AG1-272 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:59
Twitty's Creek 115 kV
15.42 MW Capacity / 20.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-272 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the Dominion zone — Charlotte County, Virginia. The installed facilities will have a total capability of 20.0 MW with 15.42 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-272 |
| Project Name | Twitty's Creek 115 kV |
| Developer Name | CV-Tollhouse LLC |
| State | Virginia |
| County | Charlotte |
| Transmission Owner | Dominion |
| MFO | 20.0 MW |
| MWE | 20.0 MW |
| MWC | 15.42 MW |
| Fuel Type | Solar; Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-272 "Twitty's Creek 115 kV" will interconnect with the Dominion transmission system. The primary POI is a direct connect to the Twitty's Creek 115 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 20.0 MW (Capacity 15.42 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 192.22 % | 199.71 % | 205.86 | B | 411.12 | 15.42 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 192.22 % | 199.71 % | 205.86 | B | 411.13 | 15.42 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 235-A
CONTINGENCY 'DVP_P1-2: LN 235-A' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Single | AC | 184.82 % | 187.67 % | 182.64 | B | 342.76 | 5.3 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 138.0 % | 141.93 % | 182.64 | B | 259.22 | 7.17 | |
| DVP |
3WILLIS-3FARMVIL 115.0 kV Ckt 1 line
314726 to 314691 ckt 1 |
Base Case | Single | AC | 110.68 % | 113.48 % | 186.12 | A | 211.21 | 5.37 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P1-2: LN 84
CONTINGENCY 'DVP_P1-2: LN 84' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Single | AC | 122.04 % | 127.6 % | 269.78 | B | 344.23 | 15.42 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 298
CONTINGENCY 'DVP_P1-2: LN 298' OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Single | AC | 111.78 % | 114.11 % | 198.06 | B | 226.0 | 4.67 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P1-2: LN 84
CONTINGENCY 'DVP_P1-2: LN 84' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Single | AC | 122.34 % | 127.93 % | 269.78 | B | 345.12 | 15.42 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
Base Case | Single | AC | 106.28 % | 108.22 % | 176.81 | A | 191.34 | 3.43 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 99.03 % | 101.95 % | 198.06 | B | 201.92 | 5.77 | |
| DVP |
3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line
314713 to 314726 ckt 1 |
DVP_P1-2: LN 1012-D
CONTINGENCY 'DVP_P1-2: LN 1012-D' OPEN BRANCH FROM BUS 964240 TO BUS 314681 CKT 1 /*AG1-285 TAP 115.0 - 3CHASCTY 115.0 END |
Single | DC | 102.07 % | 106.72 % | 331.82 | B | 354.11 | 15.42 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 99.04 % | 101.95 % | 198.06 | B | 201.92 | 5.77 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P1-2: LN 84
CONTINGENCY 'DVP_P1-2: LN 84' OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Single | AC | 122.89 % | 128.54 % | 269.78 | B | 346.78 | 15.42 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P1-2: LN 1012-B
CONTINGENCY 'DVP_P1-2: LN 1012-B' OPEN BRANCH FROM BUS 963320 TO BUS 965590 CKT 1 /*AG1-181 TAP 115.0 - AG1-427 TAP 115.0 END |
Single | AC | 99.6 % | 102.58 % | 198.06 | B | 203.16 | 5.77 | |
| DVP |
3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line
314713 to 314726 ckt 1 |
DVP_P1-2: LN 1012-C
CONTINGENCY 'DVP_P1-2: LN 1012-C' OPEN BRANCH FROM BUS 965590 TO BUS 964240 CKT 1 /*AG1-427 TAP 115.0 - AG1-285 TAP 115.0 END |
Single | DC | 102.07 % | 106.72 % | 331.82 | B | 354.12 | 15.42 | |
| DVP |
3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer
314559 to 314561 ckt 1 |
DVP_P1-2: LN 140
CONTINGENCY 'DVP_P1-2: LN 140' OPEN BRANCH FROM BUS 313720 TO BUS 314526 CKT 1 /*3NEWSOMS 115.0 - 3HANDSOM 115.0 OPEN BRANCH FROM BUS 314526 TO BUS 314534 CKT 1 /*3HANDSOM 115.0 - 3S HAMPT 115.0 OPEN BUS 314526 /*3HANDSOM 115.0 END |
Single | AC | 99.72 % | 100.17 % | 239.89 | B | 240.3 | 1.13 | |
| DVP |
6POWHATN-6JUDES F 230.0 kV Ckt 1 line
314333 to 314310 ckt 1 |
DVP_P1-2: LN 2028-C
CONTINGENCY 'DVP_P1-2: LN 2028-C' OPEN BRANCH FROM BUS 313707 TO BUS 961060 CKT 1 /*6FORK UNION 230.0 - AF2-397 TAP 230.0 END |
Single | AC | 99.94 % | 100.22 % | 800.88 | B | 802.62 | 2.26 | |
| DVP |
6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line
314310 to 314322 ckt 1 |
DVP_P1-2: LN 2028-C
CONTINGENCY 'DVP_P1-2: LN 2028-C' OPEN BRANCH FROM BUS 313707 TO BUS 961060 CKT 1 /*6FORK UNION 230.0 - AF2-397 TAP 230.0 END |
Single | AC | 99.89 % | 100.18 % | 800.88 | B | 802.29 | 2.26 | |
| DVP |
8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line
314940 to 941030 ckt 1 |
DVP_P1-2: LN 511-C
CONTINGENCY 'DVP_P1-2: LN 511-C' OPEN BRANCH FROM BUS 942930 TO BUS 314936 CKT 1 /*AE2-313 TAP 500.0 - 8RAWLINGS 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE 500.0 - 8RAWLINGS 500.0 END |
Single | AC | 100.01 % | 100.08 % | 4070.2 | B | 4073.29 | 2.36 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer
314691 to 314692 ckt 2 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 285.17 % | 290.48 % | 208.7 | C | 606.23 | 11.07 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 172.76 % | 178.49 % | 349.0 | C | 622.93 | 20.0 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 172.76 % | 178.49 % | 349.0 | C | 622.93 | 20.0 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-6: CHASE C T342
CONTINGENCY 'DVP_P4-6: CHASE C T342' OPEN BUS 313527 /*AB2-043 C 0.6 OPEN BUS 313528 /*AB2-043 COL 34.5 OPEN BUS 313529 /*3BLUE STONE 115.0 OPEN BUS 314267 /*3CHASCTY2 115.0 OPEN BUS 314518 /*3CHASC_1 115.0 OPEN BUS 314681 /*3CHASCTY 115.0 OPEN BUS 924022 /*AB2-043 E O1 0.6 END |
Breaker | DC | 216.51 % | 220.54 % | 221.4 | C | 488.27 | 8.92 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 172.76 % | 178.49 % | 349.0 | C | 622.93 | 20.0 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 172.76 % | 178.49 % | 349.0 | C | 622.93 | 20.0 | |
| DVP |
3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer
314691 to 314692 ckt 1 |
DVP_P4-2: 29822
CONTINGENCY 'DVP_P4-2: 29822' OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1 /*6BREMODIST 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 313868 TO BUS 314747 CKT 1 /*6CARTERV 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2 /*6BEARGRDN 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314326 TO BUS 315191 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G1 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315192 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN G2 18.0 OPEN BRANCH FROM BUS 314326 TO BUS 315193 CKT 1 /*6BEARGRDN 230.0 - 1BEARGRDN S1 22.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1 /*3BREMO 115.0 - 6BREMO 230.0 OPEN BUS 314326 /*6BEARGRDN 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 314747 /*6BREMO 230.0 OPEN BUS 315191 /*1BEARGRDN G1 18.0 OPEN BUS 315192 /*1BEARGRDN G2 18.0 OPEN BUS 315193 /*1BEARGRDN S1 22.0 OPEN BUS 924032 /*AB2-045 E 230.0 END |
Breaker | AC | 171.92 % | 174.42 % | 221.4 | C | 386.17 | 6.05 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 172.76 % | 178.49 % | 349.0 | C | 622.93 | 20.0 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 172.76 % | 178.49 % | 349.0 | C | 622.93 | 20.0 | |
| DVP |
AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line
964240 to 314681 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 147.34 % | 153.23 % | 349.0 | C | 534.76 | 20.0 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 130.88 % | 136.61 % | 349.0 | C | 476.76 | 20.0 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 130.88 % | 136.61 % | 349.0 | C | 476.76 | 20.0 | |
| DVP |
3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line
314679 to 963320 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 129.79 % | 135.52 % | 349.0 | C | 472.95 | 20.0 | |
| DVP |
3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line
314679 to 963320 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 129.79 % | 135.52 % | 349.0 | C | 472.95 | 20.0 | |
| DVP |
AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line
965590 to 964240 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 147.65 % | 153.57 % | 349.0 | C | 535.96 | 20.0 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-6: CAROLIN T122
CONTINGENCY 'DVP_P4-6: CAROLIN T122' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314578 CKT 1 /*3CAROLNA 115.0 - 3HORNRTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 315126 CKT 1 /*3CAROLNA 115.0 - 1ROARAP2 14.4 OPEN BRANCH FROM BUS 314559 TO BUS 315128 CKT 1 /*3CAROLNA 115.0 - 1ROARAP4 14.4 OPEN BUS 314559 /*3CAROLNA 115.0 OPEN BUS 314835 /*3CAROL_1 115.0 OPEN BUS 315126 /*1ROARAP2 14.4 OPEN BUS 315128 /*1ROARAP4 14.4 END |
Breaker | AC | 132.62 % | 134.11 % | 199.0 | B | 266.88 | 3.08 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 145.27 % | 150.01 % | 349.0 | C | 523.53 | 16.52 | |
| DVP |
3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer
314696 to 314697 ckt 2 |
DVP_P4-2: 3202
CONTINGENCY 'DVP_P4-2: 3202' OPEN BRANCH FROM BUS 313852 TO BUS 314716 CKT 1 /*3WELCOTAP 115.0 - 3REEDY C 115.0 OPEN BRANCH FROM BUS 313852 TO BUS 314718 CKT 1 /*3WELCOTAP 115.0 - 3S BOSTN 115.0 OPEN BRANCH FROM BUS 313852 TO BUS 314724 CKT 1 /*3WELCOTAP 115.0 - 3WELCO 115.0 OPEN BRANCH FROM BUS 314696 TO BUS 314697 CKT 1 /*3SEDGE HILL 115.0 - 6SEDGE HILL 230.0 OPEN BRANCH FROM BUS 314696 TO BUS 314717 CKT 1 /*3SEDGE HILL 115.0 - 3SINAI 115.0 OPEN BRANCH FROM BUS 314717 TO BUS 314718 CKT 1 /*3SINAI 115.0 - 3S BOSTN 115.0 OPEN BUS 313852 /*3WELCOTAP 115.0 OPEN BUS 314717 /*3SINAI 115.0 OPEN BUS 314718 /*3S BOSTN 115.0 OPEN BUS 314724 /*3WELCO 115.0 END |
Breaker | AC | 137.65 % | 138.81 % | 279.1 | C | 387.43 | 3.26 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 13002
CONTINGENCY 'DVP_P4-2: 13002' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 OPEN BRANCH FROM BUS 314595 TO BUS 314600 CKT 1 /*3PL HILL 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314600 TO BUS 314615 CKT 1 /*3PLHITP 115.0 - 3SKIPPERS 115.0 OPEN BUS 314595 /*3PL HILL 115.0 OPEN BUS 314600 /*3PLHITP 115.0 END |
Breaker | AC | 114.2 % | 115.34 % | 199.0 | B | 229.53 | 2.69 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P4-2: 102802
CONTINGENCY 'DVP_P4-2: 102802' OPEN BRANCH FROM BUS 313722 TO BUS 314559 CKT 1 /*3OCCONEECHEE 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 313723 TO BUS 314559 CKT 1 /*3PECAN 115.0 - 3CAROLNA 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314561 CKT 1 /*3CAROLNA 115.0 - 6CAROLNA 230.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314600 CKT 1 /*3CAROLNA 115.0 - 3PLHITP 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314835 CKT 1 /*3CAROLNA 115.0 - 3CAROL_1 115.0 END |
Breaker | AC | 114.2 % | 115.34 % | 199.0 | B | 229.53 | 2.69 | |
| DVP |
AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line
963320 to 965590 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 149.2 % | 155.33 % | 349.0 | C | 542.11 | 20.0 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 113.6 % | 118.33 % | 349.0 | C | 412.98 | 16.52 | |
| DVP |
3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line
314679 to 963320 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 112.51 % | 117.24 % | 349.0 | C | 409.18 | 16.52 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 15832
CONTINGENCY 'DVP_P4-2: 15832' OPEN BRANCH FROM BUS 313755 TO BUS 314701 CKT 1 /*3FLAT CREEK 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 313755 TO BUS 314707 CKT 1 /*3FLAT CREEK 115.0 - 3MORAN 115.0 OPEN BRANCH FROM BUS 314519 TO BUS 314701 CKT 1 /*3LONEPINE_1 115.0 - 3LONEPN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314707 CKT 1 /*3FARMVIL 115.0 - 3MORAN 115.0 OPEN BUS 313755 /*3FLAT CREEK 115.0 OPEN BUS 314519 /*3LONEPINE_1 115.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 314707 /*3MORAN 115.0 END |
Breaker | DC | 103.27 % | 104.69 % | 406.0 | C | 425.05 | 5.93 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-5: FARMVIL L432
CONTINGENCY 'DVP_P4-5: FARMVIL L432' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314691 /*3FARMVIL 115.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 101.33 % | 102.73 % | 406.0 | C | 417.1 | 5.91 | |
| DVP |
AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line
316115 to 314696 ckt 1 |
DVP_P4-2: 235T298
CONTINGENCY 'DVP_P4-2: 235T298' OPEN BRANCH FROM BUS 313802 TO BUS 314268 CKT 1 /*6PRINCE EDW 230.0 - 6BRIERY 230.0 OPEN BRANCH FROM BUS 313802 TO BUS 314692 CKT 1 /*6PRINCE EDW 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314268 TO BUS 934620 CKT 1 /*6BRIERY 230.0 - AD1-088 TAP 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314692 CKT 1 /*6BUCKING 230.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314677 TO BUS 314747 CKT 1 /*6BUCKING 230.0 - 6BREMO 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 1 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 314691 TO BUS 314692 CKT 2 /*3FARMVIL 115.0 - 6FARMVIL 230.0 OPEN BRANCH FROM BUS 962490 TO BUS 934620 CKT 1 /*AG1-098 TAP 230.0 - AD1-088 TAP 230.0 OPEN BUS 313802 /*6PRINCE EDW 230.0 OPEN BUS 314268 /*6BRIERY 230.0 OPEN BUS 314677 /*6BUCKING 230.0 OPEN BUS 924032 /*AB2-045 E 230.0 OPEN BUS 934620 /*AD1-088 TAP 230.0 OPEN BUS 934621 /*AD1-088 MAIN 230.0 OPEN BUS 934622 /*AD1-088 COL1 34.5 OPEN BUS 934623 /*AD1-088 TER 13.8 OPEN BUS 934624 /*AD1-088 COL2 34.5 OPEN BUS 934625 /*AD1-088 C 0.7 OPEN BUS 934626 /*AD1-088 E 0.7 END |
Breaker | DC | 99.93 % | 101.33 % | 406.0 | C | 411.41 | 5.91 | |
| DVP |
3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line
314722 to 314679 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 104.3 % | 110.16 % | 349.0 | C | 384.44 | 20.0 | |
| DVP |
3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line
314679 to 963320 ckt 1 |
DVP_P4-2: 8442
CONTINGENCY 'DVP_P4-2: 8442' CHANGE BUS 314713 LOAD BY -100 PERCENT /*3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314521 TO BUS 314713 CKT 1 /*3PAMPL_1 115.0 - 3PAMPLIN 115.0 OPEN BRANCH FROM BUS 314691 TO BUS 314726 CKT 1 /*3FARMVIL 115.0 - 3WILLIS 115.0 OPEN BRANCH FROM BUS 314713 TO BUS 314726 CKT 1 /*3PAMPLIN 115.0 - 3WILLIS 115.0 OPEN BUS 314521 /*3PAMPL_1 115.0 OPEN BUS 314726 /*3WILLIS 115.0 END |
Breaker | AC | 103.25 % | 109.12 % | 349.0 | C | 380.82 | 20.0 | |
| CPLE/DVP |
3KERR-3GW KING TAP 115.0 kV Ckt 1 line
314702 to 304102 ckt 1 |
DVP_P7-1: LN 22-90
CONTINGENCY 'DVP_P7-1: LN 22-90' OPEN BRANCH FROM BUS 314265 TO BUS 314584 CKT 1 /*3FIVEFORKSDP 115.0 - 3LITTLTN 115.0 OPEN BRANCH FROM BUS 314265 TO BUS 314673 CKT 1 /*3FIVEFORKSDP 115.0 - 3PALMERSPRNG 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314571 CKT 1 /*3CAROLNA 115.0 - 3EATON F 115.0 OPEN BRANCH FROM BUS 314559 TO BUS 314585 CKT 1 /*3CAROLNA 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314571 TO BUS 316125 CKT 1 /*3EATON F 115.0 - AC1-054 TAP 115.0 OPEN BRANCH FROM BUS 314584 TO BUS 314585 CKT 1 /*3LITTLTN 115.0 - 3L GASTN 115.0 OPEN BRANCH FROM BUS 314702 TO BUS 316125 CKT 1 /*3KERR 115.0 - AC1-054 TAP 115.0 OPEN BUS 314265 /*3FIVEFORKSDP 115.0 OPEN BUS 314571 /*3EATON F 115.0 OPEN BUS 314584 /*3LITTLTN 115.0 OPEN BUS 314585 /*3L GASTN 115.0 OPEN BUS 316125 /*AC1-054 TAP 115.0 OPEN BUS 316126 /*AC1-054 MAIN 115.0 OPEN BUS 316127 /*AC1-054 COL2 22.9 OPEN BUS 316128 /*AC1-054 COL1 22.9 OPEN BUS 316129 /*AC1-054 C 0.4 OPEN BUS 925785 /*AC1-054 E 0.4 END |
Tower | AC | 130.4 % | 131.87 % | 199.0 | B | 262.43 | 3.04 | |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 120.0 MW | 120.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 20.0 MW | 20.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965641 | AG1-432 C O1 | 80/20 | 120.0 MW | 120.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965831 | AG1-451 | 80/20 | 20.0 MW | 20.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 942461 | AE2-259 C O1 | 80/20 | 60.0 MW | 60.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961791 | AG1-021 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 961891 | AG1-030 C | 80/20 | 37.77 MW | 37.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963171 | AG1-166 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963181 | AG1-167 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963191 | AG1-168 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963201 | AG1-169 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963211 | AG1-170 C | 80/20 | 5.52 MW | 5.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963301 | AG1-179 C | 80/20 | 3.87 MW | 3.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963311 | AG1-180 | 80/20 | 1.89 MW | 1.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963321 | AG1-181 C O1 | 80/20 | 32.77 MW | 32.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 963361 | AG1-185 O1 | 80/20 | 15.86 MW | 15.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964111 | AG1-272 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964121 | AG1-273 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964131 | AG1-274 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964241 | AG1-285 C O1 | 80/20 | 18.39 MW | 18.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 964791 | AG1-342 C | 80/20 | 3.1 MW | 3.1 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965191 | AG1-384 C | 80/20 | 5.3 MW | 5.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965591 | AG1-427 C | 80/20 | 17.61 MW | 17.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965601 | AG1-428 C O2 | 80/20 | 3.23 MW | 3.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965641 | AG1-432 C O1 | 80/20 | 73.68 MW | 73.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965721 | AG1-440 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965731 | AG1-441 C | 80/20 | 5.18 MW | 5.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965771 | AG1-445 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965781 | AG1-446 | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 965831 | AG1-451 | 80/20 | 12.28 MW | 12.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 966621 | AG1-532 C | 80/20 | 0.47 MW | 0.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313506 | AB1-173 C OP | 80/20 | 2.2 MW | 2.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314429 | 3JTRSVLE | 80/20 | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314572 | 3EMPORIA | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 314704 | 3LAWRENC | 80/20 | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315158 | 1KERR 1 | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315159 | 1KERR 2 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315160 | 1KERR 3 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315161 | 1KERR 4 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315162 | 1KERR 5 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 927261 | AC1-222 C | 80/20 | 1.32 MW | 1.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 934311 | AD1-055 C | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 936265 | AD2-033 C | 80/20 | 24.79 MW | 24.