.83 MW | 17.83 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 959312 | AF2-222 E | 50/50 | 11.95 MW | 11.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960061 | AF2-297 C | 50/50 | 5.27 MW | 5.27 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960062 | AF2-297 E | 50/50 | 3.51 MW | 3.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960111 | AF2-302 C | 50/50 | 3.01 MW | 3.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 960112 | AF2-302 E | 50/50 | 2.01 MW | 2.01 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315266 | 1PLYWOOD A | 50/50 | 0.85 MW | 0.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316118 | AC1-105 C | 50/50 | 3.93 MW | 3.93 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 316131 | AB2-060 C | 50/50 | 1.23 MW | 1.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924162 | AB2-060 E OP | 50/50 | 3.39 MW | 3.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924301 | AB2-077 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924302 | AB2-077 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924311 | AB2-078 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924312 | AB2-078 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924321 | AB2-079 C O1 | 50/50 | 1.53 MW | 1.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924322 | AB2-079 E O1 | 50/50 | 1.02 MW | 1.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925611 | AC1-036 C | 50/50 | 0.25 MW | 0.25 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 925612 | AC1-036 E | 50/50 | 1.61 MW | 1.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938371 | AE1-056 C | 50/50 | 8.68 MW | 8.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938372 | AE1-056 E | 50/50 | 4.74 MW | 4.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938821 | AE1-108 C O1 | 50/50 | 25.28 MW | 25.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938822 | AE1-108 E O1 | 50/50 | 16.85 MW | 16.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939181 | AE1-148 C | 50/50 | 5.53 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 939182 | AE1-148 E | 50/50 | 3.69 MW | 3.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 940661 | AE2-053 O1 | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941011 | AE2-092 C | 50/50 | 20.63 MW | 20.63 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941012 | AE2-092 E | 50/50 | 13.75 MW | 13.75 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941791 | AE2-182 C | 50/50 | 2.42 MW | 2.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 941792 | AE2-182 E | 50/50 | 1.13 MW | 1.13 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946291 | AF1-293 C O1 | 50/50 | 34.15 MW | 34.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946292 | AF1-293 E O1 | 50/50 | 6.14 MW | 6.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946301 | AF1-294 C | 50/50 | 5.17 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946302 | AF1-294 E | 50/50 | 3.45 MW | 3.45 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 946591 | AF1-323 C | 50/50 | 8.28 MW | 8.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957481 | AF2-042 C | 50/50 | 48.3 MW | 48.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 957482 | AF2-042 E | 50/50 | 32.2 MW | 32.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958131 | AF2-107 C | 50/50 | 3.74 MW | 3.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958132 | AF2-107 E | 50/50 | 2.05 MW | 2.05 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958211 | AF2-115 C | 50/50 | 3.15 MW | 3.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958212 | AF2-115 E | 50/50 | 2.1 MW | 2.1 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924032 | AB2-045 E | 50/50 | 2.21 MW | 2.21 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933501 | AC2-165 C | 50/50 | 13.98 MW | 13.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 933502 | AC2-165 E | 50/50 | 10.52 MW | 10.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314333 | 6POWHATN | 50/50 | 0.49 MW | 0.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 314677 | 6BUCKING | 50/50 | 0.81 MW | 0.81 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958501 | AF2-144 C | 50/50 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 958502 | AF2-144 E | 50/50 | 1.43 MW | 1.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315191 | 1BEARGRDN G1 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315192 | 1BEARGRDN G2 | 50/50 | 13.43 MW | 13.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 315193 | 1BEARGRDN S1 | 50/50 | 17.36 MW | 17.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 923862 | AB2-026 E | 50/50 | 1.3 MW | 1.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938561 | AE1-075 C | 50/50 | 0.43 MW | 0.43 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 938562 | AE1-075 E | 50/50 | 1.24 MW | 1.24 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962561 | AG1-105 C O1 | 50/50 | 6.46 MW | 6.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 962562 | AG1-105 E O1 | 50/50 | 4.31 MW | 4.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 313527 | AB2-043 C | 50/50 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 924022 | AB2-043 E O1 | 50/50 | 2.18 MW | 2.18 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | 961063 | AF2-397 BAT | 50/50 | 25.57 MW | 25.57 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.77 MW | 1.77 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 29.8 MW | 29.8 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.56 MW | 3.56 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 6.99 MW | 6.99 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 2.69 MW | 2.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.85 MW | 1.85 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.15 MW | 0.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.2 MW | 0.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.74 MW | 0.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.39 MW | 0.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 4.96 MW | 4.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.04 MW | 0.04 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.49 MW | 1.49 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 511T591 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.1 MW | 0.1 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.04 MW | 9.04 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.22 MW | 10.22 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.74 MW | 28.74 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.16 MW | 19.