AG1-196 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1

v1.00 released 2023-12-14 10:52

Grottoes 115 kV

150.0 MW Capacity / 150.0 MW Energy

Introduction

In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.

Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.

Transition Cycle #1:

The AG1-196 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.

Transition Sort Retool Study Process and Criteria:

In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).

Expedited Process Eligibility: OATT Tariff Part VII, section 304:

A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.

Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.

Transition Sort Retool Results Provided:

This report includes a list of:

  1. the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
  2. other interconnection projects that may also contribute to the overloaded facility, and
  3. the total estimated cost for any required Network Upgrades.

Important Notes:

Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.

Notes regarding Results displayed:

  1. Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
  2. For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.

Next Steps for your project:

Transition Cycle #1 Rules:

Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.

Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.

Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:

  1. Phase I System Impact Study and Decision Point I; and
  2. Phase II System Impact Study and Decision Point II; and
  3. Phase III System Impact Study and Decision Point III

Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.

General

The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the Dominion zone — Augusta County, Virginia. The installed facilities will have a total capability of 150.0 MW with 150.0 MW of this output being recognized by PJM as Capacity.

Project Information
Queue Number AG1-196
Project Name Grottoes 115 kV
Developer Name Hecate Energy Grottoes Solar LLC
State Virginia
County Augusta
Transmission Owner Dominion
MFO 150.0 MW
MWE 150.0 MW
MWC 150.0 MW
Fuel Type Solar; Storage
Basecase Study Year 2024

Point of Interconnection

AG1-196 "Grottoes 115 kV" will interconnect with the Dominion transmission system.

 

Summer Peak Analysis

The Queue Project was evaluated as a 150.0 MW (Capacity 150.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:

Important to Note:

Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.

Notes regarding Results displayed:

