AG1-195 Transition Sort Retool Results -- Reprioritized to Transition Cycle #1
v1.00 released 2023-12-14 10:44
Valley 230 kV
150.0 MW Capacity / 150.0 MW Energy
Introduction
In accordance with Tariff Part VII, Subpart B, section 304, PJM performed load flow analysis (Transition Sort Retool) on all AE1 through AG1 projects that have met eligibility requirements according to Tariff, Part VII, Subpart B, section 303. The purpose of this study is to determine whether a project would be classified as eligible for the Expedited Process (Fast Lane) or if it would be reprioritized to be studied as part of Transition Cycle #1 (TC1) using the criteria from the Expedited Process Eligibility section of Tariff Part VII, section 304. This is not a System Impact Study report.
Below are the results of the study, details of how the study was performed, criterion used in the evaluation of the Expedited Process vs. TC1 determination, and next steps in the interconnection process for your project.
Transition Cycle #1:
The AG1-195 project has not met the Expedited Process Eligibility requirements in Tariff Part VII, Subpart B, section 304 and will therefore be reprioritized to Transition Cycle #1. Please see "Transition Cycle #1 Rules" below.
Transition Sort Retool Study Process and Criteria:
In order to determine Expedited Process vs. Transition Cycle #1 classification, projects which met the Transition Eligibility requirements from Tariff Part VII, Subpart B, section 303 were studied on the base case model that was used for the original System Impact Study analysis. Both a summer peak and light load load flow analysis were performed. Projects that have cost allocation eligibility or are identified as the first to cause a system violation which requires the need for a Network Upgrade with a total estimated cost greater than $5 million will be reprioritized to Transition Cycle #1. All other projects will be eligible for the expedited procedures set forth in Tariff Part VII, Subpart B, section 304 (B).
Expedited Process Eligibility: OATT Tariff Part VII, section 304:
A project is not eligible for the expedited process if it has cost allocation eligibility or is identified as the first to cause, as determined according to Tariff, Part VI, section 217.3, for a Network Upgrade which has a total estimated cost of greater than $5,000,000. Such cost estimate will be based on Transmission Provider's most recently available data.
Not considered in the Transition Sorting: The cost of the Interconnection Facilities is not considered when determining a project's eligibility for the expedited process. Affected Systems upgrade costs are also not considered in the evaluation.
Transition Sort Retool Results Provided:
This report includes a list of:
- the overloaded flowgates (overloaded facilities + contingency pair) that the project contributes towards
- other interconnection projects that may also contribute to the overloaded facility, and
- the total estimated cost for any required Network Upgrades.
Important Notes:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
Next Steps for your project:
Transition Cycle #1 Rules:
Refer to Tariff Part VII, Subpart B, section 304 (C) for the Transition Cycle #1 Project Rules.
Transition Cycle #1 will start no later than one year from the Transition Start Date (July 10, 2023). Transition Cycle #1 will run simultaneously with the expedited process, however Transition Cycle #1, Phase III will not begin until all expedited process projects have been completed.
Projects that are reprioritized to Transition Cycle #1 will not need to re-apply to the Interconnection Cycle Process. Therefore, there is no Application Review Phase for Transition Cycle #1. The cycle process for Transition Cycle #1 includes three Study Phases and three Decision Points:
- Phase I System Impact Study and Decision Point I; and
- Phase II System Impact Study and Decision Point II; and
- Phase III System Impact Study and Decision Point III
Refer to Tariff Part VII, Subpart D, section 307 for the Transition Cycle #1 study process.
General
The Interconnection Customer (IC), has proposed a Solar; Storage generating facility located in the Dominion zone — Augusta County, Virginia. The installed facilities will have a total capability of 150.0 MW with 150.0 MW of this output being recognized by PJM as Capacity.
| Project Information | |
|---|---|
| Queue Number | AG1-195 |
| Project Name | Valley 230 kV |
| Developer Name | Hecate Energy Weyers Cave LLC |
| State | Virginia |
| County | Augusta |
| Transmission Owner | Dominion |
| MFO | 150.0 MW |
| MWE | 150.0 MW |
| MWC | 150.0 MW |
| Fuel Type | Solar; Storage |
| Basecase Study Year | 2024 |
Point of Interconnection
AG1-195 "Valley 230 kV" will interconnect with the Dominion transmission system. The primary POI is a direct connect to the Valley 230 kV substation.