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.39 MW | 25.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.92 MW | 16.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.62 MW | 39.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.44 MW | 9.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.23 MW | 39.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.52 MW | 29.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.71 MW | 14.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.69 MW | 8.69 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.56 MW | 7.56 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.83 MW | 0.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.64 MW | 1.64 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.15 MW | 1.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.3 MW | 5.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.35 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.04 MW | 9.04 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.22 MW | 10.22 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.74 MW | 28.74 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.16 MW | 19.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.39 MW | 25.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.92 MW | 16.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.62 MW | 39.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.44 MW | 9.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.23 MW | 39.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.52 MW | 29.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.71 MW | 14.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.69 MW | 8.69 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.56 MW | 7.56 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.83 MW | 0.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.64 MW | 1.64 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.44 MW | 0.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.15 MW | 1.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.37 MW | 0.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.3 MW | 5.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.35 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.45 MW | 14.45 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.21 MW | 8.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.24 MW | 7.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.81 MW | 0.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.09 MW | 1.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.12 MW | 5.12 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | 50/50 | 7.48 MW | 7.48 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.45 MW | 14.45 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.21 MW | 8.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.24 MW | 7.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.81 MW | 0.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.58 MW | 1.58 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.09 MW | 1.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.12 MW | 5.12 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.3 MW | 1.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961801 | AG1-022 C | 50/50 | 3.44 MW | 3.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963321 | AG1-181 C O1 | 50/50 | 14.06 MW | 14.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964231 | AG1-284 C O1 | 50/50 | 17.02 MW | 17.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964232 | AG1-284 E O1 | 50/50 | 11.35 MW | 11.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965581 | AG1-426 | 50/50 | 5.45 MW | 5.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965642 | AG1-432 E O1 | 50/50 | 20.08 MW | 20.08 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966251 | AG1-494 C | Adder | 1.67 MW | 1.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 966252 | AG1-494 E | Adder | 2.5 MW | 2.12 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946592 | AF1-323 E | 50/50 | 6.3 MW | 6.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960111 | AF2-302 C | 50/50 | 3.44 MW | 3.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938821 | AE1-108 C O1 | 50/50 | 28.76 MW | 28.76 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 938822 | AE1-108 E O1 | 50/50 | 19.17 MW | 19.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941011 | AE2-092 C | 50/50 | 25.4 MW | 25.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941012 | AE2-092 E | 50/50 | 16.93 MW | 16.93 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946291 | AF1-293 C O1 | 50/50 | 39.64 MW | 39.64 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946292 | AF1-293 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 946591 | AF1-323 C | 50/50 | 9.45 MW | 9.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958131 | AF2-107 C | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958132 | AF2-107 E | 50/50 | 2.41 MW | 2.41 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961061 | AF2-397 C | 50/50 | 36.67 MW | 36.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 961062 | AF2-397 E | 50/50 | 24.45 MW | 24.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958501 | AF2-144 C | Adder | -2.72 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.92 MW | 19.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | 957912 | AF2-085 BAT | Adder | 2.2 MW | 1.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.73 MW | 0.73 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.85 MW | 14.85 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.88 MW | 8.88 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.68 MW | 7.68 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.82 MW | 0.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.67 MW | 1.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.45 MW | 0.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.17 MW | 1.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.08 MW | 0.08 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.37 MW | 1.37 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 2028T2054-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.21 MW | 0.21 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964231 | AG1-284 C O1 | 50/50 | 17.01 MW | 17.01 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 966252 | AG1-494 E | Adder | 2.48 MW | 2.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941011 | AE2-092 C | 50/50 | 25.3 MW | 25.