  1. Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
  2. For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Summer Peak Analysis
Area Facility Description Contingency Name Contingency Type DC|AC Initial Loading Final Loading Rating (MVA) Rating Type MVA to Mitigate MW Contribution Details
DVP 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1
DVP_P1-2: LN 553
CONTINGENCY 'DVP_P1-2: LN 553'
 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1   /*8ELMONT      500.0 - 8CUNINGHAM   500.0
END
Single AC 111.38 % 114.38 % 550.84 B 630.02 16.03
DVP 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1
DVP_P1-2: LN 550
CONTINGENCY 'DVP_P1-2: LN 550'
 OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1                /*8MT STM      500.0 - 8VALLEY      500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
END
Single AC 103.78 % 107.08 % 550.84 B 589.84 17.34
DVP 3ENDLCAV-3N SHEND 115.0 kV Ckt 1 line
314799 to 314809 ckt 1
DVP_P4-2: 272T291
CONTINGENCY 'DVP_P4-2: 272T291'
 OPEN BRANCH FROM BUS 314741 TO BUS 314749 CKT 1   /*6BARRCK1     230.0 - 6CHARLVL     230.0
 OPEN BRANCH FROM BUS 314741 TO BUS 314752 CKT 1   /*6BARRCK1     230.0 - 6CROZET2     230.0
 OPEN BRANCH FROM BUS 314752 TO BUS 314794 CKT 1   /*6CROZET2     230.0 - 6DOOMS       230.0
 OPEN BRANCH FROM BUS 314793 TO BUS 314794 CKT 3   /*3DOOMS       115.0 - 6DOOMS       230.0
 OPEN BRANCH FROM BUS 314794 TO BUS 314803 CKT 1   /*6DOOMS       230.0 - 6GROTOES     230.0
 OPEN BRANCH FROM BUS 314794 TO BUS 314893 CKT 1   /*6DOOMS       230.0 - 6DOOMS_1     230.0
 OPEN BRANCH FROM BUS 314802 TO BUS 314803 CKT 1   /*3GROTOES     115.0 - 6GROTOES     230.0
 OPEN BUS 314741                                   /*6BARRCK1     230.0
 OPEN BUS 314752                                   /*6CROZET2     230.0
 OPEN BUS 314893                                   /*6DOOMS_1     230.0
END
Breaker AC 71.62 % 128.91 % 251.0 C 323.56 114.26
DVP 3ENDLCAV-3N SHEND 115.0 kV Ckt 1 line
314799 to 314809 ckt 1
DVP_P4-2: 260T272
CONTINGENCY 'DVP_P4-2: 260T272'
 OPEN BRANCH FROM BUS 314793 TO BUS 314794 CKT 3   /*3DOOMS       115.0 - 6DOOMS       230.0
 OPEN BRANCH FROM BUS 314794 TO BUS 314803 CKT 1   /*6DOOMS       230.0 - 6GROTOES     230.0
 OPEN BRANCH FROM BUS 314794 TO BUS 314893 CKT 1   /*6DOOMS       230.0 - 6DOOMS_1     230.0
 OPEN BRANCH FROM BUS 314802 TO BUS 314803 CKT 1   /*3GROTOES     115.0 - 6GROTOES     230.0
 OPEN BRANCH FROM BUS 314803 TO BUS 314806 CKT 1   /*6GROTOES     230.0 - 6HARSNBG     230.0
 OPEN BUS 314893                                   /*6DOOMS_1     230.0
END
Breaker AC 71.07 % 128.41 % 251.0 C 322.31 114.3
DVP 3N SHEND-3MERCK5 115.0 kV Ckt 1 line
314809 to 314798 ckt 1
DVP_P4-2: 260T272
CONTINGENCY 'DVP_P4-2: 260T272'
 OPEN BRANCH FROM BUS 314793 TO BUS 314794 CKT 3   /*3DOOMS       115.0 - 6DOOMS       230.0
 OPEN BRANCH FROM BUS 314794 TO BUS 314803 CKT 1   /*6DOOMS       230.0 - 6GROTOES     230.0
 OPEN BRANCH FROM BUS 314794 TO BUS 314893 CKT 1   /*6DOOMS       230.0 - 6DOOMS_1     230.0
 OPEN BRANCH FROM BUS 314802 TO BUS 314803 CKT 1   /*3GROTOES     115.0 - 6GROTOES     230.0
 OPEN BRANCH FROM BUS 314803 TO BUS 314806 CKT 1   /*6GROTOES     230.0 - 6HARSNBG     230.0
 OPEN BUS 314893                                   /*6DOOMS_1     230.0
END
Breaker AC 31.25 % 109.33 % 251.0 C 274.41 150.0
DVP 6GROTOES-3GROTOES 230.0/115.0 kV Ckt 1 transformer
314803 to 314802 ckt 1
DVP_P7-1: LN 2017-2134-A
CONTINGENCY 'DVP_P7-1: LN 2017-2134-A'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314800 TO BUS 944070 CKT 1   /*6ENDLCAV     230.0 - AF1-075 TAP  230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 104.91 % 153.66 % 294.1 C 451.92 121.81
DVP 6GROTOES-3GROTOES 230.0/115.0 kV Ckt 1 transformer
314803 to 314802 ckt 1
DVP_P7-1: LN 2017-2134-B
CONTINGENCY 'DVP_P7-1: LN 2017-2134-B'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314805 TO BUS 314806 CKT 1   /*6E MARKET ST 230.0 - 6HARSNBG     230.0
 OPEN BRANCH FROM BUS 944070 TO BUS 314806 CKT 1   /*AF1-075 TAP  230.0 - 6HARSNBG     230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 104.79 % 153.4 % 294.1 C 451.15 121.81