Summer Peak Analysis
The Queue Project was evaluated as a 150.0 MW (Capacity 150.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential Summer peak period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Summer Peak Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1 |
DVP_P1-2: LN 553
CONTINGENCY 'DVP_P1-2: LN 553' OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT 500.0 - 8CUNINGHAM 500.0 END |
Single | AC | 108.73 % | 111.38 % | 550.84 | B | 613.5 | 14.13 | |
| DVP |
6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line
314749 to 314772 ckt 1 |
DVP_P1-2: LN 550
CONTINGENCY 'DVP_P1-2: LN 550' OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1 /*8MT STM 500.0 - 8VALLEY 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 END |
Single | AC | 100.7 % | 103.78 % | 550.84 | B | 571.68 | 16.21 | |
| DVP |
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
314908 to 314911 ckt 1 |
DVP_P1-2: LN 550
CONTINGENCY 'DVP_P1-2: LN 550' OPEN BRANCH FROM BUS 314917 TO BUS 314926 CKT 1 /*8MT STM 500.0 - 8VALLEY 500.0 SET POSTCONTRATING 3811 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 SET PRECONTRATING 3464 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J 500.0 - 8MT STM 500.0 END |
Single | AC | 108.85 % | 109.2 % | 2442.12 | B | 2666.87 | 31.18 | |
| Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 961801 | AG1-022 C | 80/20 | 1.12 MW | 1.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 962741 | AG1-123 C O1 | 80/20 | 1.95 MW | 1.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963021 | AG1-151 O1 | 80/20 | 8.16 MW | 8.16 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963471 | AG1-196 O1 | 80/20 | 16.03 MW | 16.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 964231 | AG1-284 C O1 | 80/20 | 5.0 MW | 5.0 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 964831 | AG1-346 C | 80/20 | 0.76 MW | 0.76 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965581 | AG1-426 | 80/20 | 1.7 MW | 1.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965641 | AG1-432 C O1 | 80/20 | 7.32 MW | 7.32 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965831 | AG1-451 | 80/20 | 1.22 MW | 1.22 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966251 | AG1-494 C | 80/20 | 1.05 MW | 1.05 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 942461 | AE2-259 C O1 | 80/20 | 3.66 MW | 3.66 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 960111 | AF2-302 C | 80/20 | 1.12 MW | 1.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938371 | AE1-056 C | 80/20 | 1.95 MW | 1.95 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938821 | AE1-108 C O1 | 80/20 | 8.96 MW | 8.96 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 941011 | AE2-092 C | 80/20 | 10.11 MW | 10.11 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 946291 | AF1-293 C O1 | 80/20 | 13.04 MW | 13.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 946591 | AF1-323 C | 80/20 | 3.07 MW | 3.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 958131 | AF2-107 C | 80/20 | 2.04 MW | 2.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 235034 | 01SHY_Z2-039 | 80/20 | 0.01 MW | 0.01 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 235035 | 01NHY_Z2-039 | 80/20 | 0.02 MW | 0.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 237092 | AD1-085_C | 80/20 | 0.15 MW | 0.15 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 940451 | AE2-029 C | 80/20 | 3.03 MW | 3.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 943571 | AF1-028 O1 | 80/20 | 16.32 MW | 16.32 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 933501 | AC2-165 C | 80/20 | 3.12 MW | 3.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 944071 | AF1-075 C O1 | 80/20 | 4.39 MW | 4.39 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 961061 | AF2-397 C | 80/20 | 11.82 MW | 11.82 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 313738 | 3CUSHAW | 80/20 | 0.09 MW | 0.09 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 314677 | 6BUCKING | 80/20 | 0.21 MW | 0.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 314859 | 4WSTVACO | 80/20 | 4.02 MW | 4.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 926001 | AC1-076 C | Adder | -2.89 MW | -2.45 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966671 | AG1-537 C | 80/20 | 4.18 MW | 4.18 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315186 | 1LOWMORA | 80/20 | 0.41 MW | 0.41 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315188 | 1LOWMORC | 80/20 | 0.41 MW | 0.41 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315191 | 1BEARGRDN G1 | 80/20 | 3.85 MW | 3.85 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315192 | 1BEARGRDN G2 | 80/20 | 3.85 MW | 3.85 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315193 | 1BEARGRDN S1 | 80/20 | 4.97 MW | 4.97 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315201 | 1BATH 1A | 80/20 | 6.84 MW | 6.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315202 | 1BATH 2B | 80/20 | 6.84 MW | 6.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315203 | 1BATH 3C | 80/20 | 6.84 MW | 6.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315204 | 1BATH 4D | 80/20 | 6.84 MW | 6.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315205 | 1BATH 5E | 80/20 | 6.85 MW | 6.85 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315206 | 1BATH 6F | 80/20 | 6.86 MW | 6.86 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315216 | 1CUNINGA | 80/20 | 2.89 MW | 2.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315217 | 1CUNINGB | 80/20 | 2.89 MW | 2.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315218 | 1CUNINGC | 80/20 | 2.89 MW | 2.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315219 | 1CUNINGD | 80/20 | 6.46 MW | 6.46 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 315616 | AA1-038 C | 80/20 | 0.96 MW | 0.96 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 932854 | AC2-112 C | 80/20 | 13.48 MW | 13.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 938625 | AE1-084 C | 80/20 | 6.51 MW | 6.51 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 941381 | AE2-134 | Adder | -1.99 MW | -1.69 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 963461 | AG1-195 | 80/20 | 14.13 MW | 14.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965531 | AG1-421 C | 80/20 | 12.9 MW | 12.9 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 965541 | AG1-422 | 80/20 | 5.38 MW | 5.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | 966851 | AG1-556 C | 80/20 | 9.46 MW | 9.46 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 0.47 MW | 0.47 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.72 MW | 0.72 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 15.48 MW | 15.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 23.83 MW | 23.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 16.39 MW | 16.39 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 0.7 MW | 0.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.21 MW | 3.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.06 MW | 0.06 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.17 MW | 1.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.84 MW | 2.84 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.64 MW | 0.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 2.66 MW | 2.66 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.55 MW | 0.55 MW |