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 942461 | AE2-259 C O1 | 80/20 | 36.84 MW | 36.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 943901 | AF1-058 C | 80/20 | 0.75 MW | 0.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958801 | AF2-171 C | 80/20 | 41.22 MW | 41.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 959311 | AF2-222 C | 80/20 | 36.05 MW | 36.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960061 | AF2-297 C | 80/20 | 2.99 MW | 2.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 960081 | AF2-299 C | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315163 | 1KERR 6 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315164 | 1KERR 7 | 80/20 | 0.92 MW | 0.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 315266 | 1PLYWOOD A | 80/20 | 0.63 MW | 0.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316118 | AC1-105 C | 80/20 | 3.19 MW | 3.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316129 | AC1-054 C | 80/20 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316131 | AB2-060 C | 80/20 | 2.02 MW | 2.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 923991 | AB2-040 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924301 | AB2-077 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924311 | AB2-078 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 924321 | AB2-079 C O1 | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 925611 | AC1-036 C | 80/20 | 0.5 MW | 0.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 938371 | AE1-056 C | 80/20 | 19.46 MW | 19.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 939181 | AE1-148 C | 80/20 | 7.77 MW | 7.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 940661 | AE2-053 O1 | 80/20 | 2.88 MW | 2.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946281 | AF1-292 C | 80/20 | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 946301 | AF1-294 C | 80/20 | 11.32 MW | 11.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 958211 | AF2-115 C | 80/20 | 6.9 MW | 6.9 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 316087 | AB2-174 C | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 962561 | AG1-105 C O1 | 80/20 | 7.36 MW | 7.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | 313527 | AB2-043 C | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 13.97 MW | 13.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 3.32 MW | 3.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 4.07 MW | 4.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.25 MW | 1.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.0 MW | 1.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.8 MW | 0.8 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 235-A | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.08 MW | 0.08 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 961791 | AG1-021 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 961891 | AG1-030 C | 80/20 | 24.36 MW | 24.36 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963171 | AG1-166 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963181 | AG1-167 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963191 | AG1-168 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963201 | AG1-169 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963211 | AG1-170 C | 80/20 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963301 | AG1-179 C | 80/20 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963311 | AG1-180 | 80/20 | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 46.99 MW | 46.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 22.74 MW | 22.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 34.86 MW | 34.86 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 964791 | AG1-342 C | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 7.17 MW | 7.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 33.05 MW | 33.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965601 | AG1-428 C O2 | 80/20 | 1.42 MW | 1.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 55.78 MW | 55.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965721 | AG1-440 C | 80/20 | 2.25 MW | 2.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965731 | AG1-441 C | 80/20 | 2.25 MW | 2.25 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965771 | AG1-445 | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965781 | AG1-446 | 80/20 | 1.3 MW | 1.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 9.3 MW | 9.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 314429 | 3JTRSVLE | 80/20 | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315158 | 1KERR 1 | 80/20 | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315159 | 1KERR 2 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315160 | 1KERR 3 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315161 | 1KERR 4 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315162 | 1KERR 5 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 936265 | AD2-033 C | 80/20 | 14.45 MW | 14.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 27.89 MW | 27.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 41.84 MW | 41.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 46.48 MW | 46.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315163 | 1KERR 6 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 315164 | 1KERR 7 | 80/20 | 0.4 MW | 0.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 316131 | AB2-060 C | 80/20 | 0.94 MW | 0.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924301 | AB2-077 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924311 | AB2-078 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 924321 | AB2-079 C O1 | 80/20 | 1.07 MW | 1.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 0.68 MW | 0.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 18.04 MW | 18.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 939181 | AE1-148 C | 80/20 | 3.42 MW | 3.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 940661 | AE2-053 O1 | 80/20 | 1.27 MW | 1.27 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 946301 | AF1-294 C | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 958211 | AF2-115 C | 80/20 | 4.57 MW | 4.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 962561 | AG1-105 C O1 | 80/20 | 3.14 MW | 3.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.37 MW | 0.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963301 | AG1-179 C | 80/20 | 1.88 MW | 1.88 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963311 | AG1-180 | 80/20 | 0.92 MW | 0.92 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 31.57 MW | 31.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 15.27 MW | 15.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964111 | AG1-272 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964121 | AG1-273 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964131 | AG1-274 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 12.75 MW | 12.75 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.43 MW | 1.43 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965191 | AG1-384 C | 80/20 | 5.37 MW | 5.37 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965591 | AG1-427 C | 80/20 | 12.41 MW | 12.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 1.57 MW | 1.57 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 100.11 MW | 100.11 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965721 | AG1-440 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965731 | AG1-441 C | 80/20 | 2.49 MW | 2.49 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965771 | AG1-445 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965781 | AG1-446 | 80/20 | 1.44 MW | 1.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 965831 | AG1-451 | 80/20 | 16.68 MW | 16.68 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.16 MW | 0.16 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 936265 | AD2-033 C | 80/20 | 4.15 MW | 4.15 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 50.05 MW | 50.05 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 958801 | AF2-171 C | 80/20 | 49.79 MW | 49.79 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 959311 | AF2-222 C | 80/20 | 37.78 MW | 37.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.44 MW | 0.44 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.19 MW | 1.19 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.51 MW | 0.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 938371 | AE1-056 C | 80/20 | 24.51 MW | 24.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 939181 | AE1-148 C | 80/20 | 3.78 MW | 3.78 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.4 MW | 1.4 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 3.46 MW | 3.46 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.07 MW | 0.07 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 4.51 MW | 4.51 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.2 MW | 1.2 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.38 MW | 1.38 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.41 MW | 0.41 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.33 MW | 0.33 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.02 MW | 0.02 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.06 MW | 0.06 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.18 MW | 0.18 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.04 MW | 0.04 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.27 MW | 0.27 MW |
| 3WILLIS-3FARMVIL 115.0 kV Ckt 1 line l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.03 MW | 0.03 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 961791 | AG1-021 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 961891 | AG1-030 C | 80/20 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963171 | AG1-166 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963181 | AG1-167 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963191 | AG1-168 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963201 | AG1-169 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963211 | AG1-170 C | 80/20 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963301 | AG1-179 C | 80/20 | 3.09 MW | 3.09 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963311 | AG1-180 | 80/20 | 1.51 MW | 1.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963321 | AG1-181 C O1 | 80/20 | 28.69 MW | 28.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 963361 | AG1-185 O1 | 80/20 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964111 | AG1-272 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964121 | AG1-273 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964131 | AG1-274 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964241 | AG1-285 C O1 | 80/20 | 15.69 MW | 15.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 964791 | AG1-342 C | 80/20 | 2.21 MW | 2.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965191 | AG1-384 C | 80/20 | 4.67 MW | 4.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965591 | AG1-427 C | 80/20 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965601 | AG1-428 C O2 | 80/20 | 2.58 MW | 2.58 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965641 | AG1-432 C O1 | 80/20 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965721 | AG1-440 C | 80/20 | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965731 | AG1-441 C | 80/20 | 4.05 MW | 4.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965771 | AG1-445 | 80/20 | 2.34 MW | 2.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965781 | AG1-446 | 80/20 | 2.34 MW | 2.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 965831 | AG1-451 | 80/20 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 314429 | 3JTRSVLE | 80/20 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 314704 | 3LAWRENC | 80/20 | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315158 | 1KERR 1 | 80/20 | 0.26 MW | 0.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315159 | 1KERR 2 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315160 | 1KERR 3 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315161 | 1KERR 4 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315162 | 1KERR 5 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 936265 | AD2-033 C | 80/20 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 942461 | AE2-259 C O1 | 80/20 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 958801 | AF2-171 C | 80/20 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 959311 | AF2-222 C | 80/20 | 31.82 MW | 31.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315163 | 1KERR 6 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 315164 | 1KERR 7 | 80/20 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316118 | AC1-105 C | 80/20 | 1.97 MW | 1.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316129 | AC1-054 C | 80/20 | 3.16 MW | 3.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 316131 | AB2-060 C | 80/20 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924301 | AB2-077 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924311 | AB2-078 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 924321 | AB2-079 C O1 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 925611 | AC1-036 C | 80/20 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 938371 | AE1-056 C | 80/20 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 939181 | AE1-148 C | 80/20 | 6.24 MW | 6.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 940661 | AE2-053 O1 | 80/20 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 946301 | AF1-294 C | 80/20 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 958211 | AF2-115 C | 80/20 | 6.19 MW | 6.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 962561 | AG1-105 C O1 | 80/20 | 5.48 MW | 5.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | 313527 | AB2-043 C | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.01 MW | 1.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 298 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 961791 | AG1-021 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 961891 | AG1-030 C | 80/20 | 24.59 MW | 24.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963171 | AG1-166 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963181 | AG1-167 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963191 | AG1-168 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963201 | AG1-169 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963211 | AG1-170 C | 80/20 | 3.6 MW | 3.6 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963301 | AG1-179 C | 80/20 | 2.4 MW | 2.4 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963311 | AG1-180 | 80/20 | 1.17 MW | 1.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963321 | AG1-181 C O1 | 80/20 | 21.16 MW | 21.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 963361 | AG1-185 O1 | 80/20 | 10.24 MW | 10.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964111 | AG1-272 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964121 | AG1-273 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964131 | AG1-274 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964241 | AG1-285 C O1 | 80/20 | 11.73 MW | 11.73 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 964791 | AG1-342 C | 80/20 | 1.83 MW | 1.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965191 | AG1-384 C | 80/20 | 3.43 MW | 3.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965591 | AG1-427 C | 80/20 | 11.24 MW | 11.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965601 | AG1-428 C O2 | 80/20 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965641 | AG1-432 C O1 | 80/20 | 48.39 MW | 48.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965721 | AG1-440 C | 80/20 | 3.18 MW | 3.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965731 | AG1-441 C | 80/20 | 3.18 MW | 3.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965771 | AG1-445 | 80/20 | 1.84 MW | 1.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965781 | AG1-446 | 80/20 | 1.84 MW | 1.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 965831 | AG1-451 | 80/20 | 8.06 MW | 8.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 314429 | 3JTRSVLE | 80/20 | 0.82 MW | 0.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 314704 | 3LAWRENC | 80/20 | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315158 | 1KERR 1 | 80/20 | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315159 | 1KERR 2 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315160 | 1KERR 3 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315161 | 1KERR 4 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315162 | 1KERR 5 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 936265 | AD2-033 C | 80/20 | 15.99 MW | 15.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 942461 | AE2-259 C O1 | 80/20 | 24.2 MW | 24.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 958801 | AF2-171 C | 80/20 | 26.89 MW | 26.89 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 959311 | AF2-222 C | 80/20 | 23.37 MW | 23.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315163 | 1KERR 6 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 315164 | 1KERR 7 | 80/20 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316118 | AC1-105 C | 80/20 | 1.78 MW | 1.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316129 | AC1-054 C | 80/20 | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 316131 | AB2-060 C | 80/20 | 1.28 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924301 | AB2-077 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924311 | AB2-078 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 924321 | AB2-079 C O1 | 80/20 | 1.52 MW | 1.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 925611 | AC1-036 C | 80/20 | 0.33 MW | 0.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 938371 | AE1-056 C | 80/20 | 12.73 MW | 12.73 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 939181 | AE1-148 C | 80/20 | 4.82 MW | 4.82 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 940661 | AE2-053 O1 | 80/20 | 1.79 MW | 1.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 946301 | AF1-294 C | 80/20 | 7.39 MW | 7.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 958211 | AF2-115 C | 80/20 | 4.5 MW | 4.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 962561 | AG1-105 C O1 | 80/20 | 4.42 MW | 4.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | 313527 | AB2-043 C | 80/20 | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.08 MW | 0.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 5.74 MW | 5.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.5 MW | 1.5 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 1.75 MW | 1.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.52 MW | 0.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.42 MW | 0.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.23 MW | 0.