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941012 | AE2-092 E | 50/50 | 16.87 MW | 16.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946291 | AF1-293 C O1 | 50/50 | 39.56 MW | 39.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946292 | AF1-293 E O1 | 50/50 | 7.12 MW | 7.12 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.59 MW | 14.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.39 MW | 8.39 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.36 MW | 7.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.6 MW | 1.6 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.43 MW | 0.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.11 MW | 1.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.03 MW | 5.03 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.32 MW | 1.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P4-2: 233T2028-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 3SHERWOD-3RED HIL 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SHERWOD-3RED HIL 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 964231 | AG1-284 C O1 | 50/50 | 42.0 MW | 42.0 MW |
| 3SHERWOD-3RED HIL 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 964232 | AG1-284 E O1 | 50/50 | 28.0 MW | 28.0 MW |
| 3SHERWOD-3RED HIL 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 941011 | AE2-092 C | 50/50 | 82.8 MW | 82.8 MW |
| 3SHERWOD-3RED HIL 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 941012 | AE2-092 E | 50/50 | 55.2 MW | 55.2 MW |
| 3SHERWOD-3RED HIL 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 946291 | AF1-293 C O1 | 50/50 | 108.4 MW | 108.4 MW |
| 3SHERWOD-3RED HIL 115.0 kV Ckt 1 line l/o DVP_P4-2: YT1030 | 946292 | AF1-293 E O1 | 50/50 | 19.5 MW | 19.5 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.55 MW | 10.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.03 MW | 6.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.33 MW | 11.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.2 MW | 5.2 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.06 MW | 20.06 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.81 MW | 4.81 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.1 MW | 7.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.03 MW | 10.03 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.28 MW | 6.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.44 MW | 11.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.25 MW | 10.25 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.28 MW | 2.28 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.13 MW | 19.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.85 MW | 16.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.53 MW | 29.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.65 MW | 36.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.43 MW | 24.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314333 | 6POWHATN | 50/50 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | 50/50 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | 50/50 | 4.99 MW | 4.99 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | 50/50 | 4.55 MW | 4.55 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938561 | AE1-075 C | 50/50 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | 50/50 | 4.33 MW | 4.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.19 MW | 1.86 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.8 MW | 0.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.09 MW | 5.09 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | 50/50 | 39.25 MW | 39.25 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | 50/50 | 29.54 MW | 29.54 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| AC2-165 TAP-6POWHATN 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 0.85 MW | 0.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 4.69 MW | 4.69 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | Adder | 6.79 MW | 5.78 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | Adder | 4.53 MW | 3.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | Adder | 1.13 MW | 0.96 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | Adder | 3.4 MW | 2.89 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | Adder | 2.26 MW | 1.93 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 2.33 MW | 2.33 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 0.85 MW | 0.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 20.37 MW | 20.37 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 4.85 MW | 4.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | Adder | 0.51 MW | 0.43 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | Adder | 3.4 MW | 2.89 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933502 | AC2-165 E | Adder | 2.56 MW | 2.17 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 5.3 MW | 5.3 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | 0.52 MW | 0.45 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958502 | AF2-144 E | Adder | 0.35 MW | 0.3 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 923862 | AB2-026 E | Adder | 0.32 MW | 0.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938562 | AE1-075 E | Adder | 0.3 MW | 0.26 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966673 | AG1-537 BAT | Adder | 5.88 MW | 5.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.13 MW | 0.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.86 MW | 0.86 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 0.85 MW | 0.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 7.04 MW | 7.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 4.69 MW | 4.69 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 2.03 MW | 2.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | Adder | 6.79 MW | 5.78 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | Adder | 4.53 MW | 3.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | Adder | 1.13 MW | 0.96 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | Adder | 3.4 MW | 2.89 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | Adder | 2.26 MW | 1.93 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 2.33 MW | 2.33 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 1.27 MW | 1.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 0.85 MW | 0.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 10.7 MW | 10.7 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 7.13 MW | 7.