| Details for 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961791 | AG1-021 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961801 | AG1-022 C | 80/20 | 1.26 MW | 1.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961891 | AG1-030 C | 80/20 | 5.49 MW | 5.49 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962491 | AG1-098 C O1 | 80/20 | 3.25 MW | 3.25 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962741 | AG1-123 C O1 | 80/20 | 2.24 MW | 2.24 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962751 | AG1-124 C O1 | 80/20 | 3.29 MW | 3.29 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963021 | AG1-151 O1 | 80/20 | 9.03 MW | 9.03 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963171 | AG1-166 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963181 | AG1-167 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963191 | AG1-168 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963201 | AG1-169 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963211 | AG1-170 C | 80/20 | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963321 | AG1-181 C O1 | 80/20 | 5.27 MW | 5.27 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963361 | AG1-185 O1 | 80/20 | 2.55 MW | 2.55 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963471 | AG1-196 O1 | 80/20 | 17.34 MW | 17.34 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964111 | AG1-272 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964121 | AG1-273 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964131 | AG1-274 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964231 | AG1-284 C O1 | 80/20 | 5.62 MW | 5.62 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964831 | AG1-346 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965191 | AG1-384 C | 80/20 | 0.83 MW | 0.83 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965581 | AG1-426 | 80/20 | 1.92 MW | 1.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965641 | AG1-432 C O1 | 80/20 | 9.5 MW | 9.5 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965831 | AG1-451 | 80/20 | 1.58 MW | 1.58 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966251 | AG1-494 C | 80/20 | 1.21 MW | 1.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314429 | 3JTRSVLE | 80/20 | 0.18 MW | 0.18 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934625 | AD1-088 C | 80/20 | 3.65 MW | 3.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 936265 | AD2-033 C | 80/20 | 4.02 MW | 4.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942461 | AE2-259 C O1 | 80/20 | 4.75 MW | 4.75 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958801 | AF2-171 C | 80/20 | 5.81 MW | 5.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 959311 | AF2-222 C | 80/20 | 5.55 MW | 5.55 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 960111 | AF2-302 C | 80/20 | 1.26 MW | 1.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 242889 | 05REUSENS | 80/20 | 0.04 MW | 0.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 925611 | AC1-036 C | 80/20 | 0.08 MW | 0.08 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938371 | AE1-056 C | 80/20 | 2.67 MW | 2.67 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938821 | AE1-108 C O1 | 80/20 | 10.13 MW | 10.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941011 | AE2-092 C | 80/20 | 11.2 MW | 11.2 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941791 | AE2-182 C | 80/20 | 0.59 MW | 0.59 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946291 | AF1-293 C O1 | 80/20 | 14.58 MW | 14.58 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946301 | AF1-294 C | 80/20 | 1.59 MW | 1.59 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946591 | AF1-323 C | 80/20 | 3.48 MW | 3.48 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958131 | AF2-107 C | 80/20 | 2.33 MW | 2.33 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958211 | AF2-115 C | 80/20 | 0.97 MW | 0.97 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 235034 | 01SHY_Z2-039 | 80/20 | 0.01 MW | 0.01 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 235035 | 01NHY_Z2-039 | 80/20 | 0.02 MW | 0.02 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 237092 | AD1-085_C | 80/20 | 0.16 MW | 0.16 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940451 | AE2-029 C | 80/20 | 3.28 MW | 3.28 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943571 | AF1-028 O1 | 80/20 | 18.07 MW | 18.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 933501 | AC2-165 C | 80/20 | 4.35 MW | 4.35 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944071 | AF1-075 C O1 | 80/20 | 4.92 MW | 4.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961061 | AF2-397 C | 80/20 | 12.98 MW | 12.98 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 313738 | 3CUSHAW | 80/20 | 0.1 MW | 0.1 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314333 | 6POWHATN | 80/20 | 0.15 MW | 0.15 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314677 | 6BUCKING | 80/20 | 0.26 MW | 0.26 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314859 | 4WSTVACO | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 926001 | AC1-076 C | Adder | -2.55 MW | -2.17 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958501 | AF2-144 C | 80/20 | 0.65 MW | 0.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966671 | AG1-537 C | 80/20 | 4.45 MW | 4.45 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315186 | 1LOWMORA | 80/20 | 0.44 MW | 0.44 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315188 | 1LOWMORC | 80/20 | 0.44 MW | 0.44 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315191 | 1BEARGRDN G1 | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315192 | 1BEARGRDN G2 | 80/20 | 4.38 MW | 4.38 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315193 | 1BEARGRDN S1 | 80/20 | 5.67 MW | 5.67 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315201 | 1BATH 1A | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315202 | 1BATH 2B | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315203 | 1BATH 3C | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315204 | 1BATH 4D | 80/20 | 7.89 MW | 7.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315205 | 1BATH 5E | 80/20 | 7.9 MW | 7.9 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315206 | 1BATH 6F | 80/20 | 7.92 MW | 7.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315216 | 1CUNINGA | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315217 | 1CUNINGB | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315218 | 1CUNINGC | 80/20 | 1.89 MW | 1.89 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315219 | 1CUNINGD | 80/20 | 4.22 MW | 4.22 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315616 | AA1-038 C | 80/20 | 1.04 MW | 1.04 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 932854 | AC2-112 C | 80/20 | 14.33 MW | 14.33 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938561 | AE1-075 C | 80/20 | 0.13 MW | 0.13 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938625 | AE1-084 C | 80/20 | 6.92 MW | 6.92 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941381 | AE2-134 | Adder | -1.76 MW | -1.49 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963461 | AG1-195 | 80/20 | 16.21 MW | 16.21 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965531 | AG1-421 C | 80/20 | 13.88 MW | 13.88 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965541 | AG1-422 | 80/20 | 5.78 MW | 5.