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.34 MW | 0.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o Base Case | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.04 MW | 0.04 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 961791 | AG1-021 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 961891 | AG1-030 C | 80/20 | 19.62 MW | 19.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963171 | AG1-166 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963181 | AG1-167 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963191 | AG1-168 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963201 | AG1-169 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963211 | AG1-170 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 37.85 MW | 37.85 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 18.31 MW | 18.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 28.08 MW | 28.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 26.62 MW | 26.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965641 | AG1-432 C O1 | 80/20 | 44.93 MW | 44.93 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 965831 | AG1-451 | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 314429 | 3JTRSVLE | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 936265 | AD2-033 C | 80/20 | 11.64 MW | 11.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 942461 | AE2-259 C O1 | 80/20 | 22.46 MW | 22.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 33.7 MW | 33.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 37.44 MW | 37.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 316131 | AB2-060 C | 80/20 | 0.76 MW | 0.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924301 | AB2-077 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924311 | AB2-078 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 924321 | AB2-079 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 0.55 MW | 0.55 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 14.53 MW | 14.53 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 939181 | AE1-148 C | 80/20 | 2.75 MW | 2.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 940661 | AE2-053 O1 | 80/20 | 1.02 MW | 1.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 946301 | AF1-294 C | 80/20 | 6.04 MW | 6.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 958211 | AF2-115 C | 80/20 | 3.68 MW | 3.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | 313527 | AB2-043 C | 80/20 | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.26 MW | 3.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.98 MW | 0.98 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-D | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 964241 | AG1-285 C O1 | 80/20 | 75.0 MW | 75.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-D | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 961791 | AG1-021 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 961891 | AG1-030 C | 80/20 | 19.62 MW | 19.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 963171 | AG1-166 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 963181 | AG1-167 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 963191 | AG1-168 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 963201 | AG1-169 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 963211 | AG1-170 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 37.85 MW | 37.85 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 18.31 MW | 18.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 964241 | AG1-285 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 26.62 MW | 26.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 965641 | AG1-432 C O1 | 80/20 | 44.93 MW | 44.93 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 965831 | AG1-451 | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 314429 | 3JTRSVLE | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 936265 | AD2-033 C | 80/20 | 11.64 MW | 11.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 942461 | AE2-259 C O1 | 80/20 | 22.46 MW | 22.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 33.7 MW | 33.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 37.44 MW | 37.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 316131 | AB2-060 C | 80/20 | 0.76 MW | 0.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 924301 | AB2-077 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 924311 | AB2-078 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 924321 | AB2-079 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 0.55 MW | 0.55 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 938371 | AE1-056 C | 80/20 | 14.53 MW | 14.53 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 939181 | AE1-148 C | 80/20 | 2.75 MW | 2.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 940661 | AE2-053 O1 | 80/20 | 1.02 MW | 1.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 946301 | AF1-294 C | 80/20 | 6.04 MW | 6.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 958211 | AF2-115 C | 80/20 | 3.68 MW | 3.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | 313527 | AB2-043 C | 80/20 | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.26 MW | 3.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.98 MW | 0.98 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 84 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 961791 | AG1-021 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 961891 | AG1-030 C | 80/20 | 19.62 MW | 19.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 963171 | AG1-166 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 963181 | AG1-167 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 963191 | AG1-168 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 963201 | AG1-169 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 963211 | AG1-170 C | 80/20 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 963321 | AG1-181 C O1 | 80/20 | 37.85 MW | 37.85 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 963361 | AG1-185 O1 | 80/20 | 18.31 MW | 18.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 964111 | AG1-272 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 964121 | AG1-273 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 964131 | AG1-274 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 964241 | AG1-285 C O1 | 80/20 | 5.63 MW | 5.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 965191 | AG1-384 C | 80/20 | 5.77 MW | 5.77 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 965591 | AG1-427 C | 80/20 | 5.34 MW | 5.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 965641 | AG1-432 C O1 | 80/20 | 44.93 MW | 44.93 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 965831 | AG1-451 | 80/20 | 7.49 MW | 7.49 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 314429 | 3JTRSVLE | 80/20 | 0.67 MW | 0.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 936265 | AD2-033 C | 80/20 | 11.64 MW | 11.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 942461 | AE2-259 C O1 | 80/20 | 22.46 MW | 22.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 958801 | AF2-171 C | 80/20 | 33.7 MW | 33.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 959311 | AF2-222 C | 80/20 | 37.44 MW | 37.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 316131 | AB2-060 C | 80/20 | 0.76 MW | 0.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 924301 | AB2-077 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 924311 | AB2-078 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 924321 | AB2-079 C O1 | 80/20 | 0.87 MW | 0.87 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 925611 | AC1-036 C | 80/20 | 0.55 MW | 0.55 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 938371 | AE1-056 C | 80/20 | 14.53 MW | 14.53 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 939181 | AE1-148 C | 80/20 | 2.75 MW | 2.75 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 940661 | AE2-053 O1 | 80/20 | 1.02 MW | 1.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 946301 | AF1-294 C | 80/20 | 6.04 MW | 6.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 958211 | AF2-115 C | 80/20 | 3.68 MW | 3.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | 313527 | AB2-043 C | 80/20 | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.2 MW | 0.2 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 3.26 MW | 3.26 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.83 MW | 0.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.98 MW | 0.98 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.29 MW | 0.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.13 MW | 0.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.19 MW | 0.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 1012-B | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963321 | AG1-181 C O1 | 80/20 | 101.09 MW | 101.09 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 963361 | AG1-185 O1 | 80/20 | 48.91 MW | 48.91 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964111 | AG1-272 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964121 | AG1-273 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 964131 | AG1-274 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965191 | AG1-384 C | 80/20 | 15.42 MW | 15.42 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 965591 | AG1-427 C | 80/20 | 71.1 MW | 71.1 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 958801 | AF2-171 C | 80/20 | 90.0 MW | 90.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 959311 | AF2-222 C | 80/20 | 100.0 MW | 100.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 925611 | AC1-036 C | 80/20 | 1.47 MW | 1.47 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | 938371 | AE1-056 C | 80/20 | 38.8 MW | 38.8 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3PAMPLIN-3WILLIS 115.0 kV Ckt 1 line l/o DVP_P1-2: LN 1012-C | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961791 | AG1-021 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961891 | AG1-030 C | 80/20 | 5.6 MW | 5.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961941 | AG1-037 C | 80/20 | 0.32 MW | 0.32 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962331 | AG1-082 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962341 | AG1-083 C | 80/20 | 1.29 MW | 1.29 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963171 | AG1-166 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963181 | AG1-167 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963191 | AG1-168 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963201 | AG1-169 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963211 | AG1-170 C | 80/20 | 0.68 MW | 0.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963301 | AG1-179 C | 80/20 | 2.95 MW | 2.95 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963311 | AG1-180 | 80/20 | 1.44 MW | 1.44 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963321 | AG1-181 C O1 | 80/20 | 7.68 MW | 7.68 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 963361 | AG1-185 O1 | 80/20 | 3.72 MW | 3.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964111 | AG1-272 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964121 | AG1-273 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964131 | AG1-274 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964241 | AG1-285 C O1 | 80/20 | 6.55 MW | 6.55 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964791 | AG1-342 C | 80/20 | 1.42 MW | 1.42 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 964801 | AG1-343 C | 80/20 | 9.76 MW | 9.76 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 966811 | AG1-552 C | 80/20 | 5.13 MW | 5.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965191 | AG1-384 C | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965291 | AG1-394 C | 80/20 | 3.49 MW | 3.49 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965591 | AG1-427 C | 80/20 | 6.18 MW | 6.18 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965601 | AG1-428 C O2 | 80/20 | 2.46 MW | 2.46 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965721 | AG1-440 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965731 | AG1-441 C | 80/20 | 8.72 MW | 8.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965771 | AG1-445 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 965781 | AG1-446 | 80/20 | 5.04 MW | 5.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 966621 | AG1-532 C | 80/20 | 0.69 MW | 0.69 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313506 | AB1-173 C OP | 80/20 | 9.14 MW | 9.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313719 | 3CHESTNUT | 80/20 | 0.72 MW | 0.72 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314429 | 3JTRSVLE | 80/20 | 0.15 MW | 0.15 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314572 | 3EMPORIA | 80/20 | 0.31 MW | 0.31 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314582 | 3KELFORD | 80/20 | 0.22 MW | 0.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314623 | 3WITAKRS | 80/20 | 0.07 MW | 0.07 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314704 | 3LAWRENC | 80/20 | 0.16 MW | 0.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315126 | 1ROARAP2 | 80/20 | 3.48 MW | 3.48 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315128 | 1ROARAP4 | 80/20 | 3.33 MW | 3.33 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315158 | 1KERR 1 | 80/20 | 0.39 MW | 0.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315159 | 1KERR 2 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315160 | 1KERR 3 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315161 | 1KERR 4 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315162 | 1KERR 5 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 920591 | AA2-165 C | 80/20 | 0.1 MW | 0.1 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 926201 | AC1-098 C | 80/20 | 5.16 MW | 5.16 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 926211 | AC1-099 C | 80/20 | 1.73 MW | 1.73 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 927145 | AC1-208 C | 80/20 | 10.12 MW | 10.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 936265 | AD2-033 C | 80/20 | 6.0 MW | 6.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 943171 | AE2-346 C | 80/20 | 0.9 MW | 0.9 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 958801 | AF2-171 C | 80/20 | 5.11 MW | 5.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 959311 | AF2-222 C | 80/20 | 7.08 MW | 7.08 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 960081 | AF2-299 C | 80/20 | 1.27 MW | 1.27 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315163 | 1KERR 6 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315164 | 1KERR 7 | 80/20 | 1.09 MW | 1.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315606 | 3AA2-053SOLA | 80/20 | 3.22 MW | 3.22 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316129 | AC1-054 C | 80/20 | 11.8 MW | 11.8 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316131 | AB2-060 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316140 | AB2-099 C | 80/20 | 0.38 MW | 0.38 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 923262 | AB1-132 C OP | Adder | -12.43 MW | -10.56 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 923991 | AB2-040 C O1 | 80/20 | 9.96 MW | 9.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924301 | AB2-077 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924311 | AB2-078 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 924321 | AB2-079 C O1 | 80/20 | 1.13 MW | 1.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 925611 | AC1-036 C | 80/20 | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 932631 | AC2-084 C | 80/20 | 7.36 MW | 7.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 938371 | AE1-056 C | 80/20 | 1.96 MW | 1.96 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 939181 | AE1-148 C | 80/20 | 7.6 MW | 7.6 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 940661 | AE2-053 O1 | 80/20 | 2.81 MW | 2.81 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 946281 | AF1-292 C | 80/20 | 0.75 MW | 0.75 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 946301 | AF1-294 C | 80/20 | 1.39 MW | 1.39 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 957521 | AF2-046 C | 80/20 | 20.0 MW | 20.0 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 958211 | AF2-115 C | 80/20 | 0.85 MW | 0.85 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 314589 | 3MURPHYS | 80/20 | 0.12 MW | 0.12 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315607 | 3AA1-063SOLA | 80/20 | 3.13 MW | 3.13 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 315608 | 3AA2-088SOLA | 80/20 | 1.88 MW | 1.88 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 316087 | AB2-174 C | 80/20 | 1.35 MW | 1.35 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 962561 | AG1-105 C O1 | 80/20 | 3.36 MW | 3.36 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 961681 | AG1-008 C | 80/20 | 20.04 MW | 20.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.09 MW | 0.09 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 1.83 MW | 1.83 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.82 MW | 0.82 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.78 MW | 0.78 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.17 MW | 0.17 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.04 MW | 0.04 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.11 MW | 0.11 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.14 MW | 0.14 MW |