DVP AE2-029 TAP-3ELKTON 115.0 kV Ckt 1 line
940450 to 313706 ckt 1
DVP_P7-1: LN 2017-2134-A
CONTINGENCY 'DVP_P7-1: LN 2017-2134-A'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314800 TO BUS 944070 CKT 1   /*6ENDLCAV     230.0 - AF1-075 TAP  230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 119.07 % 132.38 % 251.0 C 332.27 28.19
DVP AE2-029 TAP-3ELKTON 115.0 kV Ckt 1 line
940450 to 313706 ckt 1
DVP_P7-1: LN 2017-2134-B
CONTINGENCY 'DVP_P7-1: LN 2017-2134-B'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314805 TO BUS 314806 CKT 1   /*6E MARKET ST 230.0 - 6HARSNBG     230.0
 OPEN BRANCH FROM BUS 944070 TO BUS 314806 CKT 1   /*AF1-075 TAP  230.0 - 6HARSNBG     230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 118.88 % 132.11 % 251.0 C 331.59 28.19
DVP 3ELKTON-3MERCK5 115.0 kV Ckt 1 line
313706 to 314798 ckt 1
DVP_P7-1: LN 2017-2134-A
CONTINGENCY 'DVP_P7-1: LN 2017-2134-A'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314800 TO BUS 944070 CKT 1   /*6ENDLCAV     230.0 - AF1-075 TAP  230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 116.92 % 130.17 % 251.0 C 326.72 28.19
DVP 3ELKTON-3MERCK5 115.0 kV Ckt 1 line
313706 to 314798 ckt 1
DVP_P7-1: LN 2017-2134-B
CONTINGENCY 'DVP_P7-1: LN 2017-2134-B'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314805 TO BUS 314806 CKT 1   /*6E MARKET ST 230.0 - 6HARSNBG     230.0
 OPEN BRANCH FROM BUS 944070 TO BUS 314806 CKT 1   /*AF1-075 TAP  230.0 - 6HARSNBG     230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 116.73 % 129.91 % 251.0 C 326.06 28.19
DVP 3GROTOES-AE2-029 TAP 115.0 kV Ckt 1 line
314802 to 940450 ckt 1
DVP_P7-1: LN 2017-2134-A
CONTINGENCY 'DVP_P7-1: LN 2017-2134-A'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314800 TO BUS 944070 CKT 1   /*6ENDLCAV     230.0 - AF1-075 TAP  230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 114.47 % 127.77 % 251.0 C 320.69 28.19
DVP 3GROTOES-AE2-029 TAP 115.0 kV Ckt 1 line
314802 to 940450 ckt 1
DVP_P7-1: LN 2017-2134-B
CONTINGENCY 'DVP_P7-1: LN 2017-2134-B'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314805 TO BUS 314806 CKT 1   /*6E MARKET ST 230.0 - 6HARSNBG     230.0
 OPEN BRANCH FROM BUS 944070 TO BUS 314806 CKT 1   /*AF1-075 TAP  230.0 - 6HARSNBG     230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 114.28 % 127.49 % 251.0 C 320.0 28.19
DVP 3N SHEND-3ENDLCAV 115.0 kV Ckt 1 line
314809 to 314799 ckt 1
DVP_P7-1: LN 2017-2134-A
CONTINGENCY 'DVP_P7-1: LN 2017-2134-A'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314800 TO BUS 944070 CKT 1   /*6ENDLCAV     230.0 - AF1-075 TAP  230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 112.87 % 119.39 % 251.0 C 299.67 14.79
DVP 3N SHEND-3ENDLCAV 115.0 kV Ckt 1 line
314809 to 314799 ckt 1
DVP_P7-1: LN 2017-2134-B
CONTINGENCY 'DVP_P7-1: LN 2017-2134-B'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314805 TO BUS 314806 CKT 1   /*6E MARKET ST 230.0 - 6HARSNBG     230.0
 OPEN BRANCH FROM BUS 944070 TO BUS 314806 CKT 1   /*AF1-075 TAP  230.0 - 6HARSNBG     230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 112.39 % 118.86 % 251.0 C 298.33 14.79
DVP 3MERCK5-3N SHEND 115.0 kV Ckt 1 line
314798 to 314809 ckt 1
DVP_P7-1: LN 2017-2134-A
CONTINGENCY 'DVP_P7-1: LN 2017-2134-A'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314800 TO BUS 944070 CKT 1   /*6ENDLCAV     230.0 - AF1-075 TAP  230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 93.54 % 106.64 % 251.0 C 267.66 28.19
DVP 3MERCK5-3N SHEND 115.0 kV Ckt 1 line
314798 to 314809 ckt 1
DVP_P7-1: LN 2017-2134-B
CONTINGENCY 'DVP_P7-1: LN 2017-2134-B'
 OPEN BRANCH FROM BUS 314800 TO BUS 314805 CKT 1   /*6ENDLCAV     230.0 - 6E MARKET ST 230.0
 OPEN BRANCH FROM BUS 314805 TO BUS 314806 CKT 1   /*6E MARKET ST 230.0 - 6HARSNBG     230.0
 OPEN BRANCH FROM BUS 944070 TO BUS 314806 CKT 1   /*AF1-075 TAP  230.0 - 6HARSNBG     230.0
 OPEN BUS 314805                                   /*6E MARKET ST 230.0
END
Tower AC 93.36 % 106.4 % 251.0 C 267.05 28.19