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966851 | AG1-556 C | 80/20 | 10.31 MW | 10.31 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 1.09 MW | 1.09 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 0.81 MW | 0.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 26.07 MW | 26.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 21.87 MW | 21.87 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 17.65 MW | 17.65 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 1.64 MW | 1.64 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 3.7 MW | 3.7 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.14 MW | 0.14 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 1.12 MW | 1.12 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 2.81 MW | 2.81 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 0.78 MW | 0.78 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.19 MW | 0.19 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 3.07 MW | 3.07 MW |
| 6CHARLVL-6PROFFIT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 0.52 MW | 0.52 MW |
| Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940491 | AE2-034 C | Adder | 8.75 MW | 7.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 957531 | AF2-047 C | Adder | 20.78 MW | 17.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938771 | AE1-103 C | Adder | 3.6 MW | 3.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314184 | 3SHACKLE | 80/20 | 0.86 MW | 0.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314229 | 6MT RD221 | 80/20 | 0.2 MW | 0.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314236 | 6NRTHEST | 80/20 | 0.29 MW | 0.29 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314241 | 6OLDCHRC | 80/20 | 1.43 MW | 1.43 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314243 | 3PROV 92 | 80/20 | 0.73 MW | 0.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314309 | 6IRON208 | 80/20 | 0.68 MW | 0.68 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314375 | 6CORRCTN | 80/20 | 0.62 MW | 0.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 314421 | 6WINCHST | 80/20 | 0.2 MW | 0.2 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315060 | 1CHESTF5 | 80/20 | 94.99 MW | 94.99 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315061 | 1CHESTG7 | 80/20 | 6.04 MW | 6.04 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315062 | 1CHESTS7 | 80/20 | 2.77 MW | 2.77 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315063 | 1CHESTG8 | 80/20 | 5.94 MW | 5.94 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315064 | 1CHESTS8 | 80/20 | 3.06 MW | 3.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315065 | 1CHESTF6 | Adder | 143.03 MW | 121.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315067 | 1DARBY 1 | 80/20 | 4.09 MW | 4.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315068 | 1DARBY 2 | 80/20 | 4.09 MW | 4.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315069 | 1DARBY 3 | 80/20 | 4.11 MW | 4.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315070 | 1DARBY 4 | 80/20 | 4.11 MW | 4.11 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315076 | 1HOPPOLC | 80/20 | 2.32 MW | 2.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315077 | 1HOPHCF1 | 80/20 | 3.62 MW | 3.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315078 | 1HOPHCF2 | 80/20 | 3.62 MW | 3.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315079 | 1HOPHCF3 | 80/20 | 3.62 MW | 3.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315080 | 1HOPHCF4 | 80/20 | 5.5 MW | 5.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315083 | 1SPRUNCA | Adder | 13.99 MW | 11.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315084 | 1SPRUNCB | Adder | 13.99 MW | 11.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315092 | 1YORKTN3 | 80/20 | 34.36 MW | 34.36 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 925863 | AC1-065 C | 80/20 | 8.81 MW | 8.81 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 926754 | AC1-161 C | Adder | 39.55 MW | 33.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 926784 | AC1-164 C | 80/20 | 64.04 MW | 64.04 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 927044 | AC1-191 C | 80/20 | 14.9 MW | 14.9 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934014 | AD1-025 C | Adder | 23.47 MW | 19.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934061 | AD1-033 C | Adder | 9.62 MW | 8.17 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934141 | AD1-041 C | Adder | 7.52 MW | 6.39 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934391 | AD1-063 C | 80/20 | 0.4 MW | 0.4 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 934575 | AD1-082 C | Adder | 10.02 MW | 8.51 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 935164 | AD1-151 C | Adder | 22.58 MW | 19.19 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 936151 | AD2-021 | 80/20 | 0.06 MW | 0.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 936661 | AD2-085 C | Adder | 4.4 MW | 3.74 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 936761 | AD2-097 C | Adder | 2.65 MW | 2.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 937221 | AD2-160 C O1 | Adder | 7.46 MW | 6.34 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942151 | AE2-227 C | 80/20 | 3.22 MW | 3.22 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942161 | AE2-228 C | Adder | 2.98 MW | 2.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942341 | AE2-247 C | Adder | 1.91 MW | 1.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942371 | AE2-250 C O1 | Adder | 13.01 MW | 11.06 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942401 | AE2-253 C | Adder | 7.85 MW | 6.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942551 | AE2-270 | Adder | 37.47 MW | 31.85 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943431 | AF1-014 C | 80/20 | 1.83 MW | 1.83 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943461 | AF1-017 C | Adder | 1.73 MW | 1.47 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943471 | AF1-018 | 80/20 | 10.3 MW | 10.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943611 | AF1-032 C | Adder | 2.22 MW | 1.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 943621 | AF1-033 C | Adder | 3.24 MW | 2.75 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944631 | AF1-128 O1 | 80/20 | 59.44 MW | 59.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944871 | AF1-152 C | Adder | 6.64 MW | 5.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 945361 | AF1-201 C O1 | 80/20 | 22.76 MW | 22.76 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961711 | AG1-011 | Adder | 39.87 MW | 33.89 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966871 | AG1-558 C | 80/20 | 3.71 MW | 3.71 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315216 | 1CUNINGA | 80/20 | 10.12 MW | 10.