| 3CAROLNA-6CAROLNA 115.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 140 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6POWHATN-6JUDES F 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961791 | AG1-021 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961801 | AG1-022 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 961891 | AG1-030 C | 80/20 | 15.83 MW | 15.83 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962491 | AG1-098 C O1 | 80/20 | 9.05 MW | 9.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962741 | AG1-123 C O1 | 80/20 | 2.77 MW | 2.77 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962751 | AG1-124 C O1 | 80/20 | 3.57 MW | 3.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963171 | AG1-166 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963181 | AG1-167 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963191 | AG1-168 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963201 | AG1-169 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963211 | AG1-170 C | 80/20 | 2.3 MW | 2.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963321 | AG1-181 C O1 | 80/20 | 14.05 MW | 14.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 963361 | AG1-185 O1 | 80/20 | 6.8 MW | 6.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964111 | AG1-272 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964121 | AG1-273 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964131 | AG1-274 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964231 | AG1-284 C O1 | 80/20 | 17.0 MW | 17.0 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964241 | AG1-285 C O1 | 80/20 | 8.14 MW | 8.14 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 964791 | AG1-342 C | 80/20 | 1.8 MW | 1.8 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965191 | AG1-384 C | 80/20 | 2.26 MW | 2.26 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965581 | AG1-426 | 80/20 | 5.44 MW | 5.44 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965591 | AG1-427 C | 80/20 | 7.79 MW | 7.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965641 | AG1-432 C O1 | 80/20 | 30.1 MW | 30.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965721 | AG1-440 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965731 | AG1-441 C | 80/20 | 2.36 MW | 2.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965771 | AG1-445 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965781 | AG1-446 | 80/20 | 1.36 MW | 1.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 965831 | AG1-451 | 80/20 | 5.02 MW | 5.02 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 966251 | AG1-494 C | 80/20 | 1.65 MW | 1.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314429 | 3JTRSVLE | 80/20 | 0.52 MW | 0.52 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315153 | 1CLOVER1 | 80/20 | 4.67 MW | 4.67 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315154 | 1CLOVER2 | 80/20 | 4.62 MW | 4.62 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315158 | 1KERR 1 | 80/20 | 0.15 MW | 0.15 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315159 | 1KERR 2 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315160 | 1KERR 3 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315161 | 1KERR 4 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315162 | 1KERR 5 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 927261 | AC1-222 C | 80/20 | 1.23 MW | 1.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934311 | AD1-055 C | 80/20 | 0.85 MW | 0.85 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934615 | AD1-087 C | 80/20 | 2.71 MW | 2.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 934625 | AD1-088 C | 80/20 | 10.23 MW | 10.23 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 935171 | AD1-152 C O1 | 80/20 | 2.69 MW | 2.69 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 936265 | AD2-033 C | 80/20 | 10.65 MW | 10.65 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 937481 | AD2-202 C O1 | 80/20 | 0.79 MW | 0.79 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 942461 | AE2-259 C O1 | 80/20 | 15.05 MW | 15.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 943901 | AF1-058 C | 80/20 | 0.66 MW | 0.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958801 | AF2-171 C | 80/20 | 17.16 MW | 17.16 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 959311 | AF2-222 C | 80/20 | 15.3 MW | 15.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960061 | AF2-297 C | 80/20 | 2.66 MW | 2.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 960111 | AF2-302 C | 80/20 | 3.43 MW | 3.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315163 | 1KERR 6 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315164 | 1KERR 7 | 80/20 | 0.43 MW | 0.43 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315266 | 1PLYWOOD A | 80/20 | 0.46 MW | 0.46 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 316118 | AC1-105 C | 80/20 | 2.19 MW | 2.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 316131 | AB2-060 C | 80/20 | 0.91 MW | 0.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924301 | AB2-077 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924311 | AB2-078 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 924321 | AB2-079 C O1 | 80/20 | 1.1 MW | 1.1 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 925611 | AC1-036 C | 80/20 | 0.21 MW | 0.21 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938371 | AE1-056 C | 80/20 | 8.05 MW | 8.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938821 | AE1-108 C O1 | 80/20 | 28.7 MW | 28.7 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 939181 | AE1-148 C | 80/20 | 3.59 MW | 3.59 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 940661 | AE2-053 O1 | 80/20 | 1.33 MW | 1.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941011 | AE2-092 C | 80/20 | 25.27 MW | 25.27 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 941791 | AE2-182 C | 80/20 | 1.66 MW | 1.66 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946291 | AF1-293 C O1 | 80/20 | 39.53 MW | 39.53 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946301 | AF1-294 C | 80/20 | 4.71 MW | 4.71 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 946591 | AF1-323 C | 80/20 | 9.42 MW | 9.42 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958131 | AF2-107 C | 80/20 | 4.37 MW | 4.37 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958211 | AF2-115 C | 80/20 | 2.87 MW | 2.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 933501 | AC2-165 C | 80/20 | 39.24 MW | 39.24 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314333 | 6POWHATN | 80/20 | 1.72 MW | 1.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 314677 | 6BUCKING | 80/20 | 0.87 MW | 0.87 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 958501 | AF2-144 C | 80/20 | 7.49 MW | 7.49 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315191 | 1BEARGRDN G1 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315192 | 1BEARGRDN G2 | 80/20 | 15.39 MW | 15.39 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 315193 | 1BEARGRDN S1 | 80/20 | 19.91 MW | 19.91 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 938561 | AE1-075 C | 80/20 | 1.5 MW | 1.5 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 962561 | AG1-105 C O1 | 80/20 | 4.05 MW | 4.05 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | 313527 | AB2-043 C | 80/20 | 0.3 MW | 0.3 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.72 MW | 0.72 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.33 MW | 0.33 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 14.41 MW | 14.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 8.13 MW | 8.13 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 7.19 MW | 7.19 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 1.57 MW | 1.57 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.41 MW | 0.41 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 1.08 MW | 1.08 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.36 MW | 0.36 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.07 MW | 0.07 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 1.29 MW | 1.29 MW |
| 6JUDES F-6MDLTHAN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2028-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.19 MW | 0.19 MW |
| Details for 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 961791 | AG1-021 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 961891 | AG1-030 C | 80/20 | 13.82 MW | 13.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 962491 | AG1-098 C O1 | 80/20 | 20.69 MW | 20.69 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963041 | AG1-153 C | 80/20 | 17.6 MW | 17.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963111 | AG1-160 C | 80/20 | 18.44 MW | 18.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963171 | AG1-166 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963181 | AG1-167 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963191 | AG1-168 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963201 | AG1-169 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963211 | AG1-170 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963321 | AG1-181 C O1 | 80/20 | 15.44 MW | 15.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 963361 | AG1-185 O1 | 80/20 | 7.47 MW | 7.47 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 964111 | AG1-272 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 964121 | AG1-273 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 964131 | AG1-274 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 964241 | AG1-285 C O1 | 80/20 | 11.41 MW | 11.41 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 964791 | AG1-342 C | 80/20 | 5.47 MW | 5.47 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 966691 | AG1-539 C | 80/20 | 5.64 MW | 5.64 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 966761 | AG1-547 C | 80/20 | 3.77 MW | 3.77 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 965191 | AG1-384 C | 80/20 | 2.36 MW | 2.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 965591 | AG1-427 C | 80/20 | 10.81 MW | 10.81 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 965641 | AG1-432 C O1 | 80/20 | 18.63 MW | 18.63 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 965721 | AG1-440 C | 80/20 | 5.26 MW | 5.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 965731 | AG1-441 C | 80/20 | 5.26 MW | 5.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 965771 | AG1-445 | 80/20 | 3.04 MW | 3.04 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 965781 | AG1-446 | 80/20 | 3.04 MW | 3.04 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 965831 | AG1-451 | 80/20 | 3.1 MW | 3.1 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 966361 | AG1-505 C | 80/20 | 48.35 MW | 48.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 966371 | AG1-506 C | 80/20 | 48.35 MW | 48.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 247284 | 05LEESVG | 80/20 | 0.93 MW | 0.93 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 314429 | 3JTRSVLE | 80/20 | 0.42 MW | 0.42 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315153 | 1CLOVER1 | 80/20 | 30.43 MW | 30.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315154 | 1CLOVER2 | 80/20 | 30.14 MW | 30.14 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315156 | 1HALLBR1 | 80/20 | 1.11 MW | 1.11 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315158 | 1KERR 1 | 80/20 | 0.35 MW | 0.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315159 | 1KERR 2 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315160 | 1KERR 3 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315161 | 1KERR 4 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315162 | 1KERR 5 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 926023 | AC1-080 C | 80/20 | 0.43 MW | 0.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 926051 | AC1-083 C O1 | 80/20 | 4.86 MW | 4.86 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 926645 | AC1-145 C | 80/20 | 0.38 MW | 0.38 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 927251 | AC1-221 C | 80/20 | 3.73 MW | 3.73 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 927261 | AC1-222 C | 80/20 | 5.71 MW | 5.71 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 933941 | AD1-017 C | 80/20 | 0.97 MW | 0.97 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 934311 | AD1-055 C | 80/20 | 3.96 MW | 3.96 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 934341 | AD1-058 C | 80/20 | 9.36 MW | 9.36 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 934615 | AD1-087 C | 80/20 | 17.65 MW | 17.65 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 934625 | AD1-088 C | 80/20 | 22.84 MW | 22.84 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 934991 | AD1-131 C | 80/20 | 3.07 MW | 3.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 935171 | AD1-152 C O1 | 80/20 | 17.29 MW | 17.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 936161 | AD2-022 C O1 | 80/20 | 12.6 MW | 12.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 936171 | AD2-023 C O1 | 80/20 | 7.35 MW | 7.35 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 936265 | AD2-033 C | 80/20 | 11.91 MW | 11.91 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 937481 | AD2-202 C O1 | 80/20 | 5.17 MW | 5.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 942461 | AE2-259 C O1 | 80/20 | 9.31 MW | 9.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 942671 | AE2-283 C | 80/20 | 4.59 MW | 4.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 942751 | AE2-291 C | 80/20 | 10.79 MW | 10.79 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 942761 | AE2-292 C O1 | 80/20 | 13.43 MW | 13.43 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 943811 | AF1-049 C | 80/20 | 9.05 MW | 9.05 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 943901 | AF1-058 C | 80/20 | 3.16 MW | 3.16 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 944141 | AF1-082 | 80/20 | 1.87 MW | 1.87 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 945811 | AF1-246 C O1 | 80/20 | 19.09 MW | 19.09 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 958801 | AF2-171 C | 80/20 | 13.85 MW | 13.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 959311 | AF2-222 C | 80/20 | 15.31 MW | 15.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 960061 | AF2-297 C | 80/20 | 12.65 MW | 12.65 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 961121 | AF2-403 | 80/20 | 0.93 MW | 0.93 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315163 | 1KERR 6 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315164 | 1KERR 7 | 80/20 | 0.98 MW | 0.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315266 | 1PLYWOOD A | 80/20 | 1.88 MW | 1.88 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 316020 | AB2-059 C OP | 80/20 | 1.17 MW | 1.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 316118 | AC1-105 C | 80/20 | 8.29 MW | 8.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 316131 | AB2-060 C | 80/20 | 1.41 MW | 1.41 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 922922 | AB1-081 C OP | 80/20 | 0.99 MW | 0.99 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 924301 | AB2-077 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 924311 | AB2-078 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 924321 | AB2-079 C O1 | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 925591 | AC1-034 C | 80/20 | 4.44 MW | 4.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 925611 | AC1-036 C | 80/20 | 0.22 MW | 0.22 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 925661 | AC1-042 C | 80/20 | 1.85 MW | 1.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 932761 | AC2-100 C | 80/20 | 8.59 MW | 8.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 938371 | AE1-056 C | 80/20 | 5.99 MW | 5.99 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 939181 | AE1-148 C | 80/20 | 7.56 MW | 7.56 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 940081 | AE1-250 C | 80/20 | 13.17 MW | 13.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 940571 | AE2-044 C | 80/20 | 2.9 MW | 2.9 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 940661 | AE2-053 O1 | 80/20 | 2.8 MW | 2.8 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 941431 | AE2-140 C O1 | 80/20 | 13.82 MW | 13.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 941791 | AE2-182 C | 80/20 | 3.71 MW | 3.71 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 941801 | AE2-185 C | 80/20 | 4.17 MW | 4.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 941821 | AE2-187 C | 80/20 | 4.17 MW | 4.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 946301 | AF1-294 C | 80/20 | 3.79 MW | 3.79 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 957481 | AF2-042 C | 80/20 | 136.39 MW | 136.39 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 958211 | AF2-115 C | 80/20 | 2.31 MW | 2.31 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 926754 | AC1-161 C | Adder | -31.93 MW | -27.14 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 934061 | AD1-033 C | Adder | -7.2 MW | -6.12 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 934575 | AD1-082 C | Adder | -6.69 MW | -5.69 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 937221 | AD2-160 C O1 | Adder | -5.42 MW | -4.61 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 942401 | AE2-253 C | Adder | -5.7 MW | -4.85 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 943611 | AF1-032 C | Adder | -1.56 MW | -1.32 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 943621 | AF1-033 C | Adder | -2.13 MW | -1.81 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315102 | 1BRUNSWICKG1 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315103 | 1BRUNSWICKG2 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315104 | 1BRUNSWICKG3 | 80/20 | 27.08 MW | 27.08 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315105 | 1BRUNSWICKS1 | 80/20 | 56.26 MW | 56.26 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315241 | 1Z1-086 GT1 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315242 | 1Z1-086 GT2 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315243 | 1Z1-086 GT3 | 80/20 | 36.01 MW | 36.01 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 315244 | 1Z1-086 ST | 80/20 | 62.59 MW | 62.59 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 316132 | AB2-190 C | Adder | -16.2 MW | -13.77 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 932044 | AC2-012 C | Adder | -7.78 MW | -6.61 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 938741 | AE1-100 C O1 | 80/20 | 4.44 MW | 4.44 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 939431 | AE1-175 C | Adder | -2.09 MW | -1.78 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 940601 | AE2-047 C O1 | 80/20 | 4.11 MW | 4.11 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 957491 | AF2-043 C | Adder | -1.91 MW | -1.62 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 962961 | AG1-145 C | Adder | -1.89 MW | -1.6 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 962561 | AG1-105 C O1 | 80/20 | 11.17 MW | 11.17 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 313527 | AB2-043 C | 80/20 | 0.49 MW | 0.49 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 316083 | AB2-161 C | Adder | -2.94 MW | -2.5 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | 316123 | AC1-075 C | 80/20 | 1.29 MW | 1.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 9.63 MW | 9.63 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 3.07 MW | 3.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 180.98 MW | 180.98 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 62.2 MW | 62.2 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 65.2 MW | 65.2 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 14.58 MW | 14.58 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 15.29 MW | 15.29 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.82 MW | 0.82 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.05 MW | 3.05 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.9 MW | 8.9 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 2.07 MW | 2.07 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.55 MW | 0.55 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 12.3 MW | 12.3 MW |