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 30.55 MW | 30.55 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 20.37 MW | 20.37 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 26.94 MW | 26.94 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 4.85 MW | 4.85 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 3.49 MW | 3.49 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | Adder | 0.51 MW | 0.43 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | Adder | 3.4 MW | 2.89 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933502 | AC2-165 E | Adder | 2.56 MW | 2.17 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 7.95 MW | 7.95 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 5.3 MW | 5.3 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | 0.52 MW | 0.45 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958502 | AF2-144 E | Adder | 0.35 MW | 0.3 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 923862 | AB2-026 E | Adder | 0.32 MW | 0.27 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938562 | AE1-075 E | Adder | 0.3 MW | 0.26 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966673 | AG1-537 BAT | Adder | 5.88 MW | 5.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.38 MW | 0.38 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 6.2 MW | 6.2 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.04 MW | 1.04 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.57 MW | 0.57 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.13 MW | 0.13 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.32 MW | 0.32 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.01 MW | 0.01 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.07 MW | 0.07 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.86 MW | 0.86 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.0 MW | 0.0 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.25 MW | 0.25 MW |
| AE2-092 TAP-3SHERWOD 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.0 MW | 0.0 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
| Details for 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961791 | AG1-021 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961792 | AG1-021 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961801 | AG1-022 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961802 | AG1-022 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961891 | AG1-030 C | 50/50 | 15.84 MW | 15.84 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961892 | AG1-030 E | 50/50 | 10.56 MW | 10.56 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962491 | AG1-098 C O1 | 50/50 | 9.06 MW | 9.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962492 | AG1-098 E O1 | 50/50 | 6.04 MW | 6.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963171 | AG1-166 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963172 | AG1-166 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963181 | AG1-167 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963182 | AG1-167 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963191 | AG1-168 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963192 | AG1-168 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963201 | AG1-169 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963202 | AG1-169 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963211 | AG1-170 C | 50/50 | 2.3 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963212 | AG1-170 E | 50/50 | 1.53 MW | 1.53 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963321 | AG1-181 C O1 | 50/50 | 14.07 MW | 14.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 963361 | AG1-185 O1 | 50/50 | 6.8 MW | 6.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964111 | AG1-272 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964112 | AG1-272 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964121 | AG1-273 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964122 | AG1-273 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964131 | AG1-274 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964132 | AG1-274 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964231 | AG1-284 C O1 | 50/50 | 17.0 MW | 17.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964232 | AG1-284 E O1 | 50/50 | 11.34 MW | 11.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964241 | AG1-285 C O1 | 50/50 | 8.15 MW | 8.15 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 964242 | AG1-285 E O1 | 50/50 | 5.43 MW | 5.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965191 | AG1-384 C | 50/50 | 2.26 MW | 2.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965192 | AG1-384 E | 50/50 | 0.67 MW | 0.67 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965581 | AG1-426 | 50/50 | 5.44 MW | 5.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965591 | AG1-427 C | 50/50 | 7.8 MW | 7.8 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965592 | AG1-427 E | 50/50 | 5.21 MW | 5.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965641 | AG1-432 C O1 | 50/50 | 30.11 MW | 30.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965642 | AG1-432 E O1 | 50/50 | 20.07 MW | 20.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 965831 | AG1-451 | 50/50 | 5.02 MW | 5.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966251 | AG1-494 C | Adder | 1.65 MW | 1.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 966252 | AG1-494 E | Adder | 2.47 MW | 2.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 313853 | 3PONTONDP | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314429 | 3JTRSVLE | 50/50 | 0.52 MW | 0.52 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314713 | 3PAMPLIN | 50/50 | 2.02 MW | 2.02 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934625 | AD1-088 C | 50/50 | 10.24 MW | 10.24 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 934626 | AD1-088 E | 50/50 | 4.82 MW | 4.82 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936265 | AD2-033 C | 50/50 | 10.66 MW | 10.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 936266 | AD2-033 E | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942461 | AE2-259 C O1 | 50/50 | 15.06 MW | 15.06 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 942462 | AE2-259 E O1 | 50/50 | 10.04 MW | 10.04 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946592 | AF1-323 E | 50/50 | 6.29 MW | 6.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958801 | AF2-171 C | 50/50 | 17.17 MW | 17.17 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958802 | AF2-171 E | 50/50 | 11.45 MW | 11.