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315217 | 1CUNINGB | 80/20 | 10.12 MW | 10.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315218 | 1CUNINGC | 80/20 | 10.12 MW | 10.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315219 | 1CUNINGD | 80/20 | 22.64 MW | 22.64 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 315233 | 1SURRY 2 | 80/20 | 36.8 MW | 36.8 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 316075 | AC2-137 C | 80/20 | 0.56 MW | 0.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 316108 | AB2-160 C | Adder | 7.32 MW | 6.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 316132 | AB2-190 C | Adder | 26.31 MW | 22.37 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 932044 | AC2-012 C | Adder | 10.34 MW | 8.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 932591 | AC2-079 C O1 | Adder | 7.38 MW | 6.27 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 938535 | AE1-072 C | Adder | 22.32 MW | 18.97 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 939195 | AE1-149 C | Adder | 13.95 MW | 11.86 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 939431 | AE1-175 C | 80/20 | 3.58 MW | 3.58 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 939611 | AE1-191 C | Adder | 15.03 MW | 12.78 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940231 | AE2-005 C | 80/20 | 1.93 MW | 1.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940431 | AE2-027 C O1 | Adder | 18.0 MW | 15.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940551 | AE2-041 | 80/20 | 10.3 MW | 10.3 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 940651 | AE2-052 | Adder | 4.65 MW | 3.95 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941101 | AE2-104 C O1 | Adder | 4.26 MW | 3.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941281 | AE2-122 C O1 | Adder | 36.48 MW | 31.01 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941291 | AE2-123 C O1 | Adder | 37.49 MW | 31.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941301 | AE2-124 C O1 | Adder | 34.08 MW | 28.96 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 946261 | AF1-291 C | Adder | 2.98 MW | 2.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 957491 | AF2-043 C | Adder | 2.72 MW | 2.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 957601 | AF2-054 C | Adder | 2.94 MW | 2.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 957631 | AF2-057 | Adder | 4.61 MW | 3.92 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 957711 | AF2-065 C | Adder | 19.11 MW | 16.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962531 | AG1-102 C | Adder | 1.55 MW | 1.32 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962961 | AG1-145 C | 80/20 | 3.23 MW | 3.23 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962971 | AG1-146 C | Adder | 3.9 MW | 3.31 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962981 | AG1-147 C | Adder | 9.09 MW | 7.73 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963221 | AG1-171 C | Adder | 2.99 MW | 2.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963231 | AG1-172 C | Adder | 2.99 MW | 2.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963241 | AG1-173 C | Adder | 2.99 MW | 2.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963251 | AG1-174 C | Adder | 2.99 MW | 2.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 963461 | AG1-195 | Adder | 31.18 MW | 26.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 964951 | AG1-359 O1 | Adder | 29.18 MW | 24.8 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 965001 | AG1-364 C O1 | Adder | 9.23 MW | 7.84 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 933294 | AC2-141 C | Adder | 39.55 MW | 33.62 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941501 | AE2-147 C | Adder | 19.92 MW | 16.93 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941581 | AE2-155 C | 80/20 | 0.18 MW | 0.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 941591 | AE2-156 O1 | Adder | 23.07 MW | 19.61 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 942001 | AE2-212 C | Adder | 2.88 MW | 2.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 957831 | AF2-077 C | Adder | 3.02 MW | 2.56 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 957871 | AF2-081 C | Adder | 12.71 MW | 10.8 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 958161 | AF2-110 C | Adder | 1.76 MW | 1.49 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 966611 | AG1-531 C | Adder | 8.08 MW | 6.87 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944581 | AF1-123 C O1 | Adder | 61.34 MW | 52.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944591 | AF1-124 C O1 | Adder | 61.34 MW | 52.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 944601 | AF1-125 C O1 | Adder | 61.34 MW | 52.14 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 962271 | AG1-075 C O1 | Adder | 22.46 MW | 19.09 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 316083 | AB2-161 C | Adder | 4.4 MW | 3.74 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | 961611 | AG1-000B C | Adder | 21.79 MW | 18.52 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_AA2-074 | LTFEXP_AA2-074->LTFIMP_AA2-074 | CLTF | 6.07 MW | 6.07 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S1 | LTFEXP_CBM-S1->LTFIMP_CBM-S1 | CBM | 2.66 MW | 2.66 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-S2 | LTFEXP_CBM-S2->LTFIMP_CBM-S2 | CBM | 121.72 MW | 121.72 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W1 | LTFEXP_CBM-W1->LTFIMP_CBM-W1 | CBM | 59.44 MW | 59.44 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CBM-W2 | LTFEXP_CBM-W2->LTFIMP_CBM-W2 | CBM | 56.79 MW | 56.79 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_CPLE | LTFEXP_CPLE->LTFIMP_CPLE | CLTF | 9.18 MW | 9.18 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LAGN | LTFEXP_LAGN->LTFIMP_LAGN | CLTF | 12.7 MW | 12.7 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGE-0012019 | LTFEXP_LGE-0012019->LTFIMP_LGE-0012019 | CLTF | 0.67 MW | 0.67 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_LGEE | LTFEXP_LGEE->LTFIMP_LGEE | CLTF | 3.12 MW | 3.12 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_MEC | LTFEXP_MEC->LTFIMP_MEC | CLTF | 8.25 MW | 8.25 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_NY | LTFEXP_NY->LTFIMP_NY | CLTF | 3.5 MW | 3.5 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_SIGE | LTFEXP_SIGE->LTFIMP_SIGE | CLTF | 0.54 MW | 0.54 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_TVA | LTFEXP_TVA->LTFIMP_TVA | CLTF | 10.45 MW | 10.45 MW |
| 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 550 | LTFEXP_WEC | LTFEXP_WEC->LTFIMP_WEC | CLTF | 1.44 MW | 1.44 MW |
Light Load Analysis
The Queue Project was evaluated as a 150.0 MW (Capacity 150.0 MW) injection in the Dominion area. Project was evaluated for compliance with applicable reliability planning criteria (PJM, NERC, NERC Regional Reliability Councils, and Transmission Owners). Potential light load period network impacts are listed below:
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
| Light Load Analysis | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Area | Facility Description | Contingency Name | Contingency Type | DC|AC | Initial Loading | Final Loading | Rating (MVA) | Rating Type | MVA to Mitigate | MW Contribution | |
| DVP |
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
314747 to 313867 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | DC | 121.08 % | 122.33 % | 678.68 | B | 830.23 | 12.06 | |
| DVP |
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
313867 to 313707 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | DC | 120.05 % | 121.3 % | 678.68 | B | 823.24 | 12.06 | |
| DVP |
6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line
313707 to 961060 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 106.53 % | 107.85 % | 661.76 | B | 713.71 | 11.41 | |
| DVP |
AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line
961060 to 314765 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 106.53 % | 107.85 % | 661.76 | B | 713.71 | 11.41 | |
| DVP |
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
314765 to 314749 ckt 1 |
DVP_P1-2: LN 534
CONTINGENCY 'DVP_P1-2: LN 534' OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1 /*8DOOMS 500.0 - 8CUNINGHAM 500.0 SET POSTCONTRATING 2858 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 SET PRECONTRATING 2650 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS 500.0 - 8VALLEY 500.0 END |
Single | AC | 104.46 % | 105.78 % | 661.76 | B | 700.01 | 11.41 | |
| Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | 80/20 | 9.44 MW | 9.44 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 25.3 MW | 25.3 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315131 | 1EDGECMA | Adder | 1.33 MW | 1.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315132 | 1EDGECMB | Adder | 1.33 MW | 1.13 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 7.52 MW | 6.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.98 MW | 0.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940551 | AE2-041 | Adder | 2.15 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.94 MW | 1.94 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 12.9 MW | 12.9 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 7.36 MW | 6.25 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 29.7 MW | 25.24 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 7.56 MW | 6.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 29.49 MW | 25.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.88 MW | 5.84 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 30.17 MW | 25.65 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.79 MW | 4.92 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | 80/20 | 8.93 MW | 8.93 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943471 | AF1-018 | Adder | 2.15 MW | 1.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 4.21 MW | 4.21 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944141 | AF1-082 | Adder | 0.92 MW | 0.79 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945362 | AF1-201 E O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.67 MW | 4.67 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.16 MW | 0.98 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 2.07 MW | 2.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | 80/20 | 9.5 MW | 9.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962531 | AG1-102 C | Adder | 0.34 MW | 0.29 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962532 | AG1-102 E | Adder | 0.7 MW | 0.6 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.83 MW | 2.83 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | Adder | 1.17 MW | 0.99 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.82 MW | 2.82 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 7.38 MW | 6.27 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.32 MW | 1.97 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.48 MW | 2.95 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965761 | AG1-444 O1 | Adder | 4.11 MW | 3.5 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.92 MW | 7.92 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 5.07 MW | 5.07 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966872 | AG1-558 E | Adder | 0.72 MW | 0.61 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315292 | 1DOMTR78 | Adder | 2.77 MW | 2.35 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.48 MW | 1.48 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 10.68 MW | 10.68 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 7.62 MW | 7.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.75 MW | 7.75 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 4.4 MW | 3.74 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 14.63 MW | 14.63 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946293 | AF1-293 BAT | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 23.62 MW | 23.62 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 7.32 MW | 7.32 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 12.06 MW | 12.06 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.73 MW | 13.73 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.43 MW | 4.43 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 8.12 MW | 8.12 MW |
| 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.74 MW | 7.74 MW |
| Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | 80/20 | 9.44 MW | 9.44 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 25.3 MW | 25.3 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.93 MW | 1.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315131 | 1EDGECMA | Adder | 1.33 MW | 1.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315132 | 1EDGECMB | Adder | 1.33 MW | 1.13 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 7.52 MW | 6.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.98 MW | 0.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940551 | AE2-041 | Adder | 2.15 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.94 MW | 1.94 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 12.9 MW | 12.9 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 7.36 MW | 6.25 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 29.7 MW | 25.24 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 7.56 MW | 6.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 29.49 MW | 25.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.88 MW | 5.84 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 30.17 MW | 25.65 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.79 MW | 4.92 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | 80/20 | 8.93 MW | 8.93 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943471 | AF1-018 | Adder | 2.15 MW | 1.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 4.21 MW | 4.21 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.64 MW | 1.64 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944141 | AF1-082 | Adder | 0.92 MW | 0.79 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945361 | AF1-201 C O1 | Adder | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 945362 | AF1-201 E O1 | Adder | 1.1 MW | 0.94 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.67 MW | 4.67 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.16 MW | 0.98 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 2.07 MW | 2.