| 8ROGERS RD-AE2-094 TAP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511-C | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.49 MW | 1.49 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 6.64 MW | 6.64 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 4.43 MW | 4.43 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 55.97 MW | 55.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 27.08 MW | 27.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 41.52 MW | 41.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 27.68 MW | 27.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 8.54 MW | 8.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 2.54 MW | 2.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 39.37 MW | 39.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 26.3 MW | 26.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 66.44 MW | 66.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 44.29 MW | 44.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 11.07 MW | 11.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 2.21 MW | 2.21 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.51 MW | 1.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 5.39 MW | 5.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 43.19 MW | 43.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 28.79 MW | 28.79 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 22.15 MW | 22.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 49.83 MW | 49.83 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 33.22 MW | 33.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 55.37 MW | 55.37 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 37.09 MW | 37.09 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 5.13 MW | 5.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 14.17 MW | 14.17 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.81 MW | 0.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 5.15 MW | 5.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 21.48 MW | 21.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 11.74 MW | 11.74 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 13.62 MW | 13.62 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 9.08 MW | 9.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 8.3 MW | 8.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 5.54 MW | 5.54 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.15 MW | 0.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.06 MW | 0.06 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961791 | AG1-021 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961792 | AG1-021 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961891 | AG1-030 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 961892 | AG1-030 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963171 | AG1-166 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963172 | AG1-166 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963181 | AG1-167 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963182 | AG1-167 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963191 | AG1-168 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963192 | AG1-168 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963201 | AG1-169 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963202 | AG1-169 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963211 | AG1-170 C | 50/50 | 5.35 MW | 5.35 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963212 | AG1-170 E | 50/50 | 3.57 MW | 3.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963321 | AG1-181 C O1 | 50/50 | 45.08 MW | 45.08 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 963361 | AG1-185 O1 | 50/50 | 21.81 MW | 21.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964111 | AG1-272 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964112 | AG1-272 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964121 | AG1-273 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964122 | AG1-273 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964131 | AG1-274 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964132 | AG1-274 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964241 | AG1-285 C O1 | 50/50 | 33.45 MW | 33.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 964242 | AG1-285 E O1 | 50/50 | 22.3 MW | 22.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965191 | AG1-384 C | 50/50 | 6.88 MW | 6.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965192 | AG1-384 E | 50/50 | 2.04 MW | 2.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965591 | AG1-427 C | 50/50 | 31.71 MW | 31.71 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965592 | AG1-427 E | 50/50 | 21.18 MW | 21.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965641 | AG1-432 C O1 | 50/50 | 53.51 MW | 53.51 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965642 | AG1-432 E O1 | 50/50 | 35.67 MW | 35.67 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 965831 | AG1-451 | 50/50 | 8.92 MW | 8.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 313853 | 3PONTONDP | 50/50 | 1.78 MW | 1.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314429 | 3JTRSVLE | 50/50 | 1.22 MW | 1.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 314713 | 3PAMPLIN | 50/50 | 4.34 MW | 4.34 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936265 | AD2-033 C | 50/50 | 34.78 MW | 34.78 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 936266 | AD2-033 E | 50/50 | 23.19 MW | 23.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942461 | AE2-259 C O1 | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 942462 | AE2-259 E O1 | 50/50 | 17.84 MW | 17.84 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958801 | AF2-171 C | 50/50 | 40.13 MW | 40.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958802 | AF2-171 E | 50/50 | 26.76 MW | 26.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959311 | AF2-222 C | 50/50 | 44.59 MW | 44.59 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 959312 | AF2-222 E | 50/50 | 29.88 MW | 29.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 316131 | AB2-060 C | 50/50 | 4.13 MW | 4.13 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 924162 | AB2-060 E OP | 50/50 | 11.42 MW | 11.42 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925611 | AC1-036 C | 50/50 | 0.65 MW | 0.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 925612 | AC1-036 E | 50/50 | 4.15 MW | 4.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938371 | AE1-056 C | 50/50 | 17.3 MW | 17.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 938372 | AE1-056 E | 50/50 | 9.45 MW | 9.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946301 | AF1-294 C | 50/50 | 10.97 MW | 10.97 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 946302 | AF1-294 E | 50/50 | 7.31 MW | 7.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958211 | AF2-115 C | 50/50 | 6.69 MW | 6.69 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | 958212 | AF2-115 E | 50/50 | 4.46 MW | 4.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.02 MW | 0.02 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.12 MW | 0.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-6: CHASE C T342 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.01 MW | 0.01 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961791 | AG1-021 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961792 | AG1-021 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961891 | AG1-030 C | 50/50 | 33.66 MW | 33.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 961892 | AG1-030 E | 50/50 | 22.44 MW | 22.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963171 | AG1-166 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963172 | AG1-166 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963181 | AG1-167 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963182 | AG1-167 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963191 | AG1-168 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963192 | AG1-168 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963201 | AG1-169 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963202 | AG1-169 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963211 | AG1-170 C | 50/50 | 4.95 MW | 4.95 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963212 | AG1-170 E | 50/50 | 3.3 MW | 3.3 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963301 | AG1-179 C | Adder | 3.09 MW | 2.63 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963311 | AG1-180 | Adder | 1.5 MW | 1.28 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963321 | AG1-181 C O1 | 50/50 | 28.68 MW | 28.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 963361 | AG1-185 O1 | 50/50 | 13.88 MW | 13.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964111 | AG1-272 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964112 | AG1-272 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964121 | AG1-273 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964122 | AG1-273 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964131 | AG1-274 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964132 | AG1-274 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964241 | AG1-285 C O1 | 50/50 | 15.68 MW | 15.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964242 | AG1-285 E O1 | 50/50 | 10.46 MW | 10.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964791 | AG1-342 C | Adder | 2.21 MW | 1.88 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 964792 | AG1-342 E | Adder | 1.74 MW | 1.48 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965191 | AG1-384 C | 50/50 | 4.66 MW | 4.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965192 | AG1-384 E | 50/50 | 1.39 MW | 1.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965591 | AG1-427 C | 50/50 | 15.04 MW | 15.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965592 | AG1-427 E | 50/50 | 10.05 MW | 10.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965601 | AG1-428 C O2 | Adder | 2.58 MW | 2.19 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965602 | AG1-428 E O2 | Adder | 1.72 MW | 1.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965641 | AG1-432 C O1 | 50/50 | 66.92 MW | 66.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965642 | AG1-432 E O1 | 50/50 | 44.61 MW | 44.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965721 | AG1-440 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965722 | AG1-440 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965731 | AG1-441 C | Adder | 4.05 MW | 3.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965732 | AG1-441 E | Adder | 2.7 MW | 2.29 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965771 | AG1-445 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965781 | AG1-446 | Adder | 2.34 MW | 1.99 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 965831 | AG1-451 | 50/50 | 11.15 MW | 11.15 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313853 | 3PONTONDP | 50/50 | 1.65 MW | 1.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314429 | 3JTRSVLE | 50/50 | 1.12 MW | 1.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 314713 | 3PAMPLIN | 50/50 | 4.39 MW | 4.39 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315159 | 1KERR 2 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315160 | 1KERR 3 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315161 | 1KERR 4 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315162 | 1KERR 5 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936265 | AD2-033 C | 50/50 | 21.66 MW | 21.66 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 936266 | AD2-033 E | 50/50 | 14.44 MW | 14.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942461 | AE2-259 C O1 | 50/50 | 33.46 MW | 33.46 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 942462 | AE2-259 E O1 | 50/50 | 22.31 MW | 22.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958801 | AF2-171 C | 50/50 | 36.92 MW | 36.92 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958802 | AF2-171 E | 50/50 | 24.61 MW | 24.61 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959311 | AF2-222 C | 50/50 | 31.81 MW | 31.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 959312 | AF2-222 E | 50/50 | 21.32 MW | 21.32 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 315163 | 1KERR 6 | 50/50 | 0.72 MW | 0.72 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 316131 | AB2-060 C | 50/50 | 1.7 MW | 1.7 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924162 | AB2-060 E OP | 50/50 | 4.68 MW | 4.68 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924301 | AB2-077 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924302 | AB2-077 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924311 | AB2-078 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924312 | AB2-078 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924321 | AB2-079 C O1 | 50/50 | 2.0 MW | 2.0 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924322 | AB2-079 E O1 | 50/50 | 1.33 MW | 1.33 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925611 | AC1-036 C | 50/50 | 0.44 MW | 0.44 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 925612 | AC1-036 E | 50/50 | 2.81 MW | 2.81 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938371 | AE1-056 C | 50/50 | 17.52 MW | 17.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 938372 | AE1-056 E | 50/50 | 9.57 MW | 9.57 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939181 | AE1-148 C | 50/50 | 6.23 MW | 6.23 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 939182 | AE1-148 E | 50/50 | 4.16 MW | 4.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 940661 | AE2-053 O1 | 50/50 | 2.31 MW | 2.31 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946301 | AF1-294 C | 50/50 | 10.14 MW | 10.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 946302 | AF1-294 E | 50/50 | 6.76 MW | 6.76 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958211 | AF2-115 C | 50/50 | 6.18 MW | 6.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 958212 | AF2-115 E | 50/50 | 4.12 MW | 4.12 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962561 | AG1-105 C O1 | 50/50 | 5.47 MW | 5.47 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 962562 | AG1-105 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 313527 | AB2-043 C | 50/50 | 0.56 MW | 0.56 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | 924022 | AB2-043 E O1 | 50/50 | 2.94 MW | 2.94 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.16 MW | 0.16 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.04 MW | 0.04 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 2.52 MW | 2.52 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 1.03 MW | 1.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 0.96 MW | 0.96 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.24 MW | 0.24 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.07 MW | 0.07 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 0.22 MW | 0.22 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.14 MW | 0.14 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.03 MW | 0.03 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.45 MW | 0.45 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 0.18 MW | 0.18 MW |
| 3FARMVIL-6FARMVIL 115.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 29822 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964241 | AG1-285 C O1 | 50/50 | 75.0 MW | 75.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964242 | AG1-285 E O1 | 50/50 | 50.0 MW | 50.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-285 TAP-3CHASCTY 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 120.0 MW | 120.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 80.0 MW | 80.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 20.0 MW | 20.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 40.0 MW | 40.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965591 | AG1-427 C | 50/50 | 71.1 MW | 71.1 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965592 | AG1-427 E | 50/50 | 47.5 MW | 47.5 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-427 TAP-AG1-285 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961791 | AG1-021 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961792 | AG1-021 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961891 | AG1-030 C | 50/50 | 11.84 MW | 11.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 961892 | AG1-030 E | 50/50 | 7.89 MW | 7.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963171 | AG1-166 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963172 | AG1-166 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963181 | AG1-167 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963182 | AG1-167 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963191 | AG1-168 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963192 | AG1-168 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963201 | AG1-169 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963202 | AG1-169 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963211 | AG1-170 C | Adder | 1.43 MW | 1.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963212 | AG1-170 E | Adder | 0.96 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963301 | AG1-179 C | Adder | 3.43 MW | 2.92 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963311 | AG1-180 | Adder | 1.67 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963321 | AG1-181 C O1 | 50/50 | 16.16 MW | 16.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 963361 | AG1-185 O1 | 50/50 | 7.82 MW | 7.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964111 | AG1-272 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964121 | AG1-273 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964131 | AG1-274 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964241 | AG1-285 C O1 | 50/50 | 13.75 MW | 13.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964242 | AG1-285 E O1 | 50/50 | 9.16 MW | 9.16 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964791 | AG1-342 C | Adder | 2.86 MW | 2.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 964792 | AG1-342 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965191 | AG1-384 C | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965591 | AG1-427 C | 50/50 | 12.98 MW | 12.98 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965592 | AG1-427 E | 50/50 | 8.67 MW | 8.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965601 | AG1-428 C O2 | Adder | 2.87 MW | 2.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965602 | AG1-428 E O2 | Adder | 1.91 MW | 1.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965641 | AG1-432 C O1 | Adder | 8.86 MW | 7.53 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965642 | AG1-432 E O1 | Adder | 5.91 MW | 5.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965721 | AG1-440 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965722 | AG1-440 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965731 | AG1-441 C | 50/50 | 16.02 MW | 16.