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959311 | AF2-222 C | 50/50 | 15.32 MW | 15.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 959312 | AF2-222 E | 50/50 | 10.26 MW | 10.26 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960111 | AF2-302 C | 50/50 | 3.43 MW | 3.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 960112 | AF2-302 E | 50/50 | 2.29 MW | 2.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924162 | AB2-060 E OP | Adder | 2.51 MW | 2.13 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924301 | AB2-077 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924302 | AB2-077 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924311 | AB2-078 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924312 | AB2-078 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924321 | AB2-079 C O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924322 | AB2-079 E O1 | Adder | 0.73 MW | 0.62 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925611 | AC1-036 C | 50/50 | 0.21 MW | 0.21 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 925612 | AC1-036 E | 50/50 | 1.36 MW | 1.36 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938371 | AE1-056 C | 50/50 | 8.05 MW | 8.05 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938372 | AE1-056 E | 50/50 | 4.4 MW | 4.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938821 | AE1-108 C O1 | 50/50 | 28.71 MW | 28.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 938822 | AE1-108 E O1 | 50/50 | 19.14 MW | 19.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941011 | AE2-092 C | 50/50 | 25.29 MW | 25.29 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941012 | AE2-092 E | 50/50 | 16.86 MW | 16.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941791 | AE2-182 C | 50/50 | 1.66 MW | 1.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 941792 | AE2-182 E | 50/50 | 0.77 MW | 0.77 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946291 | AF1-293 C O1 | 50/50 | 39.55 MW | 39.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946292 | AF1-293 E O1 | 50/50 | 7.11 MW | 7.11 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946301 | AF1-294 C | 50/50 | 4.71 MW | 4.71 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946302 | AF1-294 E | 50/50 | 3.14 MW | 3.14 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 946591 | AF1-323 C | 50/50 | 9.43 MW | 9.43 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958131 | AF2-107 C | 50/50 | 4.38 MW | 4.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958132 | AF2-107 E | 50/50 | 2.4 MW | 2.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958211 | AF2-115 C | 50/50 | 2.87 MW | 2.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958212 | AF2-115 E | 50/50 | 1.92 MW | 1.92 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924032 | AB2-045 E | 50/50 | 2.38 MW | 2.38 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 933501 | AC2-165 C | Adder | -17.75 MW | -15.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961061 | AF2-397 C | 50/50 | 36.66 MW | 36.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 961062 | AF2-397 E | 50/50 | 24.44 MW | 24.44 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 314677 | 6BUCKING | 50/50 | 0.87 MW | 0.87 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958501 | AF2-144 C | Adder | -2.71 MW | -2.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315191 | 1BEARGRDN G1 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315192 | 1BEARGRDN G2 | 50/50 | 15.4 MW | 15.4 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 315193 | 1BEARGRDN S1 | 50/50 | 19.91 MW | 19.91 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962561 | AG1-105 C O1 | Adder | 4.06 MW | 3.45 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 962562 | AG1-105 E O1 | Adder | 2.71 MW | 2.3 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 924022 | AB2-043 E O1 | Adder | 1.59 MW | 1.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 958503 | AF2-144 BAT | 50/50 | 2.66 MW | 2.66 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | 957912 | AF2-085 BAT | Adder | 2.18 MW | 1.86 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.34 MW | 0.34 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.55 MW | 14.55 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.32 MW | 8.32 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.31 MW | 7.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.09 MW | 1.09 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.79 MW | 0.79 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.59 MW | 1.59 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.42 MW | 0.42 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.1 MW | 1.1 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.35 MW | 0.35 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 5.0 MW | 5.0 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.31 MW | 1.31 MW |
| 6BREMO-6CARTERV 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 5-2028-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.2 MW | 0.2 MW |
Light Load Analysis
At this time light load analysis not required for this project.
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n8148 | Rebuild 6.44 miles of 115 kV Line 39 from Sherwood to Red Hills with 2-636 ACSR. | $16,100,000 | |
| n6378 | Rebuild 6.42 miles of 115 kV Line 91 from AE2-092 Tap to Sherwood with 2-636 ACSR. | $16,050,000 | |
| n7785 | Rebuild 9.46 miles of 230 kV Line 2027 from Bremo to Cartersville with 2-795 ACSR 150 C. Replace breaker lead at Bremo terminal. | $23,650,000 | |
| n8256 | Rebuild 230 kV Line #2027 from Carterville to AC2-165 Tap. | $19,175,000 | |
| n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
| n7580 | Rebuild 8.72 miles of 230 kV Line 2054 from Charlottesville to Profit D.P. with 2-636 ACSR 150 C | $21,800,000 | |
| n8453 | Rebuild 5 miles of 230 kV Line 2028 from Fork Union to AF2-397 Tap with 2-636 ACSR. | $7,500,000 | |
| n7796 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Midlothian with 2-795 ACSR 150 C. | $17,725,000 | |
| n7797 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Powhatan with 2-795 ACSR 150 C | $17,725,000 | |
| n8156 | Rebuild 12.1 miles of 230 kV Line 2028 from Mount Eagle to AF2-397 Tap with 2-636 ACSR. | $18,150,000 | |
| n8243 | Rebuild 4.01 miles of 230 kV Line 2027 from Powhatan to AC2-165 Tap with 2-795 ACSR (26/7) 150 C | $10,025,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-284 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.