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.37 MW | 2.37 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | 80/20 | 9.5 MW | 9.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.1 MW | 0.1 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.4 MW | 0.4 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962531 | AG1-102 C | Adder | 0.34 MW | 0.29 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962532 | AG1-102 E | Adder | 0.7 MW | 0.6 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.89 MW | 1.89 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.83 MW | 2.83 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | Adder | 1.17 MW | 0.99 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.88 MW | 1.88 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.82 MW | 2.82 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.34 MW | 0.34 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.52 MW | 0.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.31 MW | 0.31 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.46 MW | 0.46 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 7.38 MW | 6.27 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.32 MW | 1.97 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.48 MW | 2.95 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.56 MW | 0.56 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.85 MW | 0.85 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.98 MW | 1.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965761 | AG1-444 O1 | Adder | 4.11 MW | 3.5 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.26 MW | 2.26 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.92 MW | 7.92 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 5.07 MW | 5.07 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966872 | AG1-558 E | Adder | 0.72 MW | 0.61 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315292 | 1DOMTR78 | Adder | 2.77 MW | 2.35 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 12.38 MW | 10.52 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 28.35 MW | 24.09 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.48 MW | 1.48 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.22 MW | 1.22 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 10.68 MW | 10.68 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 7.62 MW | 7.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.75 MW | 7.75 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 6.51 MW | 6.51 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 4.4 MW | 3.74 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 14.63 MW | 14.63 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946293 | AF1-293 BAT | 80/20 | 6.8 MW | 6.8 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 23.62 MW | 23.62 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 7.32 MW | 7.32 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 12.06 MW | 12.06 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.73 MW | 13.73 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.43 MW | 4.43 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 8.12 MW | 8.12 MW |
| 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.74 MW | 7.74 MW |
| Details for 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961063 | AF2-397 BAT | 80/20 | 26.41 MW | 26.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| 6FORK UNION-AF2-397 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| AF2-397 TAP-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
| Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | |||||
|---|---|---|---|---|---|
| Monitored Fac/Ctg | Bus # | Bus Name | Type | Full MW Contribution | GenDeliv MW Contribution |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315060 | 1CHESTF5 | Adder | 8.26 MW | 7.02 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315065 | 1CHESTF6 | 80/20 | 22.23 MW | 22.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315083 | 1SPRUNCA | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 315084 | 1SPRUNCB | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 916042 | Z1-036 E | Adder | 6.71 MW | 5.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940541 | AE2-040 | 80/20 | 0.88 MW | 0.88 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940651 | AE2-052 | 80/20 | 1.08 MW | 1.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 940661 | AE2-053 O1 | 80/20 | 1.78 MW | 1.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941031 | AE2-094 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941032 | AE2-094 E | 80/20 | 11.51 MW | 11.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941281 | AE2-122 C O1 | Adder | 6.5 MW | 5.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941282 | AE2-122 E O1 | Adder | 26.24 MW | 22.31 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941291 | AE2-123 C O1 | Adder | 6.68 MW | 5.68 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941292 | AE2-123 E O1 | Adder | 26.06 MW | 22.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941301 | AE2-124 C O1 | Adder | 6.08 MW | 5.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941302 | AE2-124 E O1 | Adder | 26.67 MW | 22.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 941591 | AE2-156 O1 | Adder | 5.12 MW | 4.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 942551 | AE2-270 | Adder | 7.85 MW | 6.67 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944011 | AF1-069 C | 80/20 | 3.76 MW | 3.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944012 | AF1-069 E | 80/20 | 1.46 MW | 1.46 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946011 | AF1-266 | 80/20 | 4.17 MW | 4.17 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946291 | AF1-293 C O1 | 80/20 | 9.59 MW | 9.59 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 946292 | AF1-293 E O1 | 80/20 | 14.39 MW | 14.39 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957631 | AF2-057 | Adder | 1.02 MW | 0.87 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 957911 | AF2-085 | 80/20 | 1.84 MW | 1.84 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958501 | AF2-144 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 958502 | AF2-144 E | 80/20 | 2.14 MW | 2.14 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961061 | AF2-397 C | 80/20 | 0.0 MW | 0.0 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961062 | AF2-397 E | 80/20 | 26.23 MW | 26.23 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961711 | AG1-011 | Adder | 8.36 MW | 7.11 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961942 | AG1-037 E | 80/20 | 0.09 MW | 0.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962332 | AG1-082 E | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 962342 | AG1-083 E | 80/20 | 0.36 MW | 0.36 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963041 | AG1-153 C | 80/20 | 1.7 MW | 1.7 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963042 | AG1-153 E | 80/20 | 2.54 MW | 2.