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965732 | AG1-441 E | 50/50 | 10.68 MW | 10.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965771 | AG1-445 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965781 | AG1-446 | 50/50 | 9.25 MW | 9.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 965831 | AG1-451 | Adder | 1.48 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313853 | 3PONTONDP | Adder | 0.48 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 314713 | 3PAMPLIN | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315159 | 1KERR 2 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315160 | 1KERR 3 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315161 | 1KERR 4 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315162 | 1KERR 5 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925785 | AC1-054 E | 50/50 | 7.3 MW | 7.3 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 926274 | AC1-105 E | Adder | 1.4 MW | 1.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936265 | AD2-033 C | 50/50 | 12.62 MW | 12.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 936266 | AD2-033 E | 50/50 | 8.41 MW | 8.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942461 | AE2-259 C O1 | Adder | 4.43 MW | 3.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 942462 | AE2-259 E O1 | Adder | 2.95 MW | 2.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958801 | AF2-171 C | 50/50 | 10.81 MW | 10.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958802 | AF2-171 E | 50/50 | 7.21 MW | 7.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959311 | AF2-222 C | 50/50 | 14.91 MW | 14.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 959312 | AF2-222 E | 50/50 | 9.99 MW | 9.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315163 | 1KERR 6 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 315164 | 1KERR 7 | 50/50 | 2.55 MW | 2.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316118 | AC1-105 C | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316129 | AC1-054 C | 50/50 | 15.84 MW | 15.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 316131 | AB2-060 C | 50/50 | 1.77 MW | 1.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924162 | AB2-060 E OP | 50/50 | 4.9 MW | 4.9 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924301 | AB2-077 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924302 | AB2-077 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924311 | AB2-078 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924312 | AB2-078 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924321 | AB2-079 C O1 | 50/50 | 2.38 MW | 2.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924322 | AB2-079 E O1 | 50/50 | 1.58 MW | 1.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925611 | AC1-036 C | 50/50 | 0.23 MW | 0.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 925612 | AC1-036 E | 50/50 | 1.43 MW | 1.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938371 | AE1-056 C | Adder | 4.16 MW | 3.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 938372 | AE1-056 E | Adder | 2.27 MW | 1.93 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939181 | AE1-148 C | 50/50 | 17.48 MW | 17.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 939182 | AE1-148 E | 50/50 | 11.65 MW | 11.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 940661 | AE2-053 O1 | 50/50 | 6.47 MW | 6.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946301 | AF1-294 C | Adder | 2.94 MW | 2.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 946302 | AF1-294 E | Adder | 1.96 MW | 1.67 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958211 | AF2-115 C | Adder | 1.79 MW | 1.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 958212 | AF2-115 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962561 | AG1-105 C O1 | 50/50 | 6.82 MW | 6.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 962562 | AG1-105 E O1 | 50/50 | 4.55 MW | 4.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 313527 | AB2-043 C | 50/50 | 0.63 MW | 0.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | 924022 | AB2-043 E O1 | 50/50 | 3.28 MW | 3.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.44 MW | 0.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.66 MW | 0.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.42 MW | 0.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.06 MW | 0.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.18 MW | 0.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.81 MW | 0.81 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.24 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-6: CAROLIN T122 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.47 MW | 0.47 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 86.08 MW | 86.08 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 41.65 MW | 41.65 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961791 | AG1-021 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961891 | AG1-030 C | Adder | 12.01 MW | 10.21 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961892 | AG1-030 E | Adder | 8.0 MW | 6.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963171 | AG1-166 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963181 | AG1-167 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963191 | AG1-168 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963201 | AG1-169 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963211 | AG1-170 C | Adder | 1.41 MW | 1.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963301 | AG1-179 C | Adder | 3.75 MW | 3.19 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963311 | AG1-180 | Adder | 1.83 MW | 1.55 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963321 | AG1-181 C O1 | 50/50 | 17.24 MW | 17.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 963361 | AG1-185 O1 | 50/50 | 8.34 MW | 8.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964111 | AG1-272 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964112 | AG1-272 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964121 | AG1-273 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964122 | AG1-273 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964131 | AG1-274 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964132 | AG1-274 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964241 | AG1-285 C O1 | 50/50 | 15.1 MW | 15.1 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964242 | AG1-285 E O1 | 50/50 | 10.07 MW | 10.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964791 | AG1-342 C | 50/50 | 10.66 MW | 10.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 964792 | AG1-342 E | 50/50 | 8.37 MW | 8.37 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966691 | AG1-539 C | 50/50 | 10.05 MW | 10.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966692 | AG1-539 E | 50/50 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966761 | AG1-547 C | Adder | 4.41 MW | 3.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 966762 | AG1-547 E | Adder | 2.37 MW | 2.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965191 | AG1-384 C | 50/50 | 2.51 MW | 2.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965192 | AG1-384 E | 50/50 | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965591 | AG1-427 C | 50/50 | 14.24 MW | 14.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965592 | AG1-427 E | 50/50 | 9.52 MW | 9.52 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965601 | AG1-428 C O2 | Adder | 3.13 MW | 2.66 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965602 | AG1-428 E O2 | Adder | 2.08 MW | 1.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965721 | AG1-440 C | Adder | 6.17 MW | 5.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965722 | AG1-440 E | Adder | 4.11 MW | 3.49 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965731 | AG1-441 C | Adder | 6.17 MW | 5.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965732 | AG1-441 E | Adder | 4.11 MW | 3.49 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965771 | AG1-445 | Adder | 3.56 MW | 3.03 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 965781 | AG1-446 | Adder | 3.56 MW | 3.03 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 314713 | 3PAMPLIN | Adder | 0.99 MW | 0.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315156 | 1HALLBR1 | 50/50 | 1.46 MW | 1.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315159 | 1KERR 2 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315161 | 1KERR 4 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315162 | 1KERR 5 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925785 | AC1-054 E | Adder | 2.15 MW | 1.82 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926023 | AC1-080 C | 50/50 | 0.83 MW | 0.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926274 | AC1-105 E | 50/50 | 8.2 MW | 8.2 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926646 | AC1-145 E | Adder | 2.31 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 927261 | AC1-222 C | 50/50 | 12.09 MW | 12.09 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 927262 | AC1-222 E | 50/50 | 11.51 MW | 11.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 934311 | AD1-055 C | 50/50 | 8.39 MW | 8.39 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 934312 | AD1-055 E | 50/50 | 2.16 MW | 2.16 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 935171 | AD1-152 C O1 | Adder | -4.31 MW | -3.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 936265 | AD2-033 C | 50/50 | 13.51 MW | 13.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 936266 | AD2-033 E | 50/50 | 9.0 MW | 9.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942671 | AE2-283 C | Adder | 5.37 MW | 4.57 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942672 | AE2-283 E | Adder | 2.82 MW | 2.4 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942751 | AE2-291 C | 50/50 | 19.22 MW | 19.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942752 | AE2-291 E | 50/50 | 12.81 MW | 12.81 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942761 | AE2-292 C O1 | 50/50 | 23.93 MW | 23.93 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 942762 | AE2-292 E O1 | 50/50 | 15.96 MW | 15.96 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958801 | AF2-171 C | Adder | 10.66 MW | 9.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958802 | AF2-171 E | Adder | 7.1 MW | 6.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 959311 | AF2-222 C | 50/50 | 15.64 MW | 15.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 959312 | AF2-222 E | 50/50 | 10.48 MW | 10.48 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 960061 | AF2-297 C | 50/50 | 27.34 MW | 27.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 960062 | AF2-297 E | 50/50 | 18.23 MW | 18.23 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 961121 | AF2-403 | Adder | 1.08 MW | 0.92 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315164 | 1KERR 7 | 50/50 | 1.11 MW | 1.11 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 315266 | 1PLYWOOD A | 50/50 | 3.88 MW | 3.88 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316118 | AC1-105 C | 50/50 | 17.14 MW | 17.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316129 | AC1-054 C | Adder | 4.66 MW | 3.96 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316131 | AB2-060 C | 50/50 | 1.97 MW | 1.97 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924162 | AB2-060 E OP | 50/50 | 5.43 MW | 5.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924301 | AB2-077 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924302 | AB2-077 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924311 | AB2-078 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924312 | AB2-078 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924321 | AB2-079 C O1 | 50/50 | 2.67 MW | 2.67 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924322 | AB2-079 E O1 | 50/50 | 1.78 MW | 1.78 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925611 | AC1-036 C | 50/50 | 0.24 MW | 0.24 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925612 | AC1-036 E | 50/50 | 1.51 MW | 1.51 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925661 | AC1-042 C | Adder | 2.16 MW | 1.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925662 | AC1-042 E | Adder | 3.53 MW | 3.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 938371 | AE1-056 C | Adder | 3.93 MW | 3.34 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 938372 | AE1-056 E | Adder | 2.15 MW | 1.83 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 939181 | AE1-148 C | 50/50 | 9.05 MW | 9.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 939182 | AE1-148 E | 50/50 | 6.04 MW | 6.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 940661 | AE2-053 O1 | 50/50 | 3.35 MW | 3.35 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941801 | AE2-185 C | Adder | 4.88 MW | 4.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941802 | AE2-185 E | Adder | 3.26 MW | 2.77 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941821 | AE2-187 C | Adder | 4.88 MW | 4.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 941822 | AE2-187 E | Adder | 2.17 MW | 1.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 946301 | AF1-294 C | Adder | 2.89 MW | 2.46 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 946302 | AF1-294 E | Adder | 1.93 MW | 1.64 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958211 | AF2-115 C | Adder | 1.76 MW | 1.5 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 962561 | AG1-105 C O1 | 50/50 | 21.07 MW | 21.07 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 962562 | AG1-105 E O1 | 50/50 | 14.04 MW | 14.04 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 313527 | AB2-043 C | 50/50 | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 924022 | AB2-043 E O1 | 50/50 | 3.65 MW | 3.65 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 316123 | AC1-075 C | 50/50 | 2.47 MW | 2.47 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 925997 | AC1-075 E | 50/50 | 8.22 MW | 8.22 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | 926024 | AC1-080 E | 50/50 | 2.73 MW | 2.73 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.15 MW | 1.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.14 MW | 0.14 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.31 MW | 0.31 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 0.75 MW | 0.75 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.15 MW | 0.15 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.43 MW | 0.43 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.13 MW | 0.13 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.69 MW | 0.69 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 0.05 MW | 0.05 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 0.0 MW | 0.0 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.06 MW | 0.06 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.84 MW | 0.84 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.08 MW | 0.08 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.01 MW | 0.01 MW |
| 3SEDGE HILL-6SEDGE HILL 115.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 3202 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.02 MW | 0.02 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 13002 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961791 | AG1-021 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961792 | AG1-021 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961891 | AG1-030 C | Adder | 10.33 MW | 8.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 961892 | AG1-030 E | Adder | 6.89 MW | 5.86 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963171 | AG1-166 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963172 | AG1-166 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963181 | AG1-167 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963182 | AG1-167 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963191 | AG1-168 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963192 | AG1-168 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963201 | AG1-169 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963202 | AG1-169 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963211 | AG1-170 C | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963212 | AG1-170 E | Adder | 0.83 MW | 0.71 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963301 | AG1-179 C | Adder | 3.06 MW | 2.6 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963311 | AG1-180 | Adder | 1.49 MW | 1.27 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963321 | AG1-181 C O1 | Adder | 14.11 MW | 11.99 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 963361 | AG1-185 O1 | Adder | 6.83 MW | 5.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964111 | AG1-272 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964112 | AG1-272 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964121 | AG1-273 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964122 | AG1-273 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964131 | AG1-274 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964132 | AG1-274 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964241 | AG1-285 C O1 | 50/50 | 12.0 MW | 12.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964242 | AG1-285 E O1 | 50/50 | 8.0 MW | 8.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964791 | AG1-342 C | Adder | 2.48 MW | 2.11 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 964792 | AG1-342 E | Adder | 1.95 MW | 1.66 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966811 | AG1-552 C | Adder | 1.89 MW | 1.61 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 966812 | AG1-552 E | Adder | 0.81 MW | 0.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965191 | AG1-384 C | Adder | 2.07 MW | 1.76 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965192 | AG1-384 E | Adder | 0.62 MW | 0.52 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965591 | AG1-427 C | 50/50 | 11.33 MW | 11.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965592 | AG1-427 E | 50/50 | 7.57 MW | 7.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965601 | AG1-428 C O2 | Adder | 2.56 MW | 2.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965602 | AG1-428 E O2 | Adder | 1.7 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965641 | AG1-432 C O1 | Adder | 7.74 MW | 6.58 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965642 | AG1-432 E O1 | Adder | 5.16 MW | 4.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965721 | AG1-440 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965722 | AG1-440 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965731 | AG1-441 C | 50/50 | 12.8 MW | 12.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965732 | AG1-441 E | 50/50 | 8.54 MW | 8.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965771 | AG1-445 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965781 | AG1-446 | 50/50 | 7.4 MW | 7.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 965831 | AG1-451 | Adder | 1.29 MW | 1.1 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313853 | 3PONTONDP | Adder | 0.42 MW | 0.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 314713 | 3PAMPLIN | Adder | 0.91 MW | 0.77 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315126 | 1ROARAP2 | 50/50 | 1.28 MW | 1.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315158 | 1KERR 1 | 50/50 | 0.79 MW | 0.79 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315159 | 1KERR 2 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315160 | 1KERR 3 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315161 | 1KERR 4 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315162 | 1KERR 5 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925785 | AC1-054 E | 50/50 | 6.37 MW | 6.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 926274 | AC1-105 E | Adder | 1.2 MW | 1.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927145 | AC1-208 C | Adder | 3.74 MW | 3.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 927146 | AC1-208 E | Adder | 1.66 MW | 1.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936265 | AD2-033 C | Adder | 11.01 MW | 9.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 936266 | AD2-033 E | Adder | 7.34 MW | 6.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942461 | AE2-259 C O1 | Adder | 3.87 MW | 3.29 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 942462 | AE2-259 E O1 | Adder | 2.58 MW | 2.19 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958801 | AF2-171 C | Adder | 9.44 MW | 8.02 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958802 | AF2-171 E | Adder | 6.29 MW | 5.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959311 | AF2-222 C | Adder | 13.01 MW | 11.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 959312 | AF2-222 E | Adder | 8.72 MW | 7.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315163 | 1KERR 6 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 315164 | 1KERR 7 | 50/50 | 2.22 MW | 2.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316118 | AC1-105 C | Adder | 2.52 MW | 2.14 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316129 | AC1-054 C | 50/50 | 13.82 MW | 13.82 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 316131 | AB2-060 C | 50/50 | 1.55 MW | 1.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924162 | AB2-060 E OP | 50/50 | 4.28 MW | 4.28 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924301 | AB2-077 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924302 | AB2-077 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924311 | AB2-078 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924312 | AB2-078 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924321 | AB2-079 C O1 | 50/50 | 2.08 MW | 2.08 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924322 | AB2-079 E O1 | 50/50 | 1.38 MW | 1.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 925612 | AC1-036 E | Adder | 1.25 MW | 1.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938371 | AE1-056 C | Adder | 3.63 MW | 3.09 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 938372 | AE1-056 E | Adder | 1.98 MW | 1.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939181 | AE1-148 C | 50/50 | 15.25 MW | 15.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 939182 | AE1-148 E | 50/50 | 10.17 MW | 10.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 940661 | AE2-053 O1 | 50/50 | 5.65 MW | 5.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946301 | AF1-294 C | Adder | 2.57 MW | 2.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 946302 | AF1-294 E | Adder | 1.71 MW | 1.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958211 | AF2-115 C | Adder | 1.56 MW | 1.33 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 958212 | AF2-115 E | Adder | 1.04 MW | 0.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962561 | AG1-105 C O1 | Adder | 5.92 MW | 5.03 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 962562 | AG1-105 E O1 | Adder | 3.95 MW | 3.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 313527 | AB2-043 C | 50/50 | 0.55 MW | 0.55 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | 924022 | AB2-043 E O1 | 50/50 | 2.87 MW | 2.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.45 MW | 0.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.35 MW | 1.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.68 MW | 0.68 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.37 MW | 0.37 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.78 MW | 0.78 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.26 MW | 1.26 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 102802 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.46 MW | 0.46 MW |
| Details for AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963321 | AG1-181 C O1 | 50/50 | 101.09 MW | 101.09 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 963361 | AG1-185 O1 | 50/50 | 48.91 MW | 48.91 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| AG1-181 TAP-AG1-427 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963362 | AG1-185 BAT | 50/50 | 13.36 MW | 13.36 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 18.62 MW | 18.62 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 12.41 MW | 12.41 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 2.96 MW | 2.96 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 1.97 MW | 1.97 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 12.74 MW | 12.74 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 3.78 MW | 3.78 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 57.77 MW | 57.77 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 38.51 MW | 38.51 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 9.63 MW | 9.63 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 0.99 MW | 0.99 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.67 MW | 0.67 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 6.08 MW | 6.08 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 8.37 MW | 8.37 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 5.58 MW | 5.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 28.88 MW | 28.88 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 19.26 MW | 19.26 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 61.26 MW | 61.26 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 40.84 MW | 40.84 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 80.51 MW | 80.51 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 53.94 MW | 53.94 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 1.21 MW | 1.21 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 7.68 MW | 7.68 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 24.25 MW | 24.25 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 13.25 MW | 13.25 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 6.06 MW | 6.06 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.04 MW | 4.04 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 3.7 MW | 3.7 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.46 MW | 2.46 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963362 | AG1-185 BAT | 50/50 | 13.36 MW | 13.36 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.04 MW | 0.04 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961791 | AG1-021 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961891 | AG1-030 C | 50/50 | 26.7 MW | 26.7 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 961892 | AG1-030 E | 50/50 | 17.8 MW | 17.8 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963171 | AG1-166 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963181 | AG1-167 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963191 | AG1-168 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963201 | AG1-169 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963211 | AG1-170 C | 50/50 | 3.56 MW | 3.56 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963301 | AG1-179 C | Adder | 5.32 MW | 4.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963311 | AG1-180 | Adder | 2.59 MW | 2.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963321 | AG1-181 C O1 | 50/50 | 29.96 MW | 29.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 963361 | AG1-185 O1 | 50/50 | 14.5 MW | 14.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964111 | AG1-272 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964112 | AG1-272 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964121 | AG1-273 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964122 | AG1-273 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964131 | AG1-274 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964132 | AG1-274 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964241 | AG1-285 C O1 | 50/50 | 22.23 MW | 22.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964242 | AG1-285 E O1 | 50/50 | 14.82 MW | 14.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964791 | AG1-342 C | 50/50 | 16.45 MW | 16.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 964792 | AG1-342 E | 50/50 | 12.93 MW | 12.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965191 | AG1-384 C | 50/50 | 4.57 MW | 4.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965192 | AG1-384 E | 50/50 | 1.36 MW | 1.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965591 | AG1-427 C | 50/50 | 21.07 MW | 21.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965592 | AG1-427 E | 50/50 | 14.08 MW | 14.08 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965601 | AG1-428 C O2 | Adder | 4.44 MW | 3.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965602 | AG1-428 E O2 | Adder | 2.96 MW | 2.51 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965641 | AG1-432 C O1 | 50/50 | 35.57 MW | 35.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965642 | AG1-432 E O1 | 50/50 | 23.71 MW | 23.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965721 | AG1-440 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965722 | AG1-440 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965731 | AG1-441 C | Adder | 6.51 MW | 5.54 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965732 | AG1-441 E | Adder | 4.34 MW | 3.69 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965771 | AG1-445 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965781 | AG1-446 | Adder | 3.76 MW | 3.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 965831 | AG1-451 | 50/50 | 5.93 MW | 5.93 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313853 | 3PONTONDP | 50/50 | 1.19 MW | 1.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315159 | 1KERR 2 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315160 | 1KERR 3 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315161 | 1KERR 4 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315162 | 1KERR 5 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925785 | AC1-054 E | Adder | 2.36 MW | 2.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 926274 | AC1-105 E | 50/50 | 12.87 MW | 12.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936265 | AD2-033 C | 50/50 | 23.14 MW | 23.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 936266 | AD2-033 E | 50/50 | 15.43 MW | 15.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942461 | AE2-259 C O1 | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 942462 | AE2-259 E O1 | 50/50 | 11.86 MW | 11.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 943901 | AF1-058 C | Adder | -1.13 MW | -0.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958801 | AF2-171 C | 50/50 | 26.68 MW | 26.68 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958802 | AF2-171 E | 50/50 | 17.78 MW | 17.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959311 | AF2-222 C | 50/50 | 29.64 MW | 29.64 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 959312 | AF2-222 E | 50/50 | 19.86 MW | 19.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 315163 | 1KERR 6 | 50/50 | 1.16 MW | 1.16 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316118 | AC1-105 C | 50/50 | 26.91 MW | 26.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316129 | AC1-054 C | Adder | 5.13 MW | 4.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 316131 | AB2-060 C | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924162 | AB2-060 E OP | 50/50 | 7.6 MW | 7.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924301 | AB2-077 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924302 | AB2-077 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924311 | AB2-078 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924312 | AB2-078 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924321 | AB2-079 C O1 | 50/50 | 3.36 MW | 3.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924322 | AB2-079 E O1 | 50/50 | 2.24 MW | 2.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 925612 | AC1-036 E | 50/50 | 2.76 MW | 2.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938371 | AE1-056 C | 50/50 | 11.5 MW | 11.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 938372 | AE1-056 E | 50/50 | 6.28 MW | 6.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939181 | AE1-148 C | 50/50 | 10.18 MW | 10.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 939182 | AE1-148 E | 50/50 | 6.79 MW | 6.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 940661 | AE2-053 O1 | 50/50 | 3.77 MW | 3.77 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946301 | AF1-294 C | 50/50 | 7.3 MW | 7.3 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 946302 | AF1-294 E | 50/50 | 4.87 MW | 4.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958211 | AF2-115 C | 50/50 | 4.45 MW | 4.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 958212 | AF2-115 E | 50/50 | 2.97 MW | 2.97 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962561 | AG1-105 C O1 | 50/50 | 32.22 MW | 32.22 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 962562 | AG1-105 E O1 | 50/50 | 21.48 MW | 21.48 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | 924022 | AB2-043 E O1 | 50/50 | 5.01 MW | 5.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.21 MW | 0.21 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 0.24 MW | 0.24 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.19 MW | 0.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.11 MW | 0.11 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.28 MW | 0.28 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 15832 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961792 | AG1-021 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961891 | AG1-030 C | 50/50 | 26.6 MW | 26.6 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963172 | AG1-166 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963182 | AG1-167 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963192 | AG1-168 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963202 | AG1-169 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963212 | AG1-170 E | 50/50 | 2.37 MW | 2.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965592 | AG1-427 E | 50/50 | 14.02 MW | 14.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965641 | AG1-432 C O1 | 50/50 | 35.43 MW | 35.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965642 | AG1-432 E O1 | 50/50 | 23.62 MW | 23.62 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 314713 | 3PAMPLIN | 50/50 | 2.87 MW | 2.87 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 926274 | AC1-105 E | 50/50 | 12.85 MW | 12.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942461 | AE2-259 C O1 | 50/50 | 17.71 MW | 17.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 942462 | AE2-259 E O1 | 50/50 | 11.81 MW | 11.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958801 | AF2-171 C | 50/50 | 26.57 MW | 26.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958802 | AF2-171 E | 50/50 | 17.71 MW | 17.71 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959311 | AF2-222 C | 50/50 | 29.52 MW | 29.52 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 959312 | AF2-222 E | 50/50 | 19.78 MW | 19.78 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316118 | AC1-105 C | 50/50 | 26.86 MW | 26.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-5: FARMVIL L432 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961791 | AG1-021 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961792 | AG1-021 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961891 | AG1-030 C | 50/50 | 26.59 MW | 26.59 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 961892 | AG1-030 E | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963171 | AG1-166 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963172 | AG1-166 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963181 | AG1-167 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963182 | AG1-167 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963191 | AG1-168 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963192 | AG1-168 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963201 | AG1-169 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963202 | AG1-169 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963211 | AG1-170 C | 50/50 | 3.55 MW | 3.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963212 | AG1-170 E | 50/50 | 2.36 MW | 2.36 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963301 | AG1-179 C | Adder | 5.29 MW | 4.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963311 | AG1-180 | Adder | 2.58 MW | 2.19 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963321 | AG1-181 C O1 | 50/50 | 29.85 MW | 29.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 963361 | AG1-185 O1 | 50/50 | 14.44 MW | 14.44 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964111 | AG1-272 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964112 | AG1-272 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964121 | AG1-273 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964122 | AG1-273 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964131 | AG1-274 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964132 | AG1-274 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964241 | AG1-285 C O1 | 50/50 | 22.14 MW | 22.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964242 | AG1-285 E O1 | 50/50 | 14.76 MW | 14.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964791 | AG1-342 C | 50/50 | 16.42 MW | 16.42 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 964792 | AG1-342 E | 50/50 | 12.9 MW | 12.9 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965191 | AG1-384 C | 50/50 | 4.55 MW | 4.55 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965192 | AG1-384 E | 50/50 | 1.35 MW | 1.35 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965591 | AG1-427 C | 50/50 | 20.99 MW | 20.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965592 | AG1-427 E | 50/50 | 14.03 MW | 14.03 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965601 | AG1-428 C O2 | Adder | 4.42 MW | 3.76 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965602 | AG1-428 E O2 | Adder | 2.94 MW | 2.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965641 | AG1-432 C O1 | 50/50 | 35.45 MW | 35.45 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965642 | AG1-432 E O1 | 50/50 | 23.63 MW | 23.63 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965721 | AG1-440 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965722 | AG1-440 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965731 | AG1-441 C | Adder | 6.47 MW | 5.5 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965732 | AG1-441 E | Adder | 4.31 MW | 3.67 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965771 | AG1-445 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965781 | AG1-446 | Adder | 3.74 MW | 3.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 965831 | AG1-451 | 50/50 | 5.91 MW | 5.91 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313853 | 3PONTONDP | 50/50 | 1.18 MW | 1.18 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314429 | 3JTRSVLE | 50/50 | 0.81 MW | 0.81 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 314713 | 3PAMPLIN | 50/50 | 2.88 MW | 2.88 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315159 | 1KERR 2 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315160 | 1KERR 3 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315161 | 1KERR 4 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925785 | AC1-054 E | Adder | 2.35 MW | 2.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 926274 | AC1-105 E | 50/50 | 12.85 MW | 12.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 927261 | AC1-222 C | Adder | -2.04 MW | -1.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 934311 | AD1-055 C | Adder | -1.42 MW | -1.2 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936265 | AD2-033 C | 50/50 | 23.05 MW | 23.05 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 936266 | AD2-033 E | 50/50 | 15.37 MW | 15.37 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942461 | AE2-259 C O1 | 50/50 | 17.73 MW | 17.73 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 942462 | AE2-259 E O1 | 50/50 | 11.82 MW | 11.82 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 943901 | AF1-058 C | Adder | -1.15 MW | -0.98 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958801 | AF2-171 C | 50/50 | 26.58 MW | 26.58 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958802 | AF2-171 E | 50/50 | 17.72 MW | 17.72 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959311 | AF2-222 C | 50/50 | 29.53 MW | 29.53 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 959312 | AF2-222 E | 50/50 | 19.79 MW | 19.79 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315163 | 1KERR 6 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 315164 | 1KERR 7 | 50/50 | 1.15 MW | 1.15 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316118 | AC1-105 C | 50/50 | 26.86 MW | 26.86 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316129 | AC1-054 C | Adder | 5.1 MW | 4.33 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 316131 | AB2-060 C | 50/50 | 2.74 MW | 2.74 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924162 | AB2-060 E OP | 50/50 | 7.57 MW | 7.57 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924301 | AB2-077 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924302 | AB2-077 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924311 | AB2-078 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924312 | AB2-078 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924321 | AB2-079 C O1 | 50/50 | 3.34 MW | 3.34 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924322 | AB2-079 E O1 | 50/50 | 2.23 MW | 2.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925611 | AC1-036 C | 50/50 | 0.43 MW | 0.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 925612 | AC1-036 E | 50/50 | 2.75 MW | 2.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938371 | AE1-056 C | 50/50 | 11.46 MW | 11.46 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 938372 | AE1-056 E | 50/50 | 6.26 MW | 6.26 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939181 | AE1-148 C | 50/50 | 10.13 MW | 10.13 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 939182 | AE1-148 E | 50/50 | 6.75 MW | 6.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 940661 | AE2-053 O1 | 50/50 | 3.75 MW | 3.75 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946301 | AF1-294 C | 50/50 | 7.27 MW | 7.27 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 946302 | AF1-294 E | 50/50 | 4.85 MW | 4.85 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958211 | AF2-115 C | 50/50 | 4.43 MW | 4.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 958212 | AF2-115 E | 50/50 | 2.96 MW | 2.96 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962561 | AG1-105 C O1 | 50/50 | 32.14 MW | 32.14 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 962562 | AG1-105 E O1 | 50/50 | 21.43 MW | 21.43 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 313527 | AB2-043 C | 50/50 | 0.95 MW | 0.95 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | 924022 | AB2-043 E O1 | 50/50 | 4.99 MW | 4.99 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.04 MW | 0.04 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.12 MW | 0.12 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.02 MW | 0.02 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.23 MW | 0.23 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.06 MW | 0.06 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.01 MW | 0.01 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.31 MW | 0.31 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.07 MW | 0.07 MW |
| AC1-105 TAP-3SEDGE HILL 115.0 kV Ckt 1 line l/o DVP_P4-2: 235T298 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.03 MW | 0.03 MW |
| Details for 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3TWITTYS-3CENTRAL 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964111 | AG1-272 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964112 | AG1-272 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964121 | AG1-273 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964122 | AG1-273 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964131 | AG1-274 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 964132 | AG1-274 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965191 | AG1-384 C | 50/50 | 15.42 MW | 15.42 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 965192 | AG1-384 E | 50/50 | 4.58 MW | 4.58 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 314713 | 3PAMPLIN | 50/50 | 9.73 MW | 9.73 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958801 | AF2-171 C | 50/50 | 90.0 MW | 90.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 958802 | AF2-171 E | 50/50 | 60.0 MW | 60.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959311 | AF2-222 C | 50/50 | 100.0 MW | 100.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 959312 | AF2-222 E | 50/50 | 67.0 MW | 67.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925611 | AC1-036 C | 50/50 | 1.47 MW | 1.47 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 925612 | AC1-036 E | 50/50 | 9.3 MW | 9.3 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938371 | AE1-056 C | 50/50 | 38.8 MW | 38.8 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | 938372 | AE1-056 E | 50/50 | 21.2 MW | 21.2 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_G-007 | LTFEXP_G-007->LTFIMP_G-007 | CMTX_NF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.0 MW | 0.0 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_O-066 | LTFEXP_O-066->LTFIMP_O-066 | CMTX_NF | 0.03 MW | 0.03 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 0.01 MW | 0.01 MW |
| 3CENTRAL-AG1-181 TAP 115.0 kV Ckt 1 line l/o DVP_P4-2: 8442 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.0 MW | 0.0 MW |
| Details for 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961791 | AG1-021 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961792 | AG1-021 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961891 | AG1-030 C | 50/50 | 11.7 MW | 11.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 961892 | AG1-030 E | 50/50 | 7.8 MW | 7.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963171 | AG1-166 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963172 | AG1-166 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963181 | AG1-167 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963182 | AG1-167 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963191 | AG1-168 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963192 | AG1-168 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963201 | AG1-169 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963202 | AG1-169 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963211 | AG1-170 C | Adder | 1.42 MW | 1.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963212 | AG1-170 E | Adder | 0.94 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963301 | AG1-179 C | Adder | 3.17 MW | 2.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963311 | AG1-180 | Adder | 1.55 MW | 1.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963321 | AG1-181 C O1 | 50/50 | 15.97 MW | 15.97 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 963361 | AG1-185 O1 | 50/50 | 7.73 MW | 7.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964111 | AG1-272 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964112 | AG1-272 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964121 | AG1-273 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964122 | AG1-273 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964131 | AG1-274 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964132 | AG1-274 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964241 | AG1-285 C O1 | 50/50 | 13.59 MW | 13.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964242 | AG1-285 E O1 | 50/50 | 9.06 MW | 9.06 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964791 | AG1-342 C | Adder | 2.83 MW | 2.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 964792 | AG1-342 E | Adder | 2.22 MW | 1.89 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965191 | AG1-384 C | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965192 | AG1-384 E | 50/50 | 0.7 MW | 0.7 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965591 | AG1-427 C | 50/50 | 12.83 MW | 12.83 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965592 | AG1-427 E | 50/50 | 8.57 MW | 8.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965601 | AG1-428 C O2 | Adder | 2.65 MW | 2.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965602 | AG1-428 E O2 | Adder | 1.76 MW | 1.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965641 | AG1-432 C O1 | Adder | 8.76 MW | 7.45 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965642 | AG1-432 E O1 | Adder | 5.84 MW | 4.96 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965721 | AG1-440 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965722 | AG1-440 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965731 | AG1-441 C | 50/50 | 15.95 MW | 15.95 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965732 | AG1-441 E | 50/50 | 10.63 MW | 10.63 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965771 | AG1-445 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965781 | AG1-446 | 50/50 | 9.21 MW | 9.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 965831 | AG1-451 | Adder | 1.46 MW | 1.24 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313853 | 3PONTONDP | Adder | 0.47 MW | 0.4 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 314713 | 3PAMPLIN | Adder | 1.03 MW | 0.88 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315158 | 1KERR 1 | 50/50 | 0.91 MW | 0.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315159 | 1KERR 2 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315160 | 1KERR 3 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315161 | 1KERR 4 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315162 | 1KERR 5 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 926274 | AC1-105 E | Adder | 1.38 MW | 1.18 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936265 | AD2-033 C | 50/50 | 12.47 MW | 12.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 936266 | AD2-033 E | 50/50 | 8.31 MW | 8.31 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942461 | AE2-259 C O1 | Adder | 4.38 MW | 3.72 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 942462 | AE2-259 E O1 | Adder | 2.92 MW | 2.48 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958801 | AF2-171 C | 50/50 | 10.69 MW | 10.69 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958802 | AF2-171 E | 50/50 | 7.13 MW | 7.13 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959311 | AF2-222 C | 50/50 | 14.73 MW | 14.73 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 959312 | AF2-222 E | 50/50 | 9.87 MW | 9.87 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315163 | 1KERR 6 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 315164 | 1KERR 7 | 50/50 | 2.54 MW | 2.54 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316118 | AC1-105 C | Adder | 2.89 MW | 2.46 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 316131 | AB2-060 C | 50/50 | 1.75 MW | 1.75 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924162 | AB2-060 E OP | 50/50 | 4.84 MW | 4.84 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924301 | AB2-077 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924302 | AB2-077 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924311 | AB2-078 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924312 | AB2-078 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924321 | AB2-079 C O1 | 50/50 | 2.35 MW | 2.35 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924322 | AB2-079 E O1 | 50/50 | 1.57 MW | 1.57 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925611 | AC1-036 C | 50/50 | 0.22 MW | 0.22 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 925612 | AC1-036 E | 50/50 | 1.42 MW | 1.42 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938371 | AE1-056 C | Adder | 4.11 MW | 3.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 938372 | AE1-056 E | Adder | 2.25 MW | 1.91 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939181 | AE1-148 C | 50/50 | 17.39 MW | 17.39 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 939182 | AE1-148 E | 50/50 | 11.59 MW | 11.59 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 940661 | AE2-053 O1 | 50/50 | 6.44 MW | 6.44 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946301 | AF1-294 C | Adder | 2.9 MW | 2.47 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 946302 | AF1-294 E | Adder | 1.94 MW | 1.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958211 | AF2-115 C | Adder | 1.77 MW | 1.51 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 958212 | AF2-115 E | Adder | 1.18 MW | 1.0 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962561 | AG1-105 C O1 | 50/50 | 6.74 MW | 6.74 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 962562 | AG1-105 E O1 | 50/50 | 4.5 MW | 4.5 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 313527 | AB2-043 C | 50/50 | 0.62 MW | 0.62 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | 924022 | AB2-043 E O1 | 50/50 | 3.25 MW | 3.25 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-056 | LTFEXP_AC1-056->LTFIMP_AC1-056 | CLTF | 0.43 MW | 0.43 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_AC1-131 | LTFEXP_AC1-131->LTFIMP_AC1-131 | CLTF | 1.36 MW | 1.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_BlueG | LTFEXP_BlueG->LTFIMP_BlueG | CLTF | 0.65 MW | 0.65 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CALDERWOOD | LTFEXP_CALDERWOOD->LTFIMP_CALDERWOOD | CLTF | 0.36 MW | 0.36 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CATAWBA | LTFEXP_CATAWBA->LTFIMP_CATAWBA | CLTF | 0.41 MW | 0.41 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CBM-N | LTFEXP_CBM-N->LTFIMP_CBM-N | CBM | 0.05 MW | 0.05 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_CHEOAH | LTFEXP_CHEOAH->LTFIMP_CHEOAH | CLTF | 0.38 MW | 0.38 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_COTTONWOOD | LTFEXP_COTTONWOOD->LTFIMP_COTTONWOOD | CLTF | 1.34 MW | 1.34 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_G-007A | LTFEXP_G-007A->LTFIMP_G-007A | CMTX | 0.17 MW | 0.17 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_GIBSON | LTFEXP_GIBSON->LTFIMP_GIBSON | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_HAMLET | LTFEXP_HAMLET->LTFIMP_HAMLET | CLTF | 0.8 MW | 0.8 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_PRAIRIE | LTFEXP_PRAIRIE->LTFIMP_PRAIRIE | CLTF | 1.23 MW | 1.23 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_TRIMBLE | LTFEXP_TRIMBLE->LTFIMP_TRIMBLE | CLTF | 0.21 MW | 0.21 MW |
| 3KERR-3GW KING TAP 115.0 kV Ckt 1 line l/o DVP_P7-1: LN 22-90 | LTFEXP_VFT | LTFEXP_VFT->LTFIMP_VFT | CLTF | 0.45 MW | 0.45 MW |
Light Load Analysis
The Queue Project was evaluated as a 20.0 MW (Capacity 15.42 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
(No impacts were found for this analysis)
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n6113 | Add additional 230/115 kV transformer at Carolina substation. | $6,000,000 | |
| n7766 | Rebuild 115 kV Line #1012 From AD2-063 Tap-AG1-181 Tap-Central-Twitty's Creek-AF2-222 Tap-Madsonav | $24,835,000 | |
| n7821 | Wreck and rebuild 115 kV line #1012 from Chase City to AG1-285 Tap | $13,400,000 | |
| n7819 | Wreck and rebuild 115 kV line #84 from Willis to Farmville to a double circuit. | $20,050,000 | |
| n6246 | Add additional 230/115 kV transformer (#3) for Circuit 1 at Farmville substation | $6,000,000 | |
| n7550 | Add additional 230/115 kV transformer (#4) for Circuit 2 at Farmville substation. | $6,000,000 | |
| (TBD) | Reconductor 20 miles with single 795 ACSS-TW per phase, replace breaker, disconnect switches, wave trap, line switch | $60,000,000 | |
| s2614 | For DEV portion, rebuild 4.7 miles of 115 kV Line 45 from Kerr Dam to GW King Tap with 768 ACSS. | $6,123,000 | |
| n7667 | Rebuild 115 kV Line #33 from Mt. Laurel -AC1-105 Tap -Sedge Hill. | $16,590,000 | |
| n7826 | Rebuild 115 kV line #84 from Willis Mountain to Pamplin. | $20,730,000 | |
| n7687 | Add additional 230/115 kV transformer at Sedge Hill substation. | $6,000,000 | |
| n7796 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Midlothian with 2-795 ACSR 150 C. | $17,725,000 | |
| n7797 | Rebuild 7.09 miles of 230 kV Line 2027 from Judes to Powhatan with 2-795 ACSR 150 C | $17,725,000 | |
| n6539 | Build new 500 kV Line from Rawlings to Morrisville Substation 110 miles | $400,000,000 | |
| n7823 | Wreck and rebuild 115 kV line#1012 from AG1-427 Tap to AG1-285 Tap | $3,150,000 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-272 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.