Light Load Analysis

The Queue Project was evaluated as a 150.0 MW (Capacity 150.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:

Important to Note:

Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.

Notes regarding Results displayed:

  1. Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
  2. For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Light Load Analysis
Area Facility Description Contingency Name Contingency Type DC|AC Initial Loading Final Loading Rating (MVA) Rating Type MVA to Mitigate MW Contribution Details
DVP 6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
Single DC 122.33 % 123.76 % 678.68 B 839.93 13.73
DVP 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
Single DC 121.3 % 122.72 % 678.68 B 832.88 13.73
DVP 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
Single AC 107.85 % 109.38 % 661.76 B 723.83 13.15
DVP 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
Single AC 102.73 % 103.6 % 661.76 B 685.58 10.03
DVP AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
Single AC 107.85 % 109.37 % 661.76 B 723.77 13.15
DVP 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
Single AC 105.78 % 107.3 % 661.76 B 710.07 13.15
DVP 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1
DVP_P1-2: LN 576
CONTINGENCY 'DVP_P1-2: LN 576'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
Single AC 100.5 % 101.37 % 661.76 B 670.83 10.03
DVP 3N SHEND-3MERCK5 115.0 kV Ckt 1 line
314809 to 314798 ckt 1
DVP_P1-2: LN 272
CONTINGENCY 'DVP_P1-2: LN 272'
 OPEN BRANCH FROM BUS 314793 TO BUS 314794 CKT 3   /*3DOOMS       115.0 - 6DOOMS       230.0
 OPEN BRANCH FROM BUS 314794 TO BUS 314803 CKT 1   /*6DOOMS       230.0 - 6GROTOES     230.0
 OPEN BRANCH FROM BUS 314794 TO BUS 314893 CKT 1   /*6DOOMS       230.0 - 6DOOMS_1     230.0
 OPEN BRANCH FROM BUS 314802 TO BUS 314803 CKT 1   /*3GROTOES     115.0 - 6GROTOES     230.0
 OPEN BUS 314893                                   /*6DOOMS_1     230.0
END
Single AC 19.44 % 108.82 % 204.92 B 222.99 150.0

System Reinforcements

The table below lists all network upgrades which resolve the identified overloaded facilities in this report.

Important to Note:

Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.

Notes regarding Results displayed:

  1. Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
  2. For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
  3. Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
System Reinforcements
RTEP ID Title Total Cost
n7627 Reconductor 115 kV line #119 from Elkton DP to Merck $1,482,000
n7633 Reconductor 115 kV Line #119 from Elkton to AE2-029 Tap. $3,186,000
n7632 Reconductor 115 kV Line 118 from N. Shenanddah to Endless Cavern. $4,452,000
n7629 Grottoes substation: 230/115 kV transformer Addition $6,000,000
n7628 Reconductor 115 kV Line #119 from Grottoes to AE2-029 Tap. $2,964,000
n7631 Reconductor 115 kV Line #118 from Merck to N. Shenanddah . $7,230,000
n5873 Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. $500,000
n6379 Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. $16,175,000
n7580 Rebuild 8.72 miles of 230 kV Line 2054 from Charlottesville to Profit D.P. with 2-636 ACSR 150 C $21,800,000
n7567 Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C $2,445,000
n6185.2 Rebuild 17.42 miles of 230 kV Line 2028 from Fork Union to Mount Eagle with 2-636 ACSR. $26,130,000

Attachments

Conclusion

The Transition Sort load flow retool results indicate that AG1-196 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.