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963102 | AG1-159 E | 80/20 | 1.07 MW | 1.07 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963111 | AG1-160 C | 80/20 | 1.69 MW | 1.69 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963112 | AG1-160 E | 80/20 | 2.53 MW | 2.53 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964111 | AG1-272 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964112 | AG1-272 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964121 | AG1-273 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964122 | AG1-273 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964131 | AG1-274 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964132 | AG1-274 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964791 | AG1-342 C | 80/20 | 0.32 MW | 0.32 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964792 | AG1-342 E | 80/20 | 0.48 MW | 0.48 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964801 | AG1-343 C | 80/20 | 0.28 MW | 0.28 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964802 | AG1-343 E | 80/20 | 0.42 MW | 0.42 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 964951 | AG1-359 | Adder | 6.52 MW | 5.54 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965001 | AG1-364 C O1 | Adder | 2.05 MW | 1.74 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965002 | AG1-364 E O1 | Adder | 3.07 MW | 2.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965191 | AG1-384 C | 80/20 | 0.52 MW | 0.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965192 | AG1-384 E | 80/20 | 0.78 MW | 0.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965741 | AG1-442 O1 | Adder | 1.78 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965751 | AG1-443 O1 | Adder | 1.78 MW | 1.51 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965771 | AG1-445 | 80/20 | 2.08 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965781 | AG1-446 | 80/20 | 2.08 MW | 2.08 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965811 | AG1-449 | 80/20 | 7.09 MW | 7.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965831 | AG1-451 | 80/20 | 4.61 MW | 4.61 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966251 | AG1-494 C | Adder | 1.05 MW | 0.89 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966252 | AG1-494 E | Adder | 1.57 MW | 1.34 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944581 | AF1-123 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944582 | AF1-123 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944591 | AF1-124 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944592 | AF1-124 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944601 | AF1-125 C O1 | Adder | 10.94 MW | 9.3 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 944602 | AF1-125 E O1 | Adder | 25.04 MW | 21.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963311 | AG1-180 C | 80/20 | 1.35 MW | 1.35 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963312 | AG1-180 E | 80/20 | 1.12 MW | 1.12 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963351 | AG1-184 C | 80/20 | 9.47 MW | 9.47 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963352 | AG1-184 E | 80/20 | 6.76 MW | 6.76 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963361 | AG1-185 C | 80/20 | 7.09 MW | 7.09 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963362 | AG1-185 E | 80/20 | 5.96 MW | 5.96 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965581 | AG1-426 C | 80/20 | 4.52 MW | 4.52 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965582 | AG1-426 E | 80/20 | 6.78 MW | 6.78 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 961611 | AG1-000B C | Adder | 3.87 MW | 3.29 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 943572 | AF1-028 BAT | 80/20 | 13.95 MW | 13.95 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963022 | AG1-151 BAT | 80/20 | 6.98 MW | 6.98 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963463 | AG1-195 BAT | 80/20 | 11.41 MW | 11.41 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 963473 | AG1-196 BAT | 80/20 | 13.15 MW | 13.15 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 965542 | AG1-422 BAT | 80/20 | 4.2 MW | 4.2 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966673 | AG1-537 BAT | 80/20 | 6.26 MW | 6.26 MW |
| 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534 | 966852 | AG1-556 BAT | 80/20 | 7.25 MW | 7.25 MW |
System Reinforcements
The table below lists all network upgrades which resolve the identified overloaded facilities in this report.
Important to Note:
Note for Uprate Projects: Per Tariff Part VII, Subpart B, section 304 (B), if a project is an uprate (project relies on the Interconnection Facilities of a prior project) whose base project does not qualify for the expedited process, the uprate also will not qualify for the expedited process, regardless of analysis results.
Notes regarding Results displayed:
- Some flowgate overloads that a New Service Request contributes to, but does not contribute enough to meet cost allocation eligibility (per Manual 14A, Attachment B.3), may be reported in this Transition Sort report. These types of flowgates do not affect the classification of the New Service Request as either Expedited Process or Transition Cycle #1 because cost allocation eligibility has not been met.
- For projects that were determined to not meet Expedited Process eligibility and are being reprioritized to Transition Cycle #1, not all reinforcements in excess of $5,000,000 may be shown in this report. This report may only display a subset of those reinforcements determined to be in excess of $5,000,000 which would classify the project as not meeting Expedited Process Eligibility. This is not a formal System Impact Study.
- Reinforcements previously identified by Transmission Owners for violations on lower voltage facilities are included in this report. Transmission Owner analysis will be updated as part of the Expedited Process and Transition Cycle 1 retools.
| System Reinforcements | |||
|---|---|---|---|
| RTEP ID | Title | Total Cost | |
| n5873 | Rebuild 0.16 miles of Line 2028 from Bremo to Bremo Dist with 2-636 ACSR. | $500,000 | |
| n6379 | Rebuild 6.47 miles of 230 kV Line 2028 from Mt Eagle to Charlottesville with 2-636 ACSR. | $16,175,000 | |
| n7580 | Rebuild 8.72 miles of 230 kV Line 2054 from Charlottesville to Profit D.P. with 2-636 ACSR 150 C | $21,800,000 | |
| n7567 | Rebuild 1.63 miles of 230 kV Line 2028 from Fork Union to Bremo Dist with 2-795 ACSR (26/7) 150 C | $2,445,000 | |
| n6185.2 | Rebuild 17.42 miles of 230 kV Line 2028 from Fork Union to Mount Eagle with 2-636 ACSR. | $26,130,000 | |
| b3020 | PJM baseline upgrade b3020: Rebuild 500kV Line #574 Ladysmith to Elmont . | $0 | |
Attachments
Conclusion
The Transition Sort load flow retool results indicate that AG1-195 is not eligible for the Expedited Process per PJM Tariff Part VII, Subpart B, section 304 (A) will be reprioritized to Transition Cycle #1. See next steps for your